Submittal Transmittal - NYU Langone Medical Center

advertisement
NYULMC Kimmel Pavilion
* Submittal Transmittal
Project # 130002
[For Reviewer]
FDR Drive 34th Street
New York, NY 10016
Date:
Telephone: 212-686-1191
1/8/16
Transmittal No: 8457
John Flanagan
Transmitted To:
001
Spec
102513
Christopher Brooten
Turner Construction Co.
140 Broadway -29th flr. New York, NY
10005
New York, New York 10006
Tel: 646-416-5781
Fax:
314 East 34th Street
6th Floor
New York, NY 10016
Tel: 212-686-1191
Fax:
0001 - 102513 - 2
Qty
Transmitted By:
NBBJ Architects
Submittal Package No
Item
January 08, 2016
Fax:
Description
Due Date
Acute & ICU Headwall ONLY Submittal Package
12/28/15
Sub
Section
Headwall/Foo
twall
Item #
20579
Rev Type
2
Shop Drawings
Description
Notes
Item Action
AP AN RR RJ
Acute & ICU Headwall
ONLY Submittal Package
AP=Approved
AN=Approved as noted
RR=Revise and resubmit
RJ=Rejected
Cc:
Company Name
Contact Name
Fax Number
Copies
Notes
Remarks
0001-102513-2 Acute & ICU Headwall ONLY Submittal Package
Signature
TCCO - Submittal Transmittal - For Reviewer_V4xi.rpt
RPT Revised: 5/23/12
Signed Date
Turner Construction Co.
Page 1 of 1
Submittal
Transmittal
PROJECT
NYU Kimmel Submittals
1013.60
DATE SENT
1/7/2016
SUBJECT
Acute & ICU Headwall ONLY
Submittal Package
SUBMITTAL ID
0001-102513-2
TYPE
Submittal
TRANSMITTAL ID
07778
PURPOSE
Provide as Corrected
VIA
Info Exchange
SPEC SECTION:
10 00 00
FROM
NAME
COMPANY
EMAIL
Teresa Peters
PHONE
tpeters@nbbj.com
TO
NAME
COMPANY
EMAIL
Chris Brooten
Turner
Construction
Company
cbrooten@tcco.com
REMARKS:
PHONE
Please see attached submittal response.
CONTENTS
QUANTITY:
1
DATED:
12/15/2015
NUMBER:
DESCRIPTION:
0001-102513-2 Acute & ICU Headwall ONLY Submittal Pkg.pdf
ACTION:
REMARKS:
QUANTITY:
1
DATED:
1/6/2016
NUMBER:
DESCRIPTION:
0001-102513-2 Acute & ICU Headwall ONLY Submittal Pkg_NBBJ JBB Review_.pdf
ACTION:
REMARKS:
COPIES:
John Flanagan
Carlos Azolas
(NBBJ Ennead Architects LLP)
(NBBJ Ennead Architects LLP)
Page 1 of 2
Submittal Transmittal
DATE:
ID:
William Nathans
John Koch
Vincent Rotoli
Nikolay Khomyak
Samantha Bruno
Kevin Krudwig
Fernando Suarez
1/7/2016
07778
(NBBJ Ennead Architects LLP)
(Jaros, Baum & Bolles)
(Jaros, Baum & Bolles)
(Jaros, Baum & Bolles)
(Jaros, Baum & Bolles)
Page 2 of 2
NYU Kimmel Pavilion
0001-102513-1 Acute & ICU Headwall & Footwall REV1
0001-102513-2 Acute & ICU Headwall ONLY Submittal Package
Submittal Review
07.22.2015
01.05.2016
REVIEW KEY NOTES:
1. Comply with all requirements of Section 10 2513 PATIENT HEADWALLS AND 01 3300 SUBMITTAL
PROCEDURES. It is understood that this is a preliminary MOCK-UP coordination submission for
initial review of the ICU Room mock up and further submissions may be required to insure adequate
coordination and address any mock up comments. Comply with all review comments from
10.29.2015 25th Street Mock Up review (notes inserted in submittal by TCCo, dated 11.11.2015)
including any follow up emails and subsequent clarifications / client directions and as noted in this
submittal review.
2. Provide complete LEED submittal for review in accordance with Part 1.5 of the specification.
3. The client has requested that the dialysis box be located as high above the finish floor as possible.
Ideally the top of the stainless steel enclosure / cover flange would be 1” minimum below the
equipment rail. Please confirm this is sufficient room for installation and construction / fabrication
tolerance for laminate clad panel assembly. The 31.5” dimension from headwall centerline to
centerline of the dialysis box is approved. The dialysis box location and mounting heights are
approved as submitted. TCCo submit proposed alternate latching mechanism for review with
client / coordinate installation of dialysis box with alternate latching mechanism (non-keyed) as
directed by NYU.
4. The client has confirmed that the initial mock up is to be an ICU headwall assembly.
5. Nurse Call back box to be installed as noted in this submittal for the initial ICU mock up review.
Please note that the nurse call location and requirements are still under review by the client. Nurse
NYU Kimmel Pavilion
0001-102513-1 Acute & ICU Headwall & Footwall REV1
0001-102513-2 Acute & ICU Headwall ONLY Submittal Package
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
Submittal Review
07.22.2015
01.05.2016
Call system device locations as shown are approved. Coordination cuts were only provided for the
Single Patient Station and Bed Receptacle; I have inserted a cut of the “354018 – 2 Jack Station”
identified as “AX” on the shop drawings, please insure appropriate coordination has occurred with
associated subcontractor.
Electrical device colors currently under review by client to insure conformance with current hospital
standards. Color and device design style to be reconfirmed under separate cover. Device colors as
indicated in this submittal were approved as client standard for this project.
Vertical location of electrical devices is acceptable as shown, horizontal location needs to be
coordinated with final AV equipment system components and monitor selection.
Metal laminate type and grain direction is confirmed and was previously approved by NBBJ.
Please note attached SKA-151 for Patient Bedroom 100 on floors 8 through 18, the south side of the
headwall assembly has been furred out in order to resolve a beam / riser conflict reviewed as in BIM
coordination process, coordinate with TCCo as required.
Final laminate TBD, laminates to be reviewed and confirmed with client once installed at the 25th
Street Mock Up. PL-01 Wilsonart #10776-60 “Kensington Maple” (with laminate cross grain printed
to allow for vertical grain with no vertical seams) is approved.
Anodized aluminum finish previously approved. The only detail reviewed or approved under
submittal “0003-102513-0 Headwall & Footwall Trim Details” was the custom perimeter trim
extrusion. Previously requested section details should be provided prior to final fabrication.
TCCo Note: EEG face plate and device types to be confirmed / coordinated with equipment vendor.
Cover plate finish to be brushed stainless steel to match adjacent devices.
Contract documents call for entire area of recess to receive blocking (sheet metal backing plates),
this also needs to be coordinated with final equipment selection and placement. Coordinate with
note 7. Footwall not submitted as part of this package.
Four Acute Physio Monitors need to be provided on 18th floor at Patient Bedrooms 112, 113, 114
& 115 (please note these room numbers have been updated by ASI 138 to rooms 13, 14, 15 & 16
respectively.)
Confirm all headwall types and configurations are in accordance with contract documents,
coordinate updated room numbering with ASI 138 as required.
As reviewed in the 25th Street Mock Up, accept the concept of eliminating the previous “pocket”
concept to allow for removal of the headwall face panels. I do not understand why you would
want to incorporate the painted aluminum “L” shape above the headwall panel, why not just
extend the GWB ceiling plane to intersect the headwall partition assembly (above the finished
removable face panel). The light fixture is installed in a simple cut-out in the GWB ceiling, the
fixture location needs to be coordinated with headwall installation clearances, then reviewed and
coordinated with associated carpentry subcontractor.
END OF NBBJ REVIEW
Project Name:
NYULMC – Kimmel Pavilion
Project No:
14506.A.000
Description:
0001-102513-2 Acute & ICU Headwall ONLY Submittal Pkg
Manufacturer:
Various
Submission No:
Submitted by:
0001-102513-2
Modular Services Co.
JAROS, BAUM & BOLLES
Consulting Engineers
80 Pine Street
New York, New York 10005
NO EXCEPTIONS TAKEN
MAKE CORRECTIONS NOTED
REVISE AND RESUBMIT
REJECTED
Checked by
NK/VR
Date
01/06/2016

X


Engineer’s review is for general compliance
with the design concept and contract
documents. Markings or comments or the lack
thereof shall not be construed as relieving the
Contractor from compliance with the project
plans and specifications. The Contractor
remains responsible for details and accuracy,
for confirming and correlating all quantities
and dimensions, for selecting fabrication
processes, for techniques of construction, for
performing his work in a safe manner, and for
coordinating his work with that of other trades.
JB&B Comments:
1.
2.
3.
4.
5.
All receptacles shall be hospital grade with an illuminated face.
All normal receptacles shall be gray in color.
Show conduit routing and stub-ups from junction boxes within headwall.
All emergency circuiting shall utilize hard pipe conduit.
Vacuum piping connection from plumbing system shall be made so that the end of header rises up
directly from an outlet. Refer to Podium headwall submittal for vacuum piping arrangement.
6. TCCo. to coordinate junction box grounding requirements with the electrical contractor.
7. Normal and emergency lighting to utilize separate junction boxes.
8. See submittal for additional comments.
Notes
Green: Turner
NYULMC Kimmel Pavilion
Project # 130002
FDR Drive 34th Street
New York, NY 10016
Date:
Telephone: 212-686-1191
[For Reviewer]
December 14, 2015
Fax:
12/14/15
Transmittal No: 8269
John Flanagan
Transmitted To:
Turner Construction Co.
2 Rector Street - 25th Floor
New York, New York 10006
Tel: 646-416-5781
Fax:
314 East 34th Street
6th Floor
New York, NY 10016
Tel: 212-686-1191
Fax:
0001 - 102513 - 2
Qty
001
Spec
102513
Christopher Brooten
Transmitted By:
NBBJ Architects
Submittal Package No
Item
* Submittal Transmittal
Description
Due Date
Acute & ICU Headwall ONLY Submittal Package
12/28/15
Sub
Section
Headwall/Foo
twall
Item #
Rev Type
20579
2
Shop Drawings
Description
Notes
Item Action
AP AN RR RJ
Acute & ICU Headwall
ONLY Submittal Package
AP=Approved
AN=Approved as noted
RR=Revise and resubmit
RJ=Rejected
Cc:
Company Name
Contact Name
Fax Number
Copies
Notes
Remarks
Final Approval For Release At 374 Patient Room Locations
1.) Footwall Removed From This
Submittal Package. Final Submittal
To Be Sent Under Separate Cover
Pending Mock-Up Design Approval
2.) This most recent submittal should
have incorporated all of the
comments from the previous
submittal for mock-up fabrication.
3.) All comments from the mock-up
review meeting should have been picked
up and incorporated into this submittal.
4.) Quality and design features should be
the same as the mock-up except for
items commented on in review notes.
12/14/2015
Chris Brooten
0001-102513
-2
20579
2
Signature
TCCO - Submittal Transmittal - For Reviewer_V4xi.rpt
RPT Revised: 5/23/12
5.) If there are any issues with the
Tcco/Modular comments inside the
mock-up review package, please
comment as part of this review.
Signed Date
Turner Construction Co.
Page 1 of 1
10
14
5
5
3
14
15
10
5
5
3
15
10
14
5
5
3
15
10
14
5
5
3
15
Page 1 of 3
4/18/06
DiamondCare® Medical Gas Quick-Connect Outlets for OEM
SPECIFICATION
Medical Gas Quick-Connect Outlet
The Medical Gas Outlets shall be gas specific, permanently
labeled for the services indicated and shall accept only
corresponding DISS, Puritan Bennett, Medaes® or
Chemetron® manufacturer's-style, quick-connect adapters.
The outlets shall be UL listed, CSA certified, and be fully
compliant with the latest edition of NFPA 99. Outlets shall be
tested for flow, leaks and cleaned for oxygen service prior to
shipping. The outlets shall be made in the U.S.A.
Outlet Design
A complete outlet shall consist of a gas-specific rough-in
assembly and a matching gas-specific front body assembly.
The outlet design shall allow for the change from one style of
quick-connect or DISS front body to another without any
changes or modifications to the rough-in assembly.
Rough-in Assembly
The rough-in assembly includes a gas-specific, plated steel,
mounting bracket designed to permit on-site location and
installation. The gas inlet of the outlet body shall be DISS,
copper tube or hose barb fitting connection. A secondary
valve shall be included in all pressure service rough-in
assemblies for standing pressure testing of the distribution
system and to prevent gas flow (except vacuum and WAGD)
when the front body is removed for service. Vacuum and
WAGD rough-ins shall be provided with a pressure test plug
for pressure and vacuum testing.
Front Body Assembly
The front body assembly shall be indexed to the
corresponding gas service rough-in assembly to avoid
accidental cross connection. Front bodies shall have
permanent color-coded gas service identification clearly
indicated on the front surface.
