RESETTING THE LAE CONTROL TO FACTORY DEFAULT Figure 1 Detail image of LAE Control Display. Note: The case must be powered on to reset the controller settings. 1. Locate the LAE Controller Display on your specific case. located near the compressor. It is typically 2. Hold down both the “i” and the “x” buttons for 5 seconds. The parameter SPL will show on the screen. 3. Tap the “▼” button. The screen will show the rES parameter. 4. Hold down the “i” button. While holding down the button, tap the “▼” to change the setting from “nO” to “YES”, then release the “i” button. 5. Tap the “x” button to return the controller to normal operation. parameters are now returned to the default factory settings. All Should you have any questions call Killion Customer Service at 1-800-421-5352 or email at parts.service@killionindustries.com . Killion Industries, Inc. 1380 Poinsettia Ave., Vista, CA 92081 Phone (760) 727-5102 Toll Free (800) 421-5352 Fax (760) 727-5108 www.killionindustries.com Sales@killionindustries.com parts.service@killionindustries.com PROGRAMMING THE LAE LED Display Codes: dEF = Defrost in progress. hi = High Temperature Alarm E1 = Probe T1 (case temp) failure LED Symbols: = Compressor Relay = Defrost Active = Alarm Lo = Low Temperature Alarm E2 = Probe T2 (evaporator temp) failure = Fan Relay II° = Second Setpoint Active To change the SETPOINT: 1) Hold down the 'i' button. This will show the current SETPOINT. 2) While holding the 'i' button use the '▼' and '▲' to change the SETPOINT. 3) Release the 'i' button to store the new value. To change other settings: 1) Hold down both 'i' and 'x' buttons for 5 seconds. 2) Use the '▼' and '▲' buttons to select the parameter to be modified. 3) Hold down the 'i' button to display the current value. 4) While holding down 'i', use the '▼' and '▲' buttons to set the desired value. 5) Release the 'i' button to store the new value and display the next parameter. 6) To exit the programming mode, tap the 'x' button or wait 30 seconds. Information Menu Codes t1 = case temeprature reading thi = maximum case temp recorded Loc = keyboard lock state t2 = evaporator temperature reading tLo = minimum case temp recorded Information Menu Access 1) To access the menu, tap the 'i' button. 2) Use the '▼' and '▲' buttons to select the data to be displayed. 3) Hold the 'i' button to display the selected value. 4) To exit the menu, tap the 'x' button or wait 10 seconds. Information Menu Reset 1) To reset THi and TLO tap the 'i' button. 2) Use the '▼' and '▲' buttons to select the data to be reset. 3) Hold the 'i' button to display the selected value. 4) While holding down the 'i' button, tap the 'x' button to reset the data. 5) To exit the menu, tap the 'x' button or wait 10 seconds. LAE Default Settings.xlsx ‐ Parameters FANS DEFROST THERMOSTAT 1 of 2 Code Parameter Range SPL Setpoint Low -50 to SPH ° SPH Setpoint High SPL to 120 ° Maximum limit for the Setpoint setting SP Setpoint SPL to SPH Temperature to be maintained (case setpoint) HYS Hysteresis 1 to 10 ° CRT Compressor rest time. 0 to 30 min Minimum off time for the compressor between cycles. CT1 Compressor on time. 0 to 30 min Compressor run time when temperature probe 1 is faulty. Thermostat differenetial CT2 Compressor off time. 0 to 30 min Compressor off time when temperature probe 1 is faulty. CSD Compressor door delay 0 to 30 min Compressor stop delay after the door has been opened. Active only if D1 or D2 = DOR DFM Defrost start mode DFT Defrost time DFB Defrost time backup NON - Defrost is disabled TIM - Regular timed defrost NON/TIM/FRO FRO - Defrost time count is only increased when the conditions occur for frost to form on the evaporator (optimized time increase). 0 to 99 hrs Timer value for a defrost to trigger. NO/YES DLI Defrost end temperature -50 to 120 ° DTO Maximum defrost duration 1 to 120 min DTY Defrost type DPD Evaporator pump down DRN Evaporator drip time If DFB=YES, after a power interruption, the timer will resume the count from where it left off with a±30 min apporoximation. IF DFB=NO, after a power interruption, the timer will restart the count from 0 Temperature read by temperature probe 2 at which defrost will end. Maximum time limit for defrost. OFF - off cycle defrost (compressor and heater off) OFF/ELE/GAS ELE - electric defrost (compressor off, heater on) GAS - hot gas loop defrost (compressor on, heater on) 0 to 240 sec At defrost start, defrost outputs are OFF for DPD seconds. 