MAIN BUS BARs SHALL BE SUITABLLY

advertisement
OK
TPN
MCB
TPN
MCB
TPN
MCB
R
Y
TPN
MCB
B
TPN
MCB
DLM
EM 6400
SPRING
CHARGED
EMERGENCY PUSH BUTTON
ON OFF TRIP
TRIP
CKT. HEALTHY
SPRING
CHARGED
AUTO/MANUAL
SELECTOR SWITCH
F5
63A TPN
MCB 10 KA
F6
F7
F8
63A TPN
MCB 10 KA
63A TPN
MCB 10 KA
B
0-500 Amp
400 A TPN
MCCB 36 KA
TRIP
CKT. HEALTHY
AUTO/MANUAL
SELECTOR SWITCH
500 A, TPN, 415 V, 50 Hz, ALUMIN IUM BUSBAR, SUITABLE FOR 50 KA FOR 1 SEC.
63A TPN
MCB 10 KA
Y
0-500 V
DLM
EM 6400
400/5A
10 VA CL-1
0-500 Amp
EMERGENCY PUSH BUTTON
ON OFF TRIP
F4
R
TPN
MCB
0-500 V
400/5A
10 VA CL-1
400 A TPN
MCCB 36 KA
500 A, TPN, 415 V, 50 Hz, ALUMIN IUM BUSBAR, SUITABLE FOR 50 KA FOR 1 SEC.
F9
63A TPN
MCB 10 KA
F10
63A TPN
MCB 10 KA
F11
63A TPN
MCB 10 KA
63A TPN
MCB 10 KA
F12
F13
63A TPN
MCB 10 KA
F14
63A TPN
MCB 10 KA
63A TPN
MCB 10 KA
F15
F16
F17
F18
F19
F20
F21
F22
F23
F1
63A TPN
MCB 10 KA
F2
63A TPN
MCB 10 KA
1
F3
63A TPN
MCB 10 KA
63A TPN
MCB 10 KA
F4
F5
63A TPN
MCB 10 KA
F6
63A TPN
MCB 10 KA
F7
63A TPN
MCB 10 KA
F8
63A TPN
MCB 10 KA
F9
63A TPN
MCB 10 KA
F10
63A TPN
MCB 10 KA
F11
63A TPN
MCB 10 KA
F12
63A TPN
MCB 10 KA
63A TPN
MCB 10 KA
F13
F14
63A TPN
MCB 10 KA
63A TPN
MCB 10 KA
F15
F16
63A TPN
MCB 16 KA
63A TPN
MCB 16 KA
F17
63A TPN
MCB 16 KA
F18
63A TPN
MCB 16 KA
F19
63A TPN
MCB 16 KA
F20
63A TPN
MCB 16 KA
INCOMING ELECTRICAL POWER SUPPLY DETAIL ARE AS FOLLOWS.
UTILIZATION VOLTAGE 415 V , 3 PHASE , 4 WIRE , 50 Hz
NEUTRAL ARRANGMENT SOLIDLY GROUNDED
2
3
MAIN LT PANEL SHALL BE SINGLE FRONT, FLOOR MOUNTED WITH PROVISION FOR TOP CABLE ENTRY .
INCOMERS (ACB) SHALL BE WITH MICRO PROCESSOR BASED PROTECTION.
4
INCOMERs BREAKERS (EB & DG SUPPLY) SHALL BE ELECTRICALLY & MECHANICALLY INTERLOCKED.
5
6
ALL ACB SHALL BE PROVIDED WITH OPERATION COUNTER. ALL ACB & MCCB SHALL BW WITH THERMAL MAGNETIC RELEASE,
O/C, E/F & S/C PROTECTION
AUXILIARY POWER SUPPLY SHALL BE AS FOLLOWS , ALL EQUIPMENT SHALL BE RATED FOR 230 VAC & 24 VDC CONTINUES OPERATION
7
SWITCHGEAR ANTI-CONDENSATION HEATER SUPPLY SHALL BE 230 VAC.
8
MAIN BUS BARs SHALL BE SUITABLLY-PVC SLEEVED ELECTROLYTIC ALUMINIUM. VENDOR TO PROVIDE THE BUSBAR CALCULATIONS.
SERVICE
1
INCOMING ELECTRICAL POWER SUPPLY DETAIL ARE AS FOLLOWS.
