LP550 Installation Instructions FLUORESCENT EMERGENCY BALLAST U.S. Patent No. 6,339,296 ! IMPORTANT SAFEGUARDS ! WHEN USING ELECTRICAL EQUIPMENT, BASIC SAFETY PRECAUTIONS SHOULD ALWAYS BE FOLLOWED, INCLUDING THE FOLLOWING: READ AND FOLLOW ALL SAFETY INSTRUCTIONS 1. To prevent high voltage from being present on red & yellow output leads prior to installation, inverter connector must be open. Do not join inverter connector until installation is complete and AC power is supplied to the emergency ballast. 2. This product is for use with most 14 W through 54 W (2'- 4') T5 bipin, 22 W T5 circular, 36 W through 55 W (4-pin) long compact, or 32 W (4-pin) compact,32 W (4'), 40 W (5') and 44 W HO (4') T8 bipin fluorescent lamps. 3. Make sure all connections are in accordance with the National Electrical Code and any local regulations. 4. To reduce the risk of electric shock, disconnect both normal and emergency power supplies and inverter connector of the emergency ballast before servicing. 5. This emergency ballast is for factory or field installation in the ballast channel or on top of fixture. 6. This product is suitable for use in damp locations where the ambient temperature for fixture is 0ºC minimum, +50ºC maximum. Product is also suitable for installation in sealed and gasketed fixtures. Product is not suitable for heated air outlets and wet or hazardous locations. 7. An unswitched AC power source is required (120 or 277 VAC, 60 Hz). 8. Do not install near gas or electric heaters. 9. Do not attempt to service the battery. A sealed, no-maintenance battery is used that is not field replaceable. Contact the manufacturer for information on service. 10. The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition. 11. Do not use this product for other than intended use. 12. Servicing should be performed by qualified service personnel. SAVE THESE INSTRUCTIONS THIS PRODUCT CONTAINS A RECHARGEABLE NICKEL-CADMIUM BATTERY. THE BATTERY MUST BE RECYCLED OR DISPOSED OF PROPERLY. 09/21/09 © Philips Emergency Lighting A Division of Philips Electronics North America Corporation 236 Mt. Pleasant Rd. • Collierville, TN USA 38017-2752 • Tech Support 888-263-4638 • Fax 901-854-1630 • www.philips.com/bodine 70100554 INSTALLATION WARNING: TO PREVENT HIGH VOLTAGE FROM BEING PRESENT ON RED & YELLOW OUT- PUT LEADS PRIOR TO INSTALLATION, inverter CONNECTOR MUST BE OPEN. DO NOT JOIN inverter CONNECTOR UNTIL INSTALLATION IS COMPLETE AND AC POWER IS SUPPLIED TO THE EMERGENCY BALLAST. NOTE: STEP #1 Make sure that the necessary branch circuit wiring is available. An unswitched source of power is required. The emergency ballast must be fed from the same branch circuit as the AC ballast. INSTALLING THE EMERGENCY BALLAST ILLUSTRATION 1 >Disconnect AC power from the fixture. Remove the ballast channel cover and install the emergency ballast in the ballast channel (see Illustration 1). >Remote mounting distance must be less than half the maximum remote mounting distance for the AC ballast. Consult AC ballast manufacturer before remote installation. STEP #2 INSTALLING THE TEST SWITCH > Refer to Illustration 2 and install the test switch through