User Manual SG30KU/SG36KU PV Grid-Connected Inverter SG30KU_SG36KU-UEN-Ver13-201506 Version: 1.3 About This Manual This manual is for the inverters SG30KU and SG36KU. These inverters are grid-connected, transformer-less, robust and of high conversion efficiency. The device will bring you profit from PV power system. Aim The manual contains information about the inverter, which will provide you guidelines to connect the inverter into the PV power system and operate the inverter. Related Documents The manual cannot include complete information about the PV system. You will get the additional information about other devices at www.sungrowpower.com or via webpage of device manufacturer. Target Group The manual is targeted to technical personnel who is responsible for inverter installation and commissioning in the PV power system and inverter owner who will perform daily LCD operation. How to Use This Manual Read the manual and other related documents before any work with the inverter. Documents must be stored carefully and available at all times. The contents of the manual will be periodically updated or revised due to the product development. It is probably that there are changes of manual in subsequent inverter edition. The latest manual can be acquired via visiting the web page www.sungrowpower.com. I Symbols Explanation Important instructions contained in this manual should be followed during installation, operation and maintenance of the inverter. And they will be highlighted by the following symbols. DANGER indicates a hazard with a high level of risk which, if not avoided, will result in death or serious injury. WARNING indicates a hazard with a medium level of risk which, if not avoided, could result in death or serious injury. CAUTION indicates a hazard with a low level of risk which, if not avoided, could result in minor or moderate injury. NOTICE indicates a situation which, if not avoided, could result in equipment or property damage. NOTE indicates additional information, emphasized contents or tips to help you solve problems or save time. II Symbols on the Inverter Body This symbol indicates that you should wait at least 5 minutes after disconnecting the inverter from the utility grid and from the PV input before touching any inner live parts. Hot surface! In order to reduce the risk of burns, do not touch the hot surface when the device is running. Look over the user manual before any operation on the inverter! The installation and service of the inverter unit can only be performed by qualified personnel. III Contents 1 Safety Instructions ................................................................... 1 1.1 IMPORTANT SAFETY INSTRUCTIONS .............................................................. 1 1.2 Arc Fault Detection (AFD) ................................................................................... 5 2 Product Introduction ............................................................... 6 2.1 Intended Usage ...................................................................................................... 6 2.2 Product Description.............................................................................................. 7 2.2.1 Product Appearance ................................................................................................7 2.2.2 Dimensions of Inverter ............................................................................................8 2.2.3 LCD Display Panel......................................................................................................8 2.2.4 DC Switch .....................................................................................................................9 2.3 Technical Description ........................................................................................... 9 2.3.1 Principle Description................................................................................................9 2.3.2 Functions Description .......................................................................................... 10 2.3.3 Derating ..................................................................................................................... 11 3 Installation Flow .....................................................................13 4 Unpacking and Storage .........................................................15 4.1 Unpacking and Inspection .............................................................................. 15 4.2 Available Versions............................................................................................... 16 4.3 Identifying Inverter ............................................................................................ 16 4.4 Delivery Contents ............................................................................................... 18 4.5 Storage of Inverter ............................................................................................. 19 5 Mechanical Installation .........................................................20 5.1 Selecting Installation Location ...................................................................... 20 5.2 Moving Inverter to Installation Site ............................................................. 22 5.3 Installing the Inverter ........................................................................................ 23 5.3.1 Installing on Concrete Wall ................................................................................. 24 5.3.2 Installing on Metal Frame.................................................................................... 25 IV 5.3.3 Installing on the Floor .......................................................................................... 27 5.3.4 Horizontally Installing .......................................................................................... 28 6 Electrical Connection ............................................................. 30 6.1 Connection Conduit Entries............................................................................ 30 6.2 Combiner Unit Description ............................................................................. 31 6.3 Connecting Inverter to AC Grid ..................................................................... 32 6.3.1 AC Side Requirements .......................................................................................... 32 6.3.2 Grid Connection ..................................................................................................... 33 6.4 Connecting Inverter to PV Arrays.................................................................. 35 6.4.1 PV Inputs Configuration ...................................................................................... 36 6.4.2 PV Connection Procedures ................................................................................. 38 6.5 Grounding the Inverter ..................................................................................... 41 6.5.1 Grounding System Overview............................................................................. 41 6.5.2 Second Protective Earth Terminal .................................................................... 42 6.6 Communication Connection .......................................................................... 43 6.6.1 Communication Overview.................................................................................. 43 6.6.2 Communication System ...................................................................................... 44 6.6.3 RS485 Communication Connection................................................................ 46 6.6.4 Configurable Dry Contact ................................................................................... 48 6.6.5 RS485-NET Converting Card (Optional) ......................................................... 49 7 Commissioning ...................................................................... 50 7.1 Inspection before Commissioning ............................................................... 50 7.2 Commissioning Procedure .............................................................................. 50 8 Disconnecting, Dismantling and Disposing the Inverter .... 53 8.1 Disconnecting the Inverter ............................................................................. 53 8.2 Dismantling the Inverter .................................................................................. 54 8.3 Disposing the Inverter ...................................................................................... 56 9 Troubleshooting and Maintenance ...................................... 57 9.1 Troubleshooting .................................................................................................. 57 9.1.1 Troubleshooting of LED Indicator .................................................................... 57 9.1.2 Arc Fault Detection Self-test Fault ................................................................... 58 V 9.1.3 DC Arc Fault .............................................................................................................. 58 9.1.4 Troubleshooting of Faults in LCD Screen ...................................................... 58 9.2 Maintenance ........................................................................................................ 63 9.2.1 Routine Maintenance ........................................................................................... 63 9.2.2 Maintenance Instruction ..................................................................................... 63 9.3 Contact Sungrow Service ................................................................................ 66 10 Operation of LCD Display ......................................................67 10.1 Description of Button Function..................................................................... 67 10.2 Inverter Menu Structure................................................................................... 68 10.3 Main Screen .......................................................................................................... 69 10.4 Adjust Contrast .................................................................................................... 70 10.5 Detailed Running Information....................................................................... 71 10.6 History Records ................................................................................................... 72 10.6.1 Running Information Records ......................................................................... 72 10.6.2 Fault Records ......................................................................................................... 72 10.7 Start and Stop Inverter ..................................................................................... 73 10.8 Input Parameter Settings Password............................................................. 73 10.9 System Parameters Setting ............................................................................. 74 10.9.1 Time Setting ........................................................................................................... 74 10.9.2 Energy Deviation Adjustment......................................................................... 74 10.9.3 Load Default .......................................................................................................... 75 10.9.4 Firmware Version.................................................................................................. 75 10.10 Running Parameters Setting .......................................................................... 76 10.10.1 Main Menu of Run-param .............................................................................. 76 10.10.2 Reactive Power Regulation ............................................................................ 77 10.10.3 Save P/Q-set ........................................................................................................ 77 10.11 Protective Parameters Setting ....................................................................... 78 10.12 Communication Parameters Setting ........................................................... 81 10.13 Advanced Parameters Setting ....................................................................... 81 10.13.1 PVS Detect Settings .......................................................................................... 81 10.13.2 AFD Settings........................................................................................................ 82 VI 11 Appendix ................................................................................ 84 11.1 Technical Data ...................................................................................................... 84 11.2 Grid Over-/Under-voltage Parameter .......................................................... 86 11.3 Grid Over-/Under-frequency Parameter..................................................... 86 11.4 P-Q Curve ............................................................................................................... 