Wafer Installation Instructions

advertisement
Wafer Installation Instructions
3/16 or 4/16 AWG STW Cable
Tool‐less Adjustable Aircraft Cable
1. Fixture must be installed by qualified electrician.
2. Turn power OFF.
3. Before hanging aircraft cables, inspect for any visible damage like fraying, rust, or kinks. If damage is noticed, dispose of cables. Hang aircraft cable loops from suitable ceiling fastener. Follow local building codes. Be careful not to cut, crimp, or fray aircraft cables. If fixtures are to be exposed to vibration, impact, or abuse, then add safety chain as necessary.
CAUTION: Before installing fixture, please read and follow all safety guidelines found on page 3 of 3 attached.
Page 1 of 3
The Wafer fixture is available in 2, 4, and 6 lamp versions and has been manufactured and tested to provide a safe and simple installation. Strictly follow local building, fire, and electrical codes with respect to installation and placement of these fixtures.
This fixture comes with the following:
Options that may be included:
1 x 4/16 AWG STW Power Cord
1 x Tool‐less Adjustable Aircraft Cable
Either two, four, or six lamps pre‐installed and tested depending on the model purchased.
1 x Unimo™ Universal Mounting Bracket
1 x Occupancy Sensor
1 x Hinged Frame & Wireguard/Lens
Dimming and or Emergency Ballast(s)
6. At fixture splice compartment, connect GREEN ground wires first. Then connect male ballast disconnect located on the end of the power cord to the female ballast disconnect . 7. Double check wiring and then tuck wires neatly into splice compartment and fasten splice plate to fixture.
8. If lamps have not been provided with fixture pre‐assembled, install all lamps.
9. Turn power ON.
4. Align aircraft cable toggle plates parallel and tight to aircraft cable slightly above crimp end and pass through mounting holes located on four corners of the fixture. Once toggle is completely through the hole, turn toggle so that it is parallel with top of fixture across hole and gently let fixture rest on toggle.
5. Splice end of power cord without male plug to the building power. Follow local building and electrical codes. NOTE: If your fixture is a 2‐
lamp model it will have the 3/16 AWG cable. If it is a 4‐lamp model it will have a 4/16 AWG cable and left side 2 lamps may be switched separately from right side 2 lamps. If it is a 6‐lamp model it will have a 4/16 AWG cable and the center 2 lamps may be switched separate from outside 4 lamps.
Cable end showing strain relief, splice plate, ballast disconnect , and
Ground wire.
*Fixture is damp location rated and designed for indoor applications such as warehouses, recreation centers, convention halls, etc.. Do not use in applications that will expose the fixture to water.
CAUTION: Before servicing fixture, please read and follow all safety guidelines found on page 3 of 3 attached.
Wafer Maintenance Instructions
(B)
(A)
(D)
(C)
Ballast Cover Snap
(E)
(F)
Page 2 of 3
(G)
Tabbed End
(H)
1. For ballast maintenance please note the model and type included with your fixture and replace with same or compatible model. 7. Once ballast cover snap has been disengaged from the ballast channel, gently slide the ballast cover to free tabbed end of cover from ballast channel (D).
2. Servicing of this product should only be attempted by a qualified Electrician. Local building, fire, and electrical codes should be followed.
8. Carefully turn the cover over onto the top of the ballast channel to allow inspection and servicing of ballasts (E).
3. Prior to servicing this fixture you must turn power OFF.
9. After servicing of ballasts is complete, reverse steps to re‐assemble.
4. Undo splice plate located at end of power cable connected to fixture body.
10. To service sockets, follow steps 1 through 5, then carefully remove lamps by rotating ¼ turn (F). Next remove reflectors by rotating ¼ turn fasteners 90 degrees (G).
5. To access ballasts, remove ballast cover screw (A). 6. Carefully pull the ballast cover away from fixture body (B) while squeezing together opposite end of fixture channel to release ballast cover snap (C). 11. Remove two screws located on end plate of fixture and carefully pull socket tray away from end plate (H). You may now service sockets. Reverse steps to re‐
assemble.
*Fixture is damp location rated and designed for indoor applications such as warehouses, recreation centers, convention halls, etc.. Do not use in applications that will expose the fixture to water.
NOTICE: LAMPS CONTAIN MERCURY. DISPOSE ACCORDING TO LOCAL, STATE, PROVINCIAL, OR FEDERAL LAWS.
NOTICE: GROUND SCREWS PROVIDED IN PROPER LOCATIONS. DO NOT RELOCATE.
SUITABLE FOR DAMP LOCATIONS /
CONVIENT AUX EMPLACEMENTS
HUMIDES
MINIMUM 900C SUPPLY CONDUCTORS
/ LES FILS D’ALIMENTATION 90°C
MIN.
CAUTION RISK OF FIRE /
ATTENTION –
RISQUE D'INCENDIE
THIS PRODUCT MUST BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE INSTALLATION CODE BY A PERSON FAMILIAR WITH THE CONSTRUCTION AND OPERATION OF THE PRODUCT AND THE HAZARDS INVOLVED.
To reduce the risk of death, personal injury or property damage from fire, electric shock, falling parts, cuts/abrasions, and other hazards please read all warnings and instructions included with and on the fixture box and all fixture labels.
Before installing, servicing, or performing routine maintenance upon this equipment, follow these general precautions.
Installation and service of luminaires should be performed by a qualified licensed electrician.
Maintenance of the luminaires should be performed by person(s) familiar with the luminaire’s construction and operation and any hazard involved. Regular fixture maintenance programs are recommended.
DO NOT INSTALL DAMAGED PRODUCT! This luminaire has been properly packed so that no parts should have been damaged during transit. Inspect to confirm. Any part damaged or broken during or after assembly should be replaced.
These instructions do not purport to cover all details or variations in equipment nor to provide every possible contingency to meet in connection with installation, operation, or maintenance. Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser’s or owner’s purposes, this matter should be referred to J2 Light Inc.
WARNING:
RISK OF FIRE, ELECTRICAL SHOCK, CUTS AND OR OTHER CASUALTY HAZARDS. THIS PRODUCT MUST BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE INSTALLATION CODE BY A PERSON FAMILIAR WITH THE CONSTRUCTION AND OPERATION OF THE PRODUCT AND THE HAZARDS INVOLVED. J2 LIGHT INC. ASSUMES NO RESPONSIBILITY FOR CLAIMS BROUGHT ABOUT BY IMPROPER OR CARELESS INSTALLATION OR HANDLING OF THIS PRODUCT.
ƒ
ƒ
ƒ
ƒ
ƒ
ƒ
READ AND FOLLOW ALL SAFETY INSTRUCTIONS! SAVE THESE INSTRUCTIONS AND DELIVER TO OWNER AFTER INSTALLATION.
Page 3 of 3
Download