Emergency Lighting Transfer Device

advertisement
Emergency Lighting
Transfer Device
Central Power
Systems
Evenlite’s emergency lighting transfer device allows the
user to provide emergency backup power to switched
fixtures. Backup power from a Pure Wave or Lite-Minder
inverter can be routed thru the emergency transfer device
to the fixtures from both the utility supply and the backup
power to provide the ability to switch fixtures off for
energy saving when not in use, yet have reliable backup
power available during power outages.
The emergency lighting transfer device is available for
mounting in a j-box in the ceiling (EPC-PM), or for mounting in the fixture ballast channel (EPC-A).
In-Fixture Installation


EPC-A
Recommended
Box Size
4-11/16”
5” L x 1.15” W x 1.15” D
TEST SWITCH
GREEN & RED
LED’s
Body Size:
1-1/2" x 3-1/2" x 3"
BLUE
6
EMERGENCY SWITCH LEG YELLOW
INDICATING
LED
5
Emergency Load
WHITE
EMERGENCY NEUTRAL 4 BLUE
BLACK
1
TEST SWITCH
EMERGENCY HOT
INDICATING
LED
MODEL EPC-PM WIRING DIAGRAM
RED
2
∗
17 Amp Regular Lights
WHITE
3
It is recommended to number
field wiring exactly the same
with numbers provided.
3161 State Road, Bensalem, PA 19020 USA
TEL: (800) 872 0879 • FAX:(215) 244 4208 • www.evenlite.com
REGULAR LINE HOT
ROOM
SWITCH LEGSWITCH
REGULAR LINE NEUTRAL
∗ OPTIONAL OCCUPANCY
SENSOR CONTACT
Project name:
Approved By:
Catalog No:
Type No:
Emergency Lighting Transfer Device
FEATURES
•
•
•
•
•
•
•
•
The EPC-PM easily installs in a 4-11/16” j-box
The EPC-PM is provided with red and green LED indicators, green indicates utility power is present and red
indicates emergency power is present
Failsafe operation, with built in surge protection
Energy savings realized by switching fixtures off
when not in use
Emergency backup power provided on failure
of normal utility power regardless of wall switch
position
A momentary test switch allows the user to test the
EPC-PM as required
Compatible with Pure Wave and Lite-Minder Sine Wave
Inverter Systems
Compatible with dimming systems and occupancy
sensors
•
•
•
•
•
•
•
•
MULTIPLE EPC ON A 20 AMP BREAKER
The EPC-A is UL listed for field installation in the fixture ballast channel
A green LED is provided to indicate that utility power
is present
Allows the room fixture to be switched off when not in
use for energy savings
Dedicated emergency luminaires stay on for an additional 2.5 seconds after being turned off to indicate that the emergency power source is available
Both devices are completely maintenance free
Operating temperature range for both devices is 32° to
140° F (0-60°C)
Both devices are UL 924 listed
Three year limited warranty
Model EPC-A Fixture Mount Installation Instructions












 

 










 








 






 






ORDERING GUIDE
It is recommended to number eld wiring










 
 
EPC
Model
Mounting
EPC Emergency Power Control
PM
A*
Plenum Mount
Fixture Mount
Input/Output Voltage
V1
120/120 VAC
V2 277/277 VAC
* EPC-A is 120/277 VAC field selectable
Example: EPC-PM
3161 State Road • Bensalem, PA 19020 USA
Tel: (800) 872-0879 • Fax: (215) 244-4208
www.evenlite.com
EPC 05/13
Download