TECHNICAL SPECIFICATION UNINTERRUPTED POWER SUPPLY(UPS) SYSTEM (2KVA/ 5KVA): 3.0. UNINTERRUPTED POWER SUPPLY (UPS) SYSTEM (2 KVA/ 5KVA): Any additional voltage regulator device may be considered to meet the input conditions e.g. providing properly sized CVT. a) UPS shall be free from workmanship defects, sharp edges, nicks, scratches, burs, etc. b) All fasteners shall be fixed properly. c) The equipment shall be complete with all parts and all parts shall be functional and shall meet the following minimum specifications: S.No. Parameter 1 Type of UPS 2 CAPACITY 3 Technology 4 5 AC input voltage range Input Frequency Details TRUE ONLINE 2 KVA / 5kVA The UPS shall be based on IGBT, and microprocessor controlled for providing better sine wave output 175 V to 275 V AC, Single phase. 7 8 47-53 Hz, (Suitable for working with Generator supply) UPS power factor 0.9 or better at rated load voltage 230V AC ± 2% , Single Phase AC output Output frequency 50 Hz ± 1% 9 Waveform Sinusoidal 10 Efficiency 11 Total harmonics distortion at 90% (at rated output voltage and frequency) 2% maximum 6 12 Indications 13 Protections 14 Back up time 15 Type of batteries 16 Remote monitoring port Standard visual indications for proper function of UPS (i) Over& Under Voltage cut-off, Over load, and short 2 kVA=8 Hour at 400 Watt load, 5kVA=8 Hr. at 1000W load Sealed Maintenance Free (SMF) Lead Acid battery (VRLA ) SNMP based monitoring Note: Bidder has to ensure that battery back up along with UPS shall occupy minimum space and they have to indicate the minimum space required for this purpose.