UTILIZATION VOLTAGE 415 V , 3 PHASE , 4 WIRE , 50 Hz
2
MAIN LT PANEL SHALL BE SINGLE FRONT, FLOOR MOUNTED WITH PROVISION FOR TOP CABLE ENTRY .
3
4
5
6
7
8
9
11
LEGEND
INCOMERS (ACB) SHALL BE WITH MICRO PROCESSOR BASED PROTECTION.
SYMBOL
INCOMERs BREAKERS (EB & DG SUPPLY) SHALL BE ELECTRICALLY & MECHANICALLY INTERLOCKED.
ALL ACB SHALL BE PROVIDED WITH OPERATION COUNTER. ALL ACB & MCCB SHALL BW WITH THERMAL MAGNETIC RELEASE,
O/C, E/F & S/C PROTECTION
AUXILIARY POWER SUPPLY SHALL BE AS FOLLOWS , ALL EQUIPMENT SHALL BE RATED FOR 230 VAC & 24 VDC CONTINUES OPERATION
SERVICE
VOLTS
ACB CLOSING
230
AC
EXTERNAL AC SUPPLY UNIT
ACB TRIPPING
230
AC/DC SUPPLY POWER DERIVED FROM
AC
EXTERNAL AC SUPPLY UNIT
SPRING
CHARGED MOTOR
230
AC
EXTERNAL AC SUPPLY UNIT
INDICATION
230
AC
EXTERNAL AC SUPPLY UNIT
AUX. RELAYs &
CONTACTORs
230
AC
EXTERNAL AC SUPPLY UNIT
R Y B
DESCRIPTION
9
RYB INDICATION LAMP (LED TYPE)
11
14
15
16
SUPPLY POWER DERIVED FROM
AC
EXTERNAL AC SUPPLY UNIT
AC
EXTERNAL AC SUPPLY UNIT
230
AC
EXTERNAL AC SUPPLY UNIT
230
AC
EXTERNAL AC SUPPLY UNIT
230
AC
EXTERNAL AC SUPPLY UNIT
LEGEND
SYMBOL
24 VDC SUPPLY UNIT SHALL BE PART OF MAIN LT PANEL
R Y B
ON
OFF
TRIP
DESCRIPTION
RYB INDICATION LAMP (LED TYPE)
ON, OFF, TRIP INDICATION LAMPS
DIRECT SUPPLY TO PANEL.
CT & PT RATING AND CHARACTERISTICS SHALL BE CONFIRMED BY THE SWITCHGEAR VENDOR
MOULDED CASE CIRCUIT BREAKER
THE SWITCHGEAR VENDOR SHALL BE RESPONSIBLE FOR THE COMPLETE DESIGN AS DETAILED IN THE SPECIFICATION .
RELEVENT STADARDS AND GOOD ENGINEERING PRACTICE.
12
ON
OFF
TRIP
13
ON, OFF, TRIP INDICATION LAMPS
14
DIRECT SUPPLY TO PANEL.
MAIN BUS BARs SHALL BE SUITABLLY-PVC SLEEVED ELECTROLYTIC ALUMINIUM. VENDOR TO PROVIDE THE BUSBAR CALCULATIONS.
MOULDED CASE CIRCUIT BREAKER
CT & PT RATING AND CHARACTERISTICS SHALL BE CONFIRMED BY THE SWITCHGEAR VENDOR
MINITURE CIRCUIT BREAKER
LOCAL/REMOTE (AUTO/MANUAL) SELECTOR SWITCH SHALL BE PROVIDED AS KEY OPERATED TYPE.
DLM-1
PANELS SHALL HAVE DOUBLE CONNECTION BODY EARTHING BY ALLUMINIUM EARTHING STRIP.
CT, RELAY, METERING, LAMPS ETC. SHOWN ARE INDICATIVE AND MINIMUM. CT, AUX RELAYS, METERS, INDICATING LAMPS,
SHALL BE PROVIDED.
EB INCOMER & BUS COUPLER ARE 4 POLE , DG INCOMERS ARE 4 POLE AND OUT GOING FEEDERS ARE TPN.
ALL MCB SHALL HAVE MINIMUM BREAKING CAPACITY 10 KA.
17
THE ABOVE SYSTEM CONSISTING OF AUTO CHANGE OVER BETWEEN EB & DG SUPPLY USING PLC
A
V
17
MCCB SHALL BE PROVIDED WITH FACILITIES FOR PADLOCKING IN THE "OFF" POSITION.
