FIREPROOF_D-1-3_Reliability and Effectiveness of Fire Safety

advertisement
1
Probabilistic Framework for
Onboard Fire Safety
Reliability and Effectiveness Models of Passive and Active
Fire Safety Systems (D1.3)
Philipp Lohrmann (BMT), Apurba Kar
(IRS), Antoine Breuillard (BV)
BMT
- document author -
- organisation name -
Kostas Spyrou
4.0
- document approved by -
- revision number -
13 January 2011
PU
- submission date -
- distribution level -
1
2
Document history
Revision number
1.0
Date
24/07/2009
2.0
13/10/2010
3.0
4.0
26/10/2010
13/01/2011
Remarks
Skeleton document
Final draft for revision by
partners
Final version
Revised version
2
3
Contents
1
Introduction ............................................................................................................................ 6
1.1 Overview............................................................................................................................ 6
1.2 Current SOLAS regulations for passenger ships ......................................................... 7
1.2.1
Essential systems in SOLAS Chap II-2 Part C ..................................................... 8
1.2.2
Emergency procedures .......................................................................................10
1.3 Objectives ........................................................................................................................14
2
Analysis of Fire Safety Systems..........................................................................................15
2.1 Automatic Fire Detection Systems ..............................................................................15
2.1.1
System set-up .........................................................................................................15
2.1.2
Smoke Detector .....................................................................................................19
2.1.3
Heat detector..........................................................................................................20
2.1.4
Fault tree analysis of a Detector System ............................................................22
2.2 Sprinkler Systems............................................................................................................27
2.2.1
System set-up .........................................................................................................28
2.2.2
Sprinkler Types and their working principles....................................................30
2.2.3
Regulatory requirements (Reference FSS code) ................................................34
2.2.4
Fault tree analysis of a Sprinkler System ............................................................36
2.3 Water Mist Systems ........................................................................................................36
2.3.1
System set-up .........................................................................................................36
2.3.2
Fault tree analysis of a Water Mist System/Hi-Fog System ............................40
2.4 CO2 Systems ....................................................................................................................40
2.4.1
System set-up .........................................................................................................40
2.4.2
Fault tree analysis of a CO2 system ....................................................................43
3
4
2.5 Foam Systems .................................................................................................................43
3
2.5.1
System set-up .........................................................................................................43
2.5.2
Fault tree analysis of a Foam System ..................................................................48
Reliability model of detection and suppression systems ................................................49
3.1 The generic model ..........................................................................................................49
3.2 Propagation of error.......................................................................................................50
3.3 Maintenance intervals ....................................................................................................50
3.4 Application to concrete systems ...................................................................................51
3.4.1
Heat detector..........................................................................................................51
3.4.2
Photoelectric Smoke Detector ............................................................................52
3.4.3
Ionisation Smoke Detector ..................................................................................54
3.4.4
Detector panel........................................................................................................55
3.4.5
Sprinkler system .....................................................................................................57
3.4.6
Foam System ..........................................................................................................58
3.4.7
Water Mist System.................................................................................................60
3.4.8
Hi-Fog System .......................................................................................................61
3.4.9
CO2 System............................................................................................................63
4
Conclusions ..........................................................................................................................65
5
References .............................................................................................................................66
Appendix - Fault trees and diagrams used in the failure rate analysis ..................................68
4
5
Executive summary
A ship fire is a complex scenario that depends on a large range of parameters. While the
location and cause of the fire are crucial, the sequence of events immediately after the
ignition is of equal importance. In particular, the reaction of the crew and the influence
of the fire suppression systems decide whether or not the fire escalates to dangerous
proportions. To realistically model a ship fire, it is important to have a quantitative
measure for the influence of these factors.
We present a methodology to analyse the reliability of fire suppression systems. For a
given (constant) failure rate, we use an exponential curve to describe the reliability as a
function of time. The domain of this curve is given by the maintenance interval of the
system.
To determine the failure rate of each system, we refer to historical data if possible. In
case such data is not available, we perform a detailed fault tree analysis of the system,
taking into account redundancies and manual actions. The failure rate derived in this way
is then used as input for the exponential model.
For each system, we compute the average and standard deviation of the reliability over
the maintenance interval. These figures might be referred to in subsequent scenario
analyses carried out later in the project.
5
6
1 Introduction
1.1 Overview
Although the days of wooden ships are long gone, fire remains one of the most
dangerous threats to seafaring vessels. In fact, accident statistics (Figure 1) show that fire
is the most frequent incident on cruise ships, outstripping collisions and grounding.
Figure 1- Most frequent hazards on passenger ships (1)
Since 1970, the size of cruise ships has roughly doubled every decade, with the latest
generation – the Oasis or Genesis class (2) – carrying over 5,000 passengers. This dramatic
increase in size poses new challenges for the avoidance and mitigation of fire risk.
To the present day, fire safety regulations, including SOLAS (3), have been based on
prescribed designs and performance based approaches. The weakness of this methodology is
twofold: (i) it does not provide a systematic framework for testing fire scenarios and (ii) it
might be too rigid to accommodate novel designs.
The aim of FIREPROOF is to provide a probabilistic framework that allows a risk-based
approach to fire safety. The aim of work package 1 (WP1) is to systematically generate fire
scenarios based on the set up of the vessel, including space type and fire safety systems. Each
of these scenarios comes with a probability that determines its weight in the risk analysis. The
total fire risk of the ship is then given by
𝑅=
𝑝𝑖 × πΆπ‘–
π‘–βˆˆπœŽ
6
7
where 𝜎 denotes the set of all scenarios, 𝑝𝑖 is the probability for scenario 𝑖, and 𝐢𝑖 is a
measure of the consequences (or cost) of this scenario (e.g. loss of life). In theory, this sum
runs over all possible scenarios. In practice, however, it is impossible to consider all scenarios,
and hence one has to preselect. In particular, all scenarios with low probability and low cost
would be excluded.
These scenarios constitute the input for the fire and evacuation models developed under work
package 2, which in turn will be used for benchmarking in work package 3.
1.2 Current SOLAS regulations for passenger ships
The IMO convention SOLAS Chap II-2 (see (3)) has been one of the first maritime
chapters to be rewritten (December 1996 Amendments) in a goal based manner and with
support of a Fire Test Procedures code. The goals and functional requirements are given
in the first place. Then the sub-sections are given.
The fire safety objectives of SOLAS Chapter II-2 are to:
ο‚· prevent the occurrence of fire and explosion;
ο‚· reduce the risk to life caused by fire;
ο‚· reduce the risk of damage caused by fire to the ship, its cargo and the
environment;
ο‚· contain, control and suppress fire and explosion in the compartment of origin;
ο‚· provide adequate and readily accessible means of escape for passengers and crew.
In order to achieve the fire safety objectives, the following functional requirements are
embodied in the regulations of Chapter II-2 as appropriate
ο‚· division of the ship into main vertical and horizontal zones by thermal and
structural boundaries;
ο‚· separation of accommodation spaces from the remainder of the ship by thermal
and structural boundaries;
ο‚· restricted use of combustible materials;
ο‚· detection of any fire in the zone of origin;
ο‚· containment and extinction of any fire in the space of origin;
ο‚· protection of means of escape and access for fire fighting;
ο‚· ready availability of fire-extinguishing appliances; and
ο‚· minimization of possibility of ignition of flammable cargo vapour
As mentioned above, the fire risk is composed of a frequency of ignition and a
consequent severity. The frequency of ignition can be reduced by the prevention of fire
ignition and several theoretical possibilities exist (See (4)). The severity is in fact a
probabilistic distribution of severity depending on the random nature of activation and
efficiency of fire safety systems as well as the random nature of the protection of
persons.
7
8
SOLAS ChapII-2 provides the minimum rules to decrease the frequency of ignition
onboard in the second part B (Prevention of fire and explosion), to manage the fire in
the third part C (Suppression of fire) and finally to manage the exposed with the fourth
part D (Escape). Ro-ro passenger ships have special requirements included in Part G
(Special requirements for the protection of vehicles, special category spaces and ro-ro
spaces).
In this part, the interest is to exemplify part C with essential systems mandatory onboard
passenger ships, including Ro-Pax vessels. The emergency procedures requirements are
also presented.
1.2.1 Essential systems in SOLAS Chap II-2 Part C
1.2.1.1
ο‚·
ο‚·
ο‚·
ο‚·
1.2.1.2
ο‚·
ο‚·
ο‚·
1.2.1.3
ο‚·
ο‚·
ο‚·
ο‚·
ο‚·
ο‚·
Detection and alarm (Regulation 7)
Smoke detection in service spaces, control stations and accommodation spaces,
including corridors, stairways and escape routes within accommodation spaces.
Smoke detectors need not be fitted in private bathrooms and galleys and in
spaces having little or no fire risk. (regulation 7-5.2)
Manually operated call points throughout the accommodation spaces, service
spaces and control stations. (regulation 7-7)
An efficient patrol system shall be maintained so that an outbreak of fire may be
promptly detected (Regulation 7-8)
Fire detection alarms for the systems required by paragraph 5.2 centralized in a
continuously manned central control station (regulation 7-9)
Control of smoke spread (Regulation 8)
Release of smoke from machinery spaces
Draught stops. Air spaces enclosed behind ceilings, panelling or linings shall be
divided by close-fitting draught stops spaced not more than 14m apart. In the
vertical direction, such enclosed air spaces, including those behind linings of
stairways, trunks, etc., shall be closed at each deck. (regulation 8-4)
Atriums equipped with a smoke extraction system. The smoke extraction system
shall be activated by the required smoke detection system and be capable of
manual control. The fans shall be sized such that the entire volume within the
space can be exhausted in 10 min or less.
Containment of fire (Regulation 9)
Main vertical zones bounded by "A-60" class divisions. (regulation 9-2.2.1)
Bulkheads within a main vertical zone required to be "A" class divisions shall be
at least "B" class or "C" class divisions as prescribed in the tables in regulation 92.2.3 (regulation 9-2.2.2)
Protection of stairways and lifts in accommodation area as per regulation 9-2.2.5
Penetrations in fire-resisting divisions and prevention of heat transmission as per
regulation 9-3
Openings in bulkheads and decks in passenger ships as per regulation 9-4.1
Ventilation systems as per regulation 9-7 Among others, the ventilation fans shall
be so disposed that the ducts reaching the various spaces remain within the main
8
9
vertical zone; and stairway enclosures shall be ventilated and served by an
independent fan and duct system which shall not serve any other spaces in the
ventilation systems
1.2.1.4
ο‚·
ο‚·
1.2.1.5
ο‚·
1.2.1.6
ο‚·
ο‚·
ο‚·
ο‚·
ο‚·
ο‚·
ο‚·
ο‚·
1.2.1.7
Fire fighting (Regulation 10)
Automatic sprinkler, fire detection and fire alarm system in all control stations,
accommodation and service spaces, including corridors and stairways.