86 11.5 Automatic Power Derating .............................................................................. 87 11.5.1 Temperature-related Power Derating .......................................................... 87 11.5.2 Input Voltage-related Power Derating ........................................................ 88 11.6 Exclusion of Liability .......................................................................................... 89 11.7 About Us ................................................................................................................ 90 VII 1 Safety Instructions 1.1 IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS. This manual contains important instructions for SG30KU and SG36KU inverter that shall be followed during installation and maintenance of the inverter. The SG30KU and the SG36KU have been designed and tested strictly according to the international safety regulations. As electrical and electronic equipment, safety instructions related to them must be complied with during installation, commissioning, operation and maintenance. Incorrect operation or work may result in damage to: y The life and well-being of the operator or a third party y The inverter and other properties that belong to the operator or a third party Therefore, the following safety instructions must be read and always kept in mind prior to any work. All detailed work-related safety warnings and notes will be specified at the critical points in corresponding chapter. All installation and electrical work must only be performed by qualified personnel. They have y been trained specially; y already completely read through and understood the manual and other related documents; y been familiar with safety requirements for electrical system. Technical personnel mentioned above may perform the following work: y Install the inverter onto the wall y Connect the inverter into the PV power system y Connect other devices into the PV power system y Commission the inverter y Maintain and service the inverter 1 1 Safety Instructions User Manual Before Installation There is a risk of injury due to improperly handling the device! y Always follow the instructions contained in the manual when moving and positioning the inverter. y The weight of the equipment can cause injuries, serious wounds, or bruise if improperly handled. During Installation Prior to installing the inverter onto the wall, it is crucial to make certain that the inverter is not electrically connected. System performance loss due to bad ventilation! The equipment requires good quality ventilation during operation. It is essential to keep the unit upright and nothing covering the heat sink in order to ensure that the equipment interior is well cooled down. During Electrical Connection Lethal voltage exists! PV arrays will produce electrical energy when exposed to sunlight and thus can create an electrical shock hazard. y Wiring of the PV arrays should only be performed by qualified personnel. All cables must be firmly attached, undamaged, properly insulated and adequately dimensioned. 2 User Manual 1 Safety Instructions During Inverter Operation Do not open the enclosure when the inverter is under voltage. There is an unlikely but possible risk of explosion in very specific cases of fault. The housing will protect persons and property from such an explosion, only if it is correctly sealed. There is a risk of burn! Prevent from touching device hot parts (such as heat sink) during operation. Only LCD display panel and DC switch can be touched during inverter operation. Maintenance and Service There is a risk of inverter damage or personnel injury due to incorrect service work! Always keep in mind that the inverter is power supplied by dual power source: PV arrays and utility grid. Before any service work, you should obey the following procedures. y Disconnect inverter from the utility grid side first and then PV arrays; y Wait at least ten minutes until the inner capacitors discharge completely; y Verify that no voltage or current present with appropriate testing device. Keep unrelated person away! A temporary warning sign and barrier must be posted to keep non-related person away for any period while performing electrical connection and service work. y Any fault that may impair the inverter safety functions must be repaired immediately before the inverter is restarted. y Inverter contains no owner serviceable parts inside. Please contact local authorized personnel if any service work is required. 3 1 Safety Instructions User Manual Servicing of the device in accordance with the manual should never be undertaken in the absence of proper tools, test equipment or more recent revision of the manual which is clearly and thoroughly understood. There is a risk of inverter damage if it is improperly serviced. Use only accessories and spare parts approved by the inverter manufacturer. Never modify the inverter or other components of the inverter. Otherwise it will cause loss of any or all warranty rights. There is a risk of inverter damage due to electrostatic discharge! The printed circuit boards contain components sensitive to electrostatic discharge. Wear a grounding wrist band when handling the boards. Avoid unnecessary touch with the boards during replacement. Others The selected country settings can be changed by qualified personnel only! Unauthorized modification to country settings should be prohibited. Alternation of the country settings may cause a breach of the type-certificate marking. All safety instructions, warning labels and nameplate on the inverter body: y Must be clearly visible; y Must not be removed, covered and pasted. 4 User Manual 1 Safety Instructions These regulations should also be followed: y The regulations related to the electricity fed into grid; y The safety instructions related to PV arrays; y The safety instructions related to other electrical device. 1.2 Arc Fault Detection (AFD) According to the 2011 National Electric Code (NEC) and 2013 Canadian Electric Code (CEC), if the DC voltage of a photovoltaic system is higher than 80V and the system is on a building or its DC conductors enter a building, it must be equipped with a special device that can detect a DC arc fault and interrupt the circuit. This functionality is commonly referred to as a DC AFDI. The inverter assures to detect the arc fault defined by UL1699B. The DC ARC-Fault circuit is for series arcing faults or a type 1 device. The SG30KU and SG36KU inverter’s DC Arc Fault Detection (AFDI) function is based on the Digital Signal Processor (DSP). The DC AFD module performs a self-test every time the inverter is started-up or you can manually activate AFD function on the LCD screen, the result will show on the LCD screen, which can only be pass or fail. If it fails, the corresponding fault code will be displayed and the inverter will not connect to the grid. If it passes, the inverter connects and operates normally. If a DC arc fault is detected during normal operations, the inverter will disconnect from the AC grid. The DC arc fault is displayed on the inverter’s LCD screen and the inverter is powered off until the fault is manually removed. 5 2 Product Introduction 2.1 Intended Usage SG30KU and SG36KU (They will be referred to as inverter hereinafter unless otherwise specified) which are a 3-phase string inverter without transformer, are crucial unit between the PV strings and utility grid in the PV power system. Inverter is dedicated to converting direct current power generated by the PV modules into alternating current, which conforms to parameters of local utility grid, and feeds it into the utility grid. The intended usage of the inverter is illustrated in Fig. 2-1. Fig. 2-1 Application of the inverter of the PV Power System Item Description A PV strings B C D Inverter Metering device Utility grid Note Monocrystalline silicon; polycrystalline silicon and thin-film without grounding of protection class II SG30KU, SG36KU Mter cupboard with power distribution system 4W-Y Grid or 3W-Δ Grid Any other or additional usage is not permitted except the intended usage. Inverter may only accept PV modules with Protection Class II as its input. Inverter may only be connected to utility grid via distribution board. Local loads (home appliance, lights, motor loads, etc.) cannot be connected between inverter and AC circuit breaker on the distribution board. Additionally, the unit is intended for fixed installation. Located on a part that is not removable without impairing the operation of the unit. 6 User Manual 2 Product Introduction 2.2 Product Description 2.2.1 Product Appearance Fig. 2-2 Product Components Description Item 1 2 3 Name Description LCD display panel Connection openings Inverter operation data viewing and parameters configuration can be performed via the LCD display panel. Connection openings with plastic threaded plugs for connecting conduits. The handles are designed for holding the unit when transporting, installing or servicing. Handles 5 6 7 Second PE Terminals Air outlet Mounting ear Fans 8 DC switch 9 10 Air inlet AC switch 4 Second protective earth terminals as specified in EN 50178. Exit of hot air during the inverter operation. It is used for hanging inverter onto the backplate. There are four fans to perform controlled forced-air cooling. During normal operation it is in “ON” state. It can shut down the inverter immediately in “OFF” position. Entrance of cool air. Serviced as an automatic overcurrent device. 7 2 Product Introduction User Manual 2.2.2 Dimensions of Inverter Fig. 2-3 Outline Dimensions of Inverter (unit: mm) 2.2.3 LCD Display Panel As a human-computer interaction interface, LCD display panel comprises LED indicators, buttons and LCD display screen on the front panel of the inverter. y LEDs indicate the working status of the inverter y The current running information shown on the LCD display y Fault records shown on the LCD display y Inverter configuration by pressing the buttons Fig. 2-4 LCD Display Panel 8 User Manual 2 Product Introduction Tab. 2-1 LCD Display Panel Description No. Name Description 1 LED indicators 2 Buttons 3 LCD screen “RUN” and “FAULT”. Inverter current state can be known from the two indicators. Detailed definition is shown in Tab. 2-2. Navigate in the LCD menu, set values and so on. Detailed function is shown in Tab. 10-1. LCD screen can display current state of inverter, current running information, history information and parameters to be set. Tab. 2-2 Description of LED Indicator Status LED Status “RUN”: on; “FAULT”: off “RUN”: off; “FAULT”: on “RUN”: off; “FAULT”: off Description Inverter is feeding AC power to the utility grid. A fault happens; or protection function triggers. Inverter is not energized; or there is a communication error between DSP and LCD. 2.2.4 DC Switch DC switch is designed for safely disconnecting the DC input current if required. The inverter works automatically when input and output meet the requirements. Rotating DC switch to the “OFF” position will immediately cut off the flow of DC current. Rotate the DC switch to the “ON” position, before restarting the inverter. 2.3 Technical Description 2.3.1 Principle Description The principle design of transformer-less and grid-connected inverters are illustrated below. They are equipped with MPPTs for two DC inputs to ensure that the maximum power can be utilized even in different PV modules installation conditions. Inversion circuit converts DC power into AC power, which will be fed into the utility grid via five core terminals. Protective circuits are designed to guarantee inverter safe operation and human safety. 9 2 Product Introduction User Manual A DC switch is integrated for safe disconnection of DC current. The inverter provides standard interface RS485 for communication. Inverters are also provided running records display and parameters configuration via human-computer interface – LCD display panel. We provide 3 options of inverters for the users, the S0, S1 and S2 versions are for SG30KU, the S1 and S2 versions are for SG36KU. Fig. 2-5 Main Circuit Diagram of SG30KU and SG36KU *Image shown here is indicative only. Actual product you receive may differ. 