the ballast channel cover of a troffer or through the side of a strip fixture. ILLUSTRATION 2 Fixture > Drill a 1/2" hole and install the switch as shown. > Refer to the wiring diagrams on the following pages and wire the test switch so that it removes AC power from both the emergency ballast and the AC ballast at the same time. STEP #3 Hex Nut Test Button Push to Test INSTALLING THE CHARGING INDICATOR LIGHT Test Switch Leads Hex Nut > Refer to Illustration 3A or 3B and install the charging indicator light so that it will be visible after the fixture is installed. ILLUSTRATION 3A ILLUSTRATION 3B Fixture Fixture Charging Indicator Light Charging Indicator Light Violet (+) Violet (+) Brown (–) Brown (–) 5/8" Black Bushing 1/2" White Bushing 1/2" White Bushing 5/8" Black Bushing 1/2" Punch STEP 1 STEP 2 NOTE: After installing the charging indicator light and test switch, mark each with the appropriate label. If a detached charging indicator light is used, connect by matching wire colors and install as shown above. 2 INSTALLATION STEP #4 WIRING THE EMERGENCY BALLAST > Select the appropriate wiring diagram and connect the emergency ballast to the AC ballast and lamp(s). Make sure all connections are in accordance with the National Electrical Code and any local regulations. > After installation is complete, supply AC power to the emergency ballast and join the inverter connector. > At this point, power should be connected to both the AC ballast and the emergency ballast, and the Charging Indicator Light should illuminate indicating the battery is charging. > A short-term discharge test may be conducted after the emergency ballast has been charging for one hour. Charge for 24 hours before conducting a long-term discharge test. Refer to OPERATION. > In a readily visible location, attach the label "CAUTION - This Unit Has More Than One Power Connection Point. To Reduce The Risk Of Electric Shock, Disconnect Both The Branch Circuit-Breakers Or Fuses And Emergency Power Supplies Before Servicing." OPERATION When AC power is applied, the charging indicator light is illuminated, indicating that the battery is being charged. When power fails, the emergency ballast automatically switches to emergency power (internal battery), operating one lamp at reduced illumination. When AC power is restored, the emergency ballast returns to the charging mode and delays AC ballast operation for approximately three seconds to prevent false-tripping of AC ballast (end-of-lamp-life) shutdown circuits. This emergency ballast will operate one 14 W through 55 W lamp for a minimum of 90 minutes. MAINTENANCE Although no routine maintenance is required to keep the emergency ballast functional, it should be checked periodically to ensure that it is working. The following schedule is recommended: 1. 2. 