476 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 57, NO. 2, FEBRUARY 2010 Extending the Life of Gear Box in Wind Generators by Smoothing Transient Torque With STATCOM Marta Molinas, Member, IEEE, Jon Are Suul, and Tore Undeland, Fellow, IEEE Abstract—Gearboxes for wind turbines must ensure high reliability over a period of 20 years, withstanding cumulative and transient loads. One main challenge to this is represented by electromagnetic torque transients caused by grid faults and disturbances, which will result in significant stresses and fatigue of the gearbox. Possibilities for limiting the torque transients in fixed-speed wind generators have not been previously reported. This paper presents a technique by which the transient torques during recovery after a grid fault can be smoothed in a wind farm with induction generators directly connected to the grid. A modelbased control technique using the quasi-stationary equivalent circuit of the system is suggested for controlling the torque with a static synchronous compensator (STATCOM). The basis of the approach consists of controlling the induction generator terminal voltage by the injection/absorption of reactive current using the STATCOM. By controlling the terminal voltage as a function of the generator speed during the recovery process, the electromagnetic torque of the generator is indirectly controlled, in order to reduce the drive train mechanical stresses caused by the characteristics of the induction machine when decelerating through the maximum torque region. The control concept is shown by time-domain simulations, where the smoothing effect of the proposed technique on a wind turbine is seen during the recovery after a three-phaseto-ground-fault condition. The influence of the shaft stiffness in a multimass drive train model is discussed, and the performance of the control concept in the case of parallel connection of several turbines is investigated to discuss the applicability in a wind farm. Index Terms—Static synchronous compensator (STATCOM), voltage source converter, wind energy. I. I NTRODUCTION A LLEVIATION OF mechanical stresses in wind generation systems has traditionally been associated with variable-speed wind turbine topologies by performing direct control of the electromagnetic torque through power electronics. By partial or complete decoupling of the mechanical transients of the wind turbine from the electrical transients of the power system, smoothing of the transient torques on the turbine drive train is thus possible by controlling the electromagnetic torque directly [1]–[5]. However, in fixed-speed wind generation systems based on induction generators directly connected to the grid, there has been no obvious way to control the torque for alleviating mechanical stresses in the drive train. This is confirmed by the lack of literature on such a possible approach. Still, many installations today are using this type of generation Manuscript received December 1, 2008; revised October 15, 2009. First published November 6, 2009; current version published January 13, 2010. The authors are with the Department of Electric Power Engineering, Norwegian University of Science and Technology, 7491 Trondheim, Norway. Color versions of one or more of the figures in this paper are available online at http://ieeexplore.ieee.org. Digital Object Identifier 10.1109/TIE.2009.2035464 system, and more are being planned for the future. Therefore, having the possibility to control torque transients related to grid faults could be beneficial for reducing the stresses in the drive train of fixed-speed generators. Fixed-speed generators are vulnerable to contingencies such as faults and disturbances that might appear in the nearby grid because they are locked to the grid voltage and frequency. In these cases, the stresses on the generator and drive train will be determined by the input mechanical torque and the electrical connection to the grid. However, if, as proposed in [6], an indirect control of the torque is implemented by injecting/absorbing reactive current with a static synchronous compensator (STATCOM), transient torques during recovery after a grid fault can be smoothed. This way, it could be possible to extend the life of the drive train by reducing cumulative and transient loads related to grid faults [7]. Several studies of low-voltage ride through (LVRT) have confirmed how reactive compensation can increase the torque capability and, by that, the stability limit of induction generators [8]–[10]. As shown in [11] and [12], this will also increase the maximum torque that occurs during the recovery process when standard control strategies are implemented. This paper investigates the implementation of indirect torque control (ITC) by a STATCOM to wind turbines in a wind farm. The basic assumption is to utilize a STATCOM originally installed for providing LVRT capability [8], [12] for controlling the torque of the machine only during the recovery process. The STATCOM-based torque control is implemented as a model-based control approach and added to the standard STATCOM control structure as a new mode of operation. This mode of operation was first presented in [6] and is labeled as ITC since it is based on using the STATCOM to control the voltage at the generator terminals and, by that, indirectly controlling the torque during the recovery process after a grid fault. In [6], the concept of ITC was presented and applied as a technique for torque transient alleviation in a single wind turbine unit. In this paper, a more elaborated explanation of the proposed concept is presented, and the properties of the ITC are further investigated. Based on the results in [6], the