2.3.2 Functions Description Inverter functions can be grouped as the following: y Conversion function Inverter converts the direct current power into alternating current power, which conforms to the grid requirement of its installation country. y Data storage and display Inverter stores essential data including running information and fault records, and displays them on integrated LCD display. y Parameters configuration Inverter provides various parameters configuration for optimal operation. y Communication interface 10 User Manual 2 Product Introduction Standard RS485 interface for connecting other monitoring devices into the PV system is included. y Arc Fault Detection If a DC arc fault is detected during normal operations, the inverter will disconnect from the AC grid. y Protection functions − Short circuit protection − Insulation resistance to ground surveillance − Inverter output voltage surveillance − Inverter output frequency surveillance − Residual current protection − DC component of AC output current surveillance − Anti-islanding phenomena protection − Ambient temperature surveillance − DC over-voltage protection − Over current protection − Power module over-temperature protection 2.3.3 Derating Derating the output power is a way to protect the inverter from overload and potential faults. Inverter’s derating function can be activated in the following scenarios: y Grid voltage too low y Temperature too high (Inner temperature and power modules temperature) y Power limit setting on the inverter LCD display or remote dispatch Power Limit Setting User may allocate output power value of the inverter via LCD control panel or the remote dispatch from the grid company. Under this kind of power derating, the operating states will display on the LCD screen. Over-temperature Derating Power modules over-temperature may result from high ambient temperature, poor ventilation or fault of fans. Over-temperature derating may protect the inverter as well as the power modules against damage. 11 2 Product Introduction User Manual y When the modules temperature exceeds an upper limit, the inverter start to gradually derating until the temperature decreases to normal range. y When the inner temperature exceeds an upper limit, the inverter start to gradually derating until the temperature decreases to normal range. The deration lower limitation is about 33%. If the modules temperature and the inner temperature are both exceed the limit, the actual derating power value will be the less one. Grid Under-voltage Derating Once the grid voltage is in the defined range of Vgrid(Vmin…244V), the inverter will decrease the power output. P[Vmin…244V] = Pn × (Vgrid/277V) Fig. 2-6 Grid Under-voltage Derating 12 3 Installation Flow Fig. 3-1 shows the installation flow of inverter for installer. Please follow these procedures. Fig. 3-1 Installation Flow Chart 13 3 Installation Flow User Manual Tab. 3-1 Description of Installation Flow Order Description Reference Chapter 1 Unpacking and inspection Read this manual, especially the section on “safety instruction” Store the inverter unit if not install immediately Choose the best installation site Moving the inverter to installation site Install the inverter against the chosen wall Electrical connections include DC, AC, ground and communication(optional)connection Examine before commissioning Start up inverter and configure corresponding parameters Troubleshooting Section 4.1 2 3 4 5 6 7 8 9 10 14 Chapter 1 Section 4.4 Section 5.1 Section 5.2 Section 5.3 Section 6.3...6.7 Section 7.1 Section 7.2 Section 9.1 4 Unpacking and Storage 4.1 Unpacking and Inspection The unit is thoroughly tested and strictly inspected before delivery. Damage may still occur during shipping. y Check the packing for any visible damage upon receiving. y Check the inner contents for damage after unpacking. y Check the completeness of delivery contents according to the inner packing list. If there is visible damage to the packaging or the inner contents, or if there is something missing, contact the unit dealer. Do not dispose of the original packaging. It will be the best choice to store the inverter by re-using the original packaging. Fig. 4-1 Paper Packaging of Inverter 15 4 Unpacking and Storage User Manual 4.2 Available Versions According to their rated output power, the inverters can be divided into 30kW and 36kW. We provide five wiring box versions for equal output power inverters. Tab. 4-1 shows the five wiring box versions. Tab. 4-1 Description of 30kW and 36kW models Type SG30-S0-VERSION SG30_36KU-S1-VERSION SG30_36KU-S12-VERSION Dimensions (H×W×D): 634×875×257mm 25.0×34.4×10.1in Weight: 65kg/143.3lbs. Tab. 4-2 Wiring box configurations available Type SG30-S0-VERSION SG30_36KU-S1-VERSION SG30_36KU-S2-VERSION Available Components DC Switch DC Input Fuses DC Switch DC Input Fuses DC Surge Protection Device(SPD) DC Switch DC Input Fuses DC Surge Protection Device(SPD) AC Surge Protection Device(SPD) AC Switch 4.3 Identifying Inverter A nameplate is attached to one side of the inverter and the carton respectively. It provides information on type of inverter, along with the most important specifications, marks of certification institutions, website and serial number which is available and identified by Sungrow. 16 User Manual 4 Unpacking and Storage Fig. 4-2 Nameplate of Inverters *Image shown here is indicative only. Actual product you receive may differ. Item Description 1 2 3 4 SUNGROW logo and product type Technical data of inverter Marks of certification institutions of inverter Company name, website and origin Tab. 4-3 Description of Icons on the Nameplate Icon Description CSA mark of conformity. The inverter is in compliance with directives of US and CAN. Electrical shock protection mark. Do not perform any servicing other than that specified in Electrical Connection instructions to protect against electrical hazard. Thermal hazard mark. Do not touch the hot surface when the device is running. Refer to the corresponding instructions. 17 4 Unpacking and Storage User Manual 4.4 Delivery Contents Fig. 4-3 Delivery Contents Item Name Description A B Inverter unit Backplate Expansion bolts --It is used for mounting inverter onto the wall. Seven units. It is used for fastening backplate onto concrete wall. Seven units. It is used for fastening backplate onto metal frame. C D Fastener set E Fix screws F Documents G Jumper cables 18 2 M4×16 screws for fix the inverter to the backplate. Documents include quality certificate, packing list, product test report, and inverter user manual. Configure PV configuration in parallel mode via jumper cables. User Manual 4 Unpacking and Storage 4.5 Storage of Inverter Where the inverter may not be installed immediately or inverter needs to be stored under certain condition, store the unit as the following indications: y The unit must be packed into original carton and desiccant must be put inside. If the original packaging is not available, an equivalent carton which is able to support the unit weight and size can be used. y The packing should be sealed by adhesive tape. y The unit must be stored in a clean and dry place to protect against dust and moisture. y The storage temperature should be always between -30℃ and 85℃. And the storage relative humidity can reach 100%. y The recommended number of stack layers is not more than 4. y It is very important to keep the packing away from chemicals. Otherwise it will lead to corrosion. y During the storage time, periodically check any visible damage by rats and other rodents. Replace the packaging if necessary. y The packaging should be kept upright. y After long term storage, local installer or service dept. of Sungrow should perform a comprehensive test before connecting the inverter into PV power system. 19 5 Mechanical Installation 5.1 Selecting Installation Location Selecting an optimal installation location for the inverter is decisive for its operating safety as well as its expected efficiency and service life. y Take the load capacity of the wall into account. The wall (such as concrete wall and metal structure) should be strong enough to hold the weight of the inverter over a long period of time. y Install the unit where is accessible to install, electrical connect or service. y Do not install the unit on the wall of flammable materials. y Do not install the inverter where contains flammable materials or flammable gas in the vicinity of the unit installation. y Install the unit at eye level for easily buttons operation and display read. y It is suggested that the inverter be installed vertically or horizontally with the bracket for good heat dissipation. y Never install the inverter with a forward tilt, nor with a backward tilt nor even with upside down. 20 User Manual 5 Mechanical Installation y The inverter unit with NEMA 4X can be installed indoors or outdoors also. y The ambient temperature should range from -25°C to 60°C. y The relative humidity of the installation can reach 100%. Moisture may result in corrosion and damage to the internal device components. y Avoid exposing inverter to direct sunlight or rain or snow to extend its service life despite the NEMA 4X protection degree. Exposure to the sun may cause additional internal heating which will cause power reducing. Shaded site of the building is preferred. y Take enough space for convection into consideration during installing multiple inverters. It is suggested that position the multiple inverters in a staggered way if necessary. 21 5 Mechanical Installation User Manual y Do not install the inverter in a closed cabinet. Otherwise, the inverter will not operate normally. It is necessary to make sure that hot air will be discharged by forced ventilation. y Do not install the inverter where children can reach. y Do not install the inverter in living area. Noise can be produced during running of inverter, which may affect your daily life. 5.2 Moving Inverter to Installation Site If the inverter is to be installed, remove the unit from the packaging and move it to the chosen installation site. During the moving process, the following instructions should be obeyed. y Always remember the weight of the inverters. y Grasp the equipment by both hands by means of handles. y Move the unit with the help of others or the lifting device. y Do not release the equipment unless it has been secured to the wall firmly. 22 User Manual 5 Mechanical Installation 5.3 Installing the Inverter Inverter is installed onto the wall by means of backplate enclosed in the packaging. If you don’t use the supplied backplate, you may drill holes refer to its dimension below. Fig. 5-1 Dimensions of Backplate(unit: mm) There are two sets of stainless fasteners supplied for attaching the backplate to concrete wall and metal frame. Fig. 5-2 Dimensions of Expansion Bolt Set for Concrete Wall (unit: mm) Fig. 5-3 Dimensions of Fastener Set for Metal Frame(unit: mm) 23 5 Mechanical Installation User Manual 5.3.1 Installing on Concrete Wall Step 1 Remove backplate and fasteners from the packaging. Step 2 Place the backplate onto the chosen concrete wall and adjust it until it is in a horizontal position. Step 3 Mark the positions to drill holes using the backplate as the template. Step 4 Drill holes according to the marks made before. In order to avoid electrical shock or other injury, inspect existing electronic or plumbing installations before drilling holes. Step 5 Attach the backplate to the wall firmly with the supplied expansion bolt set. The torque for fastening the nut is 35 Nm. Step 6 Assemble the cap onto the inverter for better weatherproof function. Step 7 Lift up inverter above the backplate and then slide down to make sure that the recesses on the back of the inverter fit perfectly together with the backplate. Step 8 After fit the inverter to the backplate, fasten the inverter to the backplate with two M4×16 screws. 24 User Manual 5 Mechanical Installation 5.3.2 Installing on Metal Frame Step 1 Remove backplate and fasteners from the packaging. Step 2 Choose the best installation site according to above requirements. Place the backplate onto the chosen metal frame and adjust it until it is in a horizontal position. Step 3 Mark the positions to drill holes by using the backplate as the template. Step 4 Drill 6 holes at the marks you have made. If the shape of the metal frame doesn’t fit the holes on the backplate, re-drill holes on the backplate of appropriate position according to the chosen frame. In order to avoid electrical shock or other injury, inspect existing electronic or plumbing installations before drilling holes. Step 5 Fasten the backplate against the metal frame with bolts and nuts. The dimensions of fasteners used in the following diagram are recommended. The torque for fastening the nut is 35 Nm. 25 5 Mechanical Installation User Manual Item Description Remark A B C D E F Hexagonal socket nut Spring washer Washer Hexagonal bolt Metallic wall Backplate M10 M10*45 - Step 6 Assemble the cap onto the inverter for better weatherproof function. Step 7 Lift up the inverter above the backplate and then slide down to make sure that the recesses on the back of the inverter fit perfectly together with the backplate. Step 8 After fit the inverter to the backplate, fasten the inverter to the backplate with two M4×16 screws. 26 User Manual 5 Mechanical Installation 5.3.3 Installing on the Floor Step 1 Remove floor bracket and fasteners from the packaging. Step 2 Fixing the floor bracket to the inverter. Step 3 Place the floor bracket onto the chosen floor position. Step 4 Mark the positions to drill holes using the floor bracket as the template. Step 5 Drill holes according to the marks made before. In order to avoid electrical shock or other injury, inspect existing electronic or plumbing installations before drilling holes. Step 6 Attach the floor bracket to the floor firmly with the supplied expansion bolt set. The torque for fastening the nut is 35 Nm. Step 7 Assemble the cap onto the inverter for better weatherproof function. 