SECTION 10: page Section 10: by Honeywell Emergency Lighting Design and Product Guide 10 SECTION 10: page 1 0 : e m e r genc y lig h ting design by Honeywell 10 Chapter title goes here SECTION 10: page Section 10.1: by Honeywell Emergency Lighting Design Guide 10 SECTION 10: page 1 0 : e m e r genc y lig h ting design by Honeywell 10 Chapter title goes here SECTION 10: page 1 0 . 1 : e m e r genc y lig h ting design G u ide by Honeywell Introduction When the electricity supply fails and the lights go out, it is essential that emergency lighting is automatically activated to provide adequate illumination for normal activities to continue and for the safe evacuation of the building. Instant illumination is required when the supply fails and for this reason only, fluorescent or tungsten light sources are used. Emergency lighting is demanded mainly because of legislation. This legislation itself is a direct result of public and political pressure to safeguard life and to ensure uniform standards in places where the public gather. The existing U.K. legislation for emergency lighting, BS 5266:1999, has been partially superseded by BS EN 50172:2004, and is currently under review to remove any conflicts with this European Directive. Consideration given now to the standards which the Directives evoke, will provide substantial savings in the future. BS 5266: 1999 gives a ‘standards tree’ for the different types of emergency lighting covered, and a definition for each form of lighting. Standby Lighting This is the part of emergency lighting which may be provided to enable normal activities to continue in the event of failure of the normal mains supply. For long back-up periods (in excess of three hours), it is normal for central battery systems, uninterruptible power supplies or standby generators to be used. Escape route lighting Emergency Escape Lighting This is the part of emergency lighting which is provided to ensure all means of escape can be safely and effectively used at all times. Emergency escape lighting may be subdivided into three areas: 1 Escape Route Lighting The emergency lighting on a route forming part of the means of escape from a point in a building to final exit. 2 Open Area (Anti-panic) Lighting The part of emergency lighting provided to avoid panic and provide illumination allowing people to reach a place where an escape route can be identified. 3 High Risk Area Lighting A new category provided to ensure the safety of people involved in a potentially dangerous process or situation and to enable proper shut down procedures for the safety of the operator. The full responsibilities of the Owner/Occupier are detailed within the new Regulatory Reform Fire Safety Order* (RRO) which will replace the majority of existing laws within the UK during 2005/6. To ensure the system is well designed and as reliable as possible, Gent stresses the importance of planning through all the phases of the project, from considering legal requirements to final commissioning and maintenance. Consultation between all interested parties at an early stage of design cannot be over stressed to avoid expensive modifications to a completed system. The first stage of system design is to gather the information needed on the project, normally by consultation with the Regulatory Authority and the user. This should cover legislative and likely operational requirements and customer preferences. EMERGENCY LIGHTING EMERGENCY ESCAPE LIGHTING STANDBY LIGHTING ESCAPE ROUTE LIGHTING (DEFINED) OPEN AREA (ANTI-PANIC) LIGHTING (UNDEFINED) Emergency lighting standards tree HIGH RISK TASK LIGHTING 10 SECTION 10: page 1 0 . 1 : e m e r genc y lig h ting design G u ide by Honeywell Design Guide Emergency Lighting Initial Considerations The Check List l The duration of the battery system is decided by: l Three hour duration is required in places of entertainment and for buildings where people may be sleeping. l Three hour duration is required if evacuation is not immediate, or early re-occupation is likely to occur. l One hour duration may be acceptable, in some premises, if evacuation is immediate and re-occupation is delayed until a full recharge of the system has occurred. In practice it is normally preferable to choose a three hour system. l Escape routes should be established and potential hazards investigated. l Building plans need to be assembled showing the locations of fire alarm call points, the position of fire fighting equipment and fire and safety signs. l Open areas (anti-panic) larger than 60m2 floor area should be identified. l High risk task areas should be identified and normal lighting levels established. l External illumination outside exit doors should be determined. l Other areas which need illumination although not part of the escape route, should be located, e.g. lifts, moving stairways and walkways, plant rooms and toilet accommodation over 8m2 gross area. l All emergency luminaires should be wired from the unswitched side of each local lighting circuit. l Areas of low fire risk (if a central system is being used), and the locations of central battery units and cable runs should be established. l Standby lighting requirements should be established if activities need to continue during a failure of the normal lighting supply. l The customer’s preference and operating considerations should be ascertained. Design of New Installations When referring to the provision of emergency escape lighting, EN 50172: 2004 requires that “The installation shall ensure that emergency escape lighting fulfils the following functions: a To illuminate escape route signs; b To provide illumination onto and along such routes as to allow safe movement towards and through the exits provided to a place of safety; c To ensure that fire alarm call points and fire equipment provided along escape routes can be readily located and used; d To permit operations concerned with safety measures” 10 SECTION 10: page 1 0 . 