West Bengal State Electricity Distribution Company Limited (A Government of West Bengal Enterprise) (I T & Communication Cell) Vidyut Bhavan,3rd Floor, C&D Block, Bidhan Nagar, Block-DJ, Sec-II, Kolkata-700091 Phone No.033-2358-9665, FAX No.033-2337-2427, 033-2358-9244 Website: www.wbsedcl.in, e-mail: itcell@wbsedcl.in CIN: U40109WB2007SGC113473 WBSEDCL e-TENDER NOTICE (LOCAL COMPETITIVE BIDDING) BID DOCUMENT Comprehensive Annual Maintenance Contract (CAMC) of Data Center Infrastructure for Central Data Center Rajarhat and Disaster Recovery Center, Berhampore, WBSEDCL. Cost of Bid Document : Rs.9000/- Tender Notice No: IT&C/80/584 1074 25.05.2015 Dated:10.09.2015 Comprehensive AMC for Data Center Infrastructure of Rajarhat Data Center & Berhampore Disaster Recovery Center, WBSEDCL: Tender Notice No. : IT&C/80/584 dated.10.09.2015 Page 1 CONTENTS SL. No. Description Page 1. DEFINATION &ABBREVIATION 2 2. INSTRUCTION TO BIDDER (IB) -- SECTION I 3—15 3. SCOPE OF WORK -- SECTION II 16--23 4. GENERAL CONDITIONS OF CONTRACT (GCC) -- SECTION III 24–27 5. FORMS OF BID -- ANNEXURE I, II, IIA, IIB, IIC, III, IVA, IVB, V, VI. 6. EQUIPMENTS LIST -- ANNEXURE VIIA, VIIB, VIIC,VIID, VIIE,VIIF . 7. CORRECTIVE MAINTENANCE PROFORMA- ANNEXURE VIII. Comprehensive AMC for Data Center Infrastructure of Rajarhat Data Center & Berhampore Disaster Recovery Center, WBSEDCL: Tender Notice No. : IT&C/80/584 dated.10.09.2015 Page 2 DEFINATIONS & ABBREVIATION 1. “WBSEDCL” means West Bengal State Electricity Distribution Company Limited. 2. “CAMC” means Comprehensive Annual Maintenance Contract. 3. ”IB” means Instruction to Bidder. 4. “HVAC” means High Voltage Air Conditioner. 5. “PAC” means Precession Air Conditioner. 6. “UPS” means Uninterrupted Power Supply. 7. “DSC” means Digital Signature Certificate. 8. “CA” means Certifying Authority. 9. “CCA” means Controller of Certifying Authorities. 10. “DSC” means Digital Signature Certificate. 11. “USB” means Universal Serial Bus. 12. “DD” means Demand Draft. 13. “BC” means Banker’s Cheque. 14. “BG” means Bank Guarantee. 15. “EMD” means Earnest Money Deposit. 16. “NIeT” means Notice Inviting E Tender. 17. “NIT” means Notice Inviting Tender. 18. “BOQ” means Bill of Quantity. 19. “PDF” means Portable Document Format. 20. “PF” means Provident Fund. 21. “ESI” means Employees' State Insurance. 22. “ST” means Service Tax. 23. “IT” means Income Tax. 24. “PAN” means Permanent Account Number. 25. “DC” means Data Center. 26. “DRC” means Disaster Recovery Center. 27. “LOA” means Letter of Award. 28. “SW” means Scope of Work. 29. “DG” means Diesel Generator. 30. “TR” means Transformer. 31. “VCB” means Vacuum Circuit Breaker. 32. “BMS” means Building Management System. 33. “PPC” means Precession Power Control. 34. “CTR” means Resolution Time. 35. “RPM” means Revolution Per Minute. 36. “PCB” means Printed Circuit Board. 37. “FCN” means Field Change Notices . 38. “MCB” means Miniature Circuit Breaker. 39. “MCCB” means Moulded Case Circuit Breaker. 40. “ACDB” means Alternating Current(A.C.) Distribution Board. 41. “LDB” means Light Distribution Board. 42. “PDB” means Power Distribution Board. 43. “ATS” means Automatic Transfer Switch. 44. “CCTV” means Close Circuit Television. 45. “MIS“ means Management Information Systems. 46. “GCC” means General Conditions of Contract. 47. “OEM” means Original Equipment Manufacturer. Comprehensive AMC for Data Center Infrastructure of Rajarhat Data Center & Berhampore Disaster Recovery Center, WBSEDCL: Tender Notice No. : IT&C/80/584 dated.10.09.2015 Page 3 SECTION: I INSTRUCTION TO BIDDER (IB) IB.1. West Bengal State Electricity Distribution Company Limited herein after referred to as WBSEDCL invites sealed tenders in duplicate, with firms’ own seal, for Comprehensive Annual Maintenance Contract (CAMC) of Data Center Infrastructure for Central Data Center, Rajarhat and Disaster Recovery Center, Berhampore under IT&C Cell, WBSEDCL Office as per detail “Scope of Work” and other terms and conditions furnished in the different clauses of the bid document. IB.2. Source of Fund: WBSEDCL will finance the entire work as stipulated under scope of work in the Bid documents. IB.3. Eligibility of Bidders: IB.3.1. Vendors fulfilling the Mandatory Conditions mentioned in the Annexure –II shall be considered as eligible for bidding. IB.3.2. Required supporting documents are to be submitted as per clause IB.18. IB.4. Issue of BID Documents: (i) Bids shall be offered for Comprehensive Annual Maintenance of the equipments under Electrical System, HVAC System and Building Management System taking reference from bid document. (ii) Procurement of equipments for the purpose of Comprehensive Annual Maintenance of the equipments under Electrical System, HVAC System and Building Management System including UPS, DG SET, PAC etc. installed at the Data Centre Rajarhat & Disaster Recovery Center, Berhampore as per requirements. IB.4.1. Intending Bidders desirous of participating in the tender are to log on to the website http://wbtenders.gov.in . The tender can be searched by typing wbsedcl in the search box of the website. IB.4.2. Bidders willing to take part in the process of e-tendering are required to obtain Digital Signature Certificate (DSC) in the name of person who will sign the tender, from any authorized Certifying Authority (CA) under CCA, Govt of India (viz. nCode Solution, Safescrypt, e-Mudhra). DSC is given as a USB e-Token. After obtaining the Class 2 or Class 3 Digital Signature Certificate (DSC) from the approved Certifying Authority they are required to register the fact of possessing the Digital Signature Certificates through the registration system available in the website. Intending bidders are to download the tender documents from the website stated above, directly with the help of the e-Token provided. This is the only mode of collection of tender documents. Details of submission procedure are given in “Instructions to Bidders”. IB.4.3. IB.5. Responsibility of Bidders: IB.5.1. It shall be the sole responsibility of Bidders to determine and to satisfy themselves by such means as they consider necessary or desirable for all matters pertaining to this contract including, in particular, all factors that Comprehensive AMC for Data Center Infrastructure of Rajarhat Data Center & Berhampore Disaster Recovery Center, WBSEDCL: Tender Notice No. : IT&C/80/584 dated.10.09.2015 Page 4 may affect the cost, duration and execution of the work. IB.5.2. It must be understood and agreed that such factors have properly been investigated and considered while submitting the bid. Any claim, whatsoever, including those for financial adjustments to the contract, once awarded under these documents will not be entertained by WBSEDCL. Neither any change in time schedule of the contract nor any financial adjustments, arising thereof, shall be permitted by WBSEDCL, which are based on the lack of such clear information of its effect. IB.5.3. The bid shall include all the information as per bid document. IB.5.4. The bidder shall bear all the costs associated with the preparation and submission of bid and WBSEDCL in no case shall be responsible or liable for these costs, regardless of the conduct or outcome of the bidding process. IB.5.5. In order to avoid any problem arising out of network error or server error, bidders are advised to submit the bid, well in advance of the last date and time of submission of the bid. IB.6. Formation of cartel & penal Measures: Any evidence of unfair trade practices, including overcharging, price fixing, cartelization etc. as defined in various statutes, will automatically disqualify the parties. Repeated occurrence of such evidence of above tenderers may also be viewed seriously by the WBSEDCL authority and penal measures as deemed fit would be imposed on such tenderers. IB.7. Key Dates: Schedule of Dates for e-Tendering: Sl. No. Activity Date & Time 1 Publishing Date 14.09.2015 at 14:00 Hrs. 2 Document Download start date 14.09.2015 at 14.00 Hrs. 3 Last date of receiving Pre-Bid Clarification 21.09.2015 4 Date of Pre-bid Discussion 24.09.2015 at 15.00 Hrs at 3rd Floor Conferrence Room, IT&C Cell, 3rd Floor, D-Block, Bidyut Bhaban. 5 Bid submission start date 30.09.2015 at 11.00 Hrs. 6 Last date of physical submission of Tender Fee and 09.10.2015 at 13.00 Hrs. EMD 7 Bid submission end date 09.10.2015 up to 14.00 Hrs. 8 Technical Bid opening date 15.10.2015 at 11.30 Hrs. 9 Financial Bid opening date To be informed eligible Bidders. to the Comprehensive AMC for Data Center Infrastructure of Rajarhat Data Center & Berhampore Disaster Recovery Center, WBSEDCL: Tender Notice No. : IT&C/80/584 dated.10.09.2015 Page 5 IB.8. If any ‘Strike’ or ‘Holiday, falls on any of the scheduled date, then the next working day (between mentioned working hours) shall be considered as scheduled date and schedule time. IB.9. Pre Bid Discussion: IB.9.1. Pre bid discussion will be held at WBSEDCL as per schedule indicated in “Key Dates Clause” above to clarify the queries, if any, from the vendors in respect of tender. Selected vendors who shall purchase the Bid may participate (maximum two persons per Vendor) in the said meeting for any such clarification. IB.9.2. Non-attendance at the pre bid discussion will not be a cause for disqualification of the bidders. IB.10. Clarification of Bidding Documents: For any discrepancy or obscurity in the meaning of any clause of the bid document, queries need to be sent through letter/email or to be physically submitted to the address specified in the clause IB 18.4.2 “Place of submission/ Address for Communication “ and to the date specified in the clause IB.7 “Key Dates”. Prior to Pre-bid discussion, Quaries will not be accepted by menas of any other mode eexcept the modes mentioed above. Such query received from vendors prior to pre bid discussion shall only be discussed in the pre bid meeting. After submission of bid, correspondences regarding changes in taxes, duties or statutory obligations if any can only be made. If any changes are decided in pre-bid meeting the same will be uploaded in the website http://wbtenders.gov.in and no other communication shall be made afterwards on the issues discussed in the pre bid meeting. The clarification given in pre-bid discussion shall be final and binding on the bidder. IB.11. Amendment / Addenda of Bidding Documents: At any time, prior to the deadline of submission of Bid, WBSEDCL may, for any reason, modify the Bidding Documents by issuing Addenda / Amendments and the same will be uploaded in the website http://wbtenders.gov.in only in due time. WBSEDCL shall not have any obligation to inform the vendor through any other mode of communication. IB.12. Language of the Bid: The bid so prepared by the bidder and all other correspondences and documents relating to the bid, exchanged by the bidder and WBSEDCL, shall be written in British English Language only. IB.13. Period of validity of Bid: The bid shall remain valid for acceptance up to 150 (One hundred Fifty) days from the date of opening of Technical Bid of the tender. WBSEDCL may request to extend Validity of the bid beyond 150 (One hundred Fifty) days if required so, without any change in offer. IB.14. Tender Fee : IB.14.1. All bids must be accompanied with a non- refundable tender fee. The bid shall be considered non responsive if the tender fee is not submitted along with the bid. Scanned copy of Demand Draft (DD) / Banker’s Cheque (BC) / Bank Guarantee (BG) towards Tender Fee of Rs. 9,000/(Rupees Nine Thousand only) issued by any branch of any Indian Scheduled Bank in favor of West Bengal State Electricity Distribution Company Limited payable at Kolkata, is to be uploaded while submitting the bid online. The details of the instrument are to be entered while the bid is being submitted online. Comprehensive AMC for Data Center Infrastructure of Rajarhat Data Center & Berhampore Disaster Recovery Center, WBSEDCL: Tender Notice No. : IT&C/80/584 dated.10.09.2015 Page 6 IB.15. IB.16. Earnest money [Bid Guarantee]: IB.15.1. All bids must be accompanied with a refundable earnest money, as “Bid Guarantee”. The bid shall be considered non responsive if the earnest money is not submitted along with the bid. IB.15.2. Scanned copy of Demand Draft (DD) / Banker’s Cheque (BC) / Bank Guarantee (BG) towards EMD of Rs. 9,00,000 /- (Rupees Nine lakh only) issued by any branch of any Indian Scheduled Bank in favor of West Bengal State Electricity Distribution Company Limited payable at Kolkata, is to be uploaded while submitting the bid online. The details of the instrument are to be entered while the bid is being submitted online. The Bank Guarantee to be submitted as per format in ANNEXURE-III shall remain valid for 180 days from the date of submission of bid with a claim period of 6(Six) months thereafter. IB.15.3. The Bid Guarantee of the unsuccessful Bidder/ Bidders, will be returned against their written claim within one month from the date of placement of order on the successful Bidder/ Bidders. IB.15.4. The ‘Bid Guarantee’, of the successful Bidder/ Bidders, will be returned within 30 (Thirty) days from the date of acceptance of Performance Guarantee to be submitted as per Performance Guarantee Clause of bid document. IB.15.5. No interest shall be payable by WBSEDCL on the above Bid Guarantee. IB.15.6. The Bid Guarantee shall be forfeited for any of the following reasons: IB.15.6.1. If during the period of bid validity, the bidder withdraws or modifies the bid in part or as a whole. IB.15.6.2. If the successful Bidder/ Bidders fails/fail to accept the order unconditionally as per “Acceptance of Order” clause of bid document or fails/fail to furnish the contract performance guarantee as stipulated in PBG clause of bid document. IB.15.6.3. If the successful bidder / bidders fails to extend the validity period of EMD as per “Earnest Money” Clause of bid document. IB.15.6.4. If any cartel is formed by the tenderer in their quotation. General guidance for e-Tendering: Instructions/Guidelines for electronic submission of the tenders have been mentioned below for assisting the bidders to participate in e-Tendering. IB.16.1. Registration of Bidders : Any bidder willing to take part in the process of e-Tendering will have to be enrolled & registered with the e-Procurement system, through logging on to https://wbtenders.gov.in. IB.16.2. Digital Signature certificate (DSC): Each bidder is required to obtain a class-II or Class-III Digital Signature Certificate (DSC) for submission of tenders IB.16.3. The bidder can search and download NIeT & Tender Documents electronically from the website mentioned in Clause 4 using the Digital Comprehensive AMC for Data Center Infrastructure of Rajarhat Data Center & Berhampore Disaster Recovery Center, WBSEDCL: Tender Notice No. : IT&C/80/584 dated.10.09.2015 Page 7 Signature Certificate. This is the only mode of collection of Tender Documents. IB.17. Signing of Bids: IB.17.1. The bid shall be downloaded from the website www.wbtenders.gov.in and shall be signed by a person / persons duly authorized by the bidder. IB.17.2. To be qualified for evaluation and finalization of contract, Bidder/ Bidders shall submit a written power of attorney, authorizing the signatory of the Bid to act on behalf of the Bidder in the form and manner which is acceptable by WBSEDCL. IB.17.3. All the pages of the bid and where, entries/ amendments have been made, shall be signed by the person/persons signing the bid. IB.17.4. The complete bid shall be without alterations, interlineations or erasers, except those to accord with instructions issued by WBSEDCL or as necessary to correct errors made by the bidders, in which case such corrections shall be initialed by the person/persons signing the bid. Bids not duly signed shall be treated as cancelled. IB.18. Submission of Bid: Bids shall be submitted as under : IB.18.1. Tender documents are to be submitted online through