DOUGLAS lighting controls Calculating Wire Lengths for Short Circuit Current Ratings While calculating the voltage drop involves a simple equation (Ohm's Law: V=IR) where the voltage drop is directly affected by the conductor's resistance, calculating the number of wire-feet required to impede a short circuit current is much more complex: For 120/277VAC Loads: (Breaker AIC Rating - Relay SCCR Rating) x (# of Conductors per Phase) x (Conductor Constant) x Voltage (I -n) Conductor length = 2 x (Relay SCCR Rating) x (Breaker AIC Rating) For 208/480VAC Loads: (Breaker AIC Rating - Relay SCCR Rating) x (# of Conductors per Phase) x (Conductor Constant) x Voltage (I -l) Conductor length = 1.73 x (Relay SCCR Rating) x (Breaker AIC Rating) Wire Breaker Gauge Voltage AIC Rating (AWG) (VAC) (A) 10 120 (l-n) 12 120 (l-n) 14 120 (l-n) 10 277 (l-n) 12 277 (l-n) 14 277 (l-n) 10 208 (l-l) 12 208 (l-l) 14 208 (l-l) 10 480 (l-l) 12 480 (l-l) 14 480 (l-l) Short Ciruit Current Rating (SCCR) of Relay 1,500 10,000 5,000 18,000 14,000 Required Conductor Length (ft.) between Breaker & Relay 14,000 22,000 65,000 14,000 22,000 65,000 14,000 22,000 65,000 14,000 22,000 65,000 14,000 22,000 65,000 14,000 22,000 65,000 35 37 38 22 23 24 14 14 15 81 84 88 51 53 56 32 33 35 8 9 11 5 6 7 3 4 4 17 21 25 11 13 16 7 8 10 2 3 5 1 2 3 1 1 2 4 7 11 2 5 7 2 3 5 0 2 3 0 1 2 0 1 1 0 4 8 0 2 5 0 1 3 N/A 1 2 N/A 0 1 0 0 1 N/A 1 5 N/A 1 3 N/A 1 2 14,000 22,000 65,000 14,000 22,000 65,000 14,000 22,000 65,000 14,000 22,000 65,000 14,000 22,000 65,000 14,000 22,000 65,000 70 73 77 44 46 48 28 29 30 162 169 177 102 106 110 64 67 70 15 18 22 10 11 14 6 7 9 35 42 50 22 26 32 14 17 20 3 6 10 2 4 6 1 3 4 8 15 23 5 9 14 3 6 9 0 3 7 0 2 4 0 1 3 0 7 15 0 4 10 0 3 6 N/A 1 5 N/A 1 3 N/A 0 2 N/A 3 11 N/A 2 7 N/A 1 4 Even with the relay panel mounted right next to the breaker panel, approximately 5-6 feet of wire is needed to connect the devices. The above table shows that Douglas Lighting Controls relays rated at 14,000 SCCR need virtually no additional length of wire to impede the short circuit current. The table also shows there is no advantage in rating a relay to exceed a 14,000 amp SCCR. Douglas WR-6161 Relays are Fully Compliant with NEC 2005 Article 409 DOUGLAS lighting controls