Alternatively, control stations, where water may cause damage to essential
equipment, may be fitted with an approved fixed fire-extinguishing system of
another type. Spaces having little or no fire risk such as voids, public toilets,
carbon dioxide rooms and similar spaces need not be fitted with an automatic
sprinkler system.
Water supply systems, portable fire extinguishers, Fixed fire-extinguishing
systems, Fire-fighter's outfits as per regulation 10
Structural integrity (Regulation 11)
The hull, superstructures, structural bulkheads, decks and deckhouses shall be
constructed of steel or other equivalent material (regulation 11-2)
Protection of vehicles, special category and ro-ro spaces (Regulation 20)
Detection should take into account the effect of ventilation of those spaces
Sample extraction smoke detection systems may be used
Special category spaces shall be patrolled
Structural fire protection insulation should be A60 all around the spaces except
when spaces of category (5), (9) and (10) are on the other side
sealable ro-ro spaces : CO2 or inert gas or high expansion foam as per resolution
A123 (V) MSC.1/ Circ 1272
other : water spraying system as per resolution A123 (V) MSC.1/ Circ 1272
scuppers and possibly drainage/pumping
Portable fire extinguishers
Casualty threshold, safe return to port and safe areas (Regulation 21) and Design criteria
for systems to remain operational after a fire casualty (Regulation 22)
For new ships of 120m in length or having three or more fire zones the new regulation
II-2 reg. 21 applies:
ο‚· Definition of casualty threshold defined as the loss of any space of origin of fire
up to the nearest A class boundaries being part of the space if fitted with a fixed
fire fighting system (sprinklers) or being part of the adjacent spaces otherwise.
ο‚· Safe return to port if fire breaks out but no casualty threshold is exceeded: a list
of systems should remain operational and safe areas should be designed to
accommodate the passengers.
ο‚· Design criteria for systems if fire breaks out and one casualty threshold is
exceeded in one MVZ: listed FSSs should be so arranged and segregated as to
remain operational during 3 hours in other MVZs and so that the orderly
evacuation and abandonment of the ship is possible.
9
10
1.2.2 Emergency procedures
1.2.2.1
General
Emergency procedures are of primary importance with regards to safety. An effort was
undertaken to identify systems required with respect to an emergency situation. In the
following, II-2 means SOLAS Chapter II-2; FSS/n Fire Safety Code Chapter n, and
LSA/n Life Saving Appliances Code Chapter n.
1.2.2.2
Detection and alarm
Fire detection and fire alarm systems, according to SOLAS Chapter II-2 and FSS Code,
rely on fixed fire detection (smoke detection and manual operated call point) and
automatic sprinkler. The requirements are mainly encapsulated in:
ο‚· SOLAS Chapter II-2 Regulation 7 – Detection and alarm
ο‚· SOLAS Chapter II-2 Regulation 10 – Fire fighting
ο‚· FSS Code Chapter 8 - Automatic sprinkler, fire detection and fire alarm systems
ο‚· FSS Code Chapter 9 - Fixed fire detection and fire alarm systems
The following tables summarises main requirements related to fire detection and fire
alarm systems. More details, as well as technical implementations, are described in the
next chapter.
Smoke
Manual Operated Call
Point
Sprinkler
Location
II-2/7-5.2 In service spaces, control stations and
accommodation spaces, including corridors,
stairways, escape routes within accommodation
spaces and ro-ro spaces (II-2/20.4.1)
II-2/7-7 Throughout
the accommodation
spaces, service
spaces, control
stations and ro-ro
spaces (II2/20.4.3.2)
II-2/10-6.1.1 In all control
stations, accommodation
and service spaces,
including corridors and
stairways
Section
FSS9/2.4.1.1 Grouped into sections
FSS9/2.4.1.1
FSS8/2.4.2.1 Grouped into
separate sections.
System with individually identifiable fire
detectors: a section may serve spaces on both
sides of the ship and on several decks, but shall
not be situated in more than one main vertical
zone.
Grouped into
sections
FSS9-2.5.1.1 Visual and audible fire signal at the
control panel and indicating units.
As per smoke
System
control:
Indication
10
Each of which shall
contain not more than 200
sprinklers. Shall not serve
more than two decks and
shall not be situated in
more than one main
vertical zone.
FSS8/2.5.2. Visual and
audible alarm signal
automatically at one or
11
signal
more indicating units
System
control:
location
FSS9
Ditto
/2.5.1.2 The control panel: on the navigation
bridge or in the continuously manned central
control station.
FSS8/2.5.2. On the
navigation bridge or in the
continuously-manned
central control station.
In addition, in a position
other than on the
aforementioned spaces to
ensure that the indication
of fire is immediately
received by the crew.
/2.5.1.3 Indicating unit:
- At least one, be so located that it is easily
accessible to responsible members of the crew at
all times.
- One be located on the navigation bridge if the
control panel is located in the main fire control
station.
System
control:
identificatio
n
FSS9/2.5.1.3 Indicating units shall, as a
minimum, denote the section.
Ditto
FSS8/2.5.2. units shall
indicate in which section
served by the system a fire
has occurred
Table -1: Alarm and indication
In addition, a fire patrol shall be maintained so that an outbreak of fire may be promptly
detected (II-2/7-8-1).
1.2.2.3
Control and monitoring of systems
General
Active fire protection systems should be controlled and monitored. On passenger ships,
this is mainly centralized in a continuously manned central control station (CMCCS).
According to SOLAS Chapter II-2 Regulation 3 ―Definitionβ€–:
ο‚·
ο‚·
Continuously manned central control station is a central control station which is
continuously manned by a responsible member of the crew
Central control station is a control station in which the following control and
indicator functions are centralized:
1.
2.
3.
4.
5.
6.
fixed fire detection and fire alarm systems;
automatic sprinkler, fire detection and fire alarm systems;
fire door indicator panels;
fire door closure;
watertight door indicator panels;
watertight door closures;
11
12
7.
8.
9.
10.
ο‚·
ο‚·
ventilation fans;
general/fire alarms;
communication systems including telephones; and
microphones to public address systems.
Control stations are those spaces in which the ship's radio or main navigating
equipment or the emergency source of power is located or where the fire
recording or fire control equipment is centralized. Spaces where the fire
recording or fire control equipment is centralized are also considered to be a fire
control station.
Additionally, new ChapII-2 reg. 23 imposes New Passenger ships (>1st July 2010) to have
one safety centre be part or be close to the navigation bridge and should
1. be ergonomic
2. have communication means with CMCCSs, bridge, storage rooms for FSSs and fire
equipment lockers
3. be capable to control and monitor of functionalities of FSSs:
 all powered ventilation systems;
 fire doors;
 general emergency alarm system;
 public address system;
 electrically powered evacuation guidance systems;
 watertight and semi-watertight doors;
 indicators for shell doors, loading doors and other closing
appliances;
 water leakage of inner/outer bow doors, stern doors and any
other shell door;
 television surveillance system;
 fire detection and alarm system;
 fixed fire-fighting local application system(s);
 sprinkler and equivalent systems;
 water-based systems for machinery spaces;
 alarm to summon the crew;
 atrium smoke extraction system;
 flooding detection systems; and
 fire pumps and emergency fire pumps.
Control and monitoring from the continuously manned central control station
In addition to previously discussed requirements on fire detection alarms, according to
II-2/9-3 Passenger ships carrying more than 36 passengers shall have the fire detection
alarms centralized in a continuously manned central control station. The following table
summarises control and monitoring requirements for ventilation fans and fire doors.
Location
Ventilation fan
Fire door
II-2/9-7.4.2 In general, ducts
should remain in the MVZ
MVZ
Stairway enclosure
12
13
Separated system for stairway
enclosures and dangerous areas
Galley boundaries
Ro-ro spaces boundaries
CMCCS Control
II-2/7-9.3 Remote shutting down
II-2/7-9.3 Remote closing and be capable of
reactivation
CMCCS
Indicator –
Control panel
II-2/7-9.3 closed or off status
II-2/7-9.3 & II-2/9-4.1.1.4.6 Open or closed
positions
Other
requirements
II-2/5-2.1.3 Controls so grouped
that that all fans may be stopped
from either of two separate
positions
II-2/9-4.1.1.4.5 A door closed remotely from
the central control station shall be capable of
being re-opened from both sides of the door by
local control. After such local opening, the door
shall automatically close again
Table -2: Control and monitoring: ventilation fans and fire doors
Other Control and monitoring
The following systems could also been controlled and/or monitored from the CMCCS.
Location
Fire damper
Smoke extraction system
II-2/9-4.1.1.8
II2/8-5
Where it is necessary that a ventilation duct passes
through a main vertical zone division, a fail-safe
automatic closing fire damper shall be fitted adjacent to
the division
Atrium
II/9-7.3 Ducts with a free cross-sectional area
exceeding 0.075m2 shall be fitted with fire dampers
through "A" class bulkheads or decks
Control
Fail-safe automatic
By the required smoke
detection system (*)
Be capable of being manually closed from each side of
the division
Indicator
Be capable of manual control
Shall be fitted on at least one side of the division with a
visible indicator showing whether the damper is in the
open position
Table -3: Control and monitoring: Fire damper and smoke extraction system
(*) According to IMO MSC/Circ.1034 (see (5)): ―Guidelines for smoke control and
ventilation systems for internal assembly stations and atriums on new passenger shipsβ€–,
―The automatic activation of the smoke extraction system, by means of the smoke
detectors, may be delayed for up to 2 min from the activation of the first detector, if not
13
14
acknowledged. This 2 minute delay is intended to allow for crew verification of the
smoke detector alarmβ€–. This Circular is not a mandatory text but should be brought to
the attention of interested parties.
1.3 Objectives
As stated above, the aim of work package 1 is to create a methodology for the systematic
generation of fire scenarios and their incident probabilities. The aim of task 1.3 is to
develop a probabilistic model for the reliability and effectiveness of active and passive
Fire Safety Systems (FSS). In this context, active FSS are any systems that are activated in
the event of a fire and include detection systems (smoke and heat detectors), automatic
suppression systems (sprinklers, 𝐢𝑂2 systems etc) as well as any manual measures. In
contrast, passive FSS include structural features like fire walls and fire doors.
The analysis done within this task focuses on the reliability of automatic FSS. A
methodology is developed that can in principle applied to any system, provided that its
setup is known and the failure rates of its components are available.
We will analyse the following systems:
ο‚·
ο‚·
ο‚·
ο‚·
ο‚·
ο‚·
ο‚·
Smoke detectors;
Heat detector;
Alarm panel/detector system;
Sprinkler;
Foam system;
Water mist system and Hi-Fog system;
𝐢𝑂2 system.
For each system, we perform fault tree analyses as necessary and express the reliability as
a function of time over the maintenance interval.