the website https://wbtenders.gov.in. All the documents uploaded by the Tender Inviting Authority form an integral part of the contract. Tenderers are required to upload all the tender documents along with the other documents, as asked for in the tender, through the above website within the stipulated date and time as given in the Tender. Tenders are to be submitted in two parts - one is Technical Proposal and the other is Financial Proposal. Documents for Technical Proposal are to be submitted at pre-defined folders. Price bid under financial proposal is to be submitted at predefined folder named: BOQ. The tenderer shall carefully go through the documents and prepare the required documents and upload the scanned documents in Portable Document Format (PDF) to the portal in the designated locations of Technical Bid. The bidder needs to download the Forms / Annexures, fill up the particulars in the designated Cell and upload the same in the designated location of Technical Bid. The documents uploaded shall be virus scanned and digitally signed using the Digital Signature Certificate (DSC). Tenderers should take note of all the addendum/corrigendum related to the tender and upload the latest documents as part of the tender. IB.18.2. Part-1: Technical Proposal The Technical Proposal shall contain scanned copies and/or declarations in the following standardized formats in two covers: Comprehensive AMC for Data Center Infrastructure of Rajarhat Data Center & Berhampore Disaster Recovery Center, WBSEDCL: Tender Notice No. : IT&C/80/584 dated.10.09.2015 Page 8 IB.18.2.1. i. Statutory Cover Under Statutory Cover/folder, there will be another four folders for submission of the technical documents. To be submitted in “Drafts” folder . a) Tender Fee Scanned copy of Demand Draft (DD)/ Banker’s Cheque (BC) towards tender fee as prescribed in the NIeT, in favour of West Bengal State Electricity Distribution Company Limited payable at Kolkata. b) Earnest Money Deposit (EMD) Scanned copy of Bank Guarantee (BG)/DD/BC/Pay order towards EMD as prescribed in the NIeT (Annexure -III), in favour of West Bengal State Electricity Distribution Company Limited payable at Kolkata. ii. To be submitted in “Annexure” folder a) Bid Proposal (Vide Annexure I) b)Proforma for bank guarantee for contract performance (Vide Annexure VI) c) Price Schedule in Un-priced condition (BoqAnnexureV). d)Equipment/ Component Schedule (Annexure VIIA, VIIB & VIIC, VIID, VIIE, VIIF). e) Blank Format of Log Book for Corrective Maintenance (Annexure VIII). iii. To be submitted in “NIT” folder a) Notice Inviting e-Tender (NIeT) b)Addenda/Corrigenda: if published iv. To be submitted in “Forms” folder a) Schedule of Bid:-The bidder needs to download the form for “Schedule of Bids” (Annexure-IIA), fill up the particulars in the designated Cell and upload the same in the designated location of Technical Bid. Submission of incomplete “Schedule of Bids” will render the tender liable to summary rejection. b) Mandatory Condition (Annexure-II). c) Summary statement (Annexure-IIB) of average annual turnover for a period of the last three financial years i.e for financial years 2011-2012, 2012-2013, 2013-2014, as per certified audit report for Companies and tax audit report in case of Firms or Entities other than Companies. d) Statement of orders executed during last three financial years (Annexure-IIC) i.e for financial years 2012-2013, 2013-2014, 2014-2015. e) Proforma for undertaking to be submitted by the Bidders (Vide Annexure-IVA) and Format of Letter of Bid (Vide Annexure-IVB). Note: Bidders are to keep track of all the Addendum/Corrigendum issued with a particular tender and upload all the above digitally signed along with the NIeT. Tenders submitted without the Addendum/Corrigendum will be treated as informal and liable to be rejected. Only downloaded copies of the above documents are to be uploaded, virus scanned and digitally signed by the bidder. Comprehensive AMC for Data Center Infrastructure of Rajarhat Data Center & Berhampore Disaster Recovery Center, WBSEDCL: Tender Notice No. : IT&C/80/584 dated.10.09.2015 Page 9 IB.18.2.2. i. Non-Statutory Cover (My Document). Company Details: Company Profile describing the working area. ii. Certificates: a) PF and ESI (if applicable) Registration Certificate b) Copy of PAN Card. c) Valid Professional Tax Registration certificate. d) VAT Registration Certificate.. e) Service Tax Registration No. f) Trade License No with Certificate is to be submitted by the Bidder. g) Registration No with Certificate of Incorporation as a Company under Companies Act 1956 (substituted by Companies Act 2013) for more than 5 (five) years ending 31.03.2015. h) Copy of returns for IT, filed during last three years i.e. for assessment year 2012-2013, 2013-2014, 2014-2015. iii. Financial Info: Average annual turnover for a period of the last three financial years i.e for financial year 2011 -2012, 2012-2013, 2013-2014. In this respect complete set of audit report for Companies and tax audit report in case of Firms or Entities other than Companies for financial years 2011-2012, 2012-2013, 2013-2014 are required to be submitted. iv. Credential: a) Documents to be submitted as mentioned in Annexure-II (Mandatory Condition). b) Any documents found necessary. Note : Failure of submission of any one of the above mentioned documents will render the tender liable to summary rejection. IB.18.3. Financial Proposal (Part-2) The financial proposal needs to be submitted as per pre-defined standardized formats (BoqAnnexureV) in one cover (folder) named “BOQ” under main cover “Finance”. The bidder is to upload, downloaded predefined Price Bid only with filled up amounts in specified fields. The bidder will not be allowed to upload any Techno-commercial terms and conditions in the ‘Price Bid’ offer/ BOQ. Any deviation taken in the Price part shall not be accepted. IB.18.3.1. To be submitted in “BOQ” folder. The bidder is to quote the rate in the blank spaces marked for quoting rate in the Schedule1 sheet of BoqAnnexureV for Rajarhat DC and Berhampore DRC. Only downloaded copies of the above documents are to be uploaded, virus scanned and digitally signed by the bidder. Any deviation in the format, content (Other than entry of the quoted price at the desired blank spaces) of the Price bid/BOQ will render the tender liable to summary rejection. Comprehensive AMC for Data Center Infrastructure of Rajarhat Data Center & Berhampore Disaster Recovery Center, WBSEDCL: Tender Notice No. : IT&C/80/584 dated.10.09.2015 Page 10 IB.18.4. Submission of original copies of documents of Tender Fee and Earnest Money Deposit : Mode of Payment: Tender Fee must be submitted in the form of Bank Draft (DD) / Bankers Cheque (BC) of any scheduled Bank of India. EMD must be submitted in the form of Bank Draft (DD) / Bankers Cheque (BC) / Bank Guarantee (BG) of any scheduled Bank of India. Payment in any other form will not be accepted. IB.18.4.2. Place of submission/ Address for Communication: The original copies of the DD/BC/BG, towards Tender Fee and Earnest Money Deposit shall be submitted in the following office: Office of the Chief Engineer, IT & C Cell, West Bengal State Electricity Distribution Company Limited, Vidyut Bhavan,3rd Floor, D-Block, SaltLake, Sector-2, Kolkata – 700091. Ph No:-033-2324-2550/ 2551 Email Id:- soumya.samanta@wbsedcl.in IB.18.4.3. Time of submission: The original copies of DD/BC/BG towards Tender Fee and EMD shall be submitted in a sealed envelope in the office as stated above within the date and time as specified in the NIeT. If the bidder fails to submit the original copies within the due date and time, his tender will not be opened and his bid will stand rejected. IB.18.4.1. IB.19. IB.18.5. Conditional and incomplete tenders are liable to summary rejection. IB.18.6. No price preference will be allowed to any tenderer based on the size of the industry or its geographic location. Co-operative Society will not be considered with separate status. Late Submission of Bid: Bidder shall take all possible measures to submit the bid within the schedule date & time at specified location prescribed elsewhere in the bidding document. Late submission of bid for whatever reason shall not be accepted. IB.20. Withdrawal / modification of Bids: IB.20.1. IB.20.2. IB.19. The bidder may withdraw / modify his bid after submission of bid, provided that the notice of withdrawal / modification is received in writing by WBSEDCL prior to opening of bid document (part-1) No withdrawal/modification will be allowed after opening of bid document under any circumstances. Withdrawal of a bid during the interval after opening of bid document (part-1) and the expiry of the period of bid validity specified by the bidder in the Bid Form shall result in the forfeiture of the bid guarantee through encashment of the DD/BG/BC/Pay order by WBSEDCL. Opening and evaluation of tender IB.19.1. Opening of technical proposal: IB.19.1.1. Technical proposals will be opened by the Tender Inviting Authority or his authorized representative electronically from the website stated above, using their Digital Signature Certificate. IB.19.1.2. Technical proposals for those tenderers whose original copies of DD/BC/BG towards tender fee & EMD have been received will only Comprehensive AMC for Data Center Infrastructure of Rajarhat Data Center & Berhampore Disaster Recovery Center, WBSEDCL: Tender Notice No. : IT&C/80/584 dated.10.09.2015 Page 11 IB.19.1.3. IB.19.1.4. IB.19.1.5. IB.19.1.6. be opened. Proposals corresponding to which original copy of DD/BC/BG towards tender fee & EMD has not been received, will not be opened and will stand rejected. Intending tenderers may remain present if they so desire (restricted to two persons per Tenderer). Cover (Folder) for Statutory Documents (vide Clause IB.18.2.1) will be opened first and if found in order, Cover (Folder) for Non-statutory Documents (vide Clause IB.18.2.2) will be opened. If there is any deficiency in the Statutory Documents, the tender will summarily be rejected. Decrypted (transformed into readable formats) documents of the Statutory and Non-statutory Covers will be downloaded for the purpose of evaluation. Evaluation Procedure described in clause IB.22. IB.19.2. Opening of financial proposal (price bids). Financial proposals submitted by the tenderers in the prescribed format (BoqAnneexureV) and declared technically eligible, will be opened electronically by the Tender Inviting Authority from the web portal stated above on the prescribed date. IB.19.2.2. No deviation in any form in the price-bid sheet is acceptable. IB.19.2.3. The encrypted copies will be decrypted and evaluated online. IB.19.2.4. After opening of the financial proposal the preliminary summary result containing inter-alia, name of bidders and the rates quoted by them will be uploaded. IB.19.2.5. The Tender Accepting Authority may ask any of the tenderers to submit analysis to justify the rate quoted by that tenderer. IB.19.2.6. For any discrepancy in the amount of figures and words, the quoted amount in figure will prevail. IB.19.2.1. IB.20. Process to be confidential: IB.20.3. After the opening of bids, information relating to the examination, clarification, evaluation and comparison of bids, and recommendations concerning the award of Contract shall not be disclosed to bidders or other persons not officially concerned with such process. IB.20.4. Any effort by a bidder to influence WBSEDCL or others connected in the process of examination, clarification, evaluation and comparison of bids, and in decisions concerning the award of Contract, may result in the rejection of his bid. IB.21. Conflict of Interest: IB.21.1. The Bidder shall not have a conflict of interest that may affect the Tendering Process. Any Bidder found to have a Conflict of Interest shall be disqualified. In the event of disqualification, the Bid Security of the bidder shall be forfeited for, the time, cost and effort of the Authority including consideration of such Bidder’s Proposal, without prejudice to any other right or remedy that may be available to the Authority hereunder or otherwise. Comprehensive AMC for Data Center Infrastructure of Rajarhat Data Center & Berhampore Disaster Recovery Center, WBSEDCL: Tender Notice No. : IT&C/80/584 dated.10.09.2015 Page 12 IB.21.2. IB.21.3. IB.21.4. Any Bidder found to have a Conflict of Interest if his near relative is posted as an employee/officer in any capacity in WBSEDCL, who is associated with the Tender Inviting Authority. Any Bidder found to have a Conflict of Interest if any employee of the bidding firm/company has or develops a financial or other interest with any employee/officer of WBSEDCL associated with the Tender Inviting Authority during the execution of the contract. Any Bidder has a relationship with another Bidder/Bidders, directly or through common third parties, that puts them in a position to have access to each-others’ information about, or to influence the Tendering Process of either or each of the other Bidder. IB.22. Clarification of Bids: To assist in the examination, evaluation and comparison of bids, WBSEDCL may ask the bidder individually for clarifications of his bid at the appropriate stage of evaluation. The request for clarification and the response thereof shall be in writing but no change in the price or substance of the bid shall be sought, offered or permitted. IB.23. Procedure of Evaluation : Evaluation of tenders will be done in the following steps: IB.23.1. IB.23.1.1. IB.23.1.2. IB.23.1.3. IB.23.1.4. IB.23.1.5. Evaluation of Technical Proposal While evaluation, the Tender Inviting Authority or his authorized representative may summon of the tenderers and seek clarification / information or additional documents or original hard copy of any of the documents already submitted and if these cannot be produced within the stipulated timeframe, their proposals will be liable for rejection. The summary list of tenderers, whose bids will be found technocommercially eligible, will be uploaded in the web portals. Date of opening of financial bid will be intimated to the techno-commercially qualified tenderers. All Technical proposal documents as specified in the tender will be examined and assessed for the techno-commercial, performance and management capability of the bidder. The bidder shall not take any commercial deviation from the stipulation of Bid document. If the bidder takes any commercial deviation, his Bid may be liable for rejection. Prior to opening of price bid, a meeting with qualified bidders may be arranged to bring all the bidders under same commercial terms & conditions if considered necessary. Date of meeting will be communicated to qualify bidders in due course. IB.23.2. Evaluation of price bid: IB.23.2.1. Evaluation of Price Bid will include all the relevant taxes as applicable. IB.23.2.2. The bidder shall indicate the above prices clearly in the respective price schedule. IB.23.2.3. If Rebate / Discount is offered, the financial impact of Rebate / Discount shall also be brought out in the Summary Price Bid. Comprehensive AMC for Data Center Infrastructure of Rajarhat Data Center & Berhampore Disaster Recovery Center, WBSEDCL: Tender Notice No. : IT&C/80/584 dated.10.09.2015 Page 13 IB.23.2.4. IB.24. Conditional Rebate / Discount, if any, offered by any Bidder shall be outside the purview of commercial terms & conditions & shall not be considered during Bid evaluation. Any variation, up or down, in taxes & duties or any new levy introduced subsequent to bid opening will not be considered for comparison of bids. Price: IB.24.1. IB.24.2. IB.24.3. IB.24.4. IB.24.5. IB.24.6. IB.24.7. IB.24.8. IB.24.9. The Bidder shall indicate the prices in Indian Rupees only. Incomplete or partial quotation will not be accepted and shall be liable to be rejected. No deviation in any form in the Price Bid Sheet is acceptable Prices