Frontbody Assembly
Rough-in Assembly
Medaes-type
Diamond®
Quick-Connect
Key Style
Chemtron-type
Latch Index
Quick-Connect
Key Style
DISS
Key Style
Puritan-Bennett-type
Geometric
Quick-Connect
Key Style
Faceplate
(Optional)
P/N 6803-2000-205
BeaconMedæs Š 14408 W. 105th Street
Lenexa, KS 66215 Š Phone: (913) 894-6058
Fax: (913) 894-6088
OEM
SSB-840-14
Page 1 of 2
31 January 2011
DiamondCare® Console Outlet
DISS Key Style
SPECIFICATION
Console Outlet
The DiamondCare® Console Outlet is available in a DISS
Key Style for each of the medical gas services listed in the
table on page 2. Each console outlet consists of a rough-in
assembly and a frontbody assembly.
Rough-In Assembly
The rough-in assembly is available with a copper inlet
tube (piped backbody) or a DISS male inlet fitting (DISS
backbody) for connection to a gas delivery line. The
piped rough-in assembly includes a 7” (18cm) long, type
K copper, inlet tube for brazing to the gas delivery line.
This inlet tube rotates 360°, which permits alignment with
the gas line. Both the piped and DISS rough-in assemblies
consist of a steel backplate with a non-removable, positive
pin-keying arrangement for each specific gas service. The
specific gas service is stamped into the front of the roughin. Both types of rough-in assemblies include a fully
serviceable secondary check (for pressurized gases) to help
prevent gas flow when the frontbody is removed for service.
Vacuum and WAGD services do not have secondary check
valves, according to NFPA 99 standards.
Frontbody Assembly
The console frontbody consists of a DISS keying disc and
attached barrel assembly, which houses the primary check
valve. The keying disc assembly includes a gas-specific,
positive pin-keying device, is color-coded, and labeled with
the name of the gas service. The barrel assembly includes
brass piston and frontbody check spring, which engage
and seal when a DISS-fitted treatment device is removed
from the outlet.
Features
•
Quick access to primary check valve components.
•
Large, gas-specific, color-coded, keying disc and label.
•
Outlets listed by Underwriters Laboratories® and CSA®
and manufactured in accordance with applicable CGA,
NFPA 99 and CSA® standards.
•
Cleaned for oxygen service, pressure-tested, and
capped prior to shipping.
Product Dimensions
3/8" O.D.
1/2" O.D. on rough-ins
4107 2011 25/4107 2011 27
BeaconMedæs • 1800 Overview Drive, Rock Hill, SC 29730 • Phone: (803) 817-5600 • Fax: (803) 817-5750 • www.beaconmedaes.com
DiamondCare®
Console Outlet DISS
SSB-840-33
SSB-840-33
Page 2 of 2
31 January 2011
Ordering Information
You can order a DiamondCare® Console Outlet as a complete
assembly (rough-in and frontbody), or as individual
assemblies.
Each rough-in and frontbody assembly is
individually packaged.
DISS Key Style
Finish Assembly
Only
Piped Console
Rough-in
Assembly Only
3/8" OD
Piped Console
Rough-in
Assembly Only
1/2" OD
Gas Service(1)
DISS Key Style
Complete
Assembly
O2
‰6803-8110-200
‰4107 2011 56
‰4107 2011 20
‰4107 2011 21
N2O
‰6803-8110-201
‰4107 2011 57
‰4107 2011 22
‰4107 2098 08
Vac
‰6803-8110-202
‰4107 2011 59
N/A
‰4107 2011 25
Air
‰6803-8110-203
‰4107 2011 58
‰4107 2011 23
‰4107 2011 24
CO2
‰6803-8110-204
‰4107 2011 62
‰4107 2011 28
‰4107 2100 40
N2
‰6803-8110-205
‰4107 2011 60
‰4107 2011 26
‰4107 2098 09
WAGD(2)
‰6803-8110-206
‰4107 2011 61
N/A
‰4107 2011 27
O2/CO2 mix
‰6803-8110-207
‰4107 2011 63
‰4107 2011 29
N/A
IAir
‰6803-8110-218
‰4107 2011 67
‰4107 2011 33
N/A
DISS Key Style
Finish Assembly
Only
DISS Console
Rough-in
Assembly Only
Gas Service(1)
DISS Key Style
Complete
Assembly
O2
‰6803-8110-300
‰4107 2011 56
‰4107 2011 87
N2O
‰6803-8110-301
‰4107 2011 57
‰4107 2011 88
Vac
‰6803-8110-302
‰4107 2011 59
‰4107 2011 90
Air
‰6803-8110-303
‰4107 2011 58
‰4107 2011 89
CO2
‰6803-8110-304
‰4107 2011 62
‰4107 2011 93
N2
‰6803-8110-305
‰4107 2011 60
‰4107 2011 91
‰6803-8110-306
‰4107 2011 61
‰4107 2011 92
O2/CO2 mix
‰6803-8110-307
‰4107 2011 63
‰4107 2011 94
IAir
‰6803-8110-318
‰4107 2011 67
‰4107 2011 98
(2)
WAGD
NOTES:
(1) ISO labeled confirmations are also available.
(2) WAGD: Waste Anesthetic Gas Disposal (formerly Evacuation).
Piped Console
DISS Console
CO2, N2, and O2/CO2 services are available in DISS Key Style.
For more information, contact BeaconMedæs Customer Service at
1-888-4MEDGAS (463-3427)
BeaconMedæs
1800 Overview Drive
Rock Hill, SC 29730
Phone: (803) 817-5600
Fax: (803) 817-5750
www.beaconmedaes.com
SSB-840-14
Page 2 of 3
4/18/06
Console Rough-In Assembly
Gas
Service
Color Code Label
Hose Barb
(Background/Text)
Rear Entry DISS
90° DISS
3/8” OD Tube
1/2” OD Tube
O2
White/Green
F
6-236210-00
F
6803-8130-800
F
6-236410-00
F
6803-8138-800H
F
6803-8138-800
N 2O
Blue/White
F
6-236211-00
F
6803-8130-801
F
6-236411-00
F
6803-8138-801H
F
6803-8138-801
AIR
Yellow/Black
F
6-236212-00
F
6803-8130-803
F
6-236412-00
F
6803-8138-803H
F
6803-8138-803
VAC
White/Black
F
NA
F
6803-8130-802
F
6-236413-00
F
NA
F
6803-8138-802
VAC*
White/Black
F
6-236213-00*
F
NA
F
NA
F
NA
F
NA
Nitrogen
Black/White
F
6-236214-00
F
6803-8130-805
F
6-236414-00
F
6803-8138-805H
F
6803-8138-805
Air (ISO)
Black/White
F
6-236216-00
F
NA
F
6-236416-00
F
6803-8138-809H
F
6803-8138-809
Vac (ISO)
Yellow/Black
F
6-236217-00*
F
NA
F
6-236417-00
F
NA
F
6803-8138-810
O2 (ISO)
White/Green
F
NA
F
NA
F
NA
F
6803-8138-808H
F
6803-8138-808
WAGD
Violet/White
F
NA
F
6803-8130-806
F
6-236419-00
F
NA
F
6803-8138-806
WAGD*
Violet/White
F
6-236219-00*
F
NA
F
NA
F
NA
F
NA
CO2
Gray/Black
F
6-236220-00
F
6803-8130-804
F
6-236420-00
F
6803-8138-804H
F
6803-8138-804
O2-CO2
Green/Gray
F
6-236222-00
F
6803-8130-807
F
6-236422-00
F
6803-8138-807H
F
6803-8138-807
*5/16” flexible hose connection. Hose barb assemblies are sized for 1/4” ID hose unless otherwise specified.
Console Front Body Assembly
Gas Service
Color Code Body
(Background/Text)
Puritan Bennett
Type
Medaes-Type
Chemetron-Type
DISS
O2
Green/White
F
6803-8112-800
F
6803-8111-800
F
6803-8113-800
F
6803-8110-800
N 2O
Blue/White
F
6803-8112-801
F
6803-8111-801
F
6803-8113-801
F
6803-8110-801
AIR
Yellow/Black
F
6803-8112-803
F
6803-8111-803
F
6803-8113-803
F
6803-8110-803
VAC
White/Black
F
6803-8112-802
F
6803-8111-802
F
6803-8113-802
F
6803-8110-802
Nitrogen
Black/White
F
NA
F
NA
F
NA
F
6803-8110-805
Oxygen (ISO)
White/Green
F
6803-8112-808
F
6803-8111-808
F
6803-8113-808
F
6803-8110-808
Air (ISO)
Black/White
F
6803-8112-809
F
6803-8111-809
F
6803-8113-809
F
6803-8110-809
Vac (ISO)
Yellow/Black
F
6803-8112-810
F
6803-8111-810
F
6803-8113-810
F
6803-8110-810
WAGD
Violet/White
F
6803-8112-806
F
6803-8130-806
F
6803-8113-806
F
6803-8110-806
Gray/Black
F
NA
F
NA
F
6803-8113-804
F
6803-8110-804
Green/Gray
F
NA
F
NA
F
6803-8113-807
F
6803-8110-807
CO2
O2-CO2
BeaconMedæs Š 14408 W. 105th Street
Lenexa, KS 66215 Š Phone: (913) 894-6058
Fax: (913) 894-6088
Straight Blade Devices
15 and 20 Ampere, 125 Volts
2 Pole, 3 Wire Grounding
IP20
HBL®
SUITABILITY
Extra Heavy Duty
Hospital Grade Receptacles
15A 125V
NEMA 5-15R
UL CSA
0.5 HP
20A 125V
NEMA 5-20R
UL CSA
1 HP
Duplex
Description
Color
Catalog Number
Flush, thermoplastic polyester face,
back and side wired.
Black
Blue
Brown
Gray
Ivory
Light Almond
Red
White
HBL8200BK
–
HBL8200
HBL8200GY
HBL8200I
HBL8200LA
HBL8200RED
HBL8200W
–
HBL8300BL
HBL8300
HBL8300GY
HBL8300I
HBL8300LA
HBL8300RED
HBL8300W
Flush, LED illuminated face,
back and side wired.
Gray
Ivory
Red
White
HBL8200ILGY
HBL8200ILI
HBL8200ILR
HBL8200ILW
HBL8300ILGY
HBL8300ILI
HBL8300ILR
HBL8300ILW
Tamper-Resistant receptacle
with wire leads. Complies with
requirements of NEC® article
517-18(c).
Brown
Gray
Ivory
Light Almond
Red
White
HBL8200SGA
HBL8200SGGYA
HBL8200SGIA
HBL8200SGLA
HBL8200SGRA
HBL8200SGWA
HBL8300SGA
HBL8300SGGYA
HBL8300SGIA
HBL8300SGLA
HBL8300SGRA
HBL8300SGWA
Isolated ground∆.
Orange
Red
IG8200
IG8200R
IG8300
IG8300R
6
HBL8200GY
HBL8300SGA
MRI Receptacle, Duplex
Description
Color
Catalog Number
MRI receptacle, flush, thermoplastic
polyester face, back and side wired.
Ivory
Light Almond
Red
White
HBL8200IMRI
HBL8200LAMRI
HBL8200RMRI
HBL8200WMRI
HBL8300IMRI
HBL8300LAMRI
HBL8300RMRI
HBL8300WMRI
Slender/Compact, Duplex
Description
Color
Catalog Number
Flush, thermoplastic polyester face,
back, and side wired.
Fed. Spec. verified.
Brown
Gray
Green
Ivory
Light Almond
Red
White
HBL8200H
HBL8200HG
–
HBL8200HI
HBL8200HLA
HBL8200HRED
HBL8200HW
HBL8300H
HBL8300HG
HBL8300HGN
HBL8300HI
HBL8300HLA
HBL8300HRED
HBL8300HW
HBL8300RMRI
Style Line® Decorator*
Description
Color
Catalog Number
Flush, nylon face,
back and side wired.
Brown
Gray
Ivory
Office White
Red
White
HBL2172
HBL2172GY
HBL2172I
–
HBL2172R
HBL2172WA
Isolated ground∆.
Ivory
Orange
White
HBL2182
HBL2182GY
HBL2182I
HBL2182OW
HBL2182R
HBL2182WA
–
–
–
HBL8200ILW
IG2182I
IG2182
IG2182WA
Note: ∆See section M for additional information on isolated ground devices.
*Not Fed. Spec. Listed.
See pages A-48 and A-49 for accessories.
See page L-19 for technical information.
See page Tech-10 for Tamper-Resistant description.
See section N for wallplates.