17
MCCB SHALL BE INTERLOCKED TO PREVENT THE COMPARTMENT DOOR BEING OPENED UNLESS THE MCCB IS IN THE OPEN POSITION.
17
ALL MCCB SHALL HAVE ADJUSTABLE THERMAL MAGNETIC RELEASE.
MINITURE CIRCUIT BREAKER
LOCAL/REMOTE (AUTO/MANUAL) SELECTOR SWITCH SHALL BE PROVIDED AS KEY OPERATED TYPE.
PANELS SHALL HAVE DOUBLE CONNECTION BODY EARTHING BY ALLUMINIUM EARTHING STRIP.
15
CT, RELAY, METERING, LAMPS ETC. SHOWN ARE INDICATIVE AND MINIMUM. CT, AUX RELAYS, METERS, INDICATING LAMPS,
SHALL BE PROVIDED.
16
EB INCOMER & BUS COUPLER ARE 4 POLE , DG INCOMERS ARE 4 POLE AND OUT GOING FEEDERS ARE TPN.
17
ALL MCB SHALL HAVE MINIMUM BREAKING CAPACITY 10 KA.
DIGITAL LOAD MANAGER ONLY TO
INDICATE AMPER & kW RATING
DIGITAL AMMETER
DIGITAL VOLTMETER
CURRENT TRANSFORMER (CT)
17 EACH VERTICAL SECTION SHALL BE PROVIDED WITH MAXIMUM 3 NOS. OF OUTGOING FEEDERS IN MCCB/SDF AND 2 NO FEEDER
CABLE GLAND
17 CT RATING & CHARACTERISTICS SHALL BE CONFIRMED BY SWITHGEAR VENDOR.
SPARE FEEDER
17 ON/ OFF/ TRIP INDICATION SHALL BE CONNECTED THROUGH ADD ON BLOCK
DLM-1
A
V
17 THE ABOVE SYSTEM CONSISTING OF AUTO CHANGE OVER BETWEEN EB & DG SUPPLY USING PLC
THE SWITCHGEAR VENDOR SHALL BE RESPONSIBLE FOR THE COMPLETE DESIGN AS DETAILED IN THE SPECIFICATION .
RELEVENT STADARDS AND GOOD ENGINEERING PRACTICE.
17
17
AC/DC
230
230
INDICATION
AUX. RELAYs &
CONTACTORs
24 VDC SUPPLY UNIT SHALL BE PART OF MAIN LT PANEL
SWITCHGEAR ANTI-CONDENSATION HEATER SUPPLY SHALL BE 230 VAC.
DIGITAL LOAD MANAGER ONLY TO
INDICATE AMPER & kW RATING
DIGITAL AMMETER
DIGITAL VOLTMETER
17 MCCB SHALL BE PROVIDED WITH FACILITIES FOR PADLOCKING IN THE "OFF" POSITION.
12
13
VOLTS
ACB CLOSING
ACB TRIPPING
SPRING
CHARGED MOTOR
NEUTRAL ARRANGMENT SOLIDLY GROUNDED
INSTRUMENTATION
A
V
LM
CC
TC
MDO
EDO
ASS
VSS
LVM
17 MCCB SHALL BE INTERLOCKED TO PREVENT THE COMPARTMENT DOOR BEING OPENED UNLESS THE MCCB IS IN THE OPEN POSITION.
CURRENT TRANSFORMER (CT)