control concept is analyzed both for critical faults close to the stability limit of the system and for shorter faults where the operation of the STATCOM is not needed to ensure stability of the induction generator. The torque control concept is further extended to a wind farm composed of paralleled turbines, with a STATCOM at the terminal of each generator. All STATCOMs are using the proposed technique in its control structure as an additional mode of operation that is activated only during the recovery process after a grid fault. The parallel operation of 0278-0046/$26.00 © 2010 IEEE Authorized licensed use limited to: Norges Teknisk-Naturvitenskapelige Universitet. Downloaded on March 20,2010 at 07:21:49 EDT from IEEE Xplore. Restrictions apply. MOLINAS et al.: EXTENDING LIFE OF GEAR BOX IN WIND GENERATORS 477 Fig. 1. Schematic configuration of the wind farm composed of two wind generation systems in parallel, each with a STATCOM. the STATCOM has raised new operational issues related to the reactive power exchange between STATCOMs and the grid, which are discussed in this paper. Fig. 2. Block diagram of the control system, including ITC and normal STATCOM. II. S TATCOM -BASED T ORQUE C ONTROL C ONCEPT Fig. 1 shows the schematic configuration of the wind farm in which the ITC technique is implemented. The wind farm investigated in this paper is modeled in PSCAD®™ by two wind generation units in parallel, each with a STATCOM at the terminals. One wind generation unit consists of an induction generator driven by a wind turbine through a gear box, converting the low speed of the turbine shaft into a high speed that matches the rotational speed of the induction generator. The induction generator is connected to the grid through a transformer, and a STATCOM is connected at the generator terminals to control the voltage level at the generator by injection of reactive current [6], [13]–[15]. As reported in [8] and [12], the STATCOM was originally installed to improve the transient stability and the critical clearing time of the wind generator and, by that, to increase the LVRT capability. High levels of reactive compensation to improve the fault ride-through capability of the system will, however, increase the maximum torque of the generator during the recovery process [8], [11]. In order to temporarily avoid the high level of reactive compensation during recovery, the control structure of the STATCOM is expanded, as shown in the block diagram of Fig. 2. The introduction of the ITC block, in addition to the normal STATCOM control, allows for torque transient alleviation during the recovery process after a grid fault. This is possible to achieve by reducing the voltage reference of the STATCOM control system and, by that, the reactive compensation when stability is ensured after fault clearing but before the grid voltage and the speed of the generator have returned to the prefault values. In this way, the STATCOM can improve the torque capability of the induction generator when this is needed to keep the system stable, and once stability is ensured, it can reduce the maximum torque during recovery. The strain on the drive train can thereby be reduced. This is particularly relevant in the context of LVRT where wind turbines cannot just disconnect from the grid to protect the installation from risk of mechanical damage that might be caused by the cumulative stress of repeated peak torque transients [7]. Fig. 3. Quasi-stationary equivalent circuit for the system under study, consisting of the traditional induction machine equivalent, the STATCOM modeled as a current source, and a grid equivalent. At the clearing instant of a fault and afterward, transients of the electromagnetic torque will result in significant stresses for the wind turbine mechanical system and can have harmful effects on the lifetime of drive-train-sensitive components such as the gearbox [16]–[18]. Gearbox fatigue is caused by stressing of the gearbox teeth in response to torque overloads. For an input torque in excess of the gearbox rating, the fatigue damage increases in the extent to which the rating is exceeded and also as the length of the time that the overload persists [19]. In addition to that, lifetime of the gearbox is reported to be influenced by the load–duration distribution. The accumulated duration of torque levels significantly influences the fatigue load on the gearbox and, therefore, its lifetime [7]. Taking this into account, not only the high transient torques will represent stresses on the gearbox but also the cumulative torque stresses under normal operation by adding up to the high transient torques during recovery after a fault. The short circuit initial torque transients of the induction generator are not the target of the proposed ITC concept. These transients will contribute to the cumulative stresses of the system but cannot be influenced by the STATCOM when the grid voltage is close to zero. This paper focuses on the recovery process after fault clearing and the mitigation of related transient torques observed in induction machines. A three-phase grid failure is used as an example to put in evidence the torque transients that appear after a grid fault is cleared. However, the recovery process of the induction generator is almost independent of the type of fault, which will have no significant influence on the performance of the proposed approach. Authorized licensed use limited to: Norges Teknisk-Naturvitenskapelige Universitet. Downloaded on March 20,2010 at 07:21:49 EDT from IEEE Xplore. Restrictions apply. 478 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 57, NO. 2, FEBRUARY 2010 III. M ODEL -BASED T ORQUE C ONTROL : A NALYTICAL D ERIVATION The equivalent circuit of the system in Fig. 3 is used to derive the equations that will serve as the analytical basis for the design of the model-based control. The analytical results will then be used to generate a speed-dependent reference voltage for the STATCOM control system under the ITC mode of operation. For investigation of the concept, the analytical equations are implemented in PSCAD® and used to calculate the speed-dependent voltage reference that is temporarily allowed to override the normal voltage reference value when the ITC is active, as shown in Fig. 2. The process of deriving and applying the proposed concept is explained hereafter starting from (1) which gives the relation between the quasi-stationary electromagnetic torque and the rotor current of the generator. From this equation, a reference value for the quasi-stationary rotor current can be obtained as a function of the slip of the machine, by specifying the value of the electromagnetic torque. Introducing the rotor current i2 found from (1) into (2) will give the stator current i1 as a function of the slip of the machine. By using the results from (1) and (2), the corresponding value of the terminal voltage of the generator can be found from (3). By using this equation as a speed-dependent voltage reference value for the STATCOM, indirect control of the generator torque can be obtained during the recovery process τem,i = i1,i = r2,i |i2,i |2 si r2,i si + j(x2,i + xm,i ) jxm,i (1) i2,i v 1,i = v STATCOMi,ref = i1,i (r1,i + req,r,i + j(x1,i + xeq,r,i )) . (2) (3) The core concept of the ITC is to limit the electromagnetic torque during the recovery process after a grid fault. The reference value for the torque must be set at a value that limits the torque transients but, at the same time, ensures stable deceleration of the generator until the system is recovered from the influence of the fault. The validity of implementing the simplified quasi-static model of the induction generator for calculation of critical speed and LVRT capability was discussed in [12]. When using the same model to develop the ITC concept, the validity of the quasi-stationary approach can be considered more reasonable since the electromagnetic torque is controlled to a value close to the mechanical torque. As understood from this description, the concept of ITC is derived from a rather simple set of equations. It is also seen that this control concept, and the quasi-stationary model on which it is based, gains its validity by limiting the torque of the induction generator during the recovery process after a fault. The control structure sketched in Fig. 2 also shows how the concept can be implemented only by temporarily modifying the reference value for the normal voltage control objective of the STATCOM. The control is therefore presented as an additional control feature of a STATCOM intended for voltage control and improvement of LVRT capability of wind turbines. Although very simple in the basic concept, there are no previously re- ported interpretations of the induction machine quasi-stationary equations for torque control purposes as presented in this paper. As can be seen from the equations and also from Fig. 2, the presented ITC concept will be dependent on the speed or the slip of the induction machine. One drawback of the method is therefore that practical implementation will require speed sensors. The other main issue related to this concept is that, since the decelerating torque of the generator is limited, the recovery process of the system will be longer than for the case of normal control of the STATCOM with a fixed voltage reference value. The longer recovery time will also result in a longer time with high reactive power flow in the system. The ITC control concept as presented in this paper is independent of the inner current control structure of the STATCOM. Therefore, this concept can be applied in combination with any kind of established current control strategy and modulation techniques [20], [21]. In this paper, voltage-oriented vector current control and carrier-based pulsewidth modulation (PWM) with third harmonic injection are applied [22], [23]. For simulating the system in PSCAD®/EMTDC™, an average model of the PWM is implemented to increase the simulation speed, since switching transients are not of main importance to the proposed concept [24]. IV. T ORQUE S MOOTHING C ONCEPT ON S INGLE G ENERATION U NIT To illustrate the main response of an induction generator to a grid fault when the ITC is implemented, simulations of one wind generation unit with a lumped mass model are carried out with PSCAD®/EMTDC™. The investigated case is fault clearing after a three-phase-to-ground fault condition at the generator terminals (point A) in Fig. 1. The blue solid line and the red dashed line in Fig. 4(a) show, respectively, the STATCOM current with the normal STATCOM control and the ITC, for a critical fault that brings the system close to the stability limit. It can be noticed that, some time after the clearing of the fault, during the recovery process, the STATCOM current with ITC goes from injection to absorption of reactive current to reduce the torque. With the normal STATCOM control, there will be only capacitive operation of the STATCOM, and the speed of recovery of the system is the fastest possible. The recovery process with the ITC is longer than that with the normal STATCOM control, because the decelerating torque is limited. The corresponding curves in Fig. 4(b) show the difference between the terminal voltages with the normal STATCOM control and with ITC. The terminal voltage remains below rated value for longer time due to the slower deceleration