HBL2172
NEC®
is a registered trademark of the National Fire Protection Association (NFPA).
www.hubbell-wiring.com
Dimensions in Inches (mm)
®
Wiring Device-Kellems
L-3
Responder®
Health Care Communications Systems
Model: 353001-Enhanced Single Patient Station
Features
• Functions as single bed station with two (2) additional pushbuttons
• Multiple call-in priorities available
• Tilt/Release DIN receptacle for pillow speakers with patient
entertainment controls and handset intercom with entertainment
muting during nurse call
• Tilt/Release DIN receptacle allows for ease of disconnecting
Pillow Speaker from the patient station
• Auxiliary device receptacle with separate call-in priority setting • No dummy plugs required
• Interfaces with specialty beds via separate receptacle and control module
• LED to indicate specialty bed is not connected
• Interfaces with a remote Pillow Speaker via separate station
• Output for lighting control options direct to low voltage lighting controller
• Cancel button for localized call cancellation
• 3-gang adapter plate included
• Continuous supervision of station for loss of data and/or power
faults
• Plug-in connectors for easy service
• Bio-seal options to cover buttons and allow for easy disinfecting
of the station
353001
5
Adapter Plate
Specifications
Power Required: 92.6mA @ 18VDC (full load all
connections)
Weight: 0.7 lb. (0.3 kg)
Size: W: 6.4” (16.2 cm)
H: 4.25” (10.8 cm)
D: 2.5” (6.4 cm) in back box; 0.5” (1.3 cm) off-wall with adapter plate W: 7.1” (18.1 cm)
H: 5.0” (12.7 cm)
D: 2.5” (6.4 cm) in back box; 0.7” (1.8 cm) off-wall
Housing & Finish: High-impact molded Cycoloy 2950 UL
94-5VB; light grey faceplate
Controls/Indicators: One (1) DIN receptacle, One (1) ¼”
receptacle, One (1) Cancel button, One (1) Monitor LED,
Two (2) Call-assurance LED indicators, Two (2) Special
Buttons with Call-Assurance, and Two (2) Special Bed LED
indicators
Terminations: Plug-on connectors
Backbox Requirements: 3 gang (Non-gangable), 3-1/2”
Deep
Description
The Enhanced Single Patient Station is a single bed station
with the added capability of placing two additional calls. The station also allows both patients and staff to place
different call-ins, depending on their requirements, to the
assigned nurse console(s), staff terminal(s), along with
other annunciation devices such as wireless phones. The
patient station interfaces with entertainment handsets and
specialty beds to initiate calls, control entertainment, control
lighting, and provide nurse call audio and entertainment
audio through the respective speakers.
When used with the Feature Bed Control Module, the audio
capabilities are transferred to the bed rail with entertainment muting.
The patient station is connected to its associated corridor
light or Domeless room controller and is continually supervised for both power and data. Through programming,
a message can annunciate at the associated console(s)
and / or the remote status application if a problem occurs
Architect and Engineer (A&E) Specifications available online at: customerconnection.rauland.com
Specifications subject to change without notice
©Copyright 2012 Rauland-Borg Corporation Printed in USA
USA-Mt.Prospect, IL Canada
www.rauland.com
Rev 09/2012
• 800-752-7725 • 905-607-2335
• Fax 800-217-0977
• Fax 905-607-3554
Rauland-Borg Corporation
Responder®
Health Care Communications Systems
Model: 354018 - 2 Jack Station
Features
• Two (2) isolated inputs for auxiliary alarms with callassurance LEDs
• Compatible with various 1/4” jack-compatible medical
instruments
• Annunciate medical equipment alarms on pocket pagers, wireless phones, consoles, etc
• Each input can be configured as momentary or latched
• Programmable delay of call in
• Optional antimicrobial Bio-seal to cover cancel button and
allow for easy disinfecting of the station
• Cancel button
• Annunciates cord-out
354018
Specifications
Power Required: 11.5mA @18VDC
Weight: 0.25 lbs (0.1 kg)
Size: W: 3.2” (8.1 cm)
H: 4.25” (10.8 cm)
D: 0.6” (1.5 cm in back box: 0.5” (1.3 cm) off-wall
Housing & Finish: High-impact molded Cycoloy 2950 UL
94-5VB; light grey faceplate
Controls/indicators: Two (2) ¼” jacks, One (1) Cancel
button, Two (2) call-placed LEDs
Terminations: Plug-on connector
Backbox Requirements: 1 gang (Non-gangable), 3 1/2”
Deep
Description
The 2-Jack Station provides the ability to place two unique
call priorities from a single station. The station is typically
installed in patient rooms and monitors medical equipment
that is routinely used. The 2-Jack Station allows an alarm
from patient monitoring equipment to light corridor lights,
tone and display at a console, as well as directly alert
caregivers carrying wireless devices. Each ¼” isolated jack
is supervised, so if a piece of equipment is unplugged a call
will be placed.
The 2-jack Station is also supervised for data and / or
power faults and each jack is optically isolated from the
alarming device and supports dry contact inputs.
5
Architect and Engineer (A&E) Specifications available online at: customerconnection.rauland.com
Specifications subject to change without notice
©Copyright 2008 Rauland-Borg Corporation Printed in USA
USA-Mt.Prospect, IL Canada
www.rauland.com
Rev 08/2008
• 800-752-7725 • 905-607-2335
• Fax 800-217-0977
• Fax 905-607-3554
Rauland-Borg Corporation
Responder®
Health Care Communications Systems
Model: NCBED5 - Responder 5 Feature Bed Receptacle - 37 pin
5
Features
• Interfaces Feature Bed Side Rail Controls with
Responder 5
• Simple, easy plug-on connectors to the Responder 5
Feature Bed Control Module
• Provides dedicated Bed Port for Professional Installation
of Feature Beds
• Stainless Steel Wallplate
• Dummy Plug for use when Bed is not plugged into the
Receptacle
NCBED5
Specifications
Weight: 0.2 lbs. (0.09 kg)
Dimensions:
W: 2.75” (6.1 cm)
H: 4.5” (11.4 cm)
D: 2.5” (6.4 cm)
Housing and Finish: Stainless Steel
Terminations: Three 5" cables pre-terminated with plug-on
connectors
Mounting: Mounts in a single gang backbox at least 2 1/8"
deep
Description
The NCBED5 Feature Bed Receptacle is a 37-pin receptacle that interfaces the feature bed with side rails to the
Responder 5 nurse call system. The receptacle is mounted
on a single gang stainless steel plate. The feature bed
connects to the receptacle via a bed cable (Rauland model
number NCC37 or NCC37RA). The receptacle is then
wired to the Responder 5 Feature Bed Control Module
(Rauland model number 350302) via three (3) pre-terminated 8-pin connectors for easy installation. The Feature
Bed Control Module is then wired via a single CAT5/CAT6
cable to the Responder 5 patient stations to allow for calls
from the bed side rails to be annunciated on the nurse call
system and auxiliary functions such as TV control to be
controlled from the bed side rails. A 37-pin dummy plug is
included with the NCBED5 Feature Bed Receptacle.
The NCBED5 Feature Bed Receptacle typically mounts in a
single gang US back box at least 2 1/8” deep, which allows
enough room for the Responder 5 Feature Bed Control
Module to fit behind the Feature Bed Receptacle in the
same back box.
Architect and Engineer (A&E) Specifications available online at: customerconnection.rauland.com
Specifications subject to change without notice
©Copyright 2010 Rauland-Borg Corporation Printed in USA
USA-Mt.Prospect, IL Canada
www.rauland.com
Rev 08/2010
• 800-752-7725 • 905-607-2335
• Fax 800-217-0977
• Fax 905-607-3554
Rauland-Borg Corporation
Dialysis Box Details
Currently Under
Review. Only Minor
Items Should Change
Like Door Swing, &
Keyed Lock
3
THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF MODULAR SERVICES COMPANY. ANY REPRODUCTION IN PART OR AS WHOLE WITHOUT THE WRITTEN PERMISSION OF MODULAR SERVICES COMPANY IS PROHIBITED
NOTE(S):
1.
DIMENSIONS FROM CTR OF HEADWALL AND CTR OF FRAMING
2.
MEP CLEAR SPACE SHOWN IN GREEN
TOP OF HEADWALL
FOOTWALL SIDE
2.50
2.50
0
1.50
2.50
1.50
2.50
21.00
9.00
3.00
32.50
37.00
40.00
0
0
HEADWALL SIDE
MODULAR
SERVICES COMPANY
Product Type
Cut File Location
N/A
Reference File Location
M:\Method\Project\Job-11794A\SU-13638-13641\SU-13638
Description
Project:
-
Part Number:
13638--
Rev:
-
NYU LANGONE MEDICAL
CENTER KIMMEL PAVILION
JOB 11794A
Drawn
Tolerances:
Finish
METHOD
Initials
Date
STF
6/15/15
-
Material
Comments
Weight
11252.412
lbs.
Flat Pattern Scale
1:12
Unless Otherwise Specified:
Dimensions are in Inches
1 DECIMAL PLACE: .100
2 DECIMAL PLACES: .020
3 DECIMAL PLACES: .005
SHEET 1 OF 1
THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF MODULAR SERVICES COMPANY. ANY REPRODUCTION IN PART OR AS WHOLE WITHOUT THE WRITTEN PERMISSION OF MODULAR SERVICES COMPANY IS PROHIBITED
NOTE(S):
1.
MEP CLEAR SPACE FOR DIALYSIS BOX SHOWN IN GREEN
2.
CHASE DIMENSIONED FROM CTR LINE OF WALL
Old Rendering With
Out Of Date
Device/Outlet Location
& Size.
Purpose Of Drawing Is
To Show MEP Clear
Space For BIM
Coordination
19.00
1.75
0
1.75
0
METHOD
Reference File Location
M:\Method\Project\Job-11794A\SU-13638-13641\SU-13638
Description
Project:
-
Part Number:
13638--
Rev:
-
NYU LANGONE MEDICAL
CENTER KIMMEL PAVILION
JOB 11794A
Drawn
Initials
Date
STF
6/17/15
-
Material
Comments
MODULAR
SERVICES COMPANY
Tolerances:
Finish
Product Type
Cut File Location
N/A
2.50
2.50
0
19.00
Weight
14996.986
lbs.
Flat Pattern Scale
1:22
Unless Otherwise Specified:
Dimensions are in Inches
1 DECIMAL PLACE: .100
2 DECIMAL PLACES: .020
3 DECIMAL PLACES: .005
SHEET 3 OF 3
GWB PARTITION FINISH ABOVE HEADWALL
OPENING IN PER DETAIL 10/A-635
GWB CEILING
WITH CUTOUT
FOR A42 FIXTURE
WITH REMOVAL OF POCKET,
EXTEND GWB CEILING FINISH TO
INTERSECT GWB PARTITION
APPROPRIATE TRIM TO
INSURE A UNIFORM,
FINISHED GWB EDGE.
To Be
TOP TRIM PIECE FOR LIGHT TO BUTT UP TO SHOWN IN GREEN. Powdercoated
White?
LIGHT SHOWN IN RED. 16
16
LOOKING UP AT THE LEFT SIDE OF A UNIT. TRIM CAN OVERHANG LIKE SHOWN OR BE FLUSH WITH Not To Interfere With Sheetrock Ceiling.
ALUMINUM EXTRUSIONS. Make Sure Wall Sheetrock Can Still Slide
Behind Trim As That Will Be The First
Activity Before Panel Install.
16
Be Mindful Of Same Type Of Overhand Detail At
Bottom Turner Pointed Out Which Will Interfere
With Wall Sheetrock Sliding Behind Trim.
16
SIDE VIEW OF PANEL SYSTEM WITH TOP EXTRUSION WHICH ALLOWS FOR REMOVAL OF PANELS. TOP OF REVEAL AT CEILING LINE WITH TRIM PIECE FOR LIGHT FIXTURE BUTTED TO THE TOP. 8/27/2015
Laminate ­ Kensington Maple ­ 10776
Home (http://www.wilsonart.com/)
High Pressure Laminate (http://www.wilsonart.com/laminate-surfaces)
Design Library (http://www.wilsonart.com/laminate/design-library)
Kensington Maple
KENSINGTON MAPLE 10776
(http://www.wilsonart.com/wishlist/index/add/product/5/form_key/El2eVi8CSwdlHS0A/)
Standard HPL Finish
MATTE FINISH 10776-60
LAMINATE
This pattern is part of the Wilsonart Contract Collection.
This is a directional design.
10
Features
http://www.wilsonart.com/kensington­maple­10776
1/6
8/27/2015
Laminate ­ Kensington Maple ­ 10776
Available Product Types
Where To Buy
Commercial Buyers
Find your nearest Distributors
Enter Zipcode
Find
Homeowners
Find your nearest Dealers
Enter Zipcode
Find
Order a Free Sample*
http://www.wilsonart.com/kensington­maple­10776
2/6
2/16/2015
DecoMetal® ­ Brushed Pewter Aluminum
DecoMetal®
(http://www.formica.com/en/us/products/decometal)
M2032
Brushed Pewter Aluminum
STANDARD FINISHES
DecoMetal (Finish Code: 99)
Compare finishes
WHERE TO BUY
(HTTP://WWW.FORMICA.COM/EN/US/WHERE­TO­BUY)
The Features icons below are for general reference only. For more specific product information, see Documents section below.
Swatches are a representation and may vary in color from the final product. Please obtain a sample of the product before making
a final selection.