14
15
2 Analysis of Fire Safety Systems
An important part of this task is the analysis of the Fire Safety Systems used on cruise ships.
The reliability and efficiency of these systems are crucial input parameters for any fire
simulation model that massively influence the incidence probabilities and consequences of fire
scenarios.
In this chapter, we describe in technical detail some typical FSS used on cruise ships. In
particular, we give an overview over the functionality of these systems, list its components and
briefly describe regulatory requirements. We analyse fault trees of the relevant systems to
obtain values for their failure rates.
2.1 Automatic Fire Detection Systems
2.1.1 System set-up
Definition
An Automatic Detection System comprises of detectors, manually operated call points, a
control panel displaying the location of the source of a fire and a power supply. Its purpose is
to detect a fire at its initial stage and to automatically activate an alarm.
Application as per SOLAS and FP 53/3/1 convention (6):
Table 4 - SOLAS regulation for detection systems
Operation
Any required fixed fire detection and fire alarm system with manually
operated call points shall be capable of immediate operation at all times
(This does not require a back-up control panel). In passenger ships, the
fixed fire detection and fire alarm system shall be capable of remotely
and individually identifying each detector and manually operated call
point. Fire detectors fitted in passenger ship cabins, when activated, shall
also be capable of emitting, or cause to be emitted, an audible alarm
within the space where they are located.
There shall be not less than two sources of power supply for the
15
16
Power Supply
Total operation
Smoke detector
Heat detector
Operating temperature
electrical equipment used in the operation of the fixed fire detection and
fire alarm system, one of which shall be an emergency source of power.
Separate feeders reserved shall provide the supply solely for that
purpose. Such feeders shall run to an automatic changeover switch
situated in or adjacent to the control panel for the fire detection system.
There shall be sufficient power to permit the continued operation of the
system with all detectors activated, but not more than 100 if the total
exceeds this figure
Required in all stairways, corridors and escape routes within
accommodation spaces shall be certified to operate before the
smoke density exceeds 12.5% obscuration per meter, but not until the
smoke density exceeds 2% obscuration per meter. Smoke detectors to
be installed in other spaces shall operate within sensitivity limits to the
satisfaction of the Administration having regard to the avoidance of
detector insensitivity or over sensitivity.
Heat detectors shall be certified to operate before the temperature
exceeds 78ºC but not until the temperature exceeds 54ºC, when the
temperature is raised to those limits at a rate less than 1ºC per min. At
higher rates of temperature rise, the heat detector shall operate within
temperature limits to the satisfaction of the Administration having
regard to the avoidance of detector insensitivity or over sensitivity.
The operation temperature of heat detectors in drying rooms and similar
spaces of a normal high ambient temperature may be up to 130ºC, and
up to 140ºC in saunas
1.Control and monitor input signals from all connected fire and smoke
detectors and manual call points
2. Provide output signals to the navigation bridge, continuously manned
central control station or onboard safety centre to notify the crew of fire
and fault conditions
3. Monitor power supplies and circuits necessary for the operation of the
system for loss of power and fault conditions
Control panel
4. May be arranged with output signals to other fire safety systems
including - paging systems, the fire alarm or public address system, fan
stops, fire doors, fire dampers, the sprinkler system, the smoke
extraction system, the low-location lighting system, the fixed local
application fire-extinguishing system, the CCTV system, other fire safety
systems; and fuel system quick closing valves.
16
17
The maximum spacing of detectors
Table 5 - Spacing of detectors
Type of detector
Maximum floor area
per detector (m2)
Maximum distance
apart between centers
(m)
Maximum distance
away from
bulkheads (m)
Heat
37
9
4.5
74
11
5.5
Smoke
Regulatory Requirements (FSS code, FP 53/3/1 ):
Fixed fire detection and fire alarm systems with individually identifiable fire detectors shall be
so arranged that:
1. means are provided to ensure that any fault (e.g., power break, short circuit, earth,
etc.) occurring in the section will not prevent the continued individual identification of the
remainder of the connected detectors in the section;
2. all arrangements are made to enable the initial configuration of the system to be restored
in the event of failure (e.g., electrical, electronic, informatics, etc.);
3. the first initiated fire alarm will not prevent any other detector from initiating further
fire alarms; and
4. no section will pass through a space twice. When this is not practical (e.g., for large public
spaces), the part of the section which by necessity passes through the space for a second
time shall be installed at the maximum possible distance from the other parts of the
section.
17
18
Cables used in the electrical circuits shall be flame retardant according to standard IEC 603321. On passenger ships, cables routed through other main vertical zones that they serve, and
cables to control panels in an unattended fire control station shall be fire resisting according to
standard IEC 60331, unless duplicated and well separated.
Detectors shall be located for optimum performance. Positions near beams and ventilation
ducts, or other positions where patterns of airflow could adversely affect performance, and
positions where impact or physical damage is likely, shall be avoided. Detectors shall be
located on the overhead at a minimum distance of 0.5 m away from bulkheads, except in
corridors, lockers and stairways.
The activation of any detector or manually operated call point shall initiate a visual and audible
fire detection alarm signal at the control panel and indicating units. If the signals have not
been acknowledged within 2 min, an audible fire alarm shall be automatically sounded
throughout the crew accommodation and service spaces, control stations and machinery
spaces of category A. This alarm sounding system need not be an integral part of the detection
system.
Functionality
A typical detection system has some sensing elements which can sense the presence of smoke
or heat caused by a fire in or near to the affected area. Subsequently these sensors send an
electrical signal to the fire alarm panel or to specific safety equipment for activation.
When this signal activates the audio-visual alarms on the panel, the concerned crew members
are alerted. The panel helps them to quickly identify the fire-affected zone and thus to take
appropriate countermeasures like fire extinguishing or evacuation.
The responsible crew member is expected to acknowledge the alarm by pressing a cancel
button within two minutes of its activation which silences the hooter/alarm. If this is not
done, then the alarm gets activated in all areas/zones.
The control panel has alarms for the following fault situations:
ο‚·
On detection of fire and smoke
ο‚·
Failure of main supply or low voltage of the battery backup system.
ο‚·
Excessive current (fuse gets blown).
ο‚·
Fault in the electrical power cable.
18
19
Technical details of the Fire Control Panel
ο‚·
Primary Power supply: Commonly a non-switched 120 or 240 V AC source
supplied from a commercial power utility. In non-residential applications, a branch
circuit is dedicated to the fire alarm system and its constituents. "Dedicated branch
circuits" should not be confused with "Individual branch circuits" which supply
energy to a single appliance.
ο‚·
Secondary (backup) Power supplies: This component, usually sealed, lead-acid
storage batteries or other emergency sources including generators, is used to supply
energy in the event of a primary power failure.
ο‚·
Initiating Devices: This component acts as input to the fire alarm control unit and
are either manually or automatically activated.
ο‚·
Notification appliances: This component uses energy supplied from the fire alarm
system or other stored energy source to inform crew members of the need to take
action, usually to evacuate.
ο‚·
Safety Interfaces: This interface allows the fire alarm system to control aspects of
the built environment and to prepare the place for fire and to control the spread of
smoke fumes and fire by influencing air movement, lighting, process control, human
transport and exit.
2.1.2 Smoke Detector
Definition
A smoke detector is a device that monitors the smoke concentration in the surrounding air.
Most smoke detectors work either by optical detection (photoelectric) or by physical process
(ionisation), while others use both detection methods (hybrid system) to increase sensitivity to
smoke. Smoke detectors are usually powered by a central fire alarm system, which in turn is
powered by the main power supply system with a battery backup.
Types of Smoke Detectors
Optical – This detector type is based on the fact that smoke particles scatter light. It typically
consists of a light source (bulb or infrared LED), a lens to collimate the light into a beam, and
19
20
a photodiode or other photoelectric sensor at an angle to the beam as a light detector. In the
absence of smoke, the light passes in a straight line and misses the detector. When smoke
enters the optical chamber across the path of the light beam, some light is scattered by the
smoke particles, directing it at the sensor and thus triggering the alarm.
Ionisation – This type of detector is based on the principle that Ξ±-radiation is attenuated by
smoke particles. A typical source of radiation is a small sample of Americium-241 which has a
half-life of over 430 years. The Ξ±-particles emitted by the sample pass through the ionisation
chamber, an air filled space between two electrodes. The radiation ionises gas molecules
within the ionisation chamber, which allows a small electric current to flow between the
electrodes. When smoke particles enter the ionisation chamber, they absorb the radiation and
hence reduce this current, which triggers the alarm.
While ionisation smoke detectors tend to be cheaper than optical ones, they are also more
prone to false alarms.
2.1.3 Heat detector
Definition
A heat detector is a device which responds to the changes in ambient temperature in the
vicinity of the detector. A predetermined threshold value is set in the detector system.
When the ambient temperature exceeds this threshold value, it sends out an electrical
signal to trigger the alarm. In some cases the automatic sprinkler and detection functions
are combined in one single device, such that when the temperature exceeds the threshold
limit both the fusible bulb of the sprinkler gets fused causing discharge of water and the
detector alarm gets activated simultaneously. Heat detectors are generally of three basic
types, depending on the physics of operation: β€—rate of riseβ€˜ type, fixed temperature and
rate compensation. Yet again, to increase sensitivity any combination of these two types
is used.
Types of heat detectors in comparison
Table 6 - Types of detectors
Criterion
Rate of rise
detector
Fixed temperature
Detector
20
Rate compensation
detector
21
Type of
detection
Rate-of-rise detectors
sense the rate of change
in ambient temperature.
Fixed-temperature heat
detectors operate when the
temperature of the operating
elements reaches a specific
point.
This type of detector also
activates on sensing the
rate of rise of ambient
temperature. However, at
the lower temperature
range it acts as a Fixed
temperature type and at
the higher range of
ambient temperature, in
particular close to the set
value, it works as rate-ofrise type. Thus it
provides more warning
time before the
temperature actually
reaches the set value.
Operating Operating range is
range
about 12 to 15˚F (78˚C) per min.
Operating temperature is
about 135˚F (58˚C)
(up to 5°F per minute)
Areas
Applied in areas
where it is subjected to high
used
ambient temperature,
i.e. boiler rooms or
places which require
detectors that operate
only if close to fire.
Used mainly in unattended
spaces to detect smoldering
fires that increase the
temperature of a detector
above its design value,
usually 135°F to 145°F or
185° to 200°F.
Places where there are
low rates of temperature
change
Combination type heat detectors
This type of detector has multiple sensor elements to respond to the presence of fire and/or
smoke. There are many variations in the design of such detectors such as: response from any
element, response from a partial combination of all elements or complete response from all
elements. Generally, the principle of operation of the first type is to respond to both the rateof-raise and fixed-temperature scenario. The operation based on rate-of-rise of temperature is
very useful and effective in case when fire develops rapidly because it requires much less
response time. In contrast, the elements which operate on the principle of fixed-temperature
respond slowly to the development of fire because time is required to reach the set
temperature, as such this is useful for the case of slowly developing fire. In general, the
common features of the construction of a combination detector include a vented air chamber
and a flexible diaphragm for sensing the rate-of-rise of temperature. On the other hand, the
elements based on the fixed-temperature principle usually consist of a leaf-spring restrained by
21
22
a eutectic metal which fuses on reaching the temperature at the element to its preset
temperature, closing and hence activating the circuit.
