FastNet RTU Flexible Data Concentrator & Remote Terminal Unit Automation solution for energy networks Robust and compact design Quick and easy configuration Expandable I/O Multiple protocols: DNP3, IEC 60870-5-104, IEC 60870-5-101, Modbus RTU Protocol conversions Log for 1000 events Port forwarding Telnet support for remote management FTP firmware upgrades Real time clock for time stamping 18 digital and 8 analogue inputs, 14 digital outputs Energy Network Automation RTU for real time process monitoring and data collection The FastNet is a compact RTU for energy network automation. It can be used for both data acquisition and tele­control and also works as ­protocol converter and gateway. Fully Configurable I/O Digital outputs The 14 digital outputs can be assigned individually or in pairs. Select before execute (SBE) mode is available when an additional level of security is needed to prevent erroneous operations. It can be disabled to minimise communication to the units when a narrow band medium is deployed. The digital outputs support both the pulse and persistent modes. The pulse times are individually configurable. Digital inputs The 18 digital inputs can be assigned individually or in pairs. When they are paired, on and off delays can be configured such that the RTU will not transmit the intermediate state when the circuit breaker moves from one end position to the other. Typical Application Areas • Medium voltage dis­connectors • Secondary substations, ring main units • District heating • Pumping stations • Pole mounted reclosers • Ring main units • Diesel generator • Cathodic protection • Solar farms • Wind farms • District heating/cooling • Pump Stations • Biomass generation Chatter control can be used to prevent an input from continuously sending change-of-state messages when connected to faulty equipment. Thus a single RTU cannot overload the communication channel. Digital outputs (14) Analog inputs (8) Analog inputs The 8 analog inputs have selectable sampling times and support a dead­ band, which reduces data traffic without compromising performance. A dip switch allows the user to select between voltage- and current-based measurement modes. The inputs can be used for both AC and DC signals. The analog measurements can be averaged over configurable time periods. Both scaling and offsets can be applied. Versatile Communication The FastNet supports a number of communication options. It has one RS‑485 connection, five RS‑232 ports and an RJ45 port for 10/100 Ethernet. One RS-232 port is reserved for service and support and another, on the front (top) panel, for configuration. The FastNet can handle both Digital inputs (18) Config. RS-232 Mains present input polled and event-triggered (or “report by exception”) communication. Thus a background health poll routine can be supplemented with event-triggered reporting. The individual inputs may have different classes assigned to them depending on whether they are to be detected only during a health poll or also when they change. Port forwarding is available for all the serial ports. It allows traffic to/from the SCADA port to be sent transparently through the RTU from/to a slave device. Data Radio Option The Fast Net RTU can be supplied with the PDR data radio as a fully integrated Interfaces The inputs and outputs have LED indicators. They are connected via removable screw terminals, which make the isolation and removal of a FastNet RTU very simple and quick. Quick Setup, Upgrades & Expansion Rbus I/O expansion Earth Power (9...30 VDC) RS-485 Memory card Dipswitch LEDs (Tx/Rx) RS-232 female (2) RS-232 male (2) LEDs (Tx/Rx) Ethernet telemetry solution. The PDR data radio is a wide area device supporting a fixed mesh configuration to allow communication coverage over several 100's of Km2. Support for key SCADA protocols The FastNet supports the most common SCADA protocols. The serial IEC 60870‑5‑101 and Modbus RTU, the IP-based IEC 60870-5-4‑104 and both the serial and IP transport of DNP3 are available. The FastNet is configured either via the RS-232 configuration port or with Telnet over an Ethernet connection. The user interface with its clear menu structure makes the process straightforward. The FastNet has an SD memory card slot, which can be used to store the entire configuration. It makes the setup easy. Replacing units is as simple as swapping a memory card from one FastNet to the next. A large number of FastNet units can be mass configured with a ready made master configuration file, ported via SD cards. The memory card can also be used to store an event log, allowing the analysis of “sequence of events” data. Multiple firmware upgrade options The firmware can be upgraded through: • the serial configuration port, • FTP (File Transfer Protocol), • an SD card or • a separate TFTP (Trivial File Transfer Program) server. Easy I/O expansion Modbus RTU Master support The FastNet may be used as a Modbus RTU master for up to 5 slave RTUs. Six FastNet units can therefore be daisychained for additional I/O. For SCADA communication Modbus RTU can then be converted to one of the other supported protocols. 16DO 16DI 16DO 16DI 16DO 16DI 16DO 16DI 16DO 16DI The FastNet is designed to support not only daisy chaining based on the Modbus RTU Master functionality, but also additional, “extended I/O” modules. One option is to connect a maximum of ten RTU-16D cards to the FastNet through the Rbus interface. Each card has 16 digital inputs and 16 digital outputs. This puts the maximum of digital inputs at 178 and that of digital outputs, at 174. SCADA Rbus expansion Modbus expansion 16DI 16DO 16DI 16DO 16DI 16DO 16DI 16DO 16DI 16DO FastNet RTU for real time monitoring and data collection Number of analog Inputs: 8 • 5 RS‑232 • 1 Rbus • 1 RS‑485 • 1 Ethernet, 100 Mbps • Input range: −10...+10 V 0...10 V 0...20 mA −5...+5 V −20...+20 V possible on request • Isolation: 2.5 kV Isolation • Ethernet to earth: 1.5 kV • RS‑485 to earth: 1.5 kV Protocols • IEC 60870-5-101 • IEC 60870-5-104 • DNP3 • Modbus RTU Number of digital inputs: 18, expandable up to 178 • Voltage input: 9 ... 70 VDC • Optical isolation: 4 kV • Input impedance: 10 kΩ • Functions: pulse counting, on delay, off delay, time stamp Compliance • Radiated disturbance: EN 55022:1998, -A1:2000, -A2:2003 Class B • Electrostatic discharge: EN 61000‑4‑2:1995 • Radio frequency electromagnetic field: EN 61000-4-3:1997 • Fast transients: EN 61000-4-4:1995 • Induced radio frequency field: EN 61000-4-6:1996 • Power frequency magnetic field: EN 61000-4-8:1994 Number of digital outputs: 14, expandable up to 174 Outputs 1–10 • Max. rated current: 2 A • Voltage: 125 VAC, 60 VDC • Power, resistive: 62.5 VA, 30 W • Isolation: 1.0 kV Outputs 11–14 • Max. rated current: 3 A • Voltage: 250 VAC, 130 VDC • Power, resistive: 50 VA, 60 W • Power, inductive: 25 VA, 30 W • Isolation: 1.0 kV (1.5 kV for select before execute mode) www.netcontrol.com Energy Network Automation © Netcontrol Group 2015 • Housing: extruded and diecast aluminium • Dimensions: (H × W × D) 217 mm × 146 mm × 63 mm • Weight: 1250 g • Temperature: −40...+75°C • Relative humidity: 0...95% non­ condensing • Input voltage: 9...30 VDC • Current consumption: depends on input voltage; typically 0.1...0.3 A • Power consumption: max. 7.3 W; typical 2.5 W • Processor type: ColdFire 32-bit • Internal RAM memory: 64 kB • Internal flash memory: 512 kB • External RAM memory: 8 MB • External flash memory: 4 MB • Memory card (optional): SD, minimum size 1 GB Communication interfaces M00108-BR-EN-5 Technical Specifications