Specification
Features
FIRE RESISTANT
Size and grade guide
Standard
Grade 85
10' x 4'
DECOMETAL (FINISH CODE: 99)
8' x 4'
DECOMETAL (FINISH CODE: 99)
Sheet sizes shown in feet
Thickness
http://www.formica.com/en/us/products/decometal/m2032#
1/2
The Following Are The
Mock-Up Review Notes
By NBBJ, TCCO, &
Modular Services
See Pages 8-16 For Turner &
MSC Comments To NBBJ
Meeting Notes Dated 11/11/15
Meeting:
NYULMC - KIMMEL PAVILION
MODULAR HEADWALL / FOOTWALL
Date:
10/29/2015
Rev. 11/11/15
Location:
25th Street Mock Up
Time:
2:00pm-4:00pm
Purpose:
Modular Mock Up Installation Review
Project #:
100636.00
Attendees:
NYU: Daniel Bensimon, Paul Natter, Sue Kostner, John Englert Modular: Mike Claricurzio
Turner: Chris Brooten, Adam D’Auguste Ennead: Duncan Hazard, Kevin Krudwig
JBB: Vincent Rotoli, Samantha Bruno NBBJ: John Flanagan, Bryan Langlands
Item Notes
1. 1
Please review and address the following issues relating to fabrication /
.
MEP systems / pathways of the mock up installation as follows:
0
a. Device / Outlet Alignment: All devices to be aligned horizontally
and vertically on their centerlines. Currently the medical air or
vacuum outlets (by device manufacturer) are not centered on
their cover plate (fabricated by Modular). Modular to adjust
installation as required to insure devices are centered on their
cover plates and installed in the headwall with all device and
outlet centerlines aligned. (Photos 1 & 2)
Photo 1
Photo 2
b. Vacuum Piping Installation: While the overall piping installation
is in accordance with previous review comments, the current 90⁰
piping offset at the connection to outlet is not acceptable.
Modular to modify the piping to utilize 45⁰ piping connectors.
(Photos 3)
Action By
Modular
Status
Item
Notes
Action By
Status
Photo 3
c. Emergency Power Junction Box: There was concern expressed
that the there is insufficient space in the current
compartmented junction box to insure ease access to all of the
required wiring connections. Modular is to increase the width of
the back box by 2 1/2” to 3” and increase the depth of the box
by approximately 1” if possible. The increase in width is
achievable however Turner and Modular will need to confirm id
increase in depth is achievable given constraints of adjacent
bade building pippin risers for the dialysis box, etc. (Photo 4)
Photo 4
11/11/2015
Page 2 of 7
Item
Notes
Action By
Status
d. Piping / Dissimilar Metal Isolation: Overall concern was
expressed that all dissimilar metal to metal conditions are
properly isolated, that the isolation mesh is of sufficient length
and that the mesh is properly secured to insure it will not sag or
slim over the headwalls serviceable life. Modular is to review all
conditions to insure the length are sufficient (Photo 5) and that
all areas are properly isolated (Photos 6).
Photo 5
Photo 6
e. Pipe Clamps / Supports / O-Ring Isolation: The current use of
the “Proflow” type of pipe clamps is acceptable to Facilities, as
long as they are adequately secured to the adjacent framing.
Modular is to provide individual round cut outs in the steel
framing, with the addition of the plastic O-ring type gaskets in
lieu of current larger rectangular un-gasketed openings. (Photos
7 & 8)
Photo 7
11/11/2015
Photo 8
Page 3 of 7
Item
Notes
f.
Action By
Status
Dialysis Box Drain / Piping Pathways: Dialysis box installation
was not complete nor was it reviewed as part of the mock-up
observations. Dialysis box shall have a right hinged gasketed,
lockable door. Modular and Turner to confirm that waste line /
trap and water supplies for dialysis box have been sufficiently
coordinated with electrical conduits to insure proper clearances
and pathways have been maintained. Modular and Turner to
also confirm that the dialysis box plumbing services, riser and or
lateral runs of the piping, have been fully coordinated: framing
openings properly sized, sufficient cavity space, etc. have been
provided, and piping support and installation methods
incorporated.(Photos 9 & 10) Revised per JBB comment 11/2/15.
Photo 9
Photo 10
g. Aluminum Perimeter Trim: Concern was expressed about some
minor flexing or looseness of perimeter aluminum trim. Modular
to review the tolerance on the “shelving standard” type
connectors utilized to secure the vertical aluminum trim as well
horizontal base trim. An additional screw will need to be added
at the top of each vertical to insure they remain tightly secured
over time. (Photos 11 & 12)
11/11/2015
Page 4 of 7
Item
Notes
Action By
Photo 11
Status
Photo 12
2. 1The following design /aesthetic comments were noted, please review
.and respond as required:
1
Modular
a. Headwall Horizontal Equipment Rails: There appears to be a bit
of play in some locations between the back of the fixed
horizontal rails and the face of the laminate panels. The rails
need to be fabricated to allow easy removal of the individual
panels, however Modular is to review current tolerances to
insure a consistent joint where the two materials intersect. In
general the overall aesthetic appearance of the headwall is very
good. (Photo 13)
Photo 13
11/11/2015
Page 5 of 7
Item
Notes
Action By
Status
b. Footwall Horizontal Laminate Butt Joints: The current laminate
to laminate butt joint is not acceptable as it is not a flush
condition. This may have to do with how the unit was shipped to
get into the 25th Street mock up, however Modular to review
and confirm type of joint to be used to unsure a flush condition.
The footwall should be treated like a full height wall panel as it
will not need to be demounted like the headwall. (Photo 14)
Modular also to confirm if it is possible to achieve a consistent
laminate “wood grain” match vertically.
Photo 13
c. Perimeter Trim and Interior Trim at Footwall: The mitered
corners in the trim are not flush or uniform. Modular to confirm
the joint type (Butt joint of miter) that will insure the most
uniform and consistent connection between the horizontal and
vertical trims. (Photos 14 & 15) Modular and Turner need to also
confirm the tolerance required where the footwall trim meets
the adjacent GWB wall surface. Modular to confirm how the trim
is secured to the footwall given it does not need to be
demountable.
11/11/2015
Page 6 of 7
Item
Notes
Action By
Photo 14
Status
Photo 15
This documents our understanding of the issues discussed. If any participant takes exception to the
information noted above please inform the writer.
Submitted:
11/11/2015
10.30.2015
John C. Flanagan, AIA
Page 7 of 7
Turner & Modular Services Company comments dated 11/17/15.
1A.
John Flanagan asked if we can change the med gas trim rings so that the gas outlets are
centered vertically. There is more stainless steel exposed on the bottom. See attached
photo. Turner – This will not be a problem, all devices will be centered on their cover plates,
and all device/outlet centerlines will all line up. MSC – Confirmed, we will tighten up the
tolerance for the clearance opening in the trim plate and center the cut out. MSC will send out
replacements for the mockup for review and approval.
1B.
Danny Bensimon is requesting that we use two 45’s on vacuum line offsets.
Turner – This will not be a problem. MSC – See below backup attachments for a picture of two
45’s connected to a ½” pigtail.
1C.
Paul Natter asked if the large junction box located in the bottom, center of the headwall be
increased in size. Turner – The no fly zone for the dialysis box risers were heavily coordinated,
and cannot be adjusted more than ½” wider, and then 2” lower. This would ensure there are no
hits with the already drawn/coordinated field piping in 3D. MSC – The junction box will be
increased by ½” w and extended 2” lower to create a larger junction box compartment. Aside
from this item, it is our understanding that the pull boxes, junction boxes, conduit, conduit
connectors, conduit clamps, and wire were all approved as is.
1D.
Danny Bensimon is requesting that the yellow mesh that we apply to the copper for dissimilar
metals be longer and secured in place (possibly taped). The copper is also touching the
horizontal bracing down by the outlet so we need to add the mesh in this location as well.
Turner – This will not be a problem. MSC – See below backup attachments, we will protect
and/or tape on in requested areas by using 3M #472 type tape which is listed for separation of
dissimilar metals.
1E.
Change large cut outs of the studs for the med gas lines to individual round openings. MSC –
See page #7 of Supplemental File document which shows our preferred method of using the
circle clearance opening in our steel vertical supports along with the black plastic bushing to
protect against dissimilar metals as the primary function. If we need to add the proflow clamps
for additional support we can look at this.
1F.
Danny Bensimon asked if the conduit that crosses directly beneath the Dialysis box is in the way
of the drain or feed lines. Turner – This has been coordinated, and there will be no clashes. MSC
– Please see below backup attachments for dimensional data, there will be adequate space.
1G.
Add an additional fastener to the top of the side trim, and all tolerances adjusted and
tightened. Turner – This will not be a problem. MSC – Confirmed.
2A.
Gap between the panel and the equipment rail. Turner – This will not be a problem. MSC –
Confirmed, we will provide the necessary shims to push the panel towards the face of the
extrusion.
2C.
Perimeter & Interior trim at footwall. Turner – Modular still reviewing footwall design and if
additional fasteners would be required for interior trim. MSC – The footwall design and scope
of installation is being reviewed separately. MSC confirms that the inner trims can be changed
to have a “flat” joint (non-mitered). The horizontal joint will butt up to the vertical due to the
trim design.
2B.
Butt joint quality & lining up wood grain lines up above and below the field seams. Turner –
Modular still reviewing footwall design, but since the footwall does not need to be
demountable, all joints whether they be vertical or horizontal, can utilize splines/biscuits & glue
to ensure butt joints align. Expansion/contraction of wood due to humidity at butt joint design
is still a concern over time. MSC – Initially it was thought to be possible though hard to
guarantee through large costs for material waste & labor efforts, but then after speaking with
Wilsonart, they confirmed there is variation from sheet to sheet in the laminate when the
material is spliced together at their factory because of roll sizes and running it cross grain.
3
Vinyl Tape
472
Technical Data
Product Description
3M™ Vinyl Tape 472 is backed with a pigmented rubber adhesive for abrasion
protection and many outdoor weathering applications.
Product Construction
Backing
Adhesive
Color
Standard Roll Length
Vinyl
Pigmented rubber
Black
36 yds. (33 m)
Typical Physical
Properties
Note: The following technical information and data should be considered representative
or typical only and should not be used for specification purposes.
ASTM Test Method
Adhesion to Steel:
Features
23 oz./in. width (25 N/100 mm)
D-3330
Tensile Strength at Break:
32 lbs./in. width (560 N/100 mm)
D-3759
Elongation at Break:
270%
D-3759
Backing Thickness:
9.0 mils (0.23 mm)
D-3652
Total Tape Thickness:
10.4 mils (0.26 mm)
D-3652
Temperature Use Range:
Up to 225°F (107°C)
• Best results are attained when applied to clean, dry surface at temperatures
between 60° to 80°F (16° to 27°C).
• Thick backing is ideal where heavy abrasion resistance is anticipated.
• Temperature resistance to 225°F (107°C).
• Pigmented adhesive will stain some surfaces. Testing by the user is recommended
to determine suitability in the proposed application.
• Resists most common solvents, care should be taken to avoid ketones, chlorinated
hydrocarbons, and esters, found in lacquer thinners, degreasers, paint strippers,
etc. which may cause the backing to swell or curl.
Application Ideas
• Heavy duty protection and abrasion resistance.
• Splicing and patching.
• Outdoor weathering applications.
• Electroplating.
• Dissimilar metal separation.
• Sealing barrier films and containers.
• Protecting metal from corrosion (above or below ground).
3M™ Vinyl Tape
472
Storage
Store under normal conditions of 60° to 80°F (16° to 27°C) and 40 to 60% R.H. in
the original carton.
Shelf Life
To obtain best performance, use this product within 18 months from date of
manufacture.
Product Use
All statements, technical information and recommendations contained in this document are based upon
tests or experience that 3M believes are reliable. However, many factors beyond 3M’s control can affect
the use and performance of a 3M product in a particular application, including the conditions under
which the product is used and the time and environmental conditions in which the product is expected to
perform. Since these factors are uniquely within the user’s knowledge and control, it is essential that the
user evaluate the 3M product to determine whether it is fit for a particular purpose and suitable for the
user’s method of application.
Warranty and
Limited Remedy
Unless stated otherwise in 3M’s product literature, packaging inserts or product packaging for individual
products, 3M warrants that each 3M product meets the applicable specifications at the time 3M ships the
product. Individual products may have additional or different warranties as stated on product literature,
package inserts or product packages. 3M MAKES NO OTHER WARRANTIES, EXPRESS OR IMPLIED,
INCLUDING, BUT NOT LIMITED TO, ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS
FOR A PARTICULAR PURPOSE OR ANY IMPLIED WARRANTY ARISING OUT OF A COURSE OF
DEALING, CUSTOM OR USAGE OF TRADE. User is responsible for determining whether the 3M product
is fit for a particular purpose and suitable for user’s application. If the 3M product is defective within the
warranty period, your exclusive remedy and 3M’s and seller’s sole obligation will be, at 3M’s option, to
replace the product or refund the purchase price.
Limitation of Liability
Except where prohibited by law, 3M and seller will not be liable for any loss or damage arising from the
3M product, whether direct, indirect, special, incidental or consequential, regardless of the legal theory
asserted, including warranty, contract, negligence or strict liability.
ISO 9001: 2000
This Industrial Adhesives and Tapes Division product was manufactured under a 3M quality system registered to ISO 9001: 2000 standards.
