TempTrac Boiler Operator Users Guide

advertisement
OnTrac® Installation and Operation Manual
OnTrac® Boiler Management System
CS-4 & CS-8 Setup and Operation Manual
®
Riverside Hydronics , LLC
WWW.RIVERSIDEHYDRONICS.COM
3220 Galvez Avenue - Fort Worth, Texas 76111 - Tel 1-800-990-5918
34-152 04/2014
Page | 1
OnTrac® Installation and Operation Manual
Table of Contents
Caution ................................................................................................................................. 5
Specifications: ....................................................................................................................... 5
Overview............................................................................................................................... 5
Theory of operation .................................................................................................................... 6
Two Tier System ............................................................................................................................................ 6
Single Tier System ......................................................................................................................................... 6
Startup Screen ............................................................................................................................. 6
Navigation and On Screen Help .................................................................................................. 6
OnTrac® CS-8 and OnTrac® CS-4................................................................................................... 6
CS-8 ............................................................................................................................................................... 6
CS-4 ............................................................................................................................................................... 7
Parts Description Included:............................................................................................................................ 7
Parts Location: ..................................................................................................................................................7
®
OnTrac Display Enclosure ................................................................................................................................8
Power Switch .................................................................................................................................................8
Fuse ................................................................................................................................................................8
Power Jack and Power Supply ..........................................................................................................................9
Probes .............................................................................................................................................................10
Thermal Well ..................................................................................................................................................10
Field Terminal Strip ..................................................................................................................................... 10
Ethernet Connection CS-4 & CS-8 PLC ............................................................................................................10
Ethernet Connection for CS-8 with RMC OPTION ..........................................................................................11
PLC Programmable Logic Controller ............................................................................................................. 11
PLC RS-485 PORT ............................................................................................................................................11
PLC PANEL Interface .......................................................................................................................................11
PLC BATTERY Indicator ...................................................................................................................................11
RS-485 Repeater Module ............................................................................................................................. 11
Touch Screen Panel ..................................................................................................................................... 11
Programming Port ..........................................................................................................................................11
Ethernet Port for RMC feature .......................................................................................................................11
®
OnTrac Optional Equipment: ...................................................................................................................... 12
Analog Input Module for 4-20mA Remote Setpoint Option (REMSET) ..........................................................12
Remote Equipment Option (REMEQ) .............................................................................................................12
Panel Mounted Audible Alarm (AUDALARM) .................................................................................................12
Remote Alarm Contacts (REMALARM) ...........................................................................................................12
Remote Access and Control (RMC) CS-8 Option Only ....................................................................................12
Data Acquisition (DAQ) Expands RMC Option ................................................................................................12
Getting Started: ................................................................................................................... 12
Wiring and Hookup ................................................................................................................... 12
®
Boiler – OnTrac Communication Hookup.................................................................................................... 12
Remote Equipment Option Hookup (REMEQ or PUMP) ............................................................................... 13
Remote Alarm Option Hookup (REMALARM) .............................................................................................. 14
System Sensor and Outdoor Sensor Location and Hookup ...................................................... 14
®
Riverside Hydronics , LLC
WWW.RIVERSIDEHYDRONICS.COM
3220 Galvez Avenue - Fort Worth, Texas 76111 - Tel 1-800-990-5918
34-152 04/2014
Page | 2
OnTrac® Installation and Operation Manual
TempTrac® Control Module (Satellite Module) ........................................................................ 15
Control Module For Non-Riverside Tier 2 Boilers ......................................................................................... 15
Control Module For Sensor Inputs ............................................................................................................... 15
Control Module Full Control ...........................................................................................................................16
Control Module Wiring ...................................................................................................................................16
Wiring Enable/Disable .................................................................................................................................16
Wiring Modulation signal 4-20mA ...............................................................................................................17
Temperature Sensor location .......................................................................................................................17
Alarm input from existing equipment ..........................................................................................................17
Assigning Boiler Addresses ........................................................................................................ 17
Check List before OnTrac® Power Up: ...................................................................................... 18
Check List for total setup of OnTrac®: ....................................................................................... 18
OnTrac® Service: .................................................................................................................. 19
Annual Battery Maintenance: ................................................................................................... 19
®
OnTrac PLC battery Replacement: .............................................................................................................. 19
®
®
Newer OnTrac , PLC mounted on back panel of OnTrac Box ........................................................................19
®
Older OnTrac , PLC mounted on back of Touch Panel ...................................................................................19
®
Touch Panel Battery Replacement, OnTrac CS-8 only: ................................................................................ 19
®
®
Newer OnTrac , PLC mounted on back panel of OnTrac Box ........................................................................19
®
Older OnTrac , PLC mounted on back of Touch Panel ...................................................................................19
After Battery replacement:.......................................................................................................................... 19
OnTrac® Touch Screen Interface: ......................................................................................... 20
Touch Screen Navigation ........................................................................................................... 20
Startup Screen / Lock Screen .................................................................................................... 20
System History screens ............................................................................................................. 20
Boiler Status Group screens ...................................................................................................... 21
Boiler Status Individual screen .................................................................................................. 22
Boiler Firing Rate screens .......................................................................................................... 22
Battery Screen ........................................................................................................................... 22
Time and Date screen................................................................................................................ 23
Service Boilers screen ................................................................................................................ 23
Initial Setup Button ................................................................................................................... 24
Initial Setup Buttons/Screen ..................................................................................................... 24
Audible Alarm ON/OFF button ( Optional ) ............................................................................... 25
Timers and Counters ................................................................................................................. 25
Life On Time Display .................................................................................................................................... 25
Powered on for Display ............................................................................................................................... 25
Power On Count Display .............................................................................................................................. 26
OnTrac® Hydronic Features:................................................................................................. 26
Outdoor Reset feature .............................................................................................................. 26
Tune Timing Configuration ........................................................................................................ 27
Tune Temperature screen ......................................................................................................... 27
Lead-Lag screen ......................................................................................................................... 28
Temperature Alarm feature ...................................................................................................... 29
®
Riverside Hydronics , LLC
WWW.RIVERSIDEHYDRONICS.COM
3220 Galvez Avenue - Fort Worth, Texas 76111 - Tel 1-800-990-5918
34-152 04/2014
Page | 3
OnTrac® Installation and Operation Manual
Outdoor Shutdown screen ........................................................................................................ 29
Max Boilers screen .................................................................................................................... 29
Outdoor Trigger Tier 2 screen ................................................................................................... 30
Remote Equipment ................................................................................................................... 30
Manual Override screen ............................................................................................................ 31
Remote Setpoint screen ............................................................................................................ 31
Non-Riverside Boilers screen .................................................................................................... 31
Isolation Valves.......................................................................................................................... 32
Scheduled Setback screen ......................................................................................................... 33
Proportional Control screen ...................................................................................................... 33
Control By Firing Rate screen .................................................................................................... 34
Tier 2 Independent screen ........................................................................................................ 34
Sensor Setup screen .................................................................................................................. 35
Swap labels for Probe 1 & 2 setting .......................................................................................... 35
Burner On Zero Hours utility ..................................................................................................... 36
Factory Reset ............................................................................................................................. 36
Password Protection feature..................................................................................................... 36
Enabling Password Protection ..................................................................................................................... 36
Password Level 3 PW3 ....................................................................................................................................37
Password Level 2 PW2 ....................................................................................................................................37
Password Level 1 PW1 ....................................................................................................................................37
Password Level 0 PW0 ....................................................................................................................................37
Schematic............................................................................................................................ 37
®
Riverside Hydronics , LLC
WWW.RIVERSIDEHYDRONICS.COM
3220 Galvez Avenue - Fort Worth, Texas 76111 - Tel 1-800-990-5918
34-152 04/2014
Page | 4
OnTrac® Installation and Operation Manual
Caution
Familiarity with the hydronic system is crucial in proper operation and to prevent damage to equipment. Warning:
Improper installation, operation, adjustment, alteration, service or maintenance can cause damage to the device,
property damage, personal injury, exposure to hazardous material or loss of life. Refer to the information
contained in this manual.
Warning: Do not use this electronic control as a primary limit control. Other limit and operating controls that are
intended and certified as safety controls and limits must remain in or be added to the control circuit. Use of this
control as a primary limit control can cause property damage, personal injury, exposure to hazardous material or
loss of life.
It is your responsibility to ensure this control is installed according to all applicable codes and standards.
Other than externally accessible fuse(s), there are no user serviceable parts. Refer all other service requirements to
a qualified agent. Service by other than a qualified agent voids the warranty.
Warning: Do not attempt to service this control. Such an attempt can cause damage to the device, property
damage, personal injury, exposure to hazardous material or loss of life.
Back to Table of Contents
Specifications:
Enclosure: 16-gauge, powder-coated steel, NEMA 1
Dimensions:
Weight:
Hardware Certifications: UL, CUL, CE
Assembly Certification: ETL Panel Shop Listing
Power Requirements: 115VAC ±10%, 60 Hz. 1 amp
External Power Supply: 24VDC 1AMP Vertical Wall Wart
Output Relays: 110 VAC, 15 Amp max
Environmental: 32-122°F, 10 -95% Non-condensing
Interface: Color Touchscreen
Touch Screen Panel Battery:
PLC Battery:
Data Interface:
OnTrac® to Boiler Interface:
OnTrac® CS-4
OnTrac® CS-8
12 3/4” H x 9” W x 7” D
12 lbs.
16-1/8" x 16" W x 9" D
25 lbs.
Supplied
Optional
Supplied
Optional
4” Diagonal
NONE
3V Li, Coin Cell 2032
MODBUS TCP
MODBUS RTU
8” Diagonal
3.6V Li, 1/2AA
3V Li, Coin Cell 2032
MODBUS TCP
MODBUS RTU
Back to Table of Contents
Overview
Boiler Management Systems (BMS) provide group control and coordination to provide hydronic heating using
multiple boilers in a way that is effective and efficient. Other advantages of a BMS include sharing and rotating the
work load for a balanced usage of equipment.
®
Riverside Hydronics , LLC
WWW.RIVERSIDEHYDRONICS.COM
3220 Galvez Avenue - Fort Worth, Texas 76111 - Tel 1-800-990-5918
34-152 04/2014
Page | 5
OnTrac® Installation and Operation Manual
Theory of operation
The OnTrac® Boiler Management System is designed to perform all of the function of a typical BMS (Boiler
Management System). OnTrac® however is designed to work in concert with the individual boiler controls to
maintain optimum load matching and balanced boiler runtime. OnTrac® will communicate with the boiler controls
over a RS-485 Serial Bus using the Modbus RTU protocol. Communicating with the existing boiler controls
accomplishes complete coordination without diminishing the unique operational features of the boiler.
Much of the information contained in this document is also present on the Help Screens accessible on the
OnTrac®.
The OnTrac® is offered with 2 screen sizes. OnTrac® CS-8 has a 8” touch screen, and the OnTrac® CS-4 has a 4”
touch screen. All the basic features are available on both, but the CS-8 has some additional options for remote
monitoring and data acquisition.