quoted by the Bidder shall be fixed. Bid/tenders submitted with adjustable price quotations will be rejected. Rates quoted should be for a period of Three years of Comprehensive AMC services of the equipments mentioned in Annexure - VII. The rates quoted should be inclusive of all taxes. No extra costs shall be paid for change of the defective spares if any during Comprehensive AMC period for the equipment under Scope of Work. Total CAMC price offer shall be submitted in the prescribed format (BoqAnnexureV) only. The prices (excluding tax component) shall remain FIRM till completion of the CAMC period for which the contract is awarded. For introduction of any new levy or change of tax rate will be considered till completion of the service within stipulated period. The Bidder, at his own cost, responsibility and risk may visit the Site of Service and may obtain relevant information before quoting the rates. The costs of visiting the Site shall be at the Bidder's own expense. IB.25. Acceptance of Tender: L1 bidder will be decided on the basis of technical and price bid evaluation for the overall work after satisfying each sub-category. Lowest valid rate should normally be accepted. However, the Tender Accepting Authority does not bind himself to do so and reserves the right to reject any or all the tenders, for valid reasons. IB.26. Time Schedule : The entire activity as per scope of work shall start after issue of LOA. Date of issue LOA shall be considered as zero date. IB.27. Taxes, Duties and other levies: The bidder shall be solely responsible for the taxes that may be levied on the vendor’s persons or on earning of any of his employees and shall hold the employer indemnified and harmless against any claims that may be made against the employer. The WBSEDCL shall not take any responsibility whatsoever regarding taxes under Income Tax Act 1961, for the vendor or his personnel. IB.28. Statutory Obligations: Statutory obligations as per law of the land are to be complied. Comprehensive AMC for Data Center Infrastructure of Rajarhat Data Center & Berhampore Disaster Recovery Center, WBSEDCL: Tender Notice No. : IT&C/80/584 dated.10.09.2015 Page 14 IB.29. P.F. Code No. : The vendor shall submit necessary PF code no. IB.30. Period of Contract: Initial Period of contract shall be 3 (Three) years from the date of placement of order or any other date as agreed upon mutually prior to the commencement of the contract. WBSEDCL may increase the period of contract for another two years depending upon the performance of the previous years of the bidder at the rate indicated below:4th Year Rate – Rate of 3rd Year with a maximum increase up to 5%. 5th Year Rate-- Rate of 4th Year with a maximum increase up to 5%. with same terms and conditions of the Letter of Award (LOA) placed on successful bidder which shall be accepted by the bidder without imposing any conditions. IB.31. Issue of LOA : WBSEDCL will award the contract to the successful bidder whose bid has been determined to substantially responsive and has been determined the lowest evaluated bid, provided further that the bidder is determined to be qualified to perform the contract satisfactorily. WBSEDCL shall be the sole judge in this regard. IB.32. Acceptance of LOA: The successful bidder shall submit written unconditional acceptance of LOA within 15 (Fifteen) days from date of issuance of the same. Submission of conditional acceptance of LOA shall be treated as non-compliance of this clause. IB.33. Right to reject Bids : WBSEDCL reserves the right to accept or reject any bid and to annul the bidding process and reject all bids at any time prior to award of Contract, without thereby incurring any liability to the affected bidder or bidders or any obligation to inform the affected bidder or bidders the reason for WBSEDCL's action. IB.34. Disqualification of Vendors: Adverse report / remark during CAMC service against any order from any office under WBSEDCL may disqualify the candidature of the vendor at any point of time during processing of the tender. IB.35. Representative of Vendors: The successful vendor is required to nominate officers, exclusively for this CAMC with whom WBSEDCL will contact on all matters related to this job. The vendor has to specifically furnish to WBSEDCL, the name, designation, mobile no, office & residential phone no of such person. IB.36. Mandatory Condition: The bidder shall provide documentary evidence satisfactory & acceptable to WBSEDCL to establish that they have the requisite credential, capability and experience to handle the contract and meet requirements of all the Mandatory Conditions indicated in ANNEXURE-II. IB.37. Settlement of Disputes: In case of any dispute arising out the contract, the same should be settled through meeting between the WBSEDCL and the contracting agency at the appropriate level. The necessary judicial affairs and/or Court Case shall be exclusively within the jurisdiction of High Court at Kolkata only. IB.38. Communication: The successful vendor, for communicating with WBSEDCL, for this job may use the following modes. FAX- (033) 2358 9244. Telephone – (033) 2359 9244, 2358 9230, 2319 7634. Mobile No: 8902727235. Email Id:-soumya.samanta@wbsedcl.in Comprehensive AMC for Data Center Infrastructure of Rajarhat Data Center & Berhampore Disaster Recovery Center, WBSEDCL: Tender Notice No. : IT&C/80/584 dated.10.09.2015 Page 15 SECTION: II Scope of Work [SW] COMPREHENSIVE ANNUAL MAINTENANCE CONTRACT Maintenance of all the equipment mentioned in Annexure VII shall be covered under CAMC and manage the processes and procedures to ensure reliable, safe and effective operation at DC, Rajarhat and Disaster Recovery System, Berhampore for running the facility. Uptime is defined as per overall uptime for DC as well as DRC. During the mentioned AMC period, 99% for all the DC Components as well as DRC Components (mentioned in Annexure VII) will be required. SW.1. Understand analyze the product performance on periodic basis and provide the technical recommendation/suggestion/solution if required based on the existing infrastructure. SW.2. Respond to emergency calls, provide site attendance within the call-out time, and take all the necessary corrective actions to restore the service within the minimum downtime. SW.3. The vendor shall be responsible for maintenance of all the systems as per scope of work(SW) with services rendered as per LOA issued by WBSEDCL. SW.4. Must use calibrated testing equipment as well as other items as necessary for collecting all the relevant information, data and statistics etc. SW.5. The Vendor shall be solely responsible for providing all the AMC support services under this contract and WBSEDCL will not be liable to interact with any of OEMs (Original Equipment Manufacturer). SW.6. Dedicated Electrical Equipment list with specification (Like, DG, TR. VCB, Panels, UPS, BATTERY,BMS SYSTEM,PAC and ACs etc.) of DC & DRC will be provided to VENDOR after acceptance of LOA and the information regarding any addition change of electrical equipment during AMC period would be provided to the VENDOR accordingly. SW.7. VENDOR will provide a toll free number or one dedicated land line number for registering the calls from WBSEDCL. Also Vendor shall provide one or two mobile number for registering emergency call for any critical equipment fault. SW.8. VENDOR will respond to all calls and provide 7 x 24x365 emergency service. SW.9. VENDOR will take immediate action against any breakdowns, faults or defects reported to him and take the necessary corrective actions to restore the service. SW.10. During the mentioned AMC period, uptime of 99% for all the supplied DC Components and DRC Components for quarterly basis will be required. All the equipment mentioned in Annexure VII shall be covered under AMC. The resolution time of the items mentioned in Annexure VII are as follows:SW.10.1 Critical Items like PPC, PAC, DG set, 160 KVA UPS, 10 KVA UPS, ATS and LT Panels. SW.10.1.1. Call to Resolution time (CTR) for Data Center, Rajarhat--- 6 hrs. SW.10.1.2. Call to Resolution time (CTR) for Disaster Recovery Center, Berhampore – 24 hours. SW.10.2 Non-critical Items (Items other than Critical Items). SW.10.2.1. Call to Resolution time (CTR) for Data Center Rajarhat – 24 Hours. Comprehensive AMC for Data Center Infrastructure of Rajarhat Data Center & Berhampore Disaster Recovery Center, WBSEDCL: Tender Notice No. : IT&C/80/584 dated.10.09.2015 Page 16 SW.10.2.2. Call to Resolution time (CTR) for Disaster Recovery Center, Berhampore – 48 hours. SW.11. MAINTENANCE ACTIVITY FOR ELECTRICAL SYSTEMS. SW.11.1. EMERGENCY MAINTENANCE : Emergency maintenance will be performed against all docketed call during occurrence of fault of any component under Electrical, HVAC and BMS system. Call to resolution time (CTR) is indicated in SW.10.1 and 10.2 clause. SW.11.2. QUARTERLY MAINTENANCE ACTIVITY FOR DIESEL GENERATOR SETS & AMF PANELS:Cleaning of DG set and battery terminals. Check generation of DG alarms. Check proper earthing of DG neutral and body. Check Radiator water level and inhibitor. Check any leakage in DG set. Operate Generator and Check parameters and Panel indication. Check 110v DC, 230v AC, 24v DC supply and record. Check for excessive vibration and report if any. Check the conditions of motors shaft & belts. Check & clean radiator fins, water separator, coolant level etc. Checking of proper functionality of canopy light, door lock self starter and stop solenoid and other gauges. SW.11.2.12. Checking of battery voltage and distill water and specific gravity of battery. SW.11.2.13. Record HR meter reading of DG set. SW.11.2.14. Measurement of voltage, load current, lube oil pressure, coolant temp, engine temp, frequency, RPM of DG set. SW.11.2.15. Checking of DG operation in Auto and manual mode along with o/p voltage and frequency at full load. SW.11.2.16. During maintenance work vendor should record the SEB and DG meter readings and log book to be maintained against it. SW.11.2.17. Preventive & corrective maintenance report will be maintained. SW.11.2.18. Check exhausts smoke leakage. SW.11.2.19. Check proper functioning of gauges and record discrepancies SW.11.2.20. Check Belt tension & condition of water pump, pulley drive & fan, etc. SW.11.2.21. DG batteries replacement (If needed). SW.11.2.22. Repairing of Self starter & Charging alternator, Radiator. SW.11.2.23. Cleaning of Diesel Tank. SW.11.2.24. Replacement of Fuel Pipes. SW.11.2.25. Repairing of DG cylinder pipe & exhaust line. SW.11.2.26. Radiator cloth will be replaced as & when require. SW.11.2.27. B-check will be done after 300 hrs running of DG set or after every 6 months, whichever is earlier. SW.11.2.28. Verifying Control Panel readings and indicators performing its maintenance. SW.11.2.1. SW.11.2.2. SW.11.2.3. SW.11.2.4. SW.11.2.5. SW.11.2.6. SW.11.2.7. SW.11.2.8. SW.11.2.9. SW.11.2.10. SW.11.2.11. Comprehensive AMC for Data Center Infrastructure of Rajarhat Data Center & Berhampore Disaster Recovery Center, WBSEDCL: Tender Notice No. : IT&C/80/584 dated.10.09.2015 Page 17 EXCLUSIONS: Supply and filling of Diesel SW.11.2.29. SW.11.3. QUARTERLY MAINTENANCE ACTIVITY FOR UPS (BOTH TYPE 160 KVA & 10 KVA) Cleaning up of Unit, Visual Inspection to check any deformation. SW.11.3.2. Checking and Adjustment of Power parameters like input. Output, DC voltage & Current. SW.11.3.3. Checking and Adjustment of Control parameters on different PCBs. SW.11.3.4. Checking of tightness and cleaning of battery terminals. SW.11.3.5. Functional Checking of Rectifier section. SW.11.3.6. Functional Checking of Inverter section. SW.11.3.7. Functional Checking of Static Switch Section. SW.11.3.8. Checking of Wire wound components SW.11.3.9. Operational test of the system including unit transfer and battery discharge. SW.11.3.10. Install or perform Engineering Field Change Notices (FCN) as necessary. SW.11.3.1. SW.11.4. CHECKING AND MAINTENANCE ACTIVITY FOR LT PANEL (YEARLY BASIS). SW.11.4.1. Cleaning up of dust & greasing (only on moving parts) of total panel. SW.11.4.2. Do the tightness of the junction points/nuts & bolts. SW.11.4.3. Checking the breaker settings & function. SW.11.4.4. Measuring of Panel earthing value & connections. SW.11.4.5. Checking of the cable sockets conditions. SW.11.4.6. Repair & replacement of cable sockets in case of requirements. SW.11.4.7. Checking of measuring meters & its functions. Repair only in case of requirement (Vendor will not provide any standby meter during repairing period). SW.11.4.8. Checking of measuring meters & its functions. Repair only in case of requirement (Vendor will not provide any standby meter during repairing period). SW.11.4.9. Repair & replacement of MCB/MCCB/Contractor/Relay/Circuit Breakers. SW.11.4.10. Under Voltage and Over Voltage trip settings checking. SW.11.4.11. Replacement & calibration of measuring meters. SW.11.4.12. Replacement of any bus bar SW.11.4.13. Repair & replacement of Panel metal sheet SW.11.5. YEARLY MAINTENANCE ACTIVITY FOR OTHER ELECTRICAL EQUIPMENTS SW.11.5.1. Checking of proper functioning of Main Switch. SW.11.5.2. Checking of proper body earthing of Main Switch. SW.11.5.3. Checking of proper functioning of indoor, outdoor, light and power sockets. Comprehensive AMC for Data Center Infrastructure of Rajarhat Data Center & Berhampore Disaster Recovery Center, WBSEDCL: Tender Notice No. : IT&C/80/584 dated.10.09.2015 Page 18 Checking of any loose termination within Main Switch, ACDB and other. MCB’s and proper functioning of ACDB. SW.11.5.5. Checking for functionality of PRECISION POWER CENTRE (PPC) and provide necessary maintenance for all components of PPC so as to provide continuous supply of AC power to the equipments connected with PPC installed at Data Centre, RAJARHAT and Disaster Recovery Center, Berhampore. SW.11.5.6. Checking of voltage level in the Utility Panel and provide necessary maintenance for all components of Utility Panel for the continuous flow of power to the equipments connected with the Utility Panel installed at Data Centre, RAJARHAT & Disaster Recovery Center, Berhampore. SW.11.5.7. Checking of functionality of Utility Output DB connected with 10 KVA UPS and providing necessary maintenance for continuous supply of power to the 10 KVA UPS. SW.11.5.8. Checking of functionality of LDB connected with all Lighting points of the Data Center & Disaster Recovery Center and providing necessary maintenance for continuous supply of AC power to the Lighting equipments. SW.11.5.9. Checking for functionality of PDB connected with all power points of the Data Center & Disaster Recovery Center and providing necessary maintenance for continuous supply of AC power to the power points. SW.11.5.10. Providing extra Cable Trays if required. for any damage of existing trays and for installation of new equipments at Data Center, Rajarhat & DRC, Berhampore for proper cabling of the system. SW.11.5.11. Replacing Cable and Termination kits as may be required for the proper functioning of the system installed at Rajarhat DC & Berhampore DRC. SW.11.5.12. Checking of Wiring, MCB, Switches etc installed at Rajarhat DC as well as Berhampore DRC and providing necessary replacement whenever required for smooth functioning of the system. SW.11.5.13. Check all the lighting equipments with allied accessories at Rajarhat DC as well as Berhampore DRC and replacement shall be made if required. SW.11.5.14. Checking of Industrial sockets, plugs and related components and replacement shall be made if required. SW.11.5.4. EXCLUSIONS: SW.11.5.15. Electronic Ballast of the Indoor Lights. SW.11.5.16. Tube/PL/CFL for Indoor Light fitting. SW.11.6. YEARLY MAINTENANCE ACTIVITY FOR EARTHING AND EARTHING STRIPS. SW.11.6.1. Checking for loose termination and continuity of earthing connections with earth pit. SW.11.6.2. Watering, charcoal & salt refill and cleaning of earthing pits. SW.11.6.3. Changing nuts & bolts in case of rusting. Comprehensive AMC for Data Center Infrastructure of Rajarhat Data Center & Berhampore Disaster Recovery Center, WBSEDCL: Tender Notice No. : IT&C/80/584 dated.10.09.2015 Page 19 SW.11.7. QUARTERLY MAINTENANCE ACTIVITY FOR BATTERIES FOR 10 KVAUPS, 160 KVA UPS AND DG SETS. SW.11.7.1. Checking of Battery Health. SW.11.7.2. Replacement of UPS Batteries & DG Set Batteries if required. SW.11.7.3. Checking of any loose termination of battery bank. SW.11.7.4. Checking of petroleum gel on the junction points. SW.11.7.5. Proper cleaning of termination of battery bank with greasing of terminals. SW.11.7.6. Checking of body earthing of battery bank. SW.11.7.7. Checking of individual cell voltages in float, boost mode. SW.11.8. YEARLY MAINTENANCE ACTIVITY FOR AUTOMATIC TRANSFER SWITCH(ATS). SW.11.8.1. De-energize the switchgear. SW.11.8.2. Test and re-calibrate all trip sensing and time delay functions in the switchgear. SW.11.8.3. Vacuum clean the accumulated dust from the ATS and accessory panels. SW.11.8.4. Inspect for moisture or signs of previous wetness or dripping. SW.11.8.5. Remove any grime with an approved solvent. SW.11.8.6. Inspect all insulating parts for cracks or discoloration due to excessive heat. SW.11.8.7. Inspect all main arcing contacts for excessive erosion. SW.11.8.8. Inspect all main current-carrying contacts for pitting and discoloration due to excessive heat. SW.11.8.9. Inspect all control relay contacts for excessive erosion and discoloration due to excessive heat. SW.11.8.10. Manually operate the main transfer movement to check proper contact alignment, deflection, gap, and wiping action. SW.11.8.11. Check all cable and control wire connections to the transfer switch control and sensing panel and other system components and tighten if necessary. SW.11.8.12. Re-energize the switchgear and conduct a test by simulating a normal source failure. SW.11.8.13. Testing of ATS with Test Switch. SW.12. MAINTENANCE ACTIVITY FOR HVAC, SPLIT & DUCT AC SYSTEMS. SW.12.1. QUARTERLY MAINTENANCE ACTIVITY FOR HVAC SYSTEMS SW.12.1.1. Cleaning up of Unit, Air Filter, cooling coil & condenser coil. SW.12.1.2. Cleaning of Humidifier bottle, electrodes, water supply strainer and drain inside the machine. SW.12.1.3. Checking of drive belt & replace if necessary. SW.12.1.4. Lubrication of bearings if necessary. SW.12.1.5. Checking up of operation of Unit, Controller & condenser. SW.12.1.6. Combing of fins of condenser & Evaporator coil if necessary. SW.12.1.7. Measurement of current in each individual equipment. Comprehensive AMC for Data Center Infrastructure of Rajarhat Data Center & Berhampore Disaster Recovery Center, WBSEDCL: Tender Notice No. : IT&C/80/584 dated.10.09.2015 Page 20 Checking of all the overload relay settings. Checking of all electrical components for loose connections and tightening if necessary. SW.12.1.10. Checking of refrigeration piping for any gas leakages. SW.12.1.11. Checking of refrigeration system and pressure readings. SW.12.1.12. Checking about the temperature of Server Room which must be maintained at a set temperature between18 and 22 degrees Celsius 24 hours a day, 7 days a week. Temperature must be maintained to 1 Degree Celsius from the set temperature. SW.12.1.13. Checking and maintaining constant humidity level of 50 percent, plus or minus 10 percent (45 percent to 55 percent) in the DC server room. SW.12.1.14. Checking of pulleys, Motor mounts, and Condenser fan mounts etc. SW.12.1.15. Checking of panel insulation. SW.12.1.16. Checking of temperature readings. SW.12.1.17. Checking of Microprocessor controllers for operation. SW.12.1.18. Replacement of sheet metal parts (excluding Condenser coils, consumables & air filters). SW.12.1.19. Replacement of Condenser Coils & Air Filters. SW.12.1.20. Topping up of R407C Gas. SW.12.1.21. Repairs / replacement of electrical main incoming switch (Switch fuse unit), Main incoming cable, fuses, control transformers & indicating lamps. SW.12.1.8. SW.12.1.9. EXCLUSIONS: SW.12.1.22. Repairs / replacements of Water piping & accessories, Ducting, Dampers, Duct lining, grilles, False ceiling, any kind of masonry / structural work. SW.12.2. QUARTERLY MAINTENANCE ACTIVITY FOR SPLIT & DUCT AC. SW.12.2.1. Checking of electrical connections at the machine terminals. SW.12.2.2. Dry Cleaning of filters coils. SW.12.2.3. Cleaning of Air Filter & Replace if required. SW.12.2.4. Oiling and greasing of motors. SW.12.2.5. Top-up of refrigerant. SW.12.2.6. Checking of operational performance parameters. SW.12.2.7. Repairing of cooling/condenser coils. SW.12.2.8. repair/replace all defective spares including compressor and fan motor. SW.12.2.9. Replacement of Compressor if required. SW.12.2.10. Repairing of PCBs and remote controls. SW.12.2.11. Repairing of Voltage Stabilizer and Timer. SW.12.2.12. Checking of pulleys, Motor mounts, and Condenser fan mounts etc. EXCLUSIONS: SW.12.2.13. Changing of any plastic material. Comprehensive AMC for Data Center Infrastructure of Rajarhat Data Center & Berhampore Disaster Recovery Center, WBSEDCL: Tender Notice No. : IT&C/80/584 dated.10.09.2015 Page 21 MAINTENANCE ACTIVITY FOR BUILDING MANAGEMENT SYSTEM & NOVEC 1230 GAS CYLINDER. & FIRE EXTINGUISHERS. SW.13. QUARTERLY SW.13.1. Checking and maintenance of Building management system, Field Devices and their Components. SW.13.2. Checking & cleaning up of Smoke Detectors SW.13.3. Checking of operation and maintenance of Analogue Addressable Fire Alarm System and its components. SW.13.4. Checking and maintenance of Vesda System and its components. SW.13.5. Checking of functionality of Hooters, Fire Sounder, and Manual Call Points. SW.13.6. Checking & Cleaning of Cameras & the systems associated with it. SW.13.7. Checking of VESDA filter. Replacement will be done if required. SW.13.8. Checking and maintenance of Access Control System and its components. SW.13.9. Checking and maintenance of Water Leak Detection System & Rodent Repellent System and its. SW.13.10. Checking and maintenance of CCTV Surveillance System and its components. SW.13.11. Checking and maintenance of Public Address System and its components. SW.13.12. Performing check up of status of NOVEC gas cylinders, check up its load, pressure and ensuring its healthy operation and refilling whenever required. One time FM200 gas refilling during CAMC Period (i.e. within three year) if required. SW.13.13. Performing check up of status of fire extinguisher and ensuring its healthy operation and refilling whenever required. SW.13.14. Yearly checking of all the portable fire extinguisher & refilling (if required) of fire extinguisher. SW.14. REPORTING SYSTEM. SW.14.1. MIS will be submitted at the end of each quarter as per WBSEDCL requirements. Record of readings during maintenance activity will be maintained (Soft & hard copy) by the vendor and kept at Data Center in the custody of Data Center In-Charge and Disaster Recovery Center in the custody of DRC In-Charge.. SW.14.2. Update of formats will be done with approval of WBSEDCL as per requirements. SW.14.3. “No Fault Pending Report for the three months” duly signed by the DC In-Charge, of the DC and DRC respectively. SW.14.4. Fault Details/Fault Response Details (indicating downtime of the equipments) for the three Months” duly signed by the In-Charge, of the DC and DRC respectively as per Annexure - VIII. The format will be updated time to time as per requirement of WBSEDCL. SW.14.5. Preventive maintenance reports of complete system will be updated quarterly basis and submitted to the In-Charge of the DC and DRC Comprehensive AMC for Data Center Infrastructure of Rajarhat Data Center & Berhampore Disaster Recovery Center, WBSEDCL: Tender Notice No. : IT&C/80/584 dated.10.09.2015 Page 22 respectively indicating equipments list to be maintained, date of maintenance, detail report of maintenance performance, remarks if any. Update of this maintenance format will be done time to time as per requirement of WBSEDCL and shall be submitted with the AMC Bills. SW.14.6. Proper files of all official data like, equipment manual, drawings, vendor escalation matrix etc. would be maintained at Data Center and Disaster Recovery Center. SW.14.7. Quarterly checking of BMS system & maintain data detail as per infrastructure provided for Data Center as well as Disaster Recovery Center. SW.14.8. Contracted Agency/Party shall maintain adequate books and records/reports in connection with Contract and shall make them available for inspection and audit by WBSEDCL/ any appointed third party until expiry of the contract, including any extension time. Comprehensive AMC for Data Center Infrastructure of Rajarhat Data Center & Berhampore Disaster Recovery Center, WBSEDCL: Tender Notice No. : IT&C/80/584 dated.10.09.2015 Page 23 SECTION: III General Conditions of Contract [GCC] GCC.1. General Terms: GCC.1.1. The bidder has to furnish all the information as required regarding their offer. GCC.1.2. The Bidder should have service centre facility for all equipments under Electrical System, HVAC System and Building Management System installed at the Data Centre as well as Disaster Recovery Center. GCC.1.3. For proper implementation of CAMC services WBSEDCL reserves the right to modify/cancel the entire CAMC in any point of time after placement of order without showing any reason whatsoever. GCC.1.4. Quotation from any sub-vendor will not be entertained. GCC.1.5. Any form of consortium will not be allowed. GCC.1.6. The bidder shall satisfy WBSEDCL with his ability to perform the CAMC. GCC.1.7. All correspondence, documents and Bid, exchanged between the Bidder and WBSEDCL shall be written in English language. Failure to comply with this request may disqualify a bidder. GCC.1.8. The Company reserves the right, to reject any or all the tenders, at its discretion, without assigning any reason whatsoever. GCC.1.9. To monitor the maintenance activities and to discuss other related matters, meeting will be held between Vendor and WBSEDCL depending upon the need. GCC.1.10. After placement of LOA, the vendor shall have to check the entire system under scope of work and submit a certificate for taking over the system in good condition. GCC.1.11. The Bidder shall hand over the system to WBSEDCL in good working condition after the expiry of CAMC period. GCC.2. Force Majeure : GCC.2.1. GCC.2.2. GCC.3. The vendor shall be under no liability if the vendor is prevented from carrying out any of the vendor’s obligations by reason of war, Invasion, act of foreign country, hostilities, riots, civil commotion, mutiny, accident, earthquake, fires, floods, orders and / or restrictions and other cause beyond the reasonable control of the vendor. However, such force majeure circumstances are to be intimated immediately and to be established subsequently with proper documents / proofs to the entire satisfaction of WBSEDCL. WBSEDCL will not take any additional liability towards enhanced taxes, duties and price variation due to force majeure condition. Cancellation/Termination of Order: WBSEDCL shall have the right to repudiate the contract if the work is not been performed as per satisfaction and as per “Time Schedule” Clause. The following causes may also led to cancellation of LOA. GCC.3.1. Non acceptance of LOA as per “Acceptance” clause. GCC.3.2. Non submission of Performance BG within time. GCC.3.3. If failed to perform the CAMC work. Comprehensive AMC for Data Center Infrastructure of Rajarhat Data Center & Berhampore Disaster Recovery Center, WBSEDCL: Tender Notice No. : IT&C/80/584 dated.10.09.2015 Page 24 GCC.3.4. GCC.4. In each above cases 15 days termination notice shall be issued prior to termination of LOA. Performance Guarantee: For CAMC: BG on non-judicial stamp paper of Rs.100/- by any Schedule Bank in India, as per format enclosed (ANNEXURE-VI) for an amount of 10% of the Contract value of this LOA within 15 days from the date of placement of Letter of Award of the Comprehensive AMC services to the CE, IT&C Cell, 3rd Floor, ‘D’ Block, Bidyut Bhawan, WBSEDCL. No claim shall be made against the Company in respect of interest on the Performance BG. The Performance Security Deposit is liable to be encashed in case of noncompliance of the CAMC order or failure to undertake satisfactory Comprehensive Annual Maintenance Services. BG shall be valid for 90 (Ninety) days after completion of the CAMC period. GCC.5. Arbitration & Legal Jurisdiction: GCC.5.1. During execution of this contract, if any dispute arises thereby, shall be settled amicably between WBSEDCL and yourself to the extent possible. GCC.5.2. All disputes or differences in respect of which the decision if any has not become final shall be settled by arbitration in accordance with the provisions of the Arbitration and Conciliation Act – 1996 or any statutory modification thereof. The venue of Arbitration shall be Kolkata only. GCC.5.3. The necessary legal affairs and / or court case shall be exclusively within the jurisdiction of Kolkata High Court only. GCC.6. Liquidated damage: GCC.6.1. GCC.6.2. GCC.7. WBSEDCL shall have the right to repudiate the contract if the work is not been performed as per satisfaction and as per “Time Schedule” Clause. The following causes may also led to cancellation of LOA. However, the ordering authority may at his discretion waive this condition with imposition of liquidated damage indicated herein below. During AMC Period: If the Vendor fails to set right the malfunctioning of the system within schedule downtime as indicated in relevant clause, WBSEDCL may recover from the vendor @½% (half percent) amount of CAMC order value per hour or part thereof as Liquidated Damage for critical items and same amount i.e. @½% (half percent) amount of CAMC order value per day or part thereof as Liquidated Damage for noncritical items. The maximum value of LD would be 10% (ten percent) of CAMC order value. In case of termination of LOA as per termination clause, WBSEDCL will engage third party for the maintenance of supplied and installed items and related service. The difference in cost of CAMC for engagement of third party will be deducted from outstanding bill /BG lying / to be lying with WBSEDCL. Risk Purchase / Performance: if the vendor fails to deliver the service as per the satisfaction of WBSEDCL, WBSEDCL shall be entitled to execute the job through the best and nearest substitute available elsewhere on the account and at the risk of the contracting agency or to cancel the contract and the Comprehensive AMC for Data Center Infrastructure of Rajarhat Data Center & Berhampore Disaster Recovery Center, WBSEDCL: Tender Notice No. : IT&C/80/584 dated.10.09.2015 Page 25 contracting agency shall be liable to compensate for any loss or damage which WBSEDCL may sustain by reason of such failure on the part of the Contracting Agency. GCC.8. Comprehensive Annual Maintenance Contract (CAMC): GCC.8.1. You shall perform CAMC of all equipment under Electrical System, HVAC System and Building Management System installed at the Data Centre & Disaster Recovery Center as per LOA for 3 (Three) years. All necessary spare parts under scope of service need to be kept in stock accordingly. GCC.8.2. CAMC shall also cover trouble shooting of the system including software. GCC.8.3. Scheduled preventative maintenance must be made at least once in every quarter to avoid breakdown / failure in the system. A gap of maximum 90 (thirty) days shall be maintained between 2 (two) successive preventive maintenance date. Vendor shall have to be furnished necessary monthly reports as per clause SW.14 along with the CAMC bill. GCC.8.4. In case of failure / malfunctioning of the system, the In-Charge of the respective Center or his representative will inform the vendor over telephone. Centralized registration of all calls should be maintained by the vendor to record the calls and acknowledge each and every call with a unique docket number which