3. Visually inspect the charging indicator light monthly. It should be illuminated. Test the emergency operation of the fixture at 30-day intervals for a minimum of 30 seconds. One lamp should operate at reduced illumination. Conduct a 90-minute discharge test once a year. One lamp should operate at reduced illumination for at least 90 minutes. ! REFER ANY SERVICING INDICATED BY THESE CHECKS TO QUALIFIED PERSONNEL ! EMERGENCY BALLAST AND AC BALLAST MUST BE FED FROM THE SAME BRANCH CIRCUIT TYPICAL SCHEMATICS ONLY. MAY BE USED WITH OTHER BALLASTS. CONSULT THE FACTORY FOR OTHER WIRING DIAGRAMS. WIRING DIAGRAMS for 1-LAMP emergency operation FIG 99BH ONE (1) LAMP RAPID START BALLAST FIG 119BH ONE (1) LAMP INSTANT START BALLAST WALL SWITCH HOT WALL SWITCH WHT/RED B L K TEST SWITCH B L K INVERTER CONNECTOR CHARGING INDICATOR LIGHT (CAP UNUSED LEAD) RED WHITE VIOLET BROWN BLACK 120V OR ORANGE 277V WHITE COMMON HOT RED E MB EA RL GL EA NS CT Y YELLOW LAMP YEL/BLK WHT/RED B L K TEST SWITCH B L K BLU/WHT BLUE RED BLUE BLUE RED TEST SWITCH B L K CHARGING INDICATOR LIGHT (CAP UNUSED LEAD) COMMON BROWN BLACK 120V OR ORANGE 277V YELLOW LAMP YEL/BLK BLU/WHT BLUE BLUE RED 1 LAMP INSTANT START BALLAST WHT/BLK BLK WHT WHT FIG 104BH TWO (2) LAMP INSTANT START BALLAST WALL SWITCH WHT/RED INVERTER CONNECTOR VIOLET RED E MB EA RL GL EA NS CT Y BLK WALL SWITCH B L K RED WHITE WHITE COMMON FIG 124BH TWO (2) LAMP RAPID START BALLAST HOT CHARGING INDICATOR LIGHT (CAP UNUSED LEAD) 1 LAMP RAPID START BALLAST WHT/BLK INVERTER CONNECTOR RED WHITE VIOLET BROWN BLACK 120V OR ORANGE 277V WHITE HOT RED E MB EA RL GL EA NS CT Y YELLOW LAMP 1 (EMERGENCY) YEL/BLK WHT/RED B L K TEST SWITCH BLU/WHT BLUE BLUE BLUE RED RED 2 LAMP RAPID START BALLAST WHT/BLK B L K LAMP 2 INVERTER CONNECTOR CHARGING INDICATOR LIGHT (CAP UNUSED LEAD) COMMON YELLOW YELLOW RED WHITE VIOLET BROWN BLACK 120V OR ORANGE 277V WHITE RED E MB EA RL GL EA NS CT Y YELLOW LAMP 1 (EMERGENCY) YEL/BLK BLU/WHT BLUE BLUE WHT/BLK BLK BLK WHT WHT 3 BLUE 2 LAMP INSTART START BALLAST RED LAMP 2 EMERGENCY BALLAST AND AC BALLAST MUST BE FED FROM THE SAME BRANCH CIRCUIT TYPICAL SCHEMATICS ONLY. MAY BE USED WITH OTHER BALLASTS. CONSULT THE FACTORY FOR OTHER WIRING DIAGRAMS. WIRING DIAGRAMS for 1-LAMP emergency operation FIG 107BH TWO (2) LAMP RAPID START BALLAST FOR 4-PIN LONG COMPACT FIG 107aBHTWO (2) LAMP INSTANT START BALLAST FOR 4-PIN LONG COMPACT WALL SWITCH WALL SWITCH HOT WHT/RED B L K TEST SWITCH B L K RED INVERTER CONNECTOR WHITE VIOLET CHARGING INDICATOR LIGHT BROWN (CAP UNUSED LEAD) BLACK 120V OR ORANGE 277V WHITE COMMON HOT RED E MB EA RL GL EA NS CT Y YELLOW WHT/RED B L K LAMP 1 YEL/BLK (EMERGENCY) TEST SWITCH B L K BLU/WHT BLUE BLUE BLUE WHT/BLK RED RED INVERTER CONNECTOR WHITE VIOLET CHARGING INDICATOR LIGHT BROWN (CAP UNUSED LEAD) BLACK 120V OR ORANGE 277V WHITE COMMON RED INVERTER CONNECTOR WHITE VIOLET CHARGING INDICATOR LIGHT BROWN (CAP UNUSED LEAD) BLACK 120V OR ORANGE 277V WHITE COMMON E MB EA RL GL EA NS CT Y LAMP 1 (EMERGENCY) YEL/BLK TEST SWITCH BLU/WHT BLU/WHT BLU/WHT BLUE YELLOW BLUE BLUE YELLOW 3 LAMP RAPID START BALLAST B L K RED INVERTER CONNECTOR WHITE VIOLET CHARGING INDICATOR LIGHT LAMP 2 BROWN (CAP UNUSED LEAD) BLACK 120V OR ORANGE 277V WHITE COMMON LAMP 3 BLUE RED E MB EA RL GL EA NS CT Y YELLOW LAMP 1 (EMERGENCY) YEL/BLK BLU/WHT BLUE BLUE BLK RED BLK WHT RED WHT TEST SWITCH YELLOW RED BLUE RED BLU/WHT 4 LAMP RAPID START BALLAST BLU/WHT WHT/RED B L K YELLOW BLU/WHT B L K RED INVERTER CONNECTOR WHITE