Two Tier System
OnTrac® also has the capability of operating a “2 Tier” hydronic boiler system. This front-end loaded system uses
high efficiency condensing boilers to serve as the primary heat source for the majority of the heating season but
uses less expensive non-condensing boilers or pre-existing boilers for additional heat when the system load is
exceptionally high.
Single Tier System
In a system that has boilers that are all alike, such as a system with all condensing boilers, the system can operate
as a single Tier. An advanced feature for operating two loops at one setpoint is available.
Back to Table of Contents
Startup Screen
When the system is powered up, the first screen is called the STARTUP SCREEN or LOCK SCREEN. This screen
displays the SYSTEM TEMPERATRUE, ADJUSTED SETPOINT, and the amount of time sense the OnTrac® was last
powered on. If enabled, STATUP SCREEN can also display the OUTDOOR TEMPERATRUE, and SYSTEM 2
TEMPERATURE. If passwords have been enabled, and there is a PW0 setup, then this screen will require you enter
a password before exiting to the MAIN SCREEN.
Navigation and On Screen Help
Navigate by selecting buttons. Top left button will generally take you back to the screen you were on before.
Other buttons my take you to a help screen for the feature you are looking at, or navigate to a related screen.
Back to Table of Contents
OnTrac® CS-8 and OnTrac® CS-4
Both version of the OnTrac® are similar, and have almost all the same capabilities. The major difference is the
screen sizes and the ability to support the RMC card.
Back to Table of Contents
CS-8
The OnTrac® CS-8 has an 8” display, and can support the Remote Monitoring and Control feature (RMC) and the
Data Acquisition feature. When the RMC feature is used, the OnTrac® will require a separate Ethernet connection
for this feature.
®
Riverside Hydronics , LLC
WWW.RIVERSIDEHYDRONICS.COM
3220 Galvez Avenue - Fort Worth, Texas 76111 - Tel 1-800-990-5918
34-152 04/2014
Page | 6
OnTrac® Installation and Operation Manual
CS-4
OnTrac® CS-4 is a significant cost savings from the CS-8, and still offers all the basic features, including up to 28
boilers. Size of screen is smaller, and no RMC or Data Acquisition capabilities.
Back to Table of Contents
Parts Description Included:
OnTrac® display enclosure
OnTrac® Power supply with screw on plug nut
Probe 5’ cable; System Sensor
Thermal Well for System Sensor
Probe 5’ cable; Outdoor Sensor
Documentation
Parts Location:
It is important to keep up with the parts, as many times the OnTrac® may be shipped with the boilers, but the
integration of the OnTrac® may take place months after the install of the boilers is complete. This is an
opportunity for the sensor, thermal well, or the OnTrac® to become lost at a construction site.
®
Riverside Hydronics , LLC
WWW.RIVERSIDEHYDRONICS.COM
3220 Galvez Avenue - Fort Worth, Texas 76111 - Tel 1-800-990-5918
34-152 04/2014
Page | 7
OnTrac® Installation and Operation Manual
OnTrac® Display Enclosure
Back to Table of Contents
Power Switch
The power switch does not light up. Up position is the ON position, it may take a minute before the screen
initializes.
Fuse
MDA 1 Amp TIME DELAY 6X32mm PN 5752
®
Riverside Hydronics , LLC
WWW.RIVERSIDEHYDRONICS.COM
3220 Galvez Avenue - Fort Worth, Texas 76111 - Tel 1-800-990-5918
34-152 04/2014
Page | 8
OnTrac® Installation and Operation Manual
Power Jack and Power Supply
Power Supply is made up of PN 116717 wall supply, and the plug PN 119078. Polarity typically striped wire is (+),
but should be verified. Center of plug is (+)
Plug PN 119078 provides a screw fastening to the OnTrac® box to prevent disconnects. Original plug is removed
from power supply and this one is attached via soldering to the end of the power supply cable. Polarity is inside (+),
outside (-)
Back to Table of Contents
®
Riverside Hydronics , LLC
WWW.RIVERSIDEHYDRONICS.COM
3220 Galvez Avenue - Fort Worth, Texas 76111 - Tel 1-800-990-5918
34-152 04/2014
Page | 9
OnTrac® Installation and Operation Manual
Probes
PN 104195 Probe with 5’ of cable. 2 are included with OnTrac®, one is for use as the system sensor using the
thermal well, and the other is for the outdoor sensing. It is best to mount the outdoor sensor with a plastic wire
tie to prevent any metal from affecting the air temperature reading. The wires can be extended to reach the
desired locations.
Thermal Well
PN 109535 Brass Thermal Well 1/2-14 NPT, 7/8” hex head, for system sensor. This is to be installed in the system
sensing location. This location will typically be in the building HWS or HWR headers. Decision on location is made
by review of system piping, flow, and sequence of the hydronic loop.
Field Terminal Strip
Field connection terminal are located under the field access cover.
Back to Table of Contents
Ethernet Connection CS-4 & CS-8 PLC
CS-4 and CS-8 are equipped with an Ethernet connection for MODBUS TCP. Location is at the Field Access Terminal
area. This connection is a coupler connected to the end of a short cable coming from inside the OnTrac® box and it
®
Riverside Hydronics , LLC
WWW.RIVERSIDEHYDRONICS.COM
3220 Galvez Avenue - Fort Worth, Texas 76111 - Tel 1-800-990-5918
34-152 04/2014
Page | 10
OnTrac® Installation and Operation Manual
originates at the OnTrac® PLC. Through this port, all data and parameters can be read. This port will also interface
with gateways to convert the MODBUS TCP to other protocols as required. It can also be connected to an Ethernet
switch or hub to connect to a building automation system network. If connecting to an Ethernet network, it is
important to set the IP Address of the OnTrac®. To change the IP Address on the PLC of the OnTrac® will require a
software utility and a special programming cable PN 114514. Please contact factory if this needs to be changed in
the field. If IP address information is supplied before the OnTrac® ships from the factory, it can be pre-configured.
Ethernet Connection for CS-8 with RMC OPTION
nd
CS-8 can have the RMC option card, in this situation you will have a 2 Ethernet connection, originating at the
touch panel RMC card. This Ethernet connection is used for remote access to the OnTrac® via the supplied RMC
software, and if the Data Acquisition option has been included, then it can also be used to access the data stored
on the SD card of the touch panel. The settings for this Ethernet port can be configured using the touch panel.
PLC Programmable Logic Controller
Inside the OnTrac® is a PLC that performs the control functions of the OnTrac®. This device stores the program
logic and parameters and is subject to a Lithium battery to maintain this information. All control and
communication with the Boilers and any Building Automation System or Gateway is from this PLC. The PLC is
capable of functioning even when the touch panel is not connected or working.
PLC RS-485 PORT
The PLC has a RS-485 port that communicates to the boilers through a RS-485 isolation repeater.
PLC PANEL Interface
The PLC has a 9 pin D-SUB connection that connects with the touch panel. This allows the touch panel to read and
change any parameters in the PLC.
PLC BATTERY Indicator
Next to the battery on the PLC is a LED that indicates low battery. If illuminated, then the battery is showing to be
not working on the PLC. If the OnTrac® is still functioning, it is possible to change this battery with the power ON,
and retain the program and settings. THE POWER MUST BE ON WHEN CHANGING THE BATTERY! See section on
changing the batteries.
Back to Table of Contents
RS-485 Repeater Module
Located inside the OnTrac®, this is a module that takes the RS-485 signal and provides electrical isolation between
the PLC and the boilers. If only one LED is flashing, this indicates the master is talking and nothing is responding. If
2 LEDs are blinking, then the master is talking and the salve devices are responding. Note the master is the PLC,
and the slave devices are the boilers. This device also provides line biasing to help improve communication
between the OnTrac® and the boiler’s TempTrac®
Touch Screen Panel
The touch screen serves as the human interface. This allows the operator to setup, view, and change parameters
of the system. It also provides a place to view the status of operation. The touchscreen does not perform any
controlling functions directly. This is done by the PLC. The touch panel gives graphical representation to
parameters, and values, as well as displays descriptive text to make the PLC functioning and values
understandable.
Programming Port
This is a 9-pin D-SUB serial port used to update firmware, and update the touch panel and PLC program. This port
can also be used for the RMC feature, but it will operate at a much slower speed.
Ethernet Port for RMC feature
OnTrac® CS-8 had the capability for a RMC card to be installed. If this option is present, then the OnTrac® will have
an Ethernet port. This port can be connected to a network or to a computer for Remote Monitoring and control.
®
Riverside Hydronics , LLC
WWW.RIVERSIDEHYDRONICS.COM
3220 Galvez Avenue - Fort Worth, Texas 76111 - Tel 1-800-990-5918
34-152 04/2014
Page | 11
OnTrac® Installation and Operation Manual
The software for this feature ships with the OnTrac® and must be installed on a PC with Ethernet connection to the
OnTrac®. You may need to configure the RMC features of the OnTrac®, and setup the IP address. This can be done
through the touch panel interface under the CONFIG> RMC SETUP options.
OnTrac® Optional Equipment:
Analog Input Module for 4-20mA Remote Setpoint Option (REMSET)
This option includes the addition of an Analog Input module to the OnTrac® PLC. This allows a BAS to supply a 420mA signal for Setpoint. The range of this signal can be configured in the Options screen. It is important that this
option is not confused with a BAS that is changing the setpoint using communication.
Remote Equipment Option (REMEQ)
2 Relays installed in OnTrac® to allow for equipment to be enabled when a call for heat is needed. This can also be
used as a building pump enable. This should not be used for any safety related devices, such as venting. All safety
related devices should be directly interfaced with the boilers.
Panel Mounted Audible Alarm (AUDALARM)
Alarm mounted in panel, can be silenced in the CONFIG menu.
Remote Alarm Contacts (REMALARM)
A relays provides dry contacts for alarm
Remote Access and Control (RMC) CS-8 Option Only
This is an additional card in the touch panel and software for a PC to allow Ethernet connection from a PC to the
touch panel. The RMC card has an Ethernet port for this purpose.
Data Acquisition (DAQ) Expands RMC Option
This feature offers data storage and the ability to collect that data over an Ethernet connection. For more details
regarding this feature, please refer to the program literature. This option required the RMC option to be present.
It adds a 2 GIG SD card to the RMC card, and uses a program for PC access to the SD card data over Ethernet.
Back to Table of Contents
Getting Started:
It is important to know what components and options you have with your system. You should have an OnTrac®
startup form that will provide what options are installed on the unit, as well as a place for you to record the
parameters once the startup is completed. The OnTrac® startup should be completed after the boilers have had
their startup procedure completed. It is advised that the person setting up or making adjustments to the OnTrac®
have knowledge of the entire hydronic loop. We have a “Boiler Application Survey” form that can be used as a tool
for gathering this information.
