Npower™ 3-Phase UPS: 30 to 80 kVA, 208 or 480VAC, 60 Hz

Npower™ 3-Phase UPS: 30 to 80 kVA, 208 or 480VAC, 60 Hz
•
Unmatched heritage of reliability and
availability
•
Smallest system footprint
•
Excellent efficiency with non-linear loads and
partial loads
•
Outstanding dynamic response
•
All-digital ActiveStar™ controls and graphical
user interface
The Npower is a true double-conversion UPS, the
result of an international design collaboration and
more than a decade of advanced research.
The rugged power train and advanced ActiveStar™
controls were subjected to computer simulations and
accelerated life testing to ensure reliable performance
in every type of electrical environment.
Even the physical packaging is uniquely efficient, to
make fully configured systems more compact than its
competitors.
Best of all, it’s a Liebert product – designed to give
the same million-hour critical bus MTBF as other
Liebert UPS products.
OUTPUT
Voltage: 208 or 480 VAC, 3-phase, 4-wire plus
ground
Voltage Adjustment Range: ±5%
Voltage Regulation:
±0.5% for balanced load
±1.0% for 100% unbalanced load
Dynamic Regulation: ± 2.5% deviation for 100%
load step. ±1% for loss or return of AC input
Transient Response Time: Recover to ±1% of
steady state within 1 cycle
Voltage Distortion: For linear loads, 1% THD. Less
than 2.5% THD for 100% nonlinear loads without
kVA/kW derating
Phasing Balance: 120° ±0.5° for balanced load. 120°
±1° for 100% unbalanced load
Frequency Regulation: ±0.1%
Load Power Factor Range: 1.0 to 0.7 lagging
without derating
Overload: 125% of full load for ten minutes.
150% for one minute, with true sinusoidal
waveform
STANDARDS
ETL Listed to UL 1778 UPS standards, and CSA
certified. Some configurations are certified to UL
924 standards for emergency lighting.
GENERAL SPECIFICATIONS
INPUT
Voltage: 208 or 480 VAC, 60 Hz
3-phase, 3-or 4-wire plus ground
Voltage Range: +10, -15% (no battery discharge at 20%)
Frequency Range: 60 Hz, ± 5
Current Distortion: 10% maximum reflected THD at
full load with included input filter.
Current Limit: 115% of full load input current
Current Walk-in: 20 seconds to full load
Power Factor: 0.95 lagging minimum at full load, with
included input filter
Surge Protection: Sustains input surges without
damage, per criteria listed in ANSI C62.41-1980
(IEEE 587)
ENVIRONMENTAL
Operating Temperature: 0° to 40°C (UPS), 20° to
30°C (battery)
Non-Operating Temperature: -20°C to 70°C
Relative Humidity: 0-95% non-condensing
Operating Altitude: Up to 6,600 feet (2000 meters)
without derating
Acoustical Noise: Less than 65 dBA typical,
measured 1 meter from the unit
Matching Battery Packs
Model
30
1FJ
1HJ
1LJ
1MH
1PH
1RH
1UH
1WH
11
21
28
34
50
66
74
109
Battery Time in Minutes /UPS kVA
40
50
65
7
14
19
23
36
46
52
77
10
14
18
27
35
39
60
5
8
13
20
25
30
41
Weight (lb)
30-50 kVA
1,210
Weight (lb)
65-80 kVA
1,320
Maintenance Bypass Cabinets
Model
Q
Dimensions (In.)
(WxDxH)
31.7x32.5x71
80
Dimensions (In.)
(WxDxH)
Weight
(lb)
5
9
15
19
22
33
25x32.5x71
25x32.5x71
25x32.5x71
25x32.5x71
25x32.5x71
49x32.5x71
49x32.5x71
49x32.5x71
1,600
1,800
2,350
2,470
3,000
3,900
4,250
5,450
Slim-Line Distribution Cabinet
Dimensions (In.)
(WxDxH
10x32.5x71
Weight
(lb)
250
Site Planning Data
UPS Rating
KVA
KW
30
30
30
40
40
40
50
50
50
65
65
65
80
80
80
24
24
24
32
32
32
40
40
40
52
52
52
64
64
64
Npower™ 3-Phase UPS: 30-80 kVA, 208 or 480 VAC, 60 Hz
AC Input w/Filter
Voltage
Current (Amps) Rec.
Input Output Nom.
Max.
