FEEDER, CONDUIT OR RELAY SCHEDULE TAG
JUNCTION BOX - CEILING OR WALL MOUNTED, SIZE TO CODE,
TAPE AND TAG WIRES. PROVIDE FLEX AND/OR
RECEPTACLE AS REQUIRED TO CONNECT EQUIPMENT.
C.
BEFORE BEGINNING CONSTRUCTION, PROVIDE TO THE ARCHITECT A CONSTRUCTION
SCHEDULE OF ELECTRICAL WORK. THE CONSTRUCTION SCHEDULE SHALL IDENTIFY ALL
SIGNIFICANT MILESTONES WITH COMPLETION DATES.
PANELBOARD - FLUSH MOUNTED.
D.
OBTAIN AND PAY FOR ALL PERMITS, LICENSES AND INSPECTION FEES REQUIRED BY THIS
CONTRACT WORK, UNLESS OTHERWISE NOTED.
PANELBOARD - SURFACE MOUNTED.
E.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE SAFETY OF PERSONS AND
PROPERTY AND SHALL PROVIDE INSURANCE COVERAGE AS NECESSARY FOR LIABILITY,
PERSONAL, PROPERTY DAMAGE, TO FULLY PROTECT THE OWNER, ARCHITECT AND
ENGINEER FROM ANY AND ALL CLAIMS RESULTING FROM THIS WORK.
F.
MAINTAIN RECORD DRAWINGS AT THE PROJECT SITE INDICATING ALL MODIFICATIONS TO
ELECTRICAL SYSTEMS. AT THE CONCLUSION OF THE PROJECT, PROVIDE ACCURATE
"AS-BUILT" DRAWINGS ACCEPTABLE TO THE ARCHITECT.
G.
ALL MATERIALS PROVIDED FOR THE PROJECT SHALL BE NEW, UNLESS OTHERWISE
NOTED. PROVIDE ALL INCIDENTAL MATERIALS REQUIRED FOR A COMPLETE
INSTALLATION.
H.
PROVIDE ALL REQUIRED "CUTTING, PATCHING, BACK FILL AND REPAIRS" NECESSARY TO
RESTORE DAMAGED SURFACES TO EQUAL OR BETTER THAN ORIGINAL CONDITIONS
EXISTING AT START OF WORK.
I.
ALL ELECTRICAL EQUIPMENT INSTALLED OUTDOORS SHALL BE WEATHERPROOF.
EXTERIOR CONDUIT RUNS INTO BUILDINGS SHALL BE INSTALLED WITH FLASHING,
CAULKED AND SEALED. CONDUITS FOR EXTERIOR ELECTRICAL DEVICES SHALL BE RUN
INSIDE BUILDING, UNLESS OTHERWISE NOTED. UNDERGROUND AND EXTERIOR CONDUIT
SHALL HAVE WATERTIGHT FITTINGS.
J.
ALL CONDUITS SHALL BE 3/4" MINIMUM UNLESS OTHERWISE NOTED. POWER AND
LIGHTING BRANCH CIRCUITS SHALL HAVE A MINIMUM TWO (2) #12 AWG AND ONE (1) #12
AWG GROUND TYPE THWN/THHN. THE CONTRACTOR SHALL SIZE CONDUCTORS FOR
VOLTAGE DROP. DEDICATED NEUTRALS ARE REQUIRED FOR ALL 1-POLE CIRCUIT
BREAKERS. ALL POWER WIRING SHALL BE RUN IN CONDUIT. THE USE OF MC CABLE IS
PERMITED IN INDIVIDUAL ROOMS ONLY. ALL HOMERUNS SHALL BE IN CONDUIT, PROVIDE
WIRES AND WIRE SIZES AS REQUIRED BY CODE AND AHJ. THE USE OF ROMEX (NMC) IS
NOT PERMITTED.
K.
CONDUITS SHALL NOT BE USED AS A GROUND PATH. ALL CONDUITS SHALL CONTAIN A
GROUNDING CONDUCTOR, SIZED PER NEC/CEC REQUIREMENTS.
L.
THERE SHALL BE NO ROOF PENETRATIONS WITHIN 5'-0" OF FIRE RATED OR AREA
SEPARATION WALLS. VERIFY EXACT LOCATIONS OF THESE WALLS WITH ARCHITECTURAL
DRAWINGS.
DISTRIBUTION PANEL
SWITCHBOARD
LUMINAIRE & SWITCH SYMBOLS
LUMINAIRE - SEE SCHEDULE.
MOTOR
LUMINAIRE - SEE SCHEDULE.
UNFUSED DISCONNECT SWITCH
LUMINAIRE - SEE SCHEDULE.
FUSED DISCONNECT SWITCH
LUMINAIRE - SEE SCHEDULE.
COMBINATION MAGNETIC STARTER/FUSED DISCONNECT SWITCH
LUMINAIRE - POLE MOUNTED SINGLE HEAD. SEE SCHEDULE.
MAGNETIC STARTER - NEMA SIZE INDICATED.
LUMINAIRE - POLE MOUNTED DOUBLE HEAD. SEE SCHEDULE.
MOTOR RATED SWITCH
LUMINAIRE - SINGLE WALL WASHER. SEE SCHEDULE.
T
TRANSFORMER
GROUND ROD
LUMINAIRE - DOUBLE WALL WASHER. SEE SCHEDULE.
LUMINAIRE - CORNER WALL WASHER. SEE SCHEDULE.
LUMINAIRE - SEE SCHEDULE.
LUMINAIRE - WALL MOUNTED. SEE SCHEDULE.
LUMINAIRE - WALL MOUNTED. SEE SCHEDULE.
G
EMERGENCY GENERATOR
CH
2
EQUIPMENT TAG
POWER DISTRIBUTION SYMBOLS (SINGLE LINE)
EMERGENCY LUMINAIRE - SEE SCHEDULE.
CIRCUIT BREAKER - DRAW-OUT.
EMERGENCY LUMINAIRE - SEE SCHEDULE.
CIRCUIT BREAKER
EMERGENCY LUMINAIRE - SEE SCHEDULE.
FUSED SWITCH
EMERGENCY LUMINAIRE - SEE SCHEDULE.
M
METER WITH CURRENT TRANSFORMER
EMERGENCY LUMINAIRE - SEE SCHEDULE.
TRANSFORMER
EMERGENCY LUMINAIRE - SEE SCHEDULE.
M.
AUTOMATIC TRANSFER SWITCH
EXIT LIGHT (WITH ARROW) - SEE SCHEDULE.
O.
DEMOLITION INFORMATION AND EXISTING EQUIPMENT AND DEVICE LOCATIONS AND
QUANTITIES ARE THE RESULT OF PRELIMINARY FIELD INVESTIGATION ONLY AND DO NOT
NECESSARILY REFLECT ALL DEVICES ON SITE THAT MAY EXIST OR MAY NEED TO BE
DEMOLISHED. CONTRACTOR SHALL FIELD VERIFY ALL DEVICES, CONDUIT, WIRING, AND
OTHER ITEMS WHICH MAY NEED TO BE RELOCATED, DEMOLISHED, OR PROTECTED IN PLACE
AND SHALL MAKE PROVISIONS TO DO SO IN THEIR BID.
EMERGENCY GENERATOR
EXIT LIGHT (DOUBLE FACED WITH ARROW) - SEE SCHEDULE.
EMERGENCY BATTERY PACK EXIT LIGHT - SEE SCHEDULE.
GROUND ROD
SINGLE POLE SWITCH - WALL MOUNTED AT + 48" AFF UON.
OS
OCCUPANCY SENSOR - CEILING MOUNTED
SECURITY SYMBOLS
O
S
OCCUPANCY SENSOR - WALL MOUNTED
P
PHOTOSENSOR
LCD
LCP
TS
A
CARD READER
ES
ELECTRIC DOOR STRIKE
GB
GLASSBREAK DETECTOR
M
"A" DENOTES FIXTURE TYPE
SAP
A
L1-3b
"L1" DENOTES PANEL NAME
"3" DENOTES CIRCUIT NUMBER
"b" DENOTES SWITCHING
LOWER CASE LETTER = SWITCH LEG
D = DIMMER SWITCH. SEE SPECIFICATIONS
K = KEY OPERATED SWITCH
L = LOW VOLTAGE SWITCH
M = MOMENTARY CONTACT SWITCH
TS = DIGITAL WALL TIMER
S = OCCUPANCY SENSOR SWITCH
3 = 3 WAY SWITCH
4 = 4 WAY SWITCH
X
D = DUAL TECHNOLOGY
P = PASSIVE INFRARED
U = ULTRASONIC
RECEPTACLE SYMBOLS
SINGLE RECEPTACLE - DESIGNATION AS NOTED.
DUPLEX RECEPTACLE.
GFCI DUPLEX RECEPTACLE.
DOUBLE DUPLEX RECEPTACLE.
DUPLEX RECEPTACLE - INSTALL AT + 1" ABOVE COUNTER TOP
BACK SPLASH TO BOTTOM OF RECEPTACLE FACEPLATE UON.
GFCI DUPLEX RECEPTACLE - INSTALL AT + 1" ABOVE COUNTER
TOP BACK SPLASH TO BOTTOM OF RECEPTACLE FACEPLATE UON.
FLUSH FLOOR BOX WITH DUPLEX RECEPTACLE, RJ45 DATA
OUTLET, AND RJ11 TELEPHONE OUTLET.
FLUSH FLOOR BOX WITH DUPLEX RECEPTACLE.
SURFACE MOUNTED WIRE RACEWAY - INSTALL AT + 36" AFF UON.
SIGNAL TERMINAL CABINET - FLUSH MOUNTED.
SIGNAL TERMINAL CABINET - SURFACE MOUNTED.
COMBINATION RJ11/BLANK TELEPHONE OUTLET - PROVIDE 1"
CONDUIT TO ABOVE ACCESSIBLE CEILING. "X" DENOTES QTY
OF CABLES/JACKS.
T.
SEISMIC ANCHORAGE OF ALL ELECTRICAL EQUIPMENT SHALL BE PROVIDED IN
ACCORDANCE WITH TITLE 24, CBC SECTION 1632A.
U.
THE DRAWINGS AND SPECIFICATIONS ARE FOR THE ASSISTANCE AND GUIDANCE OF THE CONTRACTOR.
EXACT LOCATIONS, DISTANCES AND ELEVATIONS WILL BE GOVERNED BY ACTUAL
CONDITIONS. COORDINATE THE CONTRACT DOCUMENTS AND FIELD CONDITIONS TO
DETERMINE EXACT ROUTING AND FINAL TERMINATIONS FOR ALL WORK.
SUFFICIENT ACCESS AND WORKING SPACE SHALL BE PROVIDED AND MAINTAINED ABOUT
ALL ELECTRIC EQUIPMENT TO PERMIT READY AND SAFE ORPERATION AND MAINTENANCE
OF SUCH EQUIPMENT PER CEC ARTICLE 110-26.
WIRING & CONDUIT RUN SYMBOLS
CONDUIT - CONCEALED IN WALLS OR CEILING.
7.
2013 CALIFORNIA GREEN CODE (PART 11, TITLE 24, CCR).
8.
2013 CALIFORNIA REFERENCED STANDARDS CODE (PART 12, TITLE 24, CCR).
9.
NFPA 72 NATIONAL FIRE ALARM CODE.
W. THE CONTRACTOR IS RESPONSIBLE TO COORDINATE THE WORK OF ALL TRADES AND
SUB-TRADES TO ENSURE THAT THE FINISHED PROJECT IS FULLY COMPLIANT WITH THE
DESIGN INTENT OF THESE DOCUMENTS, INCLUDING, BUT NOT LIMITED TO, DIMENSIONS,
ALIGNMENTS, REVEALS, CEILING HEIGHTS, PLACEMENT OF FIXTURES AND EQUIPMENT,
AND PROPER, INTEGRATED OPERATION OF BUILDING SYSTEMS.
X.
ADDITIONAL CHARGES WILL NOT BE ACCEPTED BY THE OWNER FOR WORK THAT MUST BE
ALTERED OR REDONE DUE TO IMPROPER COORDINATION OF THE WORK AMONG TRADES
AND SUB-TRADES.
Y.
ALL DUCTS, PIPING AND CONDUITS SHALL BE CONCEALED UNLESS SPECIFICALLY NOTED.
Z.
ADDITIONAL SOFFITS OR CHASES, BEYOND THOSE INDICATED IN THIS DOCUMENTS, WILL
NOT BE ALLOWED.
F ESS I ON
PRO
AL
V I D MA
A
I
D
ED
E 19203
EXP. 6-30-16
E
A
TE
LE
C T R I CA
L
RN
O F CA L I F O
10. NFPA 13 STANDARDS FOR FIRE SPRINKLER SYSTEMS.
DRAWING INDEX
E-1
GENERAL INFORMATION
E-2
ELECTRICAL SPECIFICATIONS
E-3
ELECTRICAL SPECIFICATIONS AND SCHEDULES
E-4
SITE PLAN
E-5
LEVELS 1 AND 2 ELECTRICAL DEMOLITION PLANS
E-6
LEVELS 1 AND 2 LIGHTING DEMOLITION PLANS
E-7
LEVELS 1 AND 2 LIGHTING PLANS
E-8
E-9
LEVELS 1 AND 2 POWER PLANS
SCHEDULES
E-10
WIRING DIAGRAMS
E-11
STANDARD DETAILS
E-12
STANDARD DETAILS
E-13
E-14
LUMINAIRE SCHEDULES AND T24
LUMINAIRE SCHEDULES AND T24
CONDUIT - FLEX WITH CONNECTION.
CONDUIT - STUB UP.
CONDUIT - STUB DOWN.
CONDUIT - EMERGENCY POWER SYSTEM.
AA. REFER TO TABLE BELOW FOR MAXIMUM ALLOWABLE DISTANCE FOR VARIOUS FEEDER
AND BRANCH CIRCUIT WIRING SIZES. IF THE ALLOWABLE DISTANCE IS EXCEEDED, THE
CONTRACTOR SHALL PROVIDE THE NEXT HIGHER WIRE SIZE UNTIL THE DISTANCE
REQUIREMENTS NOTED BELOW ARE MET.
CONDUIT - CAPPED.
CONDUIT - CONTINUATION.
NEW VS. EXISTING
(N) CONDUIT - CONCEALED IN WALLS OR CEILING.
(E) CONDUIT - CONCEALED IN WALLS OR CEILING.
(E) CONDUIT - TO BE REMOVED.
(N) FUSED DISCONNECT SWITCH
(E) FUSED DISCONNECT SWITCH
COMMUNICATIONS SYMBOLS
CONDUIT AND WIRING ARE SHOWN ON THESE PLANS DIAGRAMMATICALLY. EXACT
LOCATIONS SHALL BE DETERMINED IN THE FIELD TO SUIT SITE CONDITIONS.
V.
CONDUIT - HOME RUN TO PANEL, TERMINAL CABINET, ETC.
SIZE CONDUIT ACCORDING TO SPECIFICATIONS AND APPLICABLE
CODES. ALL 20A, 1P BRANCH CIRCUITS SHALL BE #12 AWG
WIRES WITH #12 AWG NEUTRALS AND GROUNDS. RUN A
MAXIMUM OF 3 BRANCH CIRCUITS PER CONDUIT.
2013 CALIFORNIA FIRE CODE (CFC) (PART 9,TITLE 24, CCR).
THE CONTRACTOR SHALL BE RESPONSIBLE FOR SITE LOCATING ALL EXISTING
UNDERGROUND SYSTEMS IN THE AREA OF UNDER GROUND WORK. REPAIR ALL DAMAGED
SYSTEMS TO OWNERS SATISFACTION. MAINTAIN EXTREME CARE DURING TRENCHING AS
EXISTING SYSTEMS ARE KNOWN TO EXIST IN THE AREA.
PAN, TILT, ZOOM (PTZ) VIDEO CAMERA
CONDUIT - DIRECT BURIAL.
6.
R.
FIXED POSITION VIDEO CAMERA
CONDUIT - EXPOSED.
2013 CALIFORNIA ENERGY CODE (PART 6,TITLE 24, CCR).
12. ADA STANDARDS FOR ACCESSIBLE DESIGN - CODE OF REGULATIONS (INCLUDING
AMENDMENTS).
SECURITY ALARM PANEL
Xx
5.
VERIFY ALL VOLTAGES OF MECHANICAL EQUIPMENT WITH MECHANICAL CONTRACTOR
PRIOR TO ROUGH-IN.
KEYPAD
MOTION DETECTOR
2013 CALIFORNIA PLUMBING CODE (CPC) (PART 5, TITLE 24, CCR).
Q.
S.
TYPICAL LUMINAIRE & SWITCH NOMENCLATURE
4.
11. ADA STANDARDS FOR ACCESSIBLE DESIGN: ADA ACCESSIBILITY GUIDELINES (ADAAG) 28,
PART 36 APPENDIX A.
LIGHTING CONTROL PANEL
KP
2013 CALIFORNIA MECHANICAL CODE (CMC) (PART 4, TITLE 24, CCR).
PROVIDE A PULL CORD IN EVERY EMPTY CONDUIT FOR USE IN FUTURE CONSTRUCTION.
DAYLIGHT CONTROL PANEL
TIME SWITCH
3.
P.
ALARM CONTACT
CR
2013 CALIFORNIA ELECTRICAL CODE (PART 3, TITLE 24, CCR).
NEER
AUXILIARY CONTACT - NORMALLY CLOSED.
2.
ST
THE CONTRACTOR SHALL, PRIOR TO BID, FIELD VERIFY ALL REQUIREMENTS FOR
MODIFYING THE EXISTING DATA, TELEPHONE, POWER, AND LIGHTING SYSTEMS TO
ACCOMMODATE ADDITIONS NOTED. PROVIDE ALL MATERIALS NEEDED TO MAKE A FULLY
OPERATIONAL SYSTEM AT THE CONCLUSION OF PROJECT WORK.
EXIT LIGHT - SEE SCHEDULE.
2013 CALIFORNIA BUILDING CODE (CBC), VOLUMES #1 AND #2 (PART 2,TITLE 24, CCR).
NO
EMERGENCY LUMINAIRE - WALL MOUNTED. SEE SCHEDULE.
N.
1.
GI
EN
AUXILIARY CONTACT - NORMALLY OPENED.
CALIFORNIA CODES AND STANDARDS
NOTE THAT BRANCH CIRCUIT WIRING IS NOT SHOWN. CIRCUIT NUMBERS ARE SHOWN
ADJACENT TO ALL OUTLETS/FIXTURES/DEVICES. PROVIDE ALL BRANCH CIRCUIT WIRING
BASED ON CIRCUIT NUMBERS SHOWN TO COMPLETE THE WIRING SYSTEM.
EMERGENCY LUMINAIRE - WALL MOUNTED. SEE SCHEDULE.
JUNCTION BOX
KILOAMPERE INTERRUPTING CAPACITY
KILOVOLT
KILOVOLT AMPERE
KILOWATT
LIGHTING
LOW VOLTAGE
MAXIMUM
THOUSAND CIRCULAR MILS
MAIN DISTRIBUTION FRAME
MECHANICAL
MANHOLE
MINIMUM
MOUNTED
MOUNTING
NORMALLY CLOSED
NATIONAL FIRE PROTECTION ASSOCIATION
NOT IN CONTRACT
NOT IN ELECTRICAL CONTRACT NUMBER,
NORMALLY OPEN
NOT TO SCALE
ON CENTER
POLE
PUBLIC ADDRESS
PULL BOX
POWER FACTOR
PHASE
PANEL
POLYVINYL CHLORIDE
EXISTING TO BE RELOCATED
REQUIRED
REQUIREMENT(S)
ROOM
RIGID STEEL CONDUIT
SHEET
SIGNAL TERMINAL CABINET
SWITCH
SWITCHBOARD
TERMINAL CABINET
TELEPHONE
TYPICAL
UNLESS OTHERWISE NOTED
VOLT
WATT, WIRE
WEATHERPROOF
TRANSFORMER
Architecture Interiors Planning
J
JB
KAIC
KV
KVA
KW
LTG
LV
MAX
KCMIL
MDF
MECH
MH
MIN
MTD
MTG
NC
NFPA
NIC
NIEC
NO
NTS
OC
P
PA
PB
PF
PH
PNL
PVC
(R)
REQD
REQT(S)
RM
RSC
SHT
STC
SW
SWBD
TC
TEL
TYP
UON
V
W
WP
XFMR
IA
"E1.0" DENOTES SHEET NUMBER. BLANK DENOTES SAME SHEET.
AMPERE
ABOVE
AMPERE FRAME, AMPERE FUSE
ABOVE FINISHED FLOOR
AMPERE INTERRUPTING CAPACITY
ARCHITECTURAL AMPERE SWITCH
AMPERE TRIP
AUTOMATIC TRANSFER SWITCH
BREAKER
BUILDING
CONDUIT
CABLE TELEVISION
CIRCUIT BREAKER
CALIFORNIA BUILDING CODE
CANDELA
CALIFORNIA ELECTRICAL CODE
CALIFORNIA FIRE CODE
CIRCUIT
CENTER LINE
CEILING
CONDUIT ONLY
COMMUNICATIONS
CALIFORNIA STATE FIRE MARSHALL
CENTER
DEMOLISH
DETAIL
DIMENSION
DISTRIBUTION
DISTRIBUTION PANEL
DRAWING
EXISTING
ELECTRICAL
EMERGENCY
ELECTRICAL METALLIC TUBING
END OF LINE RESISTOR
EQUIPMENT
FIRE ALARM
FIRE ALARM CONTROL PANEL
FUTURE FINISH
FLOOR
GROUND
HEIGHT
HORSEPOWER
INTERCOM
INTERMEDIATE DISTRIBUTION FRAME
INTERMEDIATE METAL CONDUIT
ER
WAP
POWER DISTRIBUTION SYMBOLS (PLANS)
SHEET NOTE TAG - SEE ASSOCIATED NOTE ON SAME SHEET.
COMPLY WITH ALL APPLICABLE CODES AND REGULATIONS. MATERIALS AND EQUIPMENT
SHALL BE U.L. AND CALIFORNIA STATE FIRE MARSHAL (CSFM) LISTED AND LABELED FOR
THE APPLICATION.
TELEVISION OUTLET - TYPE "F" BULKHEAD JACK. INSTALL AT + 52"
AFF UON. PROVIDE 3/4" CONDUIT TO ABOVE ACCESSIBLE CEILING
FOR CATV CABLE.
TV
SECTION OR ELEVATION DESIGNATION
"2" DENOTES SECTION OR ELEVATION NUMBER
3
B.
A
ABV
AF
AFF
AIC
ARCH AS
AT
ATS
BKR
BLDG
C
CATV
CB
CBC
CD
CEC
CFC
CKT
CL
CLG
CO
COMM
CSFM
CTR
(D)
DET
DIM
DIST
DP
DWG
(E)
ELEC
EM
EMT
EOL
EQP
FA
FACP
(F) FIN
FL
G, GND
HGT
HP
IC
IDF
IMC
FLUSH FLOOR BOX WITH MICROPHONE OUTLET
WIRELESS ACCESS POINT, CEILING MOUNTED
2
E1.0
THE CONTRACTOR SHALL VISIT THE PROJECT SITE PRIOR TO BIDDING AND ALLOW FOR
ALL FIELD CONDITIONS. OBTAIN CONTRACT DOCUMENTS FOR ALL OTHER TRADES AND BE
RESPONSIBLE FOR ALL ELECTRICAL WORK NOTED AND CALLED OUT ON THE CONTRACT
DOCUMENTS. COORDINATE ELECTRICAL WORK WITH ALL OTHER TRADES ON PROJECT.
COORDINATE ALL CONDUIT RUNS, ELECTRICAL EQUIPMENT AND PANEL LOCATIONS WITH
ALL OTHER WORK TO AVOID CONFLICTS.
.
"E2.1" DENOTES SHEET NUMBER. BLANK DENOTES SAME SHEET.
A.
ST
3
E2.1
PLAN OR DETAIL DESIGNATION
"3" DENOTES DETAIL OR PLAN NUMBER
ABBREVIATIONS
J
GENERAL SYMBOLS
ELECTRICAL GENERAL NOTES
REG I
SYMBOL LIST
(E) FUSED DISCONNECT SWITCH - TO BE REMOVED.
VOLTAGE DROP FOR COMMON COPPER WIRE GAUGES AND CURRENT
LOADS
MAX FEEDER LENGTH - 3% VD (FT)
MAX BRANCH CIRCUIT LENGTH - 2% VD (FT)
WIRE
SIZE
CIRCUIT
AMPS (A)
120V
208V
240V
277V
480V
120V
208V
12
16
46
80
93
107
185
69
10
24
48
83
96
111
192
72
8
32
58
99
115
132
229
6
40
73
127
146
169
4
52
89
154
178
206
240V
277V
480V
120
139
160
278
125
144
166
288
86
149
172
199
344
293
110
190
220
253
439
356
134
232
267
309
535
2
72
103
178
206
237
412
154
267
309
356
617
1/0
96
123
212
245
283
490
184
319
368
424
735
2/0
108
137
238
274
317
549
206
357
412
475
823
4/0
144
163
283
327
377
654
245
425
490
566
980
250
165
170
294
340
392
679
255
441
509
588
1019
300
184
181
314
362
418
725
272
471
543
627
1087
350
200
195
338
390
450
779
292
506
584
675
1169
500
248
224
388
448
517
896
336
582
672
776
1344
Revisions
No. Description
Date
(N) LUMINAIRE - SEE SCHEDULE.
(E) LUMINAIRE - SEE SCHEDULE.
(E) LUMINAIRE - TO BE REMOVED.
COMBINATION RJ11/RJ45 TELEPHONE/DATA OUTLET - PROVIDE
1" CONDUIT TO ABOVE ACCESSIBLE CEILING. "X" DENOTES QTY
OF CABLES/JACKS.
COMBINATION RJ45/BLANK DATA OUTLET - PROVIDE 1" CONDUIT
TO ABOVE ACCESSIBLE CEILING. "X" DENOTES QTY OF CABLES/JACKS.
S
SPEAKER - WALL MOUNTED. INSTALL AT + 8'-0" AFF UON.
S
SPEAKER - CEILING MOUNTED.
C
CLOCK - WALL MOUNTED. INSTALL AT + 8'-0" AFF UON.
Scale
N.T.S
2016.01.14
Date
Nov.06,
2015
Job No.
15-57
POSITION. MANUFACTURERS: EATON, GENERAL ELECTRIC, SQUARE D, SIEMENS, OR APPROVED EQUIVALENT.
ER
Architecture Interiors Planning
.
ST
J
NEER
D.
PROVIDE NEMA 1 ENCLOSURE FOR INDOORS, NEMA 3R ENCLOSURE FOR OUTDOORS. MANUFACTURERS: EATON, GENERAL ELECTRIC, SQUARE D, SIEMENS, OR
APPROVED EQUIVALENT.
COMBINATION STARTERS: HEAVY DUTY, FUSIBLE OR NON-FUSIBLE TYPE (AS INDICATED ON DRAWINGS), DUAL RATED, QUICK-MAKE, QUICK-BREAK WITH FUSE REJECTION
FEATURE FOR USE WITH CLASS R FUSES ONLY. DEVICE LABELED WITH MAXIMUM VOLTAGE, CURRENT, AND HORSEPOWER. PROVIDE COIL VOLTAGE COORDINATED WITH
CONTROL REQUIREMENTS AND THERMAL OVERLOAD UNITS SIZED TO EQUIPMENT NAMEPLATE RATING. PROVIDE ONE N.C. AND ONE N.O. AUXILIARY CONTACTS. PROVIDE
3.3 DEMOLITION
A. COORDINATE WITH OWNER SO THAT WORK CAN BE SCHEDULED NOT TO INTERRUPT OPERATIONS, NORMAL ACTIVITIES, BUILDING ACCESS, ACCESS TO DIFFERENT AREAS.
THE OWNER WILL COOPERATE TO THE BEST OF THEIR ABILITY TO ASSIST IN A COORDINATED SCHEDULE, BUT WILL REMAIN THE FINAL AUTHORITY AS TO TIME OF WORK
PERMITTED.
B. COORDINATE THE EXACT LOCATION OF EXISTING UTILITIES AND EQUIPMENT PRIOR TO COMMENCEMENT OF WORK. COMPENSATE THE OWNER FOR DAMAGES CAUSED BY
THE FAILURE TO LOCATE AND PRESERVE UTILITIES. REPLACE DAMAGED ITEMS WITH NEW MATERIAL TO MATCH EXISTING. VERIFY THAT ABANDONED WIRING AND
EQUIPMENT SERVE ONLY ABANDONED FACILITIES.
C. EXECUTION:
1. REMOVE EXISTING LUMINAIRES, SWITCHES, RECEPTACLES, AND OTHER ELECTRICAL EQUIPMENT AND DEVICES AND ASSOCIATED WIRING FROM WALLS, CEILINGS,
FLOORS, AND OTHER SURFACES SCHEDULED FOR REMODELING, RELOCATION, OR DEMOLITION UNLESS SHOWN AS RETAINED OR RELOCATED ON DRAWINGS.
2. PROVIDE TEMPORARY WIRING AND CONNECTIONS TO MAINTAIN ELECTRICAL CONTINUITY OF EXISTING SYSTEMS DURING CONSTRUCTION. REMOVE OR RELOCATE
ELECTRICAL BOXES, CONDUIT, WIRING, EQUIPMENT, LUMINAIRES, AS ENCOUNTERED IN REMOVED OR REMODELED AREAS IN THE EXISTING CONSTRUCTION AFFECTED
BY THIS WORK.
3. REMOVE AND RESTORE WIRING WHICH SERVES USABLE EXISTING OUTLETS CLEAR OF THE CONSTRUCTION OR DEMOLITION
4. IF EXISTING JUNCTION BOXES WILL BE MADE INACCESSIBLE, OR IF ABANDONED OUTLETS SERVE AS FEED THROUGH BOXES FOR OTHER EXISTING ELECTRICAL
EQUIPMENT WHICH IS BEING RETAINED, PROVIDE NEW CONDUIT AND WIRE TO BYPASS THE ABANDONED OUTLETS.
5. IF EXISTING CONDUITS PASS THROUGH PARTITIONS OR CEILING WHICH ARE BEING REMOVED OR REMODELED, PROVIDE NEW CONDUIT AND WIRE TO REROUTE CLEAR
OF THE CONSTRUCTION OR DEMOLITION AND MAINTAIN SERVICE TO THE EXISTING LOAD.
6. CONCEALED CONDUIT LOCATED IN CONCRETE WALLS OR HARDBOARD CEILING SPACES MAY BE ABANDONED IN PLACE. REMOVE CONDUCTORS AND TAG ABANDONED
CONDUITS WITH CORRESPONDING SYSTEM AND TERMINATION POINT. CUT AND CAP ABANDONED CONDUIT. DO NOT EXTEND STUBS ABOVE FINISHED FLOOR.
7. EXTEND CIRCUITING AND DEVICES IN EXISTING WALLS TO BE FURRED OUT.
8. PROVIDE TEMPORARY SUPPORT FOR ELECTRICAL SYSTEMS THAT REMAIN IN PLACE.
9. REMOVE ABANDONED WIRING TO SOURCE OF SUPPLY.
10. PROVIDE BLANK COVER PLATE FOR ABANDONED FLUSH OUTLETS.
11. MAINTAIN ACCESS TO EXISTING ELECTRICAL INSTALLATIONS WHICH REMAIN ACTIVE. MODIFY INSTALLATION OR PROVIDE ACCESS PANEL AS APPROPRIATE.
12. PROVIDE UPDATED PANEL SCHEDULES AND DIRECTORIES THAT IDENTIFY EXISTING CIRCUITS AND NUMBER OF SPARE CIRCUITS AVAILABLE UPON COMPLETION OF
DEMOLITION WORK.
13. OFFER REMOVED LUMINAIRES, WIRING DEVICES, PANELBOARDS, AND EQUIPMENT TO THE OWNER. IF OWNER CHOOSES TO RETAIN THESE ITEMS, RETURN SUCH
ITEMS TO OWNER. CAREFULLY REMOVE AND DISPOSE OF ITEMS REJECTED BY OWNER FROM PROJECT SITE AND IN A LEGAL MANNER.
3.4 CONTINUITY OF SERVICE
A. NO INTERRUPTION OF SERVICES TO ANY PART OF EXISTING FACILITIES WILL BE PERMITTED WITHOUT EXPRESS PERMISSION IN EACH INSTANCE FROM THE OWNER.
REQUESTS FOR OUTAGES SHALL STATE THE SPECIFIC DATES AND HOURS AND THE MAXIMUM DURATIONS, WITH THE OUTAGES KEPT TO THESE SPECIFIC DATES AND
HOURS AND THE MAXIMUM DURATIONS. OBTAIN WRITTEN PERMISSION FROM THE OWNER FOR ANY INTERRUPTION OF POWER, LIGHTING OR SIGNAL CIRCUITS AND
SYSTEMS.
3.5 INSTALLATION
A. INSTALL ELECTRICAL EQUIPMENT COMPLETE AS DIRECTED BY MANUFACTURER'S INSTALLATION INSTRUCTIONS. OBTAIN INSTALLATION INSTRUCTIONS FROM
MANUFACTURER PRIOR TO ROUGH-IN OF THE ELECTRICAL EQUIPMENT, EXAMINE THE INSTRUCTIONS THOROUGHLY. WHEN REQUIREMENTS OF INSTALLATION
INSTRUCTIONS CONFLICT WITH CONTRACT DOCUMENTS, REQUEST CLARIFICATION FROM ARCHITECT PRIOR TO PROCEEDING WITH INSTALLATION. THIS INCLUDES PROPER
INSTALLATION METHODS, SEQUENCING, AND COORDINATION WITH OTHER TRADES AND DISCIPLINES.
B. DELIVERY, STORAGE AND HANDLING: INSPECT AND REPORT CONCEALED DAMAGE TO CARRIER WITHIN THEIR REQUIRED TIME PERIOD. STORE IN A CLEAN, DRY
NO
C.
ELECTRIC, EATON, OR APPROVED EQUIVALENT.
SAFETY SWITCHES: HEAVY DUTY, FUSIBLE AND NON-FUSIBLE TYPE (AS INDICATED ON DRAWINGS), DUAL RATED, QUICK-MAKE, QUICK-BREAK WITH FUSE REJECTION
FEATURE FOR USE WITH CLASS R FUSES ONLY. DEVICE LABELED WITH MAXIMUM VOLTAGE, CURRENT, AND HORSEPOWER. OPERABLE HANDLE INTERLOCKED TO
3.2 MOTORS/APPLIANCE/UTILIZATION BRANCH CIRCUIT WIRING
A. CONNECT EQUIPMENT, WHETHER FURNISHED BY OWNER OR OTHER DIVISIONS OF THE CONTRACT, ELECTRICALLY COMPLETE. DO NOT INSTALL ELECTRICAL EQUIPMENT
OR WIRING ON MECHANICAL EQUIPMENT WITHOUT APPROVAL OF ARCHITECT.
B. PROVIDE MOISTURE TIGHT EQUIPMENT WIRING AND SWITCHES IN DUCTS OR PLENUMS USED FOR ENVIRONMENTAL AIR.
C. CONNECT MOTOR BRANCH CIRCUITS COMPLETE FROM PANEL TO MOTOR/EQUIPMENT AS REQUIRED BY CODE.
D. MOTOR STARTERS FOR EQUIPMENT, MOTOR START CONTROL DEVICES, AND WIRING FURNISHED BY OTHER DIVISIONS PROVIDED BY EQUIPMENT INSTALLER FOR
INSTALLATION BY THIS DIVISION, UNLESS NOTED ON DRAWINGS.
E. INSTALL FEEDER CIRCUIT TO PACKAGED HVAC EQUIPMENT. TERMINATE FEEDER CONDUCTORS AT LINE TERMINALS AS DIRECTED BY EQUIPMENT MANUFACTURER.
F. APPLIANCE/UTILIZATION EQUIPMENT: PROVIDE APPROPRIATE CABLE AND CORD CAP FOR FINAL CONNECTION UNLESS EQUIPMENT IS PROVIDED WITH SAME. VERIFY
SPECIAL PURPOSE OUTLET NEMA CONFIGURATION AND AMPERE RATING WITH EQUIPMENT SUPPLIER PRIOR TO ORDERING DEVICES AND COVERPLATES.
F ESS I ON
PRO
AL
V I D MA
A
I
D
ED
GI
EN
2.6 WIRING DEVICES
A. FINISH: STANDARD COLOR AS SELECTED BY THE ARCHITECT.
B. WALL SWITCHES: DECORATIVE AC ROCKER SWITCHES CHARACTERISTICS: QUIET ACTING, 20 AMP, 120/277 VOLT, UL LISTED FOR MOTOR LOADS UP TO 80 PERCENT OF
RATED AMPERAGE. WHERE SWITCHES ARE GANGED TOGETHER, PROVIDE A SINGLE MULTI-GANG COVERPLATE. COOPER, HUBBELL, LEVITON, PASS & SEYMOUR, OR
APPROVED EQUIVALENT.
C. RECEPTACLES: STRAIGHT PARALLEL BLADE, 125 VOLT, 2 POLE, 3 WIRE GROUNDING.
1. COMMERCIAL GRADE: RIVETED. BACK AND SIDE WIRED. BRASS GROUND CONTACT ON STEEL MOUNTING STRAP. NYLON FACE AND NYLON BASE. [20 AMP. COOPER
5362, HUBBELL 5362, BRYANT 5362, LEVITON 5362S, PASS & SEYMOUR 5362] [15 AMP. COOPER 5352, HUBBELL 5352, BRYANT 5352, LEVITON 5352, PASS & SEYMOUR 5352.
D. GROUND FAULT INTERRUPTER (GFCI) RECEPTACLE: MEETS OR EXCEEDS UL943 (CLASS A GFCI), UL498. FEED THROUGH TYPE, BACK-AND-SIDE WIRED,
TAMPER-RESISTANT, WEATHER RESISTANT SELF-TESTING, 20 AMP, 125VAC. HUBBELL GFR5362SB, COOPER WRVGF20, PASS & SEYMOUR 2095TRWR, OR APPROVED
EQUIVALENT.
E. COMBINATION TAMPER-RESISTANT COMMERCIAL-GRADE DUPLEX CONVENIENCE RECEPTACLES WITH (2) USB PORTS, 125 V, 20 A AND MINIMUM CHARGING OUTPUT OF 3.1
A. COMPLY WITH NEMA WD 1, NEMA WD 6 CONFIGURATION 5-20R, UL 498 SUPPLEMENT SD AND FEDERAL SPECIFICATION W-C-596.
F. CONTROLLED CONVENIENCE RECEPTACLES, 125 V, 20 A: COMPLY WITH NEMA WD 1, NEMA WD 6 CONFIGURATION 5-20R, UL 498 AND FEDERAL SPECIFICATION W-C-596.
MARKING PERMANENTLY PRINTED, MOLDED, OR STAMPED ON THE FACE OF THE RECEPTACLE AND IN COMPLIANCE WITH CONTROLLED RECEPTACLE MARKING
REQUIREMENTS STATED IN ARTICLE 406.3(E) OF THE 2014 NATIONAL ELECTRICAL CODE.
G. FINISH PLATES: COMMERCIAL GRADE THERMOPLASTIC, FINISH TO MATCH DEVICE FINISH.
2.7 SAFETY DISCONNECTS
A. TOGGLE TYPE DISCONNECT SWITCHES: 120 VOLT, 1-POLE, 20 AMP, 1 HP MAXIMUM. NEMA 1 ENCLOSURE FOR INDOORS, NEMA 3R ENCLOSURE FOR OUTDOORS.
B. MANUAL MOTOR STARTERS: QUICK-MAKE, QUICK-BREAK. THERMAL OVERLOAD PROTECTION. DEVICE LABELED WITH MAXIMUM VOLTAGE, CURRENT, AND HORSEPOWER.
PART 3 - EXECUTION
3.1 EXAMINATION
A. DRAWINGS ARE DIAGRAMMATIC WITH SYMBOLS REPRESENTING ELECTRICAL EQUIPMENT, OUTLETS, LUMINAIRES, AND WIRING. EXAMINE THE ENTIRE SET OF DRAWINGS
TO AVOID CONFLICTS WITH OTHER SYSTEMS. DETERMINE EXACT ROUTE AND INSTALLATION OF ELECTRICAL WIRING AND EQUIPMENT WITH CONDITIONS OF
CONSTRUCTION.
B. CLARIFICATION:
1. THE DRAWINGS GOVERN IN MATTERS OF QUANTITY, THE SPECIFICATION IN MATTERS OF QUALITY. IN EVENT OF CONFLICT ON DRAWINGS OR IN THE SPECIFICATIONS,
THE GREATER QUANTITY AND THE HIGHER QUALITY APPLY.
2. SHOULD THE ELECTRICAL DOCUMENTS INDICATE A CONDITION CONFLICTING WITH THE GOVERNING CODES AND REGULATIONS, REFRAIN FROM INSTALLING THAT
PORTION OF THE WORK UNTIL CLARIFIED BY ARCHITECT.
E 19203
EXP. 6-30-16
E
A
TE
LE
C T R I CA
L
IA
ENVIRONMENT. MAINTAIN FACTORY PACKAGING, AND IF REQUIRED, PROVIDE AN ADDITIONAL HEAVY CANVAS OR HEAVY PLASTIC COVER TO PROTECT ENCLOSURE(S)
FROM DIRT, WATER, CONSTRUCTION DEBRIS, AND TRAFFIC.
C. INSTALL EQUIPMENT REQUIRING ACCESS (I.E. JUNCTION BOXES, LUMINAIRES, POWER SUPPLIES, MOTORS, ETC.) SO THAT THEY MAY BE SERVICED, RESET, REPLACED OR
RECALIBRATED BY SERVICE PEOPLE WITH NORMAL SERVICE TOOLS AND EQUIPMENT. DO NOT INSTALL ELECTRICAL EQUIPMENT IN OBVIOUS PASSAGES, DOORWAYS,
SCUTTLES OR CRAWL SPACES WHICH WOULD IMPEDE OR BLOCK THE INTENDED USAGE.
D. NOISE CONTROL:
1. DO NOT INSTALL OUTLET BOXES BACK TO BACK. DO NOT USE STRAIGHT THROUGH BOXES.
2. DO NOT PLACE CONTACTORS, TRANSFORMERS, STARTERS AND SIMILAR NOISE PRODUCING DEVICES ON WALLS WHICH ARE COMMON TO OCCUPIED SPACES UNLESS
SPECIFICALLY CALLED FOR ON DRAWINGS. WHERE SUCH DEVICES MUST BE MOUNTED ON WALLS COMMON TO OCCUPIED SPACES, MOUNT OR ISOLATE IN SUCH A
MANNER AS TO EFFECTIVELY PREVENT THE TRANSMISSION OF THEIR INHERENT NOISE TO THE OCCUPIED SPACE.
E. FIRESTOPPING: COORDINATE LOCATION AND PROTECTION LEVEL OF FIRE AND/OR SMOKE RATED WALLS, CEILINGS, AND FLOORS. WHEN THESE ASSEMBLIES ARE
PENETRATED, SEAL AROUND CONDUIT AND EQUIPMENT WITH APPROVED FIRESTOPPING MATERIAL. INSTALL FIRESTOPPING MATERIAL COMPLETE AS DIRECTED THE
MANUFACTURER'S INSTALLATION INSTRUCTIONS. MEET REQUIREMENTS OF ASTM E814, STANDARD TEST METHOD FOR FIRE TESTS OF THROUGH-PENETRATION FIRE
STOPS.
F. CONDUIT:
1. CONDUIT JOINTS: ASSEMBLE CONDUITS CONTINUOUS AND SECURE TO BOXES, PANELS, LUMINAIRES AND EQUIPMENT WITH FITTINGS TO MAINTAIN CONTINUITY.
2. CONCEAL CONDUITS. EXPOSED CONDUITS ARE PERMITTED ONLY IN THE FOLLOWING AREAS:
a. MECHANICAL ROOMS, ELECTRICAL ROOMS OR SPACES WHERE WALLS, CEILINGS AND FLOORS WILL NOT BE COVERED WITH FINISHED MATERIALS.
b. EXISTING WALLS THAT ARE CONCRETE OR BLOCK CONSTRUCTION AND WHERE SPECIFICALLY NOTED ON THE DRAWINGS.
3. DO NOT INSTALL CONDUITS ON OR ACROSS FLOORS. WHERE EXPOSED CONDUITS ARE PERMITTED, INSTALL PARALLEL AND PERPENDICULAR TO WALLS, TIGHT TO
FINISHED SURFACES AND NEATLY OFFSET INTO BOXES.
4. KEEP CONDUITS A MINIMUM OF 12-INCHES AWAY FROM STEAM OR HOT WATER RADIANT HEATING LINES (AT OR ABOVE 104 DEGREES F) OR 3-INCHES AWAY FROM
WASTE OR WATER LINES.
5. KEEP 277/480 VOLT WIRING INDEPENDENT OF 120/208 VOLT WIRING. KEEP POWER WIRING INDEPENDENT OF COMMUNICATION SYSTEM WIRING. KEEP EMERGENCY
SYSTEM WIRING INDEPENDENT OF OTHER WIRING SYSTEMS.
6. MAXIMUM BENDS: INSTALL NO MORE THAN EQUIVALENT OF THREE 90 DEGREE BENDS BETWEEN ELECTRICAL BOXES. INSTALL NO MORE THAN EQUIVALENT OF TWO 90
DEGREE BENDS BETWEEN TELECOMMUNICATION BOXES. USE CONDUIT BODIES TO MAKE SHARP CHANGES IN DIRECTION, AS AROUND BEAMS.
7. FLEXIBLE CONDUIT: INSTALL 12 INCH MINIMUM SLACK LOOP ON FLEXIBLE METALLIC CONDUIT AND LIQUIDTIGHT FLEXIBLE METALLIC CONDUIT.
8. CONDUIT SIZE: MINIMUM TRADE SIZE 3/4 INCH.
9. CONDUIT USE LOCATIONS:
a. DRY, PROTECTED: RMC, IMC, EMT.
b. FOR SECURITY CONDUITS INSTALLED EXPOSED AND SUBJECT TO TAMPERING: RMC.
c. IN AREAS EXPOSED TO SEVERE MECHANICAL DAMAGE: RMC.
d. SHARP BENDS AND ELBOWS: RMC, EMT USE FACTORY ELBOWS.
e. INSTALL TWO PULL STRINGS/TAPES IN EMPTY RACEWAYS. SECURE PULL STRINGS/TAPES AT EACH END.
f. ELBOW FOR LOW ENERGY SIGNAL SYSTEMS: USE LONG RADIUS FACTORY ELLS WHERE LINKING SECTIONS OF RACEWAY FOR INSTALLATION OF SIGNAL CABLE.
g. FOR MOTORS, RECESSED LUMINAIRES AND EQUIPMENT CONNECTIONS SUBJECT TO MOVEMENT OR VIBRATION, USE FLEXIBLE METALLIC CONDUIT.
h. FOR MOTORS AND EQUIPMENT CONNECTIONS SUBJECT TO MOVEMENT OR VIBRATION AND SUBJECTED TO THE FOLLOWING CONDITIONS; EXTERIOR LOCATION,
MOIST OR HUMID ATMOSPHERE, WATER SPRAY, OIL OR GREASE: USE PVC COATED LIQUID TIGHT FLEXIBLE METALLIC CONDUIT.
G. CONDUIT FITTINGS:
1. USE SET SCREW TYPE FITTINGS ONLY IN DRY LOCATIONS. WHEN SET SCREW FITTINGS ARE UTILIZED, PROVIDE INSULATED CONTINUOUS EQUIPMENT GROUND
CONDUCTOR IN CONDUIT, FROM OVER CURRENT PROTECTION DEVICE TO OUTLET.
2. USE COMPRESSION FITTINGS IN DRY LOCATIONS, DAMP AND RAIN-EXPOSED LOCATIONS. MAXIMUM SIZE PERMITTED IN DAMP LOCATIONS AND LOCATIONS EXPOSED
TO RAIN IS 2 INCHES IN DIAMETER.
3. PROVIDE CORROSION-RESISTANT PUNCHED-STEEL BOX KNOCKOUT CLOSURES, CONDUIT LOCKNUTS AND PLASTIC CONDUIT BUSHINGS OF THE TYPE AND SIZE TO
SUIT EACH RESPECTIVE USE AND INSTALLATION.
4. USE INSULATED TYPE BUSHINGS WITH GROUND PROVISION AT SWITCHBOARDS, PANELBOARDS, SAFETY DISCONNECT SWITCHES, JUNCTION BOXES AND THE LIKE
THAT HAVE FEEDERS 60 AMPERES AND GREATER.
5. PROVIDE CONDUIT EXPANSION FITTINGS AT BUILDING EXPANSION JOINTS AND AT LOCATIONS WHERE CONDUIT IS EXPOSED TO THERMAL EXPANSION AND
CONTRACTION.
