2012 International Conference on Lightning Protection (ICLP), Vienna, Austria Lightning Protection Practice for Large-Extended Photovoltaic Installations Dr. Nikolaos Kokkinos Dr. Nicholas Christofides Research and Development Department Elemko SA Athens, Greece nkokkinos@elemko.gr Department of Electrical Engineering. Frederick University Nicosia, Cyprus n.christofides@frederick.ac.cy Dr. Charalambos Charalambous Department of Electrical and Computer Engineering. University of Cyprus Nicosia, Cyprus cchara@ucy.ac.cy Abstract— This paper aims to analyse the lightning protection system (LPS) of an isolated large and extended Photovoltaic (PV) installation park. The area where the PV plant operates is characterised by the high ground flash density (25 thunderstorm days per year) and the extremely high soil resistivity value (i.e. pure rock with a resistivity of more than 2000m). The paper includes the LPS system design after experimental testing results, which were performed in the laboratory. It also includes solutions to some difficult overcoming problems that were faced during the application of the lightning protection design. The main objective of this on-going work is to address the issues necessary to form a global framework for the lightning protection system (LPS) design of isolated large and extended photovoltaic installations - PV parks. In particular, this paper describes the preliminary work on LPS system designs with particular emphasis on experimental testing that is performed at ELEMKO’S H.V laboratory in Greece. This work aims in framing proposals and solutions to overcome challenges and problems that may rise during the installation of lightning protection designs. II. Keywords-Photovoltaic park, Lightning protection system I. INTRODUCTION In a country like Greece where the sun is shining for most of the year round, the number of photovoltaic (PV) installations has been significantly increasing during the last years. Nowadays, the interest and investment in large scale PV parks in the MWp range is becoming very common. The knowledge however of a proper lightning protection system (LPS) design and installation, including surge protection, for such large and extended structure areas (with long cabling loops) is still under research. This is the reason for the development of the new CENELEC document; TS 50539-12: 2009 [1] describing application principles of surge protection in PV installations. The investments in such large scale PV parks are considerable and it is merely common sense that investors should choose to adopt a LPS for their systems. When compared to the income losses incurred due to a failure or damage resulting from a lightning strike, not to mention the technical and practical difficulties associated with the repairs or component replacements, the cost of a LPS system is negligible. It is therefore advisable, not to say self-evident, that a LPS is necessary. SITE SURVEY The particular PV park under study is installed on a mountain peak, flat area, occupying a total surface of around 115,000m2. In total it contains 180 DC/AC inverters of 11kW nominal power, operating at 800VDC and 7,300 solar panels of 270Wp nominal power with dimensions of 2m x 1m each. The PV park is connected to the 21kV medium voltage (MV) distribution system via 8 substations (MV/LV). The soil was rocky (>2000Ωm) and the support structure of the PV panels was a combination of concrete reinforced bases embedded in soil and aluminium supports above soil. III. INITIAL LIGHTNING PROTECTION SYSTEM DESIGN CONSIDERATIONS Due to the high resistivity of the soil, which was not promising for an effective earthing system and in conjunction with the high ground flash density of the area, the design of the lightning and surge protection was considered of high priority. Due to the extensive area coverage of the PV park, the design of the external LPS considered both possible cases, the one for an isolated application as well as the one for a non-isolated application design, as per IEC 62305 – 3 [2]. Fig. 1 and Fig. 2 illustrate the 2 cases considered when designing the LPS. In Fig. 1, for the non-isolated case, the air terminals for every 2 consecutive rows are connected to one to one electrode installed between the 2 rows. In this scenario, it is advised that the distance between the PV frame of each row and the earth electrode does not exceed 3m. Fig. 2, illustrates the isolated case, where the air-terminal of each PV row is connected to a separate electrode directly and not through the PV framework. Each PV frame is also bonded on the same earth electrode but with independent bonding conductors. In addition, the PV park under study was designed utilizing small 11kW inverters and not central inverters. Therefore, the DC cable loop was small and there was no need to use T1+T2 SPDs on the DC side of the inverter even for the non-isolated LPS case. Fig. 4, illustrates the installation of T2 only type SPDs on the DC side resulting from the fact that the lightning loop formation is limited or non-existent. 