27 5 Mechanical Installation User Manual 5.3.4 Horizontally Installing Step 1 Remove the bracket and fasteners from the packaging. Step 2 Assemble the bracket to the recesses on the back of the inverter and make sure them fit perfectly together with the mounting ear. Fix the bracket with two M4×16 screws. Step 3 Install the fixing plates on the bracket. Step 4 Assemble the cap onto the inverter for better weatherproof function. Step 5 Move the inverter to the chosen position and attach the fixing plate to the floor firmly with the supplied expansion bolt set. Ensure there are no plants nearby! 28 User Manual 5 Mechanical Installation L1*: Distance from the center of the fans to the floor. L2*: The shortest distance from the top cover of the inverter to the PV panel. You may order the brackets from Sungrow. 29 6 Electrical Connection Once the inverter is firmly attached to the appropriate location, it can be connected to the PV power system. Installation shall comply with local regulations and technical rules. Improper operation during the wiring process can cause fatal injury to the operator or unrecoverable damage to the inverter. Only qualified personnel can perform the wiring work. Prior to any electrical connection, keep in mind that inverter has dual power supplies. It is mandatory for technical personnel to wear personal protective equipment: helmet, footwear and gloves during the electrical work. 6.1 Connection Conduit Entries Conduit entries for all versions are located on the bottom and at the sides of the combiner unit. Conduit entries are illustrated below. Fig. 6-1 Conduit entries No. Description 1 2 3 DC cable openings with plastic threaded plug. Trade size 1-1/2'' AC cable openings with plastic threaded plug. Trade size 1'' Communication cable openings with plastic threaded plug. Trade size 1/2'' Make sure the appropriate conduit hub is used in order to maintain required 30 User Manual 6 Electrical Connection spacing between wiring groups and ensure the integrity of the NEMA 4X environmental rating. If inverter is wall-mounted or horizontally-mounted, both the bottom and the knockouts on the two side of the inverter can be used for conduit entries installation. If inverter is ground-mounted, only the knockouts on the two side of the inverter can be used for conduit entries installation. 6.2 Combiner Unit Description There are five models of the combiner unit available for either the 30 kW or 36 kW versions. The major differences between the five combiner unit layouts are shown below. Tab. 6-1 Complete list of combiner unit components No. Description No. Description 1 2 3 DC switch DC SPDs (Surge Protection Devices) Configuration circuit board 6 7 8 4 AC connection circuit board 9 5 AC connection terminal block 10 AC switch AC SPD DC Fuses Equipment ground conductor busbar Communication circuit board SG30-S0-VERSION 31 6 Electrical Connection User Manual SG30_36KU-S1-VERSION SG30_36KU-S2-VERSION 6.3 Connecting Inverter to AC Grid 6.3.1 AC Side Requirements Only after receiving prior approval from the local grid company as required, should you connect the inverter to the grid. Prior to connecting to the utility grid, verify whether the grid voltage and frequency are within the range of inverter output parameters, referred to “Appendix”. Otherwise consult local grid company for solution. Residual Current Device With an integrated universal current-sensitive residual current monitoring unit inside, the inverter is able to distinguish the fault currents from normal capacitive leakage currents. The inverter will disconnect from mains as soon as a fault current of more than limit value has been detected. However if an external RCD or residual current breaker is mandatory, the switch must trigger at a failure current of 300mA or higher. 32 User Manual 6 Electrical Connection 6.3.2 Grid Connection Wiring methods used should be in accordance with the National Electric Code, ANSI/NFPA 70 and/or any prevailing local codes and regulations. An AC terminal block inside the combiner unit is used for the five-wire grid connection (L1, L2, L3, N, PE) of the inverter. AC Cable Requirements Consider the following facts when select AC cables specifications and types: y The grid impedance of the AC cable must correspond to the specification to avoid unintended disconnection from the grid or derating of the output power. y Voltage drop and other consideration may use the larger size cables. Avoid power loss in cables of more than 1% of nominal inverter rating. y Withstand ambient temperature; y Layout type (inside wall, underground, free air etc.); y UV resistance and so on. Use only Copper (Cu) wire rated for 90°C (194°F), solid or with type B or type C stranding (19 strands maximum). For conductors with finer stranding, a suitable UL listed wire ferrule must be used. The cross-section of the AC cable conductor must be sized in order to prevent accidentally disconnections of the inverter from the grid due to high impedance of the cable that connects the inverter to the power supply point. The table shows the maximum length of the cable conductor based on the cross-section. Cross-section of AC cable conductor Maximum length of the cable conductor(m) 10mm² 16 mm² 30m 50m Connecting Inverter to AC Grid When connecting the inverter to the grid, either a wye connection (three phase lines and a neutral line) or a delta connection (three phase lines) can be used. In either connection type, the ground wire connection is mandatory. 33 6 Electrical Connection User Manual Danger to human life due to high voltage existing inside the inverter! Make sure that all the DC and AC cables to the inverter are not live before you start the electrical work. To prevent electrocution hazards, all the connection operations must be carried out with the AC disconnect switch on the right side of the inverter open and locked out. For all models, connection to the AC terminal block is made by pulling conductors through a raceway connected to the AC cable knockout. Step 1 Disconnect AC circuit breaker and prevent it from reconnection inadvertently. Step 2 Loose the six screws on the lower combiner unit and remove the cover of the combiner unit. Step 3 Remove the threaded plastic plug from the AC cable knockout and replace with a conduit hub sized to fit the required wiring and raceway. Step 4 Strip off AC cables as the following indication. For conductors with finer stranding, a suitable UL listed wire ferrule must be used. Step 5 Pull AC cables through the conduit opening and connect the necessary conductors to AC pressure type terminal blocks y For Wye grid, connect Neutral, L1, L2, L3, and PE conductors. y For Delta grid, connect L1, L2, L3, and the PE conductors to the corresponding terminals on the AC Terminal Block. y Observe the AC terminal layout. Device will not work normally if the phase cable is connected to the PE terminal. y Do not squeeze or press the cable insulation layer. Improper connection may affect the normal operation of the inverter. Additionally, when using a delta connection, the unused N terminal and PE terminal must be connected with a short jumper cable (green or green/yellow) of 10AWG. 34 User Manual 6 Electrical Connection Fig. 6-2 Wye grid connection Fig. 6-3 Delta grid connection 6.4 Connecting Inverter to PV Arrays Lethal voltage exists! PV arrays produce electrical energy when exposed to light and thus can create an electrical shock hazard. Wiring should only be performed by qualified personnel. Make sure that the maximum input-ground capacity of the inverter is less than (0.12uf/kW) * 30kW/36kW, otherwise the inverter will not function properly. 35 6 Electrical Connection User Manual Before connecting the PV arrays to the inverter, make sure that the impedances between the positive terminal of the PV string and Earth and the impedances between the negative terminal of the PV string and Earth are larger than 1Mohm. There is a risk of inverter damage! The following requirements should be met; otherwise they will lead to loss of any and all warranty rights. y Make sure that the maximum short circuit current of each DC input is less than inverter allowable limit. y Make sure that the maximum open voltage of each string is less than 1000V. Voltage over 1000V can damage the inverter. 6.4.1 PV Inputs Configuration The inverter has two PV input areas DC1 input and DC2 input, each owning its MPP tracker. The two PV inputs can be configured in independent mode or parallel mode. PV Configuration Mode- Independent Mode For independent mode, the two PV inputs work independently, each with its own MPPT. Therefore the two PV inputs can be different with each other, including different PV module types, different numbers of connected in PV string, different tilt angles or orientation angle of PV modules. As shown in the following diagram, the inverter should choose independent mode due to different orientation angle between the two PV inputs. 36 User Manual 6 Electrical Connection To make sure maximum DC power can be utilized, PV strings connected to individual input area should have a homogenous structure, including the same type, the same number, identical tilt and identical orientation. Prior to connecting the inverter to PV inputs, the following electrical specifications must be met simultaneously: Total DC Power Limit DC Power Limit for Each Input Open-circuit Voltage Limit for Each Input Short-circuit Current Limit for Each Input 35000W 41000W 17500W 20500W 1000V 1000V 60A 60A Considering the negative voltage temperature coefficient of PV module, more attention should be paid to the open-circuit voltage of PV strings when designing at the lowest ambient temperature. PV Configuration Mode-Parallel Mode For parallel mode, the PV inputs can be configured in parallel inside the combiner unit. All PV strings connected to the inverter have a homogenous structure, including the same type, the same number, identical tilt and identical orientation. As shown in the following diagram, the inverter may choose parallel mode due to no difference between the two PV inputs. 37 6 Electrical Connection User Manual Prior to connecting the inverter to PV inputs, the following electrical specifications must be met simultaneously: Total DC Power Limit Open-circuit Voltage Limit for Each Input Short-circuit Current Limit for Total Input 35000W 41000W 1000V 1000V 120A 120A You should also take the negative open-circuit voltage temperature coefficient into consideration when designing the PV string. Configuration of PV Connection Mode PV configuration mode of the inverter can be performed by a switch on the configuration circuit board. y Independence mode: turn the switch ON. y Parallel mode: turn the switch OFF. 6.4.2 PV Connection Procedures Conduit entries for all versions are located on the bottom and both side of the combiner unit Make sure the appropriate conduit hub is used in order to maintain required spacing between wiring groups and ensure the integrity of the NEMA 4X environmental rating. 38 User Manual 6 Electrical Connection DC Cable Requirements Use only Copper (Cu) wire rated for 90°C (194°F), solid or with type B or type C stranding (19 strands maximum). For conductors with finer stranding, a suitable UL listed wire ferrule must be used. Cross-section Area Range Max. Withstand Voltage Max. input current for each PV string 4...6mm2 12AWG…10AWG 1000V 12A The input current of each input channel should be less than 12A, otherwise the fuse may blow out. DC Cable Connection Procedures Make sure that all the DC and AC cables to the inverter are not live before you start the electrical work. Step 1 Strip off 12mm insulation layer from all DC cables. Step 2 Disconnect the DC switch and locked out. Step 3 Configure PV configuration mode via jumper cables according to actual PV conditions. Please refer to”6.4.1 PV Inputs Configuration”. If inverter selects parallel PV configuration mode, you should connect DC1+ to DC2+ and DC1- to DC2- on the DC connection circuit board with jumper cables of cross-section not less than 6mm2 (10 AWG) as the following diagram shown. The existing cable connections are not displayed in the below diagram. 39 6 Electrical Connection User Manual DC1+ DC2+ DC1- DC2- The connection of each four ports in one terminal is equipotential. Step 4 Remove the threaded plastic plug from the AC cable knockout and replace with a conduit hub sized to fit the required wiring and raceway. Step 5 Check the connection cable of PV string for the correct polarity and that the open-circuit voltage does not exceed the inverter input limit 1000V, even under the lowest operating temperature. • Check the positive and negative polarity of the PV cells. After confirmation, you can insert the DC cables into the input terminals in the cabinet of the inverter. • For the same MPPT, reverse connection of a single string is prohibited. A permanent failure of the system or inverter may follow if otherwise. Step 6 Pull all DC cables through the conduit opening and tighten a pair of positive and negative cable ends into corresponding terminals with the torque range from 1.2Nm to 1.5Nm. Connect other DC cables following the above-mentioned procedures. 