is to be used for further reference. Completion of the call is to be certified by respective In-Charge of the DC and DRC or his representative. GCC.8.5. Downtime calculation will be started from 0 (zero) hours just after docketing of the call. The maximum acceptable downtime of the Critical Items (PPC, PAC, Two nos DG sets, Two nos 160 KVA UPS and Two nos 10 KVA UPS, ATS and Two Nos. LT Panels.) will be 6 hrs for Data Center and 24 hours for Disaster Recovery Center and the maximum acceptable downtime time of the Non-critical Items will be 24 hours for Data Center and 48 hours for DRC. Downtime will be calculated in each quarter separately. GCC.8.6. Schedule preventive or un-schedule breakdown maintenance includes replacement of all un-serviceable parts free of cost by the vendor. Parts replaced will be new and equivalent to original parts. The defective parts removed will be the property of the vendor. Schedule maintenance of entire system shall be done up to the satisfaction of the In-Charge of the Data Center and Disaster Recovery Center respectively. GCC.9. Submission of bills for payment : GCC.9.1. GCC.9.2. Bills shall be prepared on quarterly basis for AMC charges only. The bills shall be submitted after end of each three months period from the date of start of Comprehensive AMC. All the bills in triplicate with Fault clearance reports and the extracts of Corrective (as per Annexure-VIII) and Preventive maintenance records (will be finalized mutually with the Vendor after awarding the contract), Comprehensive AMC for Data Center Infrastructure of Rajarhat Data Center & Berhampore Disaster Recovery Center, WBSEDCL: Tender Notice No. : IT&C/80/584 dated.10.09.2015 Page 26 GCC.9.3. GCC.10. as a proof of satisfactory performance of the contract shall be submitted to the IT & C Cell by the Vendor. Bills in triplicate, fault clearance reports and Corrective and Preventive maintenance records shall be certified by the concerned Consignee & Supervising Officer and countersigned by Controlling Officer. Terms of Payment: GCC.10.1.1. GCC.10.1.2. GCC.10.1.3. GCC.1.1.1. GCC.11. No advance payment shall be made against CAMC. Payment will be released only after submission of BG on CAMC. The CAMC charges shall be paid by WBSEDCL on quarterly basis at the end of each three monthly period from the date of start of CAMC. The payments will be made after deducting penalties if any, based on the fault clearance reports. Payment will be released after completion of scheduled preventive maintenance service for the particular period based on the reports of Corrective and Preventive maintenance records. WBSEDCL personnel for liaison : GCC.1.2. GCC.1.3. GCC.1.4. GCC.1.5. Controlling Officer: Addl. Chief Engineer, IT & C Cell. Supervising Officer for Data Center: Superintendent Engineer (E) & In-Charge of the Data Center –He shall be the Consignee and Supervising Officer of the entire CAMC work at Data Center. Supervising Officer for Disaster Recovery Center:- : Assistant Engineer (IT&C) & In-Charge of the Disaster Recovery Center –He shall be the Consignee and Supervising Officer of the entire CAMC work at Disaster Recovery Center. Paying Authority: - Manager(F&A), Establishment-Corporate, Bidyut Bhawan, WBSEDCL. GCC.12. Enclosure: 1. Annexure-I : Format of Bid Proposal 2. Annexure-II: Mandatory Condition 3. Annexure-IIA: Schedule of Bids 4. Annexure-IIB: Summary statement of average annual turnover 5. Annexure-IIC: Summary statement of Order Executed. 6. Annexure-III: Bid Guarantee-EMD-Format of BG. 7. Annexure-IVA: Undertaking. 8. Annexure-IVB: Letter of Bid. 9. BoqAnnexureV:-Price Bid Format 10. Annexure- VI: Format of Performance Bid Guarantee 11. Annexure-VII:A: Equipment List for Electrical System for DC. 12. Annexure-VII:B: Equipment List for HVAC System for DC. 13. Annexure-VII:C: Equipment List for BMS System for DC. 14. Annexure-VII:D: Equipment List for Electrical System for DRC. 15. Annexure-VII:E: Equipment List for HVAC System for DRC. 16. Annexure-VII:F: Equipment List for BMS System for DRC. 17. Annexure-VIII: Log Book for corrective maintenance. Comprehensive AMC for Data Center Infrastructure of Rajarhat Data Center & Berhampore Disaster Recovery Center, WBSEDCL: Tender Notice No. : IT&C/80/584 dated.10.09.2015 Page 27 ANNEXURE-I BID PROPOSAL From Bidder's Name and Address : Contact person : Designation : Telephone No.(Land Line & mobile) : Fax : Tender Reference : To The Chief Engineer, IT & C Cell, West Bengal State Electricity Distribution Company Limited, 3rd Floor, Block’D’, Vidyut Bhavan., Bidhannagar, Kolkata- 700 09l. Sub. : Invitation to bid for Comprehensive Annual Maintenance Contract of Data Center Infrastructure for Central Data Center Rajarhat & Disaster Recovery Center, Berhampore,WBSEDCL. Dear Sir, 1. We the undersigned Bidder/(s), having read and examined in details the specifications and other documents of the subject Tender, do hereby propose to execute the contract as per specification as set forth in your Bid-Document. 2. PRICES AND VALIDITY : 2.1. The rate of Comprehensive Annual Maintenance contract service for the infrastructure of Data Center, Rajarhat & Disaster Recovery Center, Berhampore, WBSEDCL are FIRM during the entire period of Annual Maintenance Contract and not subject to any price adjustment as per in line with the Bidding Documents. All prices and other terms and conditions of this proposal are valid for a period of 180 (one hundred eighty) days from the date of opening of the price bids. We further declare that prices stated in our proposal are in accordance with your bidding. 2.2. We confirm that our bid prices include all other taxes and duties and levies applicable for CAMC services and components, materials, equipments and other items bought out for the CAMC services and confirm that any such taxes, duties and levies additionally payable shall be to our account. 2.3. All duties & taxes such as excise duty, sales tax (but not Surcharge in lieu of Sales Tax), Service Tax, Local Tax and other Levies, if any, applicable on transaction from us to you payable extra by you against production of documentary evidence to be submitted by us. 3. BID GUARANTEE : Comprehensive AMC for Data Center Infrastructure of Rajarhat Data Center & Berhampore Disaster Recovery Center, WBSEDCL Tender Notice No. : IT&C/80/584 dated 10.09.2015 Page:28 We have enclosed a Bid Guarantee in the form of Bank Guarantee from ……………………………………….drawn in favour of WBSEDCL for an amount of Rs.............................. 4. DEVIATIONS : We declare that contract shall be executed strictly in accordance with the specifications and documents except for the deviations, all of which have been detailed out exhaustively in our deviation schedules, in volume irrespective of whatever has been stated to the contrary any where else in our proposal. Further, we agree that additional conditions, deviations, if any, found in the proposal documents other than those stated in our Deviation Schedules, save that pertaining to any rebates offered, shall not be given effect to. 5. WORK SCHEDULE : If this proposal is accepted by you, we agree to provide services and complete the entire work, in accordance with maintenance schedule indicated in the proposal, if contract will be awarded. The maintenance schedule of the various major key phases of the work will be as per maintenance Schedule submitted by us and approved by WBSEDCL in order to perform the maintenance schedule of bid documents. 6. CONTRACT PERFORMANCE GUARANTEE : We further agree that if our proposal is accepted, we shall provide a Contract Performance Guarantee of value, equivalent to ten percent (10%) of the Contract Price as stipulated in Bid document in the form of Bank Guarantee (Please specify the form of guarantee) in your favour within 15 (Fifteen) days from the date of placement of Letter of Award. Dated..................this.................day of............2015 Thanking you, we remain, Yours faithfully, Date _____________ Place ____________ (Signature) ___________________ (Printed Name) ________________ (Designation) _________________ (Common Seal) _______________ Business Address: Name & Address of Authorized Signatory: Comprehensive AMC for Data Center Infrastructure of Rajarhat Data Center & Berhampore Disaster Recovery Center, WBSEDCL Tender Notice No. : IT&C/80/584 dated 10.09.2015 Page:29 ANNEXURE-II Mandatory Condition Sl No. 1 2 3 4 Requisite Credential Requisite Supporting document Submitt ed Yes/No The bidder should not have been An undertaking in this regard should be blacklisted from any Govt. organization provided by the authorized signatory of the across India in last three years. bidder. Provide the turnover in a separate sheet (as per Annexure-IIB) with Auditor’s signature along with following supporting document duly attested. i. ii. i. Income Tax Return for assessment years Average Annual Turn Over for each of 2012-’13, 2013-’14, 2014-’15. last three financial years i.e. 2011-12, iii. ii. All enclosures forming the part of Income 2012-13, 2013-14 must be at least 50 Tax Return ( as applicable). Crore. iv. iii. Complete set of audit report for Companies under Company Act 2013 and tax audit report in case of Firms or Entities other than Companies for financial years 2011-2012, 2012-2013, 2013-2014 shall be furnished. i. Satisfactory completion certificate from Experience of successful execution in the ordering authority. similar nature of work for a single order ii. Copy of Order / Agreement. of order values at least Rs. 10 Crore or iii. Statement of orders executed during Two Orders of each at least Rs. 5 Crore last three financial years (Vide Formor Three Orders of each at least 4 Crore IIC) i.e for financial years 2012-2013, during last three calendar years i.e. 20122013-2014, 2014-2015. 2013, 2013-14, 2014-15 in India in iv. Pro-rata of physical progress certified Government / Semi-Government/ PSU by the ordering authority in case of Establishments/ Reputed Private Sectors. running project. Must have capability to provide Annual Maintenance of the equipments under Electrical System, HVAC System and Building Management System efficiently. The Bidder must have a Toll Free Number/ Dedicated Land line Number for service support where user shall log complaints. The Bidder should provide Service Centre facility for all equipments including UPS, DG Sets, PAC etc available in Kolkata, West Bengal. i. Relevant valid ISO Certification for AMC Service. ii. Self-certified document describing present system of logistic support for spares preservation and movement. iii. Self-certified document describing details of computerized call docketing facility. iv. Address of Kolkata Service Centre with Telephone No. Comprehensive AMC for Data Center Infrastructure of Rajarhat Data Center & Berhampore Disaster Recovery Center, WBSEDCL Tender Notice No. : IT&C/80/584 dated. 10.09.2015 Page30 Sl No. Requisite Credential 5 Must have back-end agreement with all major OEMs regarding availability of spares during CAMC period for the equipments under Electrical System, HVAC System and Building Management System installed at the Data Center. 6 The vendor shall maintain sufficient spares in spare-bank located at Kolkata at his own cost for the CAMC entire period Self declaration for the equipments under Electrical System including UPS, HVAC System and Building Management System. 7 8 9 The Vendor shall have a registered office in Kolkata, West Bengal. The Vendor shall not have a conflict of interest that may affect the Tendering Process. Must Comply with all statutory obligations. Requisite Supporting document Submitt ed Yes/No Attested Agreement copies confirming next six years comprehensive support for all the equipments related to Data Center Infrastructure. A documentary proof with complete address details and contact person details. Self Declaration in line with clause no IB.21. Provide the following required nos. in a separate sheet (as per Annexure-IIA) duly attested with following supporting documents. i. PF and ESI (if applicable) Registration Certificate ii. Copy of PAN Card. iii. Valid Professional Tax Registration certificate. iv. VAT Registration Certificate.. v. Service Tax Registration No. vi. Trade License No with Certificate is to be submitted by the Bidder. vii. Registration No with Certificate of Incorporation as a Company under Companies Act 1956 (substituted by Companies Act 2013) for more than 5 (five) years ending 31.03.2015. Valid ISO 9001:2008 certification, in case of Original Equipment Manufacturer 10 (OEM), valid ISO 14001 certification Attested Copy of valid certificates. And valid ISO 20000-1:2011 certification. N.B. : Each page of all the documents/copy of certificates should be submitted with attestation by the authorized signatory and with seal & date. Signature of the bidder with Office Seal Dated----------------------Comprehensive AMC for Data Center Infrastructure of Rajarhat Data Center & Berhampore Disaster Recovery Center, WBSEDCL Tender Notice No. : IT&C/80/584 dated. 10.09.2015 Page31 Annexure - IIA SCHEDULE OF BIDS : 1. Name of the tenderer with office address Tel No./Fax no./E.mail address : 2. Address of Kolkata office and Tel no./Fax no./ Email address with the name of contact person 3 Contact Person with Telephone No., Mobile No., E-mail ID and FAX No. of the Bidder Tender Fee Details (Amount in the form of DD/ Pay Order/ Banker’s Cheque) Earnest Money (Amount and in the form of BG/DD/PAY ORDER) submitted : Details of Earnest Money in BG/DD/Pay Order as submitted: : 4. 5. 6. 7. Category of organisation : : : 8. Company Registration No. : 9. PF/ESI Registration No. & valid upto ( a copy should be enclosed) Valid Trade License No. Service Tax registration No. Professional Tax Registration No. VAT Registration No. PAN Card No. Whether agreed to (YES/NO): : a) Terms of Payment b) Earnest Money clause c) Risk purchase clause d) Liquidated damage clause Offer valid upto : : : : : The price should be Firm. : 10. 11. 12. 13. 14. 15. 16. 17. : : : : 150 days from the date of opening of Technical Part of the Tender. The Prices are Firm. ( Signature and Seal of Tenderer ) Dated----------------------- Comprehensive AMC for Data Center Infrastructure of Rajarhat Data Center & Berhampore Disaster Recovery Center, WBSEDCL Tender Notice No. : IT&C/80/584 dated. 10.09.2015 Page32 Annexure - IIB Certificate regarding Summary Statement of Yearly Turnover This is to certify that the following statement is the summary of the audit report /tax audit report arrived in favour of . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . for the three consecutive years or for such period since inception of the Firm, if it was set in less than such three year's period. Financial Sl. No. Year 1. 2011-12 2. 2012-13 3. 2013-14 Turnover rounded up to two digit after decimal (Rs. In Lakh) Remarks Total Average Turnover: Note: 1. Year proceeding the current financial year is to be considered as Year-1. 2. Average turnover is to be expressed in lakh of rupees, rounded up to two digits after decimal. 3. Average turnover for 3 years is to be obtained by dividing the total turnover by 3.0. If the Firm was set up in less than 3 year's period, consider the turnover for the period from inception to the Year-1. It may be either 1.0 or 2.0. Average turnover is to be obtained by dividing the total turnover by 1.0 or 2.0, as the case may be. 4. In case, the firm was set up in less than 3 year's period, mention the year of inception in the ‘Remarks’ column. (Signature with Designation & Seal) Dated----------------------- Comprehensive AMC for Data Center Infrastructure of Rajarhat Data Center & Berhampore Disaster Recovery Center, WBSEDCL: Tender Notice No. : IT&C/80/584 dated 10.09.2015 Page33 Annexure - IIC STATEMENT OF ORDERS EXECUTED DURING LAST THREE FINANCIAL YEARS (20122013, 2013-2014, 2014-2015) REGARDING COMPREHENSIVE ANNUAL MAINTENANCE CONTRACT FOR DATA CENTER INFRASTRUCTURE. Sl. No. Work Description Financial year Order No. and date Name order issuing authority Order Value in Rs. Scanned Copy of Performance report of the order submitted or Not (YES/NO) Remarks …………………………………………………………………… (SIGNATURE OF THE TENDERER WITH OFFICE SEAL) Dated----------------------- Comprehensive AMC for Data Center Infrastructure of Rajarhat Data Center & Berhampore Disaster Recovery Center, WBSEDCL: Tender Notice No. : IT&C/80/584 dated. 