3
Industrial Business
Industrial Adhesives and Tapes Division
3M Center, Building 21-1W-10, 900 Bush Avenue
St. Paul, MN 55144-1000
800-362-3550 • 877-369-2923 (fax)
www.3M.com/industrial
Recycled Paper
40% pre-consumer
10% post-consumer
Printed in U.S.A.
©3M 70-0709-5017-8
(2001 / 7/05)
SIDE VIEW WITH WHITEHALL DIALYISIS BOX DRAIN OUTLET AND CONDUIT PIECE IN QUESTION BOTTOM VIEW OF WHITEHALL DIALYSIS BOX DRAIN PIPE AND CONDUIT PIECE IN QUESTION CENTER TO CENTER OF DIALYSIS DRAIN TO CONDUIT IS 2.384 INCHES TOP VIEW OF DIALYSIS INLET CONNECTIONS The Following Is The
Shop Drawing Set
Which Was Reviewed
For Mock-Up
Construction Only
NYU Kimmel Pavilion
0001-102513-1 Acute & ICU Headwall & Footwall REV1
Submittal Review
07.22.2015
REVIEW KEY NOTES:
1. Comply with all requirements of Section 10 2513 PATIENT HEADWALLS AND 01 3300 SUBMITTAL
PROCEDURES. It is understood that this is a preliminary MOCK-UP coordination submission for
initial review of the ICU Room mock up and further submissions may be required to insure
adequate coordination and address any mock up comments.
2. Provide complete LEED submittal for review in accordance with Part 1.5 of the specification.
3. The client has requested that the dialysis box be located as high above the finish floor as possible.
Ideally the top of the stainless steel enclosure / cover flange would be 1” minimum below the
equipment rail. Please confirm this is sufficient room for installation and construction / fabrication
tolerance for laminate clad panel assembly. The 31.5” dimension from headwall centerline to
centerline of the dialysis box is approved.
4. The client has confirmed that the initial mock up is to be an ICU headwall assembly.
5. Nurse Call back box to be installed as noted in this submittal for the initial ICU mock up review.
Please note that the nurse call location and requirements are still under review by the client.
6. Electrical device colors currently under review by client to insure conformance with current hospital
standards. Color and device design style to be reconfirmed under separate cover.
7. Vertical location of electrical devices is acceptable as shown, horizontal location needs to be
coordinated with final AV equipment system components and monitor selection.
NYU Kimmel Pavilion
0001-102513-1 Acute & ICU Headwall & Footwall REV1
Submittal Review
07.22.2015
8. Metal laminate type and grain direction is confirmed and was previously by NBBJ.
9. Please note attached SKA-151 for Patient Bedroom 100 on floors 8 through 18, the south side of the
headwall assembly has been furred out in order to resolve a beam / riser conflict reviewed as in BIM
coordination process, coordinate with TCCo as required.
10. Final laminate TBD, laminates to be reviewed and confirmed with client once installed at the 25th
Street Mock Up.
11. Anodized aluminum finish previously approved. The only detail reviewed or approved under
submittal “0003-102513-0 Headwall & Footwall Trim Details” was the custom perimeter trim
extrusion. Previously requested section details should be provided prior to final fabrication.
12. TCCo Note: EEG face plate and device types to be confirmed / coordinated with equipment vendor.
Cover plate finish to be brushed stainless steel to match adjacent devices.
13. Contract documents call for entire area of recess to receive blocking (sheet metal backing plates),
this also needs to be coordinated with final equipment selection and placement. Coordinate with
note 7.
END OF NBBJ REVIEW
Project Name:
NYULMC – Kimmel Pavilion
Project No:
14506.A.000
Description:
0001-102513-1 Acute & ICU Headwall & Footwall REV1
Manufacturer:
Various
Submission No:
Submitted by:
0001-102513-1
Modular Services Co.
JAROS, BAUM & BOLLES
Consulting Engineers
80 Pine Street
New York, New York 10005
NO EXCEPTIONS TAKEN
MAKE CORRECTIONS NOTED
REVISE AND RESUBMIT
REJECTED
Checked by
NK/JK/VR
Date
07/23/2015

X


Engineer’s review is for general compliance
with the design concept and contract
documents. Markings or comments or the lack
thereof shall not be construed as relieving the
Contractor from compliance with the project
plans and specifications. The Contractor
remains responsible for details and accuracy,
for confirming and correlating all quantities
and dimensions, for selecting fabrication
processes, for techniques of construction, for
performing his work in a safe manner, and for
coordinating his work with that of other trades.
JB&B Comments:
1.
2.
3.
4.
5.
All receptacles shall be hospital grade with an illuminated face.
All normal receptacles shall be gray in color.
Show conduit routing and stub-ups from junction boxes within headwall.
All emergency circuiting shall utilize hard pipe conduit.
Vacuum piping connection from plumbing system shall be made so that the end of header rises up
directly from an outlet. Refer to Podium headwall submittal for vacuum piping arrangement.
6. TCCo. to coordinate junction box grounding requirements with the electrical contractor.
7. Normal and emergency lighting to utilize separate junction boxes.
8. See submittal for additional comments.
NYULMC Kimmel Pavilion
* Submittal Transmittal
Project # 130002
[For Reviewer]
FDR Drive 34th Street
New York, NY 10016
Date:
Telephone: 212-686-1191
7/7/15
Transmittal No: 6040
John Flanagan
Transmitted To:
Turner Construction Co.
2 Rector Street - 25th Floor
New York, New York 10006
Tel: 646-416-5781
Fax:
314 East 34th Street
6th Floor
New York, NY 10016
Tel: 212-686-1191
Fax:
0001 - 102513 - 1
Qty
001
Spec
102513
Christopher Brooten
Transmitted By:
NBBJ Architects
Submittal Package No
Item
July 07, 2015
Fax:
Description
Due Date
Acute & ICU Headwall & Footwall Submittal Package REVISION 1
7/21/15
Sub
Section
Headwall/Foo
twall
Item #
20579
Rev Type
1
Shop Drawings
Description
Notes
Item Action
AP AN RR RJ
Acute & ICU Headwall &
Footwall Submittal Package
REVISION 1
AP=Approved
AN=Approved as noted
RR=Revise and resubmit
RJ=Rejected
Cc:
Company Name
Contact Name
Fax Number
Copies
Notes
Remarks
Approved as noted version needed for release of full scale mock- up ONLY. Please advise whether the mock-up is to be ACUTE of ICU.
Final review of the drawings can be done after seeing the mock-up.
4
Signature
TCCO - Submittal Transmittal - For Reviewer_V4xi.rpt
RPT Revised: 5/23/12
Signed Date
Turner Construction Co.
Page 1 of 1
ARCHITECTS REVIEW
COMMENTS AND KEY
NOTES IN BLUE.
Notes
Red: NBBJ
Green: Turner
Blue: JBB
Re-Submittal #2 For Approval
Method™ Headwall System
7500 Series
Tower Units
RECEIVED
07/6/2015
TURNER CONSTRUCTION
NYULMC
Kimmel Pavilion
For
New York University Langone Medical Center
FDR Drive 34th Street
New York, NY 10016
Kimmel Pavilion Project
Purchase Order #4700044758
Turner Construction Company
375 Hudson Street
New York, NY 10014
Prepared For:
Manhattan Medical
Mike Claricurzio
456 Maple Avenue
Doylestown, Pennsylvania 18901
267-614-1811
07/7/2015
Chris Brooten
Prepared by:
Modular Services Company
Justin Smith
500 East Britton Road
Oklahoma City, OK 73114
888-687-0938 Ext 7247
888-204-9768 fax
MSC Job #11794A
July, 2015
0001-102513
-1
20579
1
Approved As Noted Stamp Needed For
MSC To Fabricate One Full Scale Patient
Room Mock-Up
This Will Also Allow MSC To Begin To 3D
Draw The Headwall/Footwalls & Upload
Into Project BIM Model
500 East Britton Road Oklahoma City, OK 73114 888.687.0938 FAX 888.204.9768 www.modularservices.com
TableofContents–TowerUnitSubmittals
Specifications Chassis Construction ................................................................................................................................. 2 Device Mounting Panels .................................................................................................................. 2 Horizontal Accessory Channels, Anodized Reveals & Perimeter Trim ................................ 2 Medical Gas Outlets ............................................................................................... 3 Electrical Wiring & Equipment ............................................................... 3‐4 Provisions for Equipment ............................................................ 4 Accessories ..................................................................... 5 Product Cut Sheets Beacon Diamondcare DISS Outlets ........................................................................................................ 6‐9 Hubbell Hospital Grade Illuminated Receptacles .......................................................................... 10 GCX Type Monitor Channel ............................................................................................... 11 Vacuum Bottle Slide, Channel Mount .................................................................. 12 Verification List (Acute Care & ICU – Headwall and Footwall) Verification Items Previously Confirmed in Re‐Submittal #1 ............................................................. 13‐15 Outstanding Verification Items & Customer Approval …………………………………………………………15‐16 MSC Submittal Drawings Acute Care Elevation, Legend & Wiring Diagram............................................................................... 17‐18 ICU Elevation, Legend & Wiring Diagram ................................................................................. 19‐20 ICU Footwall Elevation, Legend & Wiring Diagram........................................................... 21 Acute Care Footwall Elevation, Legend & Wiring Diagram ................................. 22 MEP Drawings for Dialysis Plumbing………………………………………………23‐24 Laminate Finishes Wilsonart and Formica Color Selections for Headwalls and Footwalls ............................................. 25‐26 SPECIFICATIONS
I.
HEADWALL ASSEMBLY GENERAL CONSTRUCTION
A.
CHASSIS CONSTRUCTION
THE MEDICAL GAS AND ELECTRICAL SERVICE ASSEMBLY IS CONSTRUCTED OF
HEAVY GAUGE 6063-T5 ALLOY, EXTRUDED ALUMINUM PROFILES AND 16 GAUGE
GALVANIZED STEEL INTERNAL SUPPORTS.
THE BACKBOX HOUSINGS OF THE UNIT ARE CONSTRUCTED OF 16 GAUGE
STEEL. METAL BARRIERS ARE PROVIDED INSIDE THE HOUSINGS TO SEGREGATE
SERVICES AS REQUIRED. THE HOUSINGS ARE ATTACHED TO A 16 GAUGE
METAL FRAME.
THE UNIT WILL BE PRE-PIPED AND PRE-WIRED TO CONNECTION POINTS AS
INDICATED ON THE ENCLOSED ELEVATION DRAWINGS.
B.
DEVICE MOUNTING PANELS
DEVICE MOUNTING PANELS CONSIST OF VERTICAL GRADE, DECORATIVE HIGH
PRESSURE LAMINATE FACING, A 3/4” THICKNESS HIGH DENSITY, FIRE
RETARDANT PARTICLE BOARD CORE AND A 0.022" THICKNESS HIGH PRESSURE
LAMINATE BACK. EACH PANEL MOUNTS DIRECTLY TO THE CHASSIS OF THE UNIT
AND DEVICE COVERPLATES ARE ATTACHED DIRECTLY FROM THE FACE FOR
EASE OF REMOVAL AND SERVICING OF DEVICES.
BASES ARE TO BE COVERED WITH A COVE BASE OR OTHER MATERIAL (BY
OTHERS) DURING INSTALLATION TO MATCH THE FLOOR TRIM USED AROUND
THE PERIMETER OF THE ROOM.
C.
HORIZONTAL ACCESSORY CHANNELS
HORIZONTAL ACCESSORY CHANNELS ARE CONSTRUCTED OF EXTRA-HEAVY
GAUGE 6063-T5 ALLOY EXTRUDED ALUMINUM AND ARE CLEAR ANODIZED.
HORIZONTAL ACCESSORY CHANNELS ARE INTERNAL TYPE AND ARE FLUSH
WITH THE FRONT FACE OF THE DEVICE MOUNTING PANELS. THE FRONT AND
REAR LOWER EDGES OF EACH HORIZONTAL ACCESSORY CHANNEL ARE
RADIUSED FOR EASE OF CLEANING.
D.
ANODIZED ALUMINUM REVEALS
REVEALS ARE TO HAVE A CLEAR ANODIZED ALUMINUM FINISH. THE REVEAL
SIZE IS ½”.
E.
PERIMTER TRIM
Per NBBJ Email About 6-17 PreNET
CUSTOM TRIM TO HAVE AN ANODIZED ALUMINUM FINISH AS APPROVED
DURING THE SUBMITTALS AND MOCK-UP PROCESS.
11
II.
MEDICAL GAS OUTLETS
MEDICAL GAS OUTLETS ARE BEACON MEDAES BRAND “DIAMONDCARE”, DISS STYLE
THREADED TYPE. PLEASE SEE ENCLOSED CATALOG DATA.
THE MEDICAL GAS OUTLETS ARE TYPICALLY PROVIDED WITH THE STYLE TO MATCH
THOSE CURRENTLY BEING USED IN THE FACILITY SO THAT THE SUCTION/OXYGEN
THERAPY EQUIPMENT CURRENTLY BEING USED WILL BE COMPATIBLE. OUTLET TYPES
AVAILABLE INCLUDE LATCH-KEY (CHEMETRON) STYLE QUICK CONNECT, DIAMOND
(MEDAES/OHMEDA) STYLE QUICK CONNECT, GEOMETRIC (PURITAN BENNETT) STYLE
QUICK CONNECT, AND DISS STYLE THREADED TYPE. PLEASE SEE ENCLOSED
CATALOG DATA.