17 ALL MCCB SHALL HAVE ADJUSTABLE THERMAL MAGNETIC RELEASE.
AMMETER
VOLTMETER
LOAD MANAGER
CLOSING COIL
TRIPPING COIL
MANUAL DRAW OUT
ELECTRICAL DRAW OUT
AMMETER SELECTOR SWITCH
VOLTMETER SELECTOR SWITCH
LINE VOLTAGE MONITOR
17 EACH VERTICAL SECTION SHALL BE PROVIDED WITH MAXIMUM 3 NOS. OF OUTGOING FEEDERS IN MCCB/SDF AND 2 NO FEEDER
CABLE GLAND
17 CT RATING & CHARACTERISTICS SHALL BE CONFIRMED BY SWITHGEAR VENDOR.
17 ON/ OFF/ TRIP INDICATION SHALL BE CONNECTED THROUGH ADD ON BLOCK
17
SPARE FEEDER
PANEL SHALL BE SUITABLE FOR FUTURE EXTENSION FROM BOTH SIDE OF THE PANEL
Date:
Project:
PANEL SHALL BE SUITABLE FOR FUTURE EXTENSION FROM BOTH SIDE OF THE PANEL
GFC
Date:
Project:
AUDITORIUM WORKS AT
SUKAST , JAMMU
HVAC PANELPDS/ELE/HVAC-1/15-16/004
SCHEMATIC DIAGRAM
AUDITORIUM WORKS AT
SUKAST , JAMMU
HVAC PANELPDS/ELE/HVAC-1/15-16/005
SCHEMATIC DIAGRAM
29.03.2016
AJAY MENGI & ASSOCIATES Scale:
ARCHITECTS , INTERIOR
DESIGNERS & PLANNERS
GANDHI NAGAR,
AMMETER
VOLTMETER
LOAD MANAGER
CLOSING COIL
TRIPPING COIL
MANUAL DRAW OUT
ELECTRICAL DRAW OUT
AMMETER SELECTOR SWITCH
VOLTMETER SELECTOR SWITCH
LINE VOLTAGE MONITOR
HVAC PANEL-2 SCHEMATIC DIAGRAM
HVAC PANEL-1 SCHEMATIC DIAGRAM
GFC
INSTRUMENTATION
A
V
LM
CC
TC
MDO
EDO
ASS
VSS
LVM
POWER DISTRIBUTION SYSTEM
F-261,INDUSTRIAL AREA
PHASE-8B,MOHALI,PUNJAB,160059
NTS
Drawn By:
KUSHAL
TPN
MCB
TPN
MCB
R
Y
B
TPN
MCB
0-500 V
DLM
EM 6400
250/5A
10 VA CL-1 3
0-300 Amp
250 A TPN
MCCB 36 KA
EMERGENCY PUSH BUTTON
ON OFF TRIP
SPRING
CHARGED
TRIP
CKT. HEALTHY
AUTO/MANUAL
SELECTOR SWITCH
500 A, TPN, 415 V, 50 Hz, ALUMIN IUM BUSBAR, SUITABLE FOR 50 KA FOR 1 SEC.
F1
F2
F3
F4
63A TPN
MCB 10 KA
1
63A TPN
MCB 10 KA
63A TPN
MCB 10 KA
F5
63A TPN
MCB 10 KA
F6
63A TPN
MCB 10 KA
F7
63A TPN
MCB 10 KA
F8
63A TPN
MCB 16 KA
63A TPN
MCB 16 KA
INCOMING ELECTRICAL POWER SUPPLY DETAIL ARE AS FOLLOWS.
UTILIZATION VOLTAGE 415 V , 3 PHASE , 4 WIRE , 50 Hz
NEUTRAL ARRANGMENT SOLIDLY GROUNDED
2
MAIN LT PANEL SHALL BE SINGLE FRONT, FLOOR MOUNTED WITH PROVISION FOR TOP CABLE ENTRY .
3
INCOMERS (ACB) SHALL BE WITH MICRO PROCESSOR BASED PROTECTION.
4
INCOMERs BREAKERS (EB & DG SUPPLY) SHALL BE ELECTRICALLY & MECHANICALLY INTERLOCKED.
5 ALL ACB SHALL BE PROVIDED WITH OPERATION COUNTER. ALL ACB & MCCB SHALL BW WITH THERMAL MAGNETIC RELEASE,
O/C, E/F & S/C PROTECTION
6 AUXILIARY POWER SUPPLY SHALL BE AS FOLLOWS , ALL EQUIPMENT SHALL BE RATED FOR 230 VAC & 24 VDC CONTINUES OPERATION
SERVICE
7
VOLTS AC/DC SUPPLY POWER DERIVED FROM
ACB CLOSING
230
AC
EXTERNAL AC SUPPLY UNIT
ACB TRIPPING
230
AC
EXTERNAL AC SUPPLY UNIT
SPRING
CHARGED MOTOR
230
AC
EXTERNAL AC SUPPLY UNIT
INDICATION
230
AC
EXTERNAL AC SUPPLY UNIT
AUX. RELAYs &
CONTACTORs
230
AC
EXTERNAL AC SUPPLY UNIT
SYMBOL
R Y B
ON
MAIN BUS BARs SHALL BE SUITABLLY-PVC SLEEVED ELECTROLYTIC ALUMINIUM. VENDOR TO PROVIDE THE BUSBAR CALCULATIONS.
