Model 610-N4X NEMA 4X Control Enclosure Operator’s Installation and Instruction Manual Covers 610-N4X and 610-N4X-BBU DETCON, Inc. 3200 Research Forest Dr., The Woodlands, Texas 77387 Ph.281.367.4100 / Fax 281.298.2868 www.detcon.com/ July 25, 2011 • Document #2869 • Revision 2.2 Model 610-N4X This page left intentionally blank 610-N4X Instruction Manual ii Model 610-N4X Table of Contents 1.0 1.1 1.2 1.3 1.4 2.0 2.1 2.2 Introduction.............................................................................................................................................. 1 Description ........................................................................................................................................... 1 Specifications ....................................................................................................................................... 1 Auxiliary Alarm Relay Board (AARB)................................................................................................ 2 Remote Alarm Reset ............................................................................................................................ 3 Installation................................................................................................................................................ 3 Alarm and Fault Jumpers ..................................................................................................................... 5 Start Up ................................................................................................................................................ 5 3.0 Maintenance & Repair ............................................................................................................................ 6 4.0 Spare Parts List........................................................................................................................................ 7 5.0 Warranty .................................................................................................................................................. 7 Table of Figures Figure 1 Auxiliary Alarm Relay Board ................................................................................................................ 2 Figure 2 Mounting................................................................................................................................................ 3 Figure 3 Motherboard Wiring Diagram ............................................................................................................... 4 Figure 4 Backplane Configuration Jumpers ......................................................................................................... 5 Figure 5 Power Supply Wiring............................................................................................................................. 6 610-N4X Instruction Manual iii Model 610-N4X This page left intentionally blank Shipping Address: 3200 A-1 Research Forest Dr., The Woodlands Texas 77381 Mailing Address: P.O. Box 8067, The Woodlands Texas 77387-8067 Phone: 888.367.4286, 281.367.4100 • Fax: 281.292.2860 • www.detcon.com • sales@detcon.com 610-N4X Instruction Manual iv Model 610-N4X 1.0 Introduction Detcon Model 610-N4X Gas Detection System consists of 3 major assemblies: 1. The 610-N4X Fiberglass or Stainless Steel control enclosure. 2. The Model 10 single channel digital control modules. 3. The remote mount gas sensor assemblies. The NEMA 4X control enclosure is detailed in this manual; the Model 10 Control Modules are detailed in the Detcon Model 10 Operators Installation and Instruction Manual, and applicable sensor assemblies in their corresponding Operators Installation and Instruction Manual. 1.1 Description Detcon Model 610-N4X control enclosure, along with Model 10 Control Modules, is designed to serve as a host assembly for up to six remote mount gas detection sensors. The control enclosure is rated NEMA 4X, which is by definition rain tight and therefore suitable for outdoor location in electrically non-hazardous environments. All control modules are plug-in front panel accessible for easy maintenance and repair. The unit is powered by 110~240VAC unless otherwise specified at the time of order. Discrete output terminal strips located on the controller motherboard are provided for sensor terminations. 