MEDICAL GAS OUTLETS ARE PRE-MANIFOLDED (EXECPT VACUUM) WITH TYPE L
COPPER TUBING FOR MEDICAL GAS SYSTEMS AND WILL TERMINATE WHERE
INDICATED ON THE ENCLOSED DRAWINGS. SEE ENCLOSED DRAWINGS FOR TUBING
DIAMETERS AT TERMINATION POINTS.
ALL TUBING AND FITTINGS ARE CLEANED IN ACCORDANCE WITH NFPA 99 AND CGA G-4.1
REQUIREMENTS. ALL JOINTS ARE MADE WITH SILVER BRAZING ALLOY WITH A
MELTING POINT OF AT LEAST 1000° BY BRAZERS CERTIFIED TO ASSE6010 STANDARD
FOR MEDICAL GAS SYSTEM INSTALLERS. A CONTINUOUS NITROGEN NF PURGE IS
MAINTAINED DURING ALL BRAZING OPERATIONS TO PREVENT THE FORMATION OF
COPPER OXIDE. TUBING ENDS ARE SECURELY CAPPED AND PROPERLY IDENTIFIED.
ALL COPPER TUBING IS PROTECTED FROM CONTACT WITH DISSIMILAR METALS TO
PREVENT GALVANIC CORROSION.
III.
ELECTRICAL WIRING AND EQUIPMENT
A.
WIRING
UNITS ARE COMPLETELY PRE-WIRED WITH ALL SERVICE CONNECTIONS
TERMINATING IN BARRIERED COMPARTMENTS AS INDICATED ON THE
ENCLOSED DRAWINGS. LINE VOLTAGE CURRENT CARRYING CONDUCTORS
ARE #10 SOLID COPPER TYPE FOR NORMAL AND EMERGENCY POWER CIRCUITS.
ALL WIRING COMPLIES WITH NFPA 70 AS MINIMUM STANDARDS. ALSO ALL
ELECTRICAL COMPONENTS ARE U.L. LISTED. UNIT IS LISTED AS A
PREFABRICATED ASSEMBLY.
A COPPER GROUND BUS IS PROVIDED IN THE SERVICE CONNECTION
COMPARTMENT THAT WILL ACCEPT #6 TO #14 AWG GROUNDING CONDUCTORS.
ALL POWER RECEPTACLES HAVE A COPPER GROUND CONDUCTOR ATTACHED
TO THE GROUND SCREW OF THE RECEPTACLE AND THE GROUND WIRE TIE
POINT TO ENSURE THAT THE STRUCTURE IS NOT USED AS THE SOLE GROUND
PATH BETWEEN THE POWER RECEPTACLES AND THE GROUND BUS. ADDITIONAL
BUSES WITHIN THE UNIT ARE PROVIDED AS NECESSARY FOR GROUND WIRE
TIE POINTS.
6
B.
IV.
WIRING DEVICES
1.
NORMAL POWER ILLUMINATED DUPLEX RECEPTACLES
NEMA 5-20R, 125 VOLT A.C., 20 AMP, HOSPITAL GRADE.
- 8300 GRAY,
2.
EMERGENCY POWER ILLUMINATED DUPLEX RECEPTACLES - 8300 RED,
NEMA 5-20R, 125 VOLT A.C., 20 AMP, HOSPITAL GRADE.
3.
NORMAL POWER SAFETY-TYPE W/ LED INDICATOR DUP. RECEPTACLES 8300 GRAY, NEMA 5-20R, 125 VOLT A.C., 20 AMP, HOSPITAL GRADE.
4.
EMERGENCY POWER SAFETY-TYPE W/ LED INDICATOR DUPLEX
RECEPTACLES - 8300 RED, NEMA 5-20R, 125 VOLT A.C., 20 AMP, HOSPITAL
GRADE.
PROVISIONS FOR EQUIPMENT BY OTHERS
A.
NURSE CALL PROVISIONS
AN APPROPRIATELY SIZED RACEWAY AND COMPARTMENT ARE PROVIDED FOR
THE INSTALLATION OF THE NURSE CALL PATIENT STATION AND ITS
ASSOCIATED WIRING.
B.
MULTI-PIN BED RECEPTACLE PROVISIONS
A SINGLE GANG ISOLATED COMPARTMENT AND RACEWAYS AS APPROPRIATE
ARE PROVIDED FOR INSTALLATION OF THE MULTI-PIN BED RECEPTACLE AND
ITS ASSOCIATED WIRING.
C.
DATA OUTLET PROVISIONS
A SINGLE GANG ISOLATED COMPARTMENT AND RACEWAY EXTENDING FROM
THIS COMPARTMENT TO THE INCOMING SERVICE CONNECTION POINT ARE
SUPPLIED TO ACCOMMODATE THE DATA RECEPTACLE. A MATCHING FACE
PLATE WITH A SINGLE CATEGORY 5, RJ-45 RECEPTACLE IS SUPPLIED BY
MODULAR SERVICES, IF REQUIRED, FOR USE AS THE DATA SYSTEM
RECEPTACLE (WIRING TO THE RECEPTACLE IS TO BE SUPPLIED BY OTHERS).
D.
DIALYSIS BOX PROVISIONS
MSC TO PROVIDE THE APPROPRIATE PROVISION AND BRACING FOR
INSTALLATION OF THE DIALYSIS BOX (PROVIDED AND INSTALLED BY OTHERS).
EEG MONITOR
12
V.
ACCESSORIES
A.
MOUNTING CHANNEL FOR PHYSIOLOGICAL MONITOR SWIVEL AND TILTING
MOUNTING CHANNEL AND BRACING SHALL BE FURNISHED TO ACCOMMODATE
GCX BRAND HEART MONITOR TILT/SWIVEL BRACKET. INTERNAL BRACING OF
MODULAR HEADWALL WILL SUPPORT HEART MONITORS WEIGHING UP TO 80
POUNDS. PLEASE SEE ENCLOSED CATALOG DATA.
B.
520-2703 VACUUM BOTTLE SLIDE, PROVIDER CHANNEL MOUNT.
PLEASE SEE ENCLOSED CATALOG DATA.
Page 1 of 3
4/18/06
DiamondCare® Medical Gas Quick-Connect Outlets for OEM
SPECIFICATION
Medical Gas Quick-Connect Outlet
The Medical Gas Outlets shall be gas specific, permanently
labeled for the services indicated and shall accept only
corresponding DISS, Puritan Bennett, Medaes® or
Chemetron® manufacturer's-style, quick-connect adapters.
The outlets shall be UL listed, CSA certified, and be fully
compliant with the latest edition of NFPA 99. Outlets shall be
tested for flow, leaks and cleaned for oxygen service prior to
shipping. The outlets shall be made in the U.S.A.
Outlet Design
A complete outlet shall consist of a gas-specific rough-in
assembly and a matching gas-specific front body assembly.
The outlet design shall allow for the change from one style of
quick-connect or DISS front body to another without any
changes or modifications to the rough-in assembly.
Rough-in Assembly
The rough-in assembly includes a gas-specific, plated steel,
mounting bracket designed to permit on-site location and
installation. The gas inlet of the outlet body shall be DISS,
copper tube or hose barb fitting connection. A secondary
valve shall be included in all pressure service rough-in
assemblies for standing pressure testing of the distribution
system and to prevent gas flow (except vacuum and WAGD)
when the front body is removed for service. Vacuum and
WAGD rough-ins shall be provided with a pressure test plug
for pressure and vacuum testing.
Front Body Assembly
The front body assembly shall be indexed to the
corresponding gas service rough-in assembly to avoid
accidental cross connection. Front bodies shall have
permanent color-coded gas service identification clearly
indicated on the front surface.
Frontbody Assembly
Rough-in Assembly
Medaes-type
Diamond®
Quick-Connect
Key Style
Chemtron-type
Latch Index
Quick-Connect
Key Style
DISS
Key Style
Puritan-Bennett-type
Geometric
Quick-Connect
Key Style
Faceplate
(Optional)
P/N 6803-2000-205
Confirmed in previous
submittal
BeaconMedæs Š 14408 W. 105th Street
Lenexa, KS 66215 Š Phone: (913) 894-6058
Fax: (913) 894-6088
OEM
SSB-840-14
Page 1 of 2
31 January 2011
DiamondCare® Console Outlet
DISS Key Style
SPECIFICATION
Console Outlet
The DiamondCare® Console Outlet is available in a DISS
Key Style for each of the medical gas services listed in the
table on page 2. Each console outlet consists of a rough-in
assembly and a frontbody assembly.
Rough-In Assembly
The rough-in assembly is available with a copper inlet
tube (piped backbody) or a DISS male inlet fitting (DISS
backbody) for connection to a gas delivery line. The
piped rough-in assembly includes a 7” (18cm) long, type
K copper, inlet tube for brazing to the gas delivery line.
This inlet tube rotates 360°, which permits alignment with
the gas line. Both the piped and DISS rough-in assemblies
consist of a steel backplate with a non-removable, positive
pin-keying arrangement for each specific gas service. The
specific gas service is stamped into the front of the roughin. Both types of rough-in assemblies include a fully
serviceable secondary check (for pressurized gases) to help
prevent gas flow when the frontbody is removed for service.
Vacuum and WAGD services do not have secondary check
valves, according to NFPA 99 standards.
Frontbody Assembly
The console frontbody consists of a DISS keying disc and
attached barrel assembly, which houses the primary check
valve. The keying disc assembly includes a gas-specific,
positive pin-keying device, is color-coded, and labeled with
the name of the gas service. The barrel assembly includes
brass piston and frontbody check spring, which engage
and seal when a DISS-fitted treatment device is removed
from the outlet.
Features
•
Quick access to primary check valve components.
•
Large, gas-specific, color-coded, keying disc and label.
•
Outlets listed by Underwriters Laboratories® and CSA®
and manufactured in accordance with applicable CGA,
NFPA 99 and CSA® standards.
•
Cleaned for oxygen service, pressure-tested, and
capped prior to shipping.
Product Dimensions
3/8" O.D.
1/2" O.D. on rough-ins
4107 2011 25/4107 2011 27
BeaconMedæs • 1800 Overview Drive, Rock Hill, SC 29730 • Phone: (803) 817-5600 • Fax: (803) 817-5750 • www.beaconmedaes.com
DiamondCare®
Console Outlet DISS
SSB-840-33
SSB-840-33
Page 2 of 2
31 January 2011
Ordering Information
You can order a DiamondCare® Console Outlet as a complete
assembly (rough-in and frontbody), or as individual
assemblies.
Each rough-in and frontbody assembly is
individually packaged.
DISS Key Style
Finish Assembly
Only
Piped Console
Rough-in
Assembly Only
3/8" OD
Piped Console
Rough-in
Assembly Only
1/2" OD
Gas Service(1)
DISS Key Style
Complete
Assembly
O2
‰6803-8110-200
‰4107 2011 56
‰4107 2011 20
‰4107 2011 21
N2O
‰6803-8110-201
‰4107 2011 57
‰4107 2011 22
‰4107 2098 08
Vac
‰6803-8110-202
‰4107 2011 59
N/A
‰4107 2011 25
Air
‰6803-8110-203
‰4107 2011 58
‰4107 2011 23
‰4107 2011 24
CO2
‰6803-8110-204
‰4107 2011 62
‰4107 2011 28
‰4107 2100 40
N2
‰6803-8110-205
‰4107 2011 60
‰4107 2011 26
‰4107 2098 09
WAGD(2)
‰6803-8110-206
‰4107 2011 61
N/A
‰4107 2011 27
O2/CO2 mix
‰6803-8110-207
‰4107 2011 63
‰4107 2011 29
N/A
IAir
‰6803-8110-218
‰4107 2011 67
‰4107 2011 33
N/A
DISS Key Style
Finish Assembly
Only
DISS Console
Rough-in
Assembly Only
Gas Service(1)
DISS Key Style
Complete
Assembly
O2
‰6803-8110-300
‰4107 2011 56
‰4107 2011 87
N2O
‰6803-8110-301
‰4107 2011 57
‰4107 2011 88
Vac
‰6803-8110-302
‰4107 2011 59
‰4107 2011 90
Air
‰6803-8110-303
‰4107 2011 58
‰4107 2011 89
CO2
‰6803-8110-304
‰4107 2011 62
‰4107 2011 93
N2
‰6803-8110-305
‰4107 2011 60
‰4107 2011 91
‰6803-8110-306
‰4107 2011 61
‰4107 2011 92
O2/CO2 mix
‰6803-8110-307
‰4107 2011 63
‰4107 2011 94
IAir
‰6803-8110-318
‰4107 2011 67
‰4107 2011 98
(2)
WAGD
NOTES:
(1) ISO labeled confirmations are also available.
(2) WAGD: Waste Anesthetic Gas Disposal (formerly Evacuation).
