Mircom FH-240 NOTIFICATION APPLIANCES

advertisement
NOTIFICATION APPLIANCES
Mircom FH-240
Select-A-Horn Series
Features
•
Meets or exceeds NFPA/ANSI Standards and
ADA Accessibility Guidelines
•
UL/ULC listed for wall mounting
•
Screw terminal capacity up to 12 AWG
•
Universal mounting plate included
•
24VDC with two field selectable settings
•
Polarized with wide listed voltage ranges using
filtered DC or unfiltered FWR input voltage
•
Horn field selectable tones:
- 3000 Hz interrupted or Electro-mechanical
- Temporal or Non-temporal
- High or Low dBA output
All models mount to 4 inch square, single gang,
double gang or octagonal backbox
•
Description
The FH-240 Select-A-Horn Series is designed to comply
with NFPA/ANSI audible emergency evacuations signal
and UL 464 audible signaling appliances. The Horn
provides two different field selectable tones, and a
High/Low output setting that can be achieved with the
use of mini jumpers located on back of the unit.
•
Synchronization requires an SDM-240 Sync
Module
•
Available in red or white housing
Jumper Settings
These appliances are polarized for connecting to
supervised fire alarm circuits. The FH-240 can be
synchronized by using the SDM-240 Sync Module
to comply with NFPA recommendations concerning
photosensitive epilepsy when installing 2 or more visual
appliances within the field of view. The strobe signals
are listed for indoor use, wall mount, under UL 1971
standard.
PC3 PC2 PC1
Back of FH-240
Engineering Specifications
Tone Selection
Jum per
The audible alarm indicating appliance shall be a model
FH-240 or equivalent device. The Horn shall be listed
under UL 464 Standard for audible signaling appliance
and shall be approved for fire protective service. The
sound output shall be field selectable. The Horn shall
provide two different field selectable tones and a
High and Low field selectable sound output setting.
The signaling Horn shall operate on 24VDC from a
non-coded regulated DC supply or full-wave rectified,
unfiltered supply. The Horn shall have a universal back
mounting plate, capable of WALL mounting to a back
box. When strobe synchronization is required, the
Horn shall be compatible with the Summit’s SDM-240
sync module. Signaling devices shall be installed in
accordance with current NFPA guideline.
PC3
Pattern
PC2
Tone
PC1
Volume
Non
Temporal
Electro
Mechanical
High
Temporal
3000Hz
Low
S5375
S5375
Issue 1
Page 1 of 2
SUMMIT SYSTEMS TECHNOLOGIES
Canada 25 Interchange Way, Vaughan (Toronto), Ontario L4K 5W3 Telephone: (905) 695-3549 Fax: (905) 660-4113 • Web Page: www.summit-st.net
U.S.A. 4575 Witmer Industrial Estates, Niagara Falls, NY 14305 Telephone: (866) 786-6480 Fax: (888) 660-4113 • E-mail: mail@summit-st.net
Catalog Number 501 • Not to be used for installation purposes.
Dimensions
Specifications
PC3: Pattern
PC2: Tone
PC1: Volume
Horn
Current Draw Table
PC2
PC1
Regulated
24V DC
Regulated
24V FWR
Regulated 24V
DC
1
1
1
57
91
83
3000 Hz
1
1
0
42
44
74
1
0
1
70
68
84
LOW
1
0
0
36
38
74
5
(127)
Front View
HIGH
0
1
1
57
91
79
3-3/8 (85.7)
LOW
0
1
0
42
44
69
1-13/16(46)
HIGH
0
0
1
70
68
80
LOW
0
0
0
36
38
70
Under ULC 525/526
3-3/8(85.7)
Electro
Mechanical
LOW
HIGH
ULC Current @ 24VDC (mA)
Low
15
High
42
1-17/32(39)
Side View
3-9/32(83.5)
Non-Temp
3000 Hz
Temporal
PC3
HIGH
Electro
Mechanical
Min. Sound
Output (dBA @
10ft per UL464)
Max. RMS Operating Current
(mA)
inches (mm)
5 (127)
3-9/32
(83.5)
Back View
Typical Wiring Diagrams
F.A.C.P.
Horn Signal
Circuit
SDM-240 SYNC MODULE
F.A.C.P.
Strobe Signal
Circuit
H
To Next
Device or
End-of-Line
Resistor
Control
Panel
H
INPUT
OUTPUT
To Next
Device or
End-of-Line
Resistor
Refer to Fig. 1
Fig. 1
F.A.C.P.
Signal Circuit
H
SDM-240 SYNC MODULE
INPUT
OUTPUT
To Next
Device or
End-of-Line
Resistor
Refer to Fig. 1
H
IN
OUT
IN
OUT
HORN
Mounting Options
4” Square Back Box
Single Gang Box
FH-240
Universal
Mounting Plate
FH-240
Double Gang Box
Universal
Mounting Plate
FH-240
Universal
Mounting Plate
4BX-1
4SP-M
FH-240
Ordering Information
Model Number
Color
FH-240R
Red
FH-240W
White
Page 2 of 2
Input Voltage
Operating
Voltage Range
Horn
Sound
Output
Wiring
Type
Mounting
Type
Sync
Module
Temperature
Operating
Range
Regulated
24V DC/FWR
16 ~ 33VDC
16 ~ 33VFWR
Selectable
Terminals
Wall or Ceiling
Mount
SDM-240
32°F ~ 120°F
(0°C ~ 49°C)
SUMMIT SYSTEMS TECHNOLOGIES
Catalog Number 501 • Not to be used for installation purposes.
Issue 1
Summit reserves the right to make changes at any time without notice in prices, colors, materials, components, equipment, specifications and models and also to discontinue models.
ISO 9001:2000
REGISTERED
Download