Wiring and Hookup
Boiler – OnTrac® Communication Hookup
The RS485 serial line applied to the OnTrac® is a “Two Wire” electrical interface in accordance with the EIA/TIA485 standard. A third conductor is to provide shielding and a common ground for the system. A balanced twisted
pair with shield is recommended. AWG26 or larger can run up to 1000m. It is recommended that the RS485 serial
line be run separately from any other electrical wiring in order to minimize electric interference. On a RS485 2
wire-bus, at any time only one driver has the right for transmitting.
®
Riverside Hydronics , LLC
WWW.RIVERSIDEHYDRONICS.COM
3220 Galvez Avenue - Fort Worth, Texas 76111 - Tel 1-800-990-5918
34-152 04/2014
Page | 12
OnTrac® Installation and Operation Manual
•
•
•
•
Connect the positive wire to the + terminal on the field connection terminal strip.
Connect the negative wire to the – terminal on the field connection terminal strip.
Connect the common ground and shield to the G terminal on the field connection terminal strip.
Connect earth ground to ground lug.
Remote Equipment Option Hookup (REMEQ or PUMP)
The Remote Equipment feature is provided for the activation of equipment such as circulation pumps. Air louvers
and active ventilation systems should not be interfaced directly with the OnTrac®; they should be interfaced
directly with the boilers. When there is a call for heat the OnTrac® will energize the remote equipment contacts
and wait for a set time for any Remote Proving circuits to be energized. There are two relay outputs provided.




There are two Remote Equipment outputs available. Both relays are rated for 110VAC with a maximum
switching current of 10A.
Normally Open contact is available with terminals P1 and P2
Normally Closed contact is available with terminals P3 and P4
When used as a circulation pump for a building loop, the option for invert the logic so that N.C. contact
can be used to drive the pump is available. This allows pump operation is the OnTrac® loses power.
®
Riverside Hydronics , LLC
WWW.RIVERSIDEHYDRONICS.COM
3220 Galvez Avenue - Fort Worth, Texas 76111 - Tel 1-800-990-5918
34-152 04/2014
Page | 13
OnTrac® Installation and Operation Manual
Remote Alarm Option Hookup (REMALARM)
The Remote Alarm contacts are provided as a remote indication of a system alarm. This indication is not specific in
nature but intended to alert the user of a problem. Details of the alarm condition can be found by viewing the
Boiler Status screen on the OnTrac® or at the individual boiler.
•
•
The relay contacts for this feature are rated for 110VAC with a maximum switching current of 15A.
Connect the alarm load to A1 and A2.
Back to Table of Contents
System Sensor and Outdoor Sensor Location and Hookup
The system and outdoor sensors for the OnTrac® are connected typically through Boiler 1 for the system sensor
and Boiler 2 for the outdoor sensor. This is the default assignment but the location can be changed in the event of
a faulty control. Follow the instruction below for wiring termination.
The wire leads for the system and outdoor sensor should be connected to the TempTrac® control located on the
control panel of the boiler. For the system sensor, use sensor (P/N 102163) and brass thermal well (P/N 109535)
1/2-14 NPT. A thermal well is not necessary for the outdoor sensor.
1.
2.
3.
4.
5.
Turn off power to the boiler.
Remove and screw to access the back side of the TempTrac®
Run the wires from the probe to the TempTrac®. Terminal 17 is the common for all the probes. Probe 1
connects to Terminal 14, Probe 2 connects to terminal 15, Probe 3 connects to Terminal 16. The other
wire of all probes goes to terminal 17 of the TempTrac®
The probes do not have a polarity, and the wires can be extended.
Run the probe and wires as required for local code and standards. The wiring type is; low voltage sensor
wire.
®
Riverside Hydronics , LLC
WWW.RIVERSIDEHYDRONICS.COM
3220 Galvez Avenue - Fort Worth, Texas 76111 - Tel 1-800-990-5918
34-152 04/2014
Page | 14
OnTrac® Installation and Operation Manual
Back to Table of Contents
TempTrac® Control Module (Satellite Module)
We offer a Satellite control module that can be used for sensor inputs as well as control of other equipment. The
uses of this device if open, as it is a bridge to interface with other equipment of perform functions not normally
associated with our equipment.
Control Module For Non-Riverside Tier 2 Boilers
When non-Riverside Hydronics boilers are controlled by the OnTrac® boiler management system, the optional
TempTrac® Boiler Control module can be applied as a fully functional operating control or used to enable and
disable only.
This module will be treated as a boiler in the wiring of TempTrac® models.
If the module is applied as an enable/disable (ON/OFF ONLY), the R1 & R2 terminals will interrupt the operating
circuit of the boiler or equipment. The modulation, staging and primary temperature regulation function will be
controlled by the existing boiler controls. Warning: Do not disable the existing boiler controls or bypass the existing
temperature limits. When the (ON/OFF ONLY) function is used the TempTrac® temperature sensor can be used for
displaying the boiler temperature only or left to display the room temperature. The sensor is coiled and placed
inside the enclosure. Do not disconnect sensor.
Control Module For Sensor Inputs
The TempTrac® Control Module can be used as an auxiliary sensor reading device. Some boilers are able to use
Probe 3 for this purpose and this module is not needed. Some boilers (such as the M3) do not have Probe 3
available for this purpose and will require this module for system sensor and/or outdoor temperature reading. It
can also be used as an option to allow the system sensor to not be dependent on one boiler being operational.
Probe 1 & Probe 3 inputs should be used for Outdoor and System sensors.
®
Riverside Hydronics , LLC
WWW.RIVERSIDEHYDRONICS.COM
3220 Galvez Avenue - Fort Worth, Texas 76111 - Tel 1-800-990-5918
34-152 04/2014
Page | 15
OnTrac® Installation and Operation Manual
Control Module Full Control
If the TempTrac® Control Module is applied in the (FULL CONTROL), R1 & R2 terminals will interrupt the operation
of the boiler and T1 and T2 terminals will provide a 4 to 20mA signal to modulate the firing rate of the burner. If
applied, terminals A1 & A2 can be wired to an alarm input from the boiler. The TempTrac® control will
communicate boiler water temperature to the OnTrac® Multiple Boiler Control. Alarm condition can also be
communicated back to the OnTrac® if the alarm input is wired to A1 & A2
Control Module Wiring
Wiring Enable/Disable
The first step will be routing the operating circuit through the R1 & R2 terminals (15Amp Max). This will also
require that the existing operating control set-point be raised so as not to interrupt the normal operation of the
boiler. If this is not possible, the existing operating control must be removed. Warning: Do not bypass the existing
boiler limits.
®
Riverside Hydronics , LLC
WWW.RIVERSIDEHYDRONICS.COM
3220 Galvez Avenue - Fort Worth, Texas 76111 - Tel 1-800-990-5918
34-152 04/2014
Page | 16
OnTrac® Installation and Operation Manual
Wiring Modulation signal 4-20mA
Next, the existing modulation control must be disconnected and replaced with the modulation signal from the
TempTrac® Control Module (T1 & T2).
Temperature Sensor location
The temperature sensor must be installed in a location that allows the control module to monitor the boiler water
temperature. If the sensor is not installed in a thermal well, care should be taken to find a clean surface location
near the boiler outlet and insulate the junction well. The sensor probe dimensions are: ¼” dia x 1 ¾” long. The wire
length is 5ft but can be increased to up to 100ft.
Alarm input from existing equipment
The alarm terminals (A1 & A2) require a 120Vac input to indicate an alarm condition to the OnTrac®.
Back to Table of Contents
Assigning Boiler Addresses
The first step commissioning an OnTrac® system will be the assignment of the address number for each boiler. The
following instructions are specific to the TempTrac®. If your boiler uses a different control refer to the
programming instruction for that control to set the control address.
1.
2.
3.
4.
5.
6.
7.
8.
Enter the Programming mode by pressing the “set” and “DOWN” key for more than 3 seconds. (lead
with the SET key)
Pressing the “DOWN” key, parameters will display in top, and value in bottom.
Select “Pr2” – “PAS” (parameter – value), and press the “set” key.
The value “0 - -” with a flashing zero is displayed
Use “UP” or “DOWN” keys to input the security code in the flashing digit; confirm the figure by pressing
“set”. The security code is “321“
Once you have entered the “Pr2” menu press the “DOWN” key until you see the parameter “Adr” appear
on the top of the screen
Now press the “set” key once and the number will begin to blink. Use the arrow key to set the address
from (1 to 28). The address range (1 to 20) is reserved for Tier 1 boilers only. The address range (21 to 28)
is reserved for Tier 2 boilers
Each boiler must be assigned a different address in order for proper communication to occur
Back to Table of Contents
®
Riverside Hydronics , LLC
WWW.RIVERSIDEHYDRONICS.COM
3220 Galvez Avenue - Fort Worth, Texas 76111 - Tel 1-800-990-5918
34-152 04/2014
Page | 17
OnTrac® Installation and Operation Manual
Check List before OnTrac® Power Up:







OnTrac® is mounted and has power
Boilers have power
Boilers are daisy chain wired to the RS-485 MODBUS RTU and connected to the OnTrac®
If used, isolation valves are wired to boilers
If used, boiler pumps are wired to boilers
Building pump is operational
The loop is capable of taking some heat, if not, disable the gas
Back to Table of Contents
Check List for total setup of OnTrac®:
The OnTrac® should have a sheet for configuration and system loop information specific to the job site and the
serial number of that OnTrac®. This should be reference as it will be specific to the hydronic loop you are working
on. In general, the following should be done:
 Gather all hydronic loop information available, and sequence information that needs to be followed.
 The boilers have been through the startup procedure, and combustion has been adjusted
 Boiler TempTrac® Modbus addresses have been set, Tier 1: 1-__ And Tier 2: 21-__
 System sensor installed in the proper location and connected to a boiler?
 See OnTrac® Configuration Sheet, Usually connected to Probe 3 of Boiler #1
 Outdoor Temperature Probe, if required
 Usually connected to Probe 3 of Boiler #2
 System ready to accept heat, system loop pump is running?
 On primary only system with isolation valves
 Isolation valves are initiated from output 3 of TempTrac®, Boiler terminals LOCAL 1 & LOCAL 2
 This is a dry signal contact (1 amp) and should be buffered with a relay.
 Remote Equipment Boiler (Boiler Pump, Louvers, Powered venting)
 Ensure equipment is setup to run from boiler supplied relay contact as a signal.
 Remote Equipment OnTrac® (BLD Pump option)
 Ensure building pump is connected to operate from OnTrac® contacts
 The boiler TempTrac can be configured to operate in several different manors. Ensure the TempTrac is
configured to operate properly for this loop and configuration
 Building Automation System (BAS)
 Interface methods
 Discreet connections OnTrac®
 C1 & C2 enable system. C1&C2 open = disabled, jumped = enabled
 Analog Input option for 4-20mA setpoint signal
 MODBUS TCP (Ethernet, standard)
 Controls contractor will require the OnTrac® MODBUS POINT LIST
 Default IP address of OnTrac® is 192.168.1.100
 Gateway interface to BACNET or LONWORKS, Default IP address of gateway is 192.168.1.24
 Does this OnTrac® have the RMC option?
