ELG3311: Tutorial 2 Problem 2-1: The secondary winding of a transformer has a terminal voltage of vs (t) = 282.8 sin 377t V. The turns ratio of the transformer is 50:200 (a = 0.25). If the secondary current of the transformer is iS (t) = 7.07 sin (377t – 36.87o) A, what is the primary current of this transformer? What is the voltage regulation and efficiency? The impedance of this transformer referred to the primary side are: RT = 0.005 Ω XT = 0.225 Ω RC = 75 Ω XM = 20 Ω Solution: The following equivalent circuit is referred to the primary. IP RT XT Ie VP RC jX aVS The secondary voltage and current are VS = IS = 282.8 2 7.07 2 ∠0o V = 200∠0o V ∠ - 36.87 o A = 5∠ - 36.87 o A The secondary voltage referred to the primary side is VSP = aVS = 0.25 × 200∠0o = 50∠0o The secondary current referred to the primary side is ISP = IS 5∠ − 36.87 o = = 20∠ − 36.87 o A a 0.25 The primary circuit voltage is given by VP = VSP + ISP (RT + jX T ) ( ) VP = 50∠0o + 20∠ - 36.87 o (0.05 + j 0.225) = 53.6∠3.2o V The excitation current of this transformer is 1 Ie = IC + I m = 53.6∠3.2o 53.6∠3.2o + = 0.7145∠3.2o + 2.675∠ - 86.8o = 2.77∠ - 71.9o 75 j 20 The total primary current is I P = ISP + I e = 20∠ - 36.87 o + 2.77∠ - 71.9o = 22.3∠ - 41o A The voltage regulation of the transformer VR = VP - aVS 53.6 − 50 × 100% = × 100% = 7.2% 50 aVS The input power is ( ) Pin = VP I P cosθ = 53.6 × 22.3 × cos 3.2o + 41o = 857 W The output power is Pout = VS IS cos θ = 200 × 5 × cos 36.87 o = 800 W The efficiency η= Pout 800 × 100% = × 100% = 93.4% Pin 857 2 Problem 2-2: A 20-kVA 8000/277-V distribution transformer has the following resistances and reactances: RP = 32 Ω XP = 45 Ω RC = 250 kΩ RS = 0.05 Ω XS = 0.06 Ω Xm = 30 kΩ The excitation branch impedances are given referred to the high-voltage side of the transformer a. b. c. d. Find the equivalent circuit of this transformer referred to the high-voltage side. Find the per-unit equivalent circuit of this transformer. Assume that this transformer is supplying rated load at 277 V and 0.8 PF lagging. What is the transformer’s input voltage? What is its voltage regulation? What is the transformer’s efficiency under the conditions of part (c)? Solution: The turns ratio a = 8000/277 = 28.89. The secondary impedances referred to the primary side are RSP = a 2 RS = (28.89)2 (0.05) = 41.7 Ω X SP = a 2 X S = (28.89 )2 (0.06) = 50.1 Ω IP 41.7 Ω j45 Ω 32Ω j50.1Ω IS/a Ie j30 Ω 250 kΩ VP aVS (b) The rated KVA of the transformer is 20 kVA, and the rated voltage on the primary side is 8000 V, therefore, the rated current in the primary side is 20 kVA/8000 V = 2.5 A. Accordingly, the base impedance on the primary side is Z base = Vbase 8000 = = 3200 Ω I base 2.5 Since Zpu = Zactual/Zbase, the resulting per unit equivalent circuit is IP 0.01 0.013 j0.0141 J0.0157 IS/a Ie VP 78.125 J9.375 aVS 3 ( c ) The equivalent circuit referred to the primary side is shown in the following diagram: IP 41.7 Ω j45 Ω 32Ω j50.1Ω IS/a Ie VP j30 Ω 250 kΩ IS = 20kVA ∠ − 36.87 o = 72.2∠ - 36.87 o 277V ISP = 72.2∠ - 36.87 o = 2.5∠ − 36.87 o A 28.89 aVS The primary voltage is VP = VSP + (R T + jX T ) ISP ( ) = 8000∠0o + (73.7 + j95.1) 2.5∠ - 36.87 o = 8290∠0.55o The voltage regulation is VR = 8290 - 8000 × 100% = 3.63% 8000 (d) The losses are ( ) 2 Pcopper = ISP RT = (2.5)2 (73.7 ) = 461 W Pcore = (VSP ) 2 RC = 82902 = 275 W 250,000 The efficiency is η= Pout 20kVA × 0.8 × 100% = 95.6% × 100% = 20kVA × 0.8 + 461 + 275 Pout + Pcopper + Pcore 4 Problem 2-3: A 2000-VA, 230/115-V transformer has been tested to determine it equivalent circuit. The results of the test are shown below: OC VOC = 230 V IOC = 0.45 A POC = 30 W SC VSC = 13.2 V ISC = 6 A PSC = 20.1 W All data given were taken from the primary side of the transformer. a. b. Find the equivalent circuit of the transformer referred to low-voltage side. Find VR at rated conditions and (1) 0.8 PF lagging, (2) 1.0 PF, (3) 0.8 PF lagging. Solution: From OC Test, we get RC = 1763 Ω X m = 534 Ω From SC, we get RT = 0.588 Ω X T = j 2.128 Ω The equivalent circuit referred to the secondary side is shown in the following diagram 0.140 Ω a IP j0.532 Ω Ie VP/a 441 Ω 134 Ω VS (b) The reated secondary current is 1000 = 8.7 A IS = 115 (1) When 0.8 PF lagging ( VPS = VS + ZT IS = 115∠0o + (0.140 + j0.532) 8.7∠ − 36.87 o ) = 118.8∠1.4o VR = 118.8 - 115 × 100% = 3.3% 115 (2) When 1.0 PF ( VPS = VS + ZT IS = 115∠0o + (0.140 + j0.532 ) 8.7∠0o ) = 116.3∠2.28o V 5 VR = 116.3 - 115 × 100% = 1.1% 115 (3) When 0.8 PF leading ( VPS = VS + ZT IS = 115∠0o + (0.140 + j0.532 ) 8.7∠36.87 o ) = 113.3∠2.24o VR = 113.3 - 115 × 100% = −1.5% 115 The copper and core losses of the transformer are: 10.6 W and 32 W. The efficiency is 115 × 8.7 × 0.8 η= = 94.9% 115 × 8.7 × 0.8 + 10.6 + 32 6 Problem 2-4: A single-phase power system is shown in Figure P2-1. The power source feeds a 100-kVA 14/2.4-kV transformer through a feeder impedance of 38.2 + j140 Ω. The transformer’s equivalent series impedance referred to its low-voltage side is 0.12 + j0.5 Ω. The load on the transformer is 90 kW at 0.85 PF lagging and 2300 V. Zload VG Source a. b. c. Feeder Transformer Load What is the voltage at the power source of the system? What is the voltage regulation of the transformer? How efficient is the overall power system? Solution: We will refer this circuit to the secondary. The feeder’s impedance referred to the secondary side is 2.4 ZSline = (38.2 + j140) = 1.12 + j 4.11Ω 14 The secondary current is given by IS = 90 = 43.48 A 2300 × 0.9 IS = 43.48∠ - 25.8o (a) The power at the power source of this system (referred to the secondary lab) is S Vsource = VS + IS ZSline + IS ZT ( ) ( ) = 2300∠0o + 43.48∠ − 25.8o + (1.12 + j 4.11) + 43.48∠ − 25.8o (0.12 + j 0.5) o = 2441∠3.7 V Now find the voltage at the power source ( ) 14 o Vsource = 2441∠3.7 o = 14.24∠3.7 kV 2.4 (b) To find the VR, we must find the voltage at the primary side referred to the secondary under full load condition VPS = VS + IS ZT ( ) = 2300∠0o + 43.48∠ − 25.8o (0.12 + j 0.5) = 2314∠0.43o 7 Therefore VR = 2314 - 2300 × 100% = 0.6% 2300 (c) The power supplied by the load is (d) S Pin = Vsource IS cosθ = 2441 × 43.48 × cos 29.5o = 92.37 kW The efficiency is η= Pou t Pin × 100% = 90 × 100% = 97.4% 92.37 8 Problem 2-14: A 12.4-kV single-phase generator supplies power to the load through a transmission line. The load’s impedance is Zload = 500∠36.87o Ω, and the transmission line’s impedance is Zline = 60∠60o Ω. Zline Zload VG (a) 1:10 Zline 10:1 Zload VG (b) a. b. If the generator is directly connected to the load (Figure 2-3a), what is the ratio of the load voltage to the generator voltage? What are the transmission losses of the system? If a 1:10 step-up transformer is placed at the output of the generator and a 10:1 transformer is placed at the load end of the transmission line, what is the new ratio of the load voltage to the generated voltage? What are the transmission losses of the system now? Solution: In case of the directly-connected load, the line current is I line = I load = 12∠0o o 60∠60 + 500∠36.87 o = 22.32∠ − 39.3o A The load voltage is ( )( ) Vload = I load Zload = 22.32∠ − 39.3o 500∠36.87 o = 11.16∠ − 2.43o kV The ratio of the load voltage to the generated voltage is 11.16/12.4 = 0.9. The transmission losses are 2 Ploss = I line Zload = (22.32)2 (30) = 14.9 kW (b) Two transformers are used. The impedance of the transmission line becomes 9 2 2 ( ) 1 1 o o Z load Zline = 60∠60 = 0.6∠60 Ω line = 10 10 I load line = I load = 12.4∠0o 0.6∠60o + 500∠36.87 o = 24.773∠ − 3690 o A The load voltage is ( )( ) Vload = I load Zload = 24.773∠ - 36.90 o 500∠36.87 o = 12.386∠ − 0.03o kV The ratio of load voltage to generated voltage is 12.386/12.4=0.999. The current in the transmission line is 1 1 I line = I load = (24.77 ) = 2.477 A 10 10 The losses in the transmission line are 2 Ploss = I line Rline = (2.477 )2 (30 ) = 184 W Transmission losses have decreased by a factor of more than 80. 10