TRANSMISSION AND DISTRIBUTION How capacitors affect harmonics, and what is resonance? Information from Elspec The use of power factor correction capacitors can result in resonance in circuits where harmonics are present. In order to understand the PFC capacitor affect on harmonic current,we need to understand the harmonic sources and their nature. Most utlities worldwide produce electricity with a high quality sinusoidal waveform having ver y low distortion. However, as we move closer to the load, the distortion increases. The source of power for the average power consumer is the voltage source. The most popular implementation being the power distribution transformer. As the voltage source, the power distribution transformer's job is to maintain a stable voltage across its secondary windings. The load impedance for the voltage source should be much higher than the internal winding impedance. Ideally the internal winding impedance should be zero, but practically it is as much as 5 – 7% of the full load impedance, because of reactance and parasitic resistance (Fig. 1). The quality of the voltage sine wave on an unloaded distribution transformer depends on quality of power generation and the interference from the other distribution branches. Lets consider the theoretical case where power is generated exclusively for one distribution transformer, and the voltage is a pure sine wave. In that case, any load connected to the transformer secondary will “see” the pure sine wave voltage and will draw current based on the load impedance. When the load impedance is linear the current waveform will follow the voltage wave shape. If the load impedance is changing periodically, as in chopped or other non-linear operated loads, the current waveform may be very different from the voltage sine wave. The non-sinusoidal current can be represented as sum of a series of sine waves starting with the fundamental frequency and including multiples of the fundamental, called harmonics. Harmonics are created by nonlinear loads, and initially they are current waves. The frequencies (harmonic order) and the magnitudes of those current waves depends exclusively on the nature of the load. For example most DC drives have 6-pulse rectifiers, which generate mostly 5th and 7th order harmonics. The 5th harmonic has a frequency five times the fundamental and the 7th is seven times the fundamental. The harmonic is actually the power source at the high frequency. Since the harmonics exist in the current drawn, the source is treated as a current source. Unlike the voltage source, the ideal current Fig. 1: The distribution transformer behaves like a voltage source. source has infinity internal impedance and prefers zero load impedance to maintain the current (Fig. 2). The nonlinear load can be represented as linear load part and the high frequency current sources. For simplicity consider the situation where the only one of the connected loads is nonlinear and is produces only 5th order harmonic current (Fig. 3). The 5th harmonic current is produced by the current source which is part of the load operation, and is fed to the network through the junction A. From the junction A the current will choose the lowest impedance path to flow. The left side impedance is the internal impedance of the distribution transformer in additional to the line impedance. The total impedance of the left side is very much lower than the fully loaded right side. Most of the harmonic current will flow towards the power transformer (Fig. 4). Following the line and internal transformer impedances the harmonic current creates the high frequency voltage drop. This is how voltage harmonics are created. In addition, the current, which passes through transformer secondary will create Fig. 2: Ideal current source. the harmonics on the primary transformer side as well. Now assume that power factor correction is required due to a low power factor at the fundamental frequency. Power factor correction capacitors are added to correct the power factor. (Fig. 5) The harmonic current coming to the junction B will encounter the capacitor and connected in parallel to it resistance and reactance. The resistance part is negligible in most cases, so basically the above can be represented as parallel resonance circuit in the path of the 5th harmonic current. In the case where Xl will be equal to Xc parallel resonance will take place (Fig. 6). Parallel resonance raises the circuit Fig. 3: Harmonic source acts as a current source connected across the load. energize - November 2010 - Page 26 TRANSMISSION AND DISTRIBUTION Fig. 4: Most of the harmonic current flows in the low impedance path. Fig. 5: PFC capacitors can create a resonant circuit at harmonic frequencies. Fig. 6: Resonant circuit at 5th harmonic. Fig. 7: Detuned capacitor configuration prevents resonance. impedance. Current circulates between the capacitor and the inductance without being passed to the grounded terminal. In the case of parallel resonance or even close to resonance condition, the path, which includes distributing transformer and PF capacitors have a very high impedance at the harmonic current frequency. At parallel resonance condition the harmonic current is forced to go to the load. Since the path impedance is increased the voltage harmonic is increased as well too. This situation may cause a significant damage to the electrical infrastructure. Normally, the weakest part which fails first in such a condition is the PF capacitor. The PF capacitor most likely cannot withstand the high harmonic current which is circulating between the capacitors and the distribution transformer. Parallel resonance between the PFC capacitors and the distribution transformer windings is an extremely dangerous situation for the entire electrical system. The resonance condition depends only on the connected capacitance and the network impedance. A small harmonic source may create noticeable voltage distortion and damage to the electrical network. PFC equipment manufacturers strongly recommend the use of a “detuned ” configuration as a standard for any PFC application. The parallel resonance frequency always exists in cases where the capacitors are used for PF correction. The way to prevent parallel resonance occurring is to insure that the frequency of resonance is located outside the harmonic range. This is the main idea behind the “detuned” system configuration. The 7% or 5,67% inductors move the resonance point below the 4th harmonic which insures safe operation for the three phase delta capacitors in cases where the third harmonic is balanced (Fig. 7). The PFC capacitor itself has linear impedance. Once connected it does not create any harmonics current by itself. But, because of parallel resonance possibility the PFC capacitors can dramatically affect the harmonic situation on the network. The electromechanical connected capacitors are affected by heavy transients on the connection/disconnection point. The transients have a nonlinear waveform, which, of course, injects a lot of harmonics for a short time. Elspec equipment has completely transient free operated capacitors and no harmonics are generated on the connection and disconnection events. Contact Graham Whittle, Impact Energy, Tel 031 201-7191, graham@impactenergy.co.za energize - November 2010 - Page 28