40 User Manual 6 Electrical Connection 6.5 Grounding the Inverter Because of the transformer-less design of the inverter, neither the DC positive pole nor the DC negative pole of the PV string is permitted to be grounded. 6.5.1 Grounding System Overview All non-current carrying exposed metal parts of the equipment and other enclosures in the PV power system should be grounded (e.g., PV arrays frame and inverter enclosure). Where there is only one inverter in the PV power system, connect “PE” cable to the installation ground. 41 6 Electrical Connection User Manual Where there are multiple inverters in the PV power system, connect “PE” cables of all inverters and mounting frame of PV arrays to the same copper bus bar. In this way, it will establish equipotential connection. Inverter 1 Inverter 2 Inverter n PV Arrays 1 PV Arrays 2 PE PE PE PV Arrays n Mounting Frame of PV arrays Copper Busbar Grounding Electrode Grounding of PV Power System L1L2 L3N AC Circuit Breaker Inverter L1 L2 L3 N PE AC Grounding Electrode Grounding of Inverter AC Side Fig. 6-4 Grounding for Inverter 6.5.2 Second Protective Earth Terminal The inverter is equipped with second protective earth terminal as specified in EN 50178. Second PE Terminals There are two second PE terminals on the right side of the inverter. Users may choose one to connect PE connection. 42 User Manual 6 Electrical Connection Fig. 6-5 Second PE Terminals Second PE Connection Item Description A Screw Remark M4×12mm B C D E Lock washer Washer Cable socket Yellow-green cable 16mm2(5AWG) Fig. 6-6 Connection of the Second PE Connection *The connection parts are not included in the delivery scope. 6.6 Communication Connection 6.6.1 Communication Overview The inverter operation information can be transferred via its integrated RS485 interface to a PC with monitoring software (such as SolarInfo Insight), or to data logging device (such as SolarInfo Logger). RS485 is the standard communication choice for inverter. There are communication terminals (RS485) at the bottom of the inverter. And there apply two optional connection terminals on the configuration circuit board: RS485 A/B terminal blocks and RJ45 plug in terminals. 43 6 Electrical Connection User Manual In the case of a need of terminating resistor, switch on the 120Ω terminating resistor switch, a terminating resistor will be connected between the communication cables of the inverter. Fig. 6-7 Communication related devices on the Configuration Circuit Board Before communication connection, prepare communication cable and RJ45 plug. RS485 cable’s requirements to ensure quality of communication: y RS485 shielded twisted pair cables y Shielded network cable A converter such as RS485-232 converter or SolarInfo Logger, which converts 485 to 232 signal, is needed between inverter and PC. 6.6.2 Communication System For Single Inverter Where there is only one inverter, a RS485 cable enables connection between inverter and data logging device. 44 User Manual Inverter 6 Electrical Connection Communication Connection (RS 485 A/B bus or RJ 45) RS 485 A/B bus RJ 45 Only out. Only out. Terminating Resistor No Single one For Multiple Inverters Where there is more than one inverter, all inverters can be connected to data logging device in daisy chain. The first and last inverters in the chain must be terminated with a resistor of 120Ω. The shielding layer of RS485 cable should be single-point grounded. The maximum number that inverters are connected in the daisy chain depends on converter, data logging device and other factors. Please refer to converter’s or data logging device’s manual to obtain the limit. 45 6 Electrical Connection Inverter User Manual Communication Connection (RS 485 A/B bus or RJ 45) RS 485 A/B bus RJ 45 Only out Only out Terminating Resistor Yes Inverter 1 In and Out In and Out No Inverter 2…n-1 In and Out In and Out Yes Inverter n 6.6.3 RS485 Communication Connection RS485A/B Bus Connection Step 1 Remove the threaded plastic plug from the AC cable knockout and replace with a conduit hub sized to fit the required wiring and raceway. Step 2 Lead RS485 shielded twisted pair cables through conduit opening to the configuration circuit board. Step 3 Trip off the insulating layer of the communication cables. Connect the cables to the RS485 bus terminal blocks. Step 4 According to the position of the inverter (refer to the prior section), repeat step 1…2 to connect the other RS485 cables. Step 5 Pull cables outwards to confirm whether they are fastened firmly. Step 6 According to the position of the inverter (refer to the prior section) switch ON or OFF the terminating resistor. 46 User Manual 6 Electrical Connection Step 7 If there is no other connection procedure, recover and fix the front cover of the combiner unit. Step 8 Now perform RS485 communication connection as the diagram shown above. Connect the other end of cable to other devices. Communication terminal definition is referred to device manual. Step 9 Verify the communication connection and configure the communication parameters. If there is more than one inverter to communicate with a PC or a data logger, it is crucial to configure the communication parameters of each inverter. See “10.12 Communication Parameters Setting”. SolarInfo logger and RS485-232 converter are optional parts and can be ordered from Sungrow. RJ45 Connection Step 1 Remove the threaded plastic plug from the AC cable knockout and replace with a conduit hub sized to fit the required wiring and raceway. Step 2 Lead Network cable through conduit opening to the configuration circuit board. Step 3 Use the Ethernet crimper to crimp the cables and connect cables to RJ45 plug according to TIA/EIA 568B. Step 4 Connect the RJ45 plug into the RS485 in/RS485 out terminal on the configuration circuit board. Step 5 According to the position of the inverter (refer to the prior section), repeat step1…3 to connect the other Network cables to the RS485 out/RS485 in terminal on the configuration circuit board. Step 6 Pull cables outwards to confirm whether they are fastened firmly. 47 6 Electrical Connection User Manual Step 7 According to the position of the inverter (refer to the prior section) switch ON or OFF the terminating resistor. Step 8 If there is no other connection procedure, recover and fix the front cover of the combiner unit. Step 9 As for the wires which connect to the logging devices, use the Ethernet wire stripper to strip the insulation layer and connect the RS485 A and B cables (3 and 6) to data logging device or RS485-232 converter. Communication terminal definition is referred to the device manual. Verify the communication communication parameters. connection Step 10 and configure the SolarInfo logger and RS485-232 converter are optional parts and can be ordered from Sungrow. 6.6.4 Configurable Dry Contact There are fault output dry contacts and LOCAL STOP dry contacts located on the configurable circuit board. Fault output dry contacts: The relay can be configured as fault alarm output, which can be configured by the user as either normally open contact (by using A2&A1) or normally closed contact (by using A2&NC). The relay switches when a fault occurs. The devices to be connected to the relays must comply with the related requirements: AC Requirements DC Requirements Max. Voltage: 250Vac Max. Current: 5A Max. Voltage: 30Vdc Max. Current: 5A LOCAL STOP dry contacts: The dry contacts can be configured as LOCAL STOP by using ON&ON. When the two ON terminals are short-circuited by external signal, inverter will stop running immediately. Max. Voltage Limit Max. Current Limit 250V 5A 48 User Manual 6 Electrical Connection 6.6.5 RS485-NET Converting Card (Optional) You may plug a RS485-NET converting card in CON10 and fix it on the Communication Circuit Board with the delivery screws. The RS485-NET converting card is an optional part and can be ordered from Sungrow. 49 7 Commissioning Commissioning is a critical part for a well-installed PV system, which can protect against fires, injury and electrical shock. 7.1 Inspection before Commissioning Before starting the inverter, you should check the following items. 1. Inverter unit is accessible for operation, maintenance and service. 2. Re-check that the inverter is firmly installed onto the wall. 3. Space for ventilation well is provided for one inverter or more than one inverter. 4. Nothing is left on the top of the inverter unit. 5. Inverter and accessories are correctly connected. 6. Cables are routed in safe place or protected against mechanical damage. 7. Specification of AC circuit breaker is reasonable. 8. Terminals not used underneath the inverter are sealed. 9. Warning signs & labels are suitably affixed and durable. 7.2 Commissioning Procedure If all checking items mentioned above meet the requirements, precede the following procedures to start up the inverter for the first time. Step 1 Close external AC circuit breaker. Step 2 Rotate DC switch to “ON” position. Suppose there are sufficient sunlight and enough DC power. PV arrays initialize and supply DC power to inverter. The LCD display is activated to check the validity first. If there is a defect on the display, contact Sungrow. 50 User Manual 7 Commissioning Step 3 Press j to choose country code. Confirm the settings by Pressing ENTER. Step 4 Select the country code according to the inverter’s installation country. Each country code represents corresponding local protective parameters that have been preset before delivery. Before country setting, there is warning screen. After setting the Country parameter, please proceed to set other parameters of the inverter in accordance with the specific requirements of the local grid. Before commissioning, please check thoroughly if the set parameters meet the local grid requirement. Refer to “10.11 Protective Parameters Setting” for country code explanation. If the inverter is installed where the country code is not included, please choose item “Other” and manually set the protective parameters. If the country code is not set correctly during commissioning, reset the protective parameters as dictated in “10.11 Protective Parameters Setting”. There may be faults if otherwise. Step 5 Configure grid code on the display. Press j to select grid code. Confirm the selection by Pressing ENTER. Where, LV indicates Low Voltage Grid Code; MV indicates Middle Voltage Grid Code. Step 6 When choose MV, Press h to enter the LVRT function selection, Press j to switch on or off the LVRT function and Press ENTER to confirm the selection. The Kf configure item will appear only when switching on the LVRT function. 51 7 Commissioning User Manual If the Country selected does not have the “Grid codes” directives, this configuration will not affect the following procedures. However, you may select the MV to enable/disable the LVRT function regardless of the country selected. Step 7 After configuring the Grid Code, there will be a “Pro-param” type selection screen and then corresponding sub-menu will come up. For detailed information, please refer to “10.11 Protective Parameters Setting”. Step 8 Configure time according to the local time. Time setting is very important, which directly affects data logging. Press h to move cursor and Press j to scroll up time value. Confirm the settings by Pressing ENTER. Step 9 After configuring all parameters, there will be a “setting confirmation” screen. Check whether all above-mentioned parameters are correct. Confirm by Pressing ENTER. Cancel by Pressing ESC and reset. Inverter will enter into startup process. Observe status of LED indicators and the LCD main screen. If inverter‘s commissioning succeeds, the “RUN” indicator will be lit and “RUN” will be displayed on the “State” area. Step 10 If inverter’s commissioning fails, the “FAULT” indicator will be lit and “fault” will occur on the display. Press j to view “current fault” information. Remove the existing fault and then repeat starting up inverter as the above procedures. 52 8 Disconnecting, Dismantling and Disposing the Inverter 8.1 Disconnecting the Inverter For maintenance work or any service work, inverter must be switched off. In normal operation, switching off is not necessary. In order to disconnect the inverter from the AC and DC power sources, you should proceed with the following procedures. Otherwise you will be exposed to lethal voltages or the inverter will be damaged. Step 1 Rotate the external DC switch and AC switch at the sides of the inverter to the “OFF” position and prevent them from reconnecting. Step 2 Turn off the upstream DC circuit break. Please strictly follow the above sequence. Inverter will not work normally if otherwise. Step 3 Wait about ten minutes until the capacitors inside the inverter have discharged. Step 4 Loose the six screws on the lower combiner unit and then remove the lid. Step 5 Measure AC voltage to ground at the AC terminal to confirm AC output of inverter at the AC circuit breaker is voltage free. Step 6 Loose screws to remove AC cables. Step 7 Disconnect DC cables from the inverters. 