Bulletin 190-M Compact Starters

Bulletin 190-M Compact Starters
Selection Guide
Bulletin 190-M
Compact Starters
Selection Guide
3
Bulletin 190-M
• Compact Design to
45mm Wide
• Common Adapter for
Panel or DIN Rail
Mounting
• Pre-Wired Assembly
• All Control Terminations
Located on Load Side of
Starter
• Load Side Coil Terminal
Exposed for Ease of
Wiring and Accessory
Installation
• Provision for Bul. 100-C
and 140 Accessories
TABLE OF CONTENTS
Description
Page
Product Selection
Compact Starters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Description
Page
Dimensions
Compact Starters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Description
Bulletin 190-M Compact Starters are ideal for use in direct-on-line or group motor
installations. These compact starters are prewired and assembled, 45mm wide, can
be panel- or DIN Rail-mounted and will accept a wide range of MCS accessories.
Conformity to Standards:
Approvals:
IEC 947-4
CE
CSA 22.2 No. 14
CSA Certified (File: LR13908)
Your order must include:
UL 508
UL Listed (File: E 14841)
• Cat. No. of the compact starter and
protector selected.
•
with coil code
•
auxiliary configuration
• If required, Cat. No. of any
accessories.
2
Bulletin 190-M
Compact Starters
Product Selection
Type 1 Protection
• Auxiliary contact connected to terminals on the bottom
• Utilizes accessories of Bulletin 140-M Manual Motor Starter/Protectors & 100-C Contactors
• Mounting Options:
• Screw fixing
• Fixing on one or two 35mm DIN Rails
• Fixing on one 75mm DIN Rail
Type “1” short circuit coordination according to IEC 947-4-1➊
Conditional rated short-circuit current (Iq) = Ultimate short-circuit breaking capacity (Icu)
Voltages: please inquire about other voltages
Ratings AC-2, AC-3
3∅(50Hz)
[kW]
3∅(60Hz)➋
[HP]
Thermal
Release
Magnetic
Release
Icu without
Current
Limiter
Icu with
Current
Limiter
Direct-on-line Starter
400V
230V
460V
575V
[A]
[A]
[kA]
[kA]
Catalog No. ⊗ ➌ - ➍
0.02
—
—
—
0.10...0.16
1.8
100
—
190-M2-A16⊗10-A10
0.04
—
—
—
0.16...0.25
2.8
100
—
190-M2-A25⊗10-A10
0.06/0.09
—
—
—
0.25...0.40
4.4
100
—
190-M2-A40⊗10-A10
0.09/0.12
—
—
—
0.40...0.63
6.9
100
—
190-M2-A63⊗10-A10
0.18/0.37
—
1/2
1/2
0.63...1.00
11
100
—
190-M2-B10⊗10-A10
0.37/0.55
—
3/4
1
1.00...1.60
18
100
—
190-M2-B16⊗10-A10
0.55/0.75
1/2
1
1-1/2
1.60...2.50
28
100
—
190-M2-B25⊗10-A10
1.1/1.5
1
1
3
2.50...4.00
44
100
—
190-M1-B40⊗10-A10
2.2/2.5
1-1/2
3
5
4.00...6.30
69
100
—
190-M1-B63⊗10-A10
3.0/5.5
3
5
7-1/2
6.30...10.0
110
20
50
190-M1-C10⊗10-A10
5.5/7.5
5
10
10
10.0...16.0
176
10
50
190-M1-C16⊗10-A10
7.5/10
5
10
10
16.0...20.0
220
8
50
190-M1-C25⊗10-A10
11/12.5
7-1/2
15
15
20.0...25.0
275
8
50
190-M1-C25⊗10-A10
❋
➊The Bulletin 140 Manual motor Starter/Protector is a component of the 190-M Compact Starter and meets the circuit breaker requirements of
IEC 947-2. This device, however, does not meet CSA and UL circuit breaker requirements. The Bulletin 140 is CSA Certified and UL Listed as
a Manual Motor Controller and is rated for Group Motor Installations.
➋ For North American applications: HP ratings shown in the table are for reference. The final selection of the motor starter depends on the actual
motor full load current and service factor as follows.
• For motor with service factor of 1.15, or greater: Use motor nameplate full load current and choose the motor starter with the appropriate
current range. Example: Motor F.L.C. = 4.2A; S.F. = 1.15. Select Cat. No. 190-M1-B63⊗10-A10.