10.09.2015 Page34 ANNEXURE-III PROFORMA OF BANK GUARANTEE FOR BID GUARANTEE (Earnest Money) (To be stamped in accordance with Stamp Act) Ref. No. : Date : To The West Bengal State Electricity Distribution Company Limited Vidyut Bhawan DJ Block, Sector - II Salt Lake, Kolkata - 700 091 Dear Sirs, In accordance with your Notice Inviting Tender (NIT) under your Specification No._______ M/s ____________________________ having its Registered Head Office at _________________________ (hereinafter called the Bidder) wish to participate in the said Tender for __________________________. As an irrevocable Bank Guarantee against Bid Guarantee for an amount of ____ is required to be submitted by the Bidder as a condition precedent for participation in the said Tender, which amount is liable to be forfeited on the happening of any contingencies mentioned in the Tender Documents. We, the ____________ Bank at _____________ having our Head Office at ________________ (Address of Bank) guarantee and undertake to pay immediately on demand by West Bengal State Electricity Distribution Company Limited the amount of __________ (in words and figures) without any reservation, protest, demur and recourse. Any such demand made by said Purchaser shall be conclusive and binding on us irrespective of any dispute of difference raised by the Bidder. This Guarantee shall be irrevocable and shall remain valid up to **_________. If any further extension of this guarantee is required, the same shall be extended to such required period on receiving instructions from M/s ____________________ on whose behalf this Guarantee is issued. All rights of West Bengal State Electricity Distribution Company Limited under this Guarantee shall be forfeited and the Bank shall be relieved and discharged from all liabilities there under unless WBSEDCL enforce a claim under this Guarantee against the Bank within three months from the above mentioned expiry date of validity or, from that of the extended date. In witness whereof the Bank, through its authorized Officer, has set its hand and stamp on this __________ day of __________ 2015 ___ at ____________. WITNESS: ____________________________ (Signature) ________________________________________ ________________________________________ (Name) ________________________________________ ________________________________________ (Official address) Attorney as per Power of Attorney No. Date ___________________________ (Signature) (Name) (Designation with Bank Stamp) ___________________________ ___________________________ ** This date should be initially for one hundred eighty (180) days and may be extended from time to time. Comprehensive AMC for Data Center Infrastructure of Rajarhat Data Center & Berhampore Disaster Recovery Center, WBSEDCL: Tender Notice No. : IT&C/80/584 dated. 10.09.2015 Page 35 ANNEXURE-IVA PROFORMA FOR UNDERTAKING TO BE SUBMITTED BY THE BIDDER (For genuineness of the information furnished on-line and authenticity of the documents produced before Tender Committee for verification in support of his eligibility) I --------------------------------------------------, Partner/Legal Attorney/ Accredited Representative of M/s ---------------------------------------------------------------------, solemnly declare that: 1. We are submitting Tender for the Work ---------------------------------------------------------- against Tender Notice No. ---------------------------------------------- dt. -----------------------2. None of the Partners of our firm is relative of employee of ------------------------------------ (Name of the Company). 3. All information furnished by us in respect of fulfilment of eligibility criteria and qualification information of this Tender is complete, correct and true. 4. All documents/ credentials submitted along with this Tender are genuine, authentic, true and valid. 5. If any information and document submitted is found to be false/ incorrect any time, department may cancel my Tender and action as deemed fit may be taken against us, including termination of the contract, forfeiture of all dues including Earnest Money and banning / delisting of our firm and all partners of the firm etc. (Signature of the Tenderer with Seal ) Dated----------------------- Comprehensive AMC for Data Center Infrastructure of Rajarhat Data Center & Berhampore Disaster Recovery Center, WBSEDCL Tender Notice No. : IT&C/80/584 dated. 10.09.2015 Page36 Annexure – IVB FORMAT OF LETTER OF BID LETTER HEAD OF BIDDER (AS ENROLLED ONLINE ON e-Tendering PORTAL OF NIC) To, The Tender Committee, Sub: Letter of Bid for the work --------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------Ref: 1. NIeT No ------------------------------------------------------------- dated --------------2. Tender Id No. ---------------------------------------------------Dear Sir, We offer to execute the work as per our offered bill of quantity in accordance with the conditions of the NIeT document as available in the website. The details of the EMD being submitted by us has been furnished on-line. This Bid and your subsequent Letter of Acceptance / Work Order shall constitute a binding contract between us. We hereby confirm our acceptance of all terms and conditions of the NIeT document unconditionally. (Signature of the Tenderer with Seal) Dated----------------------- Comprehensive AMC for Data Center Infrastructure of Rajarhat Data Center & Berhampore Disaster Recovery Center, WBSEDCL Tender Notice No. : IT&C/80/584 dated. 10.09.2015 Page37 Annexure -V Tender Inviting Authority:Chief Engineer, IT&C Cell, WBSEDCL Name of Work: AMC for Data Center Infrastructure installed at Data Center, Rajarhat and Disaster Recovery Center Berhampore ,WBSEDCL NIT Ref No.: IT&C/80/584 Dated : 10/09/2015 Bidder Name : SCHEDULE OF WORKS (This BoQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only) Sl. No. Description of work RATE In Figures To be entered by the Bidder Rs. P Figures 1.00 All equipments under Electrical System, HVAC System and Building Management System including UPS, DG Set, PAC installed at the Data Centre, Rajarhat, WBSEDCL. 2.00 3.00 4.00 All equipments under Electrical System, HVAC System and Building Management System including UPS, DG Set, PAC installed at the Data Centre, Rajarhat, WBSEDCL. ( 2nd Year) All equipments under Electrical System, HVAC System and Building Management System including UPS, DG Set, PAC installed at the Data Centre, Rajarhat, WBSEDCL. (3rd Year) All equipments under Electrical System, HVAC System and Building Management System including UPS, DG Set, PAC installed at the Disaster Recovery Centre, 0.00 0.00 Rupees only 0.00 0.00 Rupees only 0.00 0.00 Rupees only 0.00 0.00 Rupees only 0.00 0.00 Rupees only 0.00 (1st Year) All equipments under Electrical System, HVAC System and Building Management System including UPS, DG Set, PAC installed at the Disaster Recovery Centre, Berhampore, WBSEDCL. 6.00 Words 0.00 Rupees only (1st Year) Berhampore, WBSEDCL. 5.00 AMOUNT Rs. P (2nd Year) All equipments under Electrical System, HVAC System and Building Management System including UPS, DG Set, PAC installed at the Disaster Recovery Centre, Berhampore, WBSEDCL. (3rd Year) 0.00 Total in Figures Total in Words Signature of Tenderer with seal Rupees only Page:[38] BoqAnnexureV.xls Tender Inviting Authority:Chief Engineer, IT&C Cell, WBSEDCL Annexure-V BoQ_Ver2.0 Name of Work: AMC for Data Center Infrastructure installed at Data Center, Rajarhat and Disaster Recovery Center Berhampore ,WBSEDCL NIT Ref No.: IT&C/80/584 Dated : 10/09/2015 Bidder Name: PRICE SCHEDULE (This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only) Sl. No. Item Description Item Code / Make Basic Price (in. Rs.) 1 2 3 7 1.00 All equipments under Electrical System, HVAC System and Building Management System including UPS, DG Set, PAC installed at the Data Centre, Rajarhat, 2.00 3.00 4.00 WBSEDCL. (1st Year) All equipments under Electrical System, HVAC System and Building Management System including UPS, DG Set, PAC installed at the Data Centre, Rajarhat, WBSEDCL. ( 2nd Year) All equipments under Electrical System, HVAC System and Building Management System including UPS, DG Set, PAC installed at the Data Centre, Rajarhat, WBSEDCL. (3rd Year) All equipments under Electrical System, HVAC System and Building Management System including UPS, DG Set, PAC installed at the Disaster Recovery Centre, Berhampore, WBSEDCL. 5.00 6.00 1st Year 0.00 2nd Year 0.00 3rd Year 0.00 1st Year 0.00 2nd Year 0.00 3rd Year (3rd Year) ***Total in Figures Signature of Tenderer with seal 16 0.00 (2nd Year) All equipments under Electrical System, HVAC System and Building Management System including UPS, DG Set, PAC installed at the Disaster Recovery Centre, Berhampore, WBSEDCL. 12 (1st Year) All equipments under Electrical System, HVAC System and Building Management System including UPS, DG Set, PAC installed at the Disaster Recovery Centre, Berhampore, WBSEDCL. Service Tax (in Total Amount In Rs) Rs. G+L 0.00 Page:[39] BoqAnnexureV.xls ANNEXURE-VI PROFORMA FOR BANK GUARANTEE FOR CONTRACT PERFORMANCE (To be stamped in accordance with Stamp Act) Bank Guarantee No.__________ Ref No.______________ Date : _____________ To The West Bengal State Electricity Distribution Company Limited, Vidyut Bhavan, Salt Lake, DJ Block, Sector-II, Kolkata -700 09l (India). Dear Sir, In consideration of West Bengal State Electricity Distribution Company Limited (hereinafter referred to as WBSEDCL) which expression shall unless repugnant to the context or meaning thereof include its successors, administrators and assigns having awarded to M/s _________________________________ with its Registered/Head Office at ______________________________ (hereinafter referred to as the 'Contractor') which expression shall unless repugnant to the context or meaning thereof, include its successors, administrators, executors and assigns, a Contract by issue of Order No._____ dated_________ valued at_________________________ for_________________ (Scope of Contract) and the Contractor having agreed to provide a Contract Performance Guarantee for the faithful performance of the AMC Service to *-----%(percent) of the value of the entire AMC Service vide Order No. ........................ date .....................(reference of original order), against Contract to WBSEDCL. We ____________________________(Name and Address) having its Head Office at________________________________ hereinafter referred to as the `Bank') which expression shall, unless repugnant to the context or meaning thereof include its successors, administrators, executors and assigns do hereby guarantee and undertake to pay WBSEDCL, on demand any and all moneys payable by the Contract to the extent of _________________as aforesaid at any time upto (day/month/year) without any demur, reservation, contest recourse or protest and or without any reference to the Contractor. Any such demand made by WBSEDCL on the Bank shall be conclusive and binding notwithstanding any difference between WBSEDCL and the Contractor or any dispute pending before any before any Court, Tribunal or any other Authority. The Bank undertakes not to revoke this guarantee during its currency without previous consent of WBSEDCL and further agrees that the guarantee herein contained shall continue to be enforceable till the WBSEDCL discharges this guarantee. WBSEDCL shall have the fullest liberty without affecting in any way the liability of the Bank under this guarantee from time to time extend the time for performance of the Contract by the Contractor. WBSEDCL, shall have the fullest liberty, without affecting this guarantee to postpone from time to time the exercise of any powers vested in them or of any right which they might have against the Contractor and to exercise the same at any time and any manner, and either to enforce or to forbear to enforce any covenants, contained or implied in the Contract between WBSEDCL and the Contractor or any other course of remedy or security available to WBSEDCL. The Bank shall not be released of its obligations under this presents by any exercise by WBSEDCL of its liberty with reference to the matters aforesaid or any of them or by reason or any other acts of omission or commission on the part of WBSEDCL or any other indulgence shown by WBSEDCL or by any other matter or thing whatsoever which under the law would but for this provisions have the effect of relieving the Bank. The Bank also agrees that WBSEDCL at its option shall be entitled to enforce this guarantee against the Bank as a Principal debtor, in the first instance without proceeding against the Contractor and notwithstanding any security or other guarantee that WBSEDCL may have in relation to the contractor's liabilities. Notwithstanding anything contained herein above our liability under this guarantee is restricted to____________ and shall remain in force up to and including_______________ and shall be extended from time to time for such period, as may be desired by M/s.____________________________________ to whose behalf this guarantee has been given. All rights of WBSEDCL under this guarantee shall be forfeited and the Bank shall be relieved and discharged from all liabilities there under unless the WBSEDCL enforce a claim under this guarantee against the Bank within three months from the above mentioned date or from the extended date. Dated this ______________day of______________2015 ___ at _____________________ Witness : ________________________ ___________________________ (Signature) (Signature) _______________________ (Name) _______________________ (Official address) ____________________________ (Name) _____________________________ (Designation with Bank Stamp) _____________________________ Attorney as per Power of Attorney No.____________ Date____________________ Comprehensive AMC for Data Center Infrastructure of Rajarhat Data Center & Berhampore Disaster Recovery Center, WBSEDCL Tender Notice No. : IT&C/80/584 dated. 10.09.2015 Page 40 Annexure-VII: A DATA CENTRE INFRASTRUCTURE OF WBSEDCL AT NEW TOWN, RAJARHAT EQUIPMENTS AND COMPONENTS UNDER ELECTRICAL SYSTEM Sl. No. Description Make/ Type/ Quantity Model (1) 1 1.1 (2) DG AND SYNCHRONISING-CUM-LOAD MANAGING PANEL Diesel Generator Set (RADIATOR TYPE with Acoustical Enclosure) (4) (3) 2 Sets 100 mm dia exhaust pipe 50 Mtr 150 mm dia exhaust pipe complete with: i) Thermal insulation with TF quality (thickness as required but min of 75mm thick) Vendors must confirm the same for its compliance and obtain all necessary approvals. And no separate payment shall be made of approvals. ii) Aluminium cladding(22g). iii) All M.S. support as required to support the DG exhaust pipe as per site condition (no separate payment shall be made for the supports) 150 Mtr 1 Set Electro Allied Products(EAP) 2 Sets Electro Allied Products(EAP) 2 Electro Allied Products(EAP) 2 Jaksons 630KVA / 504 KW at 0.8 PF 415V 3 Ph 50 Hz Diesel Generating Set continuously rated for unlimited no.of hours @ 100% load factor including all accessories complete with: i) Rubber-in-shear vibration mounts ii) Starting battery & leads & charger panel iii) Residential duty silencer with flanges. iv) Flexible connections v) Foundation bolts vi) Radiator heat exchanger with all accessories. vii) Auto DG Synchronisation Kit and Auto Load dependent start stop system. 