2.1.4 Fault tree analysis of a Detector System
We use the fault tree analysis to obtain a value for the failure rate of an Automatic
Detector System.
To obtain failure rates for individual components, the OREDA handbook (7), (8) has
been used. In cases where it didnβ€˜t provide the required information, RIAC data (9) has
been referred to. The type of the failure rate distribution for various components has
been assumed to be β€—Exponentialβ€˜ as indicated in the OREDA handbook. All
abbreviations used in the table below are same as those in the OREDA and RIAC data
books.
Item
Failure
Mode
Mean Standard
(Ξ») per
Dev.
πŸ”
𝟏𝟎 hrs
Mean
time to
failure
(hrs)
Data
Source
Remarks
Pump
Centrifugal,
Sea Water
MDCritical
56.17
30.45
17803
OREDA
This item has
been considered
for all sea water
lifting pumps in
the fault tree.
Valve
General
Critical
25.97
21.31
38506
OREDA
For all valves
same value has
been used.
Compressor
general
Critical,
breakdow
n
6.20
17.26
161290
OREDA
-
Pump
centrifugal
General
MDCritical,
breakdow
n
3.7
11.38
270270
OREDA
For pumps
other that sea
water lift these
values have
been used.
Fire and Gas
UDCritical,
0.43
1.13
232558
OREDA
22
23
detector
General
spurious
operation
WBCritical
1
1.1
3.35
909092
PrCCritical
Table 7 - Failure rates for components from OREDA
The data for the following items has been taken from the RIAC handbook. We have
assumed that these items also follow an exponential distribution like those given in
OREDA.
23
24
ITEMS
Part Description
Quality
Level
Application
(Ξ») per
Environment πŸπŸŽπŸ” hrs
Data
Source
Remarks
Hooter
Alarm
(annunciator,
buzzer)
COM
GB
Mean time
to failure
(hrs)
5.379207 185901
RAC
Ventilator
Ventilator, air
circulator
Timer(summary)
UNK
GM
3.717472 269000
RAC
No item in name of
Hooter in the RAC,
data for Alarm
considered
-
-
-
0.366406 2729213
RAC
-
Relay switch or
other failure in
panel
Panel ,fire control
system
MIL
GM
RAC
-
Switch Fail
Push Button
(Summary)
COM
RAC
Push button type
switch has been
considered.
RAC,
-
RAC
-
RAC
-
Timer
62.37159 16032.94
GM
38.2907
UNK
Cable connection
Cable, electrical
Audio visual
Device
Alarm
(Summary)
-
Battery
DB, BL- Battery
Battery ,
Rechargable
COM
26116
GM
25.13005 39793
0.0431
N
0.0064
24
23201856
156250000
25
MS-Uninterrupted
COM
GF
4.288808 233165
RAC
For main supply
ES-Diesel
Generator
(summary)
COM
GF
136.11
7347
RAC
For emergency supply
Pressure switch
Switch, Pressure
(Summary)
-
-
19.1454
52231.86
RAC
-
UNK
GM
RAC
-
Pressure Gauge
Gauge, Pressure
RAC
-
RAC
-
Power Supply
11.08611 90203
UNK
Level Indicator
Indicator, liquid
level
Strainer
Strainer, Water
GM
16.56534 60367
COM
GF
-
-
Nozzle
Nozzle (Summary)
Valve, Solenoid
(Summary)
UNK
Solenoid Valve
Pipe
Pipe, water
COM
3.903612 256173
0.2136
GM
4681647
16.94915
RAC
RAC
-
RAC
-
59000
GF
2.9277
25
341565
26
Actuator
Pipe(AP)
Fiber optic cable
Pipe
UNK
GM
0.032
31250000
RAC
-
-
-
-
12.5
80000
Assumed
This Item is supposed
to be reliable. We have
assumed its reliability
value as 0.85 over
8000 hrs. of mission
time and the MTTF
value estimated
accordingly.
Table 8 - Component failure rates taken from RIAC
26
27
In some cases, no data is available. In these cases expert judgement has been used to
obtain approximate failure rates. The components in question are given in the table
below.
ITEMS for which Static
Reliability has been assumed*
Assumed Reliability
Operator fails to take action
0.85
DOOR
0.85
Cylinder
0.85
Battery general
0.85
Table 9 - Static reliabilities
*Static reliability is independent of mission time. It is considered as availability on
demand.
The fault tree for a Detector System is given in the appendix. We have used the software
BlockSim to analyse the tree. We obtain the following failure rate for the whole system:
πœ† = 0.0029
1
π‘‘π‘Žπ‘¦π‘ 
2.2 Sprinkler Systems
Definition
A sprinkler system is a fixed installation that discharges water in case of a fire. It is generally
used for fighting and suppressing fire in control stations, accommodation and service spaces,
as well as corridors and stairways.
27
28
Precautionary note: In the spaces where water may cause damage to essential equipment, it
may be fitted with an alternative approved fixed fire-extinguishing system (SOLAS Regulation
10.6.1.1).
2.2.1 System set-up
A typical sprinkler system consists of three parts: pressure tank, air compressor and sprinkler
pump.
A sprinkler system is generally installed for the purpose of fire extinguishing in
accommodation areas and service spaces. These are fixed type installations. The system
consists of a network of sprinkler heads located in the areas that need to be protected, with an
appropriate spacing. Due care needs to be taken for placing the heads so that these do not get
damaged by mechanical contacts or impacts. There are different types of sprinkler heads,
differing by their mechanism of operation. One very common type is a glass bulb head, used
for automatic activation. The glass bulb gets fused at a predetermined temperature in the wide
range of 50 °C to 300 °C (10), (11).
Usually the network of sprinkler heads is divided into sections. As per FSS regulations, each of
these sections must not have more than 200 sprinkler heads. The sections are equipped with
valves which trigger signals for activation of both audible and visual alarms when water flows
through them. Thus it is possible to identify which section of the ship has been affected by
fire. There is a system fitted in the main control room which automatically keeps track of all
the sections of sprinkler heads. Functional diagrams of the system are given below.
28
29
I s o la tio n V a lv e s
W a ter
c o n n e c tio n
f r o m s h o re
T o S p r in k le r H e a d s
t o a u t o m a tic
s p r in k le r s y s te m
C o m p re s s o r
P re s s u r e S w ic h e s
C o m p r e s s e d a ir
1
2
3
F r e s h w a te r
T o B ilg e
F ilte rs
re d u c e r
S a f e ty
h y d ro p h o re
V a lv e
ta n k
P
L ev el
J ockey
S w ic th
P ump
L ev el
in d ic a to r
P ump
L ev el
P um ps
in d ic a to r
P r e s s u re
Ta nk
T o B ilg e
E n g in e
Room
T o B ilg e
F ir e p u m p
F w d . P u m p R oom
F w d . P u m p R oom
S ea C he st
S ea C he st
P
P r e s s u r e C o n tro l
P re s s u r e S w it c h e s
P S ta rt - 0 .5 8 M P a
1 : C o m p r e s s o r S ta rtin g
P S to p - 0 . 8 M P a
P s t a r t :- 0 .7 M P a , P s to p :- 0 .8 M P a
2 : S p r in k le r P u m p S ta rtin g
P s t a r t :- 0 .5
MPa
3 : L o w P r e s s u re S ig n a llin g
P s t a r t :- 0 .7 5 M P a
Figure 2 - Functional diagrams of a sprinkler system
29
30
The regulations demand that each section of sprinklers can be isolated by one stop valve only.
The stop valve in each section should be readily accessible in a location outside of the
associated section or in cabinets within stairway enclosures.
Additional isolation valves may be fitted for the purpose of servicing, maintenance or for
refilling of antifreeze solutions in the sprinkler piping. Audio-visual alarms are provided for
these additional isolation valves when fitted.
The quantities of spare nozzles carried on the ships are as follows (FSS Code):
Table 10 - Nozzles
Total number of nozzles
Required number of spares
< 300
6
300 to 1000
12
> 1000
24
The number of spare nozzles of any type need not exceed the total number of nozzles
installed of that type.
2.2.2 Sprinkler Types and their working principles
As per Resolution A.800(19), the types of Sprinklers Systems are (12):
ο‚·
ο‚·
ο‚·
ο‚·
ο‚·
ο‚·
Wet pipe systems
Dry pipe systems
Deluge systems
Antifreeze systems
Pre-action system
Water-based extinguishing medium
2.2.2.1
Wet pipe systems
This type of sprinkler is the most widely used system. It is the simplest type of sprinkler and
also the only type which can be operated automatically. Its active components are an
automatic sprinkler head and usually (but not always) an automatic alarm check valve. This
simplicity makes the system very reliable as compared to the other types. The pipelines of the
30
31
water supply system for this type of sprinkler arrangement always remain filled with fresh
water (in order to prevent corrosion) under pressure and get activated automatically with the
fusing of the sprinkler heads. The sprinkler heads get fused and open for discharge of water
only when the temperature reaches a threshold value.
Working Principle: When the sprinkler heads exposed to the threshold temperature, the heat
sensitive element (glass bulb or fusible link) is released, allowing water to flow from that
sprinkler. The glass bulb or link applies pressure to a cap which acts as a plug preventing water
from flowing until the ambient temperature around the sprinkler reaches the design activation
temperature of the individual sprinkler. Because each sprinkler activates independently when
the predetermined heat level is reached, the number of sprinklers that operate is limited to
only those near the fire, thereby maximising the available water pressure over the location of
the fire.
2.2.2.2
Dry pipe systems
On vessels operating in areas where the ambient temperature is below the freezing point of
water, the wet pipe system is not suitable to use because the static water inside the pipe might
freeze, causing blockage of the water flow. In such cases a dry pipe system is a suitable option.
In dry pipe systems, the pipes are kept pressurised with air or nitrogen instead of water when
the system is in idle state. Water is discharged only after the air/nitrogen is released on fusing
of the sprinkler bulb when exposed to the threshold temperature. Hence in the initial stage
only air/nitrogen is vented out of the sprinkler head which does not contribute to
extinguishing the fire. The actual effect of fire suppression begins when water is discharged
through sprinkler nozzles. Due to this delay this system is not as effective as the wet pipe
system in the initial stages of a fire.