1 : e m e r genc y lig h ting design G u ide by Honeywell Design Guide Design Stage 1 Locate luminaires at mandatory points of emphasis Decide upon the emergency escape routes together with the points of exit and locate luminaires at points of emphasis (these are mandatory locations) along these routes. Initial design is conducted by the siting of luminaires to cover specific hazards and to highlight safety equipment and signs. This should be performed regardless of whether the area is an emergency escape route or defined as an open area. Only when this is accomplished should the type of luminaire or its light output be considered. At each corridor intersection Outside each final exit At each exit door At fire fighting equipment On each staircase At fire alarm call points The points of emphasis where it is mandatory to site escape lighting luminaires are as follows: l At each intersection of corridors. l At each exit door. l At each change of direction (other than on a staircase). l On each staircase so that each flight of stairs receives direct light. l At any other change of floor level. l Outside each final exit and close to it. l At each fire alarm call point. l At fire fighting equipment. l At each first aid post. l To illuminate exit and safety signs required by the enforcing authority. BS 5266: 1999 requires a minimum of 1.0 lux at these points of emphasis except fire alarm call points and fire fighting equipment where the minimum required is 5.0 lux. 10 At each change of floor level To illuminate exit and safety signs SECTION 10: page 9 : e m e r genc y lig h ting D E S I G N G u ide by Honeywell Design Guide Design Stage 2 Consider other locations Consider providing additional escape lighting at these locations: l l Lift cars. Although only in very exceptional circumstances will they be part of the escape route, they do present the problem that people may be trapped in them in the event of a supply failure. Lift manufacturers are legally obliged to fit emergency lighting. Toilets with facilities exceeding 8m2 floor area and all toilets for the disabled. Large tiled areas such as changing rooms also fall under this category. This should be considered an open (antipanic) area. l Escalators, to enable users to get off them safely. This should be considered an open (anti-panic) area. l Motor generator control or plant rooms require battery supplied emergency lighting to assist any maintenance or operating personnel in the event of failure. It is also necessary to install selfcontained emergency lighting in areas adjacent to central battery systems in case of failure. l Covered car parks, the normal pedestrian routes should be provided with non-maintained luminaires of at least one hour duration. l First aid rooms, the room together with the area immediately outside. l Lighting compartments, where provision has been made for a single luminaire to cater for a room or corridor, this must be increased to a minimum of two, to prevent the area from being plunged into darkness, if the luminaire fails. Toilets exceeding 8m2 floor area Escalators Plant rooms 10 Lifts Covered car parks SECTION 10: page 1 0 . 1 : e m e r genc y lig h ting design G u ide Design Guide Design Stage 3 by Honeywell Check minimum illuminance levels When the points of emphasis have been covered, it is essential to provide any additional luminaires that might be necessary to ensure that minimum illuminance levels are met. BS 5266: Part 1: 1999 calls for a minimum of 0.2 lux at floor level on the centre line of permanently unobstructed escape routes. Points of emphasis should be illuminated to a minimum of 1.0 lux. There is no guarantee that obstructions will never occur, therefore it is advisable that 1.0 lux minimum is used throughout. 1 Decide upon the defined and open area (anti-panic) routes. 2 Check that the preferred luminaires can be used on defined escape routes. 3 Place exit signs at each final exit. 4 Position luminaires outside each final exit and any others required to aid dispersal. Note: These will probably be of the weatherproof variety. 5 Place extra directional exit signs where the final exit sign is obscured. 6 Illuminate all other ‘points of emphasis’ as defined in BS 5266: Part 7: 1999 These are: l Change of direction and level. l Fire fighting equipment. l Hazardous processes. l First-aid and plant rooms. l Tiled areas. l Escalators. l Signs. 7 Place luminaires along the defined escape route using the spacing data. Note: Remember to add extra luminaires so that each lighting compartment is covered by at least two luminaires. 8 Position luminaires into the open (anti-panic) areas using the current standard 0.5 lux min. Note: EN 50172 / BS 5266-8 requires a minimum of 2 luminaires in open areas. It should be noted that transverse to transverse installation enhances the performance of the luminaires. Escape routes require minimum levels of illuminance 10 SECTION 10: page 10 1 0 . 