Piped Console
DISS Console
CO2, N2, and O2/CO2 services are available in DISS Key Style.
For more information, contact BeaconMedæs Customer Service at
1-888-4MEDGAS (463-3427)
BeaconMedæs
1800 Overview Drive
Rock Hill, SC 29730
Phone: (803) 817-5600
Fax: (803) 817-5750
www.beaconmedaes.com
SSB-840-14
Page 2 of 3
4/18/06
Console Rough-In Assembly
Gas
Service
Color Code Label
Hose Barb
(Background/Text)
Rear Entry DISS
90° DISS
3/8” OD Tube
1/2” OD Tube
O2
White/Green
F
6-236210-00
F
6803-8130-800
F
6-236410-00
F
6803-8138-800H
F
6803-8138-800
N 2O
Blue/White
F
6-236211-00
F
6803-8130-801
F
6-236411-00
F
6803-8138-801H
F
6803-8138-801
AIR
Yellow/Black
F
6-236212-00
F
6803-8130-803
F
6-236412-00
F
6803-8138-803H
F
6803-8138-803
VAC
White/Black
F
NA
F
6803-8130-802
F
6-236413-00
F
NA
F
6803-8138-802
VAC*
White/Black
F
6-236213-00*
F
NA
F
NA
F
NA
F
NA
Nitrogen
Black/White
F
6-236214-00
F
6803-8130-805
F
6-236414-00
F
6803-8138-805H
F
6803-8138-805
Air (ISO)
Black/White
F
6-236216-00
F
NA
F
6-236416-00
F
6803-8138-809H
F
6803-8138-809
Vac (ISO)
Yellow/Black
F
6-236217-00*
F
NA
F
6-236417-00
F
NA
F
6803-8138-810
O2 (ISO)
White/Green
F
NA
F
NA
F
NA
F
6803-8138-808H
F
6803-8138-808
WAGD
Violet/White
F
NA
F
6803-8130-806
F
6-236419-00
F
NA
F
6803-8138-806
WAGD*
Violet/White
F
6-236219-00*
F
NA
F
NA
F
NA
F
NA
CO2
Gray/Black
F
6-236220-00
F
6803-8130-804
F
6-236420-00
F
6803-8138-804H
F
6803-8138-804
O2-CO2
Green/Gray
F
6-236222-00
F
6803-8130-807
F
6-236422-00
F
6803-8138-807H
F
6803-8138-807
*5/16” flexible hose connection. Hose barb assemblies are sized for 1/4” ID hose unless otherwise specified.
Console Front Body Assembly
Gas Service
Color Code Body
(Background/Text)
Puritan Bennett
Type
Medaes-Type
Chemetron-Type
DISS
O2
Green/White
F
6803-8112-800
F
6803-8111-800
F
6803-8113-800
F
6803-8110-800
N 2O
Blue/White
F
6803-8112-801
F
6803-8111-801
F
6803-8113-801
F
6803-8110-801
AIR
Yellow/Black
F
6803-8112-803
F
6803-8111-803
F
6803-8113-803
F
6803-8110-803
VAC
White/Black
F
6803-8112-802
F
6803-8111-802
F
6803-8113-802
F
6803-8110-802
Nitrogen
Black/White
F
NA
F
NA
F
NA
F
6803-8110-805
Oxygen (ISO)
White/Green
F
6803-8112-808
F
6803-8111-808
F
6803-8113-808
F
6803-8110-808
Air (ISO)
Black/White
F
6803-8112-809
F
6803-8111-809
F
6803-8113-809
F
6803-8110-809
Vac (ISO)
Yellow/Black
F
6803-8112-810
F
6803-8111-810
F
6803-8113-810
F
6803-8110-810
WAGD
Violet/White
F
6803-8112-806
F
6803-8130-806
F
6803-8113-806
F
6803-8110-806
Gray/Black
F
NA
F
NA
F
6803-8113-804
F
6803-8110-804
Green/Gray
F
NA
F
NA
F
6803-8113-807
F
6803-8110-807
CO2
O2-CO2
BeaconMedæs Š 14408 W. 105th Street
Lenexa, KS 66215 Š Phone: (913) 894-6058
Fax: (913) 894-6088
Straight Blade Devices
15 and 20 Ampere, 125 Volts
2 Pole, 3 Wire Grounding
IP20
HBL®
SUITABILITY
Extra Heavy Duty
Hospital Grade Receptacles
15A 125V
NEMA 5-15R
UL CSA
0.5 HP
20A 125V
NEMA 5-20R
UL CSA
1 HP
Duplex
Description
Color
Catalog Number
Flush, thermoplastic polyester face,
back and side wired.
Black
Blue
Brown
Gray
Ivory
Light Almond
Red
White
HBL8200BK
–
HBL8200
HBL8200GY
HBL8200I
HBL8200LA
HBL8200RED
HBL8200W
–
HBL8300BL
HBL8300
HBL8300GY
HBL8300I
HBL8300LA
HBL8300RED
HBL8300W
Flush, LED illuminated face,
back and side wired.
Gray
Ivory
Red
White
HBL8200ILGY
HBL8200ILI
HBL8200ILR
HBL8200ILW
HBL8300ILGY
HBL8300ILI
HBL8300ILR
HBL8300ILW
Tamper-Resistant receptacle
with wire leads. Complies with
requirements of NEC® article
517-18(c).
Brown
Gray
Ivory
Light Almond
Red
White
HBL8200SGA
HBL8200SGGYA
HBL8200SGIA
HBL8200SGLA
HBL8200SGRA
HBL8200SGWA
HBL8300SGA
HBL8300SGGYA
HBL8300SGIA
HBL8300SGLA
HBL8300SGRA
HBL8300SGWA
Isolated ground∆.
Orange
Red
IG8200
IG8200R
IG8300
IG8300R
6
Correctly Changed to Gray
HBL8200GY
HBL8300SGA
MRI Receptacle, Duplex
Description
Color
Catalog Number
MRI receptacle, flush, thermoplastic
polyester face, back and side wired.
Ivory
Light Almond
Red
White
HBL8200IMRI
HBL8200LAMRI
HBL8200RMRI
HBL8200WMRI
HBL8300IMRI
HBL8300LAMRI
HBL8300RMRI
HBL8300WMRI
Slender/Compact, Duplex
Description
Color
Catalog Number
Flush, thermoplastic polyester face,
back, and side wired.
Fed. Spec. verified.
Brown
Gray
Green
Ivory
Light Almond
Red
White
HBL8200H
HBL8200HG
–
HBL8200HI
HBL8200HLA
HBL8200HRED
HBL8200HW
HBL8300H
HBL8300HG
HBL8300HGN
HBL8300HI
HBL8300HLA
HBL8300HRED
HBL8300HW
HBL8300RMRI
Style Line® Decorator*
Description
Color
Catalog Number
Flush, nylon face,
back and side wired.
Brown
Gray
Ivory
Office White
Red
White
HBL2172
HBL2172GY
HBL2172I
–
HBL2172R
HBL2172WA
Isolated ground∆.
Ivory
Orange
White
HBL2182
HBL2182GY
HBL2182I
HBL2182OW
HBL2182R
HBL2182WA
–
–
–
HBL8200ILW
IG2182I
IG2182
IG2182WA
Note: ∆See section M for additional information on isolated ground devices.
*Not Fed. Spec. Listed.
See pages A-48 and A-49 for accessories.
See page L-19 for technical information.
See page Tech-10 for Tamper-Resistant description.
See section N for wallplates.
HBL2172
NEC®
is a registered trademark of the National Fire Protection Association (NFPA).
www.hubbell-wiring.com
Dimensions in Inches (mm)
®
Wiring Device-Kellems
L-3
MONITOR MOUNTING
CHANNEL & BRACKET
GCX® MOUNTING CHANNEL
Mounting Channels (right) are used to secure GCX
PolyMount® and PolyQuip® mounting products. Channels
are made of high strength aluminum and have a durable
clear anodized satin finish.
Channels permit mounting hardware to be set anywhere
in the channel. The standard channel length available is
19". Channels installed on MSC units include appropriate
factory-installed support within each unit.
When channels are being provided for installation on
something other than MSC equipment, it is the responsibility of the installing contractor to provide sufficient
support to ensure a safe installation.
GCX® MONITOR BRACKET
Monitor Brackets (below) are typically specific to the
make and model of the monitoring equipment being
accommodated, and may be ordered separately.
Please contact your Modular Services representative
or the factory with any questions you may have.
500 E. Britton Rd. • Oklahoma City, OK 73114
Tel: 800.687.0938 • Fax: 405.528.0368
www.modularservices.com
info@modularservices.com
©2007 Modular Services Company
DCN# 60-1014 — Rev. 09/2007
Accessories
Vacuum Bottle Slide
Vacuum Bottle Slides are used to hold items such as suction canisters
and other secondary equipment. The Vacuum Bottle Slide is available in
a straight 1/2" diameter post, an offset 1/2" diameter post, or a channel
mount style.
Mounting Options: Post Mount requires (1) Vertical Track Adaptor 511-1000 or (1) Provider™
Channel Adaptor 511-1009.
DESCRIPTION
STOCK NO.
Vacuum Bottle Slide, Post Mount, 1/2" Diameter
Straight Post
520-2700
Vacuum Bottle Slide, Post Mount, 1/2" Diameter
Offset Post
520-2701
Vacuum Bottle Slide, Channel Mount
520-2703
520-2700 shown here
520-2703 shown here
Acute and ICU Floors (8-18) Verification List
Items Completed in Re-submittal #1
QUANTITIES /
CONFIGURATIONS
AS PER CONTRACT
DOCUMENTS.
NBBJ
1.
Please verify that the overall dimensions of the units are compatible with the room dimensions
for each location and that the component arrangements shown on the enclosed drawings are
acceptable. Verified as acceptable – NBBJ
Also, please note that these units extend from the floor to above the finished ceiling line. Please
verify that there are no obstructions in the building wall where these units are scheduled to be
installed. Confirmed. Path will be clear to each location at time of delivery – Chris Brooten
2.
We are indicating these units to be shipped and installed in (1) recessed section. Please verify
that this is acceptable. Confirmed to be in (1) section – Chris Brooten
Please note that the insulation will be provided and installed by others.
3.
Please verify the quantity and indicate the number of as shown/opposite hand type units for each
type listed below:
Type
Acute
ICU
ICU Footwalls
Acute Footwalls
Drawing
SU-13638A/B
SU-13639A/B
SU-13640
SU-13641
Quantity
204
170
150
181
As Shown
204
170
150
181
Opposite
0
0
0
0
Verify
OK-NBBJ
OK-NBBJ
OK-NBBJ
OK-NBBJ
Please note that the units are typically provided in either the as shown or opposite arrangement
based upon the layout of the room. The “as shown” unit would be as detailed on the enclosed
elevation drawing and the “opposite” unit would be the direct mirror image of the elevation
drawing (typically provided when the room entrance is located toward the opposite side).
4.
Please verify that all rooms containing units have ceilings that are 9’0” AFF as indicated on the
enclosed drawings. Please verify that the ceiling heights shown are correct. Confirmed-NBBJ
The framing height, conduit height and medical gas piping terminations are shown at 3” above
the ceiling line. Please verify that there are no obstructions and that adequate space is
available for incoming service connections (by others). Confirmed. Locations to be clear - CB
5.
We are indicating that the units will be installed in a 6” building stud wall with (1) layers of 5/8”
gypsum surrounding the panel assembly on each side on the headwall room side. Please verify
that this is correct. Confirmed - NBBJ
It is our understanding that Footwall side of the unit will have (2) layers of 5/8” gypsum installed
over the face of our framing system (hanger system will index from face of wall surface). Please
verify that (2) layers of gypsum on the Footwall side will be used. Confirmed - NBBJ
6.
We are currently indicating a semi-recessed unit. The panel system (headwall & footwall) is
approximately 2” off of the face of the drywall surface with outer anodized or stainless trim (3D
trim options to be provided for final approval). Please verify that this is correct. Confirmed - NBBJ
7.
8.
Due to the size of the penetrations required in the building wall for these units, they are typically
not installed in fire or smoke rated partitions. Please verify that none of these units are scheduled
to be installed in a rated partition where penetrations are required to be kept to a minimum.
If required, a furr-out wall is typically provided in front of the rated partition in order to eliminate
the need for penetrations in the rated wall. Please indicate if this type of arrangement will be
provided at these locations and the size of the metal studs in the furr-out section where the units
will be installed. N/A - NBBJ
NBBJ Previously Confirmed This
It is our understanding that the lower panels should terminate at 6” AFF. Please verify that this is
correct. Confirmed - NBBJ
THIS IS CORRECT FOR UNITS AT ROOM 517 (COLUMN LINE 6.1) FLOORS 8 THRUGH 18. NBBJ
9.
We are currently indicating that the laminate color for the middle (between horizontal accessory
channels) device mounting panels to be Formica #2032 “Brushed Pewter”. Please verify that this
is what is required. Verified in email correspondence between NBBJ & Turner on 06/24/15
We are indicating a horizontal grain direction for this laminate selection. Please verify that this is
correct. Verified in same email correspondence – only offered in horizontal orientation.