420mA outputs for remote recording devices and an RS-485 serial ModBus™ output are also located on the motherboard. VDC power in, and remote alarm reset terminations are also provided on the Motherboard. Form-C relay outputs from each Control Module are provided for Alarm 1, Alarm 2, and Fault conditions. These relay outputs can be configured as discrete or zoned as determined by jumpers located between the channels on the motherboard and the relay settings determined by the dipswitches on the Model 10 Control Modules. 1.2 Specifications Electrical Classification NEMA 4X Dimensions 16 “W x 18''H x 10½”'D Capacity 6 single channels Power Input 110~240VAC/24VDC Power Consumption <5 watts per channel (includes gas sensor and control modules; Does not include annunciators.) Outputs Discrete Analog 4-20mA DC Serial RS-485 Modbus™ Discrete or zoned alarm relays (Alarm 1, Alarm 2, and Fault located on associated Mod 10 Control Modules. See the appropriate Mod 10 Control Module Manual for more information.) Operating Temperature Range -40°C to +75°C Battery Backup (If applicable) 2ea. 12V 2.9Ah batteries in series; ½ hour minimum operating time Low Voltage Cut-off Board Warranty One year 610-N4X Instruction Manual Rev. 2.2 Page 1 of 8 Model 610-N4X 1.3 Auxiliary Alarm Relay Board (AARB) An Auxiliary Alarm Relay Board is included with each Detcon Model 610-N4X. The board is mounted on the bottom quadrant of the motherboard. The AARB (Figure 1) consists of four interposing relays (contacts are rated 10Amp @ 120VAC and 8Amp @ 30VDC) with 24VDC coils. The AARB can be configured for FormC dry contacts (common, normally open and normally closed), AC power, or DC power. 3.04 2.50 2.85 Ø0.165 X4 3.35 Figure 1 Auxiliary Alarm Relay Board An ‘IN/OUT’ termination is provided for applying AC or DC power to any one of the interposing relays. A gold plated jumper tab is used to apply the power option to the corresponding relay(s). The 4 relays may be used in any combination of Form-C dry contacts, DC outputs, and AC outputs. The terminations labeled “ALM COIL PWR” (P20) located on the lower left of the motherboard are used to power the relay coils on the AARB. Terminals P1+4, P1+3, P1+2, and P1+1 on the AARB provide for various relay logic setups through the Form-C dry contact terminals of each Model 10 Control Module. P1-COM on the AARB should be wired directly back to P20-2 (ALM COIL PWR (-)) on the motherboard. The terminations labeled “ALM PWR” located on the left of the 610-N4X motherboard can be used to provide power to the In/Out termination on the AARB (AARB P2-IN/OUT). Alarm power terminations for AC (P18) come directly from the AC input terminals (P16) on the 610-N4X motherboard. The DC power terminations at P18 come directly from the VDC IN Terminals (P15). NOTE: DC power used to drive alarms must be obtained through a remote DC power source. The remote DC power source should be terminated at P15 labeled “VDC IN” located on the 610-N4X motherboard. Terminal Block P15 (VDC IN) functions as an alternative DC power source used to power the 610-N4X and as power for DC alarms. The 610-N4X power supply is not designed to provide power for alarm devices. 610-N4X Instruction Manual Rev. 2.2 Page 2 of 8 Model 610-N4X NOTE: If the Battery Option is installed (610-N4X-BBU), the batteries are connected to P15 (VDC IN). Do not use the DC output of “ALM POWER” (P18-1 and P18-2). The Batteries are not designed to provide power for alarm devices. Mounting hardware is provided on the 610-N4X motherboard for two additional Auxiliary Alarm Relay Boards. 1.4 Remote Alarm Reset A remote mounted normally open momentary switch may be used to reset the alarms of all Model 10 controllers. “ALM RESET” (P14-1 and P14-2) provides a set of terminals to connect the switch across every Model 10 Controller (Figure 3). The reset function is effective when the Model 10’s respective alarms have been programmed in the latching position and alarm conditions have passed. Each Model 10 controller also has its own discrete alarm reset switch, discussed further in the Model 10 Controller Manual. 2.0 Installation 1. Securely mount the 610-N4X Enclosure in accordance with Figure 2. 