1 : e m e r genc y lig h ting design G u ide by Honeywell Design Guide Design Stage 3 (continued) Spacing Tables BS 5266: Part 1: 1999 recommends using a larger number of low power luminaires rather than a few high power units, so that no part of the escape route is lit by just one luminaire. Thus, if a luminaire fails, the route will not be plunged into darkness and the uniformity of light distribution will be maintained. Gent has calculated the maximum spacings for all Gent luminaires to ensure a given design illuminance for routes up to 2m wide. How to Use Spacing Tables Maximum permitted spacing (in metres) to achieve 0.2 lux LUM8/NM Height (m) Tr-Tr Ax-Ax Tr-Wall Ax-Wall 2.5 11.8 6.9 4.5 2.7 3 12.3 7.3 4.5 2.8 4 12.6 7.6 4.4 2.6 6 11.9 7.0 1.1 0.8 8 5.2 3.2 1 Choose the appropriate lux level required. 2 Establish the plane/axis of the selected luminaire along the escape route (i.e. transverse or axial). 3 Establish the mounting height of the luminaire above the floor. 4 On the table for the relevant luminaire, select the appropriate lux level table. From the established mounting height, choose the maximum permissible spacing between luminaires (or from the luminaire to a wall) for the plane/axis previously chosen. See Photometric data at end of product section. Using spacing tables A-W A-A T-W Axial Height Siting emergency luminaires along an escape route 10 T-T Transverse SECTION 10: page 11 1 0 . 1 : e m e r genc y lig h ting design G u ide by Honeywell Design Guide Design Stage 3 (continued) Special considerations for escape routes and open (Anti-Panic) areas Low Voltage Downlighters Tungsten-Halogen downlighters are often used in ‘decorative’ and open (anti-panic) areas. For either application ‘cone diagrams’ are used to calculate the spacing. A particular lamp is described by the ‘watts’ and an included beam angle. Position the beams so that they just touch, this will maintain uniformity. Note: The light levels achieved are far higher than those normally required. 1m 6.30 lux 2m 158 lux 3m 70 lux 4m 39 lux 5m 16 lux Height Typical cone diagram for a 50W, 60o Dichroic lamp Low voltage down lighters Twinspots A typical application for a twinspot is a warehouse. It is only necessary to cover the gangways in these circumstances. See Photometric data at end of product section. Exit 10 Exit Warehouse application using twinspots SECTION 10: page 12 1 0 . 1 : e m e r genc y lig h ting design G u ide by Honeywell Design Guide Design Stage 3 (continued) Designing for 0.5 lux minimum BS 5266: 1999 allows for a perimeter of 0.5m to be neglected. Spacing tables provide simple and accurate data that can be easily used. The spacing tables for 0.5 lux are derated to cover diagonal points. Designing for 0.5 lux minimum Wall Wall Minimum points for obtaining 0.5 lux 0.5m The table below shows the typical spacing for an 8W fitting, assuming a regular layout to give a minimum of 0.5 lux anywhere on the floor (excluding perimeter of 0.5m). Maximum permitted spacing (in metres) to achieve 0.2 lux LUMHI8/NM 10 Maximum permitted spacing (in metres) to achieve 0.5 lux Height (m) Tr-Tr Ax-Ax Tr-Wall Ax-Wall Tr-Tr Ax-Ax Tr-Wall Ax-Wall Maximum permitted spacing (in metres) to achieve 1 lux Tr-Tr Ax-Ax Tr-Wall Ax-Wall 2 12.2 7.5 5.8 3.1 11.3 5.9 4.6 2.2 9.3 4.4 3.7 1.5 2.5 14.8 8.0 6.2 3.3 12.1 6.2 5.2 2.2 10.4 4.5 3.3 1.4 3 17.2 9.0 7.1 3.6 13.6 6.4 5.3 2.2 10.6 4.4 2.7 1.1 4 19.3 9.9 8.2 3.5 15.1 6.2 4.0 1.7 8.1 3.5 6 23.7 10.1 6.9 2.9 10.7 4.5 8 20.9 8.9 10 11.1 5.7 SECTION 10: page 13 1 0 . 1 : e m e r genc y lig h ting design G u ide Design Guide Design Stage 4 by Honeywell High risk task area BS 5266: Part 7: 1999 requires that higher levels of emergency lighting shall be provided in areas of particular risk, although no values are defined. The British standard states that the average horizontal illuminance on the reference plane shall be as high as the task demands in areas of high risk. It shall not be less than 10% of the normal lighting level, or 15 lux, whichever is the greater. In practice this minimum is unlikely ever to be a problem as it would only be valid if the risk area had a normal illumination level less than 150 lux. High risk task area High risk task area Design Procedures For a conversion unit, a direct ratio is obtained by using its ballast lumen factor (BLF). To achieve 10% of normal lighting use a minimum BLF of 0.1. To provide 10% of normal lighting, it is advisable to use either high output single point units (Twinspots) or the conversion of the installed mains luminaires to emergency operation. Consideration can also be given to the use of a central battery system. 10 SECTION 10: page 14 1 0 . 1 : e m e r genc y lig h ting design G u ide by Honeywell Design Guide This summary section illustrates the previous stages in a pictorial format. Design Stage 1 Locate luminaires at mandatory points of emphasis WC Office Stores WC l Final exits with exit signs l Where the final exit is obscured, locate exit direction signs along the escape route such that a person following them is moved towards the exit l Outside each final exit, and the immediate vicinity, to allow for dispersal l Intersections of corridors l Change of direction l Change of floor levels (steps or ramps) l Staircases, such that each flight receives direct illumination l Fire alarm call points l Fire fighting equipment l Safety signs required by the enforcing authority WC WC Reception Boiler Room Assembly Area Office Canteen Warehouse Self-Contained Luminaires Exit Signs Manual Call Points B Design Stage 2 S Consider other locations H Office Stores Reception Boiler Room Assembly Area Office Canteen 10 Warehouse l Toilets and tiled areas e.g. changing rooms greater than 8m2 l Lift cars l Escalators l Motor generators, control or plant rooms l Covered car parks l First-aid rooms SECTION 10: page 15 1 0 . 