53 8 Disconnecting, Dismantling and Disposing the Inverter User Manual 8.2 Dismantling the Inverter Step 1 Remove the cap and loose the screws from the upper lid. Step 2 Lift up the upper lid slightly, release the locking part of the ribbing of the LED screen and remove the lid. Step 3 Disconnect all connection cables between the electrical cabinet and the combiner box and insert all cables in the wire mount. 54 User Manual 8 Disconnecting, Dismantling and Disposing the Inverter Step 4 Unscrew all connection screws between the electrical cabinet and the combiner box with a suitable spanner and detach the electrical cabinet from the combiner box. 55 8 Disconnecting, Dismantling and Disposing the Inverter User Manual 8.3 Disposing the Inverter Users should take the responsibility for the disposal of the inverter. Some parts and devices in the inverter, such as LCD displayer, batteries, capacitors, may cause environment pollution. Users must comply with the related local regulations to avoid causing pollution. 56 9 Troubleshooting and Maintenance 9.1 Troubleshooting 9.1.1 Troubleshooting of LED Indicator See “Tab. 2-2 Description of LED Indicator Status” for definition of LED’s states. Type of fault Troubleshooting LED indicators and LCD screen cannot be lit 1. Disconnect AC side circuit breaker. 2. Rotate DC switch to the “OFF” position. 3. Check the polarity of DC input. 1. Disconnect AC side circuit breaker. 2. Rotate DC switch to the “OFF” position. 3. Check the correctness of electrical connection of inverter. See “6 Electrical Connection”. 4. Check whether DC input voltage exceeds the inverter start voltage of inverter. 5. If all above conditions are OK, please contact with Sungrow. 1. A fault is not removed yet. 2. Perform troubleshooting in according to fault type in LCD screen. See “9.1.4 Troubleshooting of Faults in LCD Screen”. “RUN” indicator goes out “Fault” indicator is lit 3. If it cannot be solved, please contact Sungrow. “RUN” indicator is blinking “Fault” indicator is blinking and buzzer for a minute. Warning fault occurs of the inverter. Acing warning occurs of the inverter. 57 9 Troubleshooting and Maintenance User Manual 9.1.2 Arc Fault Detection Self-test Fault An auto-test circuit is included in the module design of the inverter’s AFDI function. If a DC arc fault is detected, the corresponding fault code will display on the LCD screen. Refer to “9.1.4 Troubleshooting of Faults in LCD Screen” for display fault code and description to remove fault and manually start-up the inverter. 9.1.3 DC Arc Fault If a DC arc fault is detected during normal operations, the inverter will disconnect from the AC grid. The DC arc fault is displayed on the inverter’s LCD screen and the inverter is powered off. Please check the circuit and manually remove the fault by pressing ENTER. 9.1.4 Troubleshooting of Faults in LCD Screen When faults occur, “Fault” state will be shown on the main screen. Press j to view multiple “current fault” information pages. Fault Code Description Troubleshooting 002 The grid voltage has exceeded inverter allowable upper limit. 1. Check the voltage of the grid. 2. If the grid voltage exceeds the permissible range of inverter protective parameters, ask utility grid company for solution. 3. If the grid voltage is within the permissible range, contact Sungrow Service Dept.. 003 Inverter has checked that the instantaneous sample value of the grid voltage exceeds the allowable limit for some time. 1. This is a short-term fault due to grid condition. Wait a moment for inverter recovery. 2. If the fault still exists, please contact Sungrow Service Dept.. 58 User Manual 9 Troubleshooting and Maintenance Fault Code Description 004 The grid voltage has fallen below inverter’s allowable lower limit. 005 The grid voltage is too low. 006 007 008 009 010 011 012 Troubleshooting The AC output current exceeds inverter protective limit. Inverter has checked AC overcurrent temporarily. The grid frequency has exceeded inverter allowable upper limit. The grid frequency has fallen below inverter allowable lower limit. The inverter will self-recover after several seconds. 1. Check the frequency of the grid. 2. If the grid frequency exceeds the permissible range of inverter protective parameters, ask utility grid company for solution. 3. If the grid frequency is within the permissible range, contact Sungrow Service Dept.. 1. Check whether AC circuit breaker is triggered. 2. Check whether AC cables are all firmly connected. 3. Check whether grid is not on service. 4. If all conditions are OK and this fault still occurs in the LCD screen, contact Sungrow Service Dept.. Islanding The DC component of AC current has exceeded inverter limit. Inverter has detected that there is a failure current. 013 Inverter has checked that the grid is abnormal 014 The average 1. Check the voltage of the grid. 2. If the grid voltage exceeds the permissible range of inverter protective parameters, ask utility grid company for solution. 3. If the grid voltage is within the permissible range, contact Sungrow Service Dept.. 1. This is a short-term fault due to grid condition. Wait a moment for inverter recovery. 2. If the fault still exists, please contact Sungrow Service Dept.. 1. The inverter will resume if the output current falls below the protective value. 2. If the fault still exists, please contact Sungrow Service Dept.. grid 1. Wait a moment for inverter recovery. 2. If the fault occurs repeatedly, contact Sungrow Service Dept.. 1. Check the PV strings for ground fault. 2. If the fault occurs repeatedly, contact Sungrow Service Dept.. 1. Wait a moment for grid recovery. 2. If the grid parameters exceed the permissible range of inverter protective parameters, ask utility grid company for solution. 3. If the grid frequency is within the permissible range, contact Sungrow Service Dept.. 1. Wait a moment for inverter recovery. 59 9 Troubleshooting and Maintenance Fault Code Description Troubleshooting voltage over 10 minutes is not within the permissible range. 2. If the fault occurs repeatedly, contact Sungrow Service Dept.. 015 Grid impedance has exceeded inverter’s limit 016 The AC overloads. 017 The inverter has checked that there is unbalance between the three phase voltages. 019 The bus voltage is temporarily high. 020 The bus voltage is high. 021 022 023 024 025 026 60 User Manual output Inverter has checked that there is overcurrent of PV1 input. Inverter has checked that there is overcurrent of PV2 input. PV configuration mode has changed during inverter running. Inverter has checked the deviation of neutral point voltage. Inverter has checked out the unbalance of neutral point voltage temporarily. There is high Bus fluctuation voltage. 1. Check AC cables for appropriate size. 2. Wait a moment for inverter recovery. 3. If the fault occurs repeatedly, contact Sungrow Service Dept.. 1. Wait a moment for inverter recovery. 2. If the fault occurs repeatedly, contact Sungrow Service Dept.. 1. Wait a moment for inverter recovery. 2. If the fault occurs repeatedly, contact Sungrow Service Dept.. 1. Wait a moment for inverter recovery. 2. If the fault occurs repeatedly, contact Sungrow Service Dept.. 1. Wait a moment for inverter recovery. 2. If the fault occurs repeatedly, contact Sungrow Service Dept.. Check the layout and the wiring of PV1 input. Check the layout and the wiring of PV2 input. Check the PV input configuration mode and restart the inverter when necessary. 1. Inverter will recover if the deviation value falls below the protective limit. 2. If the fault occurs repeatedly, contact Sungrow Service Dept.. 1. Inverter will recover if the deviation value falls below the protective limit. 2. If the fault occurs repeatedly, contact Sungrow Service Dept.. 1. This is a short-term fault. Wait a moment for inverter recovery. 2. If the fault still exists, please contact Sungrow User Manual Fault Code 9 Troubleshooting and Maintenance Description Troubleshooting Service Dept.. 027 036 037 038 039 040 The DC current is not balanced between the two PV inputs for parallel PV configuration mode. The temperature of module is too high The ambient temperature is too high The inverter has checked that there is a fault of relay. The insulation resistance is low. (ISO-flt) AC or DC overcurrent fault, or DC overvoltage fault. 041 There is a fault with sampling channel. 042 Current imbalance. 043 044 045 046 047 048 The ambient temperature falls below -25oC There is a fault with DC/AC inversion circuit There is a fault with PV1 boost circuit. There is a fault with PV2 boost circuit. The PV configuration mode set on the display is not in accordance with the configuration in the combiner unit. Phase-R current 1. Wait a moment for inverter recovery. 2. If the fault occurs repeatedly, contact Sungrow Service Dept.. 1. Check whether AC output power exceeds norminal power too much. 2. Check whether fans work normally and whether there are some abnormal fans. Please replace broken fan, in necessary. 3. Clean air grills of outlet. 4. If the fault still exists, please contact with Sungrow. 1. Wait a moment for inverter recovery. 2. If the fault occurs repeatedly, contact Sungrow Service Dept.. 1. Wait a moment for inverter recovery. 2. If the fault occurs repeatedly, contact Sungrow Service Dept.. 1. Wait a moment for inverter recovery. 2. If the fault occurs repeatedly, contact Sungrow Service Dept.. 1. Wait a moment for inverter recovery. 2. If the fault occurs repeatedly, contact Sungrow Service Dept.. If the fault occurs repeatedly, contact Sungrow Service Dept.. Disconnect inverter to stop. Wait for ambient temperature to rise above -25 ℃ and then start inverter again. 1. Wait a moment for inverter recovery. 2. If the fault occurs repeatedly, contact Sungrow Service Dept.. 1. Wait a moment for inverter recovery. 2. If the fault occurs repeatedly, contact Sungrow Service Dept.. 1. Disconnect inverter. 2. Re-select PV configuration mode and re-connect PV strings. For more detailed information please refer to “6.4 Connecting Inverter to PV Arrays”. 1. Wait a moment for inverter recovery. 61 9 Troubleshooting and Maintenance Fault Code User Manual Description Troubleshooting 2. If the fault occurs repeatedly, contact Sungrow Service Dept.. 070 071 072 sampling channel fault. Phase-S current sampling channel fault. Phase-T current sampling channel fault. Hardware Overvoltage/ Overcurrent protection Fans are defective. Fault with AC SPD Fault with DC SPD 073 Fuse has blown out 074 Communication fault of LCD 075 Solar irradiation is not sufficient for inverter operation. 076 PV1 overload 077 PV2 overload 078 PV1 power abnormal warning 079 PV2 power abnormal warning 087 There is a fault with the AFD block. 088 Arcing warning 089 AFD disable warning 049 050 051 62 1. Wait a moment for inverter recovery. 2. If the fault occurs repeatedly, contact Sungrow Service Dept.. Disconnect inverter and remove the broken fan. It is necessary to replace the SPD module. Contact Sungrow Service Dept.. Disconnect inverter and replace the fuses. Contact Sungrow Service Dept.. A fault has occurred in the internal communication of the inverter. However, the inverter continues feeding into the grid. Contact Sungrow Service Dept.. 1. Wait for higher irradiation. 2. If this recurs at medium irradiation, check the PV system design and correct the connection of PV inputs. Check the PV system design and correct the connection of PV1 inputs. Check the PV system design and correct the connection of PV2 inputs. 1. Check whether the PV1 input not connected or loose. 2. If all PV1 input cables are firmly attached and the warning fault still exists, please contact Sungrow Service Dept.. 1. Check whether the PV2 input not connected or loose. 2. If all PV2 input cables are firmly attached and the warning fault still exists, please contact Sungrow Service Dept.. 1. Wait a moment for inverter recovery. 2. If the fault occurs repeatedly, contact Sungrow Service Dept.. Check the associated circuit and press ENTER to remove the fault. Remove the fault by reactivating the AFD User Manual 9 Troubleshooting and Maintenance Fault Code Description 532-547 Reverse polarity warning of PVS connection. Troubleshooting function on the LCD screen. 1. Check the polarity of the PV inputs, if the polarity is reverse, please reconnect PV strings. 2. If the fault still exists, please contact with SUNGROW. 1. Check whether the PV array is shielded. If the PV array is clear and is not shielded, check whether the PV modules are faulty. 548-563 The output current of the PVS is obviously abnormal. 2. Check whether there is any DC input cable disconnected. If yes, refer to “10.13.1 PVS Detect Settings” to reset the inverter. 3. If the fault still exists, please contact with SUNGROW. 