TPM-25 SERIES MOV THERMALLY PROTECTED MOV THERMALLY PROTECTED MOV Surge suppressor with thermal protection designed to open in the event of overheating due to the abnormal over-voltage, limited current conditions. FEATURES: • • • • • • • • • Quick thermal response and perfect circuit cutoff function due to special thermal disconnector design with arc extinguishing device. (Patent). Wide operating temperature range and high reliability. High surge current capability, Low leakage current. Floating remote signaling contact for fault alarm. Application in the AC mains, service entrance, and heavy industrial etc. Medium current 100A, 500A, 1000A SCCR 200KArms rd In accordance with UL1449 3 edition. ELECTRICAL RATINGS & SPECIFICATIONS Continuous TYPE Surge Current x 1 time In 15 times @ 8/20 @ 8/20 25KA 10kA 25KA 10kA SCCR VPR 200kA 600V 200kA 700V 10kA 200kA 900V 25KA 10kA 200kA 1000V 505 25KA 10kA 200kA 1300V 420 560 25KA 10kA 200kA 1500V TPM-22-550* 550 745 22KA 10kA 200kA 1800V TPM-22-690* 690 910 22KA 10kA 200kA 2200V VRMS (V) VDC (V) TPM-25-150* 150 200 TPM-25-180* 180 230 TPM-25-275* 275 350 25KA TPM-25-320* 320 410 TPM-25-385* 385 TPM-25-420* Operating Temperature -40°C ~ +75°C Electric Strength ≥ Insulation Resistance ≥ 10 MOhm Response Time 2500V (AC) ≤ 25 nS VERSION: 1.0 EFFECTIVE: MAY 13, 2015 TPM-25 SERIES MOV CASE OUTLINE AND DIMENSIONS 0.01 [0.30] 0.015 [0.40] 0.02 [0.5] 0.01 [0.30] 0.07-0.11 [2.0-3.0] 0.11 [2.9] 0.50 [12.8] 1.02 [26] 0.15-0.19 [4-5] 0.19 [5.0] 0.98 [25] 1.18 [30] DIMENSIONS IN INCHES [MM] VERSION: 1.0 EFFECTIVE: MAY 13, 2015 TPM-50 SERIES MOV THERMALLY PROTECTED MOV THERMALLY PROTECTED MOV Surge suppressor with thermal protection designed to open in the event of overheating due to the abnormal over-voltage, limited current conditions. FEATURES: • • • • • • • • • Quick thermal response and perfect circuit cutoff function due to special thermal disconnector design with arc extinguishing device. Wide operating temperature range and high reliability. High surge current capability, Low leakage current. Floating remote signaling contact for fault alarm. Application in the AC mains, service entrance, and heavy industrial etc. Medium current 100A, 500A, 1000A SCCR 200KArms rd UL1449 3 edition approved for Type 1 or 2 and CSA for Type 2 ELECTRICAL RATINGS & SPECIFICATIONS Continuous TYPE Varistor Voltage @1mA Surge Current 230 x 1 time @ 8/20 50KA 50KA In 15 times @ 8/20 20KA 20KA 275 350 50KA TPM-50-320* 320 410 TPM-50-420* 420 TPM-50-550* TPM-40-690* VRMS (V) VDC (V) TPM-50-150* 150 200 TPM-50-180* 180 TPM-50-275* 228-270 600V 250-310 600V 20KA 409-475 800V 50KA 20KA 485-563 1000V 560 50KA 20KA 646-748 1500V 550 745 50KA 20KA 820-1000 1500V 690 910 40KA 20KA 1000-1250 2000V Operating Temperature -40°C ~ +85°C Electric Strength ≥ Insulation Resistance ≥ 10 MOhm Response Time VPR V1mA(V) 2500V (AC) ≤ 25 nS VERSION: 2.0 EFFECTIVE: MAY 13, 2015 TPM-50 SERIES MOV CASE OUTLINE AND DIMENSIONS Certifications: Conforms to UL1449 3rd edition. Approved for Type 1 or 2 and CSA for Type 2 File No. E319342 VERSION: 2.0 EFFECTIVE: MAY 13, 2015