0 to 30 min After defrost end, time before normal cycle restarts. RT - during defrost show the real temperature from probe T1 LT - during defrost show the last temperature from probe T1 RT/LT/SP/DEF SP - during defrost show current setpoint DEF - during defrost show "DEF" DDM Defrost display mode DDY Defrost Display delay 0 to 60 min NO/YES The display will show the value from DDM during defrost and for DDY minutes after defrost ends. FID Fan during defrost FDD Fan restart temperature -50 to 120 ° Evaporator fan will restart below FDD temperature. Read from probe T2 FTO Fan restart time 0 to 120 min Maximum time delay for evaporator fan restart after a defrost. FCM Fan mode during cycle Evaporator air temperature difference Temperature difference for fan FDH restart Fan stop delay F1 FDT Fans active during defrost NON - fans are always on. TMP - temperature based control. Fans remain on when the compressor is ON. When the compressor is OFF the fans remain on as long as the temperature difference T2-T1 is greater than FDT. The fans are NON/TMP/TIM turned on again with the FDH differential. T1 = air temperature, T2 = evaporator temperature TIM - time based control. The fans are on when the compressor is ON. When the compressor is OFF, the fans switch on and off according to parameters F1, F2, F3. -120 to 0 ° T2 - T1 temperature difference for the fans to turn off when the compressor is off. 1 to 120 ° T2 - T1 temperature difference for the fans to restart. 0 to 180 sec After compressor stops, time in seconds until the fans stop. Used if FCM parameter is set to TIM F2 Fan stop time 0 to 30 min Time that fans are off while compressor is off. Used if FCM parameter is set to TIM F3 Fan run time 0 to 30 min Time that fans are on while the compressor is off. Used if FCM parameter is set to TIM Alarm threshold management NON/ABS/REL NON - temperature alarms are disabled. ABS - the values programmed into parameters ALA and AHA represent temperature alarm limits. REL - the values programmed into parameters ALR, AHR, SP, and HYS determine the alarm limits. Lower limit = SP-ALR Upper limit = SP+HYS+AHR ALA Low temperature alarm limit -50 to 120 ° Lowest temperature to trigger alarm AHA -50 to 120 ° Highest temperature to trigger alarm ATI High temperature alarm limit Low temperature alarm differential High temperature alarm differential Alarm probe ATD Temperature alarm delay 0 to 120 min Delay in minutes before temperature alarm is triggered. ADO Door alarm delay 0 to 30 min Delay in minutes before door alarm is triggered. AHM Condenser alarm setting AHT Condenser alarm limit ATM ALR ALARMS Function Minimum limit for the Setpoint setting AHR ACC Condenser cleaning -12 to 0 ° Low temperature alarm differential. If ALR = 0, low limit alarm is disabled. 0 to 12 ° High temperature alarm differential. If AHR = 0, high limit alarm is disabled. T1/T2/T3 Probe used for temperature alarm detection. NON - condenser alarm disabled NON/ALR/STP ALR - condenser alarm enabled. When alarm occurs, "HC" flashes on the display and the buzzer sounds. STP - in addition to display and buzzer from ALR, condenser power is cut and defrosts are suspended. -50 to 120 ° 0 to 52 weeks Condenser temperature alarm limit. Temperature read by T3 probe. When the condenser operation time, in weeks, matches the value from ACC, the display will flash "CL". If ACC = 0, the setting is disabled. 2 of 2 LAE Default Settings.xlsx ‐ Parameters INPUT/OUTPUT SETTINGS SECONDARY SETPOINT Code IISM Parameter Switch mode to second setpoint Range Function NON - secondary setpoint disabled. NON/MAN/DI2 MAN - button M on display toggles between primary and secondary setpoint DI2 - closing switch connected to DI2 inputs switches to secondary setpoint -50 to SPH ° Minimum limit for the Secondary Setpoint setting IISL Secondary setpoint low IISH Secondary setpoint high SPL to 120 ° Maximum limit for the Secondary Setpoint setting IISP Secondary setpoint SPL to SPH Temperature to be maintained (secondary setpoint) IIHY Secondary hysteresis 1 to 10 ° Thermostat differenetial for secondary setpoint NON - fans are always on. TMP - temperature based control. Fans remain on when the compressor is ON. When the compressor is OFF the fans remain on as long as the temperature difference T2-T1 is greater than FDT. The fans are NON/TMP/TIM turned on again with the FDH differential. T1 = air temperature, T2 = evaporator temperature TIM - time based control. The fans are on when the compressor is ON. When the compressor is OFF, the fans switch on and off according to parameters F1, F2, F3. IIFC Secondary fan control IIDF Secondary defrost time SB Standby button DI1 Digital input 1 operation DI2 Digital input 2 operation T3 Temperature probe T3 operation OS3 Temperature probe T3 offset -13 to 13 ° 0 to 99 hrs Timer value for a defrost to trigger. Enables/Disables the standby button on the display ( NON - Digital input 1 disabled. NON/DOR/ALR/ DOR - Door switch RDS ALR - when contact is closed, alarm is triggered RDS - when contact is closed, a defrost is initiated NON - Digital input 1 disabled. DOR - Door switch NON/DOR/ALR/ ALR - when contact is closed, alarm is triggered RDS/IISM/T3 RDS - when contact is closed, a defrost is initiated IISM - when contact is closed, the secondary setpoint parameters are active. T3 - temperature probe. DSP - temperature T3 to be displayed DSP/CND CND - condenser temperature measurement NO/YES T3 probe offset PSL Potentiometer setpoint min -50 to 70 ° PSR Potentiometer setpoint range 0 to 15 ° Maximum temperature setting for potentiometer maximum using PSL+PSR Minimum temperature setting for potentiometer minimum POF Potentiometer enable NO/YES Enables/Disables potentiometer temperature control. NON - light output disabled. MAN - light output controlled through M button on display front NON/MAN/D10/ D10 - light output is on when DI1 is open D20/D21 D20 - light output is on when DI2 is open D21 - light output is on when DI2 is closed LSM Light switch mode OT1 Auxiliary relay timer ON time 0 to 720 min OT2 Auxiliary relay timer cycle 1 to 24 hrs Duration in minutes that auxiliary relay will be closed. Time in hours between auxiliary relay activations NON - output disabled (always off) FAN - fan output DEF - defrost heater output LGT - output used for light control 0-1 - the relay contacts follow the on/standby state of the controller ALO - contacts open when an alarm occurs ALC - contacts close when an alarm occurs TIM - output is controlled by the OT1 and OT2 timer functions NON - output disabled (always off) FAN - fan output DEF - defrost heater output LGT - output used for light control 0-1 - the relay contacts follow the on/standby state of the controller ALO - contacts open when an alarm occurs ALC - contacts close when an alarm occurs TIM - output is controlled by the OT1 and OT2 timer functions OA1 Auxiliary relay 1 operation NON/FAN/DEF/L GT/01/ALO/ALC/TIM OA2 Auxiliary relay 2 operation NON/FAN/DEF/L GT/01/ALO/ALC/TIM OS1 OS2 Temperature probe 1 offset Evaporator temperature probe enable Temperature probe 2 offset -13 to 13 ° T2 probe offset TLD Time logging delay 1 to 30 min SCL Temperature scale 1 °C/2 °C/ °F SIM Display delay 1 to 100 sec Time delay for minimum and maximum temperature logging 1 °C - Celsius, 0.5 ° resolution 2 °C - Celsius. 1 ° resolution °F - Fahrenheit 1 ° resolution Display slow down ADR Network address 1 to 255 T2 -13 to 13 ° NO/YES T1 probe offset Enables/Disables evaporator probe T2 Network address for PC communication. FANS DEFROST THERMOSTAT LAE Default Settings.xlsx ‐ PFW‐Bulk ALARMS 1/3/2014 Code Parameter Setting SPL Setpoint Low 18.0 SPH Setpoint High 35.0 SP Setpoint 20.0 HYS Hysteresis 8.0 CRT Compressor rest time. 2 CT1 Compressor on time. 5 CT2 Compressor off time. 3 CSD Compressor door delay 0 DFM Defrost start mode TIM DFT Defrost time 3 DFB Defrost time backup NO DLI Defrost end temperature 48.0 DTO Maximum defrost duration 25 DTY Defrost type OFF DPD Evaporator pump down 0 DRN Evaporator drip time 0 DDM Defrost display mode DEF DDY Defrost Display delay 0 FID Fan during defrost YES FDD Fan restart temperature 99.0 FTO Fan restart time 0 FCM NON F1 Fan mode during cycle Evaporator air temperature difference Temperature difference for fan restart Fan stop delay F2 Fan stop time 0 FDT FDH 0.0 1.0 30 F3 Fan run time 0 ATM Alarm threshold management ABS ALA Low temperature alarm limit 10.0 AHA 60.0 ATI High temperature alarm limit Low temperature alarm differential High temperature alarm differential Alarm probe ATD Temperature alarm delay 30 ADO Door alarm delay 0 AHM Condenser alarm setting NON AHT Condenser alarm limit 60.0 ACC Condenser cleaning 0 ALR AHR 0.0 0.0 T1 SECONDARY SETPOINT LAE Default Settings.xlsx ‐ PFW‐Bulk INPUT/OUTPUT SETTINGS 1/3/2014 Code Parameter Setting IISM Switch mode to second setpoint DI2 IISL Secondary setpoint low 18.0 IISH Secondary setpoint high 35.0 IISP Secondary setpoint 24.0 IIHY Secondary hysteresis 8.0 IIFC Secondary fan control NON IIDF Secondary defrost time 3 SB Standby button NO DI1 Digital input 1 operation NON DI2 Digital input 2 operation IISM T3 Temperature probe T3 operation DSP OS3 Temperature probe T3 offset 0.0 PSL Potentiometer setpoint min 0.0 PSR Potentiometer setpoint range 0 POF Potentiometer enable NO LSM Light switch mode NON OT1 Auxiliary relay timer ON time 120 OT2 Auxiliary relay timer cycle 12 OA1 Auxiliary relay 1 operation TIM OA2 Auxiliary relay 2 operation NON OS1 0.0 YES OS2 Temperature probe 1 offset Evaporator temperature probe enable Temperature probe 2 offset TLD Time logging delay 5 SCL Temperature scale °F SIM Display delay 1 ADR Network address 1 T2 0.0