SAREx 25.1 – SAREx 30.1 Electrical data Multi-turn actuators for modulating duty with 3-phase AC motors Intermittent duty S4 - 50 %, 240 V/50 Hz Multi-turn actuator Type SAREx 25.1 SAREx 30.1 Output speed [rpm] 4 5.6 8 11 4 5.6 8 11 Motor Max. torque [Nm] Motor type Nominal power1) PN [kW] Speed [rpm] ADXQ 90-8/130 0.75 700 ADXQ 90-4/130 2.2 1,400 ADXQ 112-8/140 1.5 700 ADXQ 112-4/110 4.0 1,400 Nominal Max. cur- Starting curcurrent2) rent3) rent IN [A] Imax [A] IA [A] 1,400 2,800 10 10 9.5 9.5 15 15 16 16 13 14 13 14 19 21 21 22 25 25 54 54 54 54 87 87 cos Overcurrent AUMA power class for protection switchgear device setting [A] Contactor Thyristor 0.48 0.48 0.80 0.80 0.58 0.58 0.77 0.77 10 10 9.5 9.5 15 15 16 16 A2 A2 A2 A2 A3 A3 A3 A3 – – B3 B3 – – – – Notes on table 1) Nominal power PN Mechanical power output at motor shaft at running torque of multi-turn actuator (corresponds to approx. 50 % of maximum torque). The consumed electrical power can be calculated using the following formula: P = U x I x cos x √3 2) Nominal current IN Current at running torque 3) Max. current Imax Current at max. torque Notes on installation and sizing Motor data Motor data is approximate. Due to usual manufacturing tolerances, there may be deviations from the values given. Thermoswitches/PTC thermistors To protect against overheating, thermoswitches or PTC thermistors are embedded in the motor windings. Actuators without integral controls (AUMA NORM): Thermoswitches or PTC thermistors have to be considered within the external controls (refer to terminal plan). Note: Failure to connect thermoswitches or PTC thermistors shall void or warranty for the motor. According to EN 60079-14, a thermal overcurrent protection device (e.g. motor protection switch) must be installed for explosion-proof actuators in addition to the thermoswitches. PTC thermistors additionally require a suitable tripping device in the controls. Rating of the thermoswitches AC current 250 V, 50 – 60 Hz cos = 1 2.5 A cos = 0.6 1.6 A DC current 60 V 42 V 24 V 1.0 A 1.2 A 1.5 A Actuators with AM or AC integral controls: Thermal motor protection is already integrated. Mains voltage, mains frequency Permissible variation of mains voltage: ±10 % Permissible variation of mains frequency: ±5 % We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document. Y006.836/003/en Issue 1.15 Page 1/2 SAREx 25.1 – SAREx 30.1 Electrical data Multi-turn actuators for modulating duty with 3-phase AC motors Intermittent duty S4 - 50 %, 240 V/50 Hz Switchgear sizing For motor operation, reversing contactors (mechanically, electrically and electronically locked) or thyristors (electronically locked) can be used, Actuators without integral controls (AUMA NORM): Switchgear are supplied by the customer. We recommend specification of switchgear suitable for their rated operating power/motor power in compliance with the assigned AUMA power class. Switchgear assignment to AUMA power classes: AUMA power class Reversing contactor Rated operating power according to EN 60947-4-1 AC-3 A1 A2 A3 A4 A5 A6 400 V AC 4.0 kW 7.5 kW 15 kW 30 kW 55 kW 75 kW Reversing contactor Motor power according to UL/CSA at 480 V AC 5.0 hp 10 hp 20 hp 60 hp 75 hp 100 hp 600 V AC 5.0 hp 10 hp 25 hp 60 hp 100 hp 125 hp Actuators with AM or AC integral controls: Required switchgear in power classes A1 – A3 are directly integrated in AM or AC controls. For switchgear of power classes A4 – A6, a control box is additionally required. We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document. Y006.836/003/en Issue 1.15 Page 2/2