1 3 2 4 Figure 3. Acceptable materials for earthing system depending on the type of foundation used for the PV framework ≤ 3m ≤ 3m Figure 1. Design of Type B earth electrode using non-isolated LPS. The airterminals of 2 consecutive PV rows are connected to 1 electrode which is installed between them TABLE 1. DETAILED DESCRIPTION OF MATERIALS DEPICTED IN FIG. 1 Type of Foundation of the PV Allowed material for earthing framework system driven into the soil Galvanized steel profile directly 1 Galvanized steel, Stainless steel buried into the soil Steel profile embedded in Copper coated steel, Copper, 2 concrete Stainless steel Reinforced concrete block placed Galvanized steel, Copper coated 3 at ground level not into the soil steel, Copper, Stainless steel Reinforced concrete foundation Copper coated steel, Copper, 4 into the soil Stainless steel Note 1: Copper conductor may also be tinned Note 2: Aluminum is not allowed to be used into the soil ≤ 3m L L L N L L L N SPD SPD Uoc=1000Vdc SPD UC=275Vac SPD UC=275Vac Ιn=15κΑ (8/20μs) SPD UC=255Vac Ιn=15κΑ (8/20μs) Ιn=20κΑ (8/20μs) Ιmax=40κΑ (8/20μs) Ιmax=40κΑ (8/20μs) Ιmax=40κΑ (8/20μs) Ιmax=40κΑ (8/20μs) Up = <1.9kV Ta = <25ns T2 For PV system installations in open fields, in order to minimize the cost and at the same time increase the efficiency and life time of the earthing system (by avoiding electrochemical corrosion) it is very important that during the design the type of foundation used for the PV façade – framework is taken into consideration. In this particular project, the foundation material was reinforced concrete buried into the soil, therefore copper coated and solid copper earth electrodes were used. Fig. 3 and Table 1, depict information about the selection criteria of the materials used for the earthing system, depending as mentioned above, on the type of the foundation used for the PV framework or structures. SPD UC=275Vac Up = <1.9kV Ta = <25ns CE 40GT2 SPD UC=275Vac Ιn=15κΑ (8/20μs) T2 Up = <1.9kV Ta = <25ns CE T2 40T2 Ιn=15κΑ (8/20μs) Up = <1.9kV Ta = <25ns CE T2 40T2 Ιn=20kΑ (8/20μs) Uoc=1000Vdc Uc=500Vdc Ιn=20kΑ (8/20μs) UC=255Vac Ιmax=40kΑ (8/20μs) Ιmax=40kΑ (8/20μs) Ιmax=40kΑ (8/20μs) Ιn=20κΑ (8/20μs) Up = <4kV Up = <4kV Up = <4kV T2 CE T2 CE T2 CE PV - 1000T2 PV - 1000T2 PV - 1000T2 Up = <1.2kV Ta = <100ns CE T2 40T2 PE Uc=500Vdc Ιn=20kΑ (8/20μs) SPD UC=275Vac Ιn=15κΑ (8/20μs) Ιmax=40κΑ (8/20μs) Ιmax=40κΑ (8/20μs) Ιmax=40κΑ (8/20μs) Ιmax=40κΑ (8/20μs) Up = <1.2kV Ta = <100ns CE T2 40T2 CE 40GT2 + PE AC electric panel board For the isolated LPS it was necessary to provide an earth electrode behind each PV row so as to earth the isolated air terminals directly. For the non-isolated case however, an earth electrode for every 2 consecutive PV rows was necessary, combining the earthing of the air-terminals. Up = <1.9kV Ta = <25ns CE T2 40T2 AC electric panel board Figure 2. Design of Type B earth electrode using isolated LPS. Each isolated air terminal is connected to a separate electrode directly and not through the metal PV framework Up = <1.9kV Ta = <25ns CE T2 40T2 ≈1m PE DC Junction Box SPD UC=275Vac SPD Uoc=1000Vdc Uc=500Vdc SPD Ιn=15κΑ (8/20μs) _ String 1 String 2 >10m Common earthing system Figure 4. Installation of SPDs for PV application inside a junction box situated at a distance >10m from the inverter at the DC & AC side. Only T2 SPDs are needed on the DC side since there is no lightning loop formation. On the AC side however, T1 + T2 type SPDs are required due to the cable loop, which may allow the lightning current to flow in a parallel path to earth AC Input DC & AC Termination Set String 1 SURGE PROTECTION 8899kWhr DC Input PV Generators Inverter kW Meter String 2 DC Output AC Output Figure 5. DC & AC termination set for optimum protection of the inverter against surges arriving either from the AC or DC cabling Figure 6. Effect on the extended wiring of an open field large PV system installation due to a direct or indirect lightning strike For the effective protection of the inverters, a combined protection was developed allowing a combined termination of all DC & AC cables and at the same time providing protection from coupled surges. By using such a combined termination set, the cable lengths are kept to an absolute minimum. However, such a combination should fulfill certain standards [3-7] since coexistence of DC and AC at relative high voltages requires specific isolation distances. Fig. 5, illustrates this arrangement, where 1 termination box is used for both DC and AC cable terminations IV. EXAMINED CASE STUDIES Due to the extensive and long cable loops which are formed by the DC cables, any direct or nearby lightning will cause high induced surges, Fig. 6. Since screening of the DC cables is difficult to provide for in large PV parks, the question that arises is which external LPS provides a more suitable and more effective protection against over-voltages induced on the cables. A scaled down experiment was performed in the laboratory in order to obtain measurements and information that would assist in the external LPS design of the 2MWp PV park under study. The purpose of the laboratory tests was to evaluate the performance and apply it later on. The scaled down version of the experimental setup in the laboratory was a 2kWp PV system depicted in Fig. 7. The system consists of 9 PV modules connected in series giving a total of 200V output voltage and 10A current. During the impulse experiments the laboratory lights were switched off in order to have zero volts at the DC cable loop, which was approximately 18m long. Figure 7. PV panels tested in the laboratory and the formation of the DC cable loop (red +ve and black –ve) The initial purpose of the test was to investigate which of the following two possible cases would give a lower induced voltage across the DC cable loop of the string. In case A the impulse current was injected directly on the framework of the PV panels through an air termination rod, which was supported on the edge of the PV support framework. In case B the impulse current was injected directly on the on an isolated air termination rod, which was supported on the laboratory floor at a distance of approximately 700mm from the PV support