Analogue actuator module REG/4-gang Necessary accessories For

advertisement
V6822_562_00_GB.fm Seite 1 Dienstag, 1. Juli 2008 7:44 07
© Merten2005V6822-562-0005/08
Connections, displays and operating
elements
Analogue actuator module REG/4-gang
B
K1
K2
K3
K4
Operating instructions
D
U/I
U/I
U/I
U/I
Technical data
Auxiliary voltage:
Current consumption:
Current consumption on the
system plug:
Ambient temperature:
Storage/transport temp.:
Humidity
Environment/storage/transport:
A
E
K1 K2 K3 K4
F
Art. no. MTN682292
I
G
H
Necessary accessories
– Analogue actuator REG-K/4-gang
(Art. no. MTN682291)
For your safety
¼
DANGER
Risk of fatal injury from electrical current.
The unit may only be installed and connected by
skilled electicians. Observe the regulations valid
in the country of use, as well as the valid KNX
guidelines.
C
A
Reference potential for outputs K1 to K4
B
Analogue outputs K1 to K4
C
External supply voltage for D
D
Analogue actuators (e.g. servomotors etc.)
E
Status LED (red) of the analogue actuator module
F
Status LEDs (yellow) of the four analogue outputs
G
System connection, 6-pin, for module connection
H
Auxiliary voltage connection
I
System connection, 6-pin, for future extensions
Installing the module
The following basic rules should be observed when installing a module:
• A maximum of one module can be connected.
Getting to know the module
The analogue actuator module REG/4-gang (referred to
as a module in the following) extends the analogue actuator REG-K/4-gang by four analogue outputs, which
can be parameterised using software.
• One module can be exchanged for another of the
same type - e.g. if a module is faulty - while the system
is in operation (disconnect module from voltage!). After a module has been replaced, the analogue actuator carries out a reset after approx. 25 seconds. This
re-initialises all outputs on the analogue actuator and
the connected modules and resets them to their original status.
• Data received are converted into 0 to 1 V, 0 to 10 V,
0 to 20 mA or 4 to 20 mA output signals.These analogue output signals enable heating, air conditioning
and ventilation system actuators to adapt their output
variables based on bus information and to participate
in control processes.
• It is not permitted to add or remove modules without
adapting the configuration and downloading it into the
analogue actuator, as this may lead to system malfunctions.
• The output variables can be prioritised.
Status LED
• The analysis of module data and priority operation
processing take place in the KNX analogue actuator.
ON
• Outputs that are not required can be switched off.
Flashing quickly
• The output status is indicated by the status LEDs.
• Suitable for installation onto DIN rails EN 50022.
Voltage measurement
impedance:
Current measurement
impedance:
Type of protection:
Device width:
6 mA
-5 °C to +45 °C
-25 °C to +70 °C
max. 93% relative
humidity,
no condensation
Screw terminals
0.5 mm2 to 4 mm2
0.34 mm2 to 4 mm2
0.14 mm2 to 2.5 mm2
6-pin system plug
4
DC 0 to 1 V,
DC 0 to 10 V,
DC 0 to 20 mA ,
DC 4 to 20 mA
> 1 kΩ
< 500 Ω
IP 20 in accordance
with EN 60529
4 TE = approx. 72 mm
Schneider Electric Industries SAS
If you have technical questions, please contact the Customer Care Center in your country.
www.schneider-electric.com
This product must be installed, connected and used in
compliance with prevailing standards and/or installation
regulations. As standards, specifications and designs
develop from time to time, always ask for confirmation of
the information given in this publication.
Device status (red) during module start-up:
• The module is connected to the KNX device via the
system plug provided.
• Voltage outputs are monitored for short circuits.
Connections
Outputs, power supply:
Single-core:
Finely stranded
(without core end sleeve):
Finely stranded
(with core end sleeve):
Connection to the KNX device:
Analogue outputs
Number:
Ranges:
AC 24 V ±10 %
max. 120 mA
Flashing slowly
OFF
The module is ready for operation (self-test is ok)
The module is currently being initialised
The module is not projected
(in the KNX device)
The module is initialised and
has been started up
Requirement: The LED must
have lit up beforehand.
Device status (red) in normal operation:
ON
OFF
The module is not ready for
operation (error)
The module is initialised and
pre-programmed
Requirement: The LED must
have lit up beforehand.
Flashing slowly = 1/s; flashing quickly = 2/s
Output signals K1 to K4 (yellow):
LED off: The output signal is equal to zero
LED On: The output signal is greater than zero
V6822-562-00 05/08