H. WIRES AND CABLES:
1. CONDUCTOR INSTALLATION: INSTALL CONDUCTORS WITH CARE TO AVOID DAMAGE TO INSULATION. DO NOT APPLY GREATER TENSION ON CONDUCTORS THAN
RECOMMENDED BY MANUFACTURER DURING INSTALLATION.
2. CONDUCTOR SIZE AND QUANTITY: INSTALL NO CONDUCTORS SMALLER THAN 12AWG UNLESS OTHERWISE SHOWN. PROVIDE REQUIRED CONDUCTORS FOR A FULLY
OPERABLE SYSTEM.
I.
BOXES:
1. ANCHORING: SECURE BOXES RIGIDLY TO THE SUBSTRATE UPON WHICH THEY ARE BEING MOUNTED, OR SOLIDLY EMBED BOXES IN CONCRETE OR MASONRY.
2. NOISE CONTROL: PROVIDE ACOUSTIC PUTTY PAD TO BACK SIDE OF EACH OUTLET BOX INSTALLED IN ACOUSTIC RATED WALLS.
3. COORDINATE ELECTRICAL DEVICE LOCATIONS AND ELEVATIONS (SWITCHES AND RECEPTACLES) WITH ARCHITECTURAL DRAWINGS TO PREVENT MOUNTING DEVICES
IN MIRRORS, BACK SPLASHES, AND BEHIND CABINETS.
4. PROVIDE WEATHERPROOF OUTLETS FOR LOCATIONS EXPOSED TO WEATHER OR MOISTURE.
5. KNOCKOUT CLOSURES: PROVIDE KNOCKOUT CLOSURES TO CAP UNUSED KNOCKOUT HOLES WHERE BLANKS HAVE BEEN REMOVED.
6. CODE COMPLIANCE: COMPLY WITH CEC AS APPLICABLE TO CONSTRUCTION AND INSTALLATION OF ELECTRICAL BOXES AND FITTINGS AND SIZE BOXES ACCORDING
TO CEC, EXCEPT AS NOTED OTHERWISE.
7. MOUNT CENTER OF OUTLET BOXES AS REQUIRED BY AMERICANS WITH DISABILITIES ACT (ADA), OR NOTED ON DRAWINGS, THE FOLLOWING DISTANCE ABOVE THE
FLOOR:
a. CONTROL SWITCHES: 46 INCHES.
b. RECEPTACLES: 18 INCHES.
c. WALL PHONES: 46 INCHES.
d. TELECOM OUTLETS: 18 INCHES.
e. OTHER OUTLETS: AS INDICATED IN OTHER SECTIONS OF SPECIFICATIONS OR AS DETAILED ON DRAWINGS.
J. PROVIDE CEC-REQUIRED DISCONNECT SWITCHES WHETHER SPECIFICALLY SHOWN ON DRAWINGS OR NOT. PROVIDE DISCONNECT SWITCH AT EACH MOTOR LOCATION
WITHIN 5 FEET UNLESS OTHERWISE NOTED. LOCATE DISCONNECT MEANS IN VIEW OF AND NOT INSIDE OF EQUIPMENT, SUCH THAT TOOLS ARE NOT NEEDED TO REMOVE
COVERS OF ENERGIZED EQUIPMENT TO ACCESS THE DISCONNECTING MEANS. COORDINATE FUSE AMPERE RATING WITH INSTALLED EQUIPMENT. FUSE AMPERE RATING
VARIANCE BETWEEN ORIGINAL DESIGN INFORMATION AND INSTALLED EQUIPMENT, SIZE IN ACCORDANCE WITH BUSSMANN FUSETRON 40C RECOMMENDATIONS. DO NOT
PROVIDE FUSES OF LOWER AMPERE RATING THAN MOTOR STARTER THERMAL UNITS. PROVIDE ARC FLASH LABELS.
K. SUPPORTING DEVICES:
1. SAFETY FACTOR OF 4 REQUIRED FOR EVERY FASTENING DEVICE OR SUPPORT FOR ELECTRICAL EQUIPMENT INSTALLED. SUPPORT TO WITHSTAND FOUR TIMES
WEIGHT OF EQUIPMENT IT SUPPORTS. PROVIDE SEISMIC BRACING PER CBC REQUIREMENTS FOR THIS BUILDING LOCATION.
2. PROVIDE VERTICAL SUPPORT MEMBERS FOR EQUIPMENT AND LUMINAIRES, STRAIGHT AND PARALLEL TO BUILDING WALLS. PROVIDE HORIZONTAL SUPPORT MEMBERS
STRAIGHT AND PARALLEL TO CEILINGS OR FINISHED FLOOR, UNLESS OTHERWISE NOTED.
3. PROVIDE INDEPENDENT SUPPORTS TO STRUCTURAL MEMBER FOR LUMINAIRES, ELECTRICAL MATERIALS, OR EQUIPMENT INSTALLED IN OR ON CEILING, WALLS OR IN
VOID SPACES OR OVER FURRED OR SUSPENDED CEILINGS.
4. DO NOT USE OTHER TRADE'S FASTENING DEVICES AS SUPPORTING MEANS FOR LUMINAIRES, ELECTRICAL MATERIALS, OR EQUIPMENT.
5. DO NOT FASTEN SUPPORTS TO PIPES, DUCTS, MECHANICAL EQUIPMENT OR CONDUIT.
6. DO NOT USE SUPPORTS OR FASTENING DEVICES TO SUPPORT OTHER THAN ONE PARTICULAR ITEM.
7. SUPPORT CONDUITS WITHIN 18 INCHES OF OUTLETS, BOXES, PANELS, CABINETS AND DEFLECTIONS. MAXIMUM DISTANCE BETWEEN SUPPORTS NOT TO EXCEED 8
FOOT SPACING.
8. SUPPORT FLEXIBLE CONDUITS AND MC CABLE WITHIN 12 INCHES OF OUTLETS, BOXES, PANELS, CABINETS AND DEFLECTIONS. MAXIMUM DISTANCE BETWEEN
SUPPORTS NOT TO EXCEED 4 FOOT SPACING.
9. SECURELY SUSPEND JUNCTION BOXES, PULL BOXES OR OTHER CONDUIT TERMINATING HOUSINGS LOCATED ABOVE SUSPENDED CEILING FROM THE FLOOR ABOVE
OR ROOF STRUCTURE TO PREVENT SAGGING AND SWAYING.
10. PROVIDE SEISMIC BRACING PER CBC REQUIREMENTS.
L. ELECTRICAL IDENTIFICATION:
1. CONDUCTOR IDENTIFICATION: APPLY MARKERS ON EACH CONDUCTOR FOR POWER, CONTROL, SIGNALING AND COMMUNICATIONS CIRCUITS.
2. PROVIDE AN ENGRAVED LABEL ON EACH MAJOR UNIT OF ELECTRICAL EQUIPMENT INDICATING BOTH EQUIPMENT NAME AND CIRCUIT SERVING EQUIPMENT, INCLUDING
BUT NOT LIMITED TO THE FOLLOWING ITEMS: DISCONNECT SWITCHES, RELAYS, CONTACTORS, TIME SWITCHES, OVERRIDE SWITCHES, SERVICE DISCONNECTS,
DISTRIBUTION SWITCHES, SWITCHBOARDS, BRANCH CIRCUIT PANELBOARDS, AND TRANSFORMERS.
3. INSTALL ENGRAVED LABEL ON THE INSIDE OF FLUSH PANELS, VISIBLE WHEN DOOR IS OPENED. INSTALL LABEL ON OUTSIDE OF SURFACE PANEL. SECURE
NAMEPLATES TO INSIDE SURFACE OF DOOR ON PANELBOARD THAT IS RECESSED IN FINISHED LOCATIONS.
4. ON THE BACK OF RECEPTACLE AND SWITCH FINISH PLATES LEGIBLY WRITE WITH INDELIBLE INK PEN THE CIRCUIT THAT EACH DEVICE IS CONNECTED TO.
M. GROUNDING:
1. PERFORMANCE REQUIREMENTS: SUPPLEMENT THE GROUNDED NEUTRAL OF THE SECONDARY DISTRIBUTION SYSTEM WITH AN EQUIPMENT GROUNDING SYSTEM TO
PROPERLY SAFEGUARD THE EQUIPMENT AND PERSONNEL. INSTALL EQUIPMENT GROUNDING SUCH THAT METALLIC STRUCTURES, ENCLOSURES, RACEWAYS,
JUNCTION BOXES, OUTLET BOXES, CABINETS, MACHINE FRAMES, PORTABLE EQUIPMENT AND OTHER CONDUCTIVE ITEMS IN CLOSE PROXIMITY WITH ELECTRICAL
CIRCUITS OPERATE CONTINUOUSLY AT GROUND POTENTIAL AND PROVIDE A LOW IMPEDANCE PATH FOR POSSIBLE GROUND FAULT CURRENTS.