framework. The results are summarized in Fig. 8, Fig. 9 and Fig. 10. α Case Α ≈ 25% Isolated LPS at a distance of 0,7m behind the steel frame of the PV structure. The lightning current is driven to earth via a dedicated rod and down conductor. The metallic structure of the PV is only connected to the LPS via the earth. Case Β α Non isolated LPS, the lightning current is distributed along the metallic frame of the PV structure. The metallic structure is used a natural down conductor. T1+T2 SPDs for the DC was not mandatory. Furthermore, due to the fact that the earthing system arrangement was a cost effective solution for the non-isolated case compared with the isolated LPS case, the investor decided to use a non-isolated LPS for the particular Photovoltaic park. V. CONCLUSIONS 100% Figure 8. Examining the behavior of isolated and non isolated LPS in case of a direct lightning strike and the effect of inducted over-voltages in the DC cabling of a PV installation The design of a lightning protection system for large scale PV systems may depend on various factors and parameters. It is very important to take into consideration the installation arrangement and design adopted for large scale PV parks as it involves crucial parameters that must be taken into consideration for the effective external and internal LPS design. There are numerous large scale PV system designs all of which require a LPS that satisfies the unique, in some times, conditions present. α Case Α ≈ 25% 1 1 The open circuit voltage across the (+) and (-) negative pole of the string was 82V and the injected current was 100kA (10/350μs). Figure 9. Experimental results of scaled down experiment examining the behavior of a non-isolated LPS with respect to the induced over-voltages on the DC cabling of a PV string α Case Β 100% 1 1 The open circuit voltage across the (+) and (-) pole of the string was 390V and the injected lightning current 100kA (10/350μs). It was almost 480% than the non isolated case. This is due to the reason that the current was not distributed but driven 100% through one path creating a high magnetic field. Figure 10. Experimental results of scaled down experiment examining the behavior of an isolated LPS with respect to the induced over-voltages on the DC cabling of a PV string The results show that the non-isolated LPS will provide lower induced over-voltages on the cabling in case of a direct lightning strike. Additionally, since small inverters were used (therefore no parallel path for the DC to earth) the need of The need of an efficient lightning protection system is mandatory for photovoltaic installations by virtue of its preventing nature. Primarily, the need is imperative to prevent any physical damage to structures and life hazards. It is worth noting that the damage of the electrical and/or electronic equipment of a PV installation, due to surges originates from Lightning Electromagnetic Impulse (LEMP) as well as from Switching Electromagnetic Impulse (SEMP) [8]. However, literature survey reveals that there is still very little information published regarding the design of lightning and surge protection for large and extended PV installations. In particular, reference [9] comprehensively covers the related scientific background by emphasizing on the aspects of standardisation that should be addressed in the near future. As quoted, the current practice, for protecting PVIs from lightning surges, rests with adopting (partly) protective measures described in standards for conventional low-voltage power distribution systems. It is vital that the LPS provide an effective protection against direct or indirect lightning strikes in order avoid the destructive effects of lightning. As previously mentioned, the investment cost is very considerable and 1 thunderstorm can be catastrophic with inestimable financial consequences. The results presented in this paper propose the most cost effective and technically correct solution for the LPS design of the large scale photovoltaic system under study. The need however, for deeper and more detailed analysis is required so that amendments are made to the current standard in order to include guidance and regulations for common large scale PV installation practices and examples. ACKNOWLEDGMENT The authors wish to thank the engineering team of BIOSAR SA (GREECE) for their contribution to the photovoltaic park project. REFERENCES [1] [2] [3] [4] [5] [6] [7] [8] [9] TS 50539-12:2009, Protection of PV installation against overvoltages IEC 62305 – 3:2010, Protection against lightning Part 3: Physical damage to structures and life hazard EN 60439-1: Low voltage switchgear and controlgear assemblies – Part 1: Type tested and partially type tested assemblies. EN 60439-3: Low voltage switchgear and controlgear assemblies – Part 3: Particular requirements for low voltage switchgear and controlgear assemblies intended to be installed in places where unskilled persons have access for their use – Distribution boards HD 60304-7-712: Electrical installations of buildings – Part 7-712: Requirements for special installation locations – Solar photovoltaic (PV) power supply EN 60664-1: Insulation co-ordination for equipment within low voltage systems – Part 1: Principles, requirements and tests EN 62446:2009: Grid connected photovoltaic systems – Minimum requirements for system documentation, commissioning tests and inspection. IEC – 62305 “Protection against Lightning” Jesus C. Hernandez, Pedro G. Vidal, Francisco Jurado, “Lightning and Surge Protection in Photovoltaic Installations’’, IEEE Transcactions on Power Delivery, Vol. 23, No 4. Oct. 2008 pp. 1961-1971.