16" Ø0.3" Mounting Bracket 10" 12" Circuit Breaker 3 AMP MODEL 10 MODEL 10 MODEL 10 MODEL 10 MODEL 10 MODEL 10 ALM 2 ALM 1 FAULT ALM 2 ALM 1 FAULT ALM 2 ALM 1 FAULT ALM 2 ALM 1 FAULT ALM 2 ALM 1 FAULT ALM 2 ALM 1 FAULT ALARM RESET TEST ALARM RESET TEST ALARM RESET TEST ALARM RESET TEST ALARM RESET TEST ALARM RESET TEST 16.75" 17.85" Detcon Inc. Gas Detection Control System www.detcon.com Houston Texas Figure 2 Mounting 2. Refer to installation and wiring detail of remote mount sensor assemblies as detailed in the Sensor Instruction Manual. Terminate field wiring from sensors on the 610-N4X motherboard. Terminals are labeled “Sensor” (mA, + and –, Figure 3). 610-N4X Instruction Manual Rev. 2.2 Page 3 of 8 Model 610-N4X 3. If applicable, terminate the discrete 4-20mA outputs to external device(s). Terminals are labeled “420 Out” (+ and –, Figure 3). BRKR 1 2 P11 PS DC + - 1 2 P12 D1 6A 50V D2 6A 50V PS VAC 1 L1 2 N 3 GND P13 ALM RESET 1 2 A1 A2 A3 A4 A5 A6 A7 A8 A9 A10 A11 A12 A13 A14 A15 A16 P14 VDC IN + - 1 2 P15 VAC IN L1 N GND 1 2 3 P16 RS-485 B(-) Shld 1 2 3 P17 ALM POWER P18 + - L1 P19 N GND 1 2 3 4 5 RS-485 Shield to Gnd Tie to Chassis + mA NC NO COM NC NO COM NC NO COM 4-20 OUT P20 Earth Ground FAULT 1 2 ALM 1 ALM COIL + - A1-NO A1-NC A1-COM -485-A RST 485-S 485-B -XMXMXM-VDCVDCVDC- + A1 A2 A3 A4 A5 A6 A7 A8 A9 A10 A11 A12 A13 A14 A15 A16 C1 C2 C3 C4 C5 C6 C7 C8 C9 C10 C11 C12 C13 C14 C15 C16 CH1 CH2-CH6 CH1 CH2-CH6 P11 ALM2 SENSOR A(+) C1 C2 C3 C4 C5 C6 C7 C8 C9 C10 C11 C12 C13 C14 C15 C16 1 2 3 4 5 6 7 8 9 10 11 12 13 14 A2-COM A2-NC A2-NO FLT-COM FLT-NC FLT-NO 4-20 OUT 4-20 IN -XM+ XM+ XM+ -VDC+ VDC+ VDC+ P12-P16 Typical Jumpers A B C D E F G H I JP1-JP5 1 2 3 4 5 6 7 8 9 10 11 12 13 14 Figure 3 Motherboard Wiring Diagram 4. If applicable, terminate the RS-485 serial output to external device(s). Terminals are labeled “RS485” (A+, B–, and Shield, Figure 3). If applicable, terminate RS-485 Shield to Earth Ground via the jumper tab located to the left of the RS-485 terminals. Place the jumper on the bottom 2 contacts to tie RS-485 shield to Earth Ground or place the jumper tab on the top two terminals for storage. 5. If applicable a Remote Reset Switch can be utilized by connecting a Momentary, Normally-Open Switch to P14 (ALM RESET). 6. Earth Ground can be connected to the ground point located in the lower left quadrant of the motherboard. 610-N4X Instruction Manual Rev. 2.2 Page 4 of 8 Model 610-N4X 7. If applicable, connect a 24VDC source or standby battery to the terminal strip labeled “VDC IN” (P15+ and –) on the Motherboard (Figure 3). NOTE: If the unit has the Battery Backup Option installed (610-N4X-BBU), do not connect an external power source to P15. 8. Connect 110/220VAC input wiring to the terminals labeled “VAC IN”; P16-1 (L), P16-2 (N), and P16-GND Ground (Figure 3). The Power Supply will accept input voltages from 100 to 240VAC, 50/60Hz. 2.1 Alarm and Fault Jumpers 4-20 OUT FAULT ALM 1 ALM2 SENSOR A bank of jumpers is provided between each channel for use in setting up alarm and fault schemes. These jumpers can be installed or removed to create discrete or zoned alarm/fault schemes in conjuncture with the Model 10 Control Module relay settings. With all of the jumpers installed on the motherboard, the relays on the Control Modules are placed in parallel with each other. (I.E. All of the Alarm 1 relays are in parallel, all of the Alarm 2 relays are in parallel, and all of the Fault Relays are in parallel.) In this configuration, the normally open (“NO”) contacts of the relays would be used to generate an alarm or fault condition, as contact closure on any Control Module would create continuity between the “COM” contact and the “NO” contact output for that alarm or fault. A scheme for alarms should be conceived before power is applied to the unit, and the unit should be set up accordingly. For aid in setting up an appropriate alarm/fault scheme, contact Detcon Customer Service. + mA NC NO C NC NO C NC NO C + - CH1 CH2 CH3 CH4 1 2 3 4 5 6 7 9 9 10 11 12 13 14 1 2 3 4 5 6 7 9 9 10 11 12 13 14 1 2 3 4 5 6 7 9 9 10 11 12 13 14 1 2 3 4 5 6 7 9 9 10 11 12 13 14 A B C D E F G H I JP1 A B C D E F G H I JP2 A B C D E F G H I JP3 CH5 A B C D E F G H I JP4 1 2 3 4 5 6 7 9 9 10 11 12 13 14 CH6 A B C D E F G H I JP5 1 2 3 4 5 6 7 9 9 10 11 12 13 14 Alarm 2 Jumper positions A, B, anc C. Alarm 1 Jumper positions D, E, and F. Fault Jumper positions G, H, and I. Figure 4 Backplane Configuration Jumpers 2.2 Start Up Upon completion of all field wiring: Apply power to the 610-N4X by setting the 3Amp Circuit Breaker (the Circuit Breaker is also a Power Switch, labeled ‘3Amp’) on the front on the Card Cage. Note that each Model 10 controller digital display illuminates. NOTE: Varying readings may occur during sensor warm-up. A 10 second alarm delay will occur on power up. Refer to the applicable Sensor Instruction Manual for additional sensor start-up details. 