Working Principle: When the temperature at the sprinkler head reaches the threshold level, it
opens out, allowing the air or nitrogen to vent out through the sprinkler head. Thus the
pressure in the pipeline drops. This leads to a pressure gradient across the dry pipe valve,
allowing water to enter in to the sprinkler piping system. The venting of air or nitrogen from
the sprinkler in the initial stage causes the delay in the venting of water from the sprinklers
needed to control the fire. Therefore, during the initial stages of fire the dry pipe systems are
usually not as effective as wet pipe systems for the suppression of fire.
2.2.2.3
Comparison of Dry Pipe fire Sprinkler systems and Wet Pipe Sprinkler system
Table 11 - Different types of sprinkler systems
Criterion
Dry Pipe System
31
Wet Pipe System
32
Complexity
Dry pipe systems require
additional control equipment
and air pressure supply
components which increases
its complexity.
Wet pipe systems are simple,
with the only operating
components being the
automatic sprinkler heads.
Pipes are filled with water
under pressure so no extra
components are required.
Installation and
Maintenance costs
The added complexity
impacts the overall dry-pipe
installation costs, and
increases maintenance
expenditure primarily due to
added service labour costs.
Its simplicity and wet pipe
reduces maintenance and
installation costs.
Corrosion potential
After operation or testing,
the dry-pipe sprinkler
systemβ€˜s piping is drained,
but residual water may collect
in low spots, and moisture is
also retained in the
atmosphere within the
piping. This moisture,
coupled with the oxygen
increases pipe internal wall
corrosion rates, possibly
leading to leaks.
Wet pipe systems are filled
with water all the time, so
oxygen exposure is reduced,
hence less chance of
corrosion or leakage.
Application
Dry pipe systems are usually
only used in spaces in which
the ambient temperature may
be cold enough to freeze
water.
Wet pipe systems cannot be
used in places where the
ambient temperature drops
below the freezing point of
water.
2.2.2.4
Deluge Systems
As per IMO Resolution A.800(19), "Deluge" systems are systems employing open sprinklers
attached to a piping system connected to a water supply through a valve that is opened by the
detection system installed in the same areas as the sprinklers . In these systems, the sprinklers
fitted are of open type (i.e. without any bulb) and the sprinkler network piping system is not
filled with liquid or gas under normal condition. This type of system is suitable to rapidly
32
33
cover large areas affected by fire. Sometimes it is also used to prevent fire from entering from
other adjacent locations.
Under normal conditions (i.e. when there is no fire), the ingress of water into the sprinkler
network piping is prevented by a deluge valve fitted at the inter-connection of the water supply
line with the sprinkler network piping.
Working Principle: On activation of the automatic detector or manual call point the
corresponding signal is transmitted to the control panel, which in turn signals the deluge valve
to open, allowing water to pass into the sprinkler network piping system and water is instantly
discharged through the sprinkler heads.
2.2.2.5
Antifreeze Systems
This type of system is a wet pipe sprinkler system employing automatic sprinklers attached to
a piping network containing an antifreeze solution and connected to a water supply
(Resolution A.800(19)).
Working principle: When an automatic sprinkler is exposed to sufficient heat, the heat
sensitive element (glass bulb or fusible link) is triggered, allowing antifreeze solution to
discharge. Immediately after this, water flows from the sprinkler head.
2.2.2.6
Pre-action Systems
This type of sprinkler system employs automatic sprinklers attached to a piping system
containing air that may or may not be under pressure, with a supplemental detection
system installed in the same area as the sprinklers (Resolution A .800(19)).
Working Principle: Actuation of the detection system opens a valve that permits water to flow into
the sprinkler piping system and to be discharged from any sprinklers that may be open.
2.2.2.7
Construction and Working Principle of a Sprinkler Head
Fusible sprinkler heads can be used for both detection and extinguishing of fire. A typical
fusible sprinkler head is covered by a semicircular quartzoid bulb, which contains an
expandable liquid. A deflector plate is attached at the end of the bulb. This plate serves
the purpose of spraying the water over a larger area (Figure 3). When the bulb is exposed
to heat, it causes the liquid inside the bulb to expand, leading to breakage of the bulb,
and thus allowing the water to flow from the sprinkler head.
The water supply system for this sprinkler arrangement features a tank pressurised with
compressed air to keep the water in the pipes at a constant pressure. When the bulb fuses
and the water flows out, the pressure in the pipe lines drops, which causes a salt water
pump to start automatically. This salt water pump provides a continuous supply of water
to the sprinkler system. In case of a wet sprinkler system, the piping and heads are
initially filled with fresh water under pressure in order to protect the system from
corrosion.
33
34
Figure 3 - Sprinkler head
2.2.3 Regulatory requirements (Reference FSS code)
Table 12 - Regulations on sprinklers
Type of operation
-Automatic in operation,
-Capable of both detecting the fire and suppressing the fire.
Pressure Tank
capacity
-A pressure tank should have a volume of at least twice that of the
charge of fresh water, equivalent to the amount of water which
would be discharged in 1 min by the pump.
-Means of replenishing the air under pressure and of replenishing
the fresh water charge in the tank
-Provision to prevent passage of sea- water into the tank.
34
35
-Not less than two sources of power for the system.
Power supply
-Sources of power -Main generator and an emergency source.
One supply for the pump should be taken from the main
switchboard, and one from the emergency switchboard by separate
feeders reserved solely for that purpose.
-Provision of a redundant means of pumping.
Water-Supply
Back up
Temperature rating
Pump capacity
-The capacity of the redundant means should be sufficient to
compensate for the loss of any single supply pump or alternative
source. One of the pumps may be the main fire pump connected
to the sprinkler system.
In accommodation and service spaces the sprinklers should have a
nominal temperature rating of 57°C to 79°C, except that in locations
such as drying rooms, where high ambient temperatures might be
expected, the nominal temperature may be increased by not
more than 30°C above the maximum deck head temperature.
Pumps and alternative supply components should be capable of
supplying the required flow rate and pressure for the space with
the greatest hydraulic demand. For the purposes of this
calculation, the design area used to calculate the required flow
and pressure should be the deck area of the most hydraulically
demanding space, separated from adjacent spaces by A-class
divisions. The design area need not exceed 280 m2.
Sprinkler Piping
Should not be used for any other purpose.
Isolation Valves
Isolation valves used for service, maintenance or for refilling of
antifreeze solutions may be installed in the sprinkler piping in
addition to the section stop valves, if provided with a means for
giving a visual and audible alarm.
Sprinkler position
and Capacity
Sprinklers should be placed in an overhead position and spaced in
a pattern to maintain an average application rate of not less than 5
l/m²/min over the nominal area covered by the sprinklers.
System Location
-Sprinkler pump and tank shall be situated in a position reasonably
remote from any machinery space of category A and
-shall not be situated in space required to be protected by sprinkler
system.
35
36
Testing requirement at the time of installation (Reference FTP Code)
The response time is expressed as a response time index (RTI), which typically has values
between 35 and 250 m½s½, where a low value indicates a fast response. Under standard testing
procedures (135 °C air at a velocity of 2.5 m/s), a 68 °C sprinkler bulb will break within 7 to
33 seconds, depending on the RTI. The RTI can also be specified in imperial units, where 1
ft½s½ is equivalent to 0.55 m½s½.
2.2.4 Fault tree analysis of a Sprinkler System
Analogously to the previous section, we perform a fault tree analysis of the system. The
component failure rates are given in Table 7, Table 8 and Table 9. Once again, we use the
software BlockSim to analyse the fault tree diagram given in the appendix. The resulting
failure rate is
1
πœ† = 0.00036
π‘‘π‘Žπ‘¦π‘ 
2.3 Water Mist Systems
2.3.1 System set-up
Definition
Water mist systems are fixed installations that produce small droplets of water to control
and/or extinguish fires.
Working principle
The system works in two ways to control and extinguish fire. The first effect is to remove
oxygen from the atmosphere in the vicinity of the fire and the second one is the cooling
effect.
High-pressure water mist systems generate very small droplets of water. When exposed to the
heat of fire, these droplets evaporate. As this happens, the vapour displaces the oxygen in the
vicinity of the flammable material in the area affected by fire. This helps with the extinction
and controlling of fire by disruption of the oxygen supply.
36
37
Water mist systems discharge water at a very high pressure, producing extremely small
droplets of water. Unlike the larger drops produced by conventional sprinklers, these smaller
particles stay afloat and eventually fill the whole space, creating an atmosphere that impedes
fire growth. Moreover, due to their large surface areas, the droplets are very efficient in
cooling and hence suppressing the fire.
Typical Schematic Diagram:
Figure 4 - Schematic diagram of a water mist system
Components requirements (FSS Code , MSC/Cir 913):
οƒ˜ NozzleοƒΌ An approved type of nozzle with an average distribution of water of at least 5
liters per minute.
οƒΌ Inside Diameter of nozzle at the tip is to be not less than 6 mm.
οƒΌ Corrosion resistant material.
οƒ˜ Distribution valvesοƒΌ To be operated from easily accessible positions outside the spaces to be
protected and which will not be readily cut off by an outbreak of fire.
οƒ˜ Water Supply Pump37
38
οƒΌ To be sufficient to pressurize the piping system at all times and capable of
automatically starting to pump on detecting a pressure drop.
οƒΌ The pump and control equipment are to be provided outside the protected
space.
οƒΌ If the pump is fed from the sources of electrical power of the main and
emergency generator, the emergency generator is to be capable of
automatically starting in the event of failure of the main source of electrical
power supply.
οƒ˜ Water Storage tank
οƒΌ Should be capable of continuously supplying water-based
medium for at least 20 minutes.
Note: Specifications for the following items have not been found in the regulations1. Operational requirements
2. Capacity/Quantity requirements
3. Specification for air supply, e.g. quantity, pressure etc.
System Description:
Water Mist Systems consist of a high-pressure pump unit with cylinders, section valves, piping
system and nozzle heads. Water is supplied via a pump unit or cylinders depending on the
system through a variety of different section valves operated either remotely or manually. For
easy operation and monitoring a control panel is installed. Water Mist Systems are an
alternative to CO2 systems (see below) and are installed in high-risk areas. Sometimes the
system is equipped with glass bulb nozzles, which contain detection bulb glass (see the section
on sprinklers) to start the system automatically in the event of fire. For some areas, the system
can be activated both automatically and manually [MSC/Cir 913]. For the protection of
machinery spaces and local risk areas, the system can be equipped with open nozzles and a
detection system to operate manually for total flooding or local protection of high-risk areas.
System Configuration:
The main component of the MIST Fire Extinguishing System and their functions are as
follows.