1 : e m e r genc y lig h ting design G u ide by Honeywell Design Guide This summary section illustrates the previous stages in a pictorial format. Design Stage 3 Check minimum illuminance levels l Place luminaires along the defined escape route using the spacing data l Ensure a minimum of 2 luminaires per lighting compartment WC Office Stores WC WC WC Reception Boiler Room Office Assembly Area Canteen Warehouse n Fire panel Open areas (anti-panic) l l l Areas >60m2 or open areas with an escape route passing through them WC Light level required: - 0.5 lux minimum anywhere (British Standard) Stores Ensure a minimum of 2 luminaires per lighting compartment Boiler Room WC WC WC Office Reception Assembly Area Office Canteen Warehouse 10 SECTION 10: page 16 1 0 . 1 : e m e r genc y lig h ting design G u ide by Honeywell Design Stage 5 Design Guide Locate exit signs and directions BS 5266 states that: “Signs are required at all exits, emergency exits and escape routes, such that the position of any exit or route to it is easily recognised and followed in an emergency. Where direct sight of an exit or emergency exit is not possible and doubt may exist as to its position, a directional sign (or series of signs) should be provided, placed such that a person moving towards it will be progressed towards an exit or emergency exit”. The Format of Signs Exits must be identified by the sign. Other information such as ‘Fire Exit for Emergency Use Only’ is now considered as a building management sign that can be displayed if needed but is not part of the safety system. Maximum Viewing Distance Viewing distances are given in BS 5266: part 7: 1999 as 200 x H for a self illuminated sign, and 100 x H for externally illuminated signs where H is the height of the pictogram. Signs Directive Implemented as a legal requirement in the U.K. by Statutory Instrument 1996 No. 341 on 1st April 1996. HSE Signs Directive format D H D = 200 x H (Self illuminated sign) D = 100 x H (Externally illuminated sign) Viewing distances for exit signs Design Stage 6 Duration of emergency lighting system BS 5266 Part 1: 1999 states: “It is considered that a design period of operation of emergency lighting system of 1 hour should be the absolute minimum of even the smallest premises considered in this code”. For most applications a duration of between 1 hour and 3 hours should meet all normal requirements. Type of System: Mode of Operation The type and category of system used depends on the size and function of the premises. The system should provide for the safe movement of people along the escape routes and through the exits. The emergency lighting design should take account of individual lamp luminaire failure, mounting height, spacing, additional escape lighting and emergency signs. Self-contained luminaires contain their own battery charger, control gear and lamp, so that if the mains supply fails, the emergency lighting will operate for the design duration. For central battery systems, the luminaire (known as a ‘slave’ luminaire) derives emergency lighting supply from a central power source, which may be a standby generator or a central battery system. Either type of luminaire can be ‘maintained’ or ‘non-maintained’. With maintained operation all emergency lighting lamps are in operation at all times. For non-maintained emergency lighting, all the emergency lighting lamps are in operation only when the supply to the normal lighting fails, the lamps are then illuminated from the battery and control gear. When the mains is restored the lamps are switched off and the battery is recharged ready for the next failure. 10 BS 5266 recommends a maintained mode of operation for premises where the normal lighting can be dimmed or reduced below the levels required for the identification and illuminance of escape routes while the premises are occupied e.g. theatres and cinemas. EN 50172:2004 also recommends maintained exit signs where the occupants may be unfamiliar with the building. A non-maintained mode of operation may be suitable for all other premises. SECTION 10: page 17 1 0 . 1 : e m e r genc y lig h ting design G u ide by Honeywell Design Guide Design Stage 7 Commissioning, testing and maintenance Control Once the design has been completed it becomes apparent that the performance of the luminaire depends as much on the light distribution as it does the light output available. Consequently it becomes essential that luminaire types specified for a particular design are not changed without a reappraisal of the photometric design. Testing and Log Book The system should include adequate facilities for testing and recording the system condition. These need to be appropriate for the specific site. It may well be desirable to test the installation in an office block by isolating the total supply, but this would be inappropriate in a hotel which is occupied 24 hours a day, seven days a week. For a hotel, a test system able to be tested by zone would be more suitable as the risks of having all the luminaires discharged while the building is occupied can be eliminated. To meet the requirements of EN 50172 a full duration test should be undertaken annually, with short duration tests monthly. Commissioning Certificate BS 5266 Part 1: 1999 requires written declaration of compliance to be available on site for inspection. These consist of: 1 Installation quality This means IEE regulations, HD384-5, must have been conformed to with suitable cable, adequate support and protection having been used. The requirement in BS 5266, that non-maintained fittings are fed from the final circuit from the normal lighting in the area, must have been complied with. 2 Photometric performance Evidence of compliance with design criteria must be obtained. Gent registered fittings are independently photometrically tested and their spacing data registered by the ICEL scheme. Copies of this data present the verification required provided that the spacings are not exceeded. 3 Declaration of a satisfactory test of operation A declaration of satisfaction test of operation is also needed. 4 Log book A log book should be kept and be readily available for inspection. It should record the date and brief details of completion, any alterations, periodic inspections and test certificates, each service, inspection or test carried out, defect and remedial action. Maintenance Finally to ensure that the system remains at full operational status, essential servicing should be defined. This normally would be performed as part of the testing routine, but in the case of consumable items, such as replacement lamps, spares should be provided for L immediate use. N Mains Lighting Emergency Lighting Emergency lighting wiring diagram 10 SECTION 10: page 18 1 0 . 1 : e m e r genc y lig h ting design G u ide by Honeywell Checklist for Assessment Yes No Are the entries made in the log book correct? n n Are up to date drawings available and correct? n n Are routine tests completed according to requirements in BS 5266? n n Are the emergency luminaires and signs suitable for use on escape routes? n n Are the fittings supplied with the correct operating voltage? n n Are the fittings clean and sited in their correct operating environment e.g. for temperature and I.P. rating? n n Are the fittings operating in the correct mode e.g. maintained for sleeping accommodation? n n Do the fittings operate for the required emergency duration? n n Are the batteries being charged? n n Are there signs which clearly indicate the emergency escape route from any position within the premises? n n Are all exits marked and directions of travel indicated? n n Are signs illuminated internally or from an external source when the normal lighting supply fails? n n Are the size of signs correct for the viewing distance? n n Do the sign legends comply with the signs directive? n n Are emergency luminaires positioned at all points of emphasis? n n Are the emergency luminaires positioned along the escape routes at the correct spacings to ensure that the required illuminance levels are achieved? n n Are emergency luminaires positioned in open areas (anti-panic) at the correct spacing to ensure that the minimum illuminance level is achieved? n n Are the non-maintained luminaires fed from final circuits? n n Are there at least two luminaires in each “lighting compartment”, thus ensuring that the area is not plunged into darkness if a luminaire fails? n n Are additional luminaires provided in lift cars, escalators, toilets etc? n n Are hazardous areas illuminated at 10% of normal illuminance? n n Does the central battery system comply with prEN 50171 and HD 384? n n Is the battery charger functioning? n n Where applicable, are the battery electrolyte levels and specific gravities satisfactory? n n Records Emergency Luminaires and Escape Route Signs Signs Luminaires Central Battery Systems 10 SECTION 10: page 19 1 0 . 1 : e m e r genc y lig h ting design G u ide Design Guide – Glossary by Honeywell Ballast - controls the operation of a fluorescent lamp from a specified low or high voltage AC or DC source (typically between 12 and 240 volts). It can also include an element for starting the lamp and sometimes for power factor correction or radio interference suppression. Ballast Lumen Factor (BLF) - is the ratio of the light output of the lamp when the ballast under test is operated at its design voltage compared with the light output of the same lamp operated with the appropriate reference ballast supplied at its rated voltage and frequency. Battery - secondary cells providing the source of power during mains failure. Battery Sealed (recombination) - a battery that is totally sealed, or constructed so that no provision is made for replacement of electrolyte. Battery Unsealed (vented) - a battery that requires replacement of electrolyte at regular periods. Battery Capacity - is the discharge capability of a battery being a product of average current and time expressed as Ampere hours over a stated duration. Note: A shorter total discharge period gives rise to a smaller available capacity. Central Battery System - is a system in which the batteries for a number of luminaires are housed in one location, usually for all emergency luminaires in one lighting sub-circuit sometimes for all emergency luminaires in a complete building. Combined Emergency Luminaire (sustained) - contains two or more lamps at least one of which is energised from the emergency supply and the remainder from the normal supply. Design Voltage - is the voltage declared by the manufacturer to which all the ballast characteristics are