9.2 Maintenance 9.2.1 Routine Maintenance Items System clean Fans Devices check Methods Check the temperature and dust of the inverter. Clean the inverter enclosure. Check the humidity and dust of the environment. Meanwhile check whether the filter function of the air inlet is ok. Clean the air inlet and outlet, when necessary. Check whether there is crack of the fan blade Check whether there is any abnormal noise of the fan turning. Clean or replace the fans. Check the fuses and the DC SPD. Replace the fuse. Contact Sungrow to order new DC SPDs. Period Six months to a year (it depends on the dust contents in air.) Once a year Every 6 months 9.2.2 Maintenance Instruction Fans’ Maintenance There are four fans at the side of the inverter for active cooling during running operation. If the fans are dirty or out of work, the inverter may not be cooled down well and its efficiency may accordingly decrease. Therefore it is necessary to clean the dirty fans or replace the broken fans as the following indications. 63 9 Troubleshooting and Maintenance User Manual y Disconnect the inverter from the grid first and then PV arrays before any maintenance work. y Lethal voltage still exists in the inverter. Please wait for at least ten minutes and then perform maintenance work. y Fans’ maintenance work may only be performed by qualified electricians. Step 1 Disconnect the AC circuit breaker. Step 2 Rotate DC switch to the “OFF” position and then turn off the upstream DC circuit break. Step 3 Wait for at least ten minutes. Step 4 Disconnect all DC and AC connection in the reverse procedures in the “6 Electrical Connection”. Step 5 Loosen the screws as the right diagram shown. Step 6 Disassemble the metal plate slightly. Step 7 Release the locking part of four connectors by pressing on the ribbing of the locking hooks and pull outwards. 64 User Manual 9 Troubleshooting and Maintenance Step 8 Remove fans from the inverter. Step 9 You can clean the dirty fans with soft brush or vacuum cleaner. Or replace the broken fans. Step 10 Re-assemble the fans onto the inverter. Step 11 Connect the four connectors and fasten them with cable ties. Step 12 Assemble the plate by fastening the four screws. Step 13 The inverter can be put into the application again. Replacing the Fuses For optional version inverter, it is necessary to replace the blow out fuses due to overcurrent. To do so, proceed as follows: Step 1 Disconnect AC circuit breaker. Step 2 Rotate DC switch to the “OFF” position and then turn off the upstream DC circuit break. Step 3 Wait for at least ten minutes. Step 4 Open the combiner unit as described in section “8 Disconnecting, Dismantling and Disposing the Inverter”. Step 5 Check, using a multimeter, the assignment and conductivity of the fuse. A fault occurs to the related fuse if it is non-conductive. Step 6 Check the fault fuse by installer. New fuse can be ordered from Sungrow. Step 7 Remove the fuse puller by pulling the handle and replace the blown out fuse. 65 9 Troubleshooting and Maintenance User Manual Step 8 Insert the fuse puller into the fuse holder. Step 9 Close the inverter and restart the inverter. Clean Air Inlet and Outlet A huge amount of heat is generated in the process of running the inverter. The inverter adopts a controlled forced-air cooling method. In order to maintain good ventilation, please check whether there is anything blocking the air inlet and outlet. Clean the air inlet and outlet with soft brush or vacuum cleaner if necessary. 9.3 Contact Sungrow Service Should you have any problems in operating on the inverter, please contact us: Service hotline: +86 551 65327817 Email: service@sungrow.cn We need the following information to provide you the best assistance: y Type of the inverter y Serial number of the inverter y Fault code/name y Brief description of the problem 66 10 Operation of LCD Display 10.1 Description of Button Function Inverter offers two buttons for user to look up the running information and configure parameters. The two buttons have multiple functions. Please refer to Tab. 10-1 before any operation onto inverter. Tab. 10-1 Button Function Button Operation Description Press less than two seconds Move upwards or downwards, or increase the set value. Hereinafter, it is referred to as “Press j”. Return to the previous menu or cancel the command. Hereinafter, it is referred to as “Press ESC”. Move left or right, or turn pages. Hereinafter, it is referred to as “Press h”. Enter into the sub-screen or confirm the command. Hereinafter, it is referred to as “Press ENTER”. Press more than two seconds Press less than two seconds Press more than two seconds The background light of the LCD screen will go out to save power if there is no button operation for one minute. You can activate it by pressing any button. 67 10 Operation of LCD Display 10.2 User Manual Inverter Menu Structure Fig. 10-1 Menu Tree-English 68 User Manual 10.3 10 Operation of LCD Display Main Screen If the inverter succeeds in commissioning, LCD display will enter into the main screen, as shown in Fig. 10-2. Fig. 10-2 Main Screen Description No. Description 1 2 3 4 5 6 7 Power curve. x-axis: time in hours; y-axis: output power yield Pin %. Icons (refer to the Tab. 10-3) and the Inverter active power limits (P-W limits). Current output power. Energy generation during this day until now. Total energy generation since initial commissioning. Inverter state. Date (year/month/date) and time. Tab. 10-2 Inverter State Description Inverter State Run Standby Stop Key-stop Start Upd fail Fault Warning Description After being energized, the inverter tracks the PV arrays’ maximum power point (MPP) and feeds AC power to grid. This mode is the normal mode. Inverter will enter into Standby mode for insufficient input power. In this mode the inverter will wait until the DC voltage recovers. The inverter is shut down. The inverter will stop operation by manual “Stop” through LCD menu. The inverter is initializing and synchronizing with the grid. IAP (In Application Programming) update fails If a fault occurs, the inverter will automatically stop operation, trigger the AC relay and show “Fault” on the LCD with the “FAULT” indicator lit. Once the fault is removed in recovery time (set by user, see “10.10 Running Parameters Setting”), the inverter will automatically resume running. Inverter has checked out some warning information. 69 10 Operation of LCD Display User Manual Inverter State Description Dispatch Derating LCD power limitation or remote dispatch. Input overload or over-temperature. Communication between device internal control modules and HMI modules failure. Com-err If inverter is in “Fault” state, Press h /j to view multiple “Current fault” information pages. To know the meaning of the fault code, please refer to “9.1.4 Troubleshooting of Faults in LCD Screen”. Tab. 10-3 Icon Description Icon Description Inverter is in IAP update process. Inverter in power reduction state. Fans inside are working. Inverter is warning the running state. 10.4 Adjust Contrast Step 1 Press ESC to enter into the contrast adjustment screen. Step 2 Press j to increase the setting value and press h to decrease the value. Step 3 Press ENTER to confirm the contrast setting. 70 User Manual 10 Operation of LCD Display The contrast value ranges from 0 to 100. The recommended value is 50 or 60. 10.5 Detailed Running Information On the main screen, there is some basic information about the inverter. For more detailed running information, please operate as follows. Main Screen(Press ENTER)→Menu→Run-info(Press ENTER) LCD screen will show four detailed running information pages. Scroll pages by pressing h /j. “DC power input” represents the total input power of PV1 and PV2. “Vdc” indicates the DC voltage of each input. “Idc” indicates the DC current of each input. “Pdc” indicates the DC power of each input. “Indep / Paral mode” is the PV configuration mode of the two PV inputs. √ indicates the corresponding input is at work. “P-W” is inverter output active power. “S-Va” is inverter output apparent power. “Country” is inverter selected country code. “Grid code” is inverter selected grid code. “Vac” is phase voltage. “Iac” is phase current. “Pac” is AC output of each phase. “F” is frequency of each phase. “CO2-reduce” indicates total CO2 emission reduction due to the inverter. “E-month” is the energy generation in this month. “h-Total” is the total running hours of the inverter. “T-today” is today running time of the inverter. “Temp” is the internal temperature of the inverter. 71 10 Operation of LCD Display User Manual All DC inputs current will be displayed on the screen. 10.6 History Records 10.6.1 Running Information Records Main Screen(Press ENTER)→Menu(Press j)→His-record(Press ENTER) →Run-record(Press ENTER) On the “Run-record” display, press j to select the date you want to view. Confirm by pressing ENTER. Inverter shows historical running information pages. Scroll pages by pressing j. Change to the next record by pressing h. 10.6.2 Fault Records Main Screen(Press ENTER)→Menu(Press j)→His-record(Press ENTER, Press j) →Flt-record(Press ENTER) Inverter shows fault record pages. Scroll pages by pressing j. 72 User Manual 10 Operation of LCD Display The inverter can only store at most 10 latest fault records. 10.7 Start and Stop Inverter Main Screen(Press ENTER)→Menu(Press j×2)→Start/Stop(Press ENTER) Press j to choose “Start”/”Stop” and press ENTER to confirm the choice. Press ENTER to confirm. 10.8 Input Parameter Settings Password The parameter settings are protected by the password. If you want to set the inverter’s parameters, you have to input the correct password. Step 1 Press ENTER to enter into “Menu” screen. Step 2 Press j to move the cursor to “Set-param” menu item and confirm by pressing ENTER. Step 3 A password confirmation screen will occur. Press h to move cursor right and Press j to input the password 111111. 73 10 Operation of LCD Display User Manual Step 4 Press ENTER to confirm the password and .enter the “Set-param” sub menu. 10.9 System Parameters Setting 10.9.1 Time Setting If there is deviation between the time on inverter main screen and your local time, you should perform the operation time setting. Otherwise the inverter data logging will fail. Clock is 24-hour format. Main Screen(Press ENTER)→Menu screen(Press j×3) →Set-param(Press ENTER)→ Enter password(Press ENTER)→Sys-param(Press ENTER, Press j)→Time(Press ENTER) On the “Time” screen, Press h to move the cursor right and Press j to set the correct date and time. Confirm settings by pressing ENTER. 10.9.2 Energy Deviation Adjustment If the accumulative value of “E-total” in the inverter is different from the value in the external metering device, you should adjust the “Energy-adj”. Main Screen(Press ENTER)→Menu screen(Press j×3)→Set-param(Press ENTER)→ Enter password(Press ENTER)→Sys-param(Press ENTER, Press j×2)→Energy-adj(Press ENTER) On the “Energy-adj” screen, Press h to move cursor right and Press j to set the correct offset value. Confirm settings by pressing ENTER. The positive symbol “+” can be changed to the negative symbol “-”. The adjustment range is from -9999 to +9999 kWh. (Energy-adj value)= (Real measured value)-(E-tot reading value). 74 User Manual 10 Operation of LCD Display 10.9.3 Load Default All history information will be unrecoverable cleared and all parameters will return to the default value except the protection parameters and time once the “load default” operation is performed. Main Screen(Press ENTER)→Menu screen(Press j×3)→Set-param(Press ENTER)→ Enter password(Press ENTER) → Sys-param(Press ENTER, Press j×3) → Load default(Press ENTER) A password confirmation screen will occur. Press h to move cursor right and Press j to input the password 111111. Press ENTER to confirm “load default”. 10.9.4 Firmware Version Main Screen(Press ENTER )→Menu screen(Press j×3)→Set-param(Press ENTER) → Enter password(Press ENTER) → Sys-param(Press ENTER, Press j×4 )→Firmware version (Press ENTER) Inverter shows detailed firmware information, including LCD version and DSP version. The firmware version information is read only. 75 10 Operation of LCD Display 10.10 User Manual Running Parameters Setting 10.10.1 Main Menu of Run-param Main Screen(Press ENTER )→Menu screen(Press j×3)→Set-param(Press ENTER)→Enter password(Press ENTER, Press j)→Run-param(Press ENTER) On the “Run-param” screen, Press j to move arrow to one item and Press ENTER to start this item setting. For each item setting, Press h to move cursor right and Press j to set the appropriate value. Confirm by Pressing ENTER. Tab. 10-4 Specification of Running Parameters Parameter Explanation Standby time Recover time P-W limits Q-Var switch The time from inverter initialization to inverter feeding power to grid. The time from the fault is cleared to inverter feeding power to grid. Inverter active power limits. Whether to start inverter reactive power adjustment function. PF Power factor +1.000 Q-Var limits Inverter reactive power limits 0.0% 76 Default Range 20s 20…255s 30s [IT: 300s] 100.0% [Pf] 0…900s 0...100% [Pf] / [Qt] / [Off] / [Q(P)] / [Q(U)] -1.000…-0.800 / +0.800…+1.000 0...