οƒ˜ Discharge nozzle
-Fire extinguishing head
οƒ˜ Section valve
-Valve for deluge discharge to the hazardous area
38
39
οƒ˜ Area valve startup solenoid valve
-Control valve to drive air-driven area valves
οƒ˜ Water pump
-High-pressure pump to feed fire extinguishing water under pressure
οƒ˜ Control panel
-Startup panel for starter to start up the high-pressure pump, Startup device for
area discharge by manual operation
οƒ˜ Fire detector (for flame and smoke)
-Smoke detector and flame detector to judge the fire area
οƒ˜ Visible and audible alarms
-Lamps and alarms to warn the persons in the area
Figure 5 - Configuration of a water mist system
Applications:
Water mist systems, as an alternative to CO2 system (see below), can generally be used in the
similar spaces as the latter. This includes engine rooms, boiler rooms, cargo spaces, galleys,
rooms containing electrical and electronic plants and equipment, fuel and lubricating oil tanks
and pumps, flammable liquid storages and paint storages. Although the Water Mist system is
considered equivalent to CO2 systems, for large ships with engine rooms of larger heights, this
39
40
system is not as effective as the CO2 system. This system is preferred for installation on small
boats, hovercrafts etc. with smaller engine rooms.
2.3.2 Fault tree analysis of a Water Mist System/Hi-Fog
System
We have analysed two different systems. The first one is a generic water mist system
analysed with the BlockSim software (Figure 28). The resulting failure rate is
1
πœ†π‘Šπ‘Žπ‘‘π‘’π‘Ÿπ‘€π‘–π‘ π‘‘ = 0.0024
π‘‘π‘Žπ‘¦π‘ 
The second system is a Hi-Fog system as used by Carnival Cruise Lines. This system (see
Figure 29) was analysed using BVβ€˜s VeriSTAR methodology. The resulting failure rate is
πœ†π»π‘–βˆ’πΉπ‘œπ‘” = 0.00094
1
π‘‘π‘Žπ‘¦π‘ 
2.4 CO2 Systems
2.4.1 System set-up
Definition
CO2 systems are fixed installations in an enclosed space that reduce the oxygen content in the
atmosphere by the emission of CO2 to an extent where combustion is no longer possible.
Overview
CO2 is well established as an effective medium for fixed fire extinguishing systems. It is widely
used in domestic as well industrial houses. On board ships it is used for the machinery spaces
and accepted as an alternative to mist and foam fire extinguishing systems (see below).
It can be used to fight electrical fire, liquid fire, melted solid fire, solid surface fire, part deepseated solid fire and gas fire.
The inhalation of CO2 poses a danger to life, and therefore this system is not suitable for
spaces occupied by passengers. It can, however, be used in machinery spaces with special
precautionary arrangements to ensure complete evacuation before discharging of CO2 in the
40
41
affected space. In particular, the system should only be activated through manual operation
and only on confirmation that the space has no soul left inside.
CO2 cylinders should be stored in well ventilated cabinets or lockers in order to prevent
accumulation of gases that might be caused by leakages.
Typical Schematic Diagram of Shipboard CO2 system (13):
Figure 6 - Schematic diagram of a CO 2 system
Components and its requirements (As per FSS Code)
οƒ˜ Cylinders- Should be kept outside protected space.
41
42
οƒ˜ Pipes, fittings and nozzlesοƒΌ Constructed of materials having a melting temperature which exceeds 925 ºC.
οƒΌ Corrosion resistant materials.
οƒ˜ Actuation and control systems- Back up power requirements.
οƒ˜ Distribution valves – Readily accessible, simple to operate and grouped
means of control outside protected space which will not be readily cut-off
by an outbreak of fire.
Salient features of the applicable rules (FSS Code, SOLAS)
Quantity of CO2οƒΌ Cargo Spaces: Sufficient quantity of CO2 shall be available to give a
minimum volume of free gas equal to 30% of the gross volume of the
largest cargo space to be protected,
οƒΌ Machinery Spaces: Sufficient quantity of CO2 shall be available to give a
minimum volume of free gas equal to the larger of the following: 40% of
the gross volume of the largest machinery space so protected or 35% of the
gross volume of the largest machinery space protected, including the casing.
CO2 discharge time 85% of the gas shall be discharged into the space within 2 min (for machinery
spaces).
Operational precautionAutomatic release of fire-extinguishing medium shall not be permitted except as
permitted by the administration
Alarm Opening of release cabinet door shall automatically activate pre -discharge
alarm.
It shall operate for the length of time needed to evacuate the space, but not less
than 20 s before medium is released.
42
43
Advantages of CO2 based system
-100% natural, environmentally friendly,
-Does not leave a residue,
-Zero ozone depletion potential.
Disadvantages
-Highly asphyxiating (suffocative),
-Even if discharge CO2 is cold, it has little cooling effect - danger of re-ignition if air is
readmitted,
-When discharged, particles of solid carbon dioxide may generate static electricity (CO2 is not
an inert medium.
For fault tree diagrams, please refer to the Appendix.
2.4.2 Fault tree analysis of a CO2 system
As in the previous sections, we analyse the fault tree diagram given in the appendix. The
resulting failure rate is
πœ† = 0.0027
1
π‘‘π‘Žπ‘¦π‘ 
2.5 Foam Systems
2.5.1 System set-up
Definition
Foam systems are fixed installations that produce foam to control and/or extinguish fires.
43
44
Working principle
Foam is generated by the formation of air bubbles from aqueous solutions. Since foam has a
lower density than flammable liquids, it remains floating on the surface and creates a β€—blanketβ€˜
on the liquids, cutting off the oxygen supply and thus suppressing the fire.
Components of a typical Foam system:
Foam storage tank
Mixing system
Control panel
Foam liquid
Emergency fire pump
44
45
LEVEL G AUG E
S T R A IN E R
TANK
REDUCER
PUMP
REDUCER
N O N R E T U R N IN G V A L V E
N O N R E T U R N IN G V A L V E
VALVE
VALVE
PUMP
P R O P O R T IO N E R
VALVE
PUMP
F O A M M A IN
IS O L A T IO N V A L V E
Figure 7 - Schematic diagram of a foam system
45
46
F o am R o o m
F o a m T a n k U n it
L ev el g au g e
P re s s u re v a c u u m V alve
F illin g L in e
F o a m M o n ito r V alve
R ec ircu la tio n L in e
F o am L iq u id
ta n k
E
F
D ra in
D
C
B
D ra in
F lu sh in g L in e
T o F ire M ain
F o a m M a in Iso la tin g V alve
Figure 8 - Configuration of a typical foam system
Regulatory Requirements (FSS Code, SOLAS, FP 53/3/1)
Table 13 - Regulations on foam systems
Quantity of foam
Shall be designed to produce foam at the required application rate
within 1 min of release.
Quantity of foam forming liquid
The quantity of foam concentrate available shall be sufficient to
produce a volume of foam equal to at least five times the volume of
the largest protected space at the nominal expansion ratio, but in any
case not less than enough for 30 min of full operation for the largest
protected space.
Operation
The system shall be capable of manual release, Automatic release of
the system shall not be permitted unless appropriate operational
measures or interlocks are provided to prevent any local application
46
47
systems required by regulation II-2/10.5.6 of the Convention from
interfering with the effectiveness of the system.
Power supply
The system shall be supplied by both main and emergency sources
of power. The emergency power supply shall be provided from
outside the protected machinery space. All electrical components in
connection with the foam generating components shall have at least
an IP 54 rating.
Warning Alarms
Means shall be provided for automatically giving audible and visual
warning of the release of the system. The alarms shall operate for the
length of time needed to evacuate the space, but in no case less than
20 s.
Filling rate
The design-filling rate for the system shall. be adequate to completely
fill the largest protected space in 10 min or less
No. of foam
producing units
A minimum of two generators shall be installed in every space
containing combustion engines, boilers, purifiers, and similar
equipment. Small workshops and similar spaces may be covered with
only one foam generator.
Distribution of foam
producing units
Foam generators shall be uniformly distributed under the uppermost
ceiling in the protected spaces including the engine casing. The
number and location of foam generators shall be adequate to ensure
all high risk areas are protected in all parts and at all levels of the
spaces. Extra foam generators may be required in obstructed
locations. The foam generators shall be arranged with at least 1 m
free space in front of the foam outlets, unless tested with less
clearance.
Operation of a foam system
οƒ˜ Open sea suction valve and start firewater pump.
οƒ˜ Open fire water supply valve.
οƒ˜ Open foam liquid non-return valve
οƒ˜ Start foam liquid pump (confirm that the flushing valve is closed)
οƒ˜ Open foam liquid proportioner valve.
οƒ˜ Open monitor as required to bring fire under control
47
48
Recent Developments with respect to the FSS Code
A new chapter 6 of FSS (Ref: FP 53/3/1)
Salient Points:
ο‚·
The system and its components shall be suitably designed to withstand ambient
temperature changes, vibration, humidity, shock, clogging and corrosion normally
encountered on ships, and manufactured and tested to satisfaction of the Administration
in accordance with the requirements of new chapter 6 of FSS (From FP 53/3/1)
ο‚·
Piping, fittings and related components inside the protected spaces (except gaskets) shall
be designed to withstand 925°C.
ο‚·
System piping, foam concentrate storage tanks, components and pipe fittings in
[continuous] contact with the foam concentrate shall be compatible with the foam
concentrate and be constructed of corrosion resistant materials such as stainless steel or
equivalent. Other system piping and foam generators shall be galvanized steel or
equivalent.
ο‚·
Means shall be provided for the crew to safely check the quantity of foam concentrate and
take periodic control samples for foam quality.
ο‚·
Means for testing the operation of the system and assuring the required pressure and flow
shall be provided by pressure gauges at both inlets (water and foam liquid supply) and at
the outlet of the foam proportioner. A test valve should be installed on the distribution
piping downstream of the foam proportioner, along with orifices, which reflect the
calculated pressure drop of the system. All sections of piping shall be provided with
connections for flushing, draining and purging with air.
2.5.2 Fault tree analysis of a Foam System
As above, we analyse the tree diagram given in the appendix. The resulting failure rate is:
πœ† = 0.0096
48
1
π‘‘π‘Žπ‘¦π‘ 
49
3 Reliability model of detection and
suppression systems
3.1 The generic model
Following the literature, we define the reliability 𝑅 of a system as the probability that the
system will function on demand. In this section, we derive the reliability as a function of
time. We assume that 𝑅 is influenced by two factors:
ο‚·
ο‚·
The systemβ€˜s intrinsic failure rate, denoted throughout this report by Ξ»,
The intervals in which the system is checked (and repaired or replaced if
necessary).
In general, Ξ» itself is time-dependent. In particular, one would expect to see the welldocumented β€—burn-inβ€˜ and β€—wear-outβ€˜ effects, resulting in the familiar β€—bathtubβ€˜ curve.
However, as we have no information about the time-dependence of the failure rate, we
will assume it to be constant. This is an acceptable approximation for most of the
systemβ€˜s life span.
