NOTIFICATION APPLIANCES Mircom FH-240 Select-A-Horn Series Features • Meets or exceeds NFPA/ANSI Standards and ADA Accessibility Guidelines • UL/ULC listed for wall mounting • Screw terminal capacity up to 12 AWG • Universal mounting plate included • 24VDC with two field selectable settings • Polarized with wide listed voltage ranges using filtered DC or unfiltered FWR input voltage • Horn field selectable tones: - 3000 Hz interrupted or Electro-mechanical - Temporal or Non-temporal - High or Low dBA output All models mount to 4 inch square, single gang, double gang or octagonal backbox • Description The FH-240 Select-A-Horn Series is designed to comply with NFPA/ANSI audible emergency evacuations signal and UL 464 audible signaling appliances. The Horn provides two different field selectable tones, and a High/Low output setting that can be achieved with the use of mini jumpers located on back of the unit. • Synchronization requires an SDM-240 Sync Module • Available in red or white housing Jumper Settings These appliances are polarized for connecting to supervised fire alarm circuits. The FH-240 can be synchronized by using the SDM-240 Sync Module to comply with NFPA recommendations concerning photosensitive epilepsy when installing 2 or more visual appliances within the field of view. The strobe signals are listed for indoor use, wall mount, under UL 1971 standard. PC3 PC2 PC1 Back of FH-240 Engineering Specifications Tone Selection Jum per The audible alarm indicating appliance shall be a model FH-240 or equivalent device. The Horn shall be listed under UL 464 Standard for audible signaling appliance and shall be approved for fire protective service. The sound output shall be field selectable. The Horn shall provide two different field selectable tones and a High and Low field selectable sound output setting. The signaling Horn shall operate on 24VDC from a non-coded regulated DC supply or full-wave rectified, unfiltered supply. The Horn shall have a universal back mounting plate, capable of WALL mounting to a back box. When strobe synchronization is required, the Horn shall be compatible with the Summit’s SDM-240 sync module. Signaling devices shall be installed in accordance with current NFPA guideline. PC3 Pattern PC2 Tone PC1 Volume Non Temporal Electro Mechanical High Temporal 3000Hz Low S5375 S5375 Issue 1 Page 1 of 2 SUMMIT SYSTEMS TECHNOLOGIES Canada 25 Interchange Way, Vaughan (Toronto), Ontario L4K 5W3 Telephone: (905) 695-3549 Fax: (905) 660-4113 • Web Page: www.summit-st.net U.S.A. 4575 Witmer Industrial Estates, Niagara Falls, NY 14305 Telephone: (866) 786-6480 Fax: (888) 660-4113 • E-mail: mail@summit-st.net Catalog Number 501 • Not to be used for installation purposes. Dimensions Specifications PC3: Pattern PC2: Tone PC1: Volume Horn Current Draw Table PC2 PC1 Regulated 24V DC Regulated 24V FWR Regulated 24V DC 1 1 1 57 91 83 3000 Hz 1 1 0 42 44 74 1 0 1 70 68 84 LOW 1 0 0 36 38 74 5 (127) Front View HIGH 0 1 1 57 91 79 3-3/8 (85.7) LOW 0 1 0 42 44 69 1-13/16(46) HIGH 0 0 1 70 68 80 LOW 0 0 0 36 38 70 Under ULC 525/526 3-3/8(85.7) Electro Mechanical LOW HIGH ULC Current @ 24VDC (mA) Low 15 High 42 1-17/32(39) Side View 3-9/32(83.5) Non-Temp 3000 Hz Temporal PC3 HIGH Electro Mechanical Min. Sound Output (dBA @ 10ft per UL464) Max. RMS Operating Current (mA) inches (mm) 5 (127) 3-9/32 (83.5) Back View Typical Wiring Diagrams F.A.C.P. Horn Signal Circuit SDM-240 SYNC MODULE F.A.C.P. Strobe Signal Circuit H To Next Device or End-of-Line Resistor Control Panel H INPUT OUTPUT To Next Device or End-of-Line Resistor Refer to Fig. 1 Fig. 1 F.A.C.P. Signal Circuit H SDM-240 SYNC MODULE INPUT OUTPUT To Next Device or End-of-Line Resistor Refer to Fig. 1 H IN OUT IN OUT HORN Mounting Options 4” Square Back Box Single Gang Box FH-240 Universal Mounting Plate FH-240 Double Gang Box Universal Mounting Plate FH-240 Universal Mounting Plate 4BX-1 4SP-M FH-240 Ordering Information Model Number Color FH-240R Red FH-240W White Page 2 of 2 Input Voltage Operating Voltage Range Horn Sound Output Wiring Type Mounting Type Sync Module Temperature Operating Range Regulated 24V DC/FWR 16 ~ 33VDC 16 ~ 33VFWR Selectable Terminals Wall or Ceiling Mount SDM-240 32°F ~ 120°F (0°C ~ 49°C) SUMMIT SYSTEMS TECHNOLOGIES Catalog Number 501 • Not to be used for installation purposes. Issue 1 Summit reserves the right to make changes at any time without notice in prices, colors, materials, components, equipment, specifications and models and also to discontinue models. ISO 9001:2000 REGISTERED