610-N4X Instruction Manual Rev. 2.2 Page 5 of 8 Model 610-N4X 3.0 Maintenance & Repair The Detcon Model 610-N4X’s modular design allows for minimum ‘down-time’ during maintenance and/or repair. Model 10 Control Modules A Model 10 control module may be changed by simply loosening its mounting screw and sliding the module out of its card cage. See the Model 10 Instruction Manual for more information on the Model 10 controllers. Circuit Breaker/Power Switch If the 3Amp Circuit Breaker/Power Switch should trip due to a high current or over voltage, the circuit breaker can be reset by pushing the breaker in (‘ON’). If the breaker trips again, a problem has occurred that will need to be alleviated before power can be restored. NOTE: The circuit Breaker/Power Switch does not remove VAC from the Power Supply or the Motherboard. If power is to be completely removed from the unit, the VAC must be disconnected from the source. NOTE: On units with Battery Backup installed (610-N4X-BBU), the Circuit Breaker will remove power from the Unit, but does not disconnect the Battery circuit from the Motherboard or the Low Voltage Cutoff Board. The Batteries must be unplugged as well as disconnecting the VAC from the source to remove power completely from the unit. 2 RED RED J1 P11 BRKR 1 2 Power Supply 1 PS P/N 360-SWS100-024 Circuit Breaker + P12 - + 7 + 6 - 5 - 4 GND 3 L1 2 N 1 RED BLACK GREEN BLACK WHITE PS VAC L1 N GND 1 2 PS DC Power Supply Wiring - without Battery Backup 1 2 3 P13 Circuit Breaker RED BLACK RED RED J1 P11 BRKR 1 Power Supply 2 PS P2 1N4001 1 2 Low-Voltage Cut-off (LV) P/N 500-505000-000 P1 P/N 360-SWS100-024 1 2 3 4 RED + P12 - + 7 + 6 - 5 - 4 GND 3 L1 2 N 1 RED BLACK RED 1 2 BLACK PS DC GREEN BLACK WHITE PS VAC L1 N GND 1 2 3 P13 Note: 1N4001 diode added to charge batteries Power Supply Wiring - With Battery Backup Figure 5 Power Supply Wiring 610-N4X Instruction Manual Rev. 2.2 Page 6 of 8 Model 610-N4X Power Supply Replacement of the power supply is accomplished by, removing the 10 screws that secure the 610-N4X face plate, disconnecting all wiring to/from the power supply, and removing the three screws holding the power supply bracket to the Motherboard. Remove the four screws that hold the power supply bracket to the power supply and reassembly with the new power supply. (Figure 5) Power Supply wiring is different between units with and units without the battery backup option; attention should be paid to the correct wiring scheme for the unit being worked on. 4.0 Spare Parts List Part # Description 224 320-228861-103 360-SWS100-024 500-502600-000 500-505000-000 3423-2 Gold plated jumper tab 3Amp Circuit Breaker/Power Switch 100 watt, 24 VDC switching power supply Auxiliary Alarm Relay Board Low Voltage Cut-off PCB (Battery Backup Units only) 12V 6.5Ah Battery (Battery Backup Units only) 5.0 Warranty Detcon Inc., as manufacturer, warrants under intended normal use each new Model 610-N4X NEMA 4X control enclosure to be free from defects in material and workmanship for a period of one year. The warranty period begins from the date of shipment to the original purchaser and ends one year thereafter. All warranties and service policies are FOB the Detcon Inc. facility located in The Woodlands, Texas. Appendix C Revision History Revision 2.0 2.1 2.2 Date Changes made Approval 04/10/2007 Previously issued B. Masi 05/27/2008 Placed rev 2.0 in M2M as rev 2.1 B. Masi 08/15/2008 Updated drawings to remove reference to common alarm. Fixed LU wiring diagram. Corrected revision number to match M2M 610-N4X Instruction Manual Rev. 2.2 Page 7 of 8 Model 610-N4X This page left intentionally blank Shipping Address: 3200 A-1 Research Forest Dr., The Woodlands Texas 77381 Mailing Address: P.O. Box 8067, The Woodlands Texas 77387-8067 Phone: 888.367.4286, 281.367.4100 • Fax: 281.292.2860 • www.detcon.com • sales@detcon.com 610-N4X Instruction Manual Rev. 2.2 Page 8 of 8