6302 9646 – 02/2004 US/CA For Contractors Installation, Operation and Maintenance Manual Sealed Combustion Hot Water Gas Boiler Logano GA244 CAUTION! Before putting the boiler into operation read this manual carefully. WARNING ! Improper installation, adjustment, alteration, service or maintenance can cause injury, loss of life or property damage. Refer to this manual. For assistance or additional information consult a qualified installer, service agency or the gas supplier. CAUTION ! The operating manual is part of the documentation that is delivered to the installation's operator. Go through the information in this manual with the owner/operator and make sure that he or she is familiar with all the necessary operating instructions. Notice: This manual must be retained for future reference. Read manual prior to installation and maintenance of the boiler Imprint Please read this manual carefully! Correct installation and adjustment of the burner and the control panel is a precondition for safe and efficient operation of the gas boiler. Read this manual and the specifications on the safety label carefully before attempting to put the boiler into operation. We reserve the right to make any changes due to technical modifications! 2 Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 Table of Contents 1 Safety Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 1.1 Application purpose . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 1.2 Guideline of Notices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 1.3 Observe the following symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 2 Regulations and Guidelines 3 Dimensions and Boiler Connections 4 Packaging and Components . 5 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8 5.1 Transporting the Boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8 5.2 Installation Surface Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9 5.3 Preparations for Boiler Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9 6 Boiler Water Connections . 7 Electrical Supply . 8 Gas Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 8.1 Gas Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 8.2 Installation at Higher Elevations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 9 Combustion Air and Ventilation Openings . . . . . . . . . . . . . . . . . . . . . . . . 15 10 Installation of the Exhaust and Air Intake System . . . . . . . . . . . . . . . . . . 17 10.1 Installation of Horizontal Wall Terminal Body . . . . . . . . . . . . . . . . . . . . . . . . . . 18 10.2 Installation of Vertical Venting System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 10.3 Installation of Exhaust and Air Intake Piping . . . . . . . . . . . . . . . . . . . . . . . . . . 21 11 Placing the Boiler in Operation . 11.1 11.2 11.3 11.4 11.5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 Lighting Instructions . . . . . . . . . . . Operating Instructions . . . . . . . . . . Shut off of Gas Supply . . . . . . . . . Start-up Procedure Chart . . . . . . . . Detailed Steps for Start-up Procedure 12 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 12.1 Maintenance Record . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 12.2 Maintenance Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 12.3 Trouble Shooting Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 13 Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49 14 Orifice Tables for High Elevations and Propane . 15 Wiring diagrams . . . . . . . . . . . . . . . . . . . 68 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69 We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 3 1 1 Safety Considerations Safety Considerations Please observe the following safety instructions. 1.1 1.3 Observe the following symbols DANGER Application purpose due to explosion of gas. The GA244 gas boiler is designed for use as a hot water heating boiler to heat water for space heating purposes for a single and multi family houses. 1.2 WARNING! z Note that the assembly of gas and vent connections, the initial start-up, the electrical connections, the maintenance and service can only be performed by a licensed service contractor or technician. Guideline of Notices Two levels of danger are identified by the following warning labels: DANGER DANGER WARNING! CAUTION! Denotes a possible severely dangerous situation where, without proper caution, bodily injury or loss of life may result. z Work only on gas components when you have a license to do so. due to electricity. WARNING! z Prior to doing any work on the heating system, disconnect all electrical power to the boiler at the emergency switch. DANGER OF INJURY/ SYSTEM DAMAGE z It is NOT sufficient to shut off only the boiler control! Denotes a possible dangerous situation that can lead to mild to moderate bodily injury or physical damage. SYSTEM DAMAGE The following symbols are used to denote a danger and other notices: due to improper installation. CAUTION! DANGER z Observe local and state codes as well as common industry practices during the installation and operation of the heating appliance. due to electricity. SYSTEM DAMAGE WARNING! APPLICATION NOTICE Application comment for optimum use of equipment and adjustment as well as useful information. CAUTION! due to inadequate cleaning and maintenance. z A boiler cleaning and maintenance should be performed annually. Verify complete system operation at the same time. z Correct the problem immediately to prevent damage to the system! We reserve the right to make any changes due to technical modifications! 4 Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 Regulations and Guidelines 2 2 Regulations and Guidelines The installation must be conform to the requirements of the authority having jurisdiction or, in the absence of such requirements, to the latest edition of the National Fuel Gas Code, ANSI Z223.1. In Canada, installation must be in accordance with the requirements of CAN/CGA B149.1 or 2 Installation Code for Gas Burning Appliances and Equipment. Where required by the authority having jurisdiction, the installation must conform to the Standard for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ASME CSD-1. Install CO detectors per local regulations. Boiler requires yearly maintenance, see maintenance section see section 12 „Maintenance“, page 35. Operating Limits of the boiler: Max. boiler temperature: 220°F Max. operating pressure: 58 psi The hot water distribution system must comply with all applicable codes and regulations. When replacing an existing boiler, it is important to check the condition of the entire hot water distribution system to insure safe operation. We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 5 3 Dimensions and Boiler Connections 3 Dimensions and Boiler Connections B D A 5 6 4 C 1 3 2 Fig. 1 Rear, side and front views, measurements in inches Pos. 1: Boiler return (1 ½“) Pos. 2: Boiler drain connection (¾“) Pos. 3: Gas connection (¾“) Pos. 4: Boiler supply (1 ½“) Pos. 5: Exhaust connection Pos. 6: Air intake connection Boiler model Heating capacity Air intake connection Exhaust connection Min. Relief Valve No. of Burners Watercontent Dry weight MBtu/hr Inches Inches lb/hr No. US Gal. lbs 37 128 4 3 130 4 6.1 635 44 148 4 3 153 4 6.1 635 53 181 4 3 188 5 7.1 688 62 212 4 4 218 6 8.2 772 Table. 1 Dimensions 37 44 53 62 A Air intake Inches 7 3/8 B Exhaust Inches 17 1/2 7 3/8 17 1/2 7.9 20.9 7.9 24.4 C D Inches 43 3/4 Inches 43 3/4 43.3 43.3 7.25 156/182 MBTu/h (Size 37/44) 25 6/8 25 6/8 29.1 32.7 Pressure Drop in psi Boiler model Table. 2 Dimensions 1.45 0.1 1.8 17.6 68.2 Flow Rate in GPM Fig. 2 We reserve the right to make any changes due to technical modifications! 6 Pressure drop through the boiler Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 Packaging and Components 4 4 Packaging and Components The boiler is shipped as a packaged unit complete with jacket panels, installed gas burner tray and gas valve and technical documents. The following components are packaged in a separate box within the boiler packaging: – 1 3/4“ female boiler drain elbow – 1 3/4“ 90° Elbow – 1 3/4“ Relief valve – 1 horizontal wall terminal body Following accessories are available as well: – Cleaning brushes – Vertical wall terminal body We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 7 Installation This boiler is certified for closet installations. To ensure adequate access to the boiler during installation and maintenance, the boiler should have a minimum space in front of the boiler of at least 33" with the access door open. When the access door is closed, a minimum clearance of 2 inches in front and on the sides of the boiler from combustibles is required (Fig.3). Maintain a minimum clearance from combustibles of 2 inches for the exhaust vent pipe. A 20“ top clearance is recommended for cleaning access and is strictly required when the boiler is placed in a fully enclosed closet. A 2“ rear clearance is required for horizontal vent pipe installations. The gas boiler is certified for installation on combustible flooring. The boiler must not be installed on carpeting. 2" 3 1 2" Provide 2“ clearance between vent pipe and combustible construction. No clearance is required between wall terminal body and combustible construction 2" 5 Installation Fig. 3 33" 5 2" 2 Minimum clearances from combustible construction Item. 1: Access door closed Item. 2: Access door open Item. 3: Exhaust vent pipe 5.1 Transporting the Boiler z Transport the boiler to the installation site in the shipping carton and on the pallet. z Remove strapping and lift off carton. z Remove the two bolts that secure boiler to the wooden pallet. z Lift the boiler from one side and slide to the side of the pallet. Push a pipe under the boiler as shown in Fig. 4 and roll boiler on several pipes to its final location. z Move the boiler to its final installation position. NOTICE ! Always protect sheet metal parts, gas pipe, burner and control panel during handling. z Never lift the boiler on these parts. We reserve the right to make any changes due to technical modifications! 8 Fig. 4 Moving the boiler Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 Installation 5.2 5 Installation Surface Requirements The boiler is very heavy when filled with water. Make sure the floor is strong enough to support the load. 5.3 Preparations for Boiler Installation z Unpack all boxes and cartons and check that all parts have been delivered using the packing list. NOTICE ! Each boiler is checked and tested carefully before leaving the factory. If there is any damage or parts are missing, inform the supplier without delay. Check all packaging materials for missing components before discarding them. We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 9 6 6 Boiler Water Connections Boiler Water Connections BOILER DAMAGE ! due to moisture. DANGER! 3 z Install this boiler so that the gas ignition system components are protected from water (dripping, spraying, rain, etc.) during appliance operation and service (circulator replacement, control replacement etc.). SYSTEM DAMAGE ! DANGER! due to over heating during low water conditions. z If this boiler is installed above radiation level it must be provided with a low water cut-off device either as a part of the boiler or at the time of installation (see Fig. 5). 2 1 2 2 4 SYSTEM DAMAGE ! DANGER! due to high temperature differences in the system. z If the boiler is used in conjunction with a refrigeration system, pipe the chilled medium in parallel with the boiler and install the proper valve to prevent the chilled medium from entering the boiler. z When the boiler is connected to heating coils located in air handling units where they may be exposed to refrigerated air circulation, the boiler must be equipped with flow control valves or other automatic means to prevent gravity circulation of the boiler water during the cooling cycle. 2 2 1 2 Fig. 5 Low water cut off installation Item. 1: Gas boiler Item. 2: heating elements (panel radiator, baseboard, etc.) Item. 3: system requiring low water cut off Item. 4: system not requiring low water cut off We reserve the right to make any changes due to technical modifications! 10 Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 Boiler Water Connections z Install the 90° street elbow (Fig. 6) and the relief valve (Fig. 6 ) on the boiler supply connection. 6 1 z Install relief valve according to ANSI/ASME Boiler and Pressure Vessel Code, Section IV. Mount the relief valve stem vertically. Use ¾" street elbow as needed. 2 NOTICE ! 3 4 Observe local and state codes when installing the boiler. FIRE DANGER ! due to hot piping. DANGER! z Maintain a minimum 2" clearance between the hot water piping and combustible walls. Water treatment Fig. 6 Rear view Item. 1: Gas boiler Item. 2: Boiler supply connection Item. 3: Relief valve NOTICE ! Item. 4: Boiler supply pipe Perform a water analysis prior to filling the boiler system. Treatment of the boiler water may be required depending on the analysis results. For extremely hard water or pH value below 7.0 consult your local water treatment company. We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 11 7 7 Electrical Supply Electrical Supply The electrical connections to the boiler must be made in accordance with all applicable local codes and the latest revision of the National Electrical Code, ANSI/NFPA-70. Installations should also conform with CSA C22.1 Canadian Electrical Code Part 1 if installed in Canada. The boiler must be electrically grounded in accordance with the requirements of the authority having jurisdiction or, in the absence of such requirements, with the National Electrical Code, ANSI/NFPA 70. NOTICE For wiring details, follow the wiring diagrams found on page 69 and page 70. Install an emergency switch near the boiler. CAUTION ! due to electricity. WARNING! z Label all wires prior to disconnection when servicing controls. z Wiring errors can cause improper and dangerous operation. z Verify proper operation after servicing. We reserve the right to make any changes due to technical modifications! 12 Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 Gas Supply 8 8 Gas Supply 8.1 Gas Connections Determine proper size gas pipe for the installation using Table 3 and Table 4. Do not forget the pipe fitting losses and observe proper size of the fittings. 1 A sediment trap must be installed at the inlet of the gas supply piping to the boiler. When local codes require, a manual shut-off valve must be installed outside the boiler jacket. It is recommended that a manual shut-off valve be installed on the main gas piping to the boiler. The gas piping must be supported external to the boiler. 2 When installing the gas supply connection, it must comply with local regulations or, if such regulations do not exist, with the National Fuel Gas Code, ANSI Z 223.1. In Canada, the gas supply connection must comply with local regulations or, if such regulations do not exist, with CSA/CGA-B149 Installation Guidelines. 3 EXPLOSION DANGER ! Fig. 7 DANGER! The possibility for explosions exists due to leaks in gas piping and connections. z All gas connections must be tested for leaks with a soap and water solution. Length of pipe (Feet) 1/2“ 3/4“ 1“ 1 1/4“ 1 1/2“ 10 132 278 520 1060 1600 20 92 190 350 730 1100 Gas supply piping: rear view Item. 1: Gas supply piping Item. 2: Manual shut off valve Item. 3: Sediment trap Gas Volume Capacity (ft3 / hr)1 30 73 152 285 590 890 40 63 130 245 500 760 50 56 115 215 440 670 75 45 93 175 360 545 100 38 79 160 305 480 150 31 64 120 250 380 Table 3 Gas Pipe Capacity for different pipe sizes 1 Maximum pipe capacity in ft³/hr, based on a specific gravity of .60 and a gas supply pressure of .5 psi or less and a pressure drop of .3 inches W.C. We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 13 8 Gas Supply Equivalent Length for Pipe Fittings in feet Steel pipe Diameter (in Inch) Type of pipe fitting 90°Elbow Tee (flow thru branch) Gate valve Gas cocks Equivalent length in feet 1/2 1.4 2.7 0.3 0.80 3/4 2.1 4.1 0.5 1.25 1 2.6 5.2 0.6 1.6 1 1/4 3.5 6.9 0.8 2.15 1 1/2 4.0 8.0 0.9 2.50 8.2 Installation at Higher Elevations The boiler is factory set for operation with natural gas at elevations up to 2,000 ft. The boiler must be derated for installations above 2,000 ft. The derate is accomplished by changing the main burner orifices. Contact your supplier in this case to obtain the suitable high elevation conversion kit (Natural gas or LP). Do NOT attempt to derate the appliance without Buderus certified parts and instructions. Table 4 Equivalent length of pipe fittings in feet The boiler must be isolated from the gas supply piping system by closing its individual manual shut-off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than ½ psi. z The boiler and its gas connection must be leak tested before placing the boiler in operation. Refer to Chapter 11 "Placing the Boiler in Operation", page 26. Pipe joint compound (pipe dope) must be resistant to corrosive action of liquified petroleum gases and applied sparingly only on male threads of pipe joints. To field convert the boiler for operation with LP gas, please contact Buderus Hydronic Systems to obtain the proper components. Do not convert the boiler without the proper parts and instructions. Parts for LP conversion are included with the documents. We reserve the right to make any changes due to technical modifications! 14 Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 Combustion Air and Ventilation Openings 9 9 Combustion Air and Ventilation Openings BOILER DAMAGE AND OPERATIONAL FAILURES ! CAUTION! Due to insufficient or lacking openings for combustion air and/or ventilation of the boiler room. BOILER DAMAGE ! due to contaminated air. CAUTION! Provisions for combustion air and ventilation are always required, regardless whether the combustion air is taken from the outside (sealed combustion) or inside (room air for combustion). Insufficient ventilation of the boiler room can lead to high air temperatures. This can result in boiler damage. z Do not store and use these chemicals in the boiler room. z Avoid excessive dust formation and build-up. z Make sure that intake and exhaust openings are sufficiently sized and no reduction or closure of openings takes place. NOTICE ! z When the problem is not resolved, do not operate the boiler. When one expects contaminated combustion air (near swimming pools, chemical cleaning operations and hair salons), sealed combustion operation is recommended. z Please note these restrictions and its dangers to the operator of the boiler. Provisions must be made for combustion air and ventilation air in accordance with section 5.3 Air for Combustion and Ventilation, of the National Fuel Gas Code, ANSI Z 223.1, or applicable provisions of the local building code. Canadian installations must comply with CSA/CGAB149.1 and .2 Installation Codes. We reserve the right to make any changes due to technical modifications! z Boiler must be clear and free from combustible materials, gasoline and other flammable vapors and liquids, and corrosive liquids and vapors. Never use chlorine and hydrocarbon containing chemicals (such as spray chemicals, solution and cleaning agents, paints, glues etc) in the vicinity of the boiler. FIRE DANGER ! due to flammable materials or liquids. DANGER! z Do not store flammable materials and liquids in the immediate vicinity of the boiler. Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 15 9 Combustion Air and Ventilation Openings All Air from Inside the Building The closet shall be provided with two permanent openings communicating directly with an additional room(s). The total input of all gas utilization equipment installed in the combined space shall be considered in making this determination. Each opening shall have a minimum free area of 1 square inch per 1,000 Btu per hour of total input rating of all gas utilization equipment in the confined space, but no less than 100 square inches. One opening shall commence within 12 inches of the top, and one opening shall commence within 12 inches of the bottom of the enclosure. The minimum dimension of air openings shall be not less than 3 inches. All Air from Outdoor The closet shall be provided with two permanent openings, one commencing within 12 inches from the top, and one commencing within 12 inches from the bottom of the enclosure. The openings shall communicate directly, or by ducts, with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors. The minimum dimension of air openings shall be no less than 3 inches. 1. Where directly communicating with the outdoors, each opening shall have a minimum free area of 1 square inch per 4,000 Btu/hr of total input rating of all equipment in the enclosure. 2. Where communicating with the outdoors through vertical ducts, each opening shall have a minimum free area of 1 square inch per 4,000 Btu/hr of total input rating of all equipment in the enclosure. 3. Where communicating with the outdoors through horizontal ducts, each opening shall have a minimum free area of 1 square inch per 2,000 Btu/hr of total input rating of all equipment in the enclosure. 4. Where ducts are used, they shall be of the same cross-sectional area as the free area of the opening to which they connect. We reserve the right to make any changes due to technical modifications! 16 Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 Installation of the Exhaust and Air Intake System 10 10 Installation of the Exhaust and Air Intake System A horizontal terminal body is included with every boiler. APPLICATION NOTICE ! Materials from the following manufacturers are approved for use for exhaust venting materials and air intake piping: Consult local and state codes pertaining to special building code and fire department requirements. Adhere to national code requirements. Manufacturer Exhaust venting piping 3“/ 4“ horizontal vertical* Typ Typ Heat fab SAF-T vent SAF-T vent O-flex-L Star 34 - Pro Tech FasNSeal - Z-Flex Z-Flex, model SVE - APPLICATION NOTICE ! Observe the listed maximum lengths of vent system, which are boiler model dependent. The maximum permissible lengths are listed in Table 7, page 24 to Table 9, page 25. Table 5 Approved exhaust vent pipe manufacturers * Vertical „trough the roof“ configuration is not part of the standard boiler package. APPLICATION NOTICE ! Install vent pipe components per manufacturer's instructions. Observe the listed maximum diameters of vent system, which are boiler model dependent. Use only 3" or 4“ (4“ for model /62 only) stainless steel (AL29-4C) components (e.g. 37/44 kW = 3“) for exhaust vent piping as listed in the above table (Table 5). Use only 4" flexible or 4" galvanized rigid pipe for combustion air intake piping. The exhaust and intake air piping components are available from your local wholesaler. Make sure to use matching components. OPERATIONAL PROBLEMS ! due to strong winds. NOTICE! The boiler will cease to operate under strong winds when no termination tee is installed at the end of the venting system. z Note that a termination tee MUST always be installed at the end of every horizontal venting system. z Purchase the suitable termination tee together with your selected vent pipe manufacturer for best fit. We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 17 10 Installation of the Exhaust and Air Intake System 10.1 Installation of Horizontal Wall Terminal Body Read these instructions first completely concerning horizontal termination body installation and observe the noted safety precautions. The horizontal wall terminal body must be installed through the wall according to previously mentioned codes and/or local requirements. z Make a 6" round opening in the outside wall at the desired location. Refer to the information on the next page regarding limitations of termination location. z Remove fresh air connection end from the terminal body and insert terminal body from the outside through the round 6" hole in the wall (Fig. 8). Install fresh air connection piece. Secure wall plate with 4 furnished screws to the wall. Fig. 8 Installation of horizontal wall terminal body z Insert a 2 or 3 foot straight exhaust pipe (Fig. 9, Item. 2) from the outside into the wall terminal body. Slide termination tee on exhaust pipe and seal joint with silicone (Fig. 9, Item. 3). Orient termination tee horizontally and observe the manufacturer's installation instructions. 1 Fig. 9 2 3 Installation of exhaust pipe Item. 1: wall terminal body Item. 2: Exhaust vent pipe Item. 3: Termination tee We reserve the right to make any changes due to technical modifications! 18 Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 Installation of the Exhaust and Air Intake System 10 z Insert the vent pipe into the terminal body far enough so that distance between the termination tee and the wall is about 10" (Fig. 10). z Secure both ends of the exhaust pipe through the terminal body using the furnished locking collars. (Fig. 10, Item. 1). Rotate collars downward and secure set screw on locking collars (Fig. 11, Item. 2). 1 z Seal the space between vent pipe and locking collars with silicone (Fig. 11, Item. 1). 1 A venting system that exits the structure through a sidewall or the like, shall terminate at least 12 inches above the ground. The installation of a screened termination tee is required to ensure trouble free operation and prevent entry of foreign objects into the vent system. 2 Fig. 10 Positioning of the termination tee Item. 1: Locking collars Item. 2: 4“ Air intake connection The termination of the system shall be located at least 12 inches above the maximum snow line in geographic areas where snow accumulates. 1 No changes or modifications are allowed in the venting system. All components must be installed in their original condition. The termination shall not terminate less than 7 ft above a paved sidewalk or driveway. The termination shall be at least 6 ft away from the combustion air intake of any other appliance. Room air only: The termination shall be at least 3 ft away from gas utility meter, service regulator or the like (for room air applications only). The termination shall terminate at least 4 ft below, 4 ft horizontally from, or 1 ft above any door, window, or gravity air inlet into any building. We reserve the right to make any changes due to technical modifications! 2 Fig. 11 Vent pipe locking collars Item. 1: Seal space with beads of silicone Item. 2: Set screws Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 19 10 Installation of the Exhaust and Air Intake System 10.2 Installation of Vertical Venting System NOTICE ! Only venting components and concentric vent pipe manufactured by Heat-Fab type SAF-T Vent can be used for vertical venting applications. Please contact Buderus Hydronic Systems,Inc. for assistance in selecting proper venting components. 1 2 Follow all instructions concerning assembly of the individual venting components. Follow in particular the instructions furnished by the vent pipe manufacturer. 3 3 The combustion air is ducted in using a concentric 6" or 7“ pipe configuration in a vertical venting application Fig. 12. 4 NOTICE ! Fig. 12 Ensure that a condensate drain is always installed at the boiler exhaust connection. Item. 1: Wall terminal body Vertical venting system (sealed combustion) Item. 2: Fire stop plate Item. 3: Support of vent system Item. 4: Condensate drain Observe the vent extension above the roof line as shown in Fig. 12. The maximum length of the concentric "through the roof" venting is 10 ft. (see Fig. 12). 1 2 Observe the maximum length of the entire vent system including the concentric piping based on Table 7, page 24 to Table 9, page 25. The concentric piping permits a zero clearance to combustibles. Note, however, that the exhaust vent pipe leading up to the concentric piping requires a 2" minimum clearance to combustibles. 3 3 Install fire stop plates when penetrating the roof (Fig. 12, Item. 2). 4 Fig. 13 Vertical venting system (Room air only) Item. 1: Roof termination Item. 2: Fire stop plate Item. 3: Support for vent system Item. 4: Condensate drain We reserve the right to make any changes due to technical modifications! 20 Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 Installation of the Exhaust and Air Intake System 10 10.3 Installation of Exhaust and Air Intake Piping Installation of exhaust vent pipe at the boiler (Fig. 15, Item. 2) z Install a condensate drain at the rear of the boiler (Fig. 14). 3 4 NOTICE ! Always install a condensate drain as the first component of the exhaust system. 2 z Place a ¼" wide silicone bead (Fig. 14, Item. 1) on the boiler exhaust collar. (Use silicone with a 500 F temperature rating, G.E. 106 or equivalent). z Slide condensate drain on exhaust collar (Fig. 14, Item. 4) and secure with the furnished pipe clamp (Fig. 14, Item. 3). (Heat-Fab condensate drain will fit around outer collar, other condensate drains fit on inner collar.) z Place a silicone bead around the clamp (Fig. 14, Item. 2) and spread out to ensure an air tight seal. 1 Fig. 14 Condensate drain Item. 1: Silicone bead Item. 2: Silicone bead Item. 3: Gear clamp Item. 4: Condensate drain Installation of the air intake pipe (Fig. 15, Item. 1) at the boiler 2 1 Follow the same installation procedure as with the exhaust piping. Do not install a condensate drain here. Fig. 15 Rear view of the boiler Item. 1: Air intake connection Item. 2: Exhaust connection We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 21 10 Installation of the Exhaust and Air Intake System DANGER ! due to possible intake of exhaust gases. WARNUNG! 4 z Connect the venting system only to a single appliance. 4 1 z Venting of an additional appliance could cause serious injury or loss of life. 2 z The venting system shall not be routed into, through or within any other vent, such as an existing masonry or factory built chimney flue. 3 FIRE DANGER ! WARNUNG! due to minimal distances between vent pipe and combustible materials. z Provide 2“ clearance between vent pipe and combustible construction. Fig. 16 Horizontal venting system z No clearance is required between wall terminal body and combustible construction. Item. 2: Termination tee Item. 1: Wall terminal body Item. 3: Condensate drain Item. 4: Support bracket of venting system The vent pipe must be properly supported. Vertical runs must use firestops as lateral supports at each ceiling level and at least one support collar at the base of the vertical run. 1 Horizontal runs require a loose fitting metal strap or similar support every 4 ft and at every elbow and pipe connection joint. 2 Make sure never to penetrate the piping components when securing the straps or installing the various vent components. When cutting pipes to length, file the cut length smooth. Do not cut off the female end of the vent pipe. 3 3 All horizontal runs must be sloped down towards the boiler at least ¼" per foot. In the case of multiple horizontal runs, slope all runs towards the boiler to prevent moisture build-up in the system. 4 Fig. 17 Vertical venting system Item. 1: Roof termination Item. 2: Fire stop plate Item. 3: Support bracket of venting system Item. 4: Condensate drain We reserve the right to make any changes due to technical modifications! 22 Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 Installation of the Exhaust and Air Intake System 10 The vent system will be under positive pressure. Check all seams for gas tightness. Allow 24 hours for silicone to cure before operating the boiler. DANGER ! due to possible intake of exhaust gases. DANGER! z When any of the previous installation procedures are completed be sure to go over the entire system to make sure all joints are secure and sealed correctly. z Check all seams and joints for gas tightness. z It is required to have the entire system checked by a qualified inspector at least annually following initial installation. NOTICE ! Table 6 shows the equivalent length for each 45° and 90° elbow for each listed vent pipe manufacturer of each GA244 model boiler. Equivalent length of vent pipe / air intake pipe in ft. model 37 model 44 model 53 model 62 Manufacturer Typ 45° 90° 45° 90° 45° 90° 45° 90° heat fab SAF-T vent 4.5 9 4.5 9 5 10 3.5 7 O-flex-L Star 34 5 10 5 10 5 10 5 10 Pro Tech FasNSeal 5 10 5 10 5 10 4 8 Z-Flex Z-Flex 4.5 9 4.5 9 5 10 4 8 Table 6 Equivalent length of vent pipe / air intake pipe NOTICE ! NOTICE! The follwing maximum equivalent length of exhaust pipe (Table 7, page 24 and Table 9, page 25) represents the maximum equivalent length of exhaust vent pipe or air intake pipe only, without condensate drain tee, vent piping within the termination body and length of the termination tee. Note that we only need to be concerned about the longest run; do not combine intake and exhaust piping. We reserve the right to make any changes due to technical modifications! To increase overall vent length, use a couple of 45° elbows on air intake piping and run the intake piping at an angle. Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 23 10 Installation of the Exhaust and Air Intake System 10.3.1 Sealed Combustion and Horizontal Venting Combustion air from outside the building. Sealed Combustion Configuration Boiler model Exhaust vent pipe/ Air intake pipe 37 50 feet 44 40 feet 53 50 feet 62 50 feet 1 Table 7 Maximum equivalent length of exhaust vent pipe or air intake pipe for horizontal venting (Fig. 18) 2 10.3.2 Room Air Configuration and Horizontal Venting Combustion air from boiler room. Fig. 18 (No air intake pipe needed) Horizontal sealed combustion vent system Item. 1: Exhaust vent pipe 3“ Item. 2: Air intake pipe 4“ Room Air Configuration Boiler model Exhaust vent pipe 37 50 feet 44 40 feet 53 50 feet 62 50 feet 2 Table 8 Maximum equivalent length of exhaust vent pipe (for horizontal venting Fig. 19) Fig. 19 1 Horizontal room air venting system Item. 1: Exhaust vent pipe 3“ Item. 2: Combustion air from room We reserve the right to make any changes due to technical modifications! 24 Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 Installation of the Exhaust and Air Intake System 10 10.3.3 Sealed Combustion and Vertical Venting Combustion air from outside the Building. Sealed Combustion Configuration Boiler model Exhaust vent pipe/ Air intake pipe 37 40 feet (max. 10 feet co-axial) 44 40 feet (max. 10 feet co-axial) 53 50 feet (max. 10 feet co-axial) 62 50 feet (max. 10 feet co-axial) 1 Table 9 Maximum equivalent length of exhaust vent pipe or air intake pipe for vertical venting (Fig. 20) NOTICE ! 2 Do not exceed 10 ft concentric piping with vertical termination. Fig. 20 Vertical sealed combustion vent system Item. 1: Exhaust vent pipe 3“ (models 37, 44 and 53) Item. 2: Air intake pipe 4“ 10.3.4 Room Air Configuration and Vertical Venting Room Air Configuration Boiler model Exhaust vent pipe 37 40 feet 44 40 feet 53 50 feet 62 50 feet 1 Tab. 10 Maximum equivalent length of exhaust vent pipe for vertical venting (Fig. 21) NOTICE ! Vertical concentric piping is only required for the length of the roof penetration. Combustion air can be drawn then directly from the boiler room. We reserve the right to make any changes due to technical modifications! Fig. 21 Vertical vent system for room air configuration Item. 1: Exhaust vent pipe 3“ (models 37, 44 and 53) Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 25 11 Placing the Boiler in Operation 11 Placing the Boiler in Operation Safe lighting and other performance criteria were met with the gas manifold and control assembly provided on the boiler when the boiler underwent factory tests specified in ANSI Z 21.13 and CSA 4.9. 2 DANGER due to electricity when control is opened. WARNUNG! z Before opening the boiler: ensure all electric power has been disconnected with the main shut-off switch. z Secure the system from someone accidentally turning on the power. 1 1. Turn off all electric power to the appliance and set the thermostat to lowest setting. 1 Fig. 22 Remove the boiler front access panel Item. 1: Screws Item. 2: Boiler front jacket panel 2. Check the combustion air inlet, exhaust vent and ventilation openings. 6 5 3. Fill the boiler system with water and purge the air from the boiler and radiators. 7 4. Remove the screws from the boiler front access panel (Fig. 22, Item. 1) and remove the boiler front access panel (Fig. 22, Item. 2). 4 5. Remove side cover plate screws (Fig. 23, Item. 1) from the right side jacket panel (Fig. 23, Item. 3) and then remove the side cover plate (Fig. 23, Item. 2). 3 Testing for leaks 6. Open the main gas supply shutoff valve. 7. Test the equalizing hose (Fig. 23, Item. 7) on the side of the gas valve connection (Fig. 23, Item. 4) and on the side of the burner box connection (Fig. 23, Item. 5) for leaks. 2 1 1 Fig. 23 Removal of side cover plate Item. 1: Screws 8. Check if the pressure test port on the burner box (Fig. 23, Item. 6) is closed. 9. Test the gas piping on the side of the gas control for leaks (Fig. 24) by applying a soap and water solution. If no leaks are found go to step 10. If any leaks are found, shut off the main gas piping shut-off valve. We reserve the right to make any changes due to technical modifications! 26 Item. 2: Side cover plate Item. 3: Right side jacket panel Item. 4: Connection port for equalizing hose, gas valve side Item. 5: Lower testing port from the burner to the gas valve Item. 6: Pressure test port, burner box Item. 7: Equalizing hose Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 Placing the Boiler in Operation 11 10. Repair leaks and repeat step 9. 11. Remove the manifold pressure tapping plug (Fig. 24, Item. 3) from the gas control, install a test fitting (Fig. 23, Item. 6) and hook up a manometer between pressure tapping plug (Fig. 24, Item. 3) (overpressure) and the pressure test port (burner box) (negative pressure) (Fig. 24, Item. 6) so that the line pressure can be checked. Check manifold pressure. Set the manifold pressure according the values in Table 11, page 29. If corrections are necessary see Table 11, page 29. 12. Open main gas piping shutoff valve and measure the supply pressure to the boiler. The supply pressure must be between 4.7 and 10.5 inches water column (WC) for natural gas or 11 and 13 inches water column for propane gas. If the pressure is not between 4.7 and 10.5 inches WC for natural gas or between 11 and 13 inches WC for propane gas, call your service technician or gas supplier. 2 1 4 Fig. 24 3 Gas control Item. 1: Gas control knob (set to “ON“) 13. Follow the lighting instructions below. Item. 2: Test port screw for gas supply measurement Item. 3: Test port screw for manifold pressure measurement Item. 4: Pilot tubing We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 27 11 Placing the Boiler in Operation 11.1 Lighting Instructions For your safety, read these instructions before lighting. WARNING ! due to not follow these instructions. WARNING! z If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life. C) Use only your hand to turn the gas control knob. Never use tools. If the knob will not turn by hand, don't try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion. D) Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water. z Follow these operating instructions. DANGER ! What to do if you smell gas: DANGER! z No open fire! Do not smoke! z Avoid formation of sparks! Do not touch any electric switch, phone, electric plug or bell! z Shut off main gas supply. z Open windows and doors! z Notify all occupants! z Leave the building! z Immediately call your gas supplier, heating contractor or fire department from a phone outside the building! A) This appliance is equipped with an ignition device which automatically lights the pilot. Do not try to light the pilot by hand. B) Check for smell of gas around the appliance area. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor. We reserve the right to make any changes due to technical modifications! 28 Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 Placing the Boiler in Operation 11.2 11 Operating Instructions STOP! Read the safety precautions on page 28 of this manual. 1. Wait five (5) minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas, STOP! Follow "B" in the safety information on page 28. If ou do not smell gas, go to the next step. 2. Locate the pilot assembly by looking through the access viewing port (Fig. 25, Item. 1) on the burner front plate. 3. Turn the gas control knob (Fig. 26, Item. 1) counterclockwise to position "ON". 4. Turn on the electrical power to the application. 1 5. Set the thermostat to the desired setting to activate the boiler (Thermostat adjustment should be at least 10 °F above the room temperature). Fig. 25 Burner tray box Item. 1: Access viewing port 6. The ignition control should initiate sparking at the pilot. The pilot should light and then the main burners should light. If the main burners do not light, shut off the main gas piping shutoff valve. Shut off all electric power to the appliance and call your service technician or gas supplier. 2 7. If the main burners light, then the gas fittings, union and orifices must be tested for leaks with a soap and water solution. If no leaks are found then go to step 9. If any leaks are found, turn off gas control knob (Fig. 26, Item. 1) clockwise to "OFF". Turn off all electric power to the appliance, set the thermostat to lowest setting. 5 1 8. Repair leaks. Repeat steps 1 through 7. 9. Check the supply pressure while the boiler is running. Pressure must be between 4.7 and 10.5 inches WC for natural gas. Pressure must be between 11 and 13 inches WC for propane gas. Record supply pressure on the boiler start-up procedure on page 33. 4 Fig. 26 3 Gas control valve Item. 1: Gas control knob (set to “ON“) Item. 2: Test port screw for gas supply measurement Item. 3: Test port screw for manifold pressure measurement Item. 4: Protective screw for pilot pressure adjustment Item. 5: Protective screw for manifold pressure adjustment 10. Check manifold pressure. Set the manifold pressure according the values in Table. 11. To adjust the manifold pressure (Fig. 26, Item. 5), remove the capscrew from the gas control and remove the hose from the manometer to the burner box test port (Fig. 23, Item. 6). Turn the pressure regulating adjusting screw clockwise to increase, or GA244 Natural Gas [inch W.C.] Propan [inch W.C.] 37 3.77 8.03 44 3.65 7.63 53 3.73 8.11 62 3.77 6.15 Table. 11 Required manifold pressure We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 29 11 Placing the Boiler in Operation counterclockwise to decrease the manifold pressure. This adjustment must be made while the boiler is in operation. 11. After adjustment, record pressure on the form on page 33, and install the capscrew (Fig. 26, Item. 5) on the gas control valve. Shut the test port screw for manifold pressure measurement. 12. Observe the pilot flame (Fig. 27, Item. 2) through viewing port (Fig. 27, Item. 1) in the burner cover plate. The flame should envelop the flame sensor 1/2 to 1 1/2 inch, see (Fig. 27, Item. 1). If the pilot flame is satisfactory then go to step 13. If the pilot flame is too small or too large, adjust the pilot using pilot adjustment screw. Turn the inner adjustment screw (Fig. 26, Item. 4) clockwise to decrease, or counterclockwise to increase the pilot flame. After adjustment, replace the cover screw (Fig. 26, Item. 4) and tighten firmly. 2 1 Fig. 27 Pilot flame Item. 1: 1/2“ to 1 1/2“ Item. 2: Pilot flame 13. Observe the main burner flame (Fig. 28, Item. 1) through the viewing port (Fig. 25, Item. 1) in the burner cover plate. The flame should have a smooth, firm contour and must be mostly blue color. If the main burner flame is satisfactory then go to step 14. If the main burner flame is lazy, yellow, or lifting off the burners, turn the gas control knob (Fig. 26, Item. 1) to "OFF". Shutt off the main gas supply shut-off valve. Disconnect all electric power to the appliance and call your technician or gas supplier. 1 14. The ignition safety shut-off must be tested. Test the safety shut-off by shutting off the main gas piping shutoff valve. The main burner and pilot flame (Fig. 27, Item. 2) will extinguish. Within six (6) seconds the gas control main gas solenoid should close and make an audible sound. The ignition will spark. Fig. 28 Main gas burner Item. 1: Main burner flame After 90 seconds, the module should go into lock out mode and the spark should stop. Disconnect the electric power to the appliance. Open the main gas shutoff valve. Turn on the electric power to the unit. A normal operating sequence should occur. If the gas control functions satisfactorily then go to step 15. If the gas control does not function satisfactorily, immediately turn the gas control knob (Fig. 29, We reserve the right to make any changes due to technical modifications! 30 Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 Placing the Boiler in Operation 11 Item. 1) clockwise to "OFF". Shut off the main gas piping shut-off valve. Disconnect all electric power to the appliance and call your service technician or gas supplier. 15. Turn the gas control knob (Fig. 29, Item. 1) counterclockwise to "OFF". 16. Shut the main gas piping shut-off valve. 17. Turn off electric power to the appliance, and set the thermostat to the lowest setting. 18. Remove the pressure test fittings from the gas supply and manifold pressure tabs in the gas control and replace the plugs. 19. Repeat steps 1 to 6, and 13 to place the appliance back in operation. Check the plugs in the gas control with a soap and water solution. If no leaks are found go to step 21. If any leaks are found, shut off the main gas piping shut-off valve and turn off all electric power to the appliance and turn the gas control knob clockwise to "OFF" (Fig. 29, Item. 1). 20. Repair leaks. Open the main gas shutoff valve and repeat step 19. 1 Fig. 29 Gas control valve Item. 1: Gas control knob 21. Wash off the soap and water solution used to test for leaks to ensure no corrosive effects from the soap. 22. Check the high limit aquastat operation to ensure that it shuts off the boiler when the boiler water temperature reaches the setpoint of the aquastat. Records fill in on form found on page 33. 23. Replace the front boiler jacket panel. We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 31 11 Placing the Boiler in Operation 11.3 Shut off of Gas Supply 1. Set thermostat to its lowest setting. 2. Turn off all electric power to the appliance if service is to be performed. 3. Remove the front boiler jacket panel, see Fig. 22, page 26. 4. Turn gas control knob (Fig. 29, Item. 1) clockwise to “OFF“. Do not force. 5. Replace the front boiler jacket panel. We reserve the right to make any changes due to technical modifications! 32 Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 Placing the Boiler in Operation 11 11.4 Start-up Procedure Chart Record the following information during initial start-up of the boiler. This record will save as a reference for yearly inspections. Please consider the instructions on the following pages. Putting into operation Remarks or measurements Natural Gas Propane 1. Note type of gas. 2. Check combustion air and ventilation openings and flue connection 3. Check boiler for correct orifices, see Table. 12 below 4. Fill boiler with water and purge air from the system. 5. Measure gas inlet pressure in inches water colum. ––––––––––––––––––– inches W. C. 6. Check manifold pressure and adjust if necessary. ––––––––––––––––––– inches W. C. 7. Leakage test during operation Check pilot and main burner flames and vent system operation. 8. Take stack measurements; see instructions on following pages. Gross stack flue gas temperature tA ––––––––––––––––––– °F Ambient air temperature tL ––––––––––––––––––– °F Net stack flue gas temperatiure tA - tL ––––––––––––––––––– °F Carbon dioxide content stack (CO2) or oxygen content (O 2) ––––––––––––––––––– % Flue gas loss qA ––––––––––––––––––– % Carbon monoxide content (CO), airfree in ppm ––––––––––––––––––– ppm 9. Check the high limit aquastat operation 10. Replace the boiler front jacket panel 11. Inform owner/sign and hand over the technical documents 12. Installing Contractor Signature:__________________ Owner: Signature:__________________ Main orifice Size Boiler model 37 44 53 62 Natural gas 3.00 3.25 3.20 3.15 Propane gas 1.95 2.15 2.10 2.20 Table. 12 Main orifice sizes We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 33 11 Placing the Boiler in Operation 11.5 Detailed Steps for Start-up Procedure 11.5.1 Taking flue gas measurements z Record all measurements on page 33. z Take sampling probe to the outside of the building. Under no circumstances drill a hole in the venting system! z Take all flue gas samples from this location. z Allow boiler to run for 5 minutes before taking measurements. Carbon monoxide content The measured carbon monoxide content must be converted according to the following formula to an air free state and entered in the record. CO2 max for natural gas is approx. 12 % (propane, approx. 14 %) CO airless = CO2 max./CO2 measured x CO measured In an airless state, CO measurements must be lower than 400 ppm or .04 % volume. Measurements around or greater than 200 ppm indicate an erroneous burner setting, dirt in the gas burner or heat exchanger, or defects in the burner. z The problem must be correctly immediately. 11.5.2 Carbon dioxide content z If the carbon dioxide content is less than 5 % or more than 9 % for natural gas or less than 6 % or more than 10 % for propane, check the setting of the air inlet plate and the integrity of the complete venting system (Fig. 18a). Inform the owner/operator and hand over the technical documents. Make the owner/operator familiar with the entire installation and the operation of the boiler. Sign the form with the owner on page 35 and turn over the documents to the owner (page 33). 11.5.3 Flue gas loss SYSTEM DANGER ! Flue gas loss can be calculated with the following formula: due to frost. CAUTION! qA = ((tA – t L) x A) /CO2 in % The heating system can freeze up if the system is shut down for the winter. qA = flue gas loss tA = gross flue gas temperature in F tL = ambient air temperature in F A = see Table 12 CO2 = carbon dioxide in % z Protect the heating installation from freezing. z Drain water from the boiler, heating system and hot water tank to prevent freezing. Values for A and B are listed below: A Natural gas 0.62 Propane gas 0.53 Table. 13 We reserve the right to make any changes due to technical modifications! 34 Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 Maintenance 12 12 Maintenance 12.1 Maintenance Record Maintenance should only be performed by a trained technician on a yearly basis. Check off the maintenance items once they are completed and enter the measurements where indicated. Read and follow the maintenance instructions on the following pages. Maintenance items Date: Date: Date: 1. Examine venting system, including combustion, ventilation and intake air 2. Inspect boiler 3. Inspect gas burner 4. Clean boiler 5. Clean gas burner 6. Measure gas supply pressure ––––––– inches W. C. –––––––inches W. C. –––––––inches W. C. 7 Measure manifold pressure ––––––– inches W. C. –––––––inches W. C. –––––––inches W. C. 8. Check for air tightness of boiler 9. Check pilot and main burner flames 10: Check inducer motor operation 11. Take measurements Gross flue gas temperature tA ––––––––––––– °F ––––––––––––– °F ––––––––––––– °F Air temperature tL ––––––––––––– °F ––––––––––––– °F ––––––––––––– °F Net flue gas temperature tA - tL ––––––––––––– °F ––––––––––––– °F ––––––––––––– °F Carbon dioxide content (CO2) in % or oxygen content (O2) ––––––––––––– % ––––––––––––– % ––––––––––––– % Flue gas loss qA, see page 36 ––––––––––––– % ––––––––––––– % ––––––––––––– % Carbon monoxide content (CO), airfree ––––––––––––– ppm ––––––––––––– ppm ––––––––––––– ppm 12. Check high limit aquastat operation 13. Check boiler area for combustible materials, gasoline and other flammable or corrosive liquids. 14. Confirmation of maintenance Confirmation by service provider (Signature) We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 35 12 Maintenance Date: Date Date Date Date ––––––– inches W. C –––––––inches W. C –––––––inches W. C –––––––inches W. C –––––––inches W. C ––––––– inches W. C –––––––inches W. C –––––––inches W. C –––––––inches W. C –––––––inches W. C ––––––––––––– °F ––––––––––––– °F ––––––––––––– °F ––––––––––––– °F ––––––––––––– °F ––––––––––––– °F ––––––––––––– °F ––––––––––––– °F ––––––––––––– °F ––––––––––––– °F ––––––––––––– °F ––––––––––––– °F ––––––––––––– °F ––––––––––––– °F ––––––––––––– °F ––––––––––––– % ––––––––––––– % ––––––––––––– % ––––––––––––– % ––––––––––––– % ––––––––––––– % ––––––––––––– % ––––––––––––– % ––––––––––––– % ––––––––––––– % ––––––––––––– ppm ––––––––––––– ppm ––––––––––––– ppm ––––––––––––– ppm ––––––––––––– ppm We reserve the right to make any changes due to technical modifications! 36 Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 Maintenance 12 12.2 Maintenance Procedure Maintenance should only be performed by a qualified service technician. When replacing parts, use only Buderus authorized components. Maintenance should be done on a yearly basis. Results of the inspection must be recorded on the form provided on page 35. Comments below refer back to points of maintenance record list on page 35. 1.: Examination of venting system, including combustion, ventilation and intake air components Inspect the venting system including the combustion, ventilation and intake air openings. Any repairs identified must be corrected immediately. Ensure that there is no obstruction of combustion, air intake and ventilation air flow. 2.: Inspection of boiler DANGER ! DANGER! due to electric power with opened boiler jacket panel. z Before removing the boiler front jacket panel: disconnect electric power to appliance or turn off power switch to the appliance. z Protect the system against accidental power up. We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 37 12 Maintenance Removal of gas burner: 1. Shut-off main gas piping shut off valve. 2. Remove the screws from the boiler front access panel (Fig. 30, Item. 1) and remove the boiler front access panel (Fig. 30, Item. 2). 2 1 1 Fig. 30 Removal of boiler jacket front panel Item. 1: Screws Item. 2: Boiler jacket front panel 3. Turn the gas control knob (Fig. 31, Item. 1) counterclockwise to "OFF". Do not force. DANGER due to explosion of the gas. WARNING! z Wait five (5) minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas, STOP! Follow "B" in the safety information on page 28. If ou do not smell gas, go to the next step. 1 Fig. 31 Gas control valve Item. 1: Gas valve knob (set to “ON“) We reserve the right to make any changes due to technical modifications! 38 Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 Maintenance 12 4. Disconnect gas pilot line (Fig. 32, Item. 1) from gas control (Fig. 32, Item. 9) 5. Label the flame roll-out switch wires (Fig. 32, Item. 2) and disconnect the wires from the flame roll-out switch (Fig. 32, Item. 3). 9 6. Disconnect gas control valve wires (Fig. 32, Item. 4) from the gas control valve (Fig. 32, Item. 7). 1 2 3 4 5 6 7 7. Secure gas supply pipe (Fig. 32, Item. 5) with a cable or rope around the gross control bracket. 8. Disconnect union (Fig. 32, Item. 6) between the gas valve (Fig. 32, Item. 7) and the main gas supply pipe (Fig. 32, Item. 5). Place the gasket from the union in a safe position. 8 DANGER ! WARNING! due to electricity . Fig. 32 z Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Item. 1: Ignition cable z Verify proper operation after servicing. Front view Item. 2: Flame roll-out switch cable Item. 3: Flame roll-out switch Item. 4: Gas valve cable Item. 5: Gas supply pipe Item. 6: Union Item. 7: Gas valve Item. 8: Air intake hose Item. 9: Gas control module 9. Loosen air intake hose (Fig. 32, Item. 8) and remove from burner tray box 10. Remove the nuts (Fig. 33, Item. 1) that secure the burner tray to the boiler and remove entire burner tray (Fig. 33, Item. 3). 11. Remove inducer motor when boiler requires cleaning; or go to 5.: “Cleaning of the gas burner“, page 42. 1 3 Fig. 33 2 1 Removal of the gas burner tray Item. 1: Nuts Item. 2: Union Item. 3: Gas burner tray assembly We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 39 12 Maintenance Removal of inducer. 1. Remove both screws (Fig. 34, Item. 1) on top rear jacket cover (Fig. 34, Item. 2). 2. Remove top rear jacket cover (Fig. 34, Item. 2). 2 1 1 Fig. 34 Removal of the Top rear jacket cover 3. Remove the screws from the fan blower box and remove the cover plate from the fan blower box. 4. Pull off the electrical connections. 5. Remove the screws from the flue collector. 2 6. Remove the screws (Fig. 35, Item. 3) that secure the sheet metal blower base. 1 3 7. Check blower wheel for dirt and clean when necessary. 4 8. Clean the boiler heat exchanger when necessary, see 4.: “Cleaning the boiler“, page 41. Fig. 35 Removal of the inductor Item. 1: Fan blower box cover plate Item. 2: Screws Item. 3: Screws Item. 4: Sheet metal blower base We reserve the right to make any changes due to technical modifications! 40 Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 Maintenance 12 3.: Inspection of the gas burner 1. Check burner box, air intake hose and burner tubes for contamination, and clean components when necessary, see 5.: “Cleaning of the gas burner“, page 42. 2. Check air intake hose for damage and replace when necessary. 4.: Cleaning the boiler The cleaning of the heat exchanger of the boiler can be achieved with brushes and/or a wet spray cleaning. a) Brush cleaning: 1. Brush out from the top the heating passages. b) Spray cleaning / combined cleaning: 1. Select proper cleaning agent based nature of buildup. (Soot or corrosive build-up). 2. Follow manufacturer's instructions with respect to use of cleaning unit and cleaning agent. It may be that the application of the cleaning agent is different that described here. 3. Heat boiler to a temperature of about 122° F. 4. Shut off main gas piping shutoff valve. Fig. 36 Cleaning with a brush Fig. 37 Spray cleaning of the boiler 5. Disconnect electric power to the appliance. 6. Remove gas burner tray and inducer blower (Refer to 2. "Inspection of the boiler"), see page 37. 7. Cover controls with aluminum foil; avoid spraying on gas and electrical controls. 8. Put dry absorbing rags on top of board insulation in the bottom of boiler. 9. Spray the heating passages evenly from the top with the cleaning agent. * Cleaning accessories= please order separate. We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 41 12 Maintenance Spray only in the heating passages! 10. Let the cleaning agent soak for about 15 minutes. 11. Remove dry absorbing rags from the bottom of the chamber. 12. Remove aluminum foil from controls. 13. Install inducer and gas burner tray (Refer to next section: "Reassembly of removed components"). 14. Bring boiler to maximum temperature. (Set Logamatic control, if present, to manual setting). Remove gas burner tray after the boiler has dried out. 15. A thorough brushing of the heating surfaces is recommended. This requires a disassembly and reassembly as previously discussed. 16. Clean burner chamber and insulation board in the bottom of the chamber. 17. Vent the boiler room thoroughly. 5.: Cleaning of the gas burner 1. Remove burner tray cover plate screws from the burner tray box. 1 2. Remove ignition cable (Fig. 38, Item. 4) from pilot burner assembly (Fig. 38, Item. 1). 3. Loosen the pilot gas line (Fig. 38, Item. 3) on the pilot burner (Fig. 38, Item. 1). 4. Remove pilot gas orifice (Fig. 38, Item. 2) and blow out to clean. 2 5. Dip burner tubes into water with dishwashing cleaning agent and brush off. Ensure that insulation does not get wet. 6. Rinse the burner rods with a stream of water: when doing so, hold the gas burner in such a way that the water penetrates into all burner perforations and runs out again through the Venturi tubes. 3 4 7. Remove the rest of the water by shaking the burner tubes. Fig. 38 8. When necessary, clean burner box housing and air intake hose. Item. 2: Pilot gas orifice 9. Check the burner perforations for free passages; remove any water from the perforations. If any perforations are damaged, the burner tray must be replaced. Item. 4: Ignition cable We reserve the right to make any changes due to technical modifications! 42 Pilot burner assembly Item. 1: Pilot burner assembly Item. 3: Pilot gas line Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 Maintenance 12 Reassembly of removed components 1. Reassemble and install the pilot burner assembly and gas burner in reverse order from its removal. Make sure that sheet metal burner box cover is assembled properly in the gasketed seal. 10 2. Reassemble and install the gas burner in reverse order from its removal. Tighten the four (4) burner tray nuts evenly (see page 38 to page 39.) 9 1 3. Secure union between gas valve (Fig. 39, Item. 7) and gas supply pipe (Fig. 39, Item. 5) and make sure to install the gasket, discussed in step 8 on page 39. 8 4. Replace gaskets and seals when necessary. 2 3 4 5 6 7 5. Reconnect wires to the flame roll-out switch (Fig. 39, Item. 2). 6. Remove rope or wire that secured the gas piping (Fig. 39, Item. 5) as discussed in step 7 on page 39. 7. Reconnect the ignition cable (Fig. 39, Item. 1) to ignition control box (Fig. 39, Item. 12). 8. Install the inducer by reversing removal process, see, page 40. 9. Take to boiler in operation according section 11 "Placing the Boiler in Operation", page 26 to page 34. 10. Take flue measurements according to the procedure on section 11.5.1 "Taking flue gas measurements", page 34. Fig. 39 Front view Item. 1: Ignition cable Item. 2: Flame roll-out switch cable Item. 3: Flame roll-out switch Item. 4: Gas valve cable Item. 5: Gas supply pipe Item. 6: Union Item. 7: Gas valve Item. 8: Air intake hose Item. 9: Gas control module Item. 10: Aquastat We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 43 12 Maintenance 11. Verify proper operation of the aquastat (Fig. 39, Item. 10). 12. Test low water cut-off operation, if present. 13. Check boiler surroundings for irregularities. Its surroundings must be free of flammable materials, gasoline or other flammable or corrosive gases and liquids. 14. Confirm the maintenance record by filling out all listed items. Sign the maintenance record and hand it to the owner/operator of the boiler. We reserve the right to make any changes due to technical modifications! 44 Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 Maintenance 12 12.3 Trouble Shooting Guide Required tools: electrical diagram on page 69 and a multimeter with 120 VAC and 24 VAC scales. Start • Checking of aquastat and transformer. Turn gas supply off. Supply power to the boiler LED light up on boiler (aquastat). NO * Check for line voltage (120 V) at N and L at plug X1. If no voltage present, check incoming line voltage. • * Check if 120 V at L1/L2 and L1X/L2X on aquastat. If no 120 V present, check wiring. If wiring is fine, replace aquastat. • * Check for 24 V between terminals C and R on aquastat If no voltage present, check wiring. If wiring is fine, replace transformer. • Checking thermostat and its wiring. Turn thermostat to call for heat. (10 F above room temperature). * Put jumper between R and W terminals of aquastat If boiler starts, check thermostat and thermostat wiring. • Performing self diagnostics on aquastat. * Check LED light on aquastat. Light blinks 2x: check aquastat sensor contacts S1 and S2 and sensor wiring. If it all looks fine, replace aquastat sensor. Light blinks 3x or 4x: internal aquastat failure, replace aquastat LED light off: aquastat is RESET mode, wait 5 minutes for automatic reset Turn thermostat on aquastat to call for heat (min. 10 °F above boiler temperature). Does fan motor starts? NO • Check for 24 V between terminals B1 and B2 of aquastat. If no 24 V, replace aquastat. • Checking the fan relay and the fan motor. * Check for 24 V between terminals 1 and 4 of “terminal of boiler block“ strip (“terminal strip“). If no 24 V, check wiring between aquastat terminals B1/B2 and terminal strip. If 24 V between terminal 1 and 4, check for 120 V between terminals L3 and N of plug X3. If no 120 V, check wiring between terminal strip and relay and between relay and terminal plug X1 (incoming power). If wiring is fine, replace relay. If 120 V is present between terminals L3 and N of plug X3, check wiring of the fan blower. If wiring is fine: replace fan blower We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 45 12 Maintenance Spark across ignitor/sensor gap (look through sight glass) NO Checking the S 8600 ignition module. • Check for 24 V between terminals 3 and 4 of the terminal strip. (Power supply to S8600 ignition module) If present: • Check wiring between terminal strip and S8600 module. • Check position of ignition cable plug on ignition sensor ceramic insulator. • Check ignition cable, ground wiring, ignition sensor ceramic insulator and gap. Set gap to 3 - 4 mm. (1/8" to 1/6"). • Check boot of the ignition cable for signs of melting or buckling. • If everything checks okay, replace S8600 ignition module. Checking the flame roll-out switch. • Check for 24 V between terminals 2 and 3 of terminal strip. If no 24 V present, check wiring between terminal strip and flame roll-out switch. Check for continuity of flame roll-out switch. If open circuit, replace flame roll-out switch. Checking the pressure switch. • Check for 24 V between terminals 1and 2 of terminal strip. If no 24 V present, do following: • Check wiring between pressure switch and terminal strip on boiler block. • Check exhaust and air intake piping for blockage. • Check air intake hose of boiler for blockage and ensure full diameter. • Check for blocked heat exchanger of the boiler. • Check total length of exhaust and air intake piping versus listed tables Table 7 to Table 9 on page 24 and page 25. If everything checks okay: replace pressure switch. Turn gas supply on. Pilot burners lights. NO Checking gas valve and S 8600 module. • Check that all manual gas valves are open, supply tubing and pressures are good and pilot burner orifice is not blocked. • Before first start-up, purge the air from gas supply pipe. • Check electrical connections between module and pilot operator on gas control. • Check for 24 V across MV-MV/PV terminals on module. If voltage is fine, replace gas control. If not, replace module. We reserve the right to make any changes due to technical modifications! 46 Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 Maintenance Sparks stops when pilot is lit. 12 NO Checking S 8600 module • Check continuity of L and N wiring on 120 V terminal. • Check continuity ignition cable and ground wire. • Check position of ignition cable plug on ignition sensor ceramic insulator. • • • • Check flame rod. Check electrical connections between flame rod and module. Check for cracked ceramic flame rod insulator. Check that pilot flame covers flame rod and is steady and blue. Adjust pilot flame. • If problem persists, replace module. Main burner lights. NO Checking gas valve and S 8600 module. • Check for 24 V across MV-MV/PV terminals, closed ciruit on module. If no voltage, replace module. • Check electrical connections between module and gas control. If okay, replace gas control. Systems run until call for heat ends. NO Checking S8600H module. • Check continuity ignition cable and ground wire. Note: If ground is poor or erratic, shutdowns may occur occasionally even though operation is normal at the time of checkout. • Check that pilot flame covers flame rod and is steady and blue. • If checks are okay, replace module. Call for heat ends, system shuts off. Troubleshooting ends NO Checking gas valve and S 8600 module. • Check for proper thermostat (controller) operation. • Remove MV lead at module. • If valve closes, recheck temperature controller and wiring, replace module • If valve does not close, replace gas control. Repeat procedure until troublefree operation is obtained. We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 47 12 Maintenance Thermostat (Controller) calls for heat START Stage 1 Trial for ignition Fan motor starts operating. Spark generator powered • Pilot valve opens. Pilot burner operation Pilot burner light,S 8600 H senses flame current. or Pilot burner does not light. S 8600 H trial for ignition continues for 90 seconds and locks out. If flame current sensed • Spark generator off Stage 2 • Main valve operator opens Power interuptions Main burner operation System shuts off. Restarts when power restored? Main burner operation Pilot flame failure • S 8600 H monitors pilot flame current Main valve closes, S 8600 H starts trial for ignition. Thermostat (controller) satisfied Main and pilot valve close, burners shut off. Fan motor is shut off. END We reserve the right to make any changes due to technical modifications! 48 Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 Parts List 13 13 Parts List The following parts are directly available from Buderus Hydronic Systems, Inc. Please use the listed description and part number when ordering replacement components. Boiler block (Fig. 40) Item. Part description No. 10 20 25 30 35 40 50 55 60 65 70 80 90 95 100 110 120 130 140 150 160 170 180 190 200 210 220 230 240 250 260 265 270 275 280 290 300 310 320 321 322 323 330 340 350 Non combustible base Bottom support rail 386x54x65 left side Bottom support rail 386x54x65 right side Combustion chamber side plate 303x135 left Combustion chamber side plate 303x135 right Hex.-screw ISO4017 M8x100 8.8 Spring DIN128 A8 A3k Washer DIN125 A8 A3k Hex.-nut ISO4032 M8 8 A3k Gasket D6x20x2 SIL24 Boiler feet Return pipe R1 1/2xNpt11/2 Supply pipe R11/2xNpt11/2x3/4 Elbow 90° Nr92 NPT3/4 Relief valve Conbraco 30PS1 Snap nut 4,8 SNU2012 Rear insulation board Sheet metal screw DIN7981 C ST4,8x22 Screw ST3,9x9,5 A3T Temperature and pressure gauge Cast iron boiler block Chrome well (Npt) Adapter 1-3/4" Connection piece DIN2950 526 3/4"x80 Elbow Air intake hose DN 100x690 Air intake hose clamp set 90-110x9 Flue gas blower box Base plate for flue gas blower Flue gas blower box cover plate Hose set DN4x2x880 Silicone Flange plate D87x140x2 Collar D79,5/D77/D75x160 Flange plate D140/D77 Flue gas fan motor 120V/60 Gasket D140xD72x5 Cover plate test-port fan blower Pressure switch for flue gas blower Pressure switch DL3ET-Z Threaded bolt DIN 939 M8x30 5.6 Washer DIN 125 A8.4 A3k Hex. nut ISO 4032 M8 Tube with sealant material for block assembly PK-W11 310 ml Silicone HT Mounting Material for boiler block 6302563026979 63026980 63026977 63026978 Mounting Material Mounting Material Mounting Material Mounting Material Mounting Material Mounting Material 5584754 5584752 99908401 5900076 Mounting Material 63026Mounting Material Mounting Material 5900076 630265446190 3869828 320840 6302663026981 63026991 63026302630263016451 63028921 630263028858 63026836 63026837 63026838 63011683 6302Mounting Material Mounting Material Mounting Material Model 37 Quantity 312 1 1 1 1 4 4 4 4 4 4 1 1 1 1 2 974 2 1 1 967 1 1 1 973 1 1 6831 6833 6834 1 1 6835 6836 1 1 1 6839 6 4 4 Model 44 Quantity 312 1 1 1 1 4 4 4 4 4 4 1 1 1 1 2 974 2 1 1 967 1 1 1 973 1 1 6832 6833 6834 1 1 6835 6836 1 1 1 6840 6 4 4 Model 53 Quantity 313 1 1 1 1 4 4 4 4 4 4 1 1 1 1 2 975 2 1 1 968 1 1 1 972 1 1 9098 9097 9096 1 1 9099 8856 1 1 1 9100 6 4 4 Model 62 Quantity 314 1 1 1 1 4 4 4 4 4 4 1 1 1 1 2 976 2 1 1 969 1 1 1 971 1 1 8849 8853 8855 1 8857 1 8856 1 1 1 8839 6 4 4 2037038 1 1 1 1 63000116 63026970 1 1 1 1 1 1 1 1 Buderus Part number Table 14 Boiler block We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 49 13 Parts List 250 280 300 310 240 320 265 270 260 275 290 140 140 230 220 210 150 80 160 100 140 90 140 220 95 130 30 322 323 120 323 170 180 190 321 110 321 322 323 140 35 40 20 70 25 321 330 140 322 323 321 340 200 322 323 10 65 55 50 60 1021933-02-Kesselblock GA244 "US/CA" Fig. 40 Boiler block We reserve the right to make any changes due to technical modifications! 50 Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 Parts List 13 Boiler Jacket Panels (Fig. 41) Item. Part description No. Buderus Part number Model 37 Quantity Model 44 Quantity Model 53 Quantity Model 62 Quantity 10 Name plate 63025232 1 1 1 1 20 Edge protection set 63020896 1 1 1 1 30 Middle panel 63025- 238 238 239 240 40 Boiler block insulation 63025- 233 233 234 235 50 Rear panel 63025- 229 229 230 231 60 Top rear cover panel 63025- 226 226 227 228 225 70 Top front cover panel 63025- 223 223 224 80 Front panel (delivered until February 2004) 63025- 220 220 221 222 80 Front panel (delivered from March 2004) 63028- 708 708 709 710 90 Side panel left (delivered until February 2004) 63025219 1 1 1 1 90 Side panel left (delivered from March 2004 ) 63028706 1 1 1 1 100 Side panel right (delivered until February 2004) 63025218 1 1 1 1 100 Side panel right (delivered from March 2004) 63028705 1 1 1 1 110 Right side panel cover plate (delivered until February 2004) 63026310 1 1 1 1 110 Right side panel cover plate (delivered from March 2004) 63028711 1 1 1 1 120 Sheet metal screw C St3.9x50 Mounting Material 20 20 20 20 130 Snap nut Mounting Material 2 2 2 2 140 Clip spring 476378 5 5 5 5 63025389 1 1 1 1 - Mounting material for boiler jacket Table 15 Boiler jacket We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 51 13 Parts List 60 120 65 70 120 120 120 50 140 120 40 120 90 120 120 30 20 Bu de rus GA 24 120 4 10 130 80 100 120 110 120 120 120 120 1021934-02-Verkleidung GA244 "US/CA" Fig. 41 Boiler jacket panels We reserve the right to make any changes due to technical modifications! 52 Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 Parts List 13 Measuring Line - Set (Fig. 42) Item. Part description No. 10 Measuring line set CE244 Buderus Part number Model 37 Quantity Model 44 Quantity Model 53 Quantity Model 62 Quantity 6302- 5822 5822 5822 5822 The measuring line set contains the following components: 20 Pressure measuring orifice G1/8" (DIN288-1) 0548- 1194 1194 1194 1194 30 Gasket ringDIN7603 A 10x13,5x1,5 Cu 6301- 5874 5874 5874 5874 40 Hex.-nut G1/8" 2 2 2 2 50 Pressure measuring orifice G1/8" 1 1 1 1 60 Silicone hose 3x1,5x120mm 1 1 1 1 70 Pressure measuring orifice 394537 1 1 1 1 Table 16 Measuring line set We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 53 13 Parts List 10 40 30 20 30 50 60 Fig. 42 Measuring line set We reserve the right to make any changes due to technical modifications! 54 70 Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 Parts List 13 Control panel GAW028 (Fig. 43) Item. Part description No. Buderus Part number Model 37 Quantity Model 44 Quantity Model 53 Quantity Model 62 Quantity - 63026298 63026298 63026299 63026300 63015750 1 1 1 1 10 Control panel GAW 028 00 compl. "US" 20 Relay 24V AC 1xS 120V AC/15A 30 Sheet metal screw DIN7981 F ST3,5x6,5 A3 see mounting-material for GAW027/GAW028 „US“ 40 Terminal strip 4 qmm 4-pin see mounting-material for GAW027/GAW028 „US“ 50 Sheet meatl screw DIN7981 F ST3,5x16 A3K see mounting-material for GAW027/GAW028 „US“ 60 Middle panel GA244 "US" 70 Ignition module S 8600H1006 80 Screw ST3,9x9,5 A3K 90 Cover plate for ignition module GAW028 "US" see boiler jacket 1 1 1 1 63015743 1 1 1 1 see mounting-material for GAW027/GAW028 „US“ 63026301 1 1 1 1 100 Tooth lock washer DIN6797 A4,3 A3K see mounting-material for GAW027/GAW028 „US“ 110 Hose AWG 2x18 063/076 63015745 1 1 1 1 120 Cabling tree GAW 022/024/026/027 63015746 1 1 1 1 130 Temperature sensor 32004955-003B 63015749 1 1 1 1 140 Blank piece für 1/4 ciruit sensor 07060110 2 2 2 2 150 Distance spring 05446800 1 1 1 1 160 Sensor bracket 07060986 1 1 1 1 170 Transformer 120V/24V "US" compl. 63015748 1 1 1 1 180 Aquastat Relay L7148F 63015742 1 1 1 1 190 Sheet metal screw DIN7981 C ST3,5x25 A3K 200 Interconnecting cable 210 Sheet metal screw DIN7981 C ST2,9x16 A3K 220 3-pin plug black 93.923.4354 05493464 1 1 1 1 230 3-pin female connector black 93.031.3253.0 07060911 1 1 1 1 240 3-pin plug green/black 05493465 1 1 1 1 250 3-pin female connector green 07060912 1 1 1 1 260 Sheet metal screw DIN7981 C ST2,9x25 A3K 270 5-pin female connector black 280 Sheet metal screw DIN7981 F ST3,5x9,5A3K see mounting-material for GAW027/GAW028 „US“ 63015744 1 1 1 1 see mounting-material for GAW027/GAW028 „US“ see mounting-material for GAW027/GAW028 „US“ 07060913 We reserve the right to make any changes due to technical modifications! 1 1 1 1 see mounting-material for GAW027/GAW028 „US“ Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 55 13 Parts List Control panel GAW028 (Fig. 43) Item. Part description No. Mounting-material for GAW027/GAW028 „US“ Buderus Part number Model 37 Quantity Model 44 Quantity Model 53 Quantity Model 62 Quantity 63015810 The mounting material contains the following components: 30 Sheet metal screw DIN7981 F ST3,5x6,5 A3 10 10 10 10 40 Terminal strip 4 qmm 4-pin 1 1 1 1 50 Sheet metal screw DIN7981 F ST3,5x16 A3K 5 5 5 5 80 Screwe ST3,9x9,5 A3E 5 5 5 5 100 Tooth lock washer DIN6797 A4,3 A3K 5 5 5 5 190 Sheet metal screw DIN7981 C ST3,5x25 A3K 5 5 5 5 210 Sheet metal screw DIN7981 C ST2,9x16 A3K 5 5 5 5 260 Sheet metal screw DIN7981 C ST2,9x25 A3K 4 4 4 4 280 Sheet metal screw DIN7981 F ST3,5x9,5A3K 2 2 2 2 Tab. 17 Control panel GAW028 We reserve the right to make any changes due to technical modifications! 56 Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 Parts List 13 10 20 30 30 40 50 50 270 240 60 260 250 230 210 200 210 220 280 170 100 30 100 80 30 80 180 70 80 190 80 190 190 160 140 190 150 100 130 30 90 30 110 100 100 30 120 100 30 Fig. 43 Control panel GAW028 We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 57 13 Parts List Burner Tray Assembly (Fig. 44) Item. Part description No. Buderus Part number Model 37 Quantity Model 44 Quantity Model 53 Quantity Model 62 Quantity 6302- 5795 5795 5796 5797 10 Burner tray assembly CE244 compl. 20 Gasket for burner tray assembly 30 Secondary air guide plate 40 Lens screw DIN7985-M4x20-5.8-A3K 0588- 3286 3286 3286 3286 50 Flame roll-out switch 377Grad f 0047- 1336 1336 1336 1336 60 Screw DIN7500 CE M5x12 CombiTorx 15 pieces/set 6302- 8938 8938 8938 8938 70 Burner tray cover plate CE244 5Gld compl. "US" 6302- 5808 5808 5809 5810 80 Bottom - gasket for burner tray cover plate Gasket set 90 Top - gasket for burner tray cover plate Gasket set 100 Observation port compl. 0710- 0256 0256 0256 0256 110 Screw St3,9x9,5 A3T 0594- 7754 7754 7754 7754 120 Gasket - Set for burner tray assembly CE244 5 section compl. 6302- 5925 5925 5926 5927 130 Clue Elastosil E 41 in 90ml tube 6301- 1270 1270 1270 1270 Gasket set Table 18 Burner tray assembly We reserve the right to make any changes due to technical modifications! 58 Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 Parts List 13 10 100 50 40 90 90 20 30 60 100 80 110 70 120 90 20 80 90 130 1021797-01-Gehäuse für Brenner CE244 "US" Fig. 44 Burner tray assembly We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 59 13 Parts List Gas Valve VR8304 (Fig. 45) Item. Part description No. Buderus Part number Model 37 Quantity Model 44 Quantity Model 53 Quantity Model 62 Quantity 10 Gas supply pipe CE244 compl. "US" with sleeve nut and gasket 6302- 5807 5807 5807 5807 20 Sleeve nut G 1 1/4 0518- 1564 1564 1564 1564 30 Gasket D27x38x2mm C4400 Klinger SIL, green 0548- 9356 9356 9356 9356 40 Socket with Flange 25,4x25,4 compl. with O-ring gasket and Screws 6302- 5821 5821 5821 5821 50 Screw 8x32x1/2 60 O-ring gasket 24, 2x3 PERBUNAN 6302- 5931 5931 5931 5931 70 VR8304 gas valve, complete w/ O-Ring, pressure tap and screws 6302- 5794 5794 5794 5794 80 Pressure measuring orifice 394537 90 Screw - Set gas valve VR8304 compl. 5928 5928 5928 5928 100 Screw 8x32x11/4 A3T s. Screw Set Gas valve VR8304 s. pressure measuring set CE244 6302s. Screw Set Gas valve VR8304 Table 19 Gas valve VR8304 We reserve the right to make any changes due to technical modifications! 60 Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 Parts List 13 10 20 30 20 30 50 60 40 50 60 70 50 60 80 100 80 100 50 90 Fig. 45 Gas valve VR8304 We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 61 13 Parts List Pilot burner, Pilot gas line (Fig. 46) Item. Part description No. Buderus Part number Model 37 Quantity Model 44 Quantity Model 53 Quantity Model 62 Quantity 10 Pilot burner Q381 A compl. with pilot orifice, union and screws 6302- 5819 5819 5819 5819 20 Screws DIN7500 CE M5x12 CombiTorx 15 pieces/set 6301- 0217 0217 0217 0217 40 Pilot gas orifice for natural gas 390686-37 6302- 4518 4518 4518 4518 40 Pilot gas orifice for propane gas 390686-61 6302- 6339 6339 6339 6339 50 Pilot burner union D4 0518- 1672 1672 1672 1672 60 Pilot gas line CE244 5/7Gld. compl. "US" with union and grommet 6302- 5817 5817 5818 5818 70 Grommet D68/D60/D48/D22 80 Ignition cable KD7 SD6,3 S6,3x0,8 HF compl. with grommet 5820 5820 5820 5820 90 Grommet DV 4/9 s. grommet Set CE244 100 Cable fastener 2,5x92 s. grommet Set CE244 110 Grommet Set CE244 compl. "US" 5823 5823 5823 5823 s. grommet Set CE244 6302- 6302- Table 20 Pilot burner, pilot gas line We reserve the right to make any changes due to technical modifications! 62 Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 Parts List 13 90 100 80 20 20 40 50 10 40 50 70 60 110 50 70 90 100 Fig. 46 Pilot burner, pilot gas line We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 63 13 Parts List Burner tray assembly (Fig. 47) Item. Part description No. Buderus Part number Model 37 Quantity Model 44 Quantity Model 53 Quantity Model 62 Quantity 10 Burner bar assembly CE 244 compl. "US with main orifices for Natural gas (G20) 0-2000FT 6302- 5802 5803 5804 5804 20 Insulation CE244 5 section compl. "US" 6302- 5811 5811 5812 5813 30 Ceramic clue Thermofix Tube 115gr. 0203- 7312 7312 7312 7312 40 Manifold CE244 5 section compl. "US" 6302- 5814 5814 5815 5816 50 Screw 8x32x1/2 s. Screw Set VR8304 60 Screw 8x32x11/4 A3T s. Screw Set VR8304 70 Grommet D68/D60/D48/D22 80 Screw DIN7500 CE M5x12 CombiTorx 15 pieces/set 6301- 0217 0217 0217 0217 90 Gasket 13x18x1,5mm 0588- 3094 3094 3094 3094 100 Main orifice 3,00 mm SW16 16mm long 4 pieces 0548- 100 Main orifice 3,25 mm SW16 16mm long 4 pieces 0548- 7620 7620 7620 7620 110 Sight glas Tempax 30x30x3,3mm 0544- 5802 5803 5804 5804 s. Grommet Set CE244"US" Table 21 Burner tray assembly We reserve the right to make any changes due to technical modifications! 64 Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 Parts List 13 10 20 30 110 100 90 80 80 40 70 60 50 Main gas orifices Fig. 47 Model/ section Orifice/ gasket Sea-level in FT 37/5 37/5 37/5 37/5 44/5 44/5 44/5 44/5 53/6 53/6 53/6 53/6 62/7 62/7 62/7 62/7 4/4 4/4 4/4 4/4 4/4 4/4 4/4 4/4 5/5 5/5 5/5 5/5 6/6 6/6 6/6 6/6 0-2000 2001-4500 4501-6000 6001-8000 0-2000 2001-4500 4501-6000 6001-8000 0-2000 2001-4500 4501-6000 6001-8000 0-2000 2001-4500 4501-6000 6001-8000 Type of gas in mm Natural gas (G20) Propane (G31) 3,00 2,85 2,75 2,60 3,25 3,05 2,95 2,80 3,20 3,05 2,95 2,80 3,15 3,00 2,90 2,75 1,95 1,85 1,80 1,70 2,15 2,05 1,95 1,85 2,10 2,00 1,90 1,85 2,20 2,10 2,00 1,90 1021794-01-Burner bar assembly CE244 "US" Burner tray assembly We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 65 13 Parts List NOTICE! The boiler is factory set for operation with natural gas at elevations up to 2000 ft. The boiler must be derated for installations above 2000 ft. The derate is accomplished by changing the main burner orifices. Contact Buderus in this case to obtain the suitable high elevation conversion kit. Types of Burners, Conversion Kits (Fig. 48) Buderus Part number Model 37 Quantity Model 44 Quantity Model 53 Quantity Model 62 Quantity 6302- 5798 5799 5800 5801 Gas conversion kit for propane CE244 G31 0-2000FT "US" 630- 26333 26334 30003 26336 Gas conversion kit for propane CE244 G31 2001-4500FT "US" 630- 27390 27393 30004 28910 Gas conversion kit for propane CE244 G31 4501-6000FT "US" 630- 27391 27394 30005 28911 Gas conversion kit for propane CE244 G31 6001-8000FT "US" 630- 27392 27395 30006 28912 Gas conversion kit for natural gas CE244 G20 0-2000FT "US" 630- 25921 27396 29999 28913 Gas conversion kit for natural gas CE244 G20 2001-4500FT "US" 630- 25922 27397 30000 28914 Gas conversion kit for natural gas CE244 G20 4501-6000FT "US" 630- 25923 27398 30001 28915 Gas conversion kit for natural gas CE244 G20 6001-8000FT "US" 630- 25924 27399 30002 28916 Item. Part description No. 10 Gas burner CE244 Gr.37/5 G20 compl. "US" Table 22 Types of burners, Gas conversion kits We reserve the right to make any changes due to technical modifications! 66 Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 Parts List 13 10 Leistung 37 kW Ser.-Nr. 63023412-00-3253-000001 00000001 The rating label is placed on the left side of the burner box. Fig. 48 Burner tray assembly, Gas conversion kits We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 67 14 Orifice Tables for High Elevations and Propane 14 Orifice Tables for High Elevations and Propane Orifice Table for Natural Gas and High Elevations Boiler model Orifice Size (mm) for different Elevations [feet] No. of Orifices Manifold Pressure [in. W.C.] 0–2000 ft 2001–4500 ft 4501–6000 ft 6001–8000 ft 37 4 3.00 2.85 2.75 2.60 3.77 44 4 3.25 3.05 2.95 2.80 3.65 53 5 3.20 3.05 2.95 2.80 3.73 62 6 3.15 3.00 2.90 2.75 3.77 Table 23 Main orifice sizes and high elevations for natural gas Orifice Table for Propane Gas and High Elevations Boiler model Orifice Size (mm) for different Elevations [feet] No. of Orifices Manifold Pressure [in. W.C.] 0–2000 ft 2001–4500 ft 4501–6000 ft 6001–8000 ft 37 4 1.95 1.85 1.80 1.70 8.03 44 4 2.15 2.05 1.95 1.85 7.63 53 5 2.10 2.00 1.90 1.85 8.11 62 6 2.20 2.10 2.00 1.90 6.15 Table 24 Main orifice sizes and high elevations for propane gas Spare part numbers for orifices Part description Buderus Part number Remark Part description Buderus Part number Main orifice 1,70 mm 63029151 Main orifice 2,75 mm 63029149 Main orifice 1,80 mm 63029387 Main orifice 2,80 mm 63029403 Main orifice 1,85 mm 63029152 Main orifice 2,85 mm 63029150 Main orifice 1,90 mm 63030022 Main orifice 2,90mm 63030025 Main orifice 1,95 mm 63029146 Main orifice 2,95mm 63029404 Main orifice 3,00mm 63029145 Vtolerance 2% SW16 Length 16 mm Main orifice 2,00 mm 63030023 Main orifice 2,05mm 63029401 Main orifice 3,05mm 63029405 Main orifice 2,10 mm 63030024 Main orifice 3,15 mm 63029406 Main orifice 2,15 mm 63029402 Main orifice 3,20 mm 63029188 Main orifice 2,20 mm 63030241 Main orifice 3,25 mm 63029147 Main orifice 2,60 mm 63029148 We reserve the right to make any changes due to technical modifications! 68 Remark Vtolerance 2% SW16 Length 16 mm Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 Wiring diagrams 15 15 Wiring diagrams Fig. 49 Wiring diagram– GA244 model We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 69 15 Fig. 50 Wiring diagrams Wiring diagram– GA244 model We reserve the right to make any changes due to technical modifications! 70 Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 Wiring diagrams Fig. 51 15 Wiring diagram – GA244 with control panel Logamatic 2107 or Logamatic 2109 We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 71 Heating Contractor: PRODUCTS MANUFACTURED BY BBT Thermotechnik GmbH 35573 Wetzlar www.buderus.de BBT North America Corporation 50 Wentworth Avenue Londonderry, NH 03053 Tel: 603-552-1100 ● Fax: 603-584-1681 www.buderus.net BBT North America Corporation reserves the right to make changes without notice due to continuing engineering and technological advances.