related. Emergency Lamp Design Lumen (ELDL) - is the claimed output of the lamp measured at the end of the declared lamp life, multiplied by the Ballast Lumen Factor (BLF) of the specific emergency lighting circuit. Emergency Lighting - is the lighting provided for use when the supply to normal lighting fails. Escape Route Lighting - is provided to ensure that the means of escape can be effectively identified and safely used when a location is occupied. Emergency Exit - a way out that is used during an emergency. “F” Mark - shows the luminaire can be mounted on combustible surfaces. Final Exit - is the terminal point of an escape route, beyond which point persons are no longer in danger from fire or any other hazard requiring evacuation of the building. High Risk Task Area Lighting - is that part of emergency lighting provided to ensure the safety of people involved in a potentially dangerous process or situation and to enable proper shutdown procedures for the safety of the operator and other occupants of the premises. Glow Wire - 850ºC Test - all emergency luminaires on escape routes must pass this test. Self-extinguishing grades of polycarbonate, PVC or glass and steel are needed. Illuminance - is the luminous flux density at a surface i.e. the luminous flux incident per unit area. The unit of illuminance is lux, that is, lumens per square metre. K Factor - is the amount that the lamp output will reduce because of the effect of battery discharge. This factor will vary dependent on the control gear characteristics. The final applied minimum voltage and type of lamp. Values can vary from 0.55 for tungsten lamp to a factor of about 0.75 to 0.85 for a fluorescent circuit. Lighting Design Lumens (LDL) - is the claimed lamp light output measured on a standard reference circuit at the end of the declared lamp life. Luminaires - are apparatus which distribute, filter and transform the lighting given by a lamp or lamps and which include all the items necessary for fixing and protecting these lamps and for connecting them to the supply circuit. Note: Internally illuminated signs are a special type of luminaire. Maintained Emergency Luminaire - is a luminaire in which the emergency lighting lamps are energized at all times when normal or emergency lighting is required. Mounting Height - is the vertical distance between the luminaire and the floor. Non-Maintained Emergency Luminaire - is a luminaire containing one or more lamps which operate from the emergency supply only upon failure of the normal mains supply. Normal Lighting - is all permanently installed artificial lighting operating from the supply in normal use, which in the absence of adequate daylight is intended for use during the whole time that the premises are occupied. Open Area (Anti-panic) Lighting - is that part of emergency escape lighting provided to avoid panic and provide illumination allowing people to reach a place where an escape route can be identified. Rated Duration - is the manufacturer’s declared duration for a battery operated emergency lighting unit, specifying the time for which it will operate after mains failure. This may be for any reasonable period, but is normally one or three hours (when fully charged). Rated Load - is the maximum load which may be connected to the system which will be supplied for the rated duration. Re-Charge Period - is the time necessary for the batteries to regain sufficient capacity to achieve their rated duration. Room Index - defines the relationship between the height, length and width of a room used for illuminance calculations. Self-Contained Emergency Luminaire - is a luminaire or sign providing maintained or non-maintained emergency lighting in which all the elements such as battery, the lamp and the control unit are contained within the housing or within one metre of the housing. Service Factor (SF) - is the ratio of the illuminance provided by an aged system with dirty luminaires to the illuminance of the same system when new. Single Point Luminaire - (see self-contained emergency luminaire). Slave or Centrally Supplied Luminaire - is an emergency luminaire without its own batteries that is designed to work in conjunction with a central battery system. Standby Lighting - is the part of emergency lighting which may be provided to enable normal activities to continue in the event of a mains supply failure. Uniformity - is the ratio of average illuminance to the minimum illuminance measured at the working plane. Utilisation Factor (UF) - is the proportion of light emitted by the lamp in the emergency lighting luminaire that reaches the working plane. 10 SECTION 10: page 20 1 0 . 1 : e m e r genc y lig h ting design G u ide by Honeywell 10 Notes SECTION 10: page 21 Section 10.2: by Honeywell Self Contained Emergency Lighting 10 SECTION 10: page 22 1 0 : e m e r genc y lig h ting design by Honeywell 10 Chapter title goes here SECTION 10: page 23 1 0 . 2 : l u m ene x e m e r genc y lig h ting by Honeywell 8W Luminaire 8W Luminaire Technical Specification Emergency Duration 3 hours Emergency Lamp O/P 105 lumens Maintained Lamp O/P 185 lumens (LUM8/M) Construction 3 part self-extinguishing unit incorporating a polycarbonate lens, ABS/PC alloy base and metal geartray. Colour: White Dimensions Length 343mm Height 78mm Depth 101mm Weight 1.0kg (LUM8/NM) 1.2kg (LUM8/M) Cable Entry Drill guides on sides and one end. BESA in rear of fitting Supply Voltage 230Vac +/- 10% 50Hz Power Consumption 8VA (LUM8/NM) 15VA (LUM8/M) Recharge Period 24 hours for full 3 hour duration Battery NiCad 2.4V 4Ah Light Source 300mm 8 Watt T5 fluorescent Monitor High intensity red LED monitoring charger output and battery connection Operating Temperature 0 to +25oC Ingress Protection IP40 (IP65 when seal fitted) Warranty 1 year Certification CE - Ref. BS 4533 / EN 60598-2-22 l Suitable for a wide range of interior and exterior applications l Cost effective with an optically efficient and durable lens design l Maintained /non-maintained versions l Weatherproof (fit seal supplied if an IP65 rating is required) l Snap-fit construction with hinged gear tray l Simple to install with screw terminal block and a BESA box mounting facility l Stylish, slim profile design with a range of optional pictograms Order Codes 8W Luminaire, IP65, LUM8/NM Non-maintained 8W Luminaire, IP65, MaintainedLUM8/M Semi-recessing Bezel for LUM8/RB 8W Luminaire, White Pictogram, Arrow Down LUM8/PAD Pictogram, Arrow Left LUM8/PAL Pictogram, Arrow Right LUM8/PAR 10 SECTION 10: page 24 1 0 . 2 : l u m ene x e m e r genc y lig h ting by Honeywell LumHigh8 Emergency Luminaire l A flexible high light output luminaire l A separate mounting bracket and battery compartment makes the Unilux easy to install and maintain l Elegant and functional design LumHigh8 Luminaire Technical Specification Order Codes High Light Output 8W LUMHI8/NM Luminaire, IP20, Non-maintained High Light Output 8W LUMHI8/M Luminaire, IP20, Maintained 10 Pictogram, Arrow Down LUMHI8/PAD Pictogram, Arrow Left LUMHI8/PAL Pictogram, Arrow Right LUMHI8/PAR Emergency Duration 3 hours Emergency Lamp O/P 137 lumens Maintained Lamp O/P 150 lumens (LUMHI8/M) Construction 3 part self-extinguishing unit incorporating a polycarbonate lens, ABS/PC alloy base and metal geartray. Colour: White Dimensions Length 363mm Height 83mm Width 149mm Weight 1.16kg Cable Entry 16/20mm knockouts on side/end of fitting Provision for rear BESA box mountings Power Consumption 6VA Non maintained 26VA Maintained Recharge Period 24 hours for full 3 hour duration Battery NiCad 3.6V 4Ah Light Source 8 Watt T5 fluorescent Operating Temperature 0 to +35oC Ingress Protection IP20 Certification CE SECTION 10: page 25 1 0 . 2 : l u m ene x e m e r genc y lig h ting by Honeywell Rectangular 8W Exit Sign Rectangular Exit Sign l Cost effective lighting solution for interior applications l Suitable for mounting on emergency escape routes as defined by BS 5266 l Maintained/non-maintained versions l Single-sided low profile unit with pictogram accessible from bottom entry l Integral threshold downlighter l Robust construction for simple surface-mounted installation l Range of self-adhesive pictogram options Technical Specification Emergency Duration 3 hours Emergency Lamp O/P 105 lumens Maintained Lamp O/P 185 lumens (LUMRECT/M) Construction Rectangular sheet steel housing, incorporating self-extinguishing opal exit screen and down-lighter. Colour: White Dimensions Length 425mm (pictogram 395mm) Height 190mm (pictogram 160mm) Depth 60mm Weight 2.3kg (LUMRECT/NM) 2.4kg (LUMRECT/M) Cable Entry 20mm knockouts in side, top and rear. Rear BESA box mounting provision Supply Voltage 230Vac +/- 10% 50Hz Power Consumption 8VA (LUMRECT/NM) 15VA (LUMRECT/M) Recharge Period 24 hours for full 3 hour duration Battery NiCad 2.4V 4Ah Light Source 300mm 8 Watt T5 fluorescent Monitor High intensity red LED monitoring charger output and battery connection Operating Temperature 0 to +25oC Ingress Protection IP20 Warranty 1 year Certification CE - Ref. BS 4533 / EN 60598-2-22 Order Codes Rectangular 8W Exit Sign, LUMRECT/NM IP20, Non-maintained Rectangular 8W Exit Sign, LUMRECT/M IP20, Maintained Pictogram for Rectangular LUMRECT/PAD Exit Sign, Arrow Down Pictogram for Rectangular LUMRECT/PAL Exit Sign, Arrow Left Pictogram for Rectangular LUMRECT/PAR Exit Sign, Arrow Right 10 SECTION 10: page 26 1 0 . 2 : l u m ene x e m e r genc y lig h ting by Honeywell l Suitable for interior applications l Cost-effective solution for large open areas with undefined escape routes l Non-maintained l Ideal for illuminating areas which could become dangerous if mains power fails l Stylish design features adjustable lamps with polycarbonate lenses l Snap-fit construction l Simple to install l Maintenance-free batteries l A high intensity LED on the unit front indicates healthy supply l 10 Independent lamp tests give indications of both left and right lamp integrity Order Codes Twinlight, 2 x 18W, 3-hour, IP20,LUMTWIN Non-maintained 2 x 18W Twinlight 18W Twinlight Technical specification Emergency Duration 3 hours Emergency Lamp O/P 2 x 264 lumens Maintained Lamp O/P N/A Construction 3 part assembly comprising an ABS housing, steel geartray and two polycarbonate fronted projectors. Colour: Buff Dimensions Length 368mm (base housing 325mm) Height 283mm (base housing 155mm) Depth 115mm Weight 6.5kg including battery Cable Entry 20mm knockouts in one end and rear of fitting Supply Voltage 230Vac +/- 10% 50Hz Power Consumption 30VA Recharge Period 24 hours for full 3 hour duration Battery 2 x sealed Lead Acid 6V 1.2Ah Light Source 2 x 18 Watt Tungsten Monitor High intensity red LED monitoring charger output and battery connection. Amber LEDs monitoring left and right lamp integrity Operating Temperature 0 to +30oC IP Rating IP20 Warranty 1 year Certification CE - Ref. BS 4533 / EN 60598-2-22 SECTION 10: page 27 1 0 . 