We assume that each system is checked after a maximum time π‘‡π‘šπ‘Žπ‘₯ . Let 𝐼 = [0, π‘‡π‘šπ‘Žπ‘₯ )
denote the maintenance interval of the given system. The reliability of the system at time t is
then given by
𝑅(πœ†, 𝑑) = 𝑒 βˆ’πœ†π‘‘ ,
(1)
𝑑 πœ– 𝐼,
where Ξ» is measured in 1 π‘‘π‘Žπ‘¦π‘  and t in days.
A fire can occur at any time during the maintenance interval; hence all values in the range
of R are equally likely to occur. We therefore compute the expectation value of R over
the maintenance interval and use this number as the systemβ€˜s reliability:
𝑅 =
1
π‘‡π‘€π‘Žπ‘₯
π‘‡π‘€π‘Žπ‘₯
π‘’βˆ’πœ†π‘‘ 𝑑𝑑 =
0
1
π‘‡π‘€π‘Žπ‘₯ πœ†
(2)
1 βˆ’ π‘’βˆ’πœ†π‘‡π‘€π‘Žπ‘₯
The variance of R can be computed as usual:
π‘£π‘Žπ‘Ÿ 𝑅 = 𝑅 2 βˆ’ 𝑅
2
=
1
1 βˆ’ 𝑒 βˆ’2πœ†π‘‡π‘€π‘Ž π‘₯ βˆ’ 𝑅
2πœ†π‘‡π‘€π‘Žπ‘₯
49
2
(3)
50
3.2 Propagation of error
In general, the failure rate Ξ» is not known exactly; often the literature provides error
margins on Ξ». This uncertainty of Ξ» propagates to an uncertainty of the reliability R.
Let Δλ denote the error (i.e. standard deviation) of the failure rate Ξ». The uncertainty of R
due to the uncertainty of Ξ» can be computed using Taylorβ€˜s expansion:
∞
Δ𝑅(πœ†, 𝑑) =
π‘˜=1
Ξ”πœ†π‘˜ πœ• π‘˜ 𝑅(πœ†, 𝑑)
π‘˜!
πœ•πœ†π‘˜
With R as given in equation ( 1 ), this takes the form
∞
Δ𝑅(πœ†, 𝑑) =
π‘˜=1
Ξ”πœ†π‘˜
(βˆ’1)π‘˜ 𝑑 π‘˜ 𝑒 βˆ’πœ†π‘‘
π‘˜!
For small values of Δλ we only use the linear term, and hence we obtain
π›₯𝑅 πœ†, 𝑑
β‰ˆ π›₯πœ† π‘‘π‘’βˆ’πœ†π‘‘
(4)
3.3 Maintenance intervals
The intervals in which fire detection and suppression systems are tested differ between
systems and between ship operators. The testing intervals are regulated by IMO
MSC/Circ.850 (14) and are currently under revision (15). In the new version, each system
may be the subject to different intervals for different tests. For example, a variety of tests
are to be performed on sprinkler systems with intervals ranging between monthly (―verify
all control and section valves are in the proper open or closed position, and all pressure
gauges are in the proper rangeβ€– etc) and 10-yearly (―perform a hydrostatic test and
internal examination of 10% of the systemβ€˜s compressed gas cylinders. If one or more
cylinders fail, a total of 50% of the onboard cylinders should be tested. If further
cylinders fail, all cylinders should be testedβ€–).
50
51
3.4 Application to concrete systems
We use the above model to obtain reliability curves for the systems considered in
Chapter 2. In each case, we plot the reliability against time and if possible give an
estimate for the error of each data point.
We will use two different maintenance intervals of one month and one year. This will
serve to highlight the effect maintenance intervals have on the reliability of the system.
3.4.1 Heat detector
According to the OREDA data (8), the mean critical failure for heat detectors is given by
1
πœ†π»π‘’π‘Žπ‘‘ = 6.4 ± 3.8 βˆ™ 10βˆ’5
π‘‘π‘Žπ‘¦
We use a maintenance interval of one year. Plugging this into equations ( 1 ) and ( 4 ), we
obtain the following reliability data:
100.00
99.50
99.00
Reliability/%
98.50
98.00
97.50
97.00
Heat Detector yearly maintenance
96.50
96.00
0
50
100
150
200
Time / Days
250
Figure 9 - Reliability of Heat detector – yearly maintenance
51
300
350
52
100.00
99.95
99.90
Reliability/%
99.85
99.80
99.75
Heat Detector monthly maintenance
99.70
99.65
0
5
10
15
20
25
30
Time / Days
Figure 10 - Reliability of Heat detector - monthly maintenance
Finally, we use equation ( 2 ) and ( 3 ) to obtain the average reliability and standard deviation:
π‘…π»π‘’π‘Žπ‘‘
π‘…π»π‘’π‘Žπ‘‘
π‘¦π‘’π‘Žπ‘Ÿπ‘™π‘¦
π‘šπ‘œπ‘›π‘‘ β„Žπ‘™π‘¦
= 98.8% ± 0.7%
= 99.90% ± 0.06%
3.4.2 Photoelectric Smoke Detector
Analogously to the previous section we use the failure rate given in the OREDA handbook:
1
πœ†π‘ƒβ„Žπ‘œπ‘‘π‘œ = 4.5 ± 2.7 βˆ™ 10βˆ’5
π‘‘π‘Žπ‘¦
Using a maintenance interval of one year, we obtain the following reliability data:
52
53
100.00
99.50
Reliability/%
99.00
98.50
98.00
Photoelectric Smoke Detector yearly maintenance
97.50
97.00
0
50
100
150
200
250
300
350
Time / Days
Figure 11 - Reliability of Photoelectric Smoke detector – yearly maintenance
100.00
99.95
Reliability/%
99.90
99.85
Photoelectric Smoke Detector monthly maintenance
99.80
99.75
0
5
10
15
Time / Days
20
25
Figure 12 - Reliability of Photoelectric Smoke detector – monthly maintenance
53
30
54
Averaging over the maintenance intervals, we obtain:
π‘…π‘ƒβ„Žπ‘œπ‘‘π‘œ
π‘…π‘ƒβ„Žπ‘œπ‘‘π‘œ
π‘¦π‘’π‘Žπ‘Ÿπ‘™π‘¦
π‘šπ‘œπ‘›π‘‘ β„Žπ‘™π‘¦
= 99.2% ± 0.5%
= 99.93% ± 0.04%
3.4.3 Ionisation Smoke Detector
The OREDA failure rate is
πœ†πΌπ‘œπ‘› = 1.0 ± 0.7 βˆ™ 10βˆ’4
1
π‘‘π‘Žπ‘¦
This yields the following data:
100.00
99.00
Reliability/%
98.00
97.00
96.00
95.00
Ionisation Smoke Detector yearly maintenance
94.00
93.00
0
50
100
150
200
Time / Days
250
300
Figure 13 - Reliability of Ionisation Smoke Detector - yearly maintenance
54
350
55
100.00
99.90
Reliability/%
99.80
99.70
99.60
Ionisation Smoke Detector monthly maintenance
99.50
99.40
0
5
10
15
20
25
30
Time / Days
Figure 14 - Reliability of Ionisation Smoke Detector - monthly maintenance
The mean reliability over the maintenance intervals is
π‘…πΌπ‘œπ‘›
π‘…πΌπ‘œπ‘›
π‘¦π‘’π‘Žπ‘Ÿπ‘™π‘¦
π‘šπ‘œπ‘›π‘‘ β„Žπ‘™π‘¦
= 98.2% ± 1.1%
= 99.85% ± 0.09%
3.4.4 Detector panel
This is the system described in section 2.1.4. As there is no historical data available, we will use
the failure rate derived by fault tree analysis:
πœ† = 0.00288
55
1
π‘‘π‘Žπ‘¦π‘ 
56
Mind that no errorbars were derived from the fault trees. With this failure rate, we obtain
the following reliability data:
100.00
90.00
80.00
70.00
Reliability/%
60.00
50.00
40.00
30.00
Detector Panel yearly maintenance
20.00
10.00
0.00
0
50
100
150
200
250
300
350
Time / Days
Figure 15 - Reliability of Detector Panel - yearly maintenance
100.00
99.00
98.00
97.00
Reliability/%
96.00
95.00
94.00
93.00
Detector Panel monthly maintenance
92.00
91.00
0
5
10
15
20
Time / Days
Figure 16 - Reliability of Detector Panel - monthly maintenance
56
25
30
57
Taking the average over the maintenance intervals, we obtain the following reliability:
π‘…π‘ƒπ‘Žπ‘›π‘’π‘™
π‘¦π‘’π‘Žπ‘Ÿπ‘™π‘¦
π‘šπ‘œπ‘›π‘‘ β„Žπ‘™π‘¦
π‘…π‘ƒπ‘Žπ‘›π‘’π‘™
= 62% ± 19%
= 95.8% ± 2.4%
3.4.5 Sprinkler system
As there is no historical data available for this system, we will use the value for Ξ» as derived by
fault tree analysis in chapter 2. The value is
πœ† = 0.00036
1
π‘‘π‘Žπ‘¦π‘ 
With this failure rate, we obtain the following reliability data:
100.00
98.00
Reliability/%
96.00
94.00
92.00
90.00
Sprinkler yearly maintenance
88.00
86.00
0
50
100
150
200
250
Time / Days
Figure 17 - Reliability of Sprinkler - yearly maintenance
57
300
350
58
100.00
99.80
Reliability/%
99.60
99.40
99.20
99.00
Sprinkler monthly maintenance
98.80
0
5
10
15
20
25
Time / Days
Figure 18 - Reliability of Sprinkler - monthly maintenance
Taking the average as above, we obtain the reliability:
π‘¦π‘’π‘Žπ‘Ÿπ‘™π‘¦
π‘…π‘†π‘π‘Ÿπ‘–π‘›π‘˜π‘™π‘’π‘Ÿ
π‘…π‘†π‘π‘Ÿπ‘–π‘›π‘˜π‘™π‘’π‘Ÿ
= 93.7% ± 3.6%
π‘šπ‘œπ‘›π‘‘ β„Žπ‘™π‘¦
= 99.5% ± 0.3%
3.4.6 Foam System
Analogously to the sprinkler system, we use the value for Ξ» derived in chapter 2,
πœ† = 0.0072
58
1
π‘‘π‘Žπ‘¦π‘ 
30
59
This yields the following reliability data:
100.00
90.00
80.00
70.00
Reliability/%
60.00
50.00
40.00
30.00
Foam System yearly maintenance
20.00
10.00
0.00
0
50
100
150
200
Time / Days
250
300
350
Figure 19 - Reliability of Foam system - yearly maintenance
100.00
95.00
Reliability/%
90.00
85.00
80.00
Foam System monthly maintenance
75.00
0
5
10
15
20
Time / Days
Figure 20 - Reliability of Foam system - monthly maintenance
59
25
30
60
The average reliability is found to be
π‘…πΉπ‘œπ‘Žπ‘š
π‘…πΉπ‘œπ‘Žπ‘š
π‘¦π‘’π‘Žπ‘Ÿπ‘™π‘¦
= 35% ± 25%
π‘šπ‘œπ‘›π‘‘ β„Žπ‘™π‘¦
= 89.9% ± 5.6%
3.4.7 Water Mist System
Analogously to the previous sections, we use the failure rate derived by fault tree analysis:
πœ† = 0.0022
1
π‘‘π‘Žπ‘¦π‘ 
Thus we obtain for the reliability:
100.00
90.00
80.00
70.00
Reliability/%
60.00
50.00
40.00
30.00
Water Mist System yearly maintenance
20.00
10.00
0.00
0
50
100
150
200
Time / Days
250
Figure 21- Reliability of Water Mist system - yearly maintenance
60
300
350
61
100.00
99.00
Reliability/%
98.00
97.00
96.00
95.00
Water Mist System monthly maintenance
94.00
93.00
0
5
10
15
Time / Days
20
25
Figure 22 - Reliability of Water Mist System - monthly maintenance
We obtain for the average reliability:
𝑅𝑀𝑖𝑠𝑑
𝑅𝑀𝑖𝑠𝑑
π‘¦π‘’π‘Žπ‘Ÿπ‘™π‘¦