9
CT & PT RATING AND CHARACTERISTICS SHALL BE CONFIRMED BY THE SWITCHGEAR VENDOR
11
LEGEND
24 VDC SUPPLY UNIT SHALL BE PART OF MAIN LT PANEL
OFF
TRIP
DESCRIPTION
RYB INDICATION LAMP (LED TYPE)
ON, OFF, TRIP INDICATION LAMPS
SWITCHGEAR ANTI-CONDENSATION HEATER SUPPLY SHALL BE 230 VAC.
8
DIRECT SUPPLY TO PANEL.
THE SWITCHGEAR VENDOR SHALL BE RESPONSIBLE FOR THE COMPLETE DESIGN AS DETAILED IN THE SPECIFICATION .
RELEVENT STADARDS AND GOOD ENGINEERING PRACTICE.
MOULDED CASE CIRCUIT BREAKER
12
13
MINITURE CIRCUIT BREAKER
LOCAL/REMOTE (AUTO/MANUAL) SELECTOR SWITCH SHALL BE PROVIDED AS KEY OPERATED TYPE.
14
PANELS SHALL HAVE DOUBLE CONNECTION BODY EARTHING BY ALLUMINIUM EARTHING STRIP.
15
CT, RELAY, METERING, LAMPS ETC. SHOWN ARE INDICATIVE AND MINIMUM. CT, AUX RELAYS, METERS, INDICATING LAMPS,
SHALL BE PROVIDED.
16
EB INCOMER & BUS COUPLER ARE 4 POLE , DG INCOMERS ARE 4 POLE AND OUT GOING FEEDERS ARE TPN.
17
ALL MCB SHALL HAVE MINIMUM BREAKING CAPACITY 10 KA.
DLM-1
A
17 THE ABOVE SYSTEM CONSISTING OF AUTO CHANGE OVER BETWEEN EB & DG SUPPLY USING PLC
V
DIGITAL LOAD MANAGER ONLY TO
INDICATE AMPER & kW RATING
DIGITAL AMMETER
DIGITAL VOLTMETER
17 MCCB SHALL BE PROVIDED WITH FACILITIES FOR PADLOCKING IN THE "OFF" POSITION.
17 MCCB SHALL BE INTERLOCKED TO PREVENT THE COMPARTMENT DOOR BEING OPENED UNLESS THE MCCB IS IN THE OPEN POSITION.
CURRENT TRANSFORMER (CT)
17 ALL MCCB SHALL HAVE ADJUSTABLE THERMAL MAGNETIC RELEASE.
17 EACH VERTICAL SECTION SHALL BE PROVIDED WITH MAXIMUM 3 NOS. OF OUTGOING FEEDERS IN MCCB/SDF AND 2 NO FEEDER
17 CT RATING & CHARACTERISTICS SHALL BE CONFIRMED BY SWITHGEAR VENDOR.
17 ON/ OFF/ TRIP INDICATION SHALL BE CONNECTED THROUGH ADD ON BLOCK
17
CABLE GLAND
SPARE FEEDER
INSTRUMENTATION
A
V
LM
CC
TC
MDO
EDO
ASS
VSS
LVM
AMMETER
VOLTMETER
LOAD MANAGER
CLOSING COIL
TRIPPING COIL
MANUAL DRAW OUT
ELECTRICAL DRAW OUT
AMMETER SELECTOR SWITCH
VOLTMETER SELECTOR SWITCH
LINE VOLTAGE MONITOR
PANEL SHALL BE SUITABLE FOR FUTURE EXTENSION FROM BOTH SIDE OF THE PANEL
HVAC PANEL-3 SCHEMATIC DIAGRAM
Date:
Project:
GFC
AUDITORIUM WORKS AT
SUKAST , JAMMU
HVAC PANELPDS/ELE/HVAC-1/15-16/006
SCHEMATIC DIAGRAM
AJAY MENGI & ASSOCIATES Scale:
ARCHITECTS , INTERIOR
DESIGNERS & PLANNERS
GANDHI NAGAR,
Drawn By:
29.03.2016
NTS
KUSHAL
POWER DISTRIBUTION SYSTEM
F-261,INDUSTRIAL AREA
PHASE-8B,MOHALI,PUNJAB,160059
AJAY MENGI & ASSOCIATES
Scale:
ARCHITECTS , INTERIOR
DESIGNERS & PLANNERS
GANDHI NAGAR,
Drawn By:
29.03.2016
NTS
KUSHAL
POWER DISTRIBUTION SYSTEM
F-261,INDUSTRIAL AREA
PHASE-8B,MOHALI,PUNJAB,160059