2 : l u m ene x e m e r genc y lig h ting by Honeywell Photometric Data Maximum permitted spacing (in metres) to achieve 0.2 lux LUM8/NM LUM8/M LUMHI8/NM LUMHI8/M Maximum permitted spacing (in metres) to achieve 0.5 lux Maximum permitted spacing (in metres) to achieve 1 lux Height (m) Tr-Tr Ax-Ax Tr-Wall Ax-Wall Tr-Tr Ax-Ax Tr-Wall Ax-Wall Tr-Tr Ax-Ax Tr-Wall Ax-Wall 2.5 11.8 6.9 4.5 2.7 8.0 4.8 2.8 1.7 5.5 3.2 1.1 0.7 3 12.3 7.3 4.5 2.8 8.0 4.8 2.5 1.5 4.8 2.8 4 12.6 7.6 4.4 2.6 7.3 4.3 6 11.9 7.0 1.1 0.8 8 5.2 3.2 2.5 10.7 6.4 4.0 2.5 7.1 4.3 2.3 1.4 4.5 2.6 3 11.0 6.6 4.0 2.4 6.9 4.1 1.7 1.1 2.8 1.7 4 11.2 6.8 3.6 2.2 4.8 2.9 6 9.3 5.6 2.5 12 6 5 2.5 3 12.5 6 4.8 2.5 4 12.4 6 3.6 2 2.5 12 6 5 2.5 3 12.5 6 4.8 2.5 4 12.4 6 3.6 2 Note: All photometric data has been compiled in accordance with BS 5225: Part 3 (Method of Photometric measurement of battery-operated emergency luminaires). Key Tr-Tr Spacing transverse to transverse Tr-Wall Transverse distance to wall Ax-Ax Spacing axial to axial Ax-Wall Axial distance to wall n Information currently not available – contact Gent n Not applicable Illuminance perpendicular to beam (lux) 10m (data for single lamp) 12V 18W filament lamp Lamp Output (1m):264 20m 0 degrees 90 degrees 0 degrees 90 degrees 0 degrees 2.89 2.89 0.72 0.72 10 degrees 6.31 1.87 1.58 0.47 20 degrees 1.25 0.35 0.31 0.09 30 degrees 0.24 0.25 0.06 0.06 40 degrees 0.18 0.23 0.05 0.06 50 degrees 0.16 0.23 0.04 0.06 60 degrees 0.11 0.12 0.03 0.03 LUMTWIN LUMINAIRE UTILISATION FACTOR DATA (self-contained luminaires at zero reflectance) Room Index (RI) 0.75 1.00 1.25 1.50 2.00 2.50 3.00 4.00 5.00 LUM8 - 0.25 0.28 0.31 0.37 0.40 0.43 0.47 0.50 LUMHIGH - 0.29 0.33 0.37 0.44 0.48 0.52 0.56 0.59 Note: All photometric data has been compiled in accordance with BS 5225: Part 3 (Method of Photometric measurement of battery-operated emergency lighting luminaires). 10 SECTION 10: page 28 1 0 . 2 : nova e m e r genc y lig h ting by Honeywell Photometric Data Escape route spacing using self contained luminaires All figures are verified by the British Standards Institute and registered by ICEL. Optilite / Stormlite Non-Maintained Optilite / Stormlite Maintained Min. - 1.0 LUX Specified Points of Emphasis & Normal Risks Min. - 0.2 LUX Permanently Unobstructed Routes Only Ceiling Mounting Height (m) Transverse to Wall (m) Transverse to Transverse to Transverse to Axial to Axial Axial to Wall Transverse to Transverse to Axial to Axial Axial to Wall Transverse Transverse Axial (m) (m) (m) Wall (m) Axial (m) (m) (m) (m) (m) 2.5 1.3 4.7 4.4 4.0 1.2 4.5 12.4 10.0 7.6 3.0 4 - 2.8 2.6 2.3 - 3.7 12.7 10.8 8.8 3.2 6 - - - - - 2.5 10.0 9.4 8.9 2.2 2.5 1.1 4.0 3.9 3.7 0.9 4.1 11.6 9.4 7.2 2.9 4 - 1.5 1.1 0.8 - 3.2 11.6 10.0 8.3 2.9 6 - - - - - 1.8 8.7 8.4 8.0 1.4 Note: Spacing data includes a maintenance factor of 0.8 and a maintained lamp derating factor of 0.85 as defined by BSI and ICEL. 10 SECTION 10: page 29 Section 10.3: by Honeywell Central Battery Systems 10 SECTION 10: page 30 1 0 : e m e r genc y lig h ting design by Honeywell 10 Chapter title goes here SECTION 10: page 31 1 0 . 3 : C E N T R A L B A T T E RY S Y S T E M S by Honeywell Central Battery Systems Central battery systems provide a solution to power and test an array of emergency luminaires all from one central point. The luminaires are all wired back to a main cabinet housing the batteries and charger. This cabinet can be housed in a secure location that only authorised personnel can access. Due to the life safety importance of emergency lighting, central battery systems should always be wired in fire protected cables. This reassures the end-user that in a fire situation the power to the luminaires would not be lost. Testing and maintenance Either AC or DC systems can be provided with a comprehensive range of slave luminaires to suit. AC CENTRAL BATTERY SYSTEMS AC features: l High efficiency and reliability l Low operating cost l Wide range of standard ratings available, with batteries to suit all applications l For use with a wide range of normal mains voltage fittings, including fluorescent and HID l High light levels achievable The principal advantages of the AC systems is that the wide range of light fittings available for use with normal mains can be used with the inverter. This results in higher light levels being achieved when using AC systems than achieved using the traditional low voltage emergency luminaires. An end user should always ensure that regular testing and maintenance is carried out for all emergency lighting products in accordance with BS5266. This is much easier with a central battery system because testing can be controlled at one central point. A competent engineer should always be used to carry out maintenance. DC CENTRAL BATTERY SYSTEMS Cost of ownership DC features: On-going costs are also reduced l Wide range of standard ratings l Extensive choice of battery types l Comprehensive instrumentation and monitoring l Gent DC central emergency power systems automatically provide an alternative lighting supply in the event of AC supply failure l Long battery design life of between 5 and 25 years depending upon the type chosen l Comprehensive ranges of options are available to customise equipment to each individual application because with a central battery system the batteries can have a design life of up to 25 years where self-contained fittings need changing every 4 years. 10 SECTION 10: page 32 1 0 . 3 : C E N T R A L B A T T E RY S Y S T E M S by Honeywell Notes