1.2 Synchronising Panel AMF, Synchronisation, Logic Control (PLC Based) in IP42 with generator control unit MS Enclosure Powder coated to be mounted separately with all necessary components and Jaksons accessories as specified 2.0 PANELS AND DISTRIBUTION BOARDS 2.1 Main LT Panel with following feeder particulars Incomer 1000A 4P EDO ACB 50KA --- 1No. with communication port RS 485 and 1No 250KA TVSS Outgoing 400A TP MCCB 35A: 2 Nos. (as an additional feeder as spare) Sets 400A TP MCCB 35KA : 2Nos. (For PAC Panel & 160 KVA UPS) 160A TP MCCB 35KA : 1No. (For Utility Panel) 40A 4P MCB : 2Nos. (For 10 KVA UPS and Spare) With Load Manager, Phase , On, Off and Trip Indicators 1200A 4P Copper Bus Bar 2.2 PAC Panel Sets with following feeder particulars Incomer 400A 4P MCCB 35KA : 1No. with communication port RS 485 and 1No 160KA TVSS Outgoing 63A 4P MCB : 10Nos. (For 8 Nos 8TR PAC and spare) DC_and_DRC_InfrastructureEquipmentsDetailsAnnexureVII.xls Page (41) Annexure-VII: A DATA CENTRE INFRASTRUCTURE OF WBSEDCL AT NEW TOWN, RAJARHAT EQUIPMENTS AND COMPONENTS UNDER ELECTRICAL SYSTEM Sl. No. Make/ Type/ Description Quantity Model (1) (2) (4) (3) 40A 4P MCB : 6Nos. (For 4 Nos 8TR PAC and spare) With Load Manager, Phase , On, Off and Trip Indicators 600A 4P AL Bus Bar 2.3 Emerson Precision Power Centre for 160 KVA UPS Incomer 400A 4P MCCB 35KA : 1No. with communication port RS 485 with 1No 160KA TVSS with 200KVA Isolation Tfr, if required Outgoings 32A DP MCB : 30Nos. (For 25 Nos Server racks and spare) With Load Manager for all electrical parameters, Alarm Indicator, Phase ON, OFF and TRIP indicator and Branch circuit monitering. 600A 4P Cu Bus Bar 2 Sets 2.4 A.C. Utility Panel Electro Allied Products(EAP) 1 Set ABB 1 Set Incomer 160A 4P MCCB 35KA : 2Nos. with communication port RS 485 Buscoupler 160A 4P MCCB 35KA : 1No Outgoing 63A 4P MCB : 4Nos. (For 2 Nos PDB and spare) 40A 4P MCB : 4Nos. (For 2 Nos LDB and spare) 32A DP MCB : 16Nos. (For 10 Nos Comfort AC and spare) With Load Manager, Phase , On, Off and Trip Indicators 250A 4P AL Bus Bar 2.5 Utility Output DB for 10 KVA UPS 16 Way double door SPN DB Incomer 63A DP MCB : 1No. Outgoings 10A SP MCB:12Nos. (for Emergency Light, Security Load etc.) 16A SP MCB : 4Nos. (for Computers etc.) 2.6 LDB for Lighting points 8 way/phase TPN DB Double door Incomer 40A TPN MCB ; 1no. Outgoing : 10A/16A SP MCB : 24 nos. ABB 2 Set 2.7 PDB for Power points 8 way/phase TPN DB Double door Incomer 63A TPN MCB 1no. Outgoing :10A/16A/32A SP MCB 24 nos. ABB 2 Set DC_and_DRC_InfrastructureEquipmentsDetailsAnnexureVII.xls Page (42) Annexure-VII: A DATA CENTRE INFRASTRUCTURE OF WBSEDCL AT NEW TOWN, RAJARHAT EQUIPMENTS AND COMPONENTS UNDER ELECTRICAL SYSTEM Sl. No. Description Make/ Type/ Quantity Model (1) 2.8 2.9 (2) 1000A FP ATS with overlapping neutral and bypass circuit With BMS Compatibility in an enclosure with double input and single output as per the specification (Equiv. to ASCO EMERSON 7000 series) 70A FP ATS with overlapping neutral in an enclosure with double input and single output EMERSON as per the specification (Equiv. to ASCO 300 series) 2.10 32A DP Push type Starter Switch for Comfort AC units as per the specification 3 3.1 3.2 3.3 3.4 3.5 3.6 3.7 4 4.1 (4) (3) Schiender Supply of CABLE TRAYS. 70mm x 450 mm wide MS perforated poweder coated 70mm x 300 mm wide MS perforated poweder coated 70mm x 200 mm wide MS perforated powder coated 50mm x 150 mm wide MS perforated powder coated 70mm x 450 mm wide GI ladder type poweder coated 70mm x 300 mm wide GI ladder type poweder coated 70mm x 200 mm wide GI Ladder powdercoated Supply of CABLES AND TERMINATION KITS. POWER CABLES 2 Nos 12 Nos 10 Nos 50 50 50 50 40 30 30 Mtr Mtr Mtr Mtr Mtr Mtr Mtr 600 Mtr 70 Mtr 300 Mtr 30 Mtr 70 Mtr 25 Mtr 180 Mtr 100 Mtr 100 Mtr 500 Mtr 1000 Mtr 1 Lot 16 Nos 4 40 6 20 4 72 8 120 Nos Nos Nos Nos Nos Nos Nos Nos 4.1.1 From Transformer to ATS , DG to Sync Panel, Sync Panel to ATS, ATS to DC LT Panel 4.3 4.3.1 31/2C X 300 sqmm Al, XLPE, Armoured From DC LT Panel to PAC Panels 31/2C X 240 sqmm Al, XLPE, Armoured From DC LT Panel to 160KVA UPS, UPS to PDU 1C x 150 sqmm copper flexible From 10KVA UPS to Output DB 1C x 16 sqmm copper flexible From DC LT Panel to 10KVA UPS 1C x 10 sqmm copper flexible From DC LT Panel to Utility Panel 4C X 50 Sqmm Copper arm Cable From PAC Panel to PEC C/O and then to PAC Units 4C X 16 Sqmm Copper arm Cable From Utility Panel to 2Nos LDB 4C X 6 Sqmm Copper arm Cable From Utility Panel to 2Nos PDB 4C X 6 Sqmm Copper arm Cable From Utility Panel to Comfort AC 3C X 6 Sqmm Copper arm Cable From PDU to Server Rack Cables 3C X 6 sqmm Cu Flexible FRLS Cable CONTROL CABLES 1100V grade multicore PVC insulated and sheathed armoured stranded copper conductor cables (furnish length, size, cores & particulars of each type of cables during detail engg.) Termination kits for Cable Termination for 31/2C x 300 AYWY 4.3.2 4.3.3 4.3.4 4.3.5 4.3.6 4.3.7 4.3.8 4.3.9 Termination for 31/2C x 240 AYWY Termination for 1C x 150 YY Termination for 1C x 16 YY Termination for 1C x 10 YY Termination for 4C x 50 YWY Termination for 4C x 16 YWY Termination for 4C x 6 YWY Termination for 3C x 6 YY 4.1.2 4.1.3 4.1.4 4.1.5 4.1.6 4.1.7 4.1.8 4.1.9 4.1.10 4.1.11 4.2 5 Supply related to POINT WIRING AND CONDUITING WORK DC_and_DRC_InfrastructureEquipmentsDetailsAnnexureVII.xls Page (43) Annexure-VII: A DATA CENTRE INFRASTRUCTURE OF WBSEDCL AT NEW TOWN, RAJARHAT EQUIPMENTS AND COMPONENTS UNDER ELECTRICAL SYSTEM Sl. No. Description Make/ Type/ Quantity Model (1) 5.1 5.2 5.3 5.4 5.5 5.6 5.7 6 6.1 6.2 6.3 (2) (4) (3) Primary point from MCB/ 5A Switch for lighting with 3 x 1.5 sqmm wire Secondary Point Looped from item 4.2 Primary point for Raw power with (2 x 4) + (1 x 2.5) sqmm wire Secondary point looped from item 4.4 5A Switch with plate and back box 5/15A Socket + 15 A switch with all accessareis 3 nos 5 Pin 5A Socket + 15 A switch with all accessareis 30 40 30 25 20 30 50 Nos Nos Nos Nos Nos Nos Nos 125 nos. 15 nos 20 nos. 60 Nos 8 nos 400 80 300 300 mtr mtr mtr mtr 6 nos LIGHTING FIXTURES & AND ACCESSORIES. 2 x 36 watts 2' x 2' Ceiling suspended recess mounted light fixtures with Tubes and all Wipro accessories (Equiv. to Wipro WVP 24236 SGW) PL Fittings 2 x18 watts with Tubes and all accessories (Equiv. to Wipro WCP 42218 Wipro SGW) 1 x 40 watts industrial type Double tube fitting with all accessories (Equiv. to Wipro WIF Wipro 14140 SGW) Notes: The rates for lighting fixtures and fans shall include all accessories and supply of all materials that may be required to make the fixture complete in all respects. All the fixtures shall be suitable for single phase, 50 cycles, 230 Volts, AC supply system. All light fixtures shall be provided with Electronic ballast as described in the schedule. All fixtures shall be factory wired with copper conductor wires. All fixtures shall be supplied with fluorescent lamps/incandescent bulbs or any other special type bulbs as called for in the item. All the fixtures shall be quoted of approved make only. 7 8 8.1 8.2 8.3 8.4 8.5 8.6 INDUSTRIAL SOCKETS AND HOUSING 32A DP+E Industrial Sockets and straight plugs of IP 44 type and of approved make in Legrand a sheet steel enclosure with 32A DP MCB EARTHING AND EARTHING STRIPS. Earthing pits with 600 x 600 x 6mm Copper Plate earth upto 10 feet deep with all accessories 6 sqmm braided copper tape for grid earthing 8 swg bare cu wire 25 x 3 copper Strip for Earthing of panel 1c x 150 sqmm cu flexible (Green Colour) wire/cable Dedicated Eathing Box of 50mm x 10mm x 200mm complete with 50mm x 6 Tinned copper strip with 6mm holes DC_and_DRC_InfrastructureEquipmentsDetailsAnnexureVII.xls Page (44) Annexure-VII: B DATA CENTRE INFRASTRUCTURE OF WBSEDCL AT NEW TOWN, RAJARHAT EQUIPMENTS AND COMPONENTS UNDER HVAC SYSTEM Sl. No. Description Make/ Type/ Quantity Model (1) (2) (4) (3) PAC UNITS Precision Air Conditioning (PAC) Units of Libert PeX Model with inert gas based refrigerant in compliance to Kiyoto protocol each of 8 TR complete with instruments, gauges, microprocessor controller and other accessories complete for precision air-conditioning of electronic control equipment at data centre Server Room in N+1 configuration Precision Air Conditioning (PAC) Units of Libert PeX Model with inert gas based refrigerant in compliance to Kiyoto protocol each of 9.5 TR complete with instruments, gauges, microprocessor controller and other accessories complete for precision air-conditioning of electronic control equipment at data centre Power Room -I (UPS/Electrical Room) in N+1 configuration Emerson 56 TR Emerson 9.5 TR 2b Precision Air Conditioning (PAC) Units of Libert PeX Model with inert gas based refrigerant in compliance to Kiyoto protocol each of 9.5 TR complete with instruments, gauges, microprocessor controller and other accessories complete for precision air-conditioning of electronic control equipment at data centre Power Room -II (UPS/Electrical Room) in N+1 configuration Emerson 9.5 TR 3 Liquid Crystal Thermometer Strips with acrylic self adhesive backing to measure quick and accurate air temperatures by showing colors as blue/green/yellow and red as per acceptable temperature standards defined by Uptime Institute inside the Data Centre Hall. Blue Star 16 Nos 4 Split type non-ductible Refrigeration Unit each of 1.5 TR with Air-cooled condensing unit, room unit, interconnecting refrigerant pipe, protection and temperature & humidity control panel, instruments, gauges and other accessories complete for air-conditioning of electronic control equipment at data centre rooms excepting Server Room and Electrical Room Blue Star 30(20 Nos) TR 5 Set of Thermometer & Humidity Meter Blue Star 3 Sets 1 2a COMFORT AC UNITS DC_and_DRC_InfrastructureEquipmentsDetailsAnnexureVII.xls Page (45) Annexure-VII: C DATA CENTRE INFRASTRUCTURE OF WBSEDCL AT NEW TOWN, RAJARHAT EQUIPMENTS AND COMPONENTS UNDER BUILDING MANAGEMENT SYSTEM (BMS) SYSTEM Sl. No. Make/ Type/ Description Quantity Model (1) (2) A BUILDING MANAGEMENT SYSTEM BMS Workstation, Pentium IV 833MHz, 20GB HDD, 256MB RAM, 52X CD ROM drive 1.44 FDD, 14" colour monitor, Microsoft Bus Mouse, 2 serial, 1 parallel port & Windows NT operating system Network Controller DDC Controller Integrator for Precision AC Units on MODBUS RTU protocol Integration Software for UPS on MODBUS RTU protocol Integration Software for DG Sets on MODBUS RTU protocol Integrated Intelligent building management server software having capacity to accomodate points (hardware & software) and more with graphics user interface comprising of the following modules Building Management Seamless integrating all utililties Fire alarm system Software Module Access Management software Module CCTV system softwarebased integration Third party- UPS, Load manager, Precesion AC, DG set integration on Modubus Integration Software for Fire Alarm, Access Control, with Graphic User Interface for Seamless Integration with the BMS Graphics FIELD DEVICES Temperature cum Humidity Sensor with all mounting accessories 2 core 1.5 sq.mm unscreened Armoured non FRLS cable 1 3 4 5 6 7 8 8.1 a b c d 8.2 9 10 B 1 2 3 4 5 6 7 8 9 10 11 12 (4) (3) dell 1 Set Siemens Euronet Euronet Euronet 1 1 1 1 1 Set Set Set Set Set Euronet 1 Set Euronet 1 Set Siemens Teleflex 6 1000 Nos Mtrs. 1 Nos. 1 105 0 18 14 30 5 12 70 1 2200 Nos. Nos. Nos. Nos. Nos. Nos. Nos. Nos. Nos. Nos. Mtrs. ANALOGUE ADDRESSABLE FIRE ALARM SYSTEM Addressable Fire Detection Panel : 1-loop panel, each loop can handle 125 Siemens detectors & 125 Modules, with power supply. Interface gateway NIC-C Addressable multielectric Smoke Detector Siemens HFP-11 Addressable Heat Detector HFPT-11 Manuall Call Point HMS-S Strobe cum hooter MTH-MC-R Control module HTRI-R Monitor module HTRI-S FIM RI RI Emergency Glow Sign ISI 2-core, 1.5 sq. mm. Shielded armoured cable Teleflex DC_and_DRC_InfrastructureEquipmentsDetailsAnnexureVII.xls Page (46) Annexure-VII: C DATA CENTRE INFRASTRUCTURE OF WBSEDCL AT NEW TOWN, RAJARHAT EQUIPMENTS AND COMPONENTS UNDER BUILDING MANAGEMENT SYSTEM (BMS) SYSTEM Sl. No. Description Make/ Type/ Quantity Model (1) (2) (4) (3) C 1.1 1.2 SAPPHIRE - FIRE SUPPRESSION SYSTEM Sapphire for server room and Electrical Room Sapphire for BMS Room Sinorix 1230 Sinorix 1231 1 1 D 1 2 3 4 VESDA SYSTEM Single Channel Air Sampling System For Server Room PVC Pipe Fittings and Supports 24 VDC Power Supply Unit VLC-55 ISI ISI PS-2425 1 1 1 1 E 1 2 3 ACCESS CONTROL SYSTEM Main Door Controller . Proximity Card Reader Proximity Card Reader with Fingerprint Reader M5E4 HID-6005 V-PROX 1 16 6 Nos. Nos. Nos. 4 Electromagnetic Lock (Single leaf ) EML-1101 +EB-LZ10 5 Nos. 5 Magnetic contact EMC-205 16 Nos. 6 Electromagnetic Lock (Double leaf ) EML1103 +EB-LZ10 11 Nos. 7 8 9 10 11 Proximity Card - Blank Face Emergency Exit Switch Panic Bar 4-core 0.8sq. mm. Shielded cable in PVC Conduit 8-core 0.8sq. mm. Shielded cable in PVC Conduit HID-1326 ERS-G 100 9 1 1000 1600 Nos. Nos. Nos. Mtrs. Mtrs. F 1 2 WATER LEAK DETECTION SYSTEM & RODENT REPELLENT SYSTEM Water Leak Cable (10 mts each) WD-CS/10M Electronic Sounder 85db Lightak 4 Zone Water Leak Conventional Panel with Battery Charger & Battery Signet with BMS integration Rodent Repellent Console Units with Transducers suitable to cater all DC Maser area. 15 1 Nos Nos 1 LOT 1 Nos 3 4 Teleflex Teleflex DC_and_DRC_InfrastructureEquipmentsDetailsAnnexureVII.xls lot lot No Per Zone Lot No. Page (47) Annexure-VII: C DATA CENTRE INFRASTRUCTURE OF WBSEDCL AT NEW TOWN, RAJARHAT EQUIPMENTS AND COMPONENTS UNDER BUILDING MANAGEMENT SYSTEM (BMS) SYSTEM Sl. No. Make/ Type/ Description Quantity Model (1) (2) G 1 CCTV SERVELLIANCE SYSTEM PC with Monitor 1/3" Colour Dome Camera with 3.6/6 mm fixed lens for indoor application, complete with power supply unit 4 Channel Video Streamer / Encoder Rack for streamer DVM Server Digital Video Management Software RG11.armoured 2-core, 1.5 sq. mm. unscreened armoured non FRLS cable 2 3 4 5 6 7 8 H 1 2 3 4 5 6 7 8 9 (4) (3) Fujitsu 1 Nos. CFD-480 24 Nos. Tracer lite ISI IBM/Dell Euronet Dlink Teleflex 6 3 1 1 2500 1200 Nos. Nos. Nos. lot Mtrs Mtrs 36 1 1 1 1 1 1 1 Nos. 1800 Nos. PUBLIC ADDRESS SYSTEM 6 watt each with line matching transformers. LBD8352/10 Volume control units LBC400/10 240 WATT Amplifier LBD1935/00 Goose neck Microphone LBB1949 System controller with 4 Zone call station LBB1990+/56/+57 Pre amplifier pre recorded voice generator LBB1925 Professional grade DVD/ Cassete player PLN-DVDT Powder coated rack with wheels ISI Cable & Conduit : 2 core 1.5 sq mm twisted HFFR/ FRLS cu cable in Teleflex yellow colour with conduit DC_and_DRC_InfrastructureEquipmentsDetailsAnnexureVII.xls Nos. Nos. Nos. Nos. Nos. Nos. Nos. Page (48) Annexure-VII: D DISASTER RECOVERY DATA CENTRE, BERHAMPORE EQUIPMENTS AND COMPONENTS UNDER ELECTRICAL SYSTEM Sl. No. Description Make/ Type/ Quantity Model (1) 1 1.1 (2) DG AND SYNCHRONISING-CUM-LOAD MANAGING PANEL Diesel Generator Set (RADIATOR TYPE with Acoustical Enclosure) (4) (3) 2 Sets 100 mm dia exhaust pipe 50 Mtr 150 mm dia exhaust pipe complete with: i) Thermal insulation with TF quality (thickness as required but min of 75mm thick) Vendors must confirm the same for its compliance and obtain all necessary approvals. And no separate payment shall be made of approvals. ii) Aluminium cladding(22g). iii) All M.S. support as required to support the DG exhaust pipe as per site condition (no separate payment shall be made for the supports) 150 Mtr 1 Set Electro Allied Products(EAP) 2 Sets Electro Allied Products(EAP) 2 Electro Allied Products(EAP) 2 Jaksons 630KVA / 504 KW at 0.8 PF 415V 3 Ph 50 Hz Diesel Generating Set continuously rated for unlimited no.of hours @ 100% load factor including all accessories complete with: i) Rubber-in-shear vibration mounts ii) Starting battery & leads & charger panel iii) Residential duty silencer with flanges. iv) Flexible connections v) Foundation bolts vi) Radiator heat exchanger with all accessories. vii) Auto DG Synchronisation Kit and Auto Load dependent start stop system. 