VIOLET CHARGING INDICATOR LIGHT LAMP 2 BROWN (CAP UNUSED LEAD) LAMP 3 BLACK 120V OR ORANGE 277V WHITE COMMON BROWN RED E MB EA RL GL EA NS CT Y LAMP 1 (EMERGENCY) YELLOW YEL/BLK BLU/WHT BLUE YELLOW BLUE BLUE WHT BLUE BLUE 4 LAMP INSTANT START BALLAST WHT/BLK BROWN BLK LAMP 3 RED WALL SWITCH LAMP 1 (EMERGENCY) YEL/BLK BLUE LAMP 2 FIG 121BH FOUR (4) LAMP INSTANT START BALLAST HOT YELLOW BLUE 3 LAMP INSTANT START BALLAST WHT/BLK RED E MB EA RL GL EA NS CT Y WHT/RED B L K RED LAMP 4 WHT LAMP 2 LAMP 3 YELLOW BLK FIG 99aBH TWO (2) LAMP RAPID START BALLAST - SERIES YELLOW RED LAMP 4 FIG 99bBH TWO (2) LAMP PROGRAM RAPID START OSRAM BALLAST WALL SWITCH WALL SWITCH HOT WHT/RED B L K 2 LAMP INSTANT START BALLAST FIG 106BH THREE (3) LAMP INSTANT START BALLAST HOT YELLOW WHT/BLK TEST SWITCH LAMP 2 BLUE BLK RED WHT/RED B L K RED BLUE WHT WALL SWITCH HOT B L K BLU/WHT WHT/BLK FIG 120BH FOUR (4) LAMP RAPID START BALLAST TEST SWITCH WHITE (EMERGENCY) YEL/BLK WHT WHT/BLK B L K OR ORANGE 277V LAMP 1 YELLOW WALL SWITCH WHT/RED B L K BLACK 120V RED E MB EA RL GL EA NS CT Y BLK WALL SWITCH HOT TEST SWITCH BROWN COMMON RED FIG 105BH THREE (3) LAMP RAPID START BALLAST B L K VIOLET (CAP UNUSED LEAD) LAMP 2 YELLOW WHITE CHARGING INDICATOR LIGHT YELLOW 2 LAMP RAPID START BALLAST RED INVERTER CONNECTOR RED INVERTER CONNECTOR WHITE VIOLET CHARGING INDICATOR LIGHT BROWN (CAP UNUSED LEAD) BLACK 120V OR ORANGE 277V WHITE COMMON HOT RED E MB EA RL GL EA NS CT Y YELLOW LAMP 1 (EMERGENCY) YEL/BLK WHT/RED B L K TEST SWITCH B L K BLU/WHT BLUE BLUE BLUE RED WHT/BLK WHITE VIOLET CHARGING INDICATOR LIGHT LAMP 2 RED 2 LAMP RAPID START BALLAST RED INVERTER CONNECTOR BROWN (CAP UNUSED LEAD) OR ORANGE 277V WHITE COMMON YELLOW BLACK 120V YELLOW RED E MB EA RL GL EA NS CT Y YELLOW LAMP 1 (EMERGENCY) YEL/BLK BLU/WHT RED BLUE RED BLUE BLUE 2 LAMP RAPID START BALLAST WHT/BLK BLK BLK WHT WHT LAMP 2 YELLOW YELLOW FIG 124BH TWO (2) LAMP RAPID START step dimming BALLAST COMMON WHT/RED RED INVERTER CONNECTOR WHITE VIOLET CHARGING INDICATOR LIGHT BROWN TEST SWITCH HOT BLK WHITE BLK (CAP UNUSED LEAD) BLACK 120V OR ORANGE 277V RED E MB EA RL GL EA NS CT Y YELLOW BLU/WHT BLUE BLUE BLUE WHT/BLK WHT S1 The white/black lead must connect to the white lead of the step-dimming ballast associated with the emergency ballast only. Connections to other ballasts or fixtures could result in abnormal operation and cause product damage. LAMP 1 (EMERGENCY) YEL/BLK RED 2 LAMP RAPID START STEP DIMMING BALLAST LAMP 2 RED YELLOW YELLOW BLK S2 BLK WIRING DIAGRAMS for Emergency-Only fixtures FIG 109aBHONE (1) 36 W - 55 W LAMP WITHOUT AC BALLAST FIG 109BH ONE (1) 14 W - 55 W LAMP WITHOUT AC BALLAST CAP HOT B L K TEST SWITCH B L K WHITE VIOLET CHARGING INDICATOR LIGHT BROWN (CAP UNUSED LEAD) BLACK 120V OR ORANGE 277V WHITE COMMON CAP RED WHT/RED RED INVERTER CONNECTOR E MB EA RL GL EA NS CT Y HOT YELLOW LAMP YEL/BLK CAP B L K TEST SWITCH BLU/WHT CAP BLUE CAP B L K INVERTER CONNECTOR CHARGING INDICATOR LIGHT (CAP UNUSED LEAD) CAP 4 RED WHITE VIOLET BROWN BLACK 120V OR ORANGE 277V WHITE COMMON WHT/BLK WHT/RED WHT/BLK RED E MB EA RL GL EA NS CT Y LAMP YELLOW YEL/BLK BLU/WHT CAP BLUE CAP