• For motor with service factor less than 1.15: Multiply motor nameplate full load current by 0.9 and use the resulting value to choose the motor
starter with the appropriate current range. Example: motor F.L.C. = 4.2A; S.F. = 1.0; 4.2A x 0.9 = 3.78A. Select Cat. No. 190-M1-B40⊗10A10.
➌ Auxiliary contacts for contactor
⊗ Standard Voltage Codes for AC Control
Option
01
Contact Configuration
1 N.C.
➍Trip and/or auxiliary contact for manual motor starter/protector
Option
T01
T10
A01
Number of N.O./N.C.
1 N.C.
1 N.O.
1 N.C.
50Hz
24V
–
110V
D
120V
–
60Hz
J
–
D
50/60 Hz
–
–
–
For other control voltage codes, contact your A-B sales office.
For other auxiliary contacts and accessories, see Pub. No. 0100C-1.0.1
3
❋
Prices – Consult Sales Office or price list
Bulletin 190-M
Compact Starters
Product Selection, Continued
Type 2 Protection
Type “2” short circuit coordination according to IEC 947-4-1 ➊
Conditional rated short-circuit current (Iq) = 50kA
Icu = Ultimate short-circuit breaking capacity
Voltages: please inquire about other voltages
Ratings AC-2, AC-3
3∅ [kW]
(50Hz)
3∅ [HP]
(60Hz)➋
Thermal
Release
Magnetic
Release
Icu
Direct-on-line Starter
400V
230V
460V
575V
[A]
[A]
[kA]
Catalog No. ⊗ ➌ - ➍
0.02
—
—
—
0.10...0.16
1.8
100
190-M2-A16⊗10-A10
0.04
—
—
—
0.16...0.25
2.8
100
190-M2-A25⊗10-A10
0.06/0.09
—
—
—
0.25...0.40
4.4
100
190-M2-A40⊗10-A10
0.09/0.12
—
—
—
0.40...0.63
6.9
100
190-M2-A63⊗10-A10
0.18/0.37
—
1/2
1/2
0.63...1.00
11
100
190-M2-B10⊗10-A10
0.37/0.55
—
3/4
1
1.00...1.60
18
100
190-M2-B16⊗10-A10
0.55/0.75
1/2
1
1-1/2
1.60...2.50
28
100
190-M2-B25⊗10-A10
1.1/1.5
1
1
3
2.50...4.00
44
100
190-M2-B40⊗10-A10
❋
➊The Bulletin 140 Manual Motor Starter/Protector is a component of the 190-M Compact Starter and meets the circuit breaker requirements of
IEC 947-2. This device, however, does not meet CSA and UL circuit breaker requirements. The Bulletin 140 is CSA Certified and UL Listed as
a Manual Motor Controller and is rated for Group Motor Installations.
➋For North American applications: HP ratings shown in the table are for reference. The final selection of the motor starter depends on the actual
motor full load current and service factor as follows.
• For motor with service factor of 1.15 or greater: Use motor nameplate full load current and choose the motor starter with the appropriate
current range. Example: Motor F.L.C. = 4.2A; S.F. = 1.15. Select Cat. No. 190-M1-B63⊗10-A10.
• For motor with service factor less than 1.15: Multiply motor nameplate full load current by 0.9 and use the resulting value to choose the motor
starter with the appropriate current range. Example: motor F.L.C. = 4.2A; S.F. = 1.0; 4.2A x 0.9 = 3.78A. Select Cat. No. 190-M1-B40⊗10A10.
⊗ Standard Voltage Codes for AC Control
➌ Auxiliary contacts for contactor
Option
01
Contact Configuration
1 N.C.
➍Trip and/or auxiliary contact for manual motor starter/protector
Option
T01
T10
A01
Number of N.O./N.C.
1 N.C.
1 N.O.
1 N.C.
24V
–
110V
D
120V
–
60Hz
J
–
D
50/60 Hz
–
–
–
50Hz
For other control voltage codes, contact your A-B sales office.
For other auxiliary contacts and accessories, see Pub. No. 0100C-1.0.1
❋
Prices – Consult Sales Office or price list
4
Bulletin 190-M
Compact Starters
Approximate Dimensions
Mounting Position
5
35x15mm DIN Rail
(1)
(2) 35x7.5mm DIN Rail
75mm DIN Rail
(1)
Dimensions are shown in millimeters. Dimensions are not intended for manufacturing purposes.
Publication 0190M-2.0 - June 1998