+100% / 0…-100% User Manual 10 Operation of LCD Display 10.10.2 Reactive Power Regulation The inverter provides reactive power regulation function. Use the “Q-Var switch” parameter to activate this function and select proper regulation mode. Mode Explanation Pf Qt Off The reactive power can be regulated by the parameter PF (Power Factor). The reactive power can be regulated by the parameter Q-Var limits (in %). The PF is limited to +1.000, and the Q-Var limits is limited to 0.0%. “Pf” Mode The reactive power can be regulated by the parameter PF on the Run-param screen. “Qt” Mode The reactive power can be regulated by the parameter Q-Var limits (in %) on the Run-param screen. “Off” Mode The PF is limited to +1.000, and the Q-Var limit is limited to 0.0%. 10.10.3 Save P/Q-set On the “Save P/Q-set” screen, Press j to move arrow to one item, Press h to move cursor right and Press j to set. Confirm by Pressing ENTER. Select “Y” to save up the values set when power down. Select “N” to restore default values when power down. Parameter Explanation P-W limits Inverter active power limits configuration. Inverter reactive power configuration, includes Q-Var switch, PF and Q-Var limits. Q-Var set 77 10 Operation of LCD Display 10.11 User Manual Protective Parameters Setting Protective parameters are designed for the limit value that can trigger the protective functions of the inverter. Main Screen(Press ENTER )→Menu screen(Press j×3)→Set-param(Press ENTER)→ Enter password(Press ENTER, Press j×2)→Pro-param(Press ENTER) A password confirmation screen will occur. Press h to move cursor right and Press j to input the password. Please ask Sungrow or your dealer for this password. To make protective parameters setting convenient, inverter provides country code selection. The protective parameters have been configured before delivery according to different countries utility grid requirements. Choose the correct country code by Press j and Press ENTER to confirm. The description of country code is illustrated below: Country Code Full Name Language CA US Other Canada United States Country not included above English English English Confirm by pressing ENTER after country code selection. Choose grid code according to actual grid condition. Note: “LV” represents Low Voltage Grid Code, and “MV” represents Middle Voltage Grid Code. When choose MV, Press h to enter the LVRT function selection, and the Kf configure item will appear. Press j to switch on or off the LVRT function and Press ENTER to confirm the selection. The Kf configure item will appear only when switching on the LVRT function. Note: If the Country selected does not have the “Grid codes” directives, the following procedures will not be affected. However, you may select the MV to enable/disable the LVRT function regardless of the country selected. 78 User Manual 10 Operation of LCD Display Press j to select protective parameter type. Press ENTER to confirm the selection. Single-stage Protective Parameter If the selected protective parameter type is “Single-stage”, the following sub-menu will come up. Press j to select parameter, Press h to move cursor right and Press j to set the appropriate value. Confirm settings by Pressing ENTER. Tab. 10-5 Single-stage Protective Parameter Explanation Parameter Explanation Max-V.grid Min-V.grid Max-Fgrid Min-F.grid Grid over-voltage value Grid under-voltage value Grid over frequency value Grid under frequency value Multi-stage Protective Parameter If the selected protective parameter type is “Multi-stage”, the following sub-menus will come up. Press j to select parameter, Press h to move cursor right and Press j to set the appropriate value. Confirm settings by Pressing ENTER. 79 10 Operation of LCD Display User Manual Tab. 10-6 Multi-stage Protective Parameter Explanation Parameter Max-V. prot Explanation Ⅰ-Max-V. grid Stage Ⅰ Grid over-voltage (U>) Ⅰ-Max-V. time Stage Ⅰ Grid over-voltage (U>) tripping time Ⅱ-Max-V. grid Stage Ⅱ Grid over-voltage (U>>) Over-voltage protection Ⅱ-Max-V. time Stage Ⅱ Grid over-voltage (U>>) tripping time Min-V. prot Under-voltage protection Ⅰ-Min-V. grid Stage Ⅰ Grid under-voltage (U<) Ⅰ-Min -V. time Stage Ⅰ Grid under-voltage (U<) tripping time Ⅱ-Min -V. grid Stage Ⅱ Grid under–voltage (U<<) Ⅱ-Min -V. time Stage Ⅱ Grid under–voltage (U<<) tripping time Max-F. prot Over-frequency protection Ⅰ-Max-F. grid Stage Ⅰ Grid over-frequency (f>) Ⅰ-Max-F. time Stage Ⅰ Grid over-frequency (f>) tripping time Ⅱ-Max-F. grid Stage Ⅱ Grid over-frequency (f>>) Ⅱ-Max-F. time Stage Ⅱ Grid over-frequency (f>>) tripping time Under-frequency protection Min-F. prot Ⅰ-Min-F. grid Stage ⅠGrid under-frequency (f<) Ⅰ-Min -F. time Stage Ⅰ Grid under-frequency (f<) tripping time Ⅱ-Min -F. grid Stage Ⅱ Grid under-frequency (f<<) Ⅱ-Min -F. time Stage Ⅱ Grid under-frequency (f<<) tripping time Confirm settings by pressing ENTER and enter the “Setting confirmation” screen. Check all above-mentioned parameter settings. Confirm them by pressing ENTER. Cancel by pressing ESC and reset. When the Country or the Grid code or LVRT switch mode is changed, the protective settings will be unavailable unless the inverter is re-energized. 80 User Manual 10.12 10 Operation of LCD Display Communication Parameters Setting Main Screen(Press ENTER )→Menu screen(Press j×3)→Set-param(Press ENTER)→ Enter password(Press ENTER, Press j×3)→Com-param(Press ENTER) Press h to move cursor right and Press j to set the appropriate value. Confirm settings by Pressing ENTER. The range of communication address is 1...247. 10.13 Advanced Parameters Setting Advanced parameters are designed for PV strings current abnormal condition detection and arcing faults detection that can trigger the protective functions of the inverter. 10.13.1 PVS Detect Settings Main Screen(Press ENTER )→Menu screen(Press j×4)→Advanced Settings(Press ENTER) → Enter password(Press ENTER) → Advanced Settings(Press ENTER) → PVS Detect Settings A password confirmation screen will occur. Press h to move cursor right and Press j to input the password 111111. PVS Detect represents the PV strings current abnormal conditions detection. Press ENTER to confirm. Press j to select PVS Detect function settings. Press ENTER to confirm the selection. 81 10 Operation of LCD Display User Manual When the PV inputs are changed, the corresponding “fault” state will be shown on the main screen. You can perform the PVS Detect Reset function to re-detect the PV input strings number. 10.13.2 AFD Settings Main Screen(Press ENTER )→Menu screen(Press j×4)→Advanced Settings(Press ENTER)→Enter password(Press ENTER)→Advanced Settings(Press j, Press ENTER)→ AFD Settings A password confirmation screen will occur. Press h to move cursor right and Press j to input the password 111111. AFD Detect represents the arcing faults detection. Press ENTER to confirm. Press j to select AFD function settings. Press ENTER to confirm the selection. When you choose AFD Self-test, the results of the self-test will show on the LCD screen. If the self-test result is OK, the inverter will continue to AC grid connection. 82 User Manual 10 Operation of LCD Display If a potential problem on the AFD board is detected, the self-test will result in fault. 83 11 Appendix 11.1 Technical Data Parameters Input Side Data SG30KU SG36KU Max. PV input power Max. input voltage Startup voltage Nominal input voltage MPP voltage range MPP voltage range for nominal power No. of MPPT(s) Max. number of PV strings per MPPT Max. PV input current(DC1/DC2) Max. input current for input connector Short-circuit current of PV input 34100W 1000Vdc 300V 710V 280...950Vdc 480...850Vdc 2 5 33A*2 12A 60A*2 41000W 560...850Vdc Output Side Data Nominal AC output power Max. AC output power(PF=1) Max. AC output apparent power Max. AC output current Nominal AC voltage AC voltage range Number of Phases Normal output frequency Grid frequency range 30000W 36000W 33240W 39800W 33240VA 39800VA 40A 48A 480Vac 422...528Vac 3Ø/3W or 4W+Ground 60Hz 57...63Hz THD < 3 % (at nominal power) DC current injection <0.5%In Power factor >0.99 default value at nominal power (adj. 0.8 overexcited...0.8 underexcited) Protection Anti-islanding protection LVRT AC short circuit protection Leakage current protection DC switch DC fuse 84 Yes Yes Yes Yes Integrated Integrated Parameters Overvoltage protection AC switch SG30KU SG36KU Type III surge arrester (Optional Type II DIN rail surge arrester) Optional System data Max. efficiency CEC efficiency Isolation method Ingress protection rating Night power consumption Operating ambient temperature range 98.5% 98.0% Transformerless NEMA4X <1W -25...+60℃ (>45℃ derating) Display Communication DC connection type AC connection type -13…+140℉(>113℉ derating) 0...100% Smart forced air cooling 4000m (>3000m derating) 13123ft(>9842ft derating) Graphic LCD RS485 Screw terminals Spring clamp terminal Certification cCSAus Safety and EMC Standard UL 1741, IEEE 1547, IEEE1547.1,CSA C22.2 107.1-01-2001,FCC Part 15 Sub-part B Class B Limits Allowable relative humidity range Cooling method Max. operating altitude Mechanical Data Dimensions (W×H×D) Mounting method Weight 622×880×250mm 25" × 34.6" × 9.8" Wall bracket or Floor bracket 65kg 85 11.2 Grid Over-/Under-voltage Parameter Voltage(at PCC) Trip time(s) V<50% 0.16 50%≤V<88%(adjustable) Adjustable 0.16 to 2 88%≤V≤110%(adjustable) Normal operation 110%<V<120% Adjustable 0.16 to 1 V>120% 0.16 11.3 Grid Over-/Under-frequency Parameter Frequency range(Hz) Clearing time(s) >60.5 < {59.8-57.0} (adjustable set point) <57.0 0.16 11.4 86 P-Q Curve Adjustable 0.16 to 300 0.16 11.5 Automatic Power Derating In order to maintain safe inverter operation under adverse environmental conditions or due to improper input voltages, the unit automatically reduces the amount of power it feeds to the grid. 11.5.1 Temperature-related Power Derating Operating parameters, such as input voltage, grid voltage and power available from the photovoltaic arrays can affect the power derating caused by ambient or inverter temperature. The following graph shows the automatic reduction in output power in relation to ambient temperature. 87 11.5.2 Input Voltage-related Power Derating The following graph shows the automatic reduction in output power when the input voltage exceeds the threshold value. 88 11.6 Exclusion of Liability The content of these documents is periodically checked and revised, please contact us or check our website www.sungrowpower.com for the latest information. Discrepancies cannot be excluded. No guarantee is made for the completeness of these documents. Please contact our company or distributors to get the latest version. Guarantee or liability claims for damages of any kind are excluded if they are caused by one or more of the followings: y Inappropriate use or install of the product y Installing or operating the product in an unintended environment y Ignoring relevant safety regulations in the deployment location when installing or operating the product y Ignoring safety warnings and instructions contained in all documents relevant to the product y Installing or operating the product under incorrect safety or protection conditions y Altering the product or supplied software without authority y The product faults due to operating attached or neighboring devices beyond allowed limit values y Damages caused by irresistible natural environment The use of supplied software produced by Sungrow Power Supply Co., Ltd. is subject to the following conditions: y Sungrow Power Supply Co., Ltd. rejects any liability for direct or indirect damages arising from the use of the SolarInfo software. This also applies to the provision or non-provision of support activities. y Using the SolarInfo software for commercial purposes is prohibited. y Decompiling, decoding or destroying the original program, including SolarInfo software and the embedded software, is prohibited. 89 11.7 About Us Sungrow power supply is a China-leading manufacturer of various power electronics products for renewable energy generation systems. Our products include converters, inverters, battery chargers and other power supplies for distributable generation system in both grid-connected and stand-alone applications. The power rating of Sungrow products covers from hundred watt to mega-watt systems. The vision of Sungrow is to help our customers acquire stable and clean power with minimum cost, maximum reliability and enhanced safety. Contact Information Should you have any question about this product, please contact us. Company: Website: Email: Address: Zip: Telephone: Fax: Sungrow Power Supply Co., Ltd. www.sungrowpower.com info@sungrow.cn, service@sungrow.cn No.1699 Xiyou Rd., New & High Technology Industrial Development Zone, Hefei, P. R. China. 230088 +86 551 6532 7834, +86 551 6532 7845 +86 551 6532 7856 Canada Add: 895 Edgeley Blvd, Vaughan, ON L4K 4V9 Toll-Free Inquiry: +1 855 760 8618 Tel: Fax: Business: After-Sales Website: +1 905 760 8618 +1 905 760 1158 info@sungrow.ca, service@sungrow.ca www.sungrow.ca U.S.A Add: 47751 Fremont Blvd., Fremont, CA 94538 Tel: +1 510 324 6125 Mobile: Email: Website: +1 905 760 1158 sales@sungrow.ca www.sungrow.ca 90 Sungrow Power Supply Co., Ltd. Add: No.1699 Xiyou Rd.,New & High Technology Industrial Development Zone, 230088,Hefei, P. R. China. Post Zip: 230088 Web: www.sungrowpower.com Tel: +86 551 6532 7834/6532 7845 E-mail: info@sungrow.cn Fax: +86 551 6532 7856 Specifications are subject to changes without advance notice.