We are indicating that the laminate color for the upper and lower device mounting panels to be
Wilsonart #7909-60 “Fusion Maple”. Please verify that this is what is required. Correct, except
finish was changed to “78” (Fine Grain) in email correspondence mentioned above.
We are indicating a horizontal grain direction for this wood grain selection per Bid Clarification
#2. Please verify that this is correct or if the material should be ordered cross grain for a vertical
orientation. Wood grain to have vertical grain direction - NBBJ
Please note that the accessory channels and ½” reveals will have a clear anodized finish.
10. The architectural elevations show the devices right next to one another. Based on the spacing
indicated on the drawings, we are currently indicating quad face plates as we provided in the
initial mock-up for these devices. Please verify that this is what is required or indicate if single
gang plates are preferred. Quad cover OK - NBBJ
Please note that if single gang devices are preferred, MSC will space the plates out
appropriately to provide enough clearance for the device openings in the panel.
11. Please verify if the receptacle at 24” AFF behind the bed should be engraved "BED MOTOR
ONLY" to help prevent other devices from being inadvertently plugged into the receptacle. Do
not engrave receptacle – JBB/NBBJ
12. It is our understanding that the device face plates should be engraved with the panel
board/circuit #. Please verify that this is correct and complete the provided MSC Engraving
Schedule. TCCO to provide schedule – Chris Brooten
13. Initial information received indicated that only the two normal power devices directly next to the
dialysis box require GFI type receptacles. Please verify that this is correct or indicate if other
devices on the dialysis side need to have GFI type receptacles or none of the devices have this
requirement. GFI type receptacles are not required - JBB
14. It is our understanding that the ICU units are to include a monitor channel only that mounts
directly to the unit with internal bracing to support the monitor and that the tilt/swivel bracket to
support the monitor will be provided and installed by others. We are indicating that the channel is
to be a standard GCX type 13" length channel. Please verify that this is what is required. Yes,
pending owner review. – NBBJ
15. For the data outlet provisions, we are indicating a compartment with a two gang opening along
with a conduit from this compartment to the ceiling line for routing wiring from the ceiling space
above (wiring to the receptacle is to be provided by others). Please verify that this is what is
required. Wiring and faceplate will be furnished by the IT contractor – JBB/NBBJ.
16. Currently, we are not showing any switches on the headwall design to match information
previously received and Architectural elevations. However, the lighting plans indicate (4)
switches (two on each side of the patient) to be installed on the units. The switches are shown
to be (3) single pole type and (1) 3-way type switch. Please verify if these switches should be
added into the design and indicate the desired location on the unit. No, they are outside of
headwall – NBBJ/JBB
If these switches are required, please indicate the voltage (120 or 277) and the circuit type
(normal or emergency) feeding the switches. Switches are not a part of headwall – NBBJ/JBB
17. MSC will provide the appropriate clearance openings within the framing system for others to
route the vent (2”), waste (2”) and water line (3/4” + insulation). Please verify that the size of
each line shown is correct. Confirmed – JBB/NBBJ. MSC has been coordinating the clearance
openings in the assembly with Turner through BIM process – see enclosed MEP drawings.
18. The framing system for the headwall will be designed to accept the attachment of finishes on the
Footwall side except for the (23) rooms highlighted in the room list on the enclosed drawings.
These rooms will have separate modules to attach the panel kits as required. Please verify that
the wall construction in these rooms will be typical with (2) layers of gypsum on the face of these
partitions. Room 115: 2 layers. Room 500: 1 layer - NBBJ
19. Please provide details on the TV or mounting bracket being used on the Footwall so that MSC
can provide the appropriate bracing. Bracket is Chief Mfg, model LSMU. Weight of TV is 123 lbs.
- NBBJ
Outstanding Verification Items
1.
We are indicating all preinstalled electrical devices in the units to be prewired to incoming service
junction boxes as indicated on the enclosed drawings. Please have your consulting electrical
or electrical contractor review our wiring diagrams and verify compatibility with
TCCO engineer
existing/planned building wiring.
Please note that we are indicating these units to include both normal and emergency power
ILLUMINATED receptacles and that the color of the devices are GRAY to indicate normal power
and RED to indicate emergency power.
Refer to NBBJ/JBB mark-ups on drawings and fabricate mock-up from that. Subcontractors and JBB will then review your physical mock-up and direct you to proceed or not. - Chris Brooten
6
2.
TCCO
Please note that the Electrical Layout plan drawing and the Architectural elevations do not match
for component locations in the Acute Care units. Also, electrical devices and low voltage
provisions are shown in the Electrical elevations in the Acute units but are not indicated on
current Architectural elevations. MSC is indicating the current circuit configuration shown in the
Electrical plans but proceeding with the component layout in the Architectural elevations (no
monitor devices). Please verify that this is correct.
Refer to NBBJ/JBB mark-ups on drawings and fabricate mock-up from that. Subcontractors and JBB will then review your physical mock-up and direct
3.
TCCO
Please provide the make and model of the dialysis box being provided by others.
We are indicating the dialysis box to be installed by others in (24) of the Acute rooms and all
(170) of the ICU rooms. Please verify that this is correct. Correct - NBBJ
Turner will forward approved submittal to MSC - Chris Brooten
4.
NBBJ
5.
NBBJ
6.
NBBJ
The dialysis box provision was moved up 3” per correspondence between Turner and NBBJ on
06/16/15. Please verify that the current location shown on the drawings is acceptable.
Information received indicated that the nurse call provision might be relocated on the headwall
assembly. Please verify that this is correct and indicate the desired location on the enclosed
drawings.
Please note that other services may need to move to accommodate the new location.
The TV devices were moved over to accommodate the appropriate clearances for the dialysis
box piping. Please verify that the configuration shown is acceptable.
7
Customer Approval:
Name:
Date:
Your signature above certifies that you have authorized Modular Services Company to proceed with
fabrication of the equipment based on the comments included in the returned submittal. Please ensure
that the returned documents include completed responses for each of the verification items along with
any other pages or drawings including notations that are to be incorporated into the units.
ADDITIONAL REMARKS:
3
5
Conduit Routing To Be Viewed During Full Scale
Mock-Up. Will be Drawn After Device Locations Are Final
Details To Be Viewed On Renderings Submitted Under Separate
Cover. Laminate Panels Definitely To Be Free Of Seems
Not Offered In Vertical Grain By
Either Formica Or Wilsonart
10
8
1" MINIMUM
See next page for Note
Regarding Dual Gang Box At
EEG Monitoring Locations:
Level 17 - ALL Rooms (34)
Level 8 - 104-115 (12)
12
Per Coordination With
Cardoza, This Needs To Be
31.5", or 35". This Will Allow
Piping To Be Fitting To Fitting.
11
3
Conduit Routing To Be Viewed During Full Scale
Mock-Up. Will be Drawn After Device Locations Are Final
Details To Be Viewed On Renderings Submitted Under Separate
Cover. Laminate Panels Definitely To Be Free Of Seems
Not Offered In Vertical Grain By
Either Formica Or Wilsonart
10
8
1" MINIMUM
9
Dual Gang Box At EEG
Monitoring Locations:
Level 17 - ALL Rooms (34)
Level 8 - 104-115 (12)
12
Per Coordination With
Cardoza, This Needs To Be
31.5", or 35". This Will Allow
Piping To Be Fitting To Fitting.
11
3
Conduit Routing To Be Viewed During Full Scale
Mock-Up. Will be Drawn After Device Locations Are Final
Details To Be Viewed On Renderings Submitted Under Separate
Cover. Laminate Panels Definitely To Be Free Of Seems
Not Offered In Vertical Grain By
Either Formica Or Wilsonart
10
8
1" MINIMUM
9
See Next Page For Dual
Gang Box At EEG Monitoring
Locations:
Level 16 - ALL Rooms (34)
Level 9 - 110-115 (6)
12
Per Coordination With
Cardoza, This Needs To Be
31.5", or 35". This Will Allow
Piping To Be Fitting To Fitting.
11
3
Conduit Routing To Be Viewed During Full Scale
Mock-Up. Will be Drawn After Device Locations Are Final
Details To Be Viewed On Renderings Submitted Under Separate
Cover. Laminate Panels Definitely To Be Free Of Seems
Not Offered In Vertical Grain By
Either Formica Or Wilsonart
10
8
1" MINIMUM
Dual Gang Box At EEG
Monitoring Locations:
Level 16 - ALL Rooms (34)
Level 9 - 110-115 (6)
12
Per Coordination With
Cardoza, This Needs To Be
31.5", or 35". This Will Allow
Piping To Be Fitting To Fitting.
11
9
3
Outlets Moved For Coordination
With Plumbing Chase
7
10
Fine Grain To
Match Headwall
13
9
Outlets Moved For Coordination
With Plumbing Chase
10
Fine Grain To
Match Headwall
9
13
THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF MODULAR SERVICES COMPANY. ANY REPRODUCTION IN PART OR AS WHOLE WITHOUT THE WRITTEN PERMISSION OF MODULAR SERVICES COMPANY IS PROHIBITED
NOTE(S):
1.
DIMENSIONS FROM CTR OF HEADWALL AND CTR OF FRAMING
2.
MEP CLEAR SPACE SHOWN IN GREEN
TOP OF HEADWALL
FOOTWALL SIDE
3
2.50
2.50
0
1.50
2.50
1.50
2.50
21.00
9.00
3.00
32.50
37.00
40.00
0
0
HEADWALL SIDE
MODULAR
SERVICES COMPANY
Product Type
Cut File Location
N/A
Reference File Location
M:\Method\Project\Job-11794A\SU-13638-13641\SU-13638
Description
Project:
-
Part Number:
13638--
Rev:
-
NYU LANGONE MEDICAL
CENTER KIMMEL PAVILION
JOB 11794A
Drawn
Tolerances:
Finish
METHOD
Initials
Date
STF
6/15/15
-
Material
Comments
Weight
11252.412
lbs.
Flat Pattern Scale
1:12
Unless Otherwise Specified:
Dimensions are in Inches
1 DECIMAL PLACE: .100
2 DECIMAL PLACES: .020
3 DECIMAL PLACES: .005
SHEET 1 OF 1
THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF MODULAR SERVICES COMPANY. ANY REPRODUCTION IN PART OR AS WHOLE WITHOUT THE WRITTEN PERMISSION OF MODULAR SERVICES COMPANY IS PROHIBITED
NOTE(S):
1.
MEP CLEAR SPACE FOR DIALYSIS BOX SHOWN IN GREEN
2.
CHASE DIMENSIONED FROM CTR LINE OF WALL
3
19.00
1.75
0
1.75
0
METHOD
Reference File Location
M:\Method\Project\Job-11794A\SU-13638-13641\SU-13638
Description
Project:
-
Part Number:
13638--
Rev:
-
NYU LANGONE MEDICAL
CENTER KIMMEL PAVILION
JOB 11794A
Drawn
Initials
Date
STF
6/17/15
-
Material
Comments
MODULAR
SERVICES COMPANY
Tolerances:
Finish
Product Type
Cut File Location
N/A
2.50
2.50
0
19.00
Weight
14996.986
lbs.
Flat Pattern Scale
1:22
Unless Otherwise Specified:
Dimensions are in Inches
1 DECIMAL PLACE: .100
2 DECIMAL PLACES: .020
3 DECIMAL PLACES: .005
SHEET 3 OF 3
Home / Commercial / Laminates / Fusion Maple 7909
"78" FINISH
10
FUSION MAPLE MATTE FINISH
Colors on screen may vary from actual product. Please order a sample to ensure color match.
Add to Favorites
View Inspiration Board
Description
LAMINATES
A maple laminate design with cathedrals and slight anigre. Overall color
is a soft natural blond with slight pink and green undertones.
This pattern is part of the Wilsonart Contract Collection.
Approximate Design Repeat Length*: 49"
Approximate Design Repeat Width*: 24"
Available Product
2/16/2015
DecoMetal® ­ Brushed Pewter Aluminum
DecoMetal®
(http://www.formica.com/en/us/products/decometal)
8
M2032
Brushed Pewter Aluminum
STANDARD FINISHES
DecoMetal (Finish Code: 99)
Compare finishes
WHERE TO BUY
(HTTP://WWW.FORMICA.COM/EN/US/WHERE­TO­BUY)
The Features icons below are for general reference only. For more specific product information, see Documents section below.
Swatches are a representation and may vary in color from the final product. Please obtain a sample of the product before making
a final selection.
Specification
Features
FIRE RESISTANT
Size and grade guide
Standard
Grade 85
10' x 4'
DECOMETAL (FINISH CODE: 99)
8' x 4'
DECOMETAL (FINISH CODE: 99)
Sheet sizes shown in feet
Thickness
http://www.formica.com/en/us/products/decometal/m2032#
1/2
9
S
C21
S
101A
100A
B12
E22
S
100
PATIENT ROOM
001
VISITOR
LOUNGE
4 1/2"
B23
B23
B13
S
B13
S
8-18th FLOORS HEADWALL PT RM 100
REFERENCE TO L 08 BIM
COORD. MEETING ITEM 64
DWG.
07.23.2015