WEIDMANN CERTIFIED SmartSpacer® THERMAL MANAGEMENT SYSTEM PURPOSE OF SYSTEM Governed by the IEEE/ANSI or the IEC Loading Guide, the transformer upper loading limit, for normal or emergency operation, is set by the winding hot spot and/or top oil temperature. The upper loading limit may also be defined as a function of the allowed percentage loss of insulation life per operating cycle. Users of power transformers therefore need to understand the actual operating temperatures as a function of load applied to the unit in real time as a way of maximizing the asset value in use and minimizing the risk of overheating, excessive loss of insulation life, and/or failure. The system is designed to monitor and acquire key operating temperatures of the apparatus. The data can be used to control the apparatus cooling systems and unit loading levels. The WEIDMANN real time InsuLogix® T monitoring system may be connected to the user’s local computer network or SCADA system to provide necessary thermal management data to the load dispatch center. ELECTRIC AND DIELECTRIC REQUIREMENTS WEIDMANN Certification for SmartSpacer® products is intended THERMAL REQUIREMENTS ® for use in EHV/UHV Transformer Insulation Systems. SmartSpacer® The SmartSpacer fiber optic probe assembly will read the winding designs can be applied in windings designed for operation up to 800 hottest-spot temperature with a tolerance of plus or minus 2ºC. Typi- kV. The assembly, along with the fiber cable leading in and out of the cal maximum operating hot spot temperature is 120ºC max during assembly, shall be free of any partial discharges in use and not result normal operation and up to 140ºC during loading beyond nameplate. in any increased stress in the adjacent oil or insulation material. The Maximum emergency or contingency loading temperature should not assembly must also be capable of withstanding all required dielectric exceed 180ºC. Measured temperatures will track the actual tempera- tests that the apparatus may be subjected to during factory testing, ture with a time constant of three minutes maximum. which may include: full wave, chopped wave, front of wave, switching surge, 60Hz applied, etc. voltages. SmartSpacer® CERTIFICATION PROCESS 4. Manufacturing Processes: All components including adhesives and assemblies meet strict manufacturing process controls in compliance with drawings and specifications that preclude any stress concentration factors or weakness in the transformer dielectric system. 5. All SmartSpacer® products are shipped with a certificate of compliance outlining that the component has met the following five-part WEIDMANN certification process: Quality: Strict conformance to written quality assurance system standards are met for components and matching sensors throughout the manufacturing, assembly, packaging, and shipping stages. The WEIDMANN Quality Management System is certified to the ISO 9001 Standard. 1. Qualification and Production Testing of Smart Spacers All WEIDMANN SmartSpacer® products are certified as individual components that are integral to the oil-filled EHV/UHV insulation systems found in medium and large power transformers on the electric power grid. SmartSpacer® assemblies utilize embedded sensors capable of communicating status or change in thermal proporties that can indicate loss-of-life criteria and probability of failure of power transformers. 2. Design: The detailed design of the insulation component and embedded sensor are compatible with normal and emergency electrical stress limits typically found in EHV and UHV liquid-filled power transformer winding designs, as specified by the transformer manufacturer and operator. Dielectric Analysis: The component, sensor, and connection system meet the strict requirements in compliance with 2D and 3D dielectric analysis intended to assure compatibility with electrical field stresses that are coordinated with the overall winding and support insulation system design. Verification Tests Mechanical Pull-out Force Compression Thermal Sensor Response Time Sensor Accuracy Dielectric 60 Hz Withstand with PD kV/ mm (ASTM D-149) 60 Hz Withstand kV/ mm (ASTM D-149) Production and Certification Tests 3. Functional Testing: Insulation components and embedded sensors are tested in the WEIDMANN or equivalent highvoltage laboratory to demonstrate the output metrics and applicable tolerances required for the sensor, and that both are suitable for use in the transformer internal environment, in both alternating current and impulse conditions, applicable to the BIL voltage class as specified by the power transformer operator. (See below chart for applicable tests.) Incoming Sensors Sensor Accuracy ± 2° C After Assembly of Button in Spacer Sensor Accuracy ± 2° C X-ray Free of voids Campaign Tests* After Fixing Sensor in Button 60 Hz Withstand with PD 6 kV/ mm (ASTM D-149) 60 Hz Withstand 8 kV/ mm (ASTM D-149) After Assembly of Button in Spacer 60 Hz Withstand with PD 6 kV/ mm (ASTM D-149) 60 Hz Withstand 8 kV/ mm (ASTM D-149) Compression 5000 PSI * Once per year, in addition to Production Tests Rev. 03.12 WEIDMANN ELECTRICAL TECHNOLOGY INC. One Gordon Mills Way, PO Box 903, St. Johnsbury, VT 05819-0903, USA T +800 242 6748, +802 748 8106, F +802 748 8630, www.weidmann-electrical.com A Member of the WICOR Group