Maxivolt MV-400 Data Sheet

advertisement
®
®
Model: MV-400
Specifications
Application
277 / 480 VAC
3 Ø / 4 Wire
Voltage
Configuration
Characteristics
Certifications
ETL-EU IEC 61643-1
RoHS
Listing
Environmental
Warranty
5 Years
USA
Customized Options Available to Meet Specific Client Needs
Maxivolt manufactures specialized products and works with clients to provide
exactly what they need. For example, if your device requires a waterproof or
explosion proof enclosure, needs a custom paint job, an installation kit to
streamline your install, or any other customization, Maxivolt can accommodate.
Surge Protective Device
Buss® 5 Amp 600V KTK-5
Normally Off Neon Lights
14 AWG Stranded
Silk Screened
NEMA® Type 2
Fusing
Indication
Conductor
Markings
Enclosure
L-N, L-L
Modes of Protection
II (2)
Type (Class)
2 kA
Nominal Discharge Current
472 (942)
Clamp Voltage L-N (L-L)
840 (1360)
VPL [Up] L-N (L-L)
100 kA
SCCR
300 (600)
MCOV L-N (L-L)
-40° C to 85° C
Operating Temperature
1% to 95%
Operating Humidity
UL 1283
Filtering
< 40 db
EMI-RFI Noise Attenuation
1 to 1.5 μF / Line
Capacitance
< 1 ns
Component Response Time
< 1 W / Line
Rated Power Dissipation
50 - 400 HZ
Frequency Range
IP 20
Degree of Protection
MV-400
Typical Applications: Lighting Panels
MV-400
Surge Protective Device
Made in USA
VOLTAGE
277 / 480 VAC
3 Ø / 4 WIRE
WARNING
®
DO NOT OPEN
ELECTRICAL
SHOCK
FUSE
REPLACE ONLY
WITH BUSS ®
5 AMP 600 V
KTK-5 WHEN
LIGHT IS ON
Approximate Size (H x W x D) 9” x 3.5“ x 4”
Hand Made With Pride Since 1988 • Made in USA • Hand Made With Pride Since 1988 • Made in USA • Hand Made With Pride Since 1988 • Made in USA • Hand Made With Pride Since 1988
Standard Installation Summary
Install According To Instructions Provided With Device
1.
2.
3.
4.
5.
6.
7.
Remove 1/2” knockout.
Mount using mounting feet with proper anchors.
Connect one black conductor to phase A.
Connect other black conductor to phase B.
Connect last black conductor to phase C.
Connect white conductor to neutral.
Install fuses.
Note: Breaker Size 15 amp (if required).
Note: Never add length to provided conductors.
Note: For optimum SPD performance minimize
conductor length and avoid sharp bends.
PHASE C
PHASE C (BLK)
NEUTRAL
®
MAXIVOLT CORPORATION
Amarillo, Texas
800-583-4773
PHASE B (BLK)
NEUTRAL
PHASE A (BLK)
TYPE 2
(CLASS II)
LISTED
IEC
61643-1
Value-Added Service
Customized Trainings, On-Site
Surveys, Support Service,
Technical Support, and More.
Think Green
Safety First
PHASE A
LOCATION
SCCR
Website Support
Find more information about
Maxivolt products and services.
www.maxivolt.com
MV-Series and ICP-Series surge
protective devices are RoHS
compliant.
PHASE B
100 kA
Phone Support
Support Service and Application
Specialists are a phone call away.
800.583.4773
N
SPD
All Maxivolt products are fused
and non-ground dependent to
minimize safety hazards.
Other Products
• MV-Series (120 VAC - 600 VAC)
• ICP-Series (12 VDC - 120 VAC)
• WS-Series (600 VAC - 5000 VAC)
Elsewhere on the Web
Find and follow Maxivolt on
Linkedin, Twitter, Facebook,
and Youtube.
inches
[millimeters]
®
Maxivolt Corporation
800 South Rusk Street
Amarillo, Texas, USA
(806) 371-0722
(806) 371-7454 (fax)
(800) 583-4773
MV4000414