π‘šπ‘œπ‘›π‘‘ β„Žπ‘™π‘¦
= 69% ± 16%
= 96.8% ± 1.8%
3.4.8 Hi-Fog System
We use the failure rate derived by the VeriSTAR analysis:
πœ† = 0.00094
We obtain the following reliability data:
61
1
π‘‘π‘Žπ‘¦π‘ 
30
62
100.00
95.00
90.00
Reliability/%
85.00
80.00
75.00
Hi-Fog System yearly maintenance
70.00
65.00
0
50
100
150
200
250
300
350
Time / Days
Figure 23- Reliability of Hi-Fog System - yearly maintenance
100.00
99.50
Reliability/%
99.00
98.50
98.00
Hi-Fog System monthly maintenance
97.50
97.00
0
5
10
15
20
Time / Days
Figure 24- Reliability of Hi-Fog System - monthly maintenance
62
25
30
63
Thus we obtain for the average reliability:
π‘¦π‘’π‘Žπ‘Ÿπ‘™π‘¦
π‘…π»π‘–βˆ’πΉπ‘œπ‘”
π‘…π»π‘–βˆ’πΉπ‘œπ‘”
= 84.7% ± 8.3%
π‘šπ‘œπ‘›π‘‘ β„Žπ‘™π‘¦
= 98.6% ± 0.8%
3.4.9 CO2 System
In chapter 2, we derived the following failure rate:
πœ† = 0.0027
1
π‘‘π‘Žπ‘¦π‘ 
Thus we obtain the following reliability data:
100.00
90.00
80.00
70.00
Reliability/%
60.00
50.00
40.00
30.00
CO2 System yearly maintenance
20.00
10.00
0.00
0
50
100
150
200
250
Time / Days
Figure 25- Reliability of CO2 system - yearly maintenance
63
300
350
64
100.00
99.00
98.00
Reliability/%
97.00
96.00
95.00
94.00
CO2 System monthly maintenance
93.00
92.00
91.00
0
5
10
15
20
Time / Days
Figure 26- Reliability of CO2 system - monthly maintenance
This gives the average reliability:
𝑅𝐢𝑂2
𝑅𝐢𝑂2
π‘¦π‘’π‘Žπ‘Ÿπ‘™π‘¦
π‘šπ‘œπ‘›π‘‘ β„Žπ‘™π‘¦
= 63% ± 18%
= 96.0% ± 2.3%
64
25
30
65
4 Conclusions
We have developed a methodology to determine the reliability of fire detection and
suppression systems as a function of time, taking into account the effects of regular
system checks.
The only input required for this method is the failure rate of the system (Ξ»). For several
devices, historical data is available and can be used to deduce the failure rate. If such data
is not available (as is generally the case for more complex system, like an alarm panel),
fault tree analysis can be used to determine the systemβ€˜s failure rate. We have
demonstrated this in Chapter 2, where we analysed detector, sprinkler, foam, water mist
and CO2 systems.
The results show a range of reliabilities for these systems. Sprinkler systems show a
particularly high reliability. This is apparently due to the presence of potential manual
backups for the automatic action of the components in the system.
The reliability of detector, CO2 and Water Mist systems is generally in the same order of
magnitude. However, CO2 systems are relatively more reliable owing to the existence of
some static blocks through AND gates in the fault tree structure. These static blocks
represent manual action and have been indicated by blue blocks in the fault trees.
Foam system, in contrast, have a significantly lower reliability caused by the presence of
large numbers of OR gates in the fault tree structure.
Figure 33 in the appendix compares the reliabilities of the five systems analysed by fault trees.
The strength of the fault tree method is that it can in principle be used for any system,
regardless of its complexity. The disadvantage of this method is the fact that it does not
take into account interactions between components and knock-on effects. In other
words, the failure probabilities of different components of the same system are not
necessarily independent; damage to one component may affect the failure probability of
other (neighbouring) components. For this reason, a failure rate derived with the fault
tree method is only an approximation of the systemβ€˜s actual failure rate. It appears that
some of the failure rates derived for this report are unrealistically high (in particular for
the foam system) and should be treated with caution. A refined analysis might be
required to obtain more reliable results.
Nonetheless, the methodology can yield useful results when no other sources of data are
available. It is advisable to compare the results of any fault tree analysis with
experimental or historical data whenever possible to verify the predictions of the model.
65
5 References
1. Nilsen, O.V. Risk Analysis for Cruise Ships (SAFEDOR, Deliverable 4.1.2). s.l. : DNV,
2007.
2. NRI. Worldcruise Network. [Online] 2010. http://www.worldcruisenetwork.com/projects/genesis/.
3. MCA. Maritime and Coast Guard Agency. [Online] 2010.
http://www.mcga.gov.uk/c4mca/mcga-guidance-regulation/mcga-gr-solas_ii-2.htm.
4. National Fire Protection Association. NFPA 550: Guide to the Fire Safety Concepts
Tree. 2007.
5. International Maritime Organization. Guidelines for Smoke Control and Ventilation
Systems for Internal Assembly Stations and Atriums on New Passenger Ships. 2002.
http://www.imo.org/includes/blastDataOnly.asp/data_id%3D5334/1034.pdf.
6. IMO Sub Committee on Fire Protection. Report to the Maritime Safety Committee. s.l. :
International Maritime Organization, 2009. http://www.uscg.mil/imo/fp/docs/fp53report.pdf.
7. SINTEF Industrial Management. Offshore Reliability Data Handbook. s.l. : OREDA
participants, 2002.
8. β€”. Offshore Reliability Data Handbook. s.l. : OREDA participants, 2009.
9. The Reliability Information Analysis Center. Nonelectronic Parts Reliability Data.
1995.
10. Maritime Training Advisory Board. Marine Fire Prevention, Fire Fighting and Fire
Safety. s.l. : Dept. of Commerce, Maritime Administration, 1979.
11. Cote, Arthur E. Operation of Fire Protection Systems. s.l. : NFPA, 2003.
12. IMO Assembly. Revised Guidelines for Approval of Sprinkler Systems. s.l. : International
Maritime Organization, 1995.
http://www.imo.org/includes/blastDataOnly.asp/data_id%3D22567/A800.pdf.
13. Indian Registry of Shipping Archive.
14. International Maritime Organization. MSC/Circ. 850. 1998.
http://www.mpa.gov.sg/sites/circulars_and_notices/pdfs/shipping_circulars/mc0007a.pdf.
15. Private correspondence with IMO.
66
16. Estimates of the Operational Reliability of Fire Protection Systems. Bukowski R.W.,
Budnick E.K. and Schemel C.F. s.l. : Fire Protection Strategies for 21st Century
Building and Fire Codes Symposium, 1999.
17. J.R., Hall. U.S. Experience with Sprinklers and Other Automatic Fire Extinguishing
Equipment. s.l. : National Fire Protection Association, 2010.
18. NTUA. Probabilistic Framework for Onboard Fire Safety - Comprehensive Fire Accidents
Database. s.l. : FIREPROOF Deliverable 1.1, 2010.
19. VTT Technical Research Centre of Finland. Survivability for Ships in Case of Fire.
s.l. : Final Report of SURSHIP-FIRE project, 2009.
20. NTUA, SSRC. Probabilistic Framework for Onboard Fire Safety - Fire Ignition Model
Specification. s.l. : FIREPROOF Deliverable 1.2, 2010.
21. International Maritime Organisation. MSC/Circ. 850. 1998.
http://www.mpa.gov.sg/sites/circulars_and_notices/pdfs/shipping_circulars/mc0007a.pdf.
67
Appendix - Fault trees and diagrams used in the
failure rate analysis
Figure 27 - Foam System on Reliasoft BlockSim
68
Water mist fails to suppress fire
OR
Solenoid valve failure
Improper Water Supply
SV
PF
MD
Section valve failure/
mistakenly closed
Piping damage
P
OR
Mechanical damage
N
OR
Pump failure
Fail to operate pump
Nozzzle Failure
V
Pre pump valve failure/
mistakenly closed
Power supply failure
V
AND
Figure 28 - Water Mist System on Reliasoft BlockSim
69
Main supply failure
Emergency supply failure
MS
ES
Figure 29 - Set-up of the Hi-Fog system
70
No Discharge
Top
A utomatic
Sprinkler Sy stem
Fail to start
Fire Main Fail to start on demand
OR
OR
No Power
Supply
A ND
O perator fails
to start
MStF
Emergency Pump
Fail to start on demand
Mechanical Damage
MD
OR
Detection
Failure
Pressure
Tank Failure
MS
No Power
Supply
Emergency Supply
Failure
Mechanical Damage
O perator Fail to start
MD
MStF
No Power
Supply
OR
A ND
D
A ND
Main Supply
Failure
Sprinkler Pump
Fail to start
A ND
ES
Main Supply
Failure
Emergency Supply
Failure
MS
ES
C ompressor
Damage
Pressure
Gauge Failure
C
PG
Jocky pump
Failure
E
V alv e Failure
RV
Figure 30 - Sprinkler System on Reliasoft BlockSim
71
Mechanical
Damage
MD
Pressure switch
Failure
Mechanical
Damage
PS
MD
Main Supply
Failure
Emergency Supply
Failure
MS
ES
Figure 31 - CO2 System on Reliasoft BlockSim
72
Figure 32 - Detector System on Reliasoft BlockSim
73
100.00
90.00
80.00
70.00
Reliability/%
60.00
50.00
Sprinkler System
40.00
Foam System
Mist System
30.00
CO2 System
20.00
Detector System
10.00
Hi-Fog System
0.00
0
50
100
150
200
Time / Days
Figure 33- Reliabilities of systems analysed by fault trees over one year
74
250
300
350
Download