introduced by the ITC control. The value of the remaining voltage depends on the system parameters and the reference torque selected when implementing the ITC. In the simulations presented in this paper, the torque reference is chosen to be 1.15 pu, which is very close to the mechanical torque of 1 pu. In Fig. 5(a), the torque trajectories for both normal STATCOM operation and for operation with ITC show how the ITC is limiting the peak torques during the recovery process. Fig. 5(b) shows the reactive current trajectory of the STATCOM as a function of the generator speed. It can be seen that, with Authorized licensed use limited to: Norges Teknisk-Naturvitenskapelige Universitet. Downloaded on March 20,2010 at 07:21:49 EDT from IEEE Xplore. Restrictions apply. MOLINAS et al.: EXTENDING LIFE OF GEAR BOX IN WIND GENERATORS 479 Fig. 4. Time responses of STATCOM reactive current with normal STATCOM control and ITC, and time responses of terminal voltage with normal STATCOM control and ITC for two different fault durations. Fig. 5. Torque and current trajectories during recovery process with normal STATCOM control and with ITC control for two different fault durations. the normal STATCOM control, the current is kept around the maximum value during the fault and the recovery process until the speed of the system is back to the initial value. With the ITC, the current during the recovery process is instead a function of the speed as given by (4), shown at the bottom of the page [6]. The same equation is obtained in [8] as an estimate of the required compensation current as a function of mechanical torque and generator speed. As expected by the torque reference setting, the maximum torque amplitude with ITC control is 1.15 pu at the beginning of the recovery process. The torque is slightly reduced as the system is getting closer to the rated speed and rated voltage because of the dynamics of the machine when decelerating as described in [12]. As a result of the almost constant torque of the ITC, there is a characteristic linear change of speed of the generator as can be seen in Fig. 6. With the normal STATCOM |iSTATCOM |2 + Fig. 6. Time response of generator speed for two different faults with and without ITC. control and for parameters used in this paper, the maximum torque amplitude that appears during the recovery process is about 43% above the rated torque. The propagation of these 2 · i2 (req,i2 · req,STATCOM + xeq,i2 · xeq,STATCOM ) (req,i2 · i2 )2 + (xeq,i2 · i2 )2 − |v g | |iSTATCOM | + =0 2 2 2 req,STATCOM + xeq,STATCOM req,STATCOM + x2eq,STATCOM (4) Authorized licensed use limited to: Norges Teknisk-Naturvitenskapelige Universitet. Downloaded on March 20,2010 at 07:21:49 EDT from IEEE Xplore. Restrictions apply. 480 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 57, NO. 2, FEBRUARY 2010 torque transients in the drive train is determined by its torsional characteristics, which is investigated in Section IV with a twomass model. Figs. 4–6 also show results corresponding to a shorter fault of 150 ms, which is well within the stability limit of the system. For this fault, the system will be stable without compensation by the STATCOM. The black dotted lines in the figures show the response with normal control of the STATCOM, while the green dashed curves show the response with the ITC concept. As shown in Fig. 5(a), the 150-ms fault is cleared at a speed where the torque capability of the induction generator is close to the maximum value. Because the remagnetization of the machine occurs at a speed where the torque capability is high and, therefore, also at a higher voltage, the flux transients are contributing more to the torque, and the maximum torque during the recovery process is even higher than that in the case of a fault close to the stability limit. In this case, the limiting effect of the ITC on the torque is increased, since the torque is brought into the same trajectory as the one described for the case of the critical fault. As can be seen from both Figs. 4(a) and 5(b), this is achieved by bringing the STATCOM current from maximum capacitive compensation during the fault to inductive operation as soon as the fault is cleared. The influence on the grid voltage is shown in Fig. 4(b), while the generator speed is shown in Fig. 6. These results indicate the general capability of the ITC in limiting the torque during recovery processes after any fault that is within the stability limit of the system. This is obtained without interfering with the primary objective of the STATCOM for improving the LVRT capability. In order to further investigate the effect of the ITC on the electromagnetic torque of the generator when the torsional torque is taken into consideration, a two-mass model of the wind generation system is introduced in the next section [25]. V. R ESPONSE OF R EAL W IND G ENERATION S YSTEM For application in a real wind farm, there are several factors that need to be taken into account when considering the implementation of a control technique as the ITC. One of the main issues will be the influence of the real drive train torsional behavior of a wind turbine with a large gear ratio. Another issue will be the control performance in a wind farm, where there will be several units operating in parallel. This might lead to interactions between the different units when the ITC control is in operation, due to the control nature of the ITC that makes the operation to depend on the effective Thévenin impedance as seen from each of the units. A. Influence of Two-Mass Model on ITC When the wind turbine and the wind generator are modeled as a single-mass lumped model with a combined inertia constant, stability analysis may give significant error when compared to a multimass model [26], [27]. The effect of inertia constants, shaft stiffness, self-damping of the individual masses, and mutual damping of the adjacent masses must be taken into consideration when investigating the performance of the ITC in real wind turbine generation systems. A two- Fig. 7. Two-mass model of the wind energy generation system. TABLE I M ACHINE AND G RID PARAMETERS U SED IN S IMULATIONS mass drive train model, as shown in Fig. 7, is simulated in PSCAD®/EMTDC™ with the parameters given in Table I under a fault at the point of common coupling (PCC) in Fig. 1. The simulation results shown in Figs. 8 and 9 illustrate the influence of shaft stiffness and mutual damping on the performance of the ITC control. In Fig. 8, the time responses of turbine and generator speeds show how the initial response after fault clearing is influenced by the shaft stiffness. With the ITC, it is seen that the generator speed is allowed to increase again after the initial torsional transient, but then, the generator goes into the characteristic linear decrease of speed. The speeds of the generator and the turbine are afterward reduced simultaneously in a smooth way, and the oscillations of the turbine speed around the generator speed, as shown in the case with normal STATCOM control, are avoided. This is confirmed by the results presented in Fig. 9 which shows the time responses of the torque on the turbine shaft and the generator. The effect of the ITC can be seen by the smoothed torque compared to the normal STATCOM control as a result of the torque limitation imposed by the ITC controller. This gives an indication of the reduced torque stresses for the gearbox compared to the stresses with normal STATCOM control. It should be noted that the reduced stresses in the turbine shaft are at the cost of a slower recovery process and lower terminal voltage after fault clearing. The STATCOM current during the fault and recovery process is shown in Fig. 10. During the fault, both cases result in maximum amount of reactive current, but after the fault clearing instant, the system with ITC responds to the voltage reference calculated according to the proposed algorithm, and the STATCOM goes from capacitive to inductive operation depending on that voltage reference value. Authorized licensed use limited to: Norges Teknisk-Naturvitenskapelige Universitet. Downloaded on March 20,2010 at 07:21:49 EDT from IEEE Xplore. Restrictions apply. MOLINAS et al.: EXTENDING LIFE OF GEAR BOX IN WIND GENERATORS 481 results with reduced damping coefficient indicated that the wind generation system can become oscillatory unstable and the ITC does not perform as expected if the system has a shaft with low damping. To improve the performance for low-damping factors, the two-mass model of the drive train system should be taken into account when designing the ITC control. This might require design of a control structure operating with closedloop control and not only in a feedforward manner as the presented model-based ITC concept. Then, it could be necessary to include feedbacks that would require either additional measurements or design of suitable observers. More advanced control methods could also be relevant for adding damping and suppressing torsional oscillations while still obtaining the objective of controlling the torque [28]–[33]. B. Operation of ITC in Parallel-Connected Wind Generation Units Fig. 8. Time responses of turbine and generator speeds with normal STATCOM and ITC. Fig. 9. Time responses of turbine shaft and generator torque with normal STATCOM and ITC. Fig. 10. Time responses of STATCOM currents with and without ITC. The influence of the mutual damping has also been investigated in [6] by reducing the value of the damping coefficient. As the damping coefficient was reduced, the responses became more oscillatory as a result of the typical speed oscillations originated by the torsional shaft of the two-mass model. The For application in a wind farm, several identical turbines operating in parallel should be considered. The main impedance separating the different turbines will, in this case, be given by the transformer impedances, and then, all turbines will see a common substation transformer as part of the impedance of the main grid. Since most of the internal grid in a wind park is usually by cable connection, local short circuit faults at the individual turbines are more unlikely to happen than faults in the main grid that will influence the entire wind farm by causing severe voltage drops. Therefore, a situation with two turbines in parallel, as shown in Fig. 1, is simulated, and for simplicity, a grid fault is applied at the PCC. When the turbines are operating at the same conditions, they will, in general, behave equally, and the ITC algorithm in the different turbines will have the same effect. Therefore, almost exactly the same curves as shown in Figs. 8–10 result from the simulation of each turbine. In cases where each turbine in the farm has different operating condition, the ITC controllers of the different turbines might interact. An example of this is shown in Figs. 11–14, where the system is simulated for the same fault as before, but where one turbine is operating with a constant mechanical torque of 1.0 pu, while the other turbine is operating with a torque of 0.9 pu. As can be seen from the simulations of the system with normal STATCOM control, the two turbines behave quite similarly with the main difference being a lower maximum speed and lower maximum torque on the generator with the lowest mechanical torque. In the case with ITC, it can be seen that the generator and shaft torques are limited to nearly the same maximum values regardless of the different operating conditions, which is clearly observed by the shaft torque trajectory in Fig. 13. In Fig. 14, an interesting behavior of the compensating current is observed. Generator 2 with lower operating torque has a faster recovery process due to a larger braking torque compared to Generator 1, since both ITC controllers are designed with the same torque threshold. This brings as a consequence that Generator 2 ITC will shift to normal STATCOM control faster than Generator 1 ITC. As a result of this, there is a transfer of reactive current between the two STATCOMS. This is partly seen in the upper Authorized licensed use limited to: Norges Teknisk-Naturvitenskapelige Universitet. Downloaded on March 20,2010 at 07:21:49 EDT from IEEE Xplore. Restrictions apply. 482 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 57, NO. 2, FEBRUARY 2010 Fig. 13. Torque trajectories of each turbine in the farm with and without the ITC for two different operating torque conditions. Fig. 11. Time responses of turbine and generator speeds with normal STATCOM and ITC with two turbines in parallel at two different operating torque conditions. Fig. 12. Time responses of turbine and generator torques with normal STATCOM and ITC with two turbines in parallel operating at two different torque conditions. plot of Fig. 14 when the STATCOM at Generator 2 runs into the capacitive limit while the STATCOM at Generator 1 runs into the inductive current limit. Since the ITC depends on the equivalent grid impedance and the voltage drop caused by the flow of reactive power, this problem cannot be completely avoided and will be most significant when the impedance between two units is small. The influence of this problem can however be reduced if each ITC could be designed with torque thresholds that are sensitive to their actual operating conditions. If the torque reference of the different units is selected such that the decelerating torque is the same, this will reduce the difference in recovery time and therefore limit the period when the controllers run into saturation. The current that will be injected/absorbed by the STATCOM under the ITC operation mode is given by (4), and as shown from this equation, it will depend upon the parameters of the Fig. 14. STATCOM current and reactive power profile at the PCC bus with and without the ITC when two turbines operate in parallel at two different torque conditions. equivalent Thévenin impedance of the rest of the farm and the grid combined, and the corresponding Thévenin-equivalent grid voltage v g . This equation determines, at the same time, the required rating of the STATCOM to operate under the ITC modality. The reactive current interchange at the PCC bus is shown in the lower plot in Fig. 14. This interchange will depend on the voltage reference set by the ITC and according to the Authorized licensed use limited to: Norges Teknisk-Naturvitenskapelige Universitet. Downloaded on March 20,2010 at 07:21:49 EDT from IEEE Xplore. Restrictions apply. MOLINAS et al.: EXTENDING LIFE OF GEAR BOX IN WIND GENERATORS Fig. 15. Generator terminal voltages, PCC voltage, and grid power with and without ITC for two turbines operating in parallel at two different torque conditions. impedance values of the Thévenin equivalent circuit of the wind farm and grid combined. The resulting influence on the voltage at the generator terminals can be observed from the upper curves of Fig. 15. In the same figure, the overall effect of the ITC on the PCC voltage is shown, indicating a remaining voltage well within today’s grid code requirements. The last plot in Fig. 15 shows the power flow into the grid for both the normal STATCOM and the ITC. It is interesting to note that, with the ITC, the power flow to the grid could be kept under control regardless of the direct connection of the generator to the grid. This is a feature that can be considered a semidecoupling effect that is similar to the one obtained with a converter-controlled grid interface. The results observed in the last figures can also be relevant when interconnecting wind farms with different sizes. The possible interaction between units with ITC control and nearby wind farms or other units with voltage regulation will also require similar considerations. VI. C ONCLUSION A technique has been developed to alleviate torque transients in fixed-speed wind generation systems with asynchronous generators during the recovery process after a grid failure. The main objective of the proposed controller is to reduce stresses in the gearbox and other mechanical components of the drive train. The new proposed technique labeled as ITC 483 has been first implemented by extending the standard control capabilities of a STATCOM compensating a single generation unit. Simulation results indicate how the STATCOM can allow for the implementation of such a control strategy to reduce the mechanical stresses on the drive train of a wind turbine during recovery after a fault, but at the expense of a reduced voltage level and a longer recovery time. Results from a critical fault and a generic shorter fault indicate the general applicability of the technique to adapt the STATCOM control to the needs of the system during recovery after any kind of contingencies. The ITC technique is additionally implemented and verified by simulating a two-mass model and two turbines operating in parallel for investigating the performance of the controller in a wind farm. The limitations of the presented concept in the case of shafts with low damping have been commented and indicated the need for further work on more sophisticated considerations in such conditions. Simulation results from operation of the ITC on two turbines in parallel indicate that some interaction between the two STATCOM control systems and the grid can occur if the different turbines are operating with different mechanical torques. This might result in unintended interchange of reactive current among units in the case of nonidentical operating conditions, and saturation of the STATCOM current references might make the ITC incapable of limiting the torque to the specified value. This problem will, however, not compromise the stability of the generator and only lead to a maximum torque that can be slightly higher than specified. As one of the drawbacks of the ITC could be the slow recovery process with low remaining voltage, a tradeoff between minimum required voltage level in the grid allowed flow of reactive power depending on grid code requirements, and smoothed transient torque should be attempted when implementing the ITC control in practice. Influence of low damping in the mechanical drive train, controller parameter sensitivity, and dependence on speed measurement are other factors which will affect the performance in practical implementation of the technique. In a further step, an experimental validation of the technique in a reduced-scale laboratory model should be carried out in order to investigate and propose a practical solution for these. R EFERENCES [1] F. D. Kanellos, S. A. Papathanassiou, and N. D. Hatziargyriou, “Dynamic analysis of a variable speed wind turbine equipped with a voltage source AC/DC/AC converter interface and a reactive current control loop,” in Proc. 10th Mediterranean Electrotech. Conf., May 2000, vol. 3, pp. 986–989. [2] S. A. Papathanassiou and M. P. Papadopoulos, “Dynamic behavior of variable speed wind turbines under stochastic wind,” IEEE Trans. Energy Convers., vol. 14, no. 4, pp. 1617–1623, Dec. 1999. [3] J. M. Carrasco, L. G. Franquelo, L. T. Bialasiewicz, E. Galván, P. C. P. Guisado, M. Á. M. Prats, J. I. León, and N. Moreno-Alfonso, “Power-electronic systems for the grid integration of renewable energy sources: A survey,” IEEE Trans. Ind. Electron., vol. 53, no. 4, pp. 1002– 1016, Aug. 2006. [4] F. Blaabjerg, R. Teodorescu, M. Liserre, and A. V. Timbus, “Overview of control and grid synchronization for distributed power generation systems,” IEEE Trans. Ind. Electron., vol. 53, no. 5, pp. 1398–1409, Oct. 2006. [5] J. A. Baroudi, V. Dinavahi, and A. M. Knight, “A review of power converter topologies for wind generators,” Renew. Energy, vol. 32, no. 14, pp. 2369–2385, Nov. 2007. Authorized licensed use limited to: Norges Teknisk-Naturvitenskapelige Universitet. Downloaded on March 20,2010 at 07:21:49 EDT from IEEE Xplore. Restrictions apply. 484 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 57, NO. 2, FEBRUARY 2010 [6] M. Molinas, J. A. Suul, and T. Undeland, “Torque transient alleviation in fixed speed wind generators by indirect torque control with STATCOM,” in Proc. 13th EPE-PEMC, Poznan, Poland, Sep. 1–3, 2008, pp. 2318–2324. [7] B. Niederstucke, A. Anders, P. Dalhoff, and R. Grzybowski, “Load Data Analysis for Wind Turbine Gearboxes,” in “Final Report, ELA—Enhanced Life Analysis of Wind Power Systems,” (Original German title: Abschlussbericht, Forchungsvorhaben ELA—Ervweiterte Lebendsdaueranalyse für Windenergieanlagen), Germanischer Lloyd WindEnergie GmbH, Hamburg, Germany, Rep. 71048, Appendix 10, 4 pp. [Online]. Available: http://edok01.tib.uni-hannover.de/edoks/ e01fb04/39616871X.pdf [8] M. Molinas, J. A. Suul, and T. Undeland, “Low voltage ride through of wind farms with cage generators: STATCOM versus SVC,” IEEE Trans. Power Electron., vol. 23, no. 3, pp. 1104–1117, May 2008. [9] S. K. Salman and A. L. J. Teo, “Improvement of fault clearing time of wind farm using reactive power compensation,” in Proc. IEEE Porto Power Tech Conf., Sep. 10–13, 2001, vol. 2, 6 pp. [10] S. K. Salman and A. L. J. Teo, “Investigation into the estimation of the critical clearing time of a grid connected wind power based embedded generator,” in Proc. IEEE/PES Transm. Distrib. Conf. Exhib., Oct. 6–10, 2002, vol. 2, pp. 975–980. [11] M. Molinas, J. A. Suul, and T. Undeland, “Wind farms with increased transient stability margin provided by a STATCOM,” in Proc. CES/IEEE 5th IPEMC, Aug. 13–16, 2006, vol. 1, pp. 63–69. [12] M. Molinas, J. A. Suul, and T. Undeland, “A simple method for analytical evaluation of LVRT in wind energy for induction generators with STATCOM or SVC,” in Proc. 12th EPE, Aalborg, Denmark, Sep. 2007, pp. 1–10. [13] G. Chicco, M. Molinas, T. Undeland, and G. Viglietti, “Study of the transient stability margin in a wind system with STATCOM,” in Proc. 6th World Energy Syst. Conf., Torino, Italy, Jul. 10–12, 2006, pp. 371–376. [14] L. Gertmar, L. Liljestrand, and H. Lendenmann, “Wind energy powersthat-be successor generation in globalization,” IEEE Trans. Energy Convers., vol. 22, no. 1, pp. 13–28, Mar. 2007. [15] S. Hartge and F. Fischer, “FACTS capabilities of wind energy converters,” in Proc. EWEC, Athens, Greece, Feb. 27–Mar. 2, 2006. [16] M. Papadopoulos, P. Malatestas, and J. Tegopoulos, “Stresses of self excited induction generators during abnormal supply conditions,” in Proc. ICEM, 1992, vol. 3, pp. 1072–1076. [17] J. Faiz, M. Ghaneei, and A. Keyhani, “Performance analysis of fast reclosing transients in induction motors,” IEEE Trans. Energy Convers., vol. 14, no. 1, pp. 101–107, Mar. 1999. [18] S. Papathanassiou and M. Papadopoulos, “Mechanical stresses in fixedspeed wind turbines due to network disturbances,” IEEE Trans. Energy Convers., vol. 16, no. 4, pp. 361–367, Dec. 2001. [19] W. E. Leithead, S. de la Salle, and D. Reardon, “Role and objectives of control of wind turbines,” Proc. Inst. Elect. Eng.—C, vol. 138, no. 2, pp. 135–148, Mar. 1991. [20] M. P. Kazmierkowski and L. Malesani, “Current control techniques for three-phase voltage-source PWM converters: A survey,” IEEE Trans. Ind. Electron., vol. 45, no. 5, pp. 691–703, Oct. 1998. [21] J. Holtz, “Pulsewidth modulation—A survey,” IEEE Trans. Ind. Electron., vol. 35, no. 5, pp. 410–420, Dec. 1992. [22] V. Blasko and V. Kaura, “A new mathematical model and control of a three-phase AC-DC voltage source converter,” IEEE Trans. Power Electron., vol. 12, no. 1, pp. 116–123, Jan. 1997. [23] D. G. Holmes and T. A. Lipo, Pulse Width Modulation for Power Converters, Principles and Practice. Piscataway, NJ: IEEE Press, 2003. [24] D. Maksimoviæ, A. M. Stankoviæ, V. J. Thottuvelil, and G. C. Verghese, “Modeling and simulation of power electronic converters,” Proc. IEEE, vol. 89, no. 6, pp. 898–912, Jun. 2001. [25] Y. Shima, R. Takahashi, T. Murata, J. Tamura, Y. Tomaki, S. Tominaga, and A. Sakahara, “Transient stability simulation of wind generator expressed by two-mass model,” IEEJ Trans. Inst. Elect. Eng. Jpn. B, vol. 125-B, no. 9, pp. 855–864, 2005. [26] S. M. Muyeen, M. Hasan Ali, R. Takahashi, T. Murata, J. Tamura, Y. Tomaki, A. Sakahara, and E. Sasano, “Comparative study on transient stability analysis of wind turbine generator system using different drive train models,” IET Renew. Power Gener., vol. 1, no. 2, pp. 131–141, Jun. 2007. [27] S. M. Muyeen, M. Hasan Ali, R. Takahashi, T. Murata, J. Tamura, Y. Tomaki, A. Sakahara, and E. Sasano, “Transient stability analysis of wind generator by using six-mass drive train model,” in Proc. ICEMS, Nagasaki, Japan, 2006. [28] Y. Hori, H. Iseki, and K. Sugiura, “Basic consideration of vibration suppression and disturbance rejection control of multi-inertia system using [29] [30] [31] [32] [33] SFLAC (state feedback and load acceleration control),” IEEE Trans. Ind. Appl., vol. 30, no. 4, pp. 889–896, Jul./Aug. 1994. K. Sugiura and Y. Hori, “Vibration suppression in 2- and 3-mass system based on the feedback of imperfect derivative of the estimated torsional torque,” IEEE Trans. Ind. Electron., vol. 43, no. 1, pp. 56–64, Feb. 1996. Y. Hori, H. Sawada, and Y. Chun, “Slow resonance ratio control for vibration suppression and disturbance rejection in torsional system,” IEEE Trans. Ind. Electron., vol. 46, no. 1, pp. 162–168, Feb. 1999. W. Li and Y. Hori, “Vibration suppression using single neuron-based PI fuzzy controller and fractional-order disturbance observer,” IEEE Trans. Ind. Electron., vol. 54, no. 1, pp. 117–126, Feb. 2007. K. Szabat and T. Orlowska-Kowalska, “Vibration suppression in a two-mass drive system using PI-speed controller and additional feedbacks—Comparative study,” IEEE Trans. Ind. Electron., vol. 54, no. 2, pp. 1193–1206, Apr. 2007. M. Cychowski, K. Szabat, and T. Orlowska-Kowalska, “Constrained model predictive control of the drive system with mechanical elasticity,” IEEE Trans. Ind. Electron., vol. 56, no. 6, pp. 1963–1973, Jun. 2009. Marta Molinas (M’94) received the Diploma in electro-mechanical engineering from the National University of Asuncion, Asuncion, Paraguay, in 1992, the M.Sc. degree from Ryukyu University, Okinawa, Japan, in 1997, and the Dr. Eng. degree from Tokyo Institute of Technology, Tokyo, Japan, in 2000. In 1998, she was with the University of Padua, Padua, Italy, as a Guest Researcher. From 2004 to 2007, she was a Postdoctoral Researcher with the Norwegian University of Science and Technology, Trondheim, Norway, where she is currently a Professor with the Department of Electric Power Engineering. From 2008 to 2009, she was a JSPS Research Fellow with the Energy Technology Research Institute, National Institute of Advanced Industrial Science and Technology, Tsukuba, Japan. Her research interests include wind/wave energy conversion systems, and power electronics and electrical machines in distributed energy systems. Prof. Molinas is actively engaged as a Reviewer for IEEE T RANSACTIONS ON I NDUSTRIAL E LECTRONICS and IEEE T RANSACTIONS ON P OWER E LECTRONICS. She is an AdCom member of the IEEE Power Electronics Society. Jon Are Suul received the M.Sc. degree from the Norwegian University of Science and Technology, Trondheim, Norway, in 2006, where he is currently working toward the Ph.D. degree in the Department of Electric Power Engineering. In 2008, he was a guest Ph.D. student with the Energy Technology Research Institute, National Institute of Advanced Industrial Science and Technology, Tsukuba, Japan. From 2006 to 2007, he was with Sintef Energy Research, working on simulation of power electronic systems. His research interests include control of power electronics converters in power systems and for renewable energy applications. Tore Undeland (M’86–SM’92–F’00) received the M.Sc. and Ph.D. degrees from the Norwegian University of Science and Technology, in 1970 and 1977, respectively. He has been a Full Professor with the Department of Electric Power Engineering, Norwegian University of Science and Technology, Trondheim, Norway, since 1984, an Adjunct Professor with Chalmers University of Technology, Göteborg, Sweden, since 2000, and a Scientific Advisor to Sintef Energy Research. He is the coauthor of the well-known book Power Electronics: Converters, Applications, and Design. His research interests are in the areas of power electronics and wind energy systems. Prof. Undeland is the President of the European Power Electronics society and a member of the Norwegian Academy of Technological Sciences. Authorized licensed use limited to: Norges Teknisk-Naturvitenskapelige Universitet. Downloaded on March 20,2010 at 07:21:49 EDT from IEEE Xplore. Restrictions apply.