OCPD
208
480
480
208
480
480
208
480
480
208
480
480
208
480
480
208
208
480
208
208
480
208
208
480
208
208
480
208
208
480
80
33
33
106
44
44
133
55
55
171
70
70
210
87
87
1
99
41
41
133
55
55
166
69
69
213
88
88
262
108
108
2,3,8,12
125
50
50
175
70
70
200
100
100
300
125
125
350
150
150
6,14
Nom.
VDC
480
480
480
480
480
480
480
480
480
480
480
480
480
480
480
4
Battery
Battery
Max.
KW
Discharge
26
26
26
34
34
34
43
43
43
55
55
55
68
68
68
AC Output
Current
Nom
OCPD
66A
83
66A
83
66A
36
88A
111
88A
111
88A
48
109A
139
109A
139
109A
60
141A
180
141A
180
141A
78
174A
222
174A
222
174A
96
1,3,5,8,12 1,3,8,12
NOTES FOR TABLE:
1. Nominal (Nom) current is based on full rated output load.
2. Maximum (Max) current (125% of nominal) is short duration for battery recharge
conditions.
3. UPS input and bypass cables must be run in separate conduit from output
cables.
4. Nominal battery voltage is shown at 2.0 volts/cell per NEC 480-2.
5. Power cables from UPS DC link to batteries should be sized for a total maximum
2.0 volt line drop (measured at the UPS) at maximum discharge current.
6. Recommended AC input and AC output overcurrent protection represents 125%
of nominal full load current (continuous) plus non-continuous loads per NEC 215.
7. Minimum-sized grounding conductors to be per NEC 250-122. Parity-sized
ground conductors are recommended. Neutral conductors to be sized for full
capacity per NEC 310-15(b)(4). References are per NEC 1999.
8. Wiring requirements:
AC Input:
3-phase, 3-wire plus ground or
3-phase, 4-wire plus ground
AC Output: 3-phase, 4-wire plus ground
DC Input:
2-wire (positive and negative), plus ground
9. All wiring is to be in accordance with national and local electrical codes.
10. Minimum access clearance is 3 feet front and 1 foot above UPS.
11. Top or bottom cable entry through removable access plates. Punch plate to suit
conduit size, then replace.
12. Control wiring and power wiring must be run in separate conduit.
13. Weights and dimensions shown do not include battery cabinet, Slim-Line
distribution cabinet or other options.
14. OCPD=Overcurrent Protection Device.
125
125
50
150
150
60
175
175
80
225
225
100
300
300
125
6,14
Mechanical Data
Dimensions (In.)
(WxDxH)
Weight
(Lb)
Floor Load
(Lb/Sq.Ft)
Heat Dissipation
(BTU/Hr)
Cooling
Air (CFM)
31.7x32.5x71
31.7x32.5x71
31.7x32.5x71
31.7x32.5x71
31.7x32.5x71
31.7x32.5x71
31.7x32.5x71
31.7x32.5x71
31.7x32.5x71
39.4x32.5x71
39.4x32.5x71
39.4x32.5x71
39.4x32.5x71
39.4x32.5x71
39.4x32.5x71
13
2,200
2,100
1,900
2,200
2,100
1,900
2,200
2,100
1,900
2,700
2,500
2,300
2,700
2,500
2,300
13
307
294
265
307
294
265
307
294
265
304
284
262
304
284
262
8,500
7,500
7,500
11,000
10,000
10,000
14,000
12,000
12,000
18,000
15,000
15,000
22,000
18,000
18,000
720
720
720
720
720
720
720
720
720
960
960
960
960
960
960
ADDITIONAL NOTES:
•
•
•
If site configuration includes a back-up emergency generator, it is recommended
that the engine generator set be properly sized and equipped for a UPS
application. Generator options would typically include an isochronous governor
(generator frequency regulation) and a UPS-compatible regulator (generator
voltage regulation). Consult generator manufacturer for required generator
options and sizing.
If site configuration includes an automatic transfer switch, refer to the Liebert
Power Line titled “Criteria for Application of Automatic Transfer Switches (ATS)
with Uninterruptible Power Supply (UPS) Systems,” publication 91K-PLT-48-02.
It is also recommended that the transfer switch be equipped with auxiliary
contacts for UPS “on generator” current limit. Consult transfer switch
manufacturer for required transfer switch options and sizing.
If site configuration requires an external isolated maintenance bypass circuit, it
should be noted that utility AC input may not be in phase with the UPS AC
output. Consult Liebert sales representative or applications engineer.