Ordering information Unit type FCA75F FCA 1 75 2 F 3 -24 4 -O 5 1Series name 2Output wattage 3Universal input 4Output voltage 5Optional N1 :with DIN rail attachment R FCA MODEL MAX OUTPUT WATTAGE[W] DC OUTPUT FCA75F-24 75(Peak 240) 24V 3.1(Peak 10)A SPECIFICATIONS MODEL VOLTAGE[V] CURRENT[A] ACIN 240V ACIN 480V FREQUENCY[Hz] INPUT OUTPUT PROTECTION CIRCUIT AND OTHERS ISOLATION ENVIRONMENT SAFETY AND NOISE REGULATIONS OTHERS *1 *2 *3 *4 *5 ACIN 240V ACIN 480V ACIN 240V INRUSH CURRENT[A] ACIN 480V LEAKAGE CURRENT[mA] VOLTAGE[V] *1 CURRENT[A] LINE REGULATION[mV] 0 - 3.1A LOAD REGULATION[mV] 0 - 10A 0 to +50C *2 RIPPLE[mVp-p] -10 - 0C *2 0 to +50C *2 RIPPLE NOISE[mVp-p] -10 - 0C *2 TEMPERATURE REGULATION[mV] -10 to +50C *5 DRIFT[mV] START-UP TIME[ms] HOLD-UP TIME[ms] OUTPUT VOLTAGE ADJUSTMENT RANGE[V] OVERCURRENT PROTECTION OVERVOLTAGE PROTECTION OPERATING INDICATION INPUT-OUTPUT INPUT-FG OUTPUT-FG OPERATING TEMP.,HUMID.AND ALTITUDE STORAGE TEMP.,HUMID.AND ALTITUDE *3 VIBRATION *3 IMPACT AGENCY APPROVALS CONDUCTED NOISE *4 CASE SIZE/WEIGHT COOLING METHOD EFFICIENCY[%] FCA75F-24 AC187 - 528 1f or DC265 - 746 0.80typ 0.45typ 50/60 (47 - 63) 82typ 78typ 25typ (At cold start) (At Room Temperature) 50typ (At cold start) (At Room Temperature) 0.75max (60Hz, According to IEC60950) 24 3.1 (Peak 10) 96max 150max 480max 240max 320max 680max 720max 600max 100max 800max (ACIN 240V, Io=100%) 10typ (ACIN 240V, Io=100%) 21.6 - 26.4 Works over 105% of peak current and recovers automatically Works at 115 - 140% of rating LED (Green) AC3,000V 1minute, Cutoff current = 10mA, DC500V 50MW min (At Room Temperature) AC2,000V 1minute, Cutoff current = 10mA, DC500V 50MW min (At Room Temperature) AC500V 1minute, Cutoff current = 100mA, DC500V 50MW min (At Room Temperature) -10 to +70C, 20 - 90%RH (Non condensing) (Refer to DERATING CURVE), 3,000m (10,000feet) max -20 to +75C, 20 - 90%RH (Non condensing), 9,000m (30,000feet) max 10 - 55Hz, 19.6m/s2 (2G), 3minutes period, 60minutes each along X, Y and Z axis 196.1m/s2 (20G), 11ms, once each X, Y and Z axis UL60950-1, C-UL, EN60950-1, EN50178 Complies with FCC-A, CISPR11-A, EN55011-A 65X125X124mm (WXHXD) / 750g max Convection Peak current for 150ms in a 30seconds period is acceptable. In case of rated input/output(ACIN240-480v/3.1A), either the 20MHz oscilloscope or the ripple noise meter(equivalent to Keisokugiken:RM101) is used. Option with DIN rail attachment(N1) is only for direction X(refer to sec4.2 in manual). Depth of power supply is 132mm with DIN rail attachment. Drift is the change in DC output for an eight hour period after a half-hour warm-up at 25C, with the input voltage held constant at the rated input/output. A-152 FCA75F External view FCA 13max 65 45 (11.5) LED DIN Rail Attachment FCA75F-24-N1 only Voltage Adjust AC(N) (35.5) (116) (72) AC(L) AC(N) Terminal Block (M4) Spacer FCA75F-24-N1 only (7) 7 (34) AC(L) 125 FG 13 -V FG (102) +V (110) + - 10 FCA75F-24 (15.5) (8) 124 (24.5) (37) 18 (12) 119 38.1±0.5 3-M3 Mounting Hole ¶Weight : 750g or less ¶Tolerance : ±1 ¶Mounting torque : 0.6N•m (6.3kgf•cm)max ¶Dimensions in mm. 12.7 31.75 64.5 59.5 º3.8 71.1±0.5 Terminal Block Cover 45.9 18max Performance data ¡STATIC CHARACTERISTICS ¡RISE TIME & FALL TIME 24 25 16 75 14 Io=100% 12 Ripple 50 10 8 25 150 160 170 180 190 200 INPUT VOLTAGE 210 220 230 240 26 15 Io=100% Io=50% 10 5 0 DC Output AC Input ACIN 480V 250 50ms/DIV ¡INRUSH CURRENT Input Voltage AC480V 24 V 20 V 60Hz (AC 200V) ¡OVERCURRENT CHARACTERISTICS OUTPUT VOLTAGE V 100 22 20A/DIV OUTPUT VOLTAGE 18 RIPPLE mVp-p V 20 OUTPUT VOLTAGE Output Voltage 22 60Hz Frequency 100% Load Input voltage AC480V 20 18 16 14 12 2 4 6 8 OUTPUT CURRENT A 10 12 50ms/DIV A-153 Basic Characteristics Data Basic Characteristics Data FCA Model Circuit method Switching frequency [kHz] FCA50F Forward converter 120 FCA75F Forward converter 120 Active filter 80 1.10(AC240V) Forward converter 120 0.55(AC480V) FCA200F * The value of input current is at ACIN 240V and rated load. A-156 Input current [A] 0.55(AC240V) 0.30(AC480V) 0.80(AC240V) 0.45(AC480V) Rated input fuse Inrush current protection Material Single sided Series/Parallel operation availability Double Series Parallel sided operation operation 500V 5A Thermistor CEM-3 Yes Yes No 500V 5A Thermistor CEM-3 Yes Yes No 500V 10A Thermistor CEM-3 Yes Yes No PCB/Pattern