Dimming actuator built-in/230/215 W Table of Contents 1. Function 2

advertisement
Chapter 9: Dimming actuators/control units
9.1 Dimming actuator, 1-gang
Dimming actuator built-in/230/215 W
Art. no. 650501
Dimming actuator built-in/230/215 WChapter 9:Dimming actuators/control unitsArt. no.650501As at 09/029.1Dimming actuator, 1-gang
–
+
Merten
Busanschluß
B
instabus
DIMMAKTOR
EB/230/215 W
6505 01
(N) (N) (N)
Dimming actuator built-in/230/215 W
Colour
1. Function
The INSTABUS dimming actuator built-in/230/215 W
dims incandescent lamps and LV halogen lamps (only
via electronic transformers) with a maximum capacity
of approx. 210 watts. Wound transformers may not be
connected to the dimming actuator.
Article no.
L
T
AC 230V
polar white 650501
Table of Contents
1.
Function
1
2.
Installation
1
3.
Technical Data
1
4.
Settings in the EIB Tool Software (ETS)
2
5.
Application overview
2
2. Installation
The INSTABUS dimming actuator built-in/230/215 W is
a built-in device for surface mounting and built-in installation. The bus coupler is already integrated in the
device. The dimming actuator is linked to the bus via a
bus connecting terminal (art. no. 689701).
When installing the device, it should be ensured that a
minimum distance of 4 cm is maintained all round.
¼
Caution!
Disconnect the mains voltage before connecting the device to the loads.
There is always residual voltage present at the
output for short-circuit protection.
The device has 6 screwless plug-in terminals:
3 terminals for neutral conductor
2 terminals for outer conductor
1 terminal for dimmed outer conductor
3. Technical Data
Power supply from the
bus:
Power supply from the
mains:
Leakage loss:
Insulation voltage:
Nominal voltage:
Nominal power
Incandescent lamps:
HV halogen lamps:
LV halogen lamps:
DC 24 V (+6 V/-4 V)/
approx. 7 mA
AC 230 V / 50 Hz
3 watts at nominal power
AC 4 kV bus/mains voltage
AC 230 V
max. 210 W
max. 210 W
MET or other electronic
transformers, max. 200 VA
Wound transformers may not be connected
Protection
Short circuit:
electronic
Overload:
via temperature switch
Ambient temperature
Operation:
-5 °C to +45 °C
Storage:
-25 °C to +55 °C
Transport:
-25 °C to +70 °C
Max. humidity:
93 %
Operating elements:
Programming button
As at 09/02
1
Chapter 9: Dimming actuators/control units
9.1 Dimming actuator, 1-gang
Dimming actuator built-in/230/215 W
Art. no. 650501
Display elements:
Connections
Bus:
Neutral conductor:
Outer conductor:
Dimmed outer conductor:
Strain relief 230 V:
Strain relief
INSTABUS:
Type of protection:
EC guidelines:
Red LED for checking the
bus voltage and for entering the phys. address
via two 1 mm pins for bus
connecting terminal
three 1-pole plug-in terminals for max. 2.5 mm2
two 1-pole plug-in terminals
for max. 2.5 mm2
one 1
-pole plug-in terminal for
max. 2.5 mm2
3 x NYM 3x1.5 mm2
2 x PYCYM 2x2x0.8 mm2
IP 20
corresponds to low voltage
guideline 73/23/EEC; corresponds to EMC guideline
89/336/EEC
Dimensions:
approx. 280x40x35 mm
(LxWxH)
Hole spacing for surface 220 mm
mounting:
4. Settings in the EIB Tool Software (ETS)
Selection in the product database
Manufacturer:
Product family:
Product type:
Program name:
Media type:
Product name:
Order number:
Merten
4.6
Dimming actuator
4.6.02 Built-in BI
Dimming 3230
Twisted Pair
Dimming actuator built-in/230/215
W
650501
5. Application overview
The following application is available:
Application
Vers. Function
Dimming 3230
18
Switching
– with adjustable
starting behaviour Memory function
(final brightness value)
– Feedback of the relay state
Dimming
– with variable dimming speed
Brightness value
– Dim or jump to value
Connection example:
Bus
+ -
L1 N
A
N
N
N
A Bus coupler
As at 09/02
2
Download