TCSC FOR PROTECTION OF TRANSMISSION LINE P.S.Chaudhari#i, #,,3,4 P. P.Kulkarni#2, R.M.Holmukhe#3, Mrs.P.A.Kulkarni #4 #iScientist, DRDO, Pune, India, #2DRDO, Pune, India Bharati Vidyapeeth University College of Engineering, Pune, India. #3 rajeshmholmukhe@hotmail.com, Abstract: A grid of transmission lines operating at high or extra high voltages is required to transmit power from generating stations to load. In addition to transmission lines that carry power from source to load, modern power systems are highly interconnected for economic reasons. The large interconnected transmission networks are prone to faults due to the lightning discharges and reduce insulation strength. Changing loads and atmospheric conditions are unpredictable factors. This may cause overloading of lines due to which voltage collapse takes place. All the above said things are undesirable for secure and economic operation of a line. These problems can be eased by providing sufficient margin of working parameters and power transfer, but it is not possible due to expansion of transmission network. Still the required margin is reduced by introduction of fast dynamic control over reactive and active power by high power electronic controllers. Here my seminar explains the discussion on the effect of this device on protection of transmission line. The TCSC is considered as a dynamical device and its transient process is modeled in order to have the response to disturbances based on its own control strategy. It is shown that not only the TCSC affects the protection of its line, but also the protection of adjacent lines would experience problems. The study is done first analytically by using simple models, then the simllated results of power system and the protective relays in Real Time Digital Simulator (RTDS) are used. Finally, the simulation results are varified by using a commercial relay. The results are reviewed for the study of the impact of TSCS on protection of transmission line Keywords- TCSC, Transmission line I.INTRODUCTION Today, transmission-level voltages are usually considered to be 110 kV and above. Lower voltages such as 66 kV and 33 kV are usually considered sub-transmission voltages but are occasionally used on long lines with light loads. Voltages less than 33 kV are usually used for distribution. Voltages above 230 kV are considered extra high voltage and require different designs compared to equipment used at lower voltages. Overhead transmission lines are uninsulated wire, so design of these lines requires minimum clearances to be observed to maintain safety. Engineers design transmission networks to transport the energy as efficiently as feasible, while at the same time taking into account economic factors, network safety and redundancy. These networks use components such as power lines, cables, circuit breakers, switches and transformers. Failure protection Under excess load conditions, the system can be designed to fail gracefully rather than all at once. Brownouts occur when the supply power drops below the demand. Blackouts occur when the supply fails completely. Rolling blackouts,or load shedding, are intentionally-engineered electrical power outages, used to distribute insufficient power when the demand for electricity outstrips the supply. Communications Operators of long transmission lines require reliable communications for control of the power grid and, often, associated generation and distribution facilities. Fault-sensing protection relays at each end of the line must communicate to monitor the flow of power into and out of the protected line section so that faulted conductors or equipment can be quickly de-energized and the balance of the system restored. Protection of the transmission line from short circuits and other faults is usually so critical that common carrier telecommunications are insufficiently reliable. In remote areas a common carrier may not be available at all. Communication systems associated with a transmission project may use: Microwaves or Power Line Communication. Much analysis is done by transmission companies to determine the maximum reliable capacity of each line, which, due to system stability considerations, may be less than the physical or thermal limit of the line. Deregulation of electricity companies in many countries has led to renewed interest in reliable economic design of transmission networks. Transmission line protection depends upon a core group of protective elements. These elements must be dependable and secure for all power system conditions as any single weakness can cause problems with a relaying scheme. Some common concerns related to a line distance relay are operating speed, load and fault impedance induced element under- and overreach, out-of-step (OOS) conditions, and Capacitive Voltage Transformer (CVT) transients. A major program to develop new technologies for enhancing power transmission has been initiated. This program, named "FACTS' for "Flexible AC Transmission Systems," is intended to provide new systems and methods of operation to help electric utilities get the most from their investments in transmission networks. Scoping studies were conducted in 1989-1990 to identify the benefits of FACTS concepts and to provide direction for the development of hardware systems. One outcome of those studies was to show that a ThyristorControlled Series Compensation (TCSC) system should be developed, as a number of benefits could be achieved in a cost-effective manner [1,3]. What is FACTS? The FACTS technology is a collection of controllers, which can be applied individually or in coordination with others to control one or more of the interrelated system parameters, such as series impedance, shunt impedance, current, voltage, and damping of oscillations. Fig 1. FACTs Controller FACTS controller is defmed as power electronic based system and other static equipment that provide control of one or more AC transmission system parameters. Out of no. of FACTS devices the one which is very efficient is the TCSC. roles in the operation and control of power scheduling power flow; decreasing components; reducing net loss; providing limiting short-circuit currents; mitigating resonance (SSR); damping the power enhancing transient stability. systems, such as unsymmetrical voltage support; sub synchronous oscillation; and Advances in high-power, high-efficiency power electronics have led to the development of thyristor-controlled series compensators in power systems. In contrast to capacitors switched by circuit breakers, TCSC will be more effective because thyristors can offer flexible adjustment, and more advanced control theories can be easily applied. Series capacitor is used in a long distance EHV lines for increasing power transfer. Use of series capacitor is for the most economic enhancing power flow though series have a problem of SSR. Series is only is used for power transfer as compared to shunt. Shunt has the main problem of location not of SSR. To provide variable series compensation thyristor control is used due to which the major problem of SSR is been reduced to much lesser extent. The first demo project of TCSC was done at west Virginia USA. In 1991.in October 1992 l" TCSC was installed at Arizona substation. and then in1993 in Oregon. Series compensation can be achieved in two ways discrete and continuos .Discrete by using TCSC and continuos by using TCSC or GTO. TCSC- thyristor controlled series capacitor Classification of FACTS controllers a) shunt connected b) series connected c) combined series-series d) combined series - shunt Classification of FACTS controllers by use of power devices A) variable impedence type B) voltage source converter based which includes VCS includes i. SVC- static var compensator ii. TCSC- thyristor controlled series capacitor iii. TCPSFthyristor controlled phase shift transformer iv. STATCOM- static synchronous compensator v. SSSC - static synchronous series compensator vi. IPFC- interline power flow controllers vii. UPFC- unified power flow controllers Why TCSC only? There have been significant activities and achievement in the research and application of flexible AC transmission systems (FACTS). Thyristor-controlled series compensation (TCSC) is an important device in the FACTS family. It can have various Fig 2. Basic TCSC diagram Fig 3. TCSC with sries inductor for current control The above two figures shows that TCR is used in parallel with a fixed capacitor to enable continuos control over series compensation. Harmonics are present in thyristor switches can be mitigated by TCSC along with SSR. GCSC is same as shown above only SCR is replaced by a GTO. In between two SCR is more advantageous as it has lower cost. Equivalent circuit of TCSC Xc ~rJ Xtcr ~ < Iter capacitive operation Xc ~r~ Xtc:r ~ Iter ;;. Inductive operation Fig 4. Equivalent circuit ofTCSC Operation of TCSC Ld circuit breaker B capacitor, MOV and bypass switches are used for its protection, while for the TCSC, co-operative operation of MOV, thyristors and bypass switches are applied for a reliable protection. This is the main difference in the behaviour of the' distance relays in the two compensation methods. The apparent impedance seen by the distance relay depends largely on the TCSC mode of operation. The TCSC mode of operation during a fault is not unique and it may transit from a mode to others sequentially; meanwhile the distance relay experiences various apparent impedances in the fault period. In normal operating mode, called capacitive-boost mode or vernier mode, the thyristor are firing properly and the bypass switch is open. From the system point of view, this mode inserts capacitors into the line up to nearly three times the fixed capacitor. TCSC controls fire pulse to change thermistor's fire angle and make TCSC to operate in thyristor blocked mode, thyristor bypassed mode and vernier mode with partial thyristor conduction. The vernier mode let a inductive loop current to flow through capacitor produce a capacitive reactance which is larger than that of fused capacitor. Normally, TCSC's stability fundamental frequency impedance is relative only to fire angle a. When a is between 145 degree and 180 degree ,the equivalent reactance is capacitive, larger a is corresponding to less capacitor reactance. When a is between 90deg and l40deg , the equivalent reactance is inductive, larger a is corresponding to larger inductive reactance. When a fault occurs, TCSC's control system would react swiftly to take some protection ensures. If short circuit current is large enough, MOV would be fired, TCSC's control system would rapidly send its commands to bypass thyristor and make TCSC become inductive. So TCSC's capacitive reactance would decrease and gradually change into inductive reactance. This characteristic makes it possible for distance relay with memory polarizing voltage and proper setting value to be used in TCSC line. If short circuit current is not large enough, TCSC's control system will not send its commands to bypass the thyristors. x A capacitive C B Une cul'tent Fig. 1 Simple power system compensated by TCSC Figure shows a TCSC module with different protective elements [6] in the middle of a simple power system. Basically, it comprises a series capacitor C in parallel with a thyristor-controlled reactor (TCR), Ls. A metal-oxide varistor MOV is connected across the series capacitor to prevent the occurrence of high capacitor over voltages. A circuit breaker is also installed across the TCSC module to bypass it if a severe fault or equipment malfunction occurs. A currentlimiting inductor Ld is incorporated in the circuit to restrict both the magnitude and the frequency of the capacitor current during the capacitor-bypass operation. There are different modes of operation of TCSC in the normal and fault conditions. During a fault, an overvoltage appears across the TCSC due to the fault current. For a conventional series o _--~G Inductive E Fig.2 OIK'>"<UUt<;NIIIJI<Oj'TCSC ~~[h~~~~t~~r:J c :::~u~imum D "" run H)hagc limit Ihyristur F..;:; lirin¥ anale vnit F ::. h!irmonic G = thyri<oto( heating limit current limit TCSC's impedance characteristic become complicated. Considering the situation shown in Fig, substituting TCSC for FSC, if relay l's PT is on line side, it can be used reliably. To relay II, Only if TCSC's capacitive reactance is not larger than a certain value, for example, the set impedance of relay II for phase to phase fault, it can be used reliably. Under normal conditions, the current waveform in TCSC's inductor is symmetrical about zero voltage point of capacitor, capacitor voltage itself is also symmetric, harmonics of voltage at relay and current in line is very little, so TCSC has no influence on protection relay. But when a fault occurs, transient voltage and current's waveform is not Symmetrical, and properly leads to TCSC confusional firing. TCSC's harmonic become very complicated. Harmonic characteristic is relative to compensation degree, fault location, fault time and many other factors. Harmonic components are various, amplitudes are large, and amplitudes don't decrease monotonously. It is very difficult to find accurate regulation for TCSC's harmonics. Fig 7. R-X diagram across the capacitor. The MOV is fast enough to conduct and reset within a half cycle. The MOV would not shortcircuit out the capacitor as the circuit breaker would. This condition is usually very short but may be repeated several times during the fault period. During MOV conduction, Ztcsc is the impedance of the parallel combination of the TCR, capacitor and the MOV in a lower resistance mode.In considering the equivalent MOV circuit proposed in the combination characteristic can be considered as a resistance in series with a boost capacitor (fixed capacitor and the TCR branch). At this moment, the relay overreaches but less than is the case without MOV conduction. (iii) Blocking mode: When the thyristors are not triggered and are kept in nonconducting state, the TCSC is operating in blocking mode. In this mode, the TCSC performs like a fixed series capacitor. When the TCSC detects an overvoltage by the MOV current, the TCR branch stops its firing sequence by a protection function. The process is effective for avoiding the over current of the thyristors or capacitor caused by fluctuation of the firing angle under the condition that the voltage phase of the capacitors changes suddenly. Herein, the equivalent MOV circuit will be the combination of a resistance in series with the fixed series. At this moment the relay overreaches less than is the case with the thyristor-fIring mode. By the process, if the overvoltage and overcurrent are cleared, the system returns to the normal mode, otherwise the energy absorbed in the MOV exceeds its limitation and the TCSC transits from the blocking mode to the bypass mode to protect theMOV and $capacitor. (iv) Bypass mode: In this mode, the thyristors are triggered continuously and the TCR branch conducts in the whole General TCSC ~, {~7 .TC~-j-i 8~~ t Fig. J TCR compensated transmission line Fig 8. General TCSC Fig 8. TCSC modes of operation According to above fig different possible TCSC modes of operation during a fault and the behaviour of the relays can be summarised as follows: (i) Capacitive-boost mode without MOV conduction: For a low fault current, the protection function of the TCSC device does not work; therefore the TCSC remains constantly in its vernier mode of normal operation; i.e. the TCR branch is triggered by its prespecified firing angle. In this case a significant compensation exists, so the conventional distance relay overreaches considerably; or may even lose its directional integrity. (ii) Capacitive-boost mode with MOV conduction: For a high fault current, MOV operates for decreasing the voltage Sample test system arrangement fa 5Ce1X.1Si ~ 11<,.'''' X, lUQ ~ lIQ P:IiW 2!ItIlVA.!pI.! Fig 9. Test system arrangement Simulated results Few simulated results are as follows 40 ,0.03 27(S} 20 o -20 9 '[ I. !' {=;\1~ I' -40 I -60 L o 1 - --- ';0 ..---------0.1 o .'0 T•• 0.3 0.2 Figur4f B. .'0 ~o __ "~. 11.. :L~. H.o'U Results of t!/~ctricQl daITlping COnvt'lO" oJut6far <."O"apuri.-rOIJ.. tt!3t.~ plott4!!d 011 Tim e (s) <' Fig 12. Simulated results 2 10.0327(5) ~ ~ 8 ~ :.:l 0.3 0.2 0.1 Time (s) Fig. 2 Capacitor voltage and line current waveforms in the thyristors-blocked operating mode Fig 10. Simulated results 1749 unil I --. -...--- 111111111111111111111111111 o.oa O~ •••.• 9..," 0.'. o...,~ •..•••• .,••.•• 0.1'" •. ,. cin:k: -I+-----~~~--~~--~ ...1 -0.5 o 0.' Real Fig. 5 Variations in eigenvalues with conduction angle. (OO~ conduction angle a ,; 18(0) '(<.1) impedance F""tg..,Z ~~. ••••~e .,....,....u.,reftl.cut. ..nib bypass la:upeclanc:e conttol 'Versus Fig 11. Simulated results Fig 13. Simulated results Thyristor Conduction angle table for 5 cycles I\~ cycles I o Fig. 6 Wavef'onns O.OS T~me using 0.1 ($) the proposed equations. (ex.-600) 2 3 4 5 Conduction anzles (u, =60u u2-24OO) 60° -108.0° 240° - 289.2° 60° -116.5° 240° - 298.5° 60° -119.1° 240° - 299.6° 60° -120.0° 2400 - 300.0° 60° -120.0° 240u - 300.0u d.ate 40 -~ .. ... ~ ~. - ... - .~ ~---. ,_., _. I 'r- , ._,_. I ······· .. r-..... 20 M • K . ·20 , ; ..• •.. ~OO:-~I~OO--~IIO~~,20~~I~~~I~~L-~I~~~I~~~1~1O~,~ (~) Fig14. Variation ofTCSC reactance with firing angle 'a' Advantages of TCSC Protective distance relays, which make use of impedance measurements in order to determine the presence and location of faults, are "fooled" by installed series capacitance on the line when the presence or absence of the capacitor in the fault circuit is not known a priori. This is because the capacitance cancels or compensates some of the inductance of the line and therefore the relay may perceive a fault to be in its first zone when the fault is actually in the second or third zone of protection. Similarly, first zone faults can be perceived to be reverse faults! Clearly this can cause some costly operating errors. The conventional protections like distance, differential, and by using relays power controllers are very much in use nowadays. In order to meet the high demand for power transmission capacity, some power companies have installed series capacitors on power transmission lines. This allows the impedance of the line to be lowered, thus yielding increased transmission capability. The series capacitor makes sense because it's simple and could be installed for 15 to 30% of the cost of installing a new line, and it can provide the benefits of increased system stability, reduced system losses, and better voltage regulation. 1 Disadvantage of TCSC Employment of series compensation creates certain problems for its protective relays and fault locators using conventional techniques because of the rapid changes introduced by the associated TCSC control actions in primary system parameters such as line impedances and load currents. The most important singularity lays in the fact that the positive sequence impedance measured by traditional distance relays is no longer an indicator of the distance to a fault. The apparent reactance and resistance seen by the relay are affected due to the uncertain variation of series compensation voltage during the fault period. The major benefits include being able to directly schedule power flows along desired paths, to rapidly modulate the effective impedance in response to power swings so that the level of secure power transfer can be increased, and to permit higher levels of conventional series compensation without being restricted by sub synchronous resonance(SSR) aspects Applications of TCSC control There have been studies on TCSC with models of real powt systems. In the US, there are Bonneville Powt Administration (BPA) system American Electric Power (AE system, 345kV Edic-Fraser transmission line in New YOl state system , and Montanatransmission system . Otlu systems include the Southern Brazil interconnected network North-Northeast Brazilian power system, Central Ind transmission corridor, and Queensland-New South Walt power system in Australia. TCSC devices have been installed in the Slatt Kayenta and Kanawha River [SO, 811 substations in the U~ In these TCSC devices, power swing damping control systerr adopt linear schemes and the transient stability contn systems adopt open-loop insertion schemes. In China, TCS' is proposed to be installed in the Yimin-Fengtun 500k' transmission lines at the Fengtun site . Several contn strategies are proposed to increase both the transient stabilit and dynamic performance, including nonlinear control ADRI control and fuzzy control. One of the TCSC plant is locate in Chattisgarh, Raipur in India. Summary There still exist several problems with the engineerin application and implementation of TCSC stability controller Control schemes that have been adopted in real power systerr are usually conventional, such as in the