1510 Side Mounted Level Switch General Instructions The SOR® 1510 Level Switch mounts into the side of a vessel. Electric switching action is provided by the float moving a magnet into the field of a hermetically sealed reed switch capsule. The unit may be mounted for either high or low liquid level alarm by rotating the switch rench flats provide for ease of rotation and proper body to the proper position. The body wrench positioning. See decal on housing. Before Installation of the Level Switch: Inspect the unit for any shipment damage. maage. Check for mechanical clearance of the float. Float must move freely without binding throughout its stroke. Use an acceptable thread compound when installing unit to ensure a leak-free fit and to avoid thread galling. To achieve required function, install the unit according to the nameplate instructions shown here. NOTE: If you suspect that a product is defective, contact the factory or the SOR Representative in your area for a return authorization number (RMA). This product should only be installed by trained and competent personnel. THIS SIDE UP N.C. @ HIGH LEVEL Nameplate Position for Low Level Alarm THIS SIDE UP N.C. @ HIGH LEVEL THIS SIDE UP N.C. @ LOW LEVEL THIS SIDE UP N.C. @ LOW LEVEL NC - indicates circuit is closed Nameplate Position for High Level Alarm Table of Contents Design and specifications are subject to change without notice. For latest revision, go to www.SORInc.com Form 451 (04.16) ©SOR Inc. Installation ...................................... 3 SIL Installation Instructions .................. 3 Float Attachment ............................... 3 Dimensions ..................................... 4 Electrical Connection.......................... 5 Special Conditions............................. 5 Wiring for DPDT Relay ........................ 6 ATEX and IECEx Marking Details ............ 6 Declaration of Conformity .................... 7 Troubleshooting ................................ 8 Replacement Parts ............................ 8 Registered Quality System to ISO 9001 1/8 Installation The unit may be mounted in any of the following installation arrangements: 1-1/2” NPT half coupling (No full coupling). 2” NPT full coupling. (Use in conjunction with 2 x 1-1/2” NPT bushing as required.) 2” NPT pipe tee. (Use in conjunction with 2 x 1-1/2” NPT bushing as required.) Optional flanged mounting. Optional chamber mounting. MD Remote Option (includes plundger, 20 foot cable and two crimps.) Screw plunger to the top of unit. Thread the 20’ cable through the hole in plunger and create a 14 inch top loop as shown below. At the bottom of the cable, a second loop can be created as a handle for actuation at the desired length. Linear = mm/inches Drawing 0098636 PLUNGER TOP 14” LOOP REMOTE CABLE CRIMP REMOTE MANUAL CHECK MD OPTION CREATE HANDLE AT DESIRED LENGTH 2/8 Form 451 (04.16) ©SOR Inc. Safety Integrity Level (SIL) Installation Requirements The SOR pressure switches have been evaluated as Type-A safety related hardware. To meet the necessary installation requirements for the SIL system, the following information must be utilized: Proof Test Interval shall be one year. Units may only be installed for use in Low Demand Mode. Products have a HFT (Hardware Fault Tolerance) of 0, and were evaluated in a Form 1538 (03.12) ©2012 SOR Inc. 1oo1 (one out of one) configuration. Float Attachment (Series 1500 with Flange) Place two drops of Loctite 271 inside the threaded hole of the float. Thread the float onto the set screw and hand-tighten. SET SCREW NOTE: Do not remove the set screw as it secures the pivot arm to the shaft. APPLY TWO DROPS LOCTITE 271 INSIDE THREADED HOLE OF FLOAT FLOAT Linear = mm/inches Drawing 0390747 Form 451 (04.16) ©SOR Inc. 3/8 Dimensions Linear = mm/inches Drawing 0390693 MC or MD MANUAL CHECK OPTION MD INCLUDES 20FT LONG CABLE 12.7 0.50 100.9 3.97 BODY 19.1 0.75 1-1/2" NPT(M) PROCESS CONNECTION FLOAT 54.0 2.12 14.3 0.56 WIRE LEADS 457.2 MIN LENGTH 18.00 COLOR CODED AND MARKED 44.5 1.75 WRENCH FLATS 144.5 5.69 69.9 2.75 78.0 3.07 1/2"NPT(F) ELECTRICAL CONNECTION 14685 W 105TH ST LENEXA KS With CK Accessory – ATEX and IECEx dual approved: Linear = mm/inches Drawing 0390760 44.5 WRENCH FLATS 1.75 457.2 MIN LENGTH 18.00 COLOR CODED AND MARKED WIRE LEADS 1-1/2" NPTM PROCESS CONNECTION OR FLANGE MOUNTING (NOT SHOWN) BODY FLOAT 55.6 2.19 14.3 0.56 31.5 1.24 MAX 22.2 WRENCH FLATS 0.87 1/2" NPTF ELECTRICAL CONNECTION 1 53.8 1 2.12 FLOAT TRAVEL 177.8 7.00 79.0 REF 3.11 NOTES: 1. ACTUATE / DEACTUATE POINTS VARY. OPERATES 56.4 SATISFACTORILY IN 2" FULL COUPLING ( ID) 2.22 Dimensions are for reference only. Contact the factory for certified drawings for a particular model number. 4/8 Form 451 (04.16) ©SOR Inc. Electrical Connection Ensure that the wiring conforms to all applicable local and national electrical codes and install unit(s) according to relevant national and local safety codes. Electrical connection is free wire leads with a 1/2” NPT(F) conduit connection. Use two wrenches — one to hold the hex conduit connection, the other to tighten conduit fitting. Switching element is a hermetically sealed reed switch. SPST Reed Switch Capsule Normally Open White Lead Common Black Lead SPDT Reed Switch Capsule Common Black Lead Normally Closed White Lead Do not exceed catalog stated electrical ratings. Improper current input to switch will cause permanent damage to contacts. Normally Open Blue Lead Special Conditions for Safe Use This apparatus may have a combined nameplate which carries multiple approvals (intrinsically safe and flameproof). The equipment should be marked as to which protection method it is installed as and shall not be changed or utilized in any other means than was originally marked by the end user. When marked and installed as Ex i equipment, the permanently attached leads must be suitably protected against mechanical damage and terminated in a suitable junction box or terminal facility having a degree of protection at least IP20. When marked and installed as Ex d equipment, the permanently attached leads must be suitably protected against mechanical damage and terminated in a suitable junction box or terminal facility. Form 451 (04.16) ©SOR Inc. 5/8 Wiring for DPDT Relay For Type 1510 Level Switches equipped with DPDT relays, a wiring schematic and pin position schematic is shown below. When the 1510 is actuated, the coil will energize and “make” both NO1 and NO2 while it will “break” NC1 and NC2. This provides a DPDT circuit. Switch Capsule Black Lead White Lead 8 C2 NC 2 NO 2 5 6 1 C1 NC 1 NO 1 4 3 2 1 C1 8 7 C2 2 Power Supply Relay Coil 3 NO 1 7 4 NC 1 5 NC 2 6 NO 2 ATEX and IECEx Marking Details For ATEX and IECEx Certified Models Manufacturer’s Registered Trademark Drawing 0720554 ATEX Listing Information Product Type Identification Product Model Identification Standards Assessed To ATEX Certification: EN 60079-0: 2009 & EN 60079-11: 2007 EN 60079-0: 2012, EN 60079-1: 2007, EN 60079-11: 2012 & EN 60079-26: 2007 IECEx Certification: IEC 60079-0: 2011, IEC 60079-1: 2007-04, IEC 60079-11: 2011 & IEC 60079-25: 2010-02 IEC 60079-0: 2004 & IEC 60079-11: 1999 6/8 Form 451 (04.16) ©SOR Inc. Declaration of Conformity For ATEX Certified Models EC Declaration of Conformity Product Type 1500 Electric Switches Manufacturer SOR Inc., 14685 West 105th Street, Lene xa, Kansas 66215-2003 5NITED3TATESOF!MERICA Date of Issue April 20, 2016 We declare that the above products conform to the following specifications and directives Carries the Marking !4%8$IRECTIVE%5%QUIPMEN T)NTENDEDFORUSE IN0OTENTIALLY%XPLOSIVE!TMOSPHERES %.%. )%#)%# %.% . %.%. )%#)%# )%#)%# !4%8-ARKING )%#%X-ARKING II 1 G Ex ia IIC Ga 4²#d4Ad²#OR 4²#4A²# 4²#d4Ad²#OR 4²#4A²# II 2 G Ex d IIC Ga/Gb Reference Documents ATEX Notified Body Person Responsible Ex ia IIC Ga 4²#d4Ad²#OR 4²#4A²# Ex d IIC Ga/Gb 4²#d4Ad²#OR 4²#4A²# EC-Type Examination Certificate Baseefa06ATEX0271X, IECEx BAS 06.0063X )SSUED*ANUARY Baseefa13ATEX0056X, IECEx BAS 13.0035X )SSUED*ULY SGS Baseefa Ltd..OTIlED"ODY.O 2OCKHEAD"USINESS0ARK3TADEN,ANE "UXTON$ERBYSHIRE3+2 :5NITED+ INGDOM "ASEEFA#USTOMER2EFERENCE.O -ICHAEL*"EQUETTE60OF%NGINEERING -ICHAEL*"EQUETTE Engineered to Order with Off -the-Shelf Speed 14685 West 105th Street, Lenexa, KS 66215-2003 s53!s &!8 Form 1385 (04.16) SOR Inc. Form 451 (04.16) ©SOR Inc. 7/8 Troubleshooting Symptom Probable Cause Float in actuated position but no output signal. No power supply. Switch damaged. (Replace.) Float in de-actuated position but still receiving an output signal. Switch damaged. (Replace.) Control will not function when installed but operates when removed from process connection. Inadequate float travel. Float travel restricted by mounting nozzle. See Mounting Requirements. Liquid in vessel at the actuation level but unit does not respond. Leaky or collapsed float. (Replace.) Liquid specific gravity too low. Float stem bound up or dirty. (Clean.) Replacement Parts Part Number Description 3130-052 316SS Float Assembly 3130-091 W9 - SPST Hermetically Sealed Switch Capsule 3130-245 W1 - SPDT Hermetically Sealed Switch Capsule 3130-259 W1 - SPDT Switch/Conduit Connection Assembly (CK Option Only) 3130-107 L9 - SPST Hermetically Sealed Switch Capsule 3130-244 L1 - SPDT Hermetically Sealed Switch Capsule 3130-260 L1 - SPDT Switch/Conduit Connection Assembly (CK Option Only) 9227-028 MC Manual Check Assembly for 1 1/2” NPT Body* 9227-029 MD Manual Check Assembly for 1 1/2” NPT Body* 9227-024 MC Manual Check Assembly for 2” NPT Body* 9227-025 MD Manual Check Assembly for 2” NPT Body* 3130-040 20’ Remote Cable with two cable crimps, for use with MC or MD accessory only. * Unit must have originally been supplied with MC or MD option. SORInc.com 14685 West 105th Street, Lenexa, KS 66215 913-888-2630 800-676-6794 USA Fax 913-888-0767 8/8 Registered Quality System to ISO 9001 Form 451 (04.16) ©SOR Inc.