1.2 Synchronising Panel AMF, Synchronisation, Logic Control (PLC Based) in IP42 with generator control unit MS Enclosure Powder coated to be mounted separately with all necessary components and Jaksons accessories as specified 2.0 PANELS AND DISTRIBUTION BOARDS 2.1 Main LT Panel with following feeder particulars Incomer 1000A 4P EDO ACB 50KA --- 1No. with communication port RS 485 and 1No 250KA TVSS Outgoing 400A TP MCCB 35A: 2 Nos. (as an additional feeder as spare) Sets 400A TP MCCB 35KA : 2Nos. (For PAC Panel & 160 KVA UPS) 160A TP MCCB 35KA : 1No. (For Utility Panel) 40A 4P MCB : 2Nos. (For 10 KVA UPS and Spare) With Load Manager, Phase , On, Off and Trip Indicators 1200A 4P Copper Bus Bar 2.2 PAC Panel Sets with following feeder particulars Incomer 400A 4P MCCB 35KA : 1No. with communication port RS 485 and 1No 160KA TVSS Outgoing 63A 4P MCB : 10Nos. (For 8 Nos 8TR PAC and spare) DC_and_DRC_InfrastructureEquipmentsDetailsAnnexureVII.xls Page (49) Annexure-VII: D DISASTER RECOVERY DATA CENTRE, BERHAMPORE EQUIPMENTS AND COMPONENTS UNDER ELECTRICAL SYSTEM Sl. No. Make/ Type/ Description Quantity Model (1) (2) (4) (3) 40A 4P MCB : 6Nos. (For 4 Nos 8TR PAC and spare) With Load Manager, Phase , On, Off and Trip Indicators 600A 4P AL Bus Bar 2.3 Emerson Precision Power Centre for 160 KVA UPS Incomer 400A 4P MCCB 35KA : 1No. with communication port RS 485 with 1No 160KA TVSS with 200KVA Isolation Tfr, if required Outgoings 32A DP MCB : 30Nos. (For 25 Nos Server racks and spare) With Load Manager for all electrical parameters, Alarm Indicator, Phase ON, OFF and TRIP indicator and Branch circuit monitering. 600A 4P Cu Bus Bar 2 Sets 2.4 A.C. Utility Panel Electro Allied Products(EAP) 1 Set ABB 1 Set Incomer 160A 4P MCCB 35KA : 2Nos. with communication port RS 485 Buscoupler 160A 4P MCCB 35KA : 1No Outgoing 63A 4P MCB : 4Nos. (For 2 Nos PDB and spare) 40A 4P MCB : 4Nos. (For 2 Nos LDB and spare) 32A DP MCB : 16Nos. (For 10 Nos Comfort AC and spare) With Load Manager, Phase , On, Off and Trip Indicators 250A 4P AL Bus Bar 2.5 Utility Output DB for 10 KVA UPS 16 Way double door SPN DB Incomer 63A DP MCB : 1No. Outgoings 10A SP MCB:12Nos. (for Emergency Light, Security Load etc.) 16A SP MCB : 4Nos. (for Computers etc.) 2.6 LDB for Lighting points 8 way/phase TPN DB Double door Incomer 40A TPN MCB ; 1no. Outgoing : 10A/16A SP MCB : 24 nos. ABB 2 Set 2.7 PDB for Power points 8 way/phase TPN DB Double door Incomer 63A TPN MCB 1no. Outgoing :10A/16A/32A SP MCB 24 nos. ABB 2 Set DC_and_DRC_InfrastructureEquipmentsDetailsAnnexureVII.xls Page (50) Annexure-VII: D DISASTER RECOVERY DATA CENTRE, BERHAMPORE EQUIPMENTS AND COMPONENTS UNDER ELECTRICAL SYSTEM Sl. No. Description Make/ Type/ Quantity Model (1) 2.8 2.9 (2) 1000A FP ATS with overlapping neutral and bypass circuit With BMS Compatibility in an enclosure with double input and single output as per the specification (Equiv. to ASCO EMERSON 7000 series) 70A FP ATS with overlapping neutral in an enclosure with double input and single output EMERSON as per the specification (Equiv. to ASCO 300 series) 2.10 32A DP Push type Starter Switch for Comfort AC units as per the specification 3 3.1 3.2 3.3 3.4 3.5 3.6 3.7 4 4.1 (4) (3) Schiender Supply of CABLE TRAYS. 70mm x 450 mm wide MS perforated poweder coated 70mm x 300 mm wide MS perforated poweder coated 70mm x 200 mm wide MS perforated powder coated 50mm x 150 mm wide MS perforated powder coated 70mm x 450 mm wide GI ladder type poweder coated 70mm x 300 mm wide GI ladder type poweder coated 70mm x 200 mm wide GI Ladder powdercoated Supply of CABLES AND TERMINATION KITS. POWER CABLES 2 Nos 12 Nos 10 Nos 50 50 50 50 40 30 30 Mtr Mtr Mtr Mtr Mtr Mtr Mtr 600 Mtr 70 Mtr 300 Mtr 30 Mtr 70 Mtr 25 Mtr 180 Mtr 100 Mtr 100 Mtr 500 Mtr 1000 Mtr 1 Lot 16 Nos 4 40 6 20 4 72 8 120 Nos Nos Nos Nos Nos Nos Nos Nos 4.1.1 From Transformer to ATS , DG to Sync Panel, Sync Panel to ATS, ATS to DC LT Panel 4.3 4.3.1 31/2C X 300 sqmm Al, XLPE, Armoured From DC LT Panel to PAC Panels 31/2C X 240 sqmm Al, XLPE, Armoured From DC LT Panel to 160KVA UPS, UPS to PDU 1C x 150 sqmm copper flexible From 10KVA UPS to Output DB 1C x 16 sqmm copper flexible From DC LT Panel to 10KVA UPS 1C x 10 sqmm copper flexible From DC LT Panel to Utility Panel 4C X 50 Sqmm Copper arm Cable From PAC Panel to PEC C/O and then to PAC Units 4C X 16 Sqmm Copper arm Cable From Utility Panel to 2Nos LDB 4C X 6 Sqmm Copper arm Cable From Utility Panel to 2Nos PDB 4C X 6 Sqmm Copper arm Cable From Utility Panel to Comfort AC 3C X 6 Sqmm Copper arm Cable From PDU to Server Rack Cables 3C X 6 sqmm Cu Flexible FRLS Cable CONTROL CABLES 1100V grade multicore PVC insulated and sheathed armoured stranded copper conductor cables (furnish length, size, cores & particulars of each type of cables during detail engg.) Termination kits for Cable Termination for 31/2C x 300 AYWY 4.3.2 4.3.3 4.3.4 4.3.5 4.3.6 4.3.7 4.3.8 4.3.9 Termination for 31/2C x 240 AYWY Termination for 1C x 150 YY Termination for 1C x 16 YY Termination for 1C x 10 YY Termination for 4C x 50 YWY Termination for 4C x 16 YWY Termination for 4C x 6 YWY Termination for 3C x 6 YY 4.1.2 4.1.3 4.1.4 4.1.5 4.1.6 4.1.7 4.1.8 4.1.9 4.1.10 4.1.11 4.2 5 Supply related to POINT WIRING AND CONDUITING WORK DC_and_DRC_InfrastructureEquipmentsDetailsAnnexureVII.xls Page (51) Annexure-VII: D DISASTER RECOVERY DATA CENTRE, BERHAMPORE EQUIPMENTS AND COMPONENTS UNDER ELECTRICAL SYSTEM Sl. No. Description Make/ Type/ Quantity Model (1) 5.1 5.2 5.3 5.4 5.5 5.6 5.7 6 6.1 6.2 6.3 (2) (4) (3) Primary point from MCB/ 5A Switch for lighting with 3 x 1.5 sqmm wire Secondary Point Looped from item 4.2 Primary point for Raw power with (2 x 4) + (1 x 2.5) sqmm wire Secondary point looped from item 4.4 5A Switch with plate and back box 5/15A Socket + 15 A switch with all accessareis 3 nos 5 Pin 5A Socket + 15 A switch with all accessareis 30 40 30 25 20 30 50 Nos Nos Nos Nos Nos Nos Nos 125 nos. 15 nos 20 nos. 60 Nos 8 nos 400 80 300 300 mtr mtr mtr mtr 6 nos LIGHTING FIXTURES & AND ACCESSORIES. 2 x 36 watts 2' x 2' Ceiling suspended recess mounted light fixtures with Tubes and all Wipro accessories (Equiv. to Wipro WVP 24236 SGW) PL Fittings 2 x18 watts with Tubes and all accessories (Equiv. to Wipro WCP 42218 Wipro SGW) 1 x 40 watts industrial type Double tube fitting with all accessories (Equiv. to Wipro WIF Wipro 14140 SGW) Notes: The rates for lighting fixtures and fans shall include all accessories and supply of all materials that may be required to make the fixture complete in all respects. All the fixtures shall be suitable for single phase, 50 cycles, 230 Volts, AC supply system. All light fixtures shall be provided with Electronic ballast as described in the schedule. All fixtures shall be factory wired with copper conductor wires. All fixtures shall be supplied with fluorescent lamps/incandescent bulbs or any other special type bulbs as called for in the item. All the fixtures shall be quoted of approved make only. 7 8 8.1 8.2 8.3 8.4 8.5 8.6 INDUSTRIAL SOCKETS AND HOUSING 32A DP+E Industrial Sockets and straight plugs of IP 44 type and of approved make in Legrand a sheet steel enclosure with 32A DP MCB EARTHING AND EARTHING STRIPS. Earthing pits with 600 x 600 x 6mm Copper Plate earth upto 10 feet deep with all accessories 6 sqmm braided copper tape for grid earthing 8 swg bare cu wire 25 x 3 copper Strip for Earthing of panel 1c x 150 sqmm cu flexible (Green Colour) wire/cable Dedicated Eathing Box of 50mm x 10mm x 200mm complete with 50mm x 6 Tinned copper strip with 6mm holes DC_and_DRC_InfrastructureEquipmentsDetailsAnnexureVII.xls Page (52) Annexure-VII: E DISASTER RECOVERY DATA CENTRE, BERHAMPORE EQUIPMENTS AND COMPONENTS UNDER HVAC SYSTEM Sl. No. Description Make/ Type/ Quantity Model (1) (2) (4) (3) PAC UNITS Precision Air Conditioning (PAC) Units of Libert PeX Model with inert gas based refrigerant in compliance to Kiyoto protocol each of 8 TR complete with instruments, gauges, microprocessor controller and other accessories complete for precision air-conditioning of electronic control equipment at data centre Server Room in N+1 configuration Precision Air Conditioning (PAC) Units of Libert PeX Model with inert gas based refrigerant in compliance to Kiyoto protocol each of 9.5 TR complete with instruments, gauges, microprocessor controller and other accessories complete for precision air-conditioning of electronic control equipment at data centre Power Room -I (UPS/Electrical Room) in N+1 configuration Emerson 56 TR Emerson 9.5 TR 2b Precision Air Conditioning (PAC) Units of Libert PeX Model with inert gas based refrigerant in compliance to Kiyoto protocol each of 9.5 TR complete with instruments, gauges, microprocessor controller and other accessories complete for precision air-conditioning of electronic control equipment at data centre Power Room -II (UPS/Electrical Room) in N+1 configuration Emerson 9.5 TR 3 Liquid Crystal Thermometer Strips with acrylic self adhesive backing to measure quick and accurate air temperatures by showing colors as blue/green/yellow and red as per acceptable temperature standards defined by Uptime Institute inside the Data Centre Hall. Blue Star 16 Nos 4 Split type non-ductible Refrigeration Unit each of 2.5 TR with Air-cooled condensing unit, room unit, interconnecting refrigerant pipe, protection and temperature & humidity control panel, instruments, gauges and other accessories complete for air-conditioning of electronic control equipment at data centre rooms excepting Server Room and Electrical Room Blue Star 30(12 Nos) TR 5 Set of Thermometer & Humidity Meter Blue Star 3 Sets 1 2a COMFORT AC UNITS DC_and_DRC_InfrastructureEquipmentsDetailsAnnexureVII.xls Page (53) Annexure-VII: F DISASTER RECOVERY DATA CENTRE, BERHAMPORE EQUIPMENTS AND COMPONENTS UNDER BUILDING MANAGEMENT SYSTEM (BMS) SYSTEM Sl. No. Make/ Type/ Description Quantity Model (1) (2) A BUILDING MANAGEMENT SYSTEM BMS Workstation, Pentium IV 833MHz, 20GB HDD, 256MB RAM, 52X CD ROM drive 1.44 FDD, 14" colour monitor, Microsoft Bus Mouse, 2 serial, 1 parallel port & Windows NT operating system Network Controller DDC Controller Integrator for Precision AC Units on MODBUS RTU protocol Integration Software for UPS on MODBUS RTU protocol Integration Software for DG Sets on MODBUS RTU protocol Integrated Intelligent building management server software having capacity to accomodate points (hardware & software) and more with graphics user interface comprising of the following modules Building Management Seamless integrating all utililties Fire alarm system Software Module Access Management software Module CCTV system softwarebased integration Third party- UPS, Load manager, Precesion AC, DG set integration on Modubus Integration Software for Fire Alarm, Access Control, with Graphic User Interface for Seamless Integration with the BMS Graphics FIELD DEVICES Temperature cum Humidity Sensor with all mounting accessories 2 core 1.5 sq.mm unscreened Armoured non FRLS cable 1 3 4 5 6 7 8 8.1 a b c d 8.2 9 10 B 1 2 3 4 5 6 7 8 9 10 11 12 (4) (3) dell 1 Set Siemens Euronet Euronet Euronet 1 1 1 1 1 Set Set Set Set Set Euronet 1 Set Euronet 1 Set Siemens Teleflex 6 1000 Nos Mtrs. 1 Nos. 1 105 0 18 14 30 5 12 70 1 2200 Nos. Nos. Nos. Nos. Nos. Nos. Nos. Nos. Nos. Nos. Mtrs. ANALOGUE ADDRESSABLE FIRE ALARM SYSTEM Addressable Fire Detection Panel : 1-loop panel, each loop can handle 125 Siemens detectors & 125 Modules, with power supply. Interface gateway NIC-C Addressable multielectric Smoke Detector Siemens HFP-11 Addressable Heat Detector HFPT-11 Manuall Call Point HMS-S Strobe cum hooter MTH-MC-R Control module HTRI-R Monitor module HTRI-S FIM RI RI Emergency Glow Sign ISI 2-core, 1.5 sq. mm. Shielded armoured cable Teleflex DC_and_DRC_InfrastructureEquipmentsDetailsAnnexureVII.xls Page (54) Annexure-VII: F DISASTER RECOVERY DATA CENTRE, BERHAMPORE EQUIPMENTS AND COMPONENTS UNDER BUILDING MANAGEMENT SYSTEM (BMS) SYSTEM Sl. No. Description Make/ Type/ Quantity Model (1) (2) (4) (3) C 1.1 1.2 SAPPHIRE - FIRE SUPPRESSION SYSTEM Sapphire for server room and Electrical Room Sapphire for BMS Room Sinorix 1230 Sinorix 1231 1 1 D 1 2 3 4 VESDA SYSTEM Single Channel Air Sampling System For Server Room PVC Pipe Fittings and Supports 24 VDC Power Supply Unit VLC-55 ISI ISI PS-2425 1 1 1 1 E 1 2 3 ACCESS CONTROL SYSTEM Main Door Controller . Proximity Card Reader Proximity Card Reader with Fingerprint Reader M5E4 HID-6005 V-PROX 1 16 6 Nos. Nos. Nos. 4 Electromagnetic Lock (Single leaf ) EML-1101 +EB-LZ10 5 Nos. 5 Magnetic contact EMC-205 16 Nos. 6 Electromagnetic Lock (Double leaf ) EML1103 +EB-LZ10 11 Nos. 7 8 9 10 11 Proximity Card - Blank Face Emergency Exit Switch Panic Bar 4-core 0.8sq. mm. Shielded cable in PVC Conduit 8-core 0.8sq. mm. Shielded cable in PVC Conduit HID-1326 ERS-G 100 9 1 1000 1600 Nos. Nos. Nos. Mtrs. Mtrs. F 1 2 WATER LEAK DETECTION SYSTEM & RODENT REPELLENT SYSTEM Water Leak Cable (10 mts each) WD-CS/10M Electronic Sounder 85db Lightak 4 Zone Water Leak Conventional Panel with Battery Charger & Battery Signet with BMS integration Rodent Repellent Console Units with Transducers suitable to cater all DC Maser area. 15 1 Nos Nos 1 LOT 1 Nos 3 4 Teleflex Teleflex DC_and_DRC_InfrastructureEquipmentsDetailsAnnexureVII.xls lot lot No Per Zone Lot No. Page (55) Annexure-VII: F DISASTER RECOVERY DATA CENTRE, BERHAMPORE EQUIPMENTS AND COMPONENTS UNDER BUILDING MANAGEMENT SYSTEM (BMS) SYSTEM Sl. No. Make/ Type/ Description Quantity Model (1) (2) G 1 CCTV SERVELLIANCE SYSTEM PC with Monitor 1/3" Colour Dome Camera with 3.6/6 mm fixed lens for indoor application, complete with power supply unit 4 Channel Video Streamer / Encoder Rack for streamer DVM Server Digital Video Management Software RG11.armoured 2-core, 1.5 sq. mm. unscreened armoured non FRLS cable 2 3 4 5 6 7 8 H 1 2 3 4 5 6 7 8 9 (4) (3) Fujitsu 1 Nos. CFD-480 24 Nos. Tracer lite ISI IBM/Dell Euronet Dlink Teleflex 6 3 1 1 2500 1200 Nos. Nos. Nos. lot Mtrs Mtrs 36 1 1 1 1 1 1 1 Nos. 1800 Nos. PUBLIC ADDRESS SYSTEM 6 watt each with line matching transformers. LBD8352/10 Volume control units LBC400/10 240 WATT Amplifier LBD1935/00 Goose neck Microphone LBB1949 System controller with 4 Zone call station LBB1990+/56/+57 Pre amplifier pre recorded voice generator LBB1925 Professional grade DVD/ Cassete player PLN-DVDT Powder coated rack with wheels ISI Cable & Conduit : 2 core 1.5 sq mm twisted HFFR/ FRLS cu cable in Teleflex yellow colour with conduit DC_and_DRC_InfrastructureEquipmentsDetailsAnnexureVII.xls Nos. Nos. Nos. Nos. Nos. Nos. Nos. Page (56) ANNEXURE - VIII LOG BOOK FOR CORRECTIVE MAINTENANCE (Comprehensive AMC of Infrastructure Equipments) Period: From _______________ to ____________________________ Location Name: IN CHARGE Name: Designation: Remarks. Solution provided Call status (Pending) /Attended Total Time taken for Fault rectification Completion of fault rectification Date & Time Attended fault on Date & Time by Vendor’s Engineer Date & Time of Fault reporting by WBSEDCL Fault Category/ Major/ Minor) Effect on Service (No/ Degrade/ Down) Problem Description Docket No. Sl. No. (A) Details of Fault during Period: Following are the details of faults and fault responses, observed during the above mentioned period. (B) The number of repeat faults attended for the same equipment/same site (C) It is also certified that No Faults are pending against these equipments at the end of above mentioned period. (Cross if any fault is pending) Comprehensive AMC for Data Center Infrastructure of Rajarhat Data Center & Berhampore Disaster Recovery Center, WBSEDCL Tender Notice No. : IT&C/80/584 dated. 10.09.2015 Page 57 Signature Signature Bidder Representative DC In-Charge/ DRC In-Charge, WBSEDCL Name: Name: Location: Location Date: Date: Comprehensive AMC for Data Center Infrastructure of Rajarhat Data Center & Berhampore Disaster Recovery Center, WBSEDCL Tender Notice No. : IT&C/80/584 dated. 10.09.2015 Page 58