Slatt, Kayenta an Kanawha River substations. In contrast, many scheme proposed in the literature are rather academic and will b impractical. The implementation of TCSC in real powe systems requires not only appropriate control theories, bi also feasibility, the amount of computation and the acquisitio of the input signals. Furthermore, some limitations in re, operation would prevent control schemes reaching expecte performances. As described in Section 2, the operating rang of TCSC will be limited by its own capacity and voltag protection of the MOV. From a purely theoretical point ( view, most studies in the literature do not consider thes limitations. In addition, some schemes require remote inpi signals, even transient variables in distant generators, whic are difficult to be measured and transferred. Therefore, would be very difficult for many control schemes to b implemented in a practical engineering project. Howeve efforts are being made to understand and analyse the problem Conclusion This paper focus on TCSC's influences on protection regior Transmission lines can be compensated by Fixed Serie Capacitors (FSC) or more effectively by Thyristor Controlle Series Capacitors (TCSC) to increase power transfe capability, improve transient stability, reduce transmissio losses, and dampen power system oscillations. However It i certain that TCSC will exert influences on distance relay' ability about reflecting ground resistance and avoiding loa impedance and will have some new requests on filterin performance. All these problems are worth study and ar being studied. TCSC dynamics have a significant impact 0 the power system protection and its transition from a mode t another can create serious problems for the conventional relays like forward overreach, reverse overreach, mis coordination in primary and back-up protection, directional malfunction and adverse effect on distance schemes. The work is in progress toward remedial actions such as adaptive relaying and optimal pilot protection schemes. The results will be reported in future. REFERENCES [I] M. Adamiak and R. Patterson, "Protection requirements for flexible AC transmission systems," in Proc. CIGRE, Paris, France, 1992. [2] T. S. Sidhu, M. Hfuda, and M. S. Sachdev, "Generating relay models for protection studies," IEEE Comput. Appl. Power, vol. II, no. 4, pp. 33-38, Oct. 1998. Mojtaba Khederzadeh received the B.Sc. degree in electrical engineering from [3] Weiguo, W. et al.: 'The impact ofTCSC on distance protection relay' .Proc. Int.Conf. Power System Technology, Powercon'98, 18-21 Aug. 1998, Vol. 1, pp. 382-388,5 Real time digital simulator, RSCAD', Ver. 1.177,2003 6 Larsen, E.V., Clark, K., Miske, S.A. Jr., and Urbanek, J.: [4] N. G. Hingorani, "Future Opportunities for Electric Power Systems," LuncheonSpeech, IEEE PES Summer Power Meeting, San Francisco, CA, July 14, 1987 [5] FACTS controllers in power transmission and distribution by N.K. Padiyar Operation of TCSC A typical configuration of TCSC is shown. It consists of a thyristor-controlled reactor (TCR), parallel capacitor and metal oxide varistor (MOV). TCSC can operate in the capacitive or inductive range. Its operating range is limited by the firing angle of thyristors, the protection of the MOV and the current limitation of capacitors. In real operation, these limitations may affect the performance of control schemes TCSC comprises a capacitor C in parallel with a thyristor Controlled Reactor TCR branch. A metal Oxide Varistor (MOV), essentially a nonlinear resistor, is connected across the capacitor to prevent the occurrence of high capacitor over voltages. The basic scheme of such compensators is shown in Figure. The amount of series compensation in the capacitive operating region is increased (or decreased) by varying the thyristor firing angleQ. The overall impedance of the TCSC is given in equation. figure (2) shows variation of TCSC reactance (XTCSC ) against of the firing angleQ. The TCSC considers three different operation modes; the basic principles of these modes and the switching policy between them are described as follows a- Vernier Mode: In high impedance fault cases, TCSC constantly remains in its vernier mode of normal operation therefore; the protection function of the TCSC does not work. The TCR branch is triggered by its pre-specified firing angle. The TCSC works as variable impedance. b- Block Mode: When the TCSC detects the over-voltage, the TCR Inductive Capacitive branch stops its firing sequence by a protection function. The TCSC works as a series capacitor in parallel with a MOV. The combination characteristic can be considered a resistance series with a capacitor,since the high resistance characteristic is introduced by the MOV. c- Bypass Mode: When the MOV operation is not enough to decrease the capacitor voltage; the TCR branch enters its bypass mode to protect the TCSC. In this mode, the TCR conducts in the whole cycle, and the TCSC device serves as inductance. d- Circuit Breaker bypass: When the energy absorbed in the MOY exceeds its setting, the fault is not cleared within a certain time, the TCSC protection function transits the circuit breaker to bypass mode. Since the series reactor in the circuit breaker is very small.