2. RACEWAY GROUNDING:
a. GROUND METALLIC RACEWAY SYSTEMS. BOND TO GROUND TERMINAL WITH CODE SIZE JUMPER EXCEPT WHERE CODE SIZE OR LARGER GROUNDING
CONDUCTOR IS INCLUDED WITH CIRCUIT, USE GROUNDING BUSHING WITH LAY-IN LUG.
b. CONNECT METAL RACEWAYS, WHICH TERMINATE WITHIN AN ENCLOSURE BUT WITHOUT MECHANICAL CONNECTION TO THE ENCLOSURE, BY GROUNDING
BUSHINGS AND GROUND WIRE TO THE GROUNDING BUS.
c. WHERE EQUIPMENT SUPPLY CONDUCTORS ARE IN FLEXIBLE METALLIC CONDUIT, INSTALL STRANDED COPPER EQUIPMENT GROUNDING CONDUCTOR FROM
OUTLET BOX TO EQUIPMENT FRAME.
d. INSTALL EQUIPMENT GROUNDING CONDUCTOR, CODE SIZE MINIMUM IN NONMETALLIC AND METALLIC RACEWAY SYSTEMS.
3. BOXES, CABINETS, ENCLOSURES AND PANELBOARDS:
a. BOND GROUNDING CONDUCTORS TO ENCLOSURE WITH SPECIFIED CONDUCTORS AND LUGS. INSTALL LUGS ONLY ON THOROUGHLY CLEANED CONTACT
SURFACES.
b. BOND SECTIONS OF SERVICE EQUIPMENT ENCLOSURE TO SERVICE GROUND BUS.
4. PROVIDE TELECOMMUNICATIONS GROUNDING BAR AT EACH TELECOMMUNICATIONS BACKBOARD. MOUNT TELECOMMUNICATIONS GROUNDING BAR 84-INCHES ABOVE
FINISHED FLOOR, JUST BELOW OVERHEAD CABLE RUNWAY. BOND THE GROUNDING BAR TO SERVICE GROUNDING BAR IN THE MAIN SERVICE EQUIPMENT WITH A 6AWG
COPPER EQUIPMENT GROUNDING CONDUCTOR.
5. MOTORS, EQUIPMENT AND APPLIANCES: INSTALL CODE SIZE EQUIPMENT GROUNDING CONDUCTOR FROM OUTLET BOX TO (MOTOR) EQUIPMENT FRAME OR
MANUFACTURER'S DESIGNATED GROUND TERMINAL.
6. RECEPTACLES: CONNECT GROUND TERMINAL OF RECEPTACLE TO EQUIPMENT GROUND SYSTEM BY NO. 14 CONDUCTOR BOLTED TO OUTLET BOX. SELF GROUNDING
NATURE OF RECEPTACLE DEVICES DOES NOT ELIMINATE CONDUCTOR BOLTED TO OUTLET BOX.
N. FUSES: FOR EACH CLASS AND AMPERE RATING OF FUSE INSTALLED, PROVIDE THREE SPARE FUSES.
O. CONTROL DEVICES:
1. CONTACTORS:
a. PROVIDE VIBRATION ISOLATION MOUNTING PADS FOR ELECTRICALLY HELD CONTACTORS INSTALLED WITHIN OR ON WALLS WHICH ARE COMMON TO OCCUPIED
SPACES. ISOLATE TERMINALS AND OPERATING MECHANISMS FROM ENCLOSURE.
b. INSTALL CONTACTORS AND RELAYS TO REDUCE NOISE SUCH THAT IT WILL NOT CREATE A DISTURBANCE OR DISTRACTION IN THE AREAS IN WHICH SUCH
EQUIPMENT IS LOCATED.
2. EMERGENCY RELAY (UL924):
a. PROVIDE UNSWITCHED EMERGENCY CIRCUIT, AND UNSWITCHED AND SWITCHED NORMAL CIRCUIT TO UL924 RELAY FOR CONTROL OF EMERGENCY LUMINAIRES
WITH REMAINING ROOM LUMINAIRES ON NORMAL POWER.
b. INSTALL EACH RELAY WITHIN DEDICATED 4-11/16-INCH JUNCTION BOX WITH DOUBLE-GANG PLASTER RING FOR WALL OR CEILING FLUSH-MOUNT AS INDICATED ON
DRAWINGS. WHERE LOCATION IN CEILING WOULD INTERFERE WITH REMOVAL OF CEILING TILES, INSTALL RELAY FLUSH-MOUNTED IN NEAREST WALL AT CEILING
LEVEL. DO NOT LOCATE BEHIND WALL SWITCH.
P. LIGHTING:
1. INSTALL LUMINAIRES SECURELY, IN NEAT AND WORKMANLIKE MANNER.
2. INSTALL LUMINAIRE OF TYPES INDICATED WHERE SHOWN AND AT INDICATED HEIGHTS; IN ACCORDANCE WITH MANUFACTURER'S WRITTEN INSTRUCTIONS AND WITH
RECOGNIZED INDUSTRY PRACTICES TO ENSURE THAT LUMINAIRES COMPLY WITH REQUIREMENTS AND SERVE INTENDED PURPOSES.
3. ALIGN, MOUNT AND LEVEL LUMINAIRES UNIFORMLY. USE BALL HANGERS FOR SUSPENDED STEM MOUNTED LUMINAIRES.
4. AVOID INTERFERENCE WITH AND PROVIDE CLEARANCE FOR EQUIPMENT. WHERE THE INDICATED LOCATIONS FOR THE LUMINAIRES CONFLICT WITH LOCATIONS FOR
EQUIPMENT, CHANGE LOCATIONS FOR THE LUMINAIRE AS DIRECTED BY ARCHITECT.
5. SUSPENDED LUMINAIRES: MOUNTING HEIGHTS INDICATE CLEARANCES BETWEEN BOTTOM OF LUMINAIRE AND FINISHED FLOORS.
6. SUPPORT LUMINAIRES: ANCHOR SUPPORTS TO STRUCTURAL SLAB OR TO STRUCTURAL MEMBERS WITHIN A PARTITION, OR ABOVE A SUSPENDED CEILING. MAINTAIN
LUMINAIRE POSITIONS AFTER CLEANING AND RELAMPING. SUPPORT LUMINAIRES WITHOUT CAUSING CEILING OR PARTITION TO DEFLECT.
7. PROVIDE RECESSED FLUORESCENT LUMINAIRES WITH TWO SUPPORT WIRES AS REQUIRED BY CBC.
8. WIRING:
a. RECESSED LUMINAIRES TO BE INSTALLED USING FLEXIBLE METALLIC CONDUIT WITH LUMINAIRE CONDUCTORS SPLICED TO BRANCH CIRCUIT CONDUCTORS IN
NEARBY ACCESSIBLE JUNCTION BOX OVER CEILING. JUNCTION BOX FASTENED TO BUILDING STRUCTURAL MEMBER WITHIN 6 FEET OF LUMINAIRE.
b. INSTALL LUMINAIRES FOR LIFT OUT AND REMOVAL FROM CEILING PATTERN WITHOUT DISCONNECTING CONDUCTORS OR DEFACING CEILING MATERIALS.
c. FLEXIBLE CONNECTIONS WHERE PERMITTED TO EXPOSED LUMINAIRES; NEAT AND STRAIGHT, WITHOUT EXCESS SLACK, ATTACHED TO SUPPORT DEVICE.
d. INSTALL JUNCTION BOX, FLEXIBLE CONDUIT AND HIGH TEMPERATURE INSULATED CONDUCTORS FOR THROUGH WIRING OF RECESSED LUMINAIRES.
9. RELAMP LUMINAIRES WHICH HAVE FAILED LAMPS AT SUBSTANTIAL COMPLETION.
10. REPLACE BALLASTS DEEMED AS EXCESSIVELY NOISY BY ARCHITECT, ENGINEER, OR OWNER.
11. INSTALL SUSPENDED LUMINAIRES AