GROUND LEVEL: PLUMBING - PLAN 2ND FLOOR: PLUMBING

advertisement
NEW 4" ST LDR UP
635 SQ FT
DISCONNECT & REMOVE EXISTING
3" STORM VENDER UP & DN & CAP
PIPING W/ FINISHED FLOOR
EXISTING FLOOR DRAIN W/ CLEAN
OUT DECK PLATE TO REMAIN.
4"
6"
SsD
325 W 38TH STREET, SUITE 210
NEW YORK, NY 10018
4"
ST
4"
X
4" ST LDR UP TO
OVERFLOW DRAIN
HEAT TRACE EXPOSED
6" STORM WATER
PIPING IN GARAGE
4" ST LDR UP TO FD
635 SQ FT
NEW 11 4" G UP
6"
STRUCTURAL ENGINEER:
Richard H. Balser, Engineers
228 W 18th Street, No. 11
New York, NY 10011
T 212-463-0008
HEAT TRACED
EXPOSED 3" W
& 34" H & CW
PIPING IN
GARAGE
SURVEYOR:
Leonard J. Strandberg and Associates
Consulting Engineers and
Land Surveyors, P.C.
92 Atlantic Avenue, Freeport, NY 11520
516-378-2064 212-213-4090
fax 516-378-6649
G
NEW 6" BURIED STORM
HOUSE TRAP IN EXISTING
3'-0" L X 3'-0" W X 3'-0" DEEP
PIT
11 4"
ST
EXISTING 34" DOMESTIC
WATER SERVICE TO
REMAIN
EXISTING LAV
TO REMAIN
3"
6"
NEW CONN
3
4"
G
G
EXISTING 40 GALLON
GAS FIRED HW HEATER
TO REMAIN.
G
CODP
4"
2"
4"
4"
G
2"
NEW 3" FRESH AIR INLET
2"
2"
2"
2"
NEW 4"
UP
CONNECT NEW 3" FAI
PIPING TO EXIST.
NEW 4" S DN
NEW 2" W
2" W
UP
2" V
2" W
3
4"
NEW
H&CW UP
EXISTING GAS METER
NEW HW CIRCULATING
PUMP BELL & GOSSET
SERVICE PR (3/4")115
VOLTS, 1 PHASE, 5 GPM,
12 TDH
3
3
4"
M
2"
MEP ENGINEER:
TWIG Consulting Engineers
7 Penn Plaza - Suite 702
New York, NY 10001
T 212-967-8944
4"
NEW 2" W UP
3
4" H & CW UP
3
4"
4"
EXISTING 2" GAS SERVICE
TO REMAIN
G
P-4
M
cs
3
G
3
4"
3
4"
6"
G
1"
6"
EXISTING 6" COMBINED
HOUSE SEWER @ 41"
PPF TO REMAIN.
CONSULTANTS:
NEW 6"
STORM DN
NEW 2" UP
NEW 4" ST LDR UP
635 SQ FT
tel: 212. 248. 7500
fax: 866. 677. 3878
NEW 3 4" G UP.
GROUND LEVEL: PLUMBING - PLAN
SCALE 1/4" - 1'-0"
NEW 3/4" G DN
NEW 4" ST LDR DN
635 SQ FT
NEW 4" ST UP TO
FD
4"
4"
NEW 4" ST UP TO
OD
4"
4"
W
09.20.2012 ISSUED FOR POST APPROVAL AMENDMENT
07.03.2012 ISSUED FOR CONSTRUCTION
NEW 3 4" CW DN
2"
PROJECT:
HSU HOUSE
NEW 4" ST LDR
DN
2"
NEW 2" W DN
2" V RISE
PROJECT ADDRESS:
P-1
NEW 3/4" H &
CW DN & RISE
94 NORTH FIRST STREET
BROOKLYN, NY 11211
P-2
P-3
R
DW
P-4
DWG TITLE:
P-2
1
2"
GROUND & 2ND LEVEL
PLUMBING
PLAN
2"
SEAL & SIGNATURE:
NEW 3/4" H & CW DN & RISE
NEW 4"V UP
NEW 4" TO OD
NEW 3 4" G DN
NEW 4" ST UP TO RD
2ND FLOOR: PLUMBING - PLAN
SCALE 1/4" - 1'-0"
DATE:
PROJECT No.:
DWG BY:
CHK BY:
DWG No.:
NYC ECC EXEMPTION:
THE PLUMBING APPLICATION IS EXEMPT FROM
THE NYC ENERGY CONSERVATION CODE (NYC
ECC) AS PER SECTION 101.6
THESE PLANS ARE APPROVED ONLY FOR THE WORK ON THE
APPLICATION SPECIFICATION SHEET. ALL OTHER MATTERS SHOWN
ARE NOT TO BE RELIED UPON OR TO BE CONSIDERED AS EITHER
BEING APPROVED OR IN ACCORDANCE WITH APPLICABLE CODES.
DOB ID No.:
PAGE No.:
SsD
NEW 4" OVERFLOW
DRAIN
NEW 4" STORM
CONTROLLED ROOF
DRAIN
NEW 4" STORM
CONTROLLED ROOF
DRAIN
NEW 4" OVERFLOW
DRAIN
325 W 38TH STREET, SUITE 210
NEW YORK, NY 10018
tel: 212. 248. 7500
fax: 866. 677. 3878
CONSULTANTS:
STRUCTURAL ENGINEER:
Richard H. Balser, Engineers
228 W 18th Street, No. 11
New York, NY 10011
T 212-463-0008
SURVEYOR:
Leonard J. Strandberg and Associates
Consulting Engineers and
Land Surveyors, P.C.
92 Atlantic Avenue, Freeport, NY 11520
516-378-2064 212-213-4090
fax 516-378-6649
RELOCATED
RTU-1 UNIT
(150 CFH)
MEP ENGINEER:
TWIG Consulting Engineers
7 Penn Plaza - Suite 702
New York, NY 10001
T 212-967-8944
NEW 4" STORM
CONTROLLED ROOF
DRAIN
NEW
RTU-2 UNIT
(150 CFH)
NEW 4"V UP THRU ROOF
NEW 11 4" GAS
DN
NEW 4" OVERFLOW
DRAIN
ROOF LEVEL: PLUMBING - PLAN
SCALE 1/4" - 1'-0"
09.20.2012 ISSUED FOR POST APPROVAL AMENDMENT
07.03.2012 ISSUED FOR CONSTRUCTION
PROJECT:
HSU HOUSE
PROJECT ADDRESS:
94 NORTH FIRST STREET
BROOKLYN, NY 11211
DWG TITLE:
ROOF LEVEL
PLUMBING
PLAN
SEAL & SIGNATURE:
DATE:
PROJECT No.:
DWG BY:
CHK BY:
DWG No.:
NYC ECC EXEMPTION:
THE PLUMBING APPLICATION IS EXEMPT FROM
THE NYC ENERGY CONSERVATION CODE (NYC
ECC) AS PER SECTION 101.6
THESE PLANS ARE APPROVED ONLY FOR THE WORK ON THE
APPLICATION SPECIFICATION SHEET. ALL OTHER MATTERS SHOWN
ARE NOT TO BE RELIED UPON OR TO BE CONSIDERED AS EITHER
BEING APPROVED OR IN ACCORDANCE WITH APPLICABLE CODES.
DOB ID No.:
PAGE No.:
SsD
325 W 38TH STREET, SUITE 210
NEW YORK, NY 10018
tel: 212. 248. 7500
fax: 866. 677. 3878
CONSULTANTS:
STRUCTURAL ENGINEER:
Richard H. Balser, Engineers
228 W 18th Street, No. 11
New York, NY 10011
T 212-463-0008
SURVEYOR:
Leonard J. Strandberg and Associates
Consulting Engineers and
Land Surveyors, P.C.
92 Atlantic Avenue, Freeport, NY 11520
516-378-2064 212-213-4090
fax 516-378-6649
1
1
MEP ENGINEER:
TWIG Consulting Engineers
7 Penn Plaza - Suite 702
New York, NY 10001
T 212-967-8944
GENERAL PIPING NOTES
1
1. PROVIDE ALL MATERIALS AND EQUIPMENT AND
PERFORM ALL LABOR REQUIRED TO INSTALL COMPLETE
AND OPERABLE PIPING SYSTEMS AS INDICATED ON THE
DRAWING.
2. UNLESS OTHERWISE NOTED, ALL PIPING IS OVERHEAD,
TIGHT TO THE UNDERSIDE OF STRUCTURE/SLAB, WITH
SPACE FOR INSULATION AS SPECIFIED.
3. INSTALL PIPING SO THAT ALL VALVES, STRAINERS,
UNIONS, TRAPS, FLANGES AND OTHER
APPURTENANCES REQUIRING ACCESS ARE
ACCESSIBLE.
4. ALL PIPING WORK SHALL BE COORDINATED WITH ALL
TRADES INVOLVED OFFSETS IN PIPING AROUND
OBSTRUCTIONS SHALL BE PROVIDED AT NO
ADDITIONAL COST TO THE OWNER.
M
5. LOCATIONS OF EXISTING SANITARY SOIL AND VENT
STACKS, HOT AND COLD WATER RISERS ARE
APPROXIMATE. THE PLUMBING CONTRACTOR SHALL
FIELD VERIFY EXACT LOCATIONS OF PLUMBING
STACKS BEFORE COMMENCING HIS WORK.
1
STORM WATER RISER DIAGRAM
2
SCALE: NOT TO SCALE
WATER RISER DIAGRAM
SCALE: NOT TO SCALE
09.20.2012 ISSUED FOR POST APPROVAL AMENDMENT
07.03.2012 ISSUED FOR CONSTRUCTION
PROJECT:
HSU HOUSE
1
PROJECT ADDRESS:
94 NORTH FIRST STREET
BROOKLYN, NY 11211
DWG TITLE:
CELLAR THRU ROOF
PLUMBING
RISER DIAGRAMS
M
SEAL & SIGNATURE:
1
3
SANITARY RISER DIAGRAM
SCALE: NOT TO SCALE
4
GAS RISER DIAGRAM
SCALE: NOT TO SCALE
DATE:
PROJECT No.:
DWG BY:
CHK BY:
DWG No.:
NYC ECC EXEMPTION:
THE PLUMBING APPLICATION IS EXEMPT FROM
THE NYC ENERGY CONSERVATION CODE (NYC
ECC) AS PER SECTION 101.6
THESE PLANS ARE APPROVED ONLY FOR THE WORK ON THE
APPLICATION SPECIFICATION SHEET. ALL OTHER MATTERS SHOWN
ARE NOT TO BE RELIED UPON OR TO BE CONSIDERED AS EITHER
BEING APPROVED OR IN ACCORDANCE WITH APPLICABLE CODES.
DOB ID No.:
PAGE No.: