4637 UDC Metering Project Hardware Submittal

SubmittalsHARDWARE
DIRECT DIGITAL
CONTROL
SYSTEM
SECTION
15900
SUBMITTAL
FOR
METERING
PROJECT
UDC Metering
4637
University of the District of Columbia
4200 Connecticut Avenue
Washington
DC
20011-
SUBMITTAL DATE:
DATE OF PLANS & SPECIFICATION:
4/6/2015
MECHANICAL ENGINEER:
Grother, P.C.
1612 K Street NW
Suite LL-3
DC
20006-
8/12/2015
Washington
MECHANICAL CONTRACTOR:
OWNER
ARCHITECT
University of the District of
Columbia
4200 Connecticut Ave. NW
Consys, Inc
732 Kennedy Street, NW
Washington
DC
20006( ) -
7964-B Conell Court, Lorton, VA,
22122,
Print Date / Time:
3/25/2015 12:22:19 PM
GENERAL CONTRACTOR
Washington
DC
20011(202) 545-1333
(202) 545-1339
Phone: (703) 550-0090 - Fax: (703)
550 0217
P.O. Box 1493, Newington, VA 221221493
Database Source: BASDWIZ\SQLEXPRESS
Hardware Submittal for Metering Project
University of the District of Columbia
Project 4637
TABLE OF CONTENTS
 Cover
 Table of Contents
 Hardware Schedule
 Materials Data Sheets
o Power Meters
 Shark SHK200-60 Power Meters
 Nexus 1271-S-9S Power Meters
o Transformers
 I25-2XX
 7RL-801
 8RL-162
 CTWH3-A-60-T90-101
 19RL-XXX
 PTG3-1-60-242S
o Onicon F-1100 Water Flow Meter
o Onicon F-2600 Inline Steam Flow Meter
o Onicon F-5200 Thermal Mass Natural Gas Meter
o Onicon D-100 Digital Flow Display
o Onicon System 10 BTU Meter
o Dell Inspiron Workstation
o Brother Laserjet Printer
o AB-16166LMMOD Enclosure
o AB-24206LMMOD Enclosure
o Protocom KT BacNet Router Gateway
o EREXT4.0 Energy Reporting Software
Energy Metering Upgrade
University of the District of Columbia
UG706/CP11
Material Sumittal
Mechanical
Drawing
Note #
Chilled Water BTU Meter
1
Vortex Shedding Steam Meter
#/Hr.
Domestic Water
2
Thermal Mass Natural Gas
Thermal Mass Natural Gas
Thermal Mass Natural Gas
4
3
Enclosure
Low Voltage Single Power & Energy Meter
Low Voltage Single Power & Energy Meter
Low Voltage Single Power & Energy Meter
Low Voltage Single Power & Energy Meter
Low Voltage Single Power & Energy Meter
Power & Energy Meter
Power & Energy Meter
Power & Energy Meter
Power & Energy Meter
Power & Energy Meter
Power & Energy Meter
Electrical
Drawing
Note #
2/E11
2/E11
2/E11
2/E11
2/E11
2/E11
2/E11
1/E11
1/E11
1/E11
1/E11
BACnet Router
Bldg. 32/42 Bldg. 38/39 Bldg. 41
Onicon System 10 BACnet
w/F-1100 Insertion & Temp Sensors
Onicon F-2600 Inline w/Optional BACnet MS/TP
Onicon F-1100 Insertion
w/Upgrade to Ss for Domestic Water
Installation kit
Onicon F-5200 Insertion
Onicon F-5200 Insertion
Onicon F-5200 Insertion
D-100-IP BACnet IP Display
Austin
SHK200-60-10-V2-D2-INP100S-X
SHK200-60-10-V2-D2-INP100S-X
SHK200-60-10-V2-D2-INP100S-X
SHK200-60-10-V2-D2-INP100S-X
SHK200-60-10-V2-D2-INP100S-X
SHK200-60-10-V2-D2-INP100S-X
SHK200-60-10-V2-D2-INP100S-X
NEXUS1272-S-9S-20-60-S-INP200
NEXUS1272-S-9S-20-60-S-INP200
NEXUS1272-S-9S-20-60-S-INP200
NEXUS1272-S-9S-20-60-S-INP200
Protocom KT
8"
4"
2000
4"
8"
4"
8440
4"
8"
2"
4000
4"
Bldg. 43
845
4"
Bldg. 44 Bldg. 46E Bldg. 46W Bldg. 47 Bldg. 52
??
4"
7160
4"
1
20" x 24"
6"
2"
4"
3"
1
1
4
2
20" x 24" 20" x 24" 3 @ 20" x 24" 20" x 24"
SHK200
Parrallel
SHK200
Parrallel
SHK200
Parrallel
X
X
X
SHK200
SHK200
SHK200
Parrallel
SHK200
SHK200
SHK200
SHK200
SHK200
Nexus 1272
Nexus 1272
Nexus 1272
Nexus 1272
X
X
4"
2 1/2"
2113
4"
4"
2"
600
4"
5"
6"
9563
6"
4"
3"
1
1
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
3"
3"
3"
2
4
16" x 16" 20" x 24"
SHK200 SHK200
SHK200
X
X
Current Transformers
2.4K
2.4K
277/480V
277/480V
277/480V
277/480V
277/480V
277/480V
277/480V
277/480V
100:5
200:5
800:5
1200:5
1600:5
2000:5
2500:5
3000:5
2000:5
3000:5
CTWH3-A-60-T90-101
CTWH3-A-60-T90-201
7RL-801
8RL-11
8RL-162
125-202
125-252
125-302
19RL-302
19RL-202
1200:5
100:5
200:5
Existing
PTG3-1-60-242S
PTG3-1-60-242S
X*
X*
X*
X*
X*
X
X*
X
X
X
Potential Transformers
7.94k
2.4K
2.4K
Billing Allocation Software
EREXT4.0
X
X*
X*
X
®
UPGRADABLE FULLY FEATURED POWER & ENERGY METER
www.electroind.com
Revenue Grade with Advanced I/O and Power Quality
Shark® 200
Meter/Transducer
Shark® 200T
Transducer Only
MV90
COMPATIBLE
From Simple to Sophisticated
Industry Leading Performance
• V-Switch™ Technology Upgrade
• Highly Accurate Metering Technology • Simple Multifunction Meter: V-Switch™ Key 1
• Extensive Data Logging
• Historical Data-logging: V-Switch™ Key 2
• Power Quality Recording up to 512 Samples/Cycle
• Advanced Power Quality Waveform
Recorder: V-Switch™ Keys 5 or 6
• Embedded Web Server - With Smartphone
& Tablet Support
New
Electro Industries/GaugeTech
The Leader in Power Monitoring and Smart Grid Solutions
• Dual Ethernet Ports Compatible with Modbus,
DNP 3.0 over TCP/IP and IEC 61850 Protocols!
HIGH PERFORMANCE WAVEFORM RECORDING
Basic Features Summary
• 0.2% Class Revenue Certifiable Energy and Demand Metering
• Meets ANSI C12.20 and IEC 62053-22 (0.2% Class)
• Multifunction Measurement
• 3 Line .56" LED display and % of Load Bar for Analog Perception
• 0.001 Hz Frequency Measurement for Generating Stations
• Standard RS485 (Modbus and DNP 3.0)
• IrDA Port Enables Laptop PC Reading and Programming
• Ultra-Compact
• Fits both ANSI and DIN Cutouts
APPLICATIONS
Advanced Features Summary
• Utility Metering • Commercial Metering
• High Performance Waveform Recorder
• Substations • Industrial Metering
• Up to 4 Megabytes Flash for Historical Data Logging & PQ Recording
• Power Generation
• Campus Metering
• Extremely Configurable Field Upgradable I/O
• Submetering
• Analog Meter Replacement
• 100BaseT Ethernet ­– Rapid Response™ Technology
• Power Quality Studies
• Disturbance Recording
• V-Switch™ Technology
• Load Studies
• Voltage Recording
• High Precision Frequency Measurement for Frequency Control
ACCURACY AND UPGRADE SWITCHES
Electro Industries introduces a new standard in panel
mounted power metering. The Shark® 200 metering system
is an ultra-compact power metering device providing
industry leading revenue metering functionality combined
with advanced data-logging, power quality, communication
and I/O traditionally found only in high performance and
high cost systems. This product is designed to incorporate
advanced features in a cost effective, small package
for large scale, low cost deployment within an electrical
distribution system.
V-Switch™ TECHNOLOGY
The Shark® 200 meter is equipped with EIG’s exclusive
V-Switch™ technology. This technology allows users to
upgrade and add features to the meter without removing it
from installation.
V-Switches Include the Following Features:
Feature
V1
Multifunction Measurement
with I/O Expansion
P P P P P P
P P P
P
P
P P P P
P P P P P P
P P P
P
P
2 Megabytes Data-Logging
3 Megabytes Data-Logging
4 Megabytes Data-Logging
Harmonic Analysis
TLC and CT/PT Compensation
Limit and Control Functions
64 Samples per Cycle
Waveform Recorder
2
512 Samples per Cycle
Waveform Recorder
V2
V3
V4
V5
V6
ACCURACY
Measured
Parameters
Accuracy %
Display Range
Voltage L-N
0.1%
0-9999 Scalable V or kV
Voltage L-L
0.2%
0-9999 V or kV Scalable
Current
0.1%
0-9999 Amps or kAmps
+/- Watts0.2%
0-9999 Watts, kWatts, MWatts
+/-Wh
5 to 8 Digits Programmable
0.2%
+/-VARs0.2%
0-9999 VARs, kVARs, MVARs
+/-VARh
0.2%
5 to 8 Digits Programmable
VA
0.2%
0-9999 VA, kVA, MVA
VAh
0.2%
5 to 8 Digits Programmable
PF
0.2%
+/- 0.5 to 1.0
Frequency
+/- 0.001 Hz
45 to 65 Hz
%THD
+/- 2.0%
1 to 99.99%
% Load Bar
+/- 1 Segment (0.005 to 6) A
Note: Applies to 3 element WYE and 2 element Delta connections. See full
accuracy specifications in Shark® 200 Meter User Manual. Neutral current
2% accuracy.
Advanced Revenue Energy Metering Capabilities
• Line Frequency Time Sync
• Traceable Watt-hour Test Pulse
• Utility Block and Rolling Average Demand
• Historical Load Profiling
• Internal Energy Logging
• Transformer and Line Loss Compensation
• CT/PT Compensation
SHARK®200
METER
EXTENSIVE DATA-LOGGING CAPABILITY (V2 and Higher)
The Shark® 200 meter offers the capability of having 2
Megabytes of data-logging to be used for historical trends, limit
alarms, I/O changes and sequence of events. The unit has a
real-time clock that allows for time stamping of all the data in the
instrument when log events are created.
I/O Change Log
• Provides a Time Stamped Log of any Relay Output
• Provides a Time Stamped Log of Input Status Changes
• 2048 Events Available
Limit/Alarm Log
Historical Logs
• Provides Magnitude and Duration
of an Event
• 3 Assignable Historical Logs
• Independently Programmed
Trending Profiles
• Includes Time Stamps and Alarm Value
• 2048 Events Available
• Up to 64 Parameters per Log
System Events Log
Historical Trending
To protect critical billing information,
the meter records and logs the following with a time stamp:
• Demand Resets
• Password Requests
• System Startup
• Energy Resets
• Log Resets
• Log Reads
Alarm Log
Limits Alarms and Control
Capability (V4 Option)
Limit Events
• Any measured parameter
• Up to 16 Limits
• Voltage Imbalance
• Current Imbalance
• Programmable Settings Changes
Limit Set Up
• Based on % of full scale settings
HIGH PERFORMANCE POWER QUALITY ANALYSIS (V5 AND V6)
Simultaneous Voltage and Current Waveform Recorder
Independent CBEMA Log Plotting
The unit records up to 512 samples per cycle for a voltage sag or
swell or a current fault event. The unit provides the pre- and postevent recording capability shown in the table below. Waveform
records are programmable to the desired sampling rate. V5 provides
up to 3 Megabytes storage and V6 provides a total of 4 Megabytes.
The meter stores an independent CBEMA log for magnitude and
duration of voltage events. This allows a user to quickly view total
surges, total sags and duration without retrieving waveform data.
The meter's advanced DSP design allows Power Quality triggers
to be based on a 1 cycle updated RMS. Up to 170 events can be
stored until the memory fills. The meter stores waveform data in a
first-in/first-out circular buffer to insure data is always recording.
Harmonic Recording to the 40th Order
The Shark® 200 meter provides advanced harmonic analysis to the
40th order for each voltage and current channel in real time. Using the
stored waveforms, harmonic analysis is available to the 255th order.
Optional Waveform Recorder
V5
V6
Samples
per Cycle
Pre Event
Cycles
16
32
64
128
256
512
32
16
8
4
2
1
Post Event
Cycles
96
48
24
12
6
3
Max Waveform
per Event
Number of
Stored Events
256
128
64
32
16
8
85
85
85
170
170
170
Harmonic Spectrum
(40th Order)
Waveform
Zoomed
Note: Sampling rate based on 60Hz systems. For 50Hz systems, multiply by 1.2.
Waveform Scope
The unit uniquely offers a
waveform scope to view the
real time waveform for voltage
and current. Waveform scope
allows the meter to be used as
a basic oscilloscope throughout
Waveform Scope Display
6 Channels of Waveforms
3
STANDARD COMMUNICATION CAPABILITY
The Shark® 200 meter provides two independent communication
ports with advanced features.
• KYZ Pulse - In addition to the RS485, the meter also includes Pulse Outputs mapped to absolute energy.
Rear Mounted Serial Port with KYZ Pulse
Front Mounted IrDA Communication
• RS485 - This port allows RS485 communication using Modbus or DNP 3.0 protocols. Baud rates are from 1200 to 57600.
Uniquely, the Shark® 200 meter also has an optical IrDA port,
allowing you to program it with an IrDA-enabled laptop PC.
FIELD EXPANDABLE I/O AND COMMUNICATION CAPABILITIES
The Shark® 200 meter offers unequaled I/O expandability. Using the two universal option slots, the unit can be easily configured to accept
new I/O cards even after installation. The unit auto-detects installed I/O option cards. Up to 2 cards of any type can be used per meter.
1. INP100S: 100BaseT Ethernet Capability
• Set delays and reset delays
The meter can provide 100BaseT Ethernet functionality.
• Status Inputs – Wet / Dry Auto Detect (Up to 150 VDC)
• Embedded web server, Smartphone compatible
• Network Time Protocol (NTP) support (Network Clock Sync)
•Must be used with V4 or higher V-Switch™ option for
limit based alarms and control
• 12 simultaneous Modbus TCP/IP connections
• Allows for control, alarm and status
• 5 simultaneous DNP over TCP/IP connections
• Dual Ethernet Ports available
6. PO1S: Four Pulse Outputs / Four Status Inputs
• Programmable to any energy parameter and pulse value
2. INP300S: IEC 61850 Protocol Ethernet Card
• Form A: Normally open contacts
• Simultaneous Modbus and IEC 61850
• Also used for End of Interval pulse
• 5 Simultaneous MMS Clients
• 120mA continuous load current
• Multiple Logical Nodes
• Status Inputs - Wet / Dry Auto Detect (Up to 150 VDC)
• Polled Operation Mode (Queried Reports)
• Provides KYZ outputs and pulse input counting
• Buffered and Unbuffered Reports
• Configurable .CID file
7. FOVPS or FOSTS: Fiber Optic Card
• Assignable to any parameter
•EIG’s exclusive Fiber Optic Daisy Chain switchable
built‑in logic mimics RS485 half duplex bus, allowing
you to daisy chain meters for lower installation costs.
Full duplex is also assignable.
• 0.1% of full scale
• ST Terminated Option (-FOSTS)
• 0 to 10K Ohms
• Versatile Link Terminated Option (-FOVPS)
• Range +/- 1.20mA
• Modbus and DNP 3.0 protocols available
• Designed for RTUs and generating stations
•The preferred communication method for intrinsic safety
and high reliability
3. 1mAOS: Four Channel Bi-directional 0-1mA Outputs
4. 20mAOS: Four Channel 4-20mA Outputs
• Assignable to any parameter
Meter
Auto
Detects
I/O Card
Type
• 0.1% of full scale
• 0 to 850 Ohms at 24VDC
• Loop Powered using up to 24 Volts DC
Simple
Field
Upgrade
• Ideal for any Process Control application
5. RO1S: Two Relay Outputs / Two Status Inputs
• 250VAC/30VDC - 5A Relays, Form C
• Trigger on user set alarms
4
Field Expandable I/O Slots
Note: I/O cards can be ordered separately - see last page
SHARK®200
METER
100BASET ETHERNET (INP100S or INP300S)
Simultaneous Data Connections
(HTTP)
(DNP 3.0 over TCP/IP)
Web Server
(Modbus TCP)
SCADA
Meter Reading Software
(INP100S)
DNP 3.0
over TCP/IP
(INP300S)
HTTP
Modbus
TCP
or
IEC 61850
Protocol
Simultaneous Connections to
Multiple Software Systems
Embedded
Web Server with
Smartphone
Support
INP100S - WEB SERVER, MODBUS, DNP
• W
eb Server with Configurable HMI • S
martphone Compatible
• 1 2 Connections Modbus TCP
• 5 Connections DNP over TCP/IP
4.65"
INP300S - WEB SERVER,
MODBUS, IEC 61850
4.10"
• IEC 61850 Protocol
[10.41cm]
[11.81cm]
•
5 Modbus200
Connections
SHARK®
METER
ANSI
4.76"
12.10cm
• W
eb Server for Status
and MOUNTING
Configuration
AND DIN
4.14”
10.52cm
0.62”
1.61cm
• Dual Ethernet Port Capable
ANSI Mounting
DIN Mounting
3.38" Sq.
9.20cm
HI
HI
HI
LO
LO
LO
3.56”
9.04cm
4.85”
[12.32cm]
5.02”
[12.75cm]
• Simultaneous Modbus, DNP over Ethernet, and IEC 61850
• 5 unit
MMS
Clientsdirectly in an ANSI C39.1 (4” round form) or an
The
mounts
IEC 92 mm DIN square form. This is perfect for new installations
and for existing panels. In new installations, simply use DIN or
SHARK® 200 METER ANSI AND DIN MOUNTING
SHARK®
200T TRANSDUCER
Ic
Ib
Ia
ANSI punches. For existing panels, pull out old analog meters
The unit mounts directly in an ANSI C39.1 (4” round form) or an
This transducer version of the Shark® 200 meter does not include
and replace them with the Shark® 200 meter. The meter uses
IEC 92 mm DIN square form. This is perfect for new installations
a display. The unit mounts directly to a DIN rail and provides an
standard voltage and current inputs so that CT and PT wiring does
and for existing panels. In new installations, simply use DIN or
RS485 Modbus or DNP 3.0 output and the expandable I/O.
not need to be replaced.
ANSI punches. For existing panels, pull out old analog meters
and replace them with the
Shark® 200 meter. The0.91"
meter uses
3.25”
3.25”
2.31cm
standard voltage and current
PT wiring does8.26cm
[8.26cm]inputs so that CT and
not need to be replaced.
4 X 0.2”
9.20cm
3.56”
[9.04cm]
4.0”
Shark® 200T - DIN Rail Mounted Transducer
American
European
(One meter fits both standards)
5
TYPICAL SUBSTATION SOLUTIONS
SUBSTATION VOLTAGE AND FREQUENCY RECORDING
Traditionally, voltage recording meters were relegated to high
cost metering or monitoring solutions. The Shark® 200 meter
can be placed throughout an electrical distribution network.
The meter provides one of the industry's lowest cost methods
of collecting voltage information within a Utility power
distribution grid.
• V
oltage reliability analysis insuring proper voltage to
customers
• C
ompare voltage reliability throughout transmission or
distribution networks
• M
onitor the output of substation transformers or line regulators
• Initiate conservation voltage reduction, reducing system
demand
• M
onitor highly accurate frequency to regulate frequency
stability
• Replace costly frequency transducers
INTERVAL LOAD PROFILING
The Shark® 200 meter allows you to log substation data over
time with regard to electrical usage, demand, voltage, current,
PF and many other parameters. This enables a complete
analysis of the power system over time.
• Provide revenue accurate load profiling
• Determine substation usage
• Analyze feeder capacity and utilization
• Provide time based load profile for planning and estimation
• D
ata trend PF distribution and imbalances for system
efficiency analysis
LOW COST SUBSTATION TELEMETRY
The Shark® 200 meter's advanced output capability
brings back data using many different communication
media such as RS485, Ethernet and analog outputs.
This insures that one meter can be used for
almost every substation application no matter what
communication infrastructure is needed.
• Perfect for new or retrofit applications
• Multiple Com paths
• One meter provides outputs for every application
• M
ultiple systems and/or users accessing data
simultaneously
6
SHARK®200
METER
DIMENSIONAL DRAWINGS
4.76"
[12.10cm]
4.71"
[12.00cm]
4.10"
[10.41cm]
5.02”
[12.75cm]
[12.32cm]
4.85”
4.14”
[10.57cm]
0.91"
[2.31cm]
3.25”
[8.26cm]
Shark® 200 Meter Side
Shark® 200 Meter Face
3.56”
HI
Ia
LO
LO
LO
Shark® 200T Transducer Side
3.56"
[9.20cm]
[8.5cm]
WIRING DIAGRAMS
HI
Ib
3.25”
[8.26cm]
3.38" Sq.
[9.04cm]
HI
Ic
0.62”
[1.61cm]
3.56”
[9.04cm]
4.85”
[12.32cm]
0.20"dia
[0.5cm]
4.0"dia
[10.2cm]
LINE
3 Phase 4 Wire WYE Direct
3.56"
[9.20cm]
LINE
3 Phase 3 Wire Delta Direct
A B C
3.56”
[9cm]
N A B C
CT
Shorting
Block
CT
Shorting
Block
GND
Earth Ground
HI
HI
HI
lc
lb
la
LO
LO
LO
Earth Ground
Power
Supply
Connection
L(+)
FUSE
N(-)
3A
Vref
1.69”
L(+)
GND
[4.3cm]
N(-)
Va
HI
HI
HI
lc
lb
la
LO
LO
LO
Power
Supply
Connection
L(+)
FUSE
N(-)
3A
Vref
L(+)
N(-)
Va
Vb
Vb
Vc
Vc
FUSES
3 x 0.1A
FUSES
3 x 0.1A
A B C
N A B C
LOAD
LOAD
3 Phase 4 Wire WYE with PTS
LINE
N A B C
3 Phase 3 Wire Delta with PTS
LINE
A B C
CT
Shorting
Block
CT
Shorting
Block
GND
Earth Ground
HI
HI
HI
lc
lb
la
LO
LO
LO
Power
Supply
Connection
L(+)
FUSE
N(-)
3A
Vref
Earth Ground
GND
L(+)
N(-)
Va
Vb
HI
HI
HI
lc
lb
la
LO
LO
LO
Power
Supply
Connection
L(+)
FUSE
N(-)
3A
Vref
L(+)
N(-)
Va
Vb
Vc
Vc
FUSES
3 x 0.1A
FUSES
2 x 0.1A
Earth Ground
N A B C
LOAD
Earth Ground
A B C
LOAD
7
Specifications
•
•
Voltage Inputs
• 20-576 Volts Line To Neutral,
0-721 Volts Line to Line
• Universal Voltage Input
• Input Withstand Capability – Meets IEEE C37.90.1 (Surge Withstand Capability)
• Programmable Voltage Range to Any PT ratio
• Supports: 3 Element WYE, 2.5 Element WYE, 2 Element Delta, 4 Wire Delta Systems
• Burden: Input Impedance 1 Mega Ohms. Burden 0.014W at 120 Volts
• Input wire gauge max (AWG
12 / 2.5mm2 )
Power Supply
Option D2:
• (90 to 265) Volts AC and (100 to 370)
Volts DC. Universal AC/DC Supply
Option D:
•
(18-60) Volts DC (24-48 VDC Systems)
Pickup Current: 0.1% of Nominal
Class 10: 5mA
Class 2: 1mA
Pass through wire diameter:
0.177” / 4.5mm
Isolation
All Inputs and Outputs are
galvanically isolated to 2500 Volts
Meter Accuracy
• See page 2
•
Note: For 2.5 element programmed
units, degrade accuracy by an
additional 0.5% of reading.
•
Note: For 1A (Class 2) Nominal,
degrade accuracy to 0.5% of reading
for watts and energy; all other values 2
times rated accuracy.
Burden: 10VA Max
Standard Communication Format
• 2 Com Ports (Back and Faceplate)
• RS485 Port (Through Backplate)
• IrDA (Through Faceplate)
• Com Port Baud Rate: (1200 - 57600)
• Com Port Address: 1-247
• 8 Bit, Parity setting: Off, Even, None
• Modbus RTU, ASCII or DNP 3.0 Protocols
Environmental Rating
Storage: (-20 to +70)° C
Operating: (-20 to +70)° C
Humidity: to 95% RH Non-Condensing
Faceplate Rating: NEMA12
(Water Resistant)
Mounting Gasket Included
Current Inputs
• Class 10: (0.005 to 11) A, 5 Amp Nominal
• Class 2: (0.001 to 2) A, 1A Nominal Secondary
•Fault Current Withstand (at 23°C):
100 Amps for 10 Seconds, 300
Amps for 3 Seconds, 500 Amps for
1 Second
• Continuous current withstand:
20 Amps for Screw Terminated or
Pass Through Connections
•Programmable Current to Any
CT Ratio
• Burden 0.005VA per phase Max at 11Amps
•
Shark® 200T Transducer DIN rail
mounted
• 2-inch DIN Rail Included
•
Shipping Container Dimensions:
6” cube
Compliance
• IEC 62053-22 (0.2% Accuracy)
• ANSI C12.20 (0.2% Accuracy)
•ANSI (IEEE) C37.90.1 Surge Withstand
• ANSI C62.41 (Burst)
• EN61000-6-2 – Immunity for
Industrial Environments: 2005
• EN61000-6-4 – Emission Standards
for Industrial Environments: 2007
• EN61326-1 - EMC Requirements:
2006
• KEMA Certified for IEC 61850
• Certified to UL 61010-1 and CSA
C22.2 No. 61010-1, UL File:
E250818
KYZ Pulse
• Type Form C Contact
• On Resistance: 35 Ohms Max
• Peak Voltage: 350 VDC
• Continuous Load Current: 120mA
• Peak Load Current: 350mA (10ms)
•Off State Leakage Current@
350VDC: 1uA
Sensing Method
• True RMS
• Sampling at over 400 samples / cycle on all channels of measured readings simultaneously
• Harmonics resolution to 40th order
• Waveform up to 512 samples/cycle
Update Rate
• Watts, VAR and VA - every 6 cycles
•
All other parameters - every 60
cycles
Dimensions and Shipping
• Weight: 2 lbs /.91 kg
• Basic Unit: H4.85" x W4.85" x L4.25"
•
Shark® 200 meter mounts in 92mm
DIN & ANSI C39.1 4" round cut-outs
Ordering Information
All fields must be filled in to create a valid part number.
Model
Option
Numbers:
Example:
Shark200
Frequency
-
Shark200
(Meter/Transducer)
Shark200T
(Transducer Only)
60
Current Input
-
V-Switch Pack
-
10
V2
50
50 Hz
System
10
10 Amp
Secondary
V1
Multifunction
Meter Only
60
60 Hz
System
2
2 Amp
Secondary
V2
Standard DataLogging Memory
Power Supply
-
Additional Accessories
V3
Power Quality Harmonics
Communication Converters
V4
Limits & Control
9PINC – RS232 Cable
D2
I/O Slot 1*
-
D2
90-265V
AC/DC
D
18-60V
DC
V5
64 Samples/cycle
Waveform Recording
CAB6490 - USB to IrDA Adapter
Unicom 2500 - RS485 to RS232 Converter
Unicom 2500-F – RS485 to RS232 to Fiber Optic
Converter
V6
512 Samples/cycle
Waveform Recording
Modem Manager, Model #, MM1 – RS485 to RS232
Converter for Modem Communication
IrDA232 - IrDA to RS232 Adapter for Remote Read
Compliance Documents
Certificate of Calibration, Part #: CCal – This provides
Certificate of Calibration with NIST traceable Test Data.
Current Transformer Kits
CT200K – 200/5 Ratio 1.00” Window 3 CTs
CT400K – 400/5 Ratio, 1.25” Window, 3 CTs
CT800K – 800/5 Ratio, 2.06” Window, 3 CTs
CT2000K – 2000/5 Ratio, 3.00” Window, 3 CTs
CT Specifications:
Frequency: 50 to 400Hz; Insulation: 600 Volts, 10kV BIL
Flexible Leads: UL 1015 105°C, CSA Approved, 24”
Long, #16AWG
Software
Option Numbers
COMEXT4P – Communicator EXTTM 4.0 Software,
single license
* Consult factory application engineer for additional
transformer ratios, types or window sizes.
Electro Industries/GaugeTech
1800 Shames Drive • Westbury, NY 11590
1- 877-EIMETER (1- 877-346-3837) • E-Mail: sales@electroind.com
Tel: 516-334-0870 • Web Site: www.electroind.com • Fax: 516-338-4741
8
INP100S
I/O Slot 2*
-
Mounting
(Shark® 200 Only)
-
X
X
X
None
X
None
X
ANSI Mounting
RO1S
2 Relays /
2 Status
RO1S
2 Relays /
2 Status
DIN
DIN Mounting
Brackets
PO1S
4 Pulses /
4 Status
PO1S
4 Pulses /
4 Status
1mAOS
4 Channel
Analog Output
0-1mA
(bidirectional)
1mAOS
4 Channel
Analog Output
0-1mA
(bidirectional)
20mAOS
4 Channel
Analog Output
4-20mA
20mAOS
4 Channel
Analog Output
4-20mA
FOSTS
Fiber Optic
Output ST
Terminated
FOSTS
Fiber Optic
Output ST
Terminated
FOVPS
Fiber Optic
Output VPIN
Terminated
FOVPS
Fiber Optic
Output VPIN
Terminated
INP100S
100BaseT
Ethernet
INP100S
100BaseT
Ethernet
INP300S
IEC 61850
Protocol
Ethernet
INP300S
IEC 61850
Protocol
Ethernet
* I/O cards can be ordered separately
using the above part numbers.
E149702 031015 V.1.25
Nexus 1262/1272
®
High Performance Utility Billing Meters with Communication and Advanced Power Quality
Nexus® 1262
www.electroind.com
Economical Meter with
Advanced Communication
Nexus® 1272
Performance Meter with
Advanced Power Quality
& Communication
Highly Advanced Revenue Meter
Highly Advanced Communication
• Auto-calibrating Metrology
• Up to 4 Com Ports
• 0.06% Watt-hr Accuracy
• Modbus RTU and Modbus TCP/IP
• Multipoint Compensation Factors
• DNP 3.0 Serial and Ethernet
• Pulse Totalizers
• Combo RJ11 Modem and Ethernet Ports
• Load Profilers and I/O
• Web Server and Email on Alarm
• MV90 Compatible
• High-Speed, Power Quality Waveform Recorders
Electro Industries/GaugeTech
MV90
The Leader in Power Monitoring and Smart Grid Solutions
COMPATIBLE
Accu-Measure Auto-Calibrating Metrology
The Nexus® 1262/1272 meters are designed for demanding smart grid and intelligent substation applications. They provide one of the most profound analyses of
electricity available in a socket meter. The units offer extensive advanced monitoring features to meet the most critical power monitoring requirements. Using advanced
DSP technology, the Nexus® meters offer immediate and stored revenue power data coupled with superior power quality and communication. To meet the sophisticated
standards required by utility companies and de-regulated power providers, the Nexus® meters' basic package starts where most other meters end. Standard features in
Nexus® units provide the ability to meet your future advanced metering needs.
ACCU-MEASURE™ AUTO-CALIBRATING METROLOGY
EIG’s Accu-Measure™ auto-calibrating metrology provides unmatched
LOAD AGGREGATION/UNIVERSAL METERING
Using
standard
pulse
inputs, the Nexus® 1262/1272
accuracy.
• Energy and Power Accuracy to within 0.06%
meter can count pulses from
• Auto-calibration over Time
external meters and accumu-
• Automatic Temperature Drift Adjustments
late usage. The pulse inputs
can be used to totalize electrical
4 QUADRANT
MEASUREMENT
usage and utility values, such
as water or gas use data.
The unit is a full four quadrant
• 8 Pulse Inputs
meter and gathers hour data information
• Individual Accumulating Registers
in every quadrant.
• 4 Totalizing Registers (Add or Subtract)
• kWh Delivered and Received
CT & PT COMPENSATION
• kVAh in Each Quadrant
The Nexus® units compensate for errors in current transformers and
• kVARh in Each Quadrant
potential transformers.
• Q Hours
• Voltage Compensation
TIME OF USE
The 1262/1272 offers robust time
• Multipoint Current
March 2014
of use functionality. Standard capabilities include:
• 8 TOU Schedules
• 4 Seasons/Year
Compensation
• Multipoint Phase Angle
Compensation
• Better than 0.01%
Resolution
• 20 Year Calendar
• Prior Month and Prior Season
• Programmable Freeze Registers
MULTIPLE DEMAND WINDOWS
The Nexus® 1262/1272 meter simultaneously monitors five demand
structures.
TRANSFORMER AND LINE LOSS COMPENSATION
Loss Compensation adjusts for both copper and iron losses with a simple
user setup.
FIELD TEST MODE
• Block Window Demand
• Rolling Window Demand
• Interval Length from 1 Second
to Many Hours
• Predictive Demand
• End of Interval Pulse Output
• Thermal Demand
• End of Interval Pulse Input
• Cumulative Demand
• Cold Load Pickup
• Test All Energy Readings
• Enable/Disable in Test
Mode
• Preset Accumulators
• Freezable Accumulators
TIME STAMPED MAX. DEMANDS
The units gather demand information for all power values. Each value is
date/time stamped.
• kW Demand, Delivered &
Received, Max/Min
• kVAR Demand, Delivered &
Received, Max/Min
2
Reliable, Functional and Feature-Rich Metering
• kVAR Coincident with kW Demand
• kVA Demand, Max/Min
• Amps Demand, Max/Min
• Voltage, Max/Min
Configure Custom Display For Any Application
Unique Display Configurator
The Nexus® 1262/1272 meter is designed with one of the industry’s most
advanced LCD display configuration technologies, which lets you choose from
multitudes of pre-programmed display screens and create fully customized
displays for any specific application. Build from scratch, as needed, user display
screens that provide information on anything the meter measures (which is
almost everything). Use the display to view not only electrical, but water or gas
usage. Also use the meter as an aggregator for total usage. Provide ambient
and transformer temperature or any other desired critical operational data on the
display.
03/18/14
15:34:05 1 ABC
03/18/14
01 kWh
15:34:05 1 ABC
00001.66
03/18/14 16:46:45
16:46:45
08/03/10
1
• Make Custom Screens Based on Modbus Registers
• Make Any Custom Labels
Delivered
CUSTOM DISPLAY CONFIGURATOR TO CREATE
EXACTLY WHAT’S NEEDED
• Customize Screen Numbering and Order
• Display Up To 5 Pieces of Information Per Screen
CC
• Display Water, Gas and Other Types of Usage
03/18/14
15:34:06 2 ABC
• Add Diagnostic Information
NORMAL MODE
03/18/14
• kWh Delivered and Received
• kVARh Delivered and Received
• kVAh Delivered and Received
• Peak Rolling Window Demand
• Peak Block Window Demand
3 DISPLAY MODES/75 SCREEN SLOTS
The meter’s memory has 75 slots for custom and/or pre-programmed
TIME OF USE MODE
screens. These slots can be allocated to any view mode with any number of
• kWh and kW Demand Delivered and Received Total
slots used in each of the modes.
• kVARh and kVAR Demand Delivered and Received for Each Register
• kVAh Delivered and Received for Each Register
• kVAh Delivered and Received Total
PRE-CONFIGURED DIAGNOSTIC SCREENS
Select from a large offering of diagnostic screens such as:
• Voltages
• Phase Angles
• Harmonic Magnitudes
• Firmware Versions
• Meter Status
• Phasor Diagram
• Per Phase Amps
• Watts/VARs
• Many More Diagnostic Screens Available
INFRARED TEST PULSE
The meter provides an infrared test pulse that can pulse for +WattHour, -Watt-Hour, +VAR-Hour, -VAR-Hour and VA-Hour. This pulse uses time
modulation, allowing the pulse to be accurate during short duration pulse tests
Highly configurable display assignments
using industry accepted reference standards.
3
Advanced Communication and I/O Capabilities
STANDARD MULTI-PORT
COMMUNICATION
CONTROL CAPABILITIES
• ElectroLogic™ Provides User-definable
• Optical Port
Control Outputs
• 2 RS485 Serial Ports
• Action and/or Alarm on Abnormal Condition
• Modbus RTU/ASCII
• Action on Boolean Logic Combinations of
• DNP 3.0
Inputs or Electrical Conditions
Total Web Solutions —
Providing Advanced Metering
Data Integration With the Web
Total Web Solutions is an advanced Ethernet
communication architecture that lets you design
custom webpages, display metering data and host
your meter power information website directly on
• Speeds Up to 115200 bps
DNP 3.0 LEVEL 2 PLUS
a Nexus® meter. The Nexus® meter hosts the web
®
OPTIONAL COMMUNICATION
The Nexus 1262/1272 meter provides advanced
data without any need for dedicated server software,
• Dial-Out Modem (56k) with Battery
DNP 3.0 protocol implementations. DNP 3.0 is
ActiveX Controls or Java Applets. The meter does the
available on the serial and Ethernet ports. EIG’s
data collection, the formatting and the page hosting.
Backed Outage Reporting
®
1262/1272 meter complies with all DNP
• 10/100BaseT Ethernet
Nexus
• Ethernet/Modem Combo
Level 1 and Level 2 certification requirements PLUS
a host of additional features including:
COMBINATION MODEM
& WEB SOLUTION
This option allows you to access the meter
through the web and through a modem for dial-up
communication. Features include:
• 56k Modem
• 10/100BaseT Ethernet
• Up to 136 Measurements:
• Multiple Meter Hosting
• Read Direct From Meters (No Server
in the Customizable DNP Point Map
• Up to 16 Relays and 8 Resets: Can Be
Controlled through DNP
• Report-By-Exception Processing: (DNP
Events) Deadbands Can Be Set on a
Per-point Basis
• Does Not Support Battery for
Outage Reporting
STANDARD I/O
• IRIG-B 1 msec Time Synchronization to
• Direct Webpage Hosting With Live Readings
64 Analog Inputs Mapped to DNP Static Points
• Email on Alarm
• 5 DNP over Ethernet Sockets
• Fully Customizable Webpage Development
64 Binary Inputs, 8 Binary Counters,
• Total Web Solutions (Web Server)
• 12 Modbus Sockets
ADVANCED FEATURES INCLUDE:
Software Needed)
• No Active Controls or Java Downloads
• IT Dept Friendly; Works Through Firewalls;
Low-Cost/High Functionality
• Instant Alarm Emails – Direct from the Meter
• 250 Events in Combinations of Four Events:
Binary Input Change, Frozen Counter,
WEBEXPLORER
Counter Change, Analog Change
(Directly Host Metering Data)
• Freeze Commands: Freeze, Freeze/No-Ack,
EIG’s WebExplorer provides you with direct
Freeze with Time, Freeze with Time/No-Ack,
access to all power data through Internet Explorer
Scheduled Freeze Command
in standard HTML format, without needing to down-
• Freeze with Time Command:
load ActiveX controls or Java applets. WebExplorer
Enables the Nexus® Meter to Have Internal
is fully programmable, so you can customize
• 4 Internal KYZ Pulse Outputs
Time-driven Frozen Counter and Frozen
your own SCADA quality webpages, graphics and
• 8 KYZ Pulse/Status Inputs
Counter Event Data
configurations.
GPS Satellite Clock
• Third Party Certification is Available
OPTIONAL EXTERNAL I/O
• 5 Simultaneous DNP Ethernet Sessions
Connect multiple external I/O Modules for
Analog Outputs
•
Analog Inputs
•
Digital Status Inputs
•
KYZ Outputs
•
Relay/Alarm Outputs
Applications
• Fully Programmable Webpage Generator
enhanced I/O capability.
•
• Easily Incorporated Into Any Existing Web
• Brings in Direct XML Links, Displaying Many
Meters on One Page
WEBXML
Creates Real Time Data in XML Format.
WebXML allows the Nexus® meter to gather data
from the Nexus® host or through other meters and
put the data directly into an XML format. This allows
you to share data through the web with multiple
applications and create custom webpages, using
WebExplorer.
4
WebExplorer
WebXML
WebReacher
Total Web Solutions
WEBALARM – EMAIL ALERTS
features are available simultaneously. Even with DNP
EIG’s WebAlarm sends real time email alerts via
3.0 over the Ethernet, you still have access to multiple
the Internet to up to 9 recipients simultaneously for
Modbus sockets, email alarms, web servers and
any combination of event notifications.
many other communication features.
• Real Time Alerts
WEBMOD
• Simultaneous Emails to Multiple Recipients
(Open Architecture 3rd Party Integration)
• Update Users on Virtually Any Abnormality
• Uses Standard SMTP — Just Assign Email
Addresses
WebXML technology is easy to configure and
extremely flexible. With WebXML, your data is instantly
• Shows the Last 10 Emails on Website for
Later Investigation
available to a host of software applications, including
standard web browsers and documentation software.
• Automatically Process and Present Data In
Readable XML Format
• Add Scale Factors, Multipliers or Other
Desired HTML Capability
• Display Data From Host Meter and/or Any
The 10/100BaseT design allows the unit to
Other Meter Using Modbus RTU or TCP/IP
speak with 12 simultaneous sockets of Modbus TCP.
(WebReacher)
EIG’s WebMod features Modbus TCP open protocol
• Customized Programming
• Easily Viewed by Different Applications
• Modbus Data Concentrator
WEBREACHER
WEBDNP
that can be easily integrated with most other soft-
Using this feature, you can gain access to the
ware or hardware. And, with the built-in Modbus data
meter speaking native DNP over Ethernet. This allows
concentrator, you can poll up to 8 devices or 512
the unit to open an exclusive network socket for DNP
unique polling items from any device that can speak
3.0. Using this unique technology, all other meter web
Modbus RTU and/or Modbus TCP protocols.
With EIG’s exclusive WebReacher technology,
View data from multiple meters generated from the
you can now access remote meters around the
Master Meter in your web browser.
world, retrieve data and consolidate it onto one
webpage or website without any separate software
SCADA package or client-side ActiveX controls or
Meter 124
WebXML provides
totalized energy usage
Internet Explorer
Java applets.
WebMod TCP/IP
• No Additional Software Application Costs
Web
M
• No Server System Required
od T
CP/I
P
• No Complex Integration
• No Costly Point Charges
od
P
TC
Meter 115
od
We
b
/IP
Mo
d
P
TC
TC
P/I
P
M
eb
W
bM
We
/IP
(Up to 32 Devices)
Meter 31
Total Web Solutions allows a
meter to display data from many
remote meters.
Meter 87
Meter 14
5
WebAlarm
WebMod
WebDNP
Nexus® 1272 Meter's Advanced Power Quality Analysis Pinpoints Electrical Reliability Issues
The processing capability and accuracy of the Nexus® 1272 meter makes it possible
to gather power quality information with unmatched precision. The Nexus® 1272 unit is
ideally suited for application on all critical loads. From health care to micro-electronics,
the 1272 has what it takes to capture every anomaly. This insures that when there is a
power problem, you have the information required to act. All Power Quality logs are time
stamped to the nearest millisecond to insure accurate recording. The meter's Advanced
Download Logic collects only new data, to minimize download times.
EVENT/OUT OF LIMIT LOG
• Records 1024 Events
• Extensive Limit Setting Capabilities
• Out of Limit Recording
with Multiple Limits per Selected
• High-Speed Input Event Recording
Quantity
• Outage Detection
WAVEFORM LOG
The waveform recording capability of the Nexus® 1272 unit is unparalleled by any
other meter. Waveform records of this quality have historically been reserved only for
transmission lines. The power of the Nexus® 1272 meter now makes this quality available
to your critical customers.
• E xtraordinary Resolution through
16-bit A/D Input
• Sample Rates from 16 to 512
Samples per Cycle
• Total Recording Time Over 100
• Up to Six Channels
• Voltage and Current Triggers
• E xternal Event Trigger
• Voltage Surge/Sag Recording
• Current Fault Analysis
Seconds
CBEMA/ITIC LOG
The separate CBEMA/ITIC Log captures all voltage transients
HARMONIC DISTORTION ANALYSIS
that fall outside these standards. The onboard log holds 1024 events.
• Log Harmonics into Historical Log for Later Analysis
The data is downloaded to a separate log in the meter database for
• Recorded Waveforms Provide Harmonics to the 255th Order
easy analysis. See all voltage disturbances on one screen through the
• View Waveform Record
Communicator EXT™ software.
• Sag/Swell Analysis
• Transient Recording
6
SystemAdvanced
PerformanceReporting
and Reliability
and
Analysis
Analysis
The accuracy and precision of the Nexus® 1272 meter, coupled with its
extraordinary logging capability, makes it an ideal tool for system performance
and reliability analysis. For the first time, at the revenue metering site, users
have the accuracy and precision of a digital fault recorder without the expense.
The Nexus® 1272 meter's 16-bit accuracy and resolution for waveform records
actually exceeds many digital fault recorder products. Combine the Nexus®
1272 unit with EIG’s suite of software solutions to further expand the level of
understanding during any monitoring situation.
COMMUNICATOR EXT
SOFTWARE FAULT
ANALYSIS
TM
• Compares Multiple Fault
• COMTRADE File Converter
Changes Fault Records to
Standard Fault Analysis File
Formats
Records
• Measures Waveform Traces
• Inserts Timing Marks to
Analyze Waveform Transients
AT THE INTERCHANGE
POINT
The Nexus® meter gives you
AT THE CUSTOMER
• Displays CBEMA Logs
the power of a sequence of events
Download the data and open
• PQDIF File Format Converter
recorder on every transmission line or
the files with Communicator EXT™
When that key customer calls,
Allows Nexus® Data to be
interchange point. The unit is always
software. Compare multiple channels;
simply perform a download from the
Read by Standard EPRI Power
watching, and has extended memory
measure amplitudes and timing with
Nexus® 1272 meter. In a few minutes,
Quality Viewing Software
capability which can record multiple
millisecond resolution; see system reli-
all the data related to any event is on
faults, or even frequency swings, dur-
ability events that lasted for several
your desktop. A completed report is
ing stability problems. Capture all volt-
seconds.
ready to review internally or email
to the customer. Probable causes
ages and currents.
TEST PROTECTIVE
EQUIPMENT
are identified and corrective actions
recommended.
Need to test protective equip-
Need to perform a more detailed
ment performance? Simply take
evaluation? Simply open the viewer to
the Nexus® record and convert it to
look at the waveforms and see exactly
COMTRADE format. Insert the file
what happened to voltages and
directly to protective test equipment
currents throughout the event. Only
to verify relay performance.
the Nexus® meter provides precise
pictures for many seconds.
Supported Meter Forms
Accuracy
FORM
RATED VOLTAGE HOOKUP
9S
0 to 277V
L-N
3E, 4W, Wye
36S
0 to 277V
L-N
2½ E, 4W, Wye
45S
0 to 480V
L-L
2E, 3W, Delta
SWB2
0 to 277V
9A
0 to 277
L-N
Programmable
(Universal Forms)
A Base Form
PARAMETERACCURACY
Voltage0.02%
Current
0.05%
Frequency
0.001Hz
W
0.06%
Wh@1.0PF
0.06%
Wh@0.5PF
0.10%
VAR
0.10%
VA
0.10%
PF
0.10%
7
Data and Event Monitoring/Recording
MULTIPLE MEMORY LOGS
SYSTEM EVENTS LOG
®
Nexus meters provide many logs
The unit records the following
to record historical, alarm and system
system events for security and anti-
event data. These logs can be used for
tampering.
profiling, recording events and logging
• Power Up
electrical power parameters over time.
• Power Down
Additionally, using the advanced I/O
• Password Access
available with the product, you can also
• Password Modification
log process measurements, including
• Change of Programmable Settings
temperature, pressure, flow, etc.
• Change of a Run Time
• Change of Clock Time by
TWO HISTORICAL
TREND LOGS
Communication (Modbus
Historical
Trending
or DNP)
These logs allow you to trend
• Test Mode Usage
virtually any electrical parameter over
• Meter Resets (Logs, Max/Min,
time. This includes all electrical and
Energy)
I/O parameters.
INPUT STATUS LOG
• Up To 64 Values per Log
This log records when a digital
• Programmable Trend Times
Replace
Conventional
Chart Recorders
status change occurred in either the
• Provides Magnitude and
internal or external inputs.
Duration of Event
• Millisecond Resolution
•
Status Log for External Events
• 2 Separately Programmable Logs
•
Internally Labeled to Define
Events
• Separately Recorded Time Base
• Records Alarms for Electrical CONTROL OUTPUT LOG
and I/O Channels
This log records the logic and
OUT OF LIMITS LOG
state that triggered a control output.
This log records all out-of-limit
alarms, including the magnitude and
The graphical log shows all the steps
that led up to the event.
the duration of the alarm.
• Displays Pre- and PostAnalysis
• Internally Labeled to Define
Events
• Advanced I/O Analysis
View Alarms, Status Changes and Control Events
Logging Specifications
8
Model
Memory
Historical
Log 11
Historical Log
21
CBEMA / ITIC 2
Out of Limit
Log 2
Waveform Log 3
Output Log 2
Input
Log 2
System
Events 2
1272
1272
Standard
Advanced
85 Days
555 Days
133 Days
133 Days
512
512
1024
1024
63
95
256
256
1024
1024
1024
1024
1262
1262
Standard
Advanced
69 Days
480 Days
32 Days
133 Days
N/A
N/A
512
512
N/A
N/A
512
512
1024
1024
1024
1024
1
Assumes logs store 4 scaled energy readings every 15 minutes
2
Number of events recorded (assumes 14 parameters monitored)
3
Number of waveform records - each record may be from 8 to 64 cycles in duration depending upon meter setup
Dial-Out On Alarm (INP2)
DIAL-OUT ON OUTAGE
The INP2 modem has a dial-out circuit with a battery that detects when
voltage is lost and dials out to provide outage notification. Additionally, the circuit
can be configured to dial out when many other circumstances occur. The Nexus®
1262/1272 meter dials to the EIG Dial-In Server, which allows users to be paged or
Event
Meter
Dials Out
on Event
emailed with notification of events. When the modem option card is installed, the
meter also includes a gateway port. This allows the meter to act as a master for up
to 7 additional meters and dial out on alarm for any of these meters.
RS485
Connection
DIAL-OUT FOR OTHER EVENTS
The meter will dial out for the following circumstances:
• Limits/Status Change
• Cycling of Control Power
• High Speed Input Change
• Password Failure on a Call
• Waveform Record Capture
Coming into the Modem
• CBEMA Power Quality Event
• Meter Communication Failure
Telephone
Dial-out
Modem
INP2
Server
Receives
Alarm
• Control Output Change
Server Provides:
• Alarm Notification
• Logging &
Download
• Automated Alerts
Visual Alarm
DIAL-IN SERVER CAPABILITIES
The EIG Dial-In Server records all notifications, accepts downloads from the
meter and allows users to be notified by email and pager, automatically. Features of
the Dial-In Server include:
• Unlimited Meters
• Scalable Multi-server Architecture
• Email Notification
• Paging Notification
Automatic Notification Via Pager,
Cell Phone or Email
• Audible System Alarm
Dial-Out Logic
Dial-In Settings
9
Dimensions and Mounting
Nexus® 1262/1272 Switchboard Case
Front View
Side View
Back View
L
Y
K
Z
Y
K
Z
Y
K
Z
Y
K
Z
KYZ
S
GATEWAY
S
S
HIGHSPEED
L
L
L
Vc
9
PE
ANALOG
la
Hi
7
10
lb
NETWORK
Hi
5
Lo
Vn
Nexus® 1262/1272 S-Base Case
Front View
N
MAIN
Hi
3
Lo
8
lc
Va
1
Lo
6
MODEM
Vb
4
2
Side View
6.19in
15.72cm
6.91in
17.55cm
4.95in
12.57cm
Nexus® I/O Modules Front View
Modules Height: 4.14” [10.51cm]
Mounting Bracket
6.88”[13.09cm]
Mounting Bracket
3.44”[8.73cm]
2.20” [5.59cm]
1.10”[2.79cm]
0.62”[1.57cm]
1.30”[3.31cm]
Nexus® 1262/1272 A-Base Case
Front View
Side View
4.95in
12.57cm
0.87in
2.20cm
10.40in
26.42cm
2.02in
5.13cm
6.84in
17.37cm
10
6.60in
16.75cm
Specifications
Wiring Diagrams
Switchboard Mount
Form 9S, 4-Wire Wye and Delta
3
3
N
LINE
  
1

2
2
Y K Z
CH1
N
1
K Z Y K Z Y K Z
| Y CH2
| CH3 | CH4 |
(-) (+) S (-) (+)
|
IRIG-B COM1
S (-) (+)
COM4
|
8 7 6 5 4 3 2 1 C
HIGH SPEED
|
L N PE
Power In

S (1) (+)
Gateway
Network Phone Line

Vc
Ia - Hi
+
Ib - Hi
+
Caution: Power Supply Input
on new units is configured
differently.
Please check wiring carefully.
Va
Ic - Hi
+
+
+
Vn
Lo
Lo
Lo
Vb
+
+
+
+
+

LINE















LOAD
LOAD
Form 45S, 3-Wire Delta
Switchboard Mount
3
LINE
Y K Z
CH1
  
1
2
K Z Y K Z Y K Z
| Y CH2
| CH3 | CH4 |
(-) (+) S (-) (+)
|
IRIG-B COM1
|
S (-) (+)
COM4
|
S (1) (+)
Gateway
8 7 6 5 4 3 2 1 C
HIGH SPEED
L N PE
Power In
Network Phone Line


Vc
Ia - Hi
+
Ib - Hi
+
Caution: Power Supply Input
on new units is configured
differently.
Please check wiring carefully.
Va
Ic - Hi
+
+
+
Vn
Lo
Lo
Lo
Vb
+
+
+
+
+
LINE












LOAD
LOAD
11
Specifications
• All Inputs and Outputs Isolated to 2500 Volts
• Com Ports Isolated From Each Other to 1000 Volts
SENSE INPUTS:
CURRENT (ac)
• Transformer (CT) rated
• Class 2 – 1A nominal, burden 0.000312VA@2.5A
• Class 10, 20 – 5A nominal, burden 0.0125VA@25A
• 16 bit A/D Inputs
• True RMS
• 8 Channel Sample & Hold
MEMORY
• All Meter Setup Parameters, Measurements
• Current surge withstand (at 23°C) - 100 Amps
for 10 seconds, 300 Amps for 3 seconds,
500 Amps for 1 second
STANDARD COMMUNICATION
• LCD Display
• IEC 62053-22 - KEMA Certified
• Line Frequency Clock Synchronization - Accuracy
Better than 1 Second per Month
ENVIRONMENTAL
& Logs Contained in Nonvolatile RAM
480V max between Vref and Va, Vb, Vc inputs;
Burden total 12VA max (including power supply);
600V max between Va, Vb, Vc inputs
• Blade powered unit low voltage (option LV):
69V max between Vref and Va, Vb, Vc inputs;
Burden total 12VA max (including power supply);
120V max between Va, Vb, Vc inputs
OPTIONAL COMMUNICATION
• 56k Modem with Dial-Out Capabilities
• Hardware Lock Secures Meter Settings
• Two 10-Character Passwords
• One Password Controls Access to Read
Meter Digitally
• Externally powered units (options SE, DE):
480V max between Vref and Va, Vb, Vc inputs;
Burden 0.33VA@576V;
600V max between Va, Vb, Vc inputs
• Modem/Ethernet Combo Card
• Input impedance 1Mohm/phase
• Eight High-Speed Input Channels
• Modbus TCP and DNP LAN/WAN
• Internal Wetting Voltage: 12V DC Typical
• 2V pickup voltage
INTERNAL 4ch SOLID STATE OUTPUTS
(KYZ)
• Type: Form C contacts, pulse or transition based
102 to 270V AC/DC @50/60Hz. 12VA max.
• North China EPRI
• Northwest China EPRI
• East China EPRI
• ATS - Korea
COMPLIANCE STANDARDS
Accuracy
• ANSI C12.20 • Additional 8 level password sequence
available by user configuration
DISPLAY
INTERNAL 8ch DIGITAL INPUTS
• Type: Self Excited, for Dry Contacts Only
• 20% over range of rated voltage
EXTERNAL POWER SUPPLY OPTIONS
• Standard external (option SE):
• China EPRI
• Separate Password Controls Access to
Program Meter
• Internal 10/100BaseT with Total Web Solutions
counts
• Type: FSTN Liquid Crystal Display (LCD)
• Resolution: 128 x 64 pixels
• Size: 72 (H) mm x 32 (W) mm (2.8" x 1.26")
• Temperature: Operational from -20 °C to +60 °C
• Backlight: LED (Green)
SHIPPING
Weight:
• Low voltage external (option DE):
(18 to 60)Vdc. Burden 9W max.
• On Resistance: 23-35Ω
Socket: 10 Lbs
• Peak Voltage: 350V DC
Dimensions:
• Separate power cord.
• Continuous Load Current: 120mA
Socket: 13" x 10" x 11" Switchboard: 16" x 14" x 11"
• Switchboard meter is always separately powered
(option SE or DE).
• Peak Load Current: 350mA (10ms)
Switchboard: 16 Lbs
• Off State Leakage Current @350V DC: 1: µA
• Opto Isolation: 3750V rms (60Hz, 1 min.)
Note: Please see Product manual for comprehensive
specifications.
ISOLATION
• ISO California
• CAM - Endesa Chile
SECURITY
• Data Speeds of up to 115200 bps
• USDA Technical Standards Committee Rural
Development Unit
• Union Fenosa - Spain
• Raintight Lexan Cover (Socket meter)
• Modbus RTU, Modbus ASCII, DNP 3.0
• NY State Public Service Commission
• CEEE - Brazil
• Display Temperature: (-20 to +60)°C
• IR Port
• Two RS485 Serial Ports
• California ISO
• NMi - Brazil
• Operating Temperature: (-40 to +85)°C
• Temperature Specifications to Indirect Light
VOLTAGE (ac)
• Blade powered unit, standard voltage (option S):
• IEC 60687 - KEMA Certified
• IRIG-B Input for Synchronizing to External GPS Clock
Signal - Accuracy Better than 1 msec
per Month
• 120% over range of Meter Class
• 0.1% of nominal pickup current
APPROVALS
2 Minutes per Month
SENSING
• Accu-Measure™ Technology
• 2 or 3 current inputs depending on Form
(Ia, Ib, Ic)
CLOCK TIMING
• Internal Clock Crystal - Accuracy Better than
•A
NSI/IEEE C37.90.1 Surge Withstand
•A
NSI C62.41
Surge Immunity
• IEC/CISPR 14-1
Continuous EM Disturbance
• IEC 61000-4-2 (EN 61000-4-2 / IEC 801-2):
Electrostatic Discharge
• IEC 61000-4-3 (EN 61000-4-3 / IEC 801-3): Radiated
EM Field Immunity
• IEC 61000-4-4 (EN 61000-4-4 / IEC 801-4): Electric
Fast Transient
• IEC 61000-4-5 (EN 61000-4-5 / IEC 801-5): Surge
Immunity
• IEC 61000-4-6 (EN 61000-4-6 / IEC 801-6):
Conducted Immunity
• IEC687-5.4.2.1
Voltage Dips and Interruptions
• IEC60687
Class 0.2 Accuracy
• IEC62053-22
Class 0.2 Accuracy
• IEC62052-11 General Requirements,
Mechanical Properties,
Climactic Influences
Ordering Information (To order, please use this guide)
Model
Memory
Form
Class (Amps)
Frequency
Power Supply1Optional
Communication
Option
Numbers:
Example:
−
1272
1272
−
A
−
−
−
−
45S
−
S
9S
Std
20
−
2
Amps
−
−
50
−
DE
−
INP200
50
50 Hz
S
Std Blade Powered
X
No Optional Com
1262
A
36S
10
60
Adv
Amps
60 Hz
SE
Std Ext
102-270V AC/DC
INP2
Modem
with Dial-Out
45S
20
DE
INP200
Amps
DC Ext
10/100BaseT Ethernet
18-60VDC
SWB2
LVINP202
(Switchboard)
69VAC
Modem &
Blade Powered
Ethernet Combo
(No Dial-Out)
9A
(A Base)
1 Switchboard Meter Only Supports SE or DE Options.
Accessory Options
OPTIONAL I/O MODULES
1mAON4
4 Analog Outputs, 0-1mA
1mAON8
8 Analog Outputs, 0-1mA
20mAON4
4 Analog Outputs, 4-20mA
20mAON8
8 Analog Outputs, 4-20mA
4RO1
4 Relay Outputs
4PO1
4 Solid State Pulse Outputs
8AI1
+/- 0-1mA, 8 Analog Inputs
8AI2
+/- 0-20mA, 8 Analog Inputs
8AI3
+/- 0-5VDC, 8 Analog Inputs
8AI4
+/- 0-10VDC, 8 Analog Inputs
8DI1
8 Status Inputs, Wet/Dry
SOFTWARE OPTIONS
POWER OPTIONS
PSIO
I/O Power Supply (Required
with I/O Module)
COMEXT4P
Communicator EXT™ Software Single-Computer
BAT1
External Replaceable Battery for
Dial Out on Outage
DISEXT.1C
Dial-In Server Single-Computer License (One Site)
DISEXT.MC
Dial-In Server Multi-Computer License (One Site)
License (One Site)
MOUNTING OPTIONS
MBIO
I/O Module Mounting Bracket
Power Supply and Mounting Bracket
(Required with any I/O Option)
Electro Industries/GaugeTech
1800 Shames Drive • Westbury, NY 11590
1- 877- EIMETER (1- 877- 346- 3837) • E-Mail: sales@electroind.com
Tel: 516-334 -0870 • Web Site: www.electroind.com • Fax: 516-338-4741
E151702 031715 V.1.15
M
Me
ed
diiu
um
m V
Vo
ollt
ta
ag
ge
e
C
Cu
ur
rr
re
en
nt
t T
Tr
ra
an
ns
sf
fo
or
rm
me
er
r
Model CTWH3-A-60-T90
Wound Primary CT
REGULATORY AGENCY APPROVALS
E145172
LR89403
Manufactured to meet the requirements of ANSI/IEEE C57.13.
APPLICATION:
High accuracy metering and relaying.
FREQUENCY:
50-400 Hz.
MAXIMUM SYSTEM VOLTAGE:
5.6kV, BIL 60kV.
CONTINUOUS THERMAL
CURRENT RATING FACTOR:
1.33 at 30 C amb., 1.0 at 55 C. amb.
o
o
400:51.10 at 30 C. amb., 0.85 at 55 C. amb.
o
o
Primary terminals are plated copper bars. See chart next
page for sizes. Secondary terminals are brass screws No.
10-32 with one flatwasher, lockwasher.
Vacuum cast in polyurethane resin.
Other ratios, secondary currents and dual ratios are
available. Refer to factory.
Approximate weight 41 lbs.
CATALOG
NUMBER
CURRENT
RATIO
ANSI METERING CLASS
RELAY
CLASS
* THERMAL
AT 60HZ
CURRENT RATING
1 SECOND
BO.1
BO.2
BO.5
BO.9
B1.8
RMS AMPS
CTWH3-A-60-T90-050
5:5
T90
0.1
0.1
0.1
0.1
0.2
470
CTWH3-A-60-T90-100
10:5
T90
0.1
0.1
0.1
0.1
0.2
900
CTWH3-A-60-T90-150
15:5
T90
0.1
0.1
0.1
0.1
0.2
1700
CTWH3-A-60-T90-200
20:5
T90
0.1
0.1
0.1
0.1
0.2
1920
CTWH3-A-60-T90-250
25:5
T90
0.1
0.1
0.1
0.1
0.2
2600
CTWH3-A-60-T90-300
30:5
T90
0.1
0.1
0.1
0.1
0.2
2900
CTWH3-A-60-T90-400
40:5
T90
0.1
0.1
0.1
0.1
0.2
3700
CTWH3-A-60-T90-500
50:5
T90
0.1
0.1
0.1
0.1
0.2
4700
CTWH3-A-60-T90-750
75:5
T90
0.1
0.1
0.1
0.1
0.2
5800
CTWH3-A-60-T90-101
100:5
T90
0.1
0.1
0.1
0.1
0.2
8600
CTWH3-A-60-T90-151
150:5
T90
0.1
0.1
0.1
0.1
0.2
12900
CTWH3-A-60-T90-201
200:5
T90
0.1
0.1
0.1
0.1
0.2
18000
CTWH3-A-60-T90-301
300:5
T90
0.1
0.1
0.1
0.1
0.2
28200
CTWH3-A-60-T90-401
400:5
T90
0.1
0.1
0.1
0.1
0.2
34000
CTWH3-A-60-T90-601
600:5
T90
0.1
0.1
0.1
0.1
0.2
51500
*With a burden of BO.1 or greater connected to the secondary.
Medium Voltage
7
M
Mo
od
de
ell C
CT
TW
WH
H3
3-A
A-6
60
0-T
T9
90
0 Wound Primary CT
RECOM MENDED MINIMUM SPACINGS
A = Unit to Unit = 0.75” minimum.
B = HV to Ground in Air = 3.00” minimum.
Recommended spacing are for guidance only. User needs to set
appropriate values to assure performance for high potential test ,
impulse test , high humidity, partial discharge, high altitude, and
other considerations like conf iguration.
BAR SIZES
DIMENSIONS
PRIMARY
8
CURRENT
A
B
5 TO 250A
0.25
1.50
300 TO 1200A
0.38
2.00
CS00A40645
Rev
• F-1100 SINGLE TURBINE •
INSERTION FLOW METER
FREQUENCY OUTPUT
Made in the USA
DESCRIPTION
ONICON insertion turbine flow meters are
suitable for measuring electrically conductive
water-based liquids. The F-1100 model provides
a high-resolution frequency output for connection
to an ONICON Display or BTU Meter.
APPLICATIONS
• Chilled water, hot water, condenser
water, and water/glycol/brine for HVAC
• Process water and water mixtures
• Domestic water
GENERAL SPECIFICATIONS
ACCURACY
± 0.5% OF READING at calibrated velocity
± 1% OF READING from 3 to 30 ft/s (10:1 range)
± 2% OF READING from 0.4 to 20 ft/s (50:1 range)
SENSING METHOD
Electronic impedance sensing
(non-magnetic and non-photoelectric)
PIPE SIZE RANGE
1¼" through 72" nominal
SUPPLY VOLTAGE
24±4 V AC/DC at 30 mA
LIQUID TEMPERATURE RANGE
Standard: 180˚ F continuous, 200˚ F peak
High Temp: 280˚ F continuous, 300˚ F peak
Meters operating above 250˚ F require
316 stainless steel construction option
AMBIENT TEMPERATURE RANGE
-5 to 160˚ F (-20 to 70˚ C)
OPERATING PRESSURE
400 PSI maximum
PRESSURE DROP
Less than 1 PSI at 20 ft/s in 1½" pipe,
decreasing in larger pipes and lower velocities
OUTPUT SIGNAL PROVIDED:
FREQUENCY OUTPUT
0-15 V peak pulse, typically less than 300 Hz
(continued on back)
2103 / 0212PA
CALIBRATION
Every ONICON flow meter is wet-calibrated in
our flow laboratory against primary volumetric
standards directly traceable to NIST. Certification
of calibration is included with every meter.
FEATURES
Unmatched Price vs. Performance - Custom
calibrated, highly accurate instrumentation
at very competitive prices.
Excellent Long-term Reliability - Patented
electronic sensing is resistant to scale and
particulate matter. Low mass turbines with
engineered jewel bearing systems provide a
mechanical system that virtually does not wear.
Industry Leading Two-year "No-fault" Warranty Reduces start-up costs with extended coverage
to include accidental installation damage
(miswiring, etc.). Certain exclusions apply; see
our complete warranty statement for details.
Simplified Hot Tap Insertion Design - Standard on
every insertion flow meter. Allows for insertion
and removal by hand without system shutdown.
OPERATING RANGE FOR
COMMON PIPE SIZES
0.17 TO 20 ft/s
± 2% accuracy begins at 0.4 ft/s
Pipe Size (Inches)
1¼
1½
2
2½
3
4
6
8
10
12
14
16
18
20
24
30
36
Flow Rate (GPM)
0.8
1
2
2.5
4
8
15
26
42
60
72
98
120
150
230
360
510
-
95
130
210
230
460
800
1800
3100
4900
7050
8600
11,400
14,600
18,100
26,500
41,900
60,900
1500 North Belcher Road, Clearwater, Florida 33765 Tel (727) 447-6140 Fax (727) 442-5699
www.onicon.com • sales@onicon.com
12-28-00
F-1100 SPECIFICATIONS cont.
MATERIAL
Wetted metal components
Standard: Electroless nickel plated brass
Optional: 316 stainless steel
ELECTRONICS ENCLOSURE
Standard: Weathertight aluminum enclosure
Optional: Submersible enclosure
ELECTRICAL CONNECTIONS
3-wire for frequency output
Standard: 10' of cable with ½" NPT conduit
connection
Optional: Indoor DIN connector with 10' of
plenum rated cable
F-1100 Wiring Information
WIRE COLOR CODE
NOTES
Connect to power supply
positive
RED
(+) 24 V AC/DC
supply voltage, 30 mA
BLACK
Connect to power supply
(–) Common ground
(Common with pipe ground) negative
(+) Frequency output
GREEN signal: 0-15 V peak
pulse
Signal for ONICON
Display or BTU meter
F-1100 Wiring Diagram
ONICON Display
or BTU Meter
ALSO AVAILABLE
RED
+ 24 V
GREEN
FREQUENCY INPUT
BLACK
SEL
GROUND
Note: Black wire is common with the pipe ground
(typically earth ground).
RST
GPM
463798
POWER
SYSTEM-1
BTU METER
POWER
Display
Modules
BTU Measurement
Systems
Typical Meter Installation
• Acceptable to install in vertical pipe
(New construction or scheduled shutdown)
• Position meter anywhere in upper 180˚
for horizontal pipe
Optional output
signal(s) to
control system
Onicon
Display or
BTU Meter
CLEARANCE
REQUIRED
FOR INSTALLATION
Connect factory wires
to field wires in appropriate
junction box.
½" FNPT
conduit connection
Insertion depth
gage provided
with each meter
Detail of hot tap adapter
with turbine assembly
withdrawn
Typically
30" - 36"
depending on
pipe size and
height of valve
assembly.
Standard Installation
Kit for Steel Pipe
1" Full port ball valve
1" Close nipple
1¼" for
hot tap
1" Branch outlet
ONICON INCORPORATED
1500 North Belcher Road
Clearwater, FL 33765
Tel (727) 447-6140
Fax (727) 442-5699
www.onicon.com
sales@onicon.com
Minimum Hole Size = 1"
Must be centered
FLOW
Note: Installation kits vary based on pipe material and application. For installations in pressurized (live)
systems, use "Hot tap" 1¼ inch installation kit and drill hole using a 1 inch wet tap drill.
2103 / 0212B
12-28-00
• F-2600 SERIES •
INLINE VORTEX
FLOW METER
APPLICATIONS
•Saturated steam
•Hot water to 500° F (260° C) standard
750° F (400° C) optional
Applications with optional pressure sensor
•Superheated steam to 500° F (260° C) standard
750° F (400° C) optional
•
Compressed air
•
Industrial gases
CALIBRATION
Every ONICON flow meter is wet calibrated in a
flow laboratory against standards that are directly
traceable to N.I.S.T. A certificate of calibration
accompanies every meter.
MADE IN THE USA
Vortex flow meters detect the frequency of alternating low
pressure vortices that are formed as flow is diverted around a
bluff body. These swirling low pressure zones apply
lateral pressure first to one side and then to the other of
sensors located downstream of the bluff body. This causes the
sensors to vibrate. The frequency of this vibration is directly
proportional to the flow velocity.
DESCRIPTION
The ONICON F-2600 Series Vortex Flow Meter is a
flexible design that provides accurate, reliable flow
measurement in steam and high temperature water
applications. The F-2600 is designed with a two stage
all welded bluff body/sensor design that enhances
signal sensitivity and extends the operating range of
the meter. This innovative feature also protects the
sensors from pressure shocks and solids suspended
in the flow stream.
The basic loop powered model provides volumetric
flow measurement for water at temperatures up to
500° F. Adding the integral temperature sensor option
allows for mass flow measurement of saturated steam.
Meters provided with integral pressure and
temperature sensors are capable of measuring mass
flow of superheated steam. Optional versions of the
meter are also available that include serial
communications and multiple analog outputs.
FEATURES
•Mass flow measurement from a single instrument
•Optional steam energy flow measurement
•Integral 1,000 W platinum RTD for precise
temperature measurement
•Optional pressure transducer for accurate
pressure readings at the meter location
•Maintenance free non-moving parts design
• Wear resistant bluff body/sensor design
•Advanced signal processing algorithms ensure
stable flow readings and reject noise
•Easy-to-install meter arrives fully programmed
and ready to use
GENERAL SPECIFICATIONS
ACCURACY
Percent of reading accuracy to within:
± 0.7% for liquids (volumetric)
± 1% for steam and gases (volumetric)
± 1.5% for steam and gases (mass)
For Reynolds Number ≥ 10,000
Repeatability: ± 0.2%
Long term stability: ±0.2% over a period of 1 year
11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699
www.onicon.com • sales@onicon.com
0775-8 / 22154
05-14
SENSING METHOD
• Vortex shedding with integral piezoelectric sensors
•Integral 1,000 W platinum RTD (optional) provides instantaneous temperature
• Integral pressure transducer (optional) provides
instantaneous pressure
OPERATING TEMPERATURE RANGE
Ambient:
-40° F (-40° C) to +185° F (+85° C)
Process:
-330° F (-200° C) to +500° F (+260° C)
Optional high temperature limit
+750° F (+400° C)
MAXIMUM OPERATING PRESSURE
≤ Flange rating or 1500 psi (103 bar)
PRESSURE LOSS
Pressure loss varies with meter size and flow rate.
Please contact ONICON for detailed information.
CONNECTION TYPE
• ANSI Class 150, 300 or 600 flanges
• Wafer style
MATERIALS
• Sensor Body:
• Bluff/Sensor Body:
• Electronics Enclosure:
316L Stainless Steel
316L Stainless Steel
Epoxy painted aluminum
ENCLOSURE
NEMA 4X (IP66)
INPUT POWER OPTIONS
• Loop power: 14-36 VDC, 22 mA maximum current
• External DC power: 18-36 VDC, 300 mA maximum current
• External AC power: 100-240 VAC 50/60 Hz, 5 W maximum power
DISPLAY
2-line, 16 character alphanumeric LCD with
backlighting option. Standard saturated steam display
menu provides: Mass Flow Rate, Temperature, Pressure
(calculated), Mass Total and Alarms (if active).
Optional remote mount transmitter version available
(Standard cable length 50 ft., maximum 150 ft.)
OUTPUT SIGNALS PROVIDED
• DC loop powered version (Standard version of meter)
Analog Rate: 2-wire, 4-20 mA
Totalization: 2-wire scaled pulse, 50 ms duration,
5-36 VDC @ 40 mA maximum
Frequency: 2-wire, open collector, 10 kHz maximum,
5-36 VDC @ 40 mA maximum
Digital: HART® serial communications
• Optional external DC or AC powered version
Analog Rate: Up to (3) 2-wire, 4-20 mA outputs
Totalization: (1) 2-wire scaled pulse output,
50 ms duration, 5-36 VDC @ 40 mA maximum
Frequency: (1) 2-wire, 10 kHz maximum,
5-36 VDC @ 40 mA maximum
Digital: HART® serial communications
Alarm: Up to (3) opto-coupled relay alarm outputs
• Optional on DC or AC powered version
MODBUS RTU RS485 or BACnet MS/TP serial
communications in place of HART®
Note: Specifications subject to change without notice.
REMOTE MOUNT INSTALLATION
5.0 in
3.0 in
8.3 in
5.7 in
2.1 in
EXIT
ENTER
2500 GPM
3.0 in
REMOTE CABLE, 50 FT
STANDARD LENGTH
0.6 in
5.0 in
2.8 in
REMOTE ELECTRONICS OPTION
AVAILABLE ON ALL MODELS
.34 in DIA.
U Bolt Provided
11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • sales@onicon.com
F-2600 Series Inline Vortex Flow Meter Catalog Sheet 05/14 - 0775-8 / 22154
Page
2
STRAIGHT RUN REQUIREMENTS
Inline Vortex Flow Meter
PIPE RUN
ECCENTRIC REDUCER
UPSTREAM
OPTIONAL
FLOW STRAIGHTENER
ANSI FLANGES
ECCENTRIC EXPANSION
DOWNSTREAM
PIPE RUN
FLOW DIRECTION
2 DIAMETERS
UPSTREAM STRAIGHT PIPE RUN
TO FLOW STRAIGHTENER
MINIMUM UPSTREAM STRAIGHT PIPE
RUN TO FIRST OBSTRUCTION
Obstruction
MINIMUM DOWNSTREAM
STRAIGHT PIPE RUN
≥ 5 DIAMETERS
*Minimum Upstream Straight
Pipe Run Requirements
Straight pipe run without
flow straightener
Straight pipe run to flow
straightener
Single 90
20 Dia
10 Dia
Tee
20 Dia
10 Dia
RDCR/EXPNDR
20 Dia
10 Dia
Two 90’s Same Plane
30 Dia
15 Dia
Ball/Gate Valve Fully Open
30 Dia
15 Dia
Two 90’s Out of Plane
40 Dia
20 Dia
Control Valve
50 Dia
25 Dia
P.R.V.
50 Dia
25 Dia
11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • sales@onicon.com
F-2600 Series Inline Vortex Flow Meter Catalog Sheet 05/14 - 0775-8 / 22154
Page
3
FLOW METER OPERATING RANGES
Meter Flow Rates for Saturated Steam
Minimum and Maximum Saturated Steam Flow Rates @ Specific Operating Pressures
Pressure
(psig)
Density
(lb/ft3)
Meter
Size in
Inches
5
15
0.0479
0.071
Pressure
(psig)
Density
0.1497 0.2042 0.2578 0.3633 0.4680 0.6784
(lb/ft3)
50
75
100
150
200
300
FLOW RATE (lbs / hr)
½”
6.5
52
7.8
74
11.3
153
13.2
209
15
271
18
372
20
493
24
716
Minimum
Maximum
3/4”
12
122
14.5
195
21
404
24.4
550
27
639
33
980
37
1163
45
1688
Minimum
Maximum
1”
20
265
24
324
35
673
41
915
46
1386
54
1631
62
2525
74
3664
Minimum
Maximum
1 ½”
49
650
59
955
85
1983
100
2698
112
3402
133
4807
151
6203
182
9000
Minimum
Maximum
2”
82
1087
99
1596
143
3313
167
4509
187
5690
222
8033
253
10365
304
15040
Minimum
Maximum
3”
183
2431
222
3570
319
7412
373
10085
419
12729
497
17969
565
23184
680
33642
Minimum
Maximum
4”
318
4231
386
6214
556
12901
648
17554
728
22156
866
31276
983
40354
1184
58556
Minimum
Maximum
6”
722
9594
875
14088
1260
29249
1470
39801
1652
50233
1962
70911
2229
91494
2685
132763
Minimum
Maximum
8”
1264
16806
1532
24680
2208
51239
2575
69723
2893
87998
3438
124222
3905
160279
4704
232575
Minimum
Maximum
Flow Rates for Water
Water Minimum and Maximum Flow Rates (GPM)
Rate
Meter Size (in)
2
3
1½
½
¾
1
Min GPM
0.9
1.4
2.2
5.5
9.2
Max GPM
22
40
67
166
276
4
6
8
21
36
81
142
618
1076
2437
4270
11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • sales@onicon.com
F-2600 Series Inline Vortex Flow Meter Catalog Sheet 05/14 - 0775-8 / 22154
Page
4
METER ORDERING INFORMATION
Vortex Meter Codification = F-26AA-BCD-EFGH
AAaa = Meter Size in Inches
05 = ½”04 = 4”
34 = ¾”06 = 6”
01 = 1”08 = 8”
15 = 1½”10 = 10”
02 = 2”12 = 12”
03 = 3"
B = Connection Type
0 = Wafer
1 = ANSI Class 150 flange
3 = ANSI Class 300 flange
6 = ANSI Class 600 flange
C = Integral or Remote Mount Transmitter
1 = Integral Mount
2 = Remote Mount
D = Temperature / Pressure Compensation
0 = Integral temperature compensation
1 = Integral temperature & pressure sensor, 30 psia maximum
2 = Integral temperature & pressure sensor, 100 psia maximum
3 = Integral temperature & pressure sensor, 300 psia maximum
4 = Integral temperature & pressure sensor, 500 psia maximum
9 = None
E = Input Power
0 = Loop powered (Only available with output signals option F=0)
1 = External 12-36 VDC powered
2 = External 85-240 VAC powered
F = Output Signals
0 = 4-20mA output*, pulse output & frequency output
1 = 4-20mA output, pulse output & frequency output, alarm output & MODBUS
2 = 4-20mA output, pulse output & frequency output, alarm output & BACnet
3 = (3) 4-20mA outputs, (3) alarm outputs, (1) pulse output (1) frequency output & MODBUS
4 = (3) 4-20mA outputs, (3) alarm outputs, (1) pulse output (1) frequency output & BACnet
5 = (3) 4-20mA outputs*, (3) alarm outputs, (1) pulse output (1) frequency output
6 = 4-20mA output*, pulse output & frequency output, alarm output
G = Maximum Operating Temperature
0 = 500° F
1 = 750° F
H = Energy Meter
0 = None
1 = Gross energy meter
2 = Net energy meter (requires additional remote temperature sensor)
* Available with HART® serial communications
Remote Temperature Sensor and Thermowell Installation Kit
(Required for net energy meter)
Part Number
Description
20100
Remote Temperature Sensor, 1,000 Ω 4-wire Class A Platinum RTD
20101
Remote Thermowell Kit for 1½” Welded Steel Pipe
20102
Remote Thermowell Kit for 2” - 5” Welded Steel Pipe
20103
Remote Thermowell Kit for 6” - 14” Welded Steel Pipe
Note: Net energy meter requires one temperature sensor and one thermowell installation kit sized to pipe.
11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • sales@onicon.com
F-2600 Series Inline Vortex Flow Meter Catalog Sheet 05/14 - 0775-8 / 22154
Page
5
FLANGED METER DIMENSIONS & WEIGHTS
5.0 in
(127 mm)
5.0 in
(127 mm)
3.0 in
(76 mm)
ENTER
EXIT
H*
FLOW
-->
L
Flow Meter Size
Flow Meter Nominal Size
½” (15 mm)
1/2 inch (15mm)
¾” (20 mm)
3/4 inch (20mm)
1” (25 mm)
1 inch (25mm)
1½” (40 mm)
1-1/2 inch (40mm)
2” (50 mm)
3” (80 mm)
2 inch (50mm)
4” (100 mm)
3 inch (80mm)
6” (150 mm)
4 inch (100mm)
8” (200 mm)
6 inch (150mm)
10” (200 mm)
8 inch (200mm)
12” (200 mm)
L
7.90 Lin
(200 mm)
4.56
7.9inin
(200mm)
mm)
(116
4.87.9
in in
(200mm)
mm)
(122
4.94
in
7.9 in
(126
(200 mm)
mm)
5.57.9
in in
(200mm)
mm)
(140
7.9
6.0 in in
(200 mm)
(153
mm)
9.84 in
6.9 in
(250 mm)
(175 mm)
11.81 in
8.0
in mm)
(300
(203
mm)
11.81
in
(300
mm)
9 in
15.0
in
(229
mm)
(380 mm)
10.5 in
17.7
in
(267
mm)
(450 mm)
H*
H
13.3 in
(338 mm)
14.8
13.4inin
(340
(376mm)
mm)
15
in in
13.5
(343
(381mm)
mm)
15
in
13.8 in
(381mm)
mm)
(351
Weight
ANSI 150
ANSI 300WEIGHT
ANSI 600
(PN 16)
(PN 40)
(PN 64)
ANSI 150
ANSI 600
ANSI 300
13.6(PN
Lb 16) 14.6 Lb
(PN 40) 15.2 Lb (PN 64)
(6.2 Kg)
(6.6 Kg)
(6.9 Kg)
12.5
Lb
12
Lb
14.7 Lb
17.1 Lb
17.7 Lb 13 Lb
(5.5 Kg) (7.8 Kg)(5.7 Kg)(8.0 Kg) (5.9 Kg)
(6.7 Kg)
15.6 13
Lb Lb
18.0 Lb14 Lb 18.8 Lb 14.5
(5.9 Kg) (8.2 Kg)(6.4 Kg)(8.5 Kg) Lb(6.6 Kg)
(7.1 Kg)
19.0 13.4
Lb Lb 24.2 Lb16.3 Lb26.2 Lb 16.3 Lb
(7.4 Kg)
(6.1 Kg) (11.0 Kg)
(8.6 Kg)
(11.9 Kg) (7.4 Kg)
15
in in
14.0
23.2 14.5
Lb Lb 26.8 Lb22.7 Lb30.2 Lb 24.6 Lb
(356
(10.5 Kg)
(13.7 Kg) (11.2 Kg)
(6.6 Kg) (12.2 Kg)(10.3 Kg)
(384mm)
mm)
14.5
in
34.8
Lb
43.4
Lb
26.8 Lb48.6 Lb 33.2 Lb
15.3 in
19.4 Lb
(368 mm)
(15.8 mm)
(19.7) (12.2 Kg)
(22.1 Kg)
(389 mm)
(15.1 Kg)
(8.8 Kg)
15.0 in
47.3 Lb
27.5 Lb 66.5 Lb39.4 Lb88.5 Lb 56.1 Lb
15.8 in
(381 mm)
(21.5 Kg)
(30.2 Kg)
(40.2 Kg)
(17.9 Kg)
(12.5 Kg)
(25.5 Kg)
(401 mm)
15.9 in
73.7 Lb
110.5 Lb
169.1 Lb
60.3 Lb(78.8 Kg) 96 Lb
16.2mm)
in
(404
(33.543.3
Kg) Lb (50.2 Kg)
(27.4 Kg)
(19.7
Kg)
(411
mm)
16.8 in
113.2 Lb
167.2 Lb
253.6 Lb (43.6 Kg)
(427
(51.4 48.4
Kg) Lb (75.9 Kg)
96 Lb(115.1 Kg) 178 Lb
17.3 mm)
in
18.1mm)
in
177.5(22.0
Lb Kg)256.7 Lb(43.6 Kg)
418.9 Lb (80.8 Kg)
(439
(460 mm)
(80.6 Kg)
(116.5 Kg) (190.2 Kg)
18.2 in
148 Lb
71 Lb
299 Lb
19.1
Lb
385.6 Lb
526.2 Lb
(462inmm) 278.8(32.2
(67.4 Kg)
Kg)
(136 Kg)
(485 mm)
(126.6 Kg) (175.1 Kg) (238.9 Kg)
Add 11 Lb (5 KG) for remote electronics
*This Dimension is the same for integral and remote mount meters.
11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • sales@onicon.com
F-2600 Series Inline Vortex Flow Meter Catalog Sheet 05/14 - 0775-8 / 22154
Page
6
WAFER METER DIMENSIONS & WEIGHTS
5.0 in
(127 mm)
5.0 in
(127 mm)
3.0 in
(76 mm)
ENTER
EXIT
2500 GPM
H*
Ø
FLOW
-->
L
Flow Meter Size
½” (15 mm)
Flow Meter Nominal Size
¾” (20 mm)
1/2 inch (15mm)
1” (25 mm)
3/4 inch (20mm)
1½” (40 mm)
1 inch (25mm)
2” (50 mm)
(80 mm)
1-1/2 inch3”(40mm)
4” (100 mm)
2 inch (50mm)
Ø
H*
2.6 in
13.3 in
1.38 in
(65 mm)
(338 mm)
(35 mm)
H1.69 in
2.6 in L
13.4 in
(65 mm)
(340 mm)
(42.9 mm)
4.56 in
14.8 in
2.6 in
13.5 in
2.00 in
(116 mm)(343 mm)
(376 mm)
(65 mm)
(50.8 mm)
2.6 in4.8 in 13.8 in 15 in2.88 in
(65 (122
mm) mm)(351 mm)
(73.2 mm)
(381 mm)
2.6 in2.8 in 14.0 in 14.8 in
3.62 in
(65 mm)
(356 mm)
(91.9 mm)
(71 mm)
(376 mm)
2.6 in
14.5 in
5.00 in
2.8 in (368 mm) 15.1
in mm)
(65 mm)
(127.0
2.6(71
in mm) 15.0 in(384 mm)
6.19 in
(65 mm)
3.0 in (381 mm)15.3(157.0
in mm)
L
(76 mm)
(102 mm)
4.7 in
(119 mm)
11.5 Lb
(5.2 Kg)
Ø
11.9 Lb
(5.4 Kg)
1.38 in
12.2 Lb
(35 mm)
(5.5 Kg)
1.69Lbin
13.8
(43 mm)
(6.3
Kg)
15.5
2.00Lbin
(7.0 Kg)
(51 mm)
20.6 Lb
2.88
in
(9.4
Kg)
(73 mm)
25.3
Lb
(11.5
3.62Kg)
in
(92 mm)
(389 mm)
meters.
in remote mount
15.8 in
3*This
inchDimension
(80mm) is the same for integral4and
4 inch (100mm)
Weight
(401 mm)
16.2 in
(411 mm)
5 in
(127 mm)
6.19 in
(157 mm)
WEIGHT
9.8 Lb
(4.4 Kg)
10 Lb
(4.5 Kg)
10.1 Lb
(4.6 Kg)
11.9 Lb
(5.4 Kg)
14.1 Lb
(6.4 Kg)
22.7 Lb
(10.3 Kg)
33 Lb
(15.0 Kg)
Add 11 Lb (5 KG) for remote electronics
11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • sales@onicon.com
F-2600 Series Inline Vortex Flow Meter Catalog Sheet 05/14 - 0775-8 / 22154
Page
7
FLOW STRAIGHTENER
Gasket Thickness,
Serrations show located under gasket, if provided.
Nominal
Note: Dimension C indicates ID for serrations.
0.1250
Dim B
Dim C
Dim A
# of holes - 35
1.0625
Diameter
2” (50mm)
3” (80mm)
4” (100mm)
6” (150mm)
8” (200mm)
Dim A
3.93
5.31
6.26
8.50
10.62
Dim B
.28
.43
.55
.78
1.02
Dim C
2.14
3.24
4.22
6.07
7.98
Part # Each
14382
14383
14384
14385
14386
PRE-CUT GASKETS
Pre-cut ⅛” gaskets for use with class 300
raised face flanges. Gaskets are suitable for
use with water, inert gases and saturated
steam up to 150 psig. For saturated steam
applications above 150 psig, contact ONICON
for assistance.
Diameter
Part # Each
½” (15mm)
18830
¾” (20mm)
18831
1” (25mm)
16811
1½” (40mm)
16812
2” (50mm)
16813
3” (80mm)
16814
4” (100mm)
16815
6” (150mm)
16816
8” (200mm)
16817
PRESSURE TRANSDUCER OPTIONS
Full Scale Operating
Pressure
Maximum Overrange
Pressure
PSIa
PSIa
30
60
100
200
300
600
500
1000
1500
2500
11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • sales@onicon.com
F-2600 Series Inline Vortex Flow Meter Catalog Sheet 05/14 - 0775-8 / 22154
Page
8
• F-5200 SERIES •
THERMAL MASS
FLOW METER
CALIBRATION
Every ONICON flow meter is wet calibrated in a flow
laboratory against standards that are directly traceable
to N.I.S.T. A certificate of calibration accompanies
every meter.
FEATURES
Made in America
DESCRIPTION
All F-5000 Series Thermal Mass Flow Meters
provide accurate mass flow measurement of
natural gas, compressed air and other industrial
gases. The proprietary sensor design measures
mass flow directly and does not require additional
pressure or temperature compensation to deliver
accurate flow data.
The F-5200 is available as an inline or an insertion
style meter. Both versions require 24 VDC power
and are provided with a single analog 4-20 mA
output and a separate scalable contact closure
pulse output.
APPLICATIONS
•Natural Gas
• Compressed Air
•Other Combustible Gases
•Industrial Gases
GENERAL SPECIFICATIONS
ACCURACY
Natural gas / Propane gas
± 1.0% of reading from 500 – 7000 SFPM
± 2.0 % of reading from 100 – 500 SFPM
Compressed air & other high velocity calibrations
± 1.0 % of reading + 0.5% of scale over a
100:1 turndown
OVERALL FLOW RANGE
5 to 35,000 SFPM
SENSING METHOD
Thermal mass flow utilizing hybrid analog/digital
sensing circuitry
PIPE SIZE RANGE
Insertion style - 1” through 24” nominal diameter
Inline style - ¼” through 4” nominal diameter
INPUT POWER
Standard
24 VDC ±10%, 100 mA maximum current
0765-3 / 19856
Excellent Long Term Reliability ONICON thermal mass flow meters employ a low
maintenance, non-moving parts technology to sense
flow and are generally unaffected by debris in the
flow stream.
Highly Accurate Over A Wide Operating Range Our proprietary hybrid analog/digital sensing circuitry is very stable and yet highly responsive to
changes in flow. This stable yet responsive design
allows for accurate flow measurement over a very
wide operating range (over 1000:1 for the inline
version). It also makes the meter ideal for measuring
low flow rates.
Inline Meters Are Provided With Built-in Flow
Conditioners - Flow conditioners are built in to all ½” through
4” diameter inline meters. The flow conditioner
significantly reduces overall straight run requirements for installation.
Insertion Meters Can Be Installed Without Interrupting
Gas Service* ONICON’s hot tap design allows for installation
without interruption to the gas service. The meter can
also be removed for service without disrupting flow.
Excellent Value ONICON insertion style meters are accurate,
easy-to-use and reliable. They are also priced independently of pipe size. This makes them an excellent value, particularly in larger diameter pipes.
* See note on next page.
The optional D-100 Flow
Display provides a local
indication of rate and
total and a network
interface for BACnet,
MODBUS, LonWorks,
JCI - N2, or
Siemens - P1 FLN
networks.
1500 North Belcher Road, Clearwater, FL 33765 • Tel (727) 447-6140 • Fax (727) 442-5699
www.onicon.com • sales@onicon.com
06-13
GENERAL SPECIFICATIONS (cont.)
FLUID TEMPERATURE RANGE
-40° F to +150° F standard (Consult ONICON for other operating ranges.)
AMBIENT TEMPERATURE RANGE
0° F to 150° F
Wire
Color
OPERATING PRESSURE
250 PSI Maximum (Consult ONICON when higher
Red
pressure ratings are required.)
PRESSURE DROP (@ 2500 SFPM, 70° F and 2 PSIG)
Black
Insertion Meter - Less than 0.5” W.C. (H20) in 1½” diameter pipes, decreasing in larger pipes
Inline Meter - (with built-in flow conditioner)
Blue
Less than 0.5” W.C (H20) in 2” and larger diameter meters
Brown
Less than 0.9” W.C (H20) in 1” and 1½” diameter meters
PROGRAMMING / MEMORY
Factory programmed for specific application.
Non-volatile memory retains all program parameters and White
totalized values in the event of power loss.
OUTPUT SIGNALS PROVIDED
Orange
Analog output:
Standard: 4-20 mA, active (internally powered)
Optional: 4-20 mA, passive (externally powered)
Scalable pulse output: Isolated contact closure output
500ms duration
MATERIAL
Wetted metal components: 316 stainless steel
ELECTRONICS ENCLOSURE
Integral mount, weathertight NEMA 4
aluminum enclosure
ELECTRICAL CONNECTIONS
10 ft multi-conductor cable with a ½“ NPT conduit connection
4-wire minimum for power and 4-20 mA output
2 additional wires required for scaled pulse output
*Installations must comply with federal, state and municipal
building codes. Review all proposed combustible gas installations
with your local code enforcement officials before attempting any
installation.
NOTE: Specifications are subject to change w
ithout notice.
0765-3 / 19856
ELECTRICAL CONNECTIONS
Description
Notes
+24 ±10% VDC @ 100
mA
Connect to power supply
positive
Supply common
Connect to power supply
negative
Analog Output (Active)
(+) Isolated analog
output
Analog output signal
(-) Analog output
common
Analog output common
Scaled Output
Scaled output, isolated
dry contact, 50 VDC
@100 mA maximum
Non-polarized contact
closure output
Scaled output, isolated
dry contact, 50 VDC
@100 mA maximum
Non-polarized contact
closure output
Operating range for common pipe sizes
5 to 7000 SFPM in schedule 40 pipe
Pipe Size
in inches
Flow Rate in SCFH
Min
Max
¼
0.2
304
⅜
0.4
557
½
0.6
886
¾
1.1
1,560
1
1.8
2,521
1¼
3.1
4,362
1½
4.2
5,938
2
7.0
9,740
2½
10
13,964
3
15
21,562
4
27
37,130
5
42
58,350
6
60
84,263
8
104
145,912
1500 North Belcher Road, Clearwater, FL 33765 • Tel (727) 447-6140 • Fax (727) 442-5699
www.onicon.com • sales@onicon.com
06-13
F-5200 TYPICAL INSERTION METER INSTALLATION
Customer provided
conduit and adapters
• Acceptable to install in vertical pipe
½” FNPT
conduit connection
Output signal(s)
to control system
• Position meter anywhere in upper 180°
for horizontal pipe
Optional
ONICON
Display
FLOW DIRECTION
Installation kit
for steel pipe
(Standard or hot tap):
Compression fitting
¾” x ½” Reducing bushing
Allow enough slack in
the flexible conduit to
permit the meter to be
removed from the valve.
Optional D-100 Display
¾” Full port ball valve
¾” Close nipple
¾” Weld-on branch outlet
Minimum hole
size = ⅝”
Must be centered
Available Output Signals:
Pulse, Analog
Serial Network Options:
BACnet, LonWorks, MODBUS,
JCI Metasys N2 and Siemens Apogee FLN
**FLOW
Optional flow conditioner
(See table for requirements.)
F-5200 TYPICAL INLINE METER INSTALLATION
Customer provided
conduit and adapters.
Output signal(s)
to control system
CLEARANCE
REQUIRED FOR
INSTALLATION
Typically
30” - 36”
depending on
pipe size and
height of
valve assembly.
• Acceptable to install in vertical pipe
• Position meter anywhere in upper 180°
for horizontal pipe
½” FNPT
conduit connection
Optional
ONICON
Display
FLOW DIRECTION
Built-in flow conditioner
** FLOW
Optional D-100 Display
Available Output Signals:
Pulse, Analog
Serial Network Options:
BACnet, LonWorks, MODBUS,
JCI Metasys N2 and Siemens Apogee FLN
Customer provided
NPT couplings
NOTE: Flanged version also available.
** Standard orientation. Contact ONICON for other options.
0765-3 / 19856
1500 North Belcher Road, Clearwater, FL 33765 • Tel (727) 447-6140 • Fax (727) 442-5699
www.onicon.com • sales@onicon.com
06-13
ORDERING INFORMATION
F-5200 Thermal Mass Model # Codification F-52AA-1BCD-EFF
F-52 = Thermal Mass Flow Meter With Display, 4 - 20 mA & Scaled Pulse Outputs
AA = Pipe Diameter
D = Process Connections
00 = Insertion
13 = 1¼”
0 = Insertion
14 = ¼”
15 = 1½”
1 = Threaded MNPT Connections
38 = ⅜”
02 = 2”
2 = ANSI Class 150 Flange
12 = ½”
25 = 2½”
3 = ANSI Class 300 Flange
34 = ¾”
03 = 3”
01 = 1”
04 = 4”
E = Flow Conditioner
1 = Insertion meter without conditioner
B = Line Voltage
2 = Insertion meter with conditioner
1 = 24 VDC
3 = Inline meter
C = Integral or Remote Mount
1 = Integral
FF = Gas Type
NG = Natural Gas
O2 = Oxygen Gas
ME = Methane Gas
DA = Duct / Flue Air
PG = Propane Gas
HE = Helium Gas
CA = Compressed Air
NI = Nitrogen Gas
CD = Carbon Dioxide
XX = Other Gases
F-5200 Thermal Mass Meter Accessory Ordering Information
(F-5200 are limited to 150o F maximum temperature and 250 PSI maximum pressure.)
Item #
Accessory Item Description
Install kits for carbon steel pipe
INSTL64
Installation kit for welded carbon steel pipe, 50 PSIG, 200° F max
INSTL69
Stainless steel installation kit for welded carbon steel pipe, 50 PSIG, 200° F max
INSTL70
Installation kit for welded carbon steel pipe, 500 PSIG, 140° F max
Install kit for stainless steel pipe
INSTL82
Stainless steel installation kit for welded stainless steel pipe, 0 PSIG, 140° F max
Compression Fitting
INSTL91
0765-3 / 19856
Insertion meter compression fitting w/o installation hardware, 125psig/140° F max
1500 North Belcher Road, Clearwater, FL 33765 • Tel (727) 447-6140 • Fax (727) 442-5699
www.onicon.com • sales@onicon.com
06-13
• D-100 FLOW DISPLAY •
WITH NETWORK INTERFACE
DESCRIPTION
The D-100 is a totalizing display module that provides
a local indication of liquid or steam flow rate and total
data. The flexible design can also be configured with
an optional network interface to communicate flow
data to the building control network. It is housed in a
steel wall mounted enclosure with a built-in user
interface/display. The standard flow input accepts
4-20 mA, pulse or contact closure flow signals. The
versatile D-100 can also function as a network
interface for 2 additional analog rate inputs and one
additional totalizing pulse input. It can also be
configured with up to 4 optional analog outputs.
APPLICATIONS
FEATURES
Works With Virtually Any Flow Meter The standard flow input of the D-100 accepts active or
passive 4 – 20 mA, active or passive pulse and contact
closure flow signals.
Serial Communications Optional communications card provides all rate and
total data to the control system through a single
network connection, reducing installation costs.
Supports a Wide Variety of Communications Protocols The D-100 can be provided with any of the following
network interface options:
•BACnet/IP
•
BACnet MS/TP
• LONWORKS FTT10
•
MODBUS RTU-RS485
•
MODBUS RTU-TCP/IP
•Johnson Controls Metasys N2
• Siemens Apogee P1
Suitable for Bi-directional Applications The D-100 accumulates separate totals for flow in
each direction. The totals may be read locally on the
display or remotely via an optional network interface.
Simple Installation and Commissioning The D-100 is factory programmed and ready for use
upon delivery. All programming functions are
accessible via front panel display and keypad.
•HVAC chilled water, condenser water and hot water
•Hot and cold domestic water
•Gray water and irrigation water
•Saturated or superheated steam
•Process monitoring
GENERAL SPECIFICATIONS
Accuracy
Analog inputs: 0.1% of full scale
Analog outputs: 0.1% of full scale
Mechanical
Electronics Enclosure:
Standard: steel NEMA 13 wall mount
10” x 8” x 4”
Optional: steel NEMA 4 wall mount 10” x 8” x 4”
Electrical
Input power:
Standard: 24VAC 50/60Hz, 500mA max
Optional: 120VAC 60Hz, 250mA max
Optional: 230VAC 50Hz, 125mA max
Internal power supply
Provides 24VDC, 250mA maximum to electronics
and sensors
Display
Standard: 2-line Alphanumeric LCD displays flow
rate and flow total
Alpha: 16 character, 0.2” high, Numeric 7 digit, 0.4”
high
PROCESS CONTROL EQUIPMENT
3GF5
0604-6
11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699
www.onicon.com • sales@onicon.com
05-14
Programming
Factory programmed for specific application
Field programmable via front panel interface
Memory
Non-volatile EEPROM memory retains all program
parameters and totalized values in the event of
power loss.
Output Signals
Pulse Outputs:
(2) isolated contact closure outputs for separately
totalizing forward and reverse flow from the
standard input
Isolated contact closure output for indicating
flow direction
Contact rating: 100 mA, 50 V
Contact duration: 0.5, 1, 2, or 6 sec
Analog Output Options:
Single isolated analog output
4-20mA, 0-10V or 0-5V outputs
Multiple (4) isolated analog outputs
4-20mA, 0-10V or 0-5V outputs
Serial Communications Options:
MODBUS RTU RS485
MODBUS RTU TCP/IP
BACnet MS/TP
BACnet UDP/IP
LONWORKS FTT10A
Johnson Controls Metasys N2
Siemens P1 FLN
Input Signals
Standard: (1) totalizing flow input 4-20 mA, contact
closure or pulse
(1) contact closure input for flow direction
Optional: (2) *auxiliary analog rate inputs 4-20 mA
(1) auxiliary totalizer input - pulse or
contact closure
Ambient Temperature Range
-20° F to 140° F
ORDERING INFORMATION
Item #
Description
D-100
Standard D-100 without network interface
D-100-RTU
D-100 with MODBUS RTU RS485 interface
D-100-TCP
D-100 with MODBUS RTU TCP/IP interface
D-100-MS/TP
D-100 with BACnet MS/TP interface
D-100-IP
D-100 with BACnet IP interface
D-100-LON
D-100 with LONWORKS FTT10A interface
D-100-N2
D-100 with Johnson Controls Metasys N2 interface
D-100-P1
D-100 with Siemens Apogee FLN interface
Note: Specifications are subject to change without notice.
* Not currently available with LONWORKS serial
communications option.
TYPICAL D-100 INSTALLATION
Flow rate and total data to
Data Acquisition System or
Building Control System
Steam
Building
120VAC or 24VAC
Input Voltage
Domestic Water Supply
0604-6
11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699
www.onicon.com • sales@onicon.com
05-14
• SYSTEM-10-BAC BTU METER •
BACnet MS/TP COMPATIBLE
DESCRIPTION
The System-10 BTU Meter provides highly accurate
thermal energy measurement in chilled water, hot water
and condenser water systems based on signal i nputs
from two matched temperature sensors (included) and
any of ONICON’s insertion or inline flow meters (ordered
separately). The System-10-BAC-MS/TP provides energy
flow and temperature data on a local alphanumeric display
and to the network via the BACnet communications MS/TP
driver. An optional auxiliary input is also available
to totalize pulses from another device and communicates
the total directly to the BACnet MS/TP network.
APPLICATIONS
FEATURES
BACnet Compatible Serial Communications - Provides
complete energy, flow and temperature data to the
control system through a single BACnet MS/TP
network connection, reducing installation costs.
Simple Installation and Commissioning - Factory
programmed and ready for use upon delivery. All
process data and programming functions are
accessible via front panel display and keypad.
Single Source Responsibility - One manufacturer
is responsible for every aspect of the energy measurement process ensuring component
compatibility and overall system accuracy.
N.I.S.T. Traceable Calibration with Certification Each Btu measurement system is individually
calibrated using application specific flow and
temperature data and is p
rovided with calibration
certifications.
Precision Solid State Temperature Sensors - Custom
calibrated and matched to an accuracy better than
±0.15° F over calibrated range.
Highly Accurate Flow Meters – ONICON offers a
wide variety of insertion and inline type flow
measurement technologies including turbine,
electromagnetic and vortex sensing. Each type offers
unique advantages depending on the application.
All ONICON flow meters are individually wet
calibrated and designed to operate over a wide flow
velocity range with accuracies ranging from ±0.2%
to ±2.0% of rate depending on the model.
Chilled water, hot water and condenser water systems for:
•Commercial office tenant billing
•Central plant monitoring
•University campus monitoring
•Institutional energy cost allocation
•Performance/efficiency evaluations
•Performance contracting energy monitoring
ORDERING INFORMATION
The System-10 BTU Meter is sold complete with
temperature sensors and standard thermowells. Flow
meters are purchased separately.
ITEM #
DESCRIPTION
SYSTEM-10-BAC MS/TP
System-10 BTU Meter BACnet MS/TP
compatible
SYSTEM-10-OPT4
Upgrade to outdoor thermowells (pair)
SYSTEM-10-OPT8
High temperature sensors (over 200°F)
SYSTEM-10-OPT9
Add one analog output
SYSTEM-10-OPT10
Add four analog outputs
SYSTEM-10-OPT11
Auxiliary pulse input
Choose from the following flow meters:
F-1100/F-1200
Insertion Turbine Flow Meter (1 1/4” - 72”)
F-1300
Inline Turbine Flow Meter (3/4” - 1”)
F-2000 Series
Full Bore Vortex Flow Meter
F-3000 Series
Full Bore Electromagnetic Flow Meter
F-3500
Insertion Electromagnetic Flow Meter (3”- 72”)
Refer to catalog for flow meter installation kits.
Consult with ONICON for additional flow meter types.
Complete Installation Package - All mechanical
installation hardware, color coded interconnecting
cabling and installation instructions are provided
to ensure error-free installation and accurate
system performance.
PROCESS CONTROL EQUIPMENT
3GF5
0412-3
1500 North Belcher Road, Clearwater, FL 33765 • Tel (727) 447-6140 • Fax (727) 442-5699
www.onicon.com • sales@onicon.com
07-13
SYSTEM-10 BTU METER SPECIFICATIONS
CALIBRATION
Flow meters and temperature sensors are individually
calibrated followed by a complete system calibration.
Field commissioning is also available.
ACCURACY
Differential temperature accuracy ±0.15° F over
calibrated range
Computing nonlinearity within ±0.05%
PROGRAMMING
Factory programmed for specific application
Field programmable via front panel interface
MEMORY
Non-volatile EEPROM memory retains all program
parameters and totalized values in the event of
power loss.
DISPLAY
Alphanumeric LCD displays total energy, total flow,
energy rate, flow rate, supply temperature and return
temperature.
Alpha: 16 character, 0.2” high; Numeric: 6 digit, 0.4” high
OUTPUT SIGNALS
BACnet MS/TP Points List
Name
BACnet
Object Type
Units
Total Energy
Analog Value
Btu, kW-hrs or ton-hrs
Energy Rate
Analog Input
Btu/hr, kW or tons
Total Flow
Analog Value
gallons, liters or meters3
Flow Rate
Analog Input
gpm, gph, mgd, l/s, l/m, l/hr or m3/hr
Supply Temperature
Analog Input
°F or °C
Return Temperature
Analog Input
°F or °C
Delta-T
Analog Input
°F or °C
Energy Total Reset
Binary Value
Not applicable
Flow Total Reset
Binary Value
Not applicable
Auxiliary Input Total
Analog Value
Pulse Accumulator
Auxiliary Input Reset
Binary Value
Not Applicable
LIQUID FLOW SIGNAL INPUT
0-15 V pulse output from any ONICON flow meter
TEMPERATURE SENSORS
Solid state sensors are custom calibrated using N.I.S.T.
traceable temperature standards.
Current based signal (mA) is unaffected by wire length.
TEMPERATURE RANGE
Liquid temperature range:
32° F to 200° F
Optional liquid temperature range: 122° F to 302° F
Ambient temperature range:
-20° F to 140° F
MECHANICAL
Electronics Enclosure:
Standard: Steel NEMA 13, wall mount, 8”x10”x4”
Optional: NEMA 4 (Not UL listed)
Approximate weight: 12 lbs
Temperature Thermowells:
Standard: 1/2” NPT brass thermowells (length
varies with pipe size) with junction box
Note: 6” pipes and larger require SS thermowell
option.
Optional: • 1/2” NPT stainless steel thermowells
• Outdoor junction box with thermal
insulation
• Hot tap thermowells with isolation
valves are available in plated brass or
stainless steel.
ELECTRICAL
Input Power*:
Standard: 24 VAC, 50/60 Hz, 500 mA
Optional: 120 VAC, 50/60 Hz, 200 mA
230 VAC, 50 Hz, 150 mA
*Based on Btu meters configured for network
connection without the optional analog outputs
Internal Supply:
Provides 24 VDC at 200 mA to electronics and flow meter
Wiring:
Temperature signals: Use 18-22 ga twisted shielded pair.
Flow signals:Use 18 - 22 ga - see flow meter specification
sheet for number of conductors.
Baud Rate: 76,800, 38,400, 19,200 or 9,600 bps
Isolated solid state dry contact for energy total:
Contact rating: 100 mA, 50 V
Contact duration: 0.5, 1, 2, or 6 sec
Optional Analog Output(s): 4-20 mA, 0-10 V or 0-5 V
One or four analog output(s) available for flow rate,
energy rate, supply/return temps, or delta-T.
Note: Specifications are subject to change without notice.
TYPICAL SYSTEM-10-BAC-MS/TP
INSTALLATION
ONICON insertion
flow meter
BTU X 10,000
24 VAC input
Insertion turbine flow meter shown.
Any ONICON flow meter may be
used with the System-10 BTU Meter.
Consult with ONICON for additional
flow meter types.
SCROLL
RESET
PROGRAM
BACnet Communications
to Control System
BACnet/IP
BACnet
MS/TP
SYSTEM-10
BTU METER
POWER
Supply Temp
Sensor
Heat Exchanger
Supply
Return Temp
Sensor
Return
0412-3
1500 North Belcher Road, Clearwater, FL 33765 • Tel (727) 447-6140 • Fax (727) 442-5699
www.onicon.com • sales@onicon.com
07-13
Dell ® Inspiron™ 3000 Series
Documentation Update
T
his document updates information contained in the
Dell Inspiron 3000 Reference and Troubleshooting
Guide.
Microprocessor Options
Hardware Features
Dell Inspiron 3000 series computers now offer the following enhanced features:
•
•
The Dell Inspiron 3000 series portable computer is available with a 200-, 233-, or 266-megahertz (MHz) Intel®
Pentium® microprocessor or a 233- or 266-MHz Intel
Pentium II microprocessor.
All microprocessors used in the Inspiron 3000 series
incorporate MMX™ technology. Current applications not
designed specifically for MMX technology should gain a
slight improvement in performance when run on a system
with a Pentium microprocessor with MMX technology.
Software written specifically to take advantage of MMX
technology (labeled “Designed for Intel MMX”) shows
even greater improvement in performance, depending on
the type of application. In addition, a Pentium microprocessor with MMX technology provides twice the amount
of internal cache memory available with the standard
Pentium microprocessor.
A minimum of 32 megabytes (MB) of synchronous
dynamic random-access memory (SDRAM).
The 32 MB consists of 16 MB of nonremovable
memory on the system board and a 16-MB
3.3-volt (V) memory module in one of the two
memory module sockets on the system board.
Memory on any Inspiron 3000 series computer can
be increased up to 144 MB by installing a combination of 16-, 32-, or 64-MB, 3.3-V memory modules
in the two memory module sockets on the system
board.
•
512 KB of static RAM (SRAM) level 2 (L2) cache
memory.
Cache memory enhances the speed of many microprocessor operations by storing the most recently
accessed contents of system memory.
•
www.dell.com
32 kilobytes (KB) of internal cache memory.
A 12.1-inch super video graphics array (SVGA)
active-matrix color display on the Inspiron
3200 D233ST and on the Inspiron 3000 M200ST
and M233ST; a 13.3-inch extended graphics array
(XGA) active-matrix color display on the
Inspiron 3000 M233XT and M266XT and on the
Inspiron 3200 D233XT and D266XT.
P/N 29530 Rev. A04 May 1998
®
•
An Intel 430TX PCIset system chip set for the
Inspiron 3000 M200ST, M233ST, M233XT, and
M266XT; an Intel 440BX PCIset system chip set for
the Inspiron 3200 D233ST, D233XT, and D266XT.
Physical Specifications
Table 1-1 provides the physical specifications for the
Inspiron 3000 series computers
.
Table 1-1. Dell Inspiron 3000 Series Physical
Specifications
Systems
Specifications
D233ST,
M200ST, and
M233ST
Height: 42 mm (1.65 inches)
Width: 299 mm (11.77 inches)
Depth: 234 mm (9.21 inches)
Weight*: 2.8 kg (6.2 lb)
D233XT,
D266XT,
M233XT, and
M266XT
Height: 51.5 mm (2.03 inches)
Width: 303 mm (11.93 inches)
Depth: 234 mm (9.21 inches)
Weight*: 3.1 kg (6.8 lb)
* The weight for all 3000 series systems includes the
hard-disk drive, diskette drive, battery, and two
PC Card blanks.
NOTE: For the full name of an abbreviation used in this
table, see the Glossary in your online System User’s
Guide.
________________
Information in this document is subject to change without notice.
 1997–1998 Dell Computer Corporation. All rights reserved. Printed in the U.S.A.
Trademarks used in this text: Dell and the DELL logo are registered trademarks and Inspiron is a trademark of Dell Computer Corporation; Intel and Pentium
are registered trademarks and MMX is a trademark of Intel Corporation. Other trademarks and trade names may be used in this document to refer to either
the entities claiming the marks and names or their products. Dell Computer Corporation disclaims any proprietary interest in trademarks and trade names other
than its own.
HL-5450DN
Business Laser Printer
With duplex and networking
for your business
HL-5450DN
High-Speed Laser Printer with Networking and Duplex
The HL-5450DN is a cost ecient, monochrome laser printer that is ideal for busy oces or
small workgroups. It features reliable, fast prinng at up to 40ppm and automac duplex printing for producing professional two-sided documents. It also oers built-in networking for sharing with others, mobile device prinngƑ, and exible paper handling via an adjustable 250-sheet
capacity paper tray and a 50-sheet capacity mul-purpose tray.
Specicaons:
Key Features at a Glance:
Print Technology
Electrophotographic Laser
Paper Size (maximum)
Up to 8.5” x 14” (legal size)
Print Speed (maximum)
Up to 40ppm
Time to First Page
Ÿ
Less than 8.5 seconds
Print Resoluon (maximum)
Up to 1200 x 1200 dpi
Processor
400 MHz
Emulaons
PCL6, BR-Script3Ƈ, IBM Proprinter, Epson FX
Yes
Duplex Prinng Capability
’
Paper Input Capacity (maximum)
250-sheet capacity paper tray, 50-sheet capacity
mul-purpose tray
Oponal Input Capacity (maximum*)’
500-sheet capacity paper tray
Output Capacity (maximum)’
150 sheets (face down), 1 sheet (face up)
Media Types
Plain paper, recycled paper, bond, labels and envelopes
Media Weights
Standard paper tray – 16 to 28 lbs.
Manual feed slot – 16 to 43 lbs.
Print Driver Sengs1
Toner Save, N-in-1 Prinng, Watermark,
Poster Prinng, ID Print, Custom Print Proles,
Booklet Prinng
• Fast prinng up to 40ppm black
• Ethernet and Hi-Speed USB 2.0 interfaces
• Automac duplex (two-sided) prinng
• Wireless prinng from your mobile device viaƑ:
AirPrint™, Google Cloud Print™, Brother™ iPrint&Scan,
Cortado Workplace
• 300-sheet paper capacity, expandable*
• High-yield 8,000-pageź replacement toner cartridge
available*
• Advanced security features including:
Secure funcon lock, Enterprise security (802.1x) and more
• High-quality output at up to 1200 x 1200 dpi
• Toner save mode to help save toner when prinng less
crical business documents
• 1 year limited warranty with toll-free technical support for
the life of your machine
Supplies & Accessories*:
TN-720
Standard Yield Toner (approx. 3,000 pages)ź
Memory (std. / max.*)
64MB/320MB
TN-750
High-Yield Toner (approx. 8,000 pages)ź
Standard Interfaces
Ethernet, Hi-Speed USB 2.0
DR-720
Drum Unit (approx. 30,000 pages)^
Operang Systems Compability
Windows®: Windows®7 / Windows Vista®/ XP /
XP Professional x64 / Server® 2003 / 2008
Mac®: Mac OS X® v10.5.8, v10.6.x, v10.7.x
Linux
LT-5400
Oponal 500-Sheet Capacity Paper Tray
BP60MPLTR
Leer-size Mul Purpose Paper (500 sheets)
Mobile Device Compability Ƒ
AirPrint™, Google Cloud Print™, Brother™ iPrint&Scan,
Cortado Workplace
Warranty
1-year limited warranty
For full technical specications and more information, see www.brother.com
Logiscs Informaon:
UPC Code
012502630791
Unit Dimensions
14.6”W x 15.1”D x 9.6” H
Unit Weight / Carton Weight
23.1 lbs. / 27.3 lbs.
Carton Dimensions
19.6”W x 18.8”D x 15” H
From ready mode and standard tray
PostScript®3™ compatible
Maximum capacity based on using 20 lb. (bond) paper
* Additional purchase required
1 Some advanced features are not supported under all operating systems or drivers. Refer to User’s Guide at www.brother.com
Ƒ Requires connection to a wireless network. See www.brother.com for details, availability, and mobile device compatibility
Approximate toner cartridge yield in accordance with ISO/IEC 19752 (letter/A4)
^ Drum yield is approx., and may vary by type of use
Join BrotherOce
www.brotherearth.com
All trademarks and registered referenced herein are the property of their respecve companies. Windows, Windows Vista, Windows Server and the Windows logo are either registered trademarks or trademarks of Microso Corporaon in the United States and/or other countries. Mac OS, the Mac logo and OS X are trademarks of Apple Inc. AirPrint™ and the AirPrint logo are trademarks of Apple Inc. Cortado is a trademark of Cortado AG.
The PCMag.com Readers Choice logo is a trademark of Zi Davis, Inc. Used under license Reprinted with permission. ©2011 Zi Davis, Inc. All Rights Reserved. All specicaons subject to change without noce.
07/16/2012
Type 1 & 3R
Enclosures
AB-16166LMMOD
TYPE 1
LARGE NEMA 1 O.E.M. CABINET
Austin Large O.E.M. enclosures are Underwriters Laboratories Listed and designed for housing electrical
and electronic controls.
Construction:
• Fabricated in accordance
with UL specifications from
code gauge steel.
AB-16
LATCH
• Removable mounting panel.
• Continuous hinge.
• Enclosures have an AB-16
flush latch except as noted.
Finish:
Austin Large O.E.M. enclosures
are provided standard with an
ANSI 61 gray polyester powder
coating. Panels are painted white.
B-3.00
A-3.00
A
.75
OMIT CENTER STUDS
IF "A" IS LESS THAN 31"
Options:
.88
• Special materials.
.88
• Special finishes.
B
• Custom box size or construction.
FRONT VIEW w/DOOR & HINGE REMOVED
C
1.00
INDUSTRY
STANDARDS
UL 50 Type 1
NEMA Type 1
CUL Type 1
Austin Electrical Enclosures
Post Office Box 2320
Yadkinville, NC 27055
Phone: 336.468.2851
800.288.2851
Type 1 & 3R
Enclosures
LARGE O.E.M. CABINET
ENCLOSURES WITH PANELS
Catalog
Number
Enclosure
Size (AxBxC)
Weight
AB-16126LM
AB-16166LM
AB-20166LM
AB-24166LM
AB-20206LM
AB-24206LM
AB-24246LM
AB-30246LM
AB-36246LM
AB-36306LM*
16x12x6 5/8
16x16x6 5/8
20x16x6 5/8
24x16x6 5/8
20x20x6 5/8
24x20x6 5/8
24x24x6 5/8
30x24x6 5/8
36x24x6 5/8
36x30x6 5/8
21
27
31
36
37
43
56
67
78
95
AB-16128LM
AB-20168LM
AB-20208LM
AB-24208LM
AB-24248LM
AB-30248LM
AB-36248LM
AB-36308LM*
16x12x8 5/8
20x16x8 5/8
20x20x8 5/8
24x20x8 5/8
24x24x8 5/8
30x24x8 5/8
36x24x8 5/8
36x30x8 5/8
23
35
40
48
58
74
81
104
AB-242010LM
AB-302410LM
AB-363010LM*
24x20x10 5/8
30x24x10 5/8
36x30x10 5/8
53
81
114
AB-242412LM
AB-363012LM*
24x24x12 5/8
36x30x12 5/8
69
123
*NOTE:
If "A" and "B" are 36 x 30, an AB-10
tee handle is standard
Austin Electrical Enclosures
Post Office Box 2320
Yadkinville, NC 27055
Phone: 336.468.2851
800.288.2851
13
Type 1 & 3R
Enclosures
AB-24206LMMOD
TYPE 1
LARGE NEMA 1 O.E.M. CABINET
Austin Large O.E.M. enclosures are Underwriters Laboratories Listed and designed for housing electrical
and electronic controls.
Construction:
• Fabricated in accordance
with UL specifications from
code gauge steel.
AB-16
LATCH
• Removable mounting panel.
• Continuous hinge.
• Enclosures have an AB-16
flush latch except as noted.
Finish:
Austin Large O.E.M. enclosures
are provided standard with an
ANSI 61 gray polyester powder
coating. Panels are painted white.
B-3.00
A-3.00
A
.75
OMIT CENTER STUDS
IF "A" IS LESS THAN 31"
Options:
.88
• Special materials.
.88
• Special finishes.
B
• Custom box size or construction.
FRONT VIEW w/DOOR & HINGE REMOVED
C
1.00
INDUSTRY
STANDARDS
UL 50 Type 1
NEMA Type 1
CUL Type 1
Austin Electrical Enclosures
Post Office Box 2320
Yadkinville, NC 27055
Phone: 336.468.2851
800.288.2851
Type 1 & 3R
Enclosures
LARGE O.E.M. CABINET
ENCLOSURES WITH PANELS
Catalog
Number
Enclosure
Size (AxBxC)
Weight
AB-16126LM
AB-16166LM
AB-20166LM
AB-24166LM
AB-20206LM
AB-24206LM
AB-24246LM
AB-30246LM
AB-36246LM
AB-36306LM*
16x12x6 5/8
16x16x6 5/8
20x16x6 5/8
24x16x6 5/8
20x20x6 5/8
24x20x6 5/8
24x24x6 5/8
30x24x6 5/8
36x24x6 5/8
36x30x6 5/8
21
27
31
36
37
43
56
67
78
95
AB-16128LM
AB-20168LM
AB-20208LM
AB-24208LM
AB-24248LM
AB-30248LM
AB-36248LM
AB-36308LM*
16x12x8 5/8
20x16x8 5/8
20x20x8 5/8
24x20x8 5/8
24x24x8 5/8
30x24x8 5/8
36x24x8 5/8
36x30x8 5/8
23
35
40
48
58
74
81
104
AB-242010LM
AB-302410LM
AB-363010LM*
24x20x10 5/8
30x24x10 5/8
36x30x10 5/8
53
81
114
AB-242412LM
AB-363012LM*
24x24x12 5/8
36x30x12 5/8
69
123
*NOTE:
If "A" and "B" are 36 x 30, an AB-10
tee handle is standard
Austin Electrical Enclosures
Post Office Box 2320
Yadkinville, NC 27055
Phone: 336.468.2851
800.288.2851
13
ProtoCom Protocol Gateway
Easily Convert Shark® or Nexus® Meters to BACnet® and LonWorks®
The ProtoCom is a one-stop solution to building automation.
It allows any integrator to easily provide power metering data
to any building automation system (BAS) that uses BACnet® or
LonWorks® protocols. Using this converter, a user can easily
convert power metering data from Electro Industries (EIG)’s
native Modbus® protocol to the desired format quickly and
easily without complex integration.
The converter communicates with host meters using RS485
Modbus protocol and provides the output via BACnet MS/TP
or BACnet /IP. The LonWorks® version will provide the
output via a LonWorks® interface. All configuration files for all
supported EIG meters have been pre-loaded and pretested.
System setup and configuration is easily accomplished using
the built-in graphical user interface. There is no need for client
setup software. All settings can be password protected from
tampering. The ProtoCom converter is ideal for developing a
comprehensive building management and LEED initiative.
®
BACnet Building Management System
HVAC
Security
Systems
Fire
Systems
ProtoCom
ProtoCom
ProtoCom-Lon
BACnet® Gateway
Lonworks® Gateway
Plug and Play – Connects to Meter’s RS485 Port with
Almost No User Configuration
Auto-discovery Detects the Connected Meter and
www.electroind.com
Measuring Office #2
Measuring Incoming
from Utility
Measuring Office #1
Maps Appropriate BACnet® or Lon Works® Points
Automatically
Enables BACnet MS/TP, BACnet/IP, LonWorks®, and
other Popular Building Management Systems
®
Shark 200 Meter
®
Shark 200 Meter
®
Nexus 1500 Meter
Perfect Add-on for Any Building Management Solution
Retrofits to Existing Meters, Saving Installation Time
and Money
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
One ProtoCom can accept multiple connections to multiple
types of supported EIG meters. Supported meters include:
Shark® 100, Shark® 200, Shark® 200S Meters
Shark® Meter in Enclosure
MP200-Y/MP200-S Metering System
MP200 Metering System in Enclosure
Nexus® 1252, Nexus® 1262, Nexus® 1272,
Nexus® 1500 Meters
DMMS 425 Meter
Dimensions: shown in inches[cm]
The protocols available for each Converter are:
ProtoCom - enables BACnet MS/TP, BACnet/IP,
Johnson Controls’ Metasys N2® , Allen-Bradley®
EtherNet/IP, Allen-Bradley® DF1
ProtoCom-Lon - enables LonWorks®
With the ProtoCom or ProtoCom-Lon your Shark®
and Nexus® meter data is available directly to the
most widely used BAS protocols worldwide.
Specifications
Power Requirements (Power Supply included)
Power: 9-30 VDC or 12-24 VAC
Current draw @ 12V
ProtoCom @ 12V = 240 mA
ProtoCom-Lon @ 12V = 250 mA
Environmental
o
o
o
o
Operating Temp.: -40 F to 167 F (-40 C to 75 C)
Relative Humidity: 5-90% RH, non-condensing
Approvals
• LonMark 3.4 Certified – ProtoCom-Lon model
• TUV approved to UL 916 standard and CSA C22-2
• RoHS Compliant
• OPC Self Certified to Compliance
• CE & FCC Approved
4.52 [114.91]
BACnet Support
• BACnet COV’s
• Supports up to 1,500 Host & Field points
• DIP switches are used to set MAC Address, Node-ID,
Baud Rate on the RS485 Field protocol
LonMark Certification on the ProtoCom-Lon
• SPID: 80:00:95:46:00:84:04:07
To Order
Model Number
ProtoCom-KT
*ProtoCom Kit
ProtoCom-Lon-KT
*ProtoCom-Lon Kit
*Kits include the Converter, a 3 foot RS485 cable and a
120/220V to 24VDC Power Supply
®
Metasys is a registered trademark of Johnson Controls, Inc.
®
LonWorks is a registered trademark of Echelon Corp.
®
BACnet is a registered trademark of ASHRAE.
®
Modbus is a registered trademark of Schneider Electric, licensed to
the Modus Organization, Inc.
®
®
Shark and Nexus are registered trademarks of Electro
Industries/GaugeTech.
®
Allen-Bradley is a registered trademark of Rockwell Automation, Inc.
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
1800 Shames Drive • Westbury, NY 11590
Tel : 516-334-0870 • Fax : 516-338-4741
E204702 040214 V.1.01
Email : sales@electroind.com
Website : www.electroind.com
Energy Dashboard, Energy
Reporting, and Cost Analysis Software
www.electroind.com
Version 4.0
Software That is Easy to Use
and Auto-Configuring
• View and Create Energy Dashboards and
Reports
• Analyze Detailed Usage Data for Planning
and Load Curtailment
• Accurately Bill Customers/Tenants
for Usage
• Improve Operational Efficiency and Change
Energy Usage Behavior
• Reduce Energy Costs by System-wide
Energy Consumption Analysis
• Verify and Quantify Energy Savings
throughout Any Enterprise
• Automatically Import Energy Data from EIG
Meters
The Energy Usage Analysis Tool to
Manage Energy
• Control Costs by Providing Tenant Ownership of His/Her Energy
Consumption
• Determine Inefficiencies and Reduce Energy Demand
• View Dashboard Data to Compare Usage over Time
• Provide Automated Reporting to Detail Savings Opportunities
Managing Energy and Commodity
Usage Has Never Been Easier!
The EnergyReporter EXT application runs in a client/server environment
- data stored on the database server can be accessed from all configured
client PCs to support an Enterprise-wide energy management solution.
Or if it works better for your purposes, install the application and the
database server on the same PC. This is a user-owned software system; it
does not run on a subscription model, so there are no recurring
monthly fees.
• View Consumption of All Usage Commodities, Including Water,
Air, Gas, and Steam
• View Loads vs. Weather Locations over Time
• Meter Virtually Unlimited Amounts of Energy Points
Allocate Accurate and Fair Energy Usage - Use EIG’s
EnergyReporter EXT application to correctly allocate costs across
customer locations and realize almost immediate energy savings. This
fully customizable software application was designed for use with EIG’s
Shark® 200 and 200S meters, the MP200 Metering System, and
all Nexus® Series meters.
Client/Server Architecture Allows for Remote Access
from Any Computer
Energy Dashboard, Charting,
and Benchmarking
• Cost by Month
• Cost by Day
• Energy Usage
Comparisons
• Top Peak Demand by Date
or Meter
• Compare Facility Usage to
Ambient Temperature
• Top Peak Demand
Real Energy Cost by Day
• View Facility Comparisons
• Compare Usage to Previous Periods of Time
• Compare Electricity and Other Commodities
• Validate Energy Savings and Efficiency
• Comply with Local Energy Codes
2
View Usage over Time
Executive Summary Usage Reports
Report on System-wide Energy Usage
Create custom reports to provide executives and management with
analysis of every aspect of energy consumption. Configure the reports
to provide the exact data the executive needs to make the proper energy
decisions. Using the EnergyReporter EXT application, reducing costs and
pinpointing energy waste is easily achievable. Report capabilities include:
• Monthly Usage Summaries
• Comparisons to Last Year
• Monthly Meter
Comparisons
• Report on Weather and
Temperature Impact on
Usage and Peak Demand
• Meter Specific Energy
Profile
• Peak Day Profile
• Peak Week Profile
• Average Hourly Usage
View Average Hourly
and Daily Usage with
Max Demand
Provide Monthly Usage
and Peak Demand
• Average Daily Usage
• Comparisons to Last Month
Automated Energy Billing Module
The EnergyReporter EXT application automatically provides bills to users
if desired. It creates customized bills based on tariffed rate structure. The
features include:
Customize bill with your company logo
Customer
and Bill
Information
Add Fixed
Charges
Different rate
structures for
different
seasons,
Peak, and
Off-Peak,
holidays
Totalized
Usage
Comparison to previous
months’usage
Add Local
Taxes
• Automated Bill Generation
• Provides Fair Usage Billing
• 4 Season TOU Rates
• Uncovers Account
Ownership Errors
• Supports Fixed, Tiered or
TOU Rates
• Customized Bill Formats
• Allowances for Fixed Costs
and Taxes
• Ability to Bill for Energy
and Other Commodities
• Provides Fast ROI
by Incentivizing Users
to Conserve
3
Automatic Report and Bill
Email Engine
• Generate Hundreds of Automated Bills or Energy Reports
• Configure the System to Send Bills to Users Automatically
on a Monthly Basis
• Provides an Automated Accounting Service, Saving Costs
in Administrative Services
• Eliminates Any Need for Costly Third Party Billing Providers
• Provides Feedback of Successful Transmission for Accounting
Purposes and a cc Address for a Copy to be Sent to a
Report Provider
• Auto-Configuration System Auto-detects Meters and
Collects Data
Recipients Receive Automated Bills and/or Reports and
Can Take Effective Action Quickly
Ordering Information
Software Module
Description
Model Number
Details
EnergyReporter EXT
Automated Billing
EREXT4
Enterprise Energy Usage Reporting
Communicator EXT 4.0
Base Software
COMEXT4
Enterprise Meter Data Retrieval
Software
Note – You must have the Communicator EXT™ 4.0 or higher Professional Version with MeterManager EXT installed to successfully run
EnergyReporter EXT.
History of Electro
Industries/GaugeTech
Founded in 1975 by engineer and inventor Samuel Kagan, Electro
Industries/GaugeTech changed the face of power monitoring with its
first breakthrough innovation: an easy-to-use digital AC power meter.
More than 39 years later, Electro Industries/GaugeTech, the Leader In
Power Monitoring and Smart Grid Solutions, continues to revolutionize
the industry with the highest quality, cutting edge power monitoring and
control technology on the market today. An ISO 9001:2008 certified
company, EIG sets the industry standard for advanced power quality
and reporting, revenue metering and substation data acquisition
and control. EIG’s products can be found on-site at virtually all of
today’s leading manufacturers, industrial giants and utilities.
g
Nexus® and Shark® are registered trademarks of Electro
Industries/GaugeTech. The distinctive shapes, styles
and overall appearance of the Nexus® 1500 meter and
the Shark® meters are trademarks of Electro Industries/
GaugeTech.
HMI EXT™ and Communicator EXT™ are
trademarks of Electro Industries/
GaugeTech.
Electro Industries/GaugeTech
1800 Shames Drive • Westbury, NY 11590
1- 877-EIMETER (1- 877-346-3837)
E-Mail: sales@electroind.com • Tel: 516-334-0870
Web Site: www.electroind.com • Fax: 516-338-4741
E167702 100114 V.1.03