 If so, then software must be given to customer.
 Default IP address of the OnTrac® RMC option card is 192.168.1.20
 Determine the quantity and type of boilers in the system
 Boilers on Tier 1 ( Condensing Boilers, or more efficient)
 Boilers on Tier 2 ( non-condensing boilers, or less efficient)
Back to Table of Contents
®
Riverside Hydronics , LLC
WWW.RIVERSIDEHYDRONICS.COM
3220 Galvez Avenue - Fort Worth, Texas 76111 - Tel 1-800-990-5918
34-152 04/2014
Page | 18
OnTrac® Installation and Operation Manual
OnTrac® Service:
Annual Battery Maintenance:
Battery replacement for the OnTrac® should be done each year. All OnTrac® controls have a PLC battery. OnTrac®
CS-8 also has a Touch panel battery. Be sure to follow the procedure when replacing the battery. Failure to
replace the battery or improper battery replacement can result in the loss of program and parameters for the
OnTrac®. In this event, you may be required to have a service technician reload the program and parameters or
send the OnTrac® to the factory for reprogramming.
OnTrac® PLC battery Replacement:
Battery is a coin cell 3.0V Lithium 2032 battery readily available in retail stores, our PN 113718.
When replacing battery, you must have the power ON to avoid losing any parameters. With power on, remove the
top left and right screw/bolts and pull the OnTrac® door out.
Newer OnTrac®, PLC mounted on back panel of OnTrac® Box
Mounted on the back panel is the OnTrac® PLC, and the coin cell battery should be visible. Be careful not to short
the traces on the circuit board with the battery or your screw driver. Also, take typical static precautions by
grounding yourself to the frame of the OnTrac® box. Using a small flathead screwdriver, gently raise the clamp
holding the battery and slide out the old battery, and replace with new battery.
Older OnTrac®, PLC mounted on back of Touch Panel
On the left side of the PLC/Panel combo should be a clip, by pressing in on this clip, you should be able to open the
back/top plastic cover to show the PLC. With the cover raised the coin cell battery should be visible. Be careful not
to short the traces on the circuit board with the battery or your screw driver. Also, take typical static precautions
by grounding yourself to the frame of the OnTrac® box. Using a small flathead screwdriver, gently raise the clamp
holding the battery and slide out the old battery, and replace with new battery.
Touch Panel Battery Replacement, OnTrac® CS-8 only:
The battery is a 3.6V Lithium ½ AA battery, available at some retail stores. Our PN 113717
It is advised to change this battery at the same time as the PLC battery. When replacing battery, you must have
the power ON to avoid losing any parameters. With power on, remove the top left and right screw/bolts and pull
the OnTrac® door out
Newer OnTrac®, PLC mounted on back panel of OnTrac® Box
On the left side of the Touch panel, there is a clip, by pressing in; you should be able to open the back cover. The
battery should be visible and easy to replace. Ensure you install with proper orientation.
Older OnTrac®, PLC mounted on back of Touch Panel
On the left side of the PLC/Panel combo should be a clip, for PLC access, and below that, recessed in a bit, there
should be another clip that will allow the entire PLC to swing out on a hinge. Pressing in on this clip, you should be
able to partially open the back panel of the touch panel. The battery should be visible and easy to replace. Ensure
you install with proper orientation.
After Battery replacement:
The OnTrac® has a battery replacement log and a feature in the software for recording the date of battery
replacement. If your OnTrac® does not have this log, or you need another, the label PN 122207
After battery replacement, it is important to go into the CONFIG>BATTERY screen and reset the battery counter.
This will start the count at 365 days until next battery warning. See BATTERY SCREEN feature
Back to Table of Contents
®
Riverside Hydronics , LLC
WWW.RIVERSIDEHYDRONICS.COM
3220 Galvez Avenue - Fort Worth, Texas 76111 - Tel 1-800-990-5918
34-152 04/2014
Page | 19
OnTrac® Installation and Operation Manual
OnTrac® Touch Screen Interface:
Touch Screen Navigation
OnTrac® touch screen navigation follows the following guide lines.
Top left goes back to previous screen.
Buttons that take you to other screens are grey.
Buttons that require a password will prompt for the password when pressed. Password protected screens will
have a slightly different color.
Some advanced features will prompt for a password when a password has not been setup. You can continue by
pressing ENTER. This is a prompt to indicate this is an advanced option.
Numbers and values in Blue indicate parameters that can be edited from that screen.
Parameters that require a number will prompt with a keypad for number entry.
Some parameters are toggles, such as feature enables.
Help buttons are available on most screens that require explanation; some screens have descriptions on the
screen.
Screens with a large amount of help documentation will use multiple help screens and will have navigation buttons
to move to the next or previous screen.
Back to Table of Contents
Startup Screen / Lock Screen
CS-4: MAIN: LOCK SCRN, and when powered up
CS-8: MAIN: LOCK SCREEN, and when powered up
User Level: Special limited only of PASSWORD 0 is set, Level 0-2
Purpose: Display temperatures only, and provide a locked screen to limit access
Edit Parameters: NONE
View Parameters: SYSTEM TEMPERATURE, ADJUSTED SETPOINT, OUTDOOR TEMPERATURE, SYSTEM 2
TEMPERATURE, POWERED UP TIME
CS-8 >
< CSC4
Details: When the OnTrac® is powered up, this is the first screen. Is PW0 is set to anything other than zero; this
will also be the LOCK SCREEN. To be used to lock the system to prevent anyone without a password from making
changes to the system. To get out of the lock screen, you will need to use the password of PW0, PW1, or PW2.
Please note that PW3 cannot be used for this. The reason is PW3=0 can disable all other passwords for the system,
but the LOCK SCREEN. That way you can just use PW0 (the lock screen) for security, or you can use PW1, 2, 3 for
security, or both. See password section for more information.
Back to Table of Contents
System History screens
CS-4: MAIN:> STATUS: HIST GRAPH
CS-8: MAIN:>STATUS: DISPLAY HISTORY GRAPH
®
Riverside Hydronics , LLC
WWW.RIVERSIDEHYDRONICS.COM
3220 Galvez Avenue - Fort Worth, Texas 76111 - Tel 1-800-990-5918
34-152 04/2014
Page | 20
OnTrac® Installation and Operation Manual
User Level: All, Display information only, clear graph, change pen numbers
Purpose: To provide trending data on screen of standard values and 2 programmable parameters
Display Parameters: OPTIONAL PIN 1, OPTIONAL PIN2, SYSTEM TEMPERATURE, BOILER 1 INLET, OUTDOOR
TEMPERATURE, BOILER 2 RETURN
Edit Parameters: OPTIONAL PIN 1, OPTIONAL PIN 2
CS-8 >
< CSC4
Details: The SYSTEM HISTORY screen is capable of providing the user with historical logging of system
temperatures such as system temperature, boiler temperature and outdoor temperature.
This feature is preprogramed to record readings every five minutes and store up to 10,000 scans. Use the arrows at
the top left corner of the screen to move back through the historical scans. The CLR button will clear all historical
data.
The preselected pens are System Temperature, Outdoor Temperature, and Return and Supply Temperatures for
Boiler 1. There are two optional pens which can be assigned to record the Return or Supply Temperatures for any
of the boilers in the system. The schedule below assigns a number to each of those temperatures if present. To
assign an optional pen a temperature, touch the number (OPTIONAL PEN 1 or OPTIONAL PEN 2) and enter number.
Select if you want INPUT (probe1) or OUTPUT(probe2) of boiler
Numbers 1 to 20 are the TIER 1 boilers
Numbers 21 to 28 are the TIER 2 boilers 1-8
Back to Table of Contents
Boiler Status Group screens
CS-4: MAIN:> STATUS: VIEW T 1 or VIEW T 2
CS-8: MAIN:> STATUS: VIEW (TIER 1) BOILERS or VIEW (TIER 2) BOILERS
User Level: All, Display information only
Purpose: Provide visual view of parameters of several boilers on one screen
Display Parameters: SYSTEM TEMPERATURE, ADJUSTED SETPOINT, OUTDOOR TEMPERATURE, TIER 2
COUNTDOWN, ENABLE STATUS, ADDING BOILERS / REMOVING BOILERS, TEMPTRAC® SETPOINT FOR BOILERS,
BOILER ENABLED OR DISABLED, BOILER IDLE OR HEATING, LOCKOUT STATUS, INLET TEMPERATURE FOR BOILERS,
OUTLET TEMPERATURE FOR BOILERS, ADD OR REMOVE BOILER COUNTDOWN, COMUNICATION STATUS
Details: For each boiler that is installed, the corresponding graphic will be visible. In the upper right of screen are
buttons to navigate to additional screens if boilers are installed that require more screens. The top section of this
screen will display System Temperature (SYS), System Setpoint (SP), Outdoor Temperature (OD), Tier 2 counter (T2
ON)
Tier 1 boilers are numbered from B1 – B20. Tier 2 boilers 1-8 are numbered B21-B28
For each boiler indicator, Black indicates boiler is disabled by the OnTrac®. Yellow indicates it is enabled.
Under the boiler indicator is the status of the boiler. IDLE indicates the boiler is enabled, but it is not adding heat
to the system. HOT or HEATING indicates the boiler is firing and adding heat to the system. Next is SETPOINT, this
is the setpoint actually read from the TempTrac. The OnTrac® supplied the setpoint to the TempTrac, but this
®
Riverside Hydronics , LLC
WWW.RIVERSIDEHYDRONICS.COM
3220 Galvez Avenue - Fort Worth, Texas 76111 - Tel 1-800-990-5918
34-152 04/2014
Page | 21
OnTrac® Installation and Operation Manual
value is read from the TempTrac. TempTrac® setpoint will be different from the ADJUSTED SYSTEM SETPOINT due
to the parameters setup in TEMPTRAC® OFFSET and PROPORTIONAL CONTROL
Back to Table of Contents
Boiler Status Individual screen
CS-4: MAIN:> STATUS: VIEW ONE
CS-8: MAIN:> STATUS: VIEW SINGLE BOILER
User Level: All, Display information only
Purpose: Provide visual view a single boiler
Display Parameters: SYSTEM TEMPERATURE, ADJUSTED SETPOINT, OUTDOOR TEMPERATURE, TEMPTRAC®
SETPOINT FOR BOILERS, BOILER ENABLED OR DISABLED, BOILER IDLE OR HEATING, INLET TEMPERATURE FOR
BOILERS, OUTLET TEMPERATURE FOR BOILERS, DELTA OF BOILER, RELAY STATUS, HOURS BURNER ON,
MODULATION RATE
Edit Parameters: BOILER NUMBER
Details: Graphically show a single boiler, inlet temperature, outlet temperature and other parameters. Number of
hours the burner has been on is displayed on this screen. Other information is available, such as current status or
the TempTrac® relays, low fire, high fire, and modulation rate. Note: RELAY 3 is for isolation valves, RELAY 1 is for
the burner enable.
Back to Table of Contents
Boiler Firing Rate screens
CS-4: MAIN:> STATUS: RATE T1, RATE T2
CS-8: MAIN:> STATUS: TIER 1 FIRING RATE, TIER 2 FIRING RATE
User Level: All, Display information only
Purpose: Provide visual view of boiler modulation rates
Display Parameters: SYSTEM TEMPERATURE, ADJUSTED SETPOINT, OUTDOOR TEMPERATURE, BOILER ENABLED
OR DISABLED, BOILER IDLE OR HEATING, LOW FIRE, MODULATING, MODULATION RATE, HIGH FIRE
Edit Parameters: None
Details: For each boiler that is installed, the corresponding graphic will be visible. Tier 1 boilers are numbered
from 1 – 20. Tier 2 boilers 1-8 are numbered 20+ 1 - 8
For each boiler indicator, RUN (R) indicates the boiler is enabled by the OnTrac® and OFF (O) indicates the boiler is
disabled by the OnTrac®. Yellow bar and number indicates modulation rate. Also yellow indicators for LOW FIRE
and HIGH FIRE are also present.
Back to Table of Contents
Battery Screen
CS-4: MAIN:> CONFIG: BATTERY SCREEN
CS-8: MAIN:> CONFIG: BATTERY SCREEN
User Level: Access to CONFIG screens, LEVEL 2-3
®
Riverside Hydronics , LLC
WWW.RIVERSIDEHYDRONICS.COM
3220 Galvez Avenue - Fort Worth, Texas 76111 - Tel 1-800-990-5918
34-152 04/2014
Page | 22
OnTrac® Installation and Operation Manual
Purpose: Allow setting of battery replacement parameter, required when battery is replaced, battery failure, and
when the OnTrac® program has been upgraded.
Display Parameters: NUMBER OF DAYS LEFT (BATTERY), BATTERY FAULT
Edit Parameters: RESET BATTERY
Details: When the battery for the PLC and/or PANEL is replaced, this button should be toggled. This resets the
counter for the annual battery replacement counter. Also in the event of a failed battery, this screen will indicate
battery failure and will need to be toggled. If a date other than the current date needs to be used for the date of
battery replacement, then change the DATE before hitting the BATTERY RESET button, and then change the date
back.
CS-4 has only 1 battery located in the PLC at the back of the OnTrac®
PLC Battery PN 113718, Generic description: 3.0V Lithium Coin Cell 2032
CS-8 has 2 batteries, one in the PLC, and the other is located in the back of the touch panel.
Panel Battery PN 113717, Generic description: 3.6V Lithium 1/2AA
Back to Table of Contents
Time and Date screen
CS-4: MAIN:> CONFIG: TIME DATE
CS-8: MAIN:> CONFIG: TIME DATE
User Level: Access to CONFIG screens, LEVEL 2-3
Purpose: Allow setting of internal real time clock, date, and day of week
Display Parameters:
Edit Parameters: TIME, DATE, DAY OF WEEK
Details: Setting of time, date and day of week. Year is only 2 digits, time is in 24 hour format, and day of week is
SUNDAY = 1, …, SATURDAY = 7
If for any reason the time and date error is present, after setting the time and date, there will be a special button
available to clear the time and date error.
Back to Table of Contents
Service Boilers screen
CS-4: MAIN:> CONFIG: SERVICE BOILERS
CS-8: MAIN:> CONFIG: SERVICE BOILERS
User Level: Access to CONFIG screens, LEVEL 2-3
Purpose: Allow service technician to work on boiler without the OnTrac® interfering
Display Parameters:
Edit Parameters: BOILER IN SERIVCE or OUT FOR MAINTENANCE
®
Riverside Hydronics , LLC
WWW.RIVERSIDEHYDRONICS.COM
3220 Galvez Avenue - Fort Worth, Texas 76111 - Tel 1-800-990-5918
34-152 04/2014
Page | 23
OnTrac® Installation and Operation Manual
Details: When a boiler is place din OUT FOR MAINTENANCE, the OnTrac® will stop communicating with the boiler.
This will allow the service technician to enable/disable the TempTrac® as well as make adjustment to it in order to
conduct maintenance. The OnTrac® will treat any boiler that is OUT FOR MAINTENANCE as it would treat a lockout
out boiler.
A warning will be displayed on the main screen indicating that a boiler or boilers are OUT FOR MAINTENANCE, this
is to help ensure a boiler is not accidentally left in this condition.
A special button to the MAINTENANCE BOILERS screen will be present on the main screen to quickly enable service
technician to put a boiler back into service before they leave the job site.
WARNING: The OnTrac® will not be able to disable any boiler in this condition, the service technician needs to be
aware of the building loop and conditions to prevent any possible over temperature situation.
Back to Table of Contents
Initial Setup Button
CS-4: MAIN: INITIAL SETUP (BLINKING) Only visible when setup is not competed
CS-8: MAIN: INITIAL SETUP (BLINKING) Only visible when setup is not competed
User Level: Special, Displayed until turned off by service Tech
Purpose: To provide shortcut to needed parameters for initial setup of OnTrac®
Edit Parameters: NUMBER OF BOILERS TIER 1 & TIER 2, SYSTEM SETPOINT, SENSOR SETUP SCREEN, BUTTON
VISIBLE, TIME SCREEN, BATTERY SCREEN
View Parameters: SYSTEM TEMPERATURE, OUTDOOR TEMPERATURE, SYSTEM 2 TEMPERATURE, MODBUS
STARTING ADDRESSES,
Details: When first installed, this option should be visible from the main menu. It is used to complete initial setup
parameters. Service technicians should configure the number of boiler for each tier, set the MODBUS RTU address
on the boilers, adjust the SYSTEM SETPOINT, and configure
NOTE: When all steps in the initial setup are completed, the BUTTON VISIBLE should be changed to BUTTON
HIDDEN to remove the INITIAL SETUP button from the main screen
Back to Table of Contents
Initial Setup Buttons/Screen
CS-4: MAIN: INITIAL SETUP
CS-8: MAIN: INITIAL SETUP
User Level: Access to CONFIG screens, LEVEL 2-3
Purpose: Allow service technician to work on boiler without the OnTrac® interfering
Display Parameters: SYSTEM TEMPERATURE, OUTDOOR TEMPERATURE, SYSTEM 2 TEMPERATURE
Edit Parameters: NUMBER OF BOILERS ON TIER 1, NUMBER OF BOILERS ON TIER 2, SYSTEM SETPOINT, VISIBLE
INITIAL SETUP BUTTON, MODBUS RTU START ADDRESS
Details: This button is enabled when first shipped, and can be re-enabled in the CONFIG screens
Provides access to the settings needed on initial install of OnTrac®
®
Riverside Hydronics , LLC
WWW.RIVERSIDEHYDRONICS.COM
3220 Galvez Avenue - Fort Worth, Texas 76111 - Tel 1-800-990-5918
34-152 04/2014
Page | 24
OnTrac® Installation and Operation Manual
Set number of boiler on Tier 1, and Tier 2.
Set SYSTEM SETPOINT, the desired temperature of the hot water supply of building loop
Quick access to the following screens for initial setup purposes:
SENSOR SETUP screen to configure SYSTEM SENSOR, OUTDOOR SENSOR, SYSTEM 2 SENSOR
TIME / DATE screen for setting time and date
BATTERY screen
Back to Table of Contents
Audible Alarm ON/OFF button ( Optional )
CS-4: MAIN:> CONFIG: AUD ALARM
CS-8: MAIN:> CONFIG: AUDIBLE ALARM
User Level: Access to CONFIG screens, LEVEL 2-3
Purpose: Turn on and off the ability to sound the audible alarm feature.
Display Parameters:
Edit Parameters: AUDIBLE ALARM ON/OFF
Details: AUDIBLE ALARM is an option, when equipped and enabled it provides a loud alarm sounds when the
OnTrac® has alarm fault. The option code when ordering this option on the OnTrac® is AUDALARM
Back to Table of Contents
Timers and Counters
Life On Time Display
CS-4: MAIN:> CONFIG:> CFG 3
CS-8: MAIN:> CONFIG:> CONFIG 2
Purpose: Display a running total of time the OnTrac® has been powered up
Display Parameters: YEARS, DAYS, HOURS, MINUTES
Details: The OnTrac® keeps a running total of time that it has been power on. Note that upon battery failure, or
program update, this value will be reset.
This can be used for diagnostic purposes, or to determine the on time since installation.
Powered on for Display
CS-4: MAIN:> CONFIG:> CFG 3, and on the MAIN screen
CS-8: MAIN:> CONFIG:> CONFIG 2, and on the MAIN screen,
Purpose: Display the OnTrac® has been powered up
Display Parameters: DAYS, HOURS, MINUTES
Edit Parameters:
®
Riverside Hydronics , LLC
WWW.RIVERSIDEHYDRONICS.COM
3220 Galvez Avenue - Fort Worth, Texas 76111 - Tel 1-800-990-5918
34-152 04/2014
Page | 25
OnTrac® Installation and Operation Manual
Details: The OnTrac® displays the amount of time that has passed since it was last powered on. This can be useful
when determining if there have been power interruptions.
Power On Count Display
CS-4: MAIN:> CONFIG:> CFG 3
CS-8: MAIN:> CONFIG:> CONFIG 2
Purpose: Display the number of times the OnTrac® has been powered up
Display Parameters: POWER ON COUNT
Details: Each time the OnTrac® is powered on, the POWER ON COUNT is incremented by 1. This is useful for
troubleshooting power issues.
Back to Table of Contents
OnTrac® Hydronic Features:
The following are feature the affect the hydronic operation.
Outdoor Reset feature
CS-4: CFG 1: OUTDOOR RESET
CS-8: CONFIG MENU 1: OUTDOOR RESET
User Level: Access to CONFIG screens, LEVEL 2-3
Purpose: Provide adjusted setpoint based on an outdoor reset schedule.
Display Parameters: SYSTEM SETPOINT, SYSTEM TEMPERATURE, OUTDOOR TEMPERATURE, CALCULATED
SETPOINT, RESET TABLE
Edit Parameters: OUTDOOR RESET FEATURE ON/OFF, THRESHOLD, BAND WIDTH, MAX SETPOINT SHIFT
Details: The OUTDOOR RESET menu sets the parameters which control the reset or adjustment of the system
setpoint based on changes in outdoor temperature which would require higher system temperature to meet an
increased load. The default state of this function is to be turned off. Once parameter changes are entered the
enable switch should be turned on.
Before using this feature, the OUTDOOR TEMPERATURE SENSOR needs to be installed and connected. See SENSOR
SETUP section.
1.(OUTDOOR TEMPERATURE THRESHOLD) is the outdoor temperature below which this function will begin the
reset adjustment.
2.(BAND WIDTH) is the temperature range below the (THRESHOLD) at which the reset function will continue to act.
3.(MAXIMUM SHIFT OF SETPOINT) is the temperature which will be proportionally added to the setpoint as the
outdoor temperature drops below the (THRESHOLD).
4.(SENSOR SETUP) is defaulted to SENSOR OFF. Use SENSOR SETUP to enable the outdoor sensor. By default
located on boiler 2, Probe #3.
5.(SETPOINT BEFORE RESET) is the system setpoint entered on the ADJUST menu provided here for reference.
6.(SETPOINT AFTER RESET) displays the system setpoint after adjustment by the Outdoor Reset function.
7.(SYSTEM TEMPERATURE) displays the current system temperature.
®
Riverside Hydronics , LLC
WWW.RIVERSIDEHYDRONICS.COM
3220 Galvez Avenue - Fort Worth, Texas 76111 - Tel 1-800-990-5918
34-152 04/2014
Page | 26
OnTrac® Installation and Operation Manual
8.(OUTDOOR TEMPERATURE) displays the current outdoor temperature.
NOTE: If the OUTDOOR TEMPERATURE SENSOR is installed on Boiler #2, In the event that the Boiler 2 control
malfunctions, the sensor location for the outdoor sensor can be reassigned to another boiler, and the sensor needs
to be moved to that boilers TempTrac® control.
Back to Table of Contents
Tune Timing Configuration
CS-4: CFG 1: TUNE TIMING
CS-8: CONFIG MENU 1: TUNE TIMING
User Level: Access to CONFIG screens, LEVEL 2-3
Purpose: Make adjustment to time interval for adding and removing boilers
Display Parameters: TIER 1 ALL ON MINIMUM, TIER 2 TOTAL DELAY BOFOR START
Edit Parameters: TIER 1 DELAY ON, TIER 2 DELAY ON, TIER 1 DELAY OFF, TIER 2 DELAY OFF, TIER 2 SYSTEM DELAY
Details: Provides the amount of time before increasing or decreasing the number of boilers. The amount of time
it take for the water to transvers the building loop should be considered before making this adjustment.
DELAY ON: When the system needs more boilers, this is the amount of time before enabling the next boiler. To
help prevent short cycling, this number should be greater than the amount of time required for the water to
transvers the building loop.
DELAY OFF: When the system needs to decrease the number of boilers, this is the number of minutes before
disabling the boiler.
When a boiler is enabled, that does not mean it is adding heat to the system. I can be idle. Depending on how the
system is setup, it may be a good idea to have a long DELAY OFF to provide a quick reaction to sudden loads.
TIER 1 ALL ON MINIMUM: Display of the minimum amount of time it will require to have all the Tier1 boilers
enabled. The NEED MORE BOILERS flag would have to be constantly enabled. (See TUNE TEMPERATURE for more
details)
TIER 2 SYSTEM ON DELAY: Amount of time to wait after TIER 1 ALL ON MINIMUM has passed all the Tier 1 boilers
are enabled before enabling Tier 2
MINIMUM TOTAL DELAY BEFORE START OF TIER 2: Display of total time required before Tier 2 could become
enabled. This can be over ridden by using the OUTDOOR TRIGGER TIER 2 feature
Back to Table of Contents
Tune Temperature screen
CS-4: CFG 1: TUNE TEMPER.
CS-8: CONFIG MENU 1: TUNE TEMPERATURE
User Level: Access to CONFIG screens, LEVEL 2-3
Purpose: Adjust conditions for adding boilers, removing boilers, enabling system, and disabling system
Display Parameters:
Edit Parameters: TIER 1 & 2 SYSTEM DIFFERENTIAL, RESET DIFFERENTIAL, TIER 1 & 2 TEMPTRAC® OFFSET,
SHUTDOWN DIFFERENTIAL
Details: Make adjustment that will affect when the system is enabled, when it will be disabled, when more boilers
are needed, and when less boilers are needed.
®
Riverside Hydronics , LLC
WWW.RIVERSIDEHYDRONICS.COM
3220 Galvez Avenue - Fort Worth, Texas 76111 - Tel 1-800-990-5918
34-152 04/2014
Page | 27
OnTrac® Installation and Operation Manual
SYSTEM DIFFERENTIAL: Defines the temperature range the OnTrac® will seek to maintain temperature control.
The lower the number, the tighter the control and more cycling.
TEMPTRAC® OFFSET: The amount above SYSTEM SETPOINT the TempTrac® at each boiler will be set. This can also
be affected by the PROPORTIONAL CONTROL feature.
RESET DIFFERENTIAL: The amount above the START ADDING BOILERS setting, to stop adding boilers
Set NEED LESS BOILERS flag if:
SYSTEM TEMPERATURE > SYSTEM SETPOINT – SYSTEM DIFFERENTIAL + RESET DIFFERENTIAL
Set NEED MORE BOILERS flag if:
SYSTEM TEMPERATURE < SYSTEM SETPOINT – SYSTEM DIFFERENTIAL
T1 TUNE and T2 TUNE buttons: Show a graphical representation of the above parameters to help make
adjustment. Show the calculated results of each adjustment as well. Use this to confirm the operation.
Back to Table of Contents
Lead-Lag screen
CS-4: CFG 1: LEAD-LAG
CS-8: CONFIG MENU 1: LEAD-LAG
User Level: Access to CONFIG screens, LEVEL 2-3
Purpose: Chose lead boiler, method of rotating lead boiler as well as the duration
Display Parameters: BURNER HOURS START, BURNER HOURS NOW, BURNER HOURS END
Edit Parameters: LL-DAYS FEATURE ON/OFF, LL-HOURS ON/OFF, DAYS EACH BOILER LEAD, HOURS EACH BOILER
LEAD, CHANGE LB AT TIME OF DAY, HOUR OF DAY TO CHANGE, HOURS BURNER ON BEFORE CHANGE, CURRENT
LEAD BOILER,
Details: Lead boiler is the first boiler to be enabled by the system, and will remain enabled until a need for heat
has been satisfied. Other boilers will be enabled as required to satisfy the heat load. The lead boiler will receive
the most on time.
Changing the lead boiler will allow for distribution of the work load during the life of the boilers. Ways to change
lead boiler: (NUMBER OF DAYS AS THE LEAD BOILER) or (NUMBER OF HOURS THE BURNER HAS BEEN ON). Also
the TIME OF TRANSITION can be configured for transition at the begging of the first hour conditions are true, or
wait for a particular hour of the day/night
DAYS: ENABLE CHANGE ON NUMBER OF DAYS AS LEAD BOILER
HOURS: ENABLE CHANGE ON NUMBER OF HOURS LEAD BURNER HAS BEEN ON
CHANGE ON: CHANGE LEAD BOILER AT NEXT HOUR OR "AT HOUR" SETTING OF DAY
AT HOUR: TIME OF DAY IN HOURS 0-23 TO CHANGE LEAD BOILER. ALSO USED FOR COUNTING DAYS
Note, DAYS will use the "AT HOUR" of day for counting days
When a lead boiler change occurs, DAYS and HOURS are reset
If both DAYS and HOURS are OFF then no change in lead boiler will occur.
If lead boiler is locked out, then a forced change will occur.
Back to Table of Contents
®
Riverside Hydronics , LLC
WWW.RIVERSIDEHYDRONICS.COM
3220 Galvez Avenue - Fort Worth, Texas 76111 - Tel 1-800-990-5918
34-152 04/2014
Page | 28
OnTrac® Installation and Operation Manual
Temperature Alarm feature
CS-4: CFG 1: TEMPERATURE ALARM, LOW LIMIT, HIGH LIMIT
CS-8: CONFIG MENU 1: TEMPERATURE ALARM, LOW LIMIT, HIGH LIMIT
User Level: Access to CONFIG screens, LEVEL 2-3
Purpose: Report an alarm condition when system temperature is too low or too high.
Display Parameters:
Edit Parameters: LOW LIMIT, HIGH LIMIT
Details: If SYSTEM TEMPERATURE fall below LOW LIMIT, or above HIGH LIMIT, then an alarm will be displayed on
the touch screen, as well as provide the alarm signal to any BAS connected via the MODBUS TCP
Back to Table of Contents
Outdoor Shutdown screen
CS-4: CFG 1: OUTDOOR SHUTDWN
CS-8: CONFIG MENU 1: OUTDOOR SHUTDWN
User Level: Access to CONFIG screens, LEVEL 2-3
Purpose: Provide a way to disable all boilers based on outdoor temperature
Display Parameters: OUTDOOR TEMPERATURE, TEMPERATURE TO END SHUTDOWN
Edit Parameters: OUTDOOR SHUTDOWN FEATURE ON/OFF, OUTDOOR SHUTDOWN THREASHOLD, OUTDOOR
SHUTDOWN DIFFERENTIAL
Details: If OUTDOOR TEMPERATUR rises above OUTDOOR SHUTDOWN THREASHOLD, then all boilers will be shut
down and the system will be disable until the outdoor temperature falls below OUTDOOR SHUTDOWN –
OUTDOOR SHUTDOWN DIFFERENTIAL. This value is displayed as the TEMPERATURE TO END SHUTDOWN.
Back to Table of Contents
Max Boilers screen
CS-4: CFG 2: MAX BOILERS
CS-8: CONFIG MENU 2: MAX BOILERS
User Level: Access to CONFIG screens, LEVEL 2-3
Purpose: Limit the maximum number of boiler that will ever be enabled on the system.
Display Parameters: ACTIVE BOILERS, TOTAL INSTALLED BOILERS
Edit Parameters: MAX BOILER FEATURE ON/OFF, MAX BOILERS TO USE
Details: If enabled, this feature will limit adding the next boiler if the total number of active boilers is at or greater
than the MAX BOILER TO USE value. Locked out boilers and boilers out for maintenance are not counted as active
boilers. This will be useful on a system that has redundant boilers, and the building loop is not designed to have all
the boilers enabled.
Back to Table of Contents
®
Riverside Hydronics , LLC
WWW.RIVERSIDEHYDRONICS.COM
3220 Galvez Avenue - Fort Worth, Texas 76111 - Tel 1-800-990-5918
34-152 04/2014
Page | 29
OnTrac® Installation and Operation Manual
Outdoor Trigger Tier 2 screen
CS-4: CFG 2: OD TRIG T2
CS-8: CONFIG MENU 2: OD TRIG T2
User Level: Access to CONFIG screens, LEVEL 2-3
Purpose: Tier 2 boiler when the outside air falls below a set value.
Display Parameters: ADJUSTED SETPOINT, OUTDOOR TEMPERATURE, ACTUAL TEMPERATURE TIER 2 WILL BE
ENABLED
Edit Parameters: OUTDOOR TRIGGER SETTING, OUTDOOR TRIGGER DIFFERENTIAL
Details: If enabled, Tier 2 will be forced enabled is the outdoor temperature falls below OUTDOOR TRIGGER
SETTING – OUTDOOR TRIGGER DIFFERENTIAL or simply ACTUAL TEMPERATURE TIER 2 WILL BE ENABLED.
This will allow a short cut to enable Tier 2 when outside temperature fall quickly, to help protect the system from a
slow reaction to the sudden temperature drop.
Back to Table of Contents
Remote Equipment
CS-4: CFG 2: REMOTE EQUIPMENT
CS-8: CONFIG MENU 2: REMOTE EQUIPMENT
User Level: Access to CONFIG screens, LEVEL 2-3
Purpose: View status of remote equipment, and provide temporary override for testing or troubleshooting
Display Parameters: REMOTE EQUIPMENT 1, REMOTE EQUIPMENT 2, ENABLE 1, ENABLE 2, REMOTE EQUIPMENT
OVERRIDE TIMER, ENABLE OVERRIDE TIMER
Edit Parameters: REMOTE EQUIPMENT OVERRIDE, PROVING OVERRIDE
Details: This screen provides a status view of the remote equipment option, and the proving inputs.
Note, the proving on the OnTrac® should never be used for any type of safety proving.
REMOTE EQUIPMENT 1 relay is connected to P1 & P2
REMOTE EQUIPMENT 2 relay is connected to P3 & P4
ENABLE 1 is monitored at C1. Jump C1 & C2 to have a valid enable. Open is disabled.
Note PROVING 1 is used to enable and disable the system. ENABLE OVERRIDE will not override this.
ENABLE 2 is monitored at C3. Jump C2 & C3 to have a valid ENABLE. Open is a ENABLE fault and will report an
error.
REMOTE EQUIPMENT OVERRIDE: This will allow a 10 minute override for enabling the remote equipment. This
tool is useful in setup, diagnostics and trouble shooting.
ENABLE OVERRIDE: Will override the ENABLE 2 input for a short period of time (30 seconds), for testing purposes.
WARNING: As the boilers are capable of operating independently, any safety related proving, such as emergency
gas device shutoff, venting, louvers, or valves must go directly to the individual boilers.
Back to Table of Contents
®
Riverside Hydronics , LLC
WWW.RIVERSIDEHYDRONICS.COM
3220 Galvez Avenue - Fort Worth, Texas 76111 - Tel 1-800-990-5918
34-152 04/2014
Page | 30
OnTrac® Installation and Operation Manual
Manual Override screen
CS-4: CFG 2: MANUAL OVERRIDE
CS-8: CONFIG MENU 2: MANUAL OVERRIDE
User Level: LEVEL 2-3 Prompts for password
Purpose: Technician tool, allows enable or disable of any boiler in system at the touch panel
Display Parameters:
Edit Parameters: MANUAL OVERRIDE: AUTO, ON, OFF for boilers 1-28
Details: MANUAL OVERRIDE will allow you to force a boiler on. This is especially useful when the boiler is used
with the isolation valve option or remote equipment. It will enable those external devices as required.
WARNING: DO NOT LEAVE A BOILER IN MANUAL OVERRIDE. This is intended as a tool, not a mode of operation.
Back to Table of Contents
Remote Setpoint screen
DO NOT USE THIS FEATURE IF A BAS IS UPDATING THE SETPOINT BY COMMUNICATING TO THE ONTRAC® OVER
MODBUS-TCP OR A GATEWAY
CS-4: CFG 2: REMOTE SETPOINT
CS-8: CONFIG MENU 2: REMOTE SETPOINT
User Level: LEVEL 2-3 Prompts for password
Purpose: Analog 4-20mA to be used as a setpoint for the system
Display Parameters: ANALOG INPUT, REMOTE SETPOINT, ADJUSTED SETPOINT
Edit Parameters: REMOTE SETPOINT FEATURE ON/OFF, MINIMUM TEMPERATURE, MAXIMUM TEMPERATURE
Details: This is an option (REMSET), not all OnTrac® have the analog input for this feature. This option is only for
controlling the system setpoint by using a 4-20mA signal from a BAS.
Making adjustments to the following to values, changes the range the BAS is capable of adjusting the system.
MINIMUM: Setpoint temperature for a 4mA signal
MAXIMUM: Setpoint temperature for a 20mA signal
WARNING: Do not enable this option if a BAS is changing the system setpoint by using communication.
Back to Table of Contents
Non-Riverside Boilers screen
CS-4: CFG 2: NON RIVERSIDE
CS-8: CONFIG MENU 2: NON-RIVERSIDE BOILERS
User Level: LEVEL 3 Prompts for password
Purpose: Allow the use of non-Riverside Hydronics boiler in Tier 2
®
Riverside Hydronics , LLC
WWW.RIVERSIDEHYDRONICS.COM
3220 Galvez Avenue - Fort Worth, Texas 76111 - Tel 1-800-990-5918
34-152 04/2014
Page | 31
OnTrac® Installation and Operation Manual
Display Parameters:
Edit Parameters: TIER 2 BOILERS 1-8 FULL CONTROL or ON/OFF ONLY
Details: This feature provides a way of using Non-Riverside Hydronics equipment as backup Tier 2 boilers. This is
accomplished by using a TempTrac® with ON/OFF output capability only. This will be a contact that will
ENABLE/DISABLE the Non-Riverside equipment.
With this option, the reuse of existing equipment Is made possible in a upgrade to increase efficiency by adding
condensing boilers to the system loop. This could enable condensing operation during most of the heating season,
and allow the older equipment to be used in the few days of the year that additional heat is required.
When NON-RIVERSIDE HYDRONICS boilers are operated as the Tier 2 boilers, the add on TempTrac® boiler control
module can be applied as a fully functional operating control or used to enable and disable only. This screen allows
that functional selection to be chosen for each boiler. When the ENABLE/DISABLE function is used, the TempTrac®
temperature sensor can be used for displaying the boiler temperature only or left to display room temperature.
WARNING: THE SENSOR MUST BE PRESENT, DO NOT DISCONNECT SENSOR.
Back to Table of Contents
Isolation Valves
CS-4: CFG 2: ISOLATION VALVES
CS-8: CONFIG MENU 2: ISOLATION VALVES
User Level: LEVEL 2-3 Prompts for password
Purpose: Isolation valve control for primary only piping
Display Parameters:
Edit Parameters: WATER VALVE CONTROL ON/OFF
Details: This feature is for hydronic primary only loops that have boilers in parallel with isolation valves.
Isolation valves will use LOCAL 1 & 2 on the COMPENENT TERMINAL STRIP of the boiler (TempTrac® output #3,
terminals 8 & 9) for activation of the isolation valves. See wiring diagram for details.
(WATER VALVE CONTROL)
When this function is turned on the OnTrac® will control the operation of a water isolation valve for each boiler.
The control terminals are located on the boiler. OnTrac® will keep at minimum 1 boiler in operation to allow
continued building loop flow.
OnTrac® will send a signal to each active boiler. Each boiler will provide a contact to energize the isolation valve.
The OnTrac® will keep at minimum 1 boiler in operation to allow continued building loop flow.
WARNING: Only use this option when each boiler has isolation valves, and the boilers are piped in primary only.
When this option is enabled, the isolation valves are subject to the OnTrac® being operational.
SPECIAL CONSIDERATION: To ensure standalone boiler operation, it is advisable to install a bypass switch in
parallel of the isolation valve contact and have the REMEQ relay option on the boiler. The REMEQ provides a
signal on P1 & P2 that can be used to enable a valve or pump, hook P1 & P2 in parallel of the isolation valve enable
contact.
With OnTrac® failure, or shutdown, one boiler can have isolation valve always open using the Bypass switch, and
the other boilers can enable and disable their isolation valves using the REMEQ relay.
Back to Table of Contents
®
Riverside Hydronics , LLC
WWW.RIVERSIDEHYDRONICS.COM
3220 Galvez Avenue - Fort Worth, Texas 76111 - Tel 1-800-990-5918
34-152 04/2014
Page | 32
OnTrac® Installation and Operation Manual
Scheduled Setback screen
CS-4: CFG 2: SCHED SETBACK
CS-8: CONFIG MENU 2: SCHEDULED SETBACK
User Level: LEVEL 3 Prompts for password
Purpose: Change system setpoint based on time of day and/or day of week
Display Parameters: ADJUSTED SETPOINT, TIME AND DATE, DAY OF WEEK
Edit Parameters: SCHEDULE 1 &2 & WEEKEND & NIGHTLY ( SETBACK AMOUNT, START, END)
Details: The SCHEDULED SETBACK menu provides four functions which reduce (Setback) the System Setpoint by a
user defined valve (1 to 70deg F) for a user defined period of time.
The first two programs are SCHEDULE 1 & 2. These require the user to enter.
The DOW (DAY OF THE WEEK) to perform the Setback. The days are numbered 1 to 7 (Sun to Sat).
The (START HOUR) is the hour of the day which the Setback begins. The hour is based on the 24 hour clock. The
Start Hour can be from 1 to 23.
The (END HOUR) is the hour of the day which the Setback ends. The End Hour can be from 1 to 24. The (SETBACK)
is a value of (1 to 70deg F)
The third program is the (WEEKEND SETBACK). This program is similar to the first two but predefines the days of
Setback to begin Friday and end Monday. This function for example could be set to begin Setback Friday at 5:00PM
(hr. 17) and end early Monday 6:00AM (hr. 6).
The (NIGHTLY SETBACK) is similar to the others except that the days of Setback are predefined to be every night of
the week.
Note:
If the (END HOUR) is set to 25 the program is disabled.
When the programs have been entered turn on the Scheduled Setback switch.
If more than one program is enabled the first of the four to be called will stay engaged until the defined time
period has ended.
WARNING: ENABLING THIS FEATURE WILL OVERRIDE THE OUTDOOR RESET FEATURE
Back to Table of Contents
Proportional Control screen
CS-4: CFG 2: PROP CTRL
CS-8: CONFIG MENU 2:
User Level: LEVEL 2-3 Prompts for password
Purpose: Allow dynamically changing setpoint to be send to the TempTrac® based on number of boilers enabled to
account for blending of heated and unheated water
Display Parameters: ADJUSTED SYSTEM SETPOINT, TIER 1 TEMPTRAC® SETPOINT, TIER 2 TEMPTRAC® SETPOINT,
TOTAL INSTALLED BOILERS, TOTAL TIER 1 INSTALLED BOILER, TOTAL TIER 2 INSTALLED BOILERS, TOTAL TIER 1
ACTIVE BOILERS, TOTAL TIER 2 ACTIVE BOILERS, TOTAL ACTIVE BOILERS ALL
Edit Parameters: PROPORTIONAL CONTROL FEATURE ON/OFF, TIRE 1 & 2 MINIMUM OFFSET TEMPTRAC®, TIER 1
& 2 MAXIMUM SETPOINT TEMPTRAC®, DELTA OF BUILDING
®
Riverside Hydronics , LLC
WWW.RIVERSIDEHYDRONICS.COM
3220 Galvez Avenue - Fort Worth, Texas 76111 - Tel 1-800-990-5918
34-152 04/2014
Page | 33
OnTrac® Installation and Operation Manual
Details: This feature is for boilers piped primary only without isolation valves. Provides blending heated water
with unheated water compensation by adjusting the setpoint of the boilers based on percentage of enabled boilers
to the total number of boilers. Note for highly variable flow, or low flow situations, it is recommended that the
control sensing (Probe 1) be located inside the boiler.
Formula for proportional water blending by adjusting boiler setpoint:
TEMPTRAC® SETPOINT = ADJUSTED SYSTEM SETPOINT – DELTA BUILDING + MINIMUM OFFSET TEMPTRAC® +
(DELTA BUILDING * NUMBER OF BOILERS / ACTIEVE BOILERS)
If greater than TEMPTRAC® MAX SETPOINT, then USE TEMPTRAC® MAX SETPOINT
BUILDING DELTA: Anticipated building load in Deg. F
TEMPTRAC® MINIMUM OFFSET: Minimum amount above ADJUSTED SYSTEM SETPOINT offset boilers setpoint
TEMPTRAC® MAXIMUM SETPOINT: Maximum setpoint the can be sent to the boiler’s TempTrac®
Boiler setpoint will range between: ADJUSTED SYSTEM SETPOINT + TEMPTRAC® MINIMUM OFFSET to TEMPTRAC®
MAXIMUM SETPOINT
Based on the proportion of active boiler to inactive to achieve desired system setpoint
WARNING: This feature is for boilers piped in primary only without using isolation valves.
Back to Table of Contents
Control By Firing Rate screen
CS-4: CFG 2: CTRL BY F. RATE
CS-8: CONFIG MENU 2: CONTROL BY FIRING RATE
User Level: LEVEL 2-3 Prompts for password
Purpose: Hold back adding and/or removing boiler until certain firing rate conditions are met
Display Parameters: ADDING BOILER FLAG or REMOVING BOILERS FLAG
Edit Parameters: FIRING RATE ON TRIGGER FEATURE ON/OFF, FIRING RATE OFF TRIGGER FEATURE ON/OFF, ADD
BOILER FIRING RATE THREASHOLD, REMOVE BOILERS FIRING RATE THREASHOLD
Details: Firing rate mode of operation is to meet a specification that requires the next boiler to be turned on when
the current boiler reaches the indicated firing rate. Start removing boilers with lead boiler falls below the specified
firing rate. Note, the ON DELAY and OFF DELAY timers are still in effect.
The default is off (AUTO) that uses calculations based on time, temperature and number of boilers to determine
load requirements.
Back to Table of Contents
Tier 2 Independent screen
CS-4: CFG 2: T2 IND
CS-8: CONFIG MENU 2: TIER 2 INDEPENDENT
User Level: LEVEL 3 Prompts for password
Purpose: Allow OnTrac® to control 2 building loops, using Tier 2 as a second loop
Display Parameters: STATUS OF SYSTEM 2 PROBE
®
Riverside Hydronics , LLC
WWW.RIVERSIDEHYDRONICS.COM
3220 Galvez Avenue - Fort Worth, Texas 76111 - Tel 1-800-990-5918
34-152 04/2014
Page | 34
OnTrac® Installation and Operation Manual
Edit Parameters: TIER 2 INDEPENDENT FEATURE ON/OFF, SENSOR SETUP SCREEN
Details: The TIER 2 INDEPENDENT OPERATION, when activated, separates the function of Tier 1 and Tier 2. This
effectively allows the user to control two separate hydronic systems with one OnTrac®. Tier 2 is assigned its own
loop sensor, which can be connected to any boiler or MODBUS device on the system
Assign the TIER 2 SENSOR ADDRESS. The default address is 21 but it can be any address in MODBUS RTU network
(1-247). It can be the same as Tier1
ENABLE the TIER 2 SENSOR in the SENSOR SETUP screen.
Turn on the INDEPENDENT function.
Although the TIER 2 INDEPENDENT OPERATION is controlled independently of Tier 1, the SYSTEM SETPOINT must
be the same as Tier 1. Other control functions that act on the System Setpoint such as Outdoor Reset, Scheduled
Setback and Remote Setpoint also act on Tier 1 and Tier 2 the same.
Lead Lag functions such as CYCLE PERIOD, CYCLE OCCURS and SYSTEM DIFFERENTIAL setting are unique to each
Tier and can be adjusted separately.
Back to Table of Contents
Sensor Setup screen
CS-4: CFG 3: SENSOR SETUP (and several other locations)
CS-8: CONFIG MENU 1: SENSOR SETUP (and several other locations)
User Level: LEVEL 2-3 Prompts for password
Purpose: Configure location of SYSTEM SENSOR, OUTDOOR SENSOR, and SYSTEM 2 SENSOR
Display Parameters: PROBE READING IN DEGREES F
Edit Parameters: SYSTEM, OUTDOOR AND SYSTEM 2 PROBE: ENABLES, MODBUS ADDRESS, PROBE TYPE
Details: Provides a method of telling the OnTrac® the location the SYSTEM PROBE, OUTDOOR PROBE, and SYSTEM
2 PROBE, have been installed at.
rd
SYSTEM PROBE is typically located on BOILER #1 as the 3 probe of that Boiler
OUTDOOR PROBE is optional, if required, it is typically hooked up as the 3dr probe on Boiler #2
OUTDOOR PROBE is required for OUTDOOR RESET, OUTDOOR SHUTDOWN, OUTDOOR TIER 2 ENABLE.
SYSTEM 2 PROBE is optional, and usually not needed. Typically will be hooked to PROBE 3 of Tier 2 Boiler #1
Last section of this is the P3P utility. If a PROBE 3 has been enabled on a TempTrac® that does not have one, this
utility can be used to disable the P3P error. This can be caused by configuring boilers as having SYSTEM PROBE and
then later changing to another boiler or removing the probe from that boiler.
Back to Table of Contents
Swap labels for Probe 1 & 2 setting
CS-4: CONFIG> A CFG: PROBE SWP T1, & PROBE SWP T2
CS-8: CONFIG> ADVANCED CONFIG: T1 SWAP PROBES, & T2 SWAP PROBES
®
Riverside Hydronics , LLC
WWW.RIVERSIDEHYDRONICS.COM
3220 Galvez Avenue - Fort Worth, Texas 76111 - Tel 1-800-990-5918
34-152 04/2014
Page | 35
OnTrac® Installation and Operation Manual
User Level: LEVEL 3 Prompts for password
Purpose: Swap the labeling of INLET and OUTLET for a tier.
Display Parameters: Current status
Edit Parameters: TIER 1 SWAP PROBES, TIER 2 SWAP PROBES
Details: Probe 1 is typically installed in the (inlet) return to the boiler, and Probe 2 is installed close to the (outlet)
supply from the boiler. In some situations, it may be necessary to swap the locations of the probes. In order for
the labeling to remain accurate through the OnTrac® screens, the option to swap the labeling is available.
Special setting: This should only be modified if directed by the factory.
Back to Table of Contents
Burner On Zero Hours utility
CS-4: CONFIG> A CFG: BURNER ON
CS-8: CONFIG> ADVANCED CONFIG: Reset BURNER ON hours in TempTrac® of ALL BOILERS
User Level: LEVEL 3 Prompts for password
Purpose: Clear the burner hours that is stored in each TempTrac®
Details: Once the button is pressed, the OnTrac® will pole each boiler and reset the hours counter to zero.
This will be useful is trying to determine hours on a burner from this point forward.
Note the TempTrac® can only keep track of hours from 0000 – 9999. The hours will go back to zero when 10000 is
reached.
Back to Table of Contents
Factory Reset
CS-4: A CFG: FACTORY RESET
CS-8: ADVANCED CONFIG: FACTORY RESET
User Level: LEVEL 3 Prompts for password
Purpose: Reset all memory back to factory settings.
Details: This will destroy all existing job specific settings. It is strongly advised to record important settings before
performing this operation. Consult factory before performing this function.
Back to Table of Contents
Password Protection feature
By default, the password feature is disabled. This is done by setting PW3 to zero. If you are prompt for a
password, you may want to consider if this is a menu feature you need to access.
Enabling Password Protection
If the control is located in a unsecure area, or tight control on adjustments is desired, it may be required to enable
passwords to standard feature, or all features.
®
Riverside Hydronics , LLC
WWW.RIVERSIDEHYDRONICS.COM
3220 Galvez Avenue - Fort Worth, Texas 76111 - Tel 1-800-990-5918
34-152 04/2014
Page | 36
OnTrac® Installation and Operation Manual
Password Level 3 PW3
CS-4: CONFIG> A CFG: ALL PASSWORDS
CS-8: CONFIG > ADVANCED CONFIG: ALL PASSWORDS
Highest access. Enter a zero in this will effectively eliminate the need for passwords to anything other than factory
options. As a suggested password to a good default password is 65536. If this password is set to zero, then all
lower passwords will be defeated except for lock screen. Even with this password set to zero, some advanced
features will still prompt for a password, but will accept zero (hit the enter key) The is a warning that this is an
advanced feature, and should not be adjusted just because you have access.
PW3 = ___ ___ ___ ___ ___ ___ ___ Factory = 0, otherwise default = 65536
Password Level 2 PW2
Service and setup level. Able to access all typical functions, including setup functions such as adding or removing
boilers.
PW2 = ___ ___ ___ ___ ___ ___ ___ Default = 2048
Password Level 1 PW1
This level will allow viewing and adjusting of the setpoint
PW1 = ___ ___ ___ ___ ___ ___ ___ Default = 1024
Password Level 0 PW0
This password is slightly different than the others. The purpose is to offer a locked screen such that passersby
cannot arbitrarily edit value any values without a password.
If PW0=0 Then the screen lock feature is disabled, and the screen lock button simply goes to the SCREEN LOCK
display, and exit by hitting the MENU button.
If PW0 is set to a value other than zero, then from the main screen, the LOCK SCREEN button will prompt for a
password. This password can be any one of PW0, PW1, PW2. In order to exit the LOCK SCREEN, you must enter a
password equal to one of the following: PW0, PW1, PW2
Note that PW3 cannot be used to enter or exit LOCK SCREEN. This allows PW3 to be set to zero, disabling
passwords in all other screens, but still allowing the LOCK SCREEN function to work.
Back to Table of Contents
Schematic
Note: Dotted lines indicate options that may or may not be installed on the OnTrac® you have
®
Riverside Hydronics , LLC
WWW.RIVERSIDEHYDRONICS.COM
3220 Galvez Avenue - Fort Worth, Texas 76111 - Tel 1-800-990-5918
34-152 04/2014
Page | 37
OnTrac® Installation and Operation Manual
NOTES:
®
Riverside Hydronics , LLC
WWW.RIVERSIDEHYDRONICS.COM
3220 Galvez Avenue - Fort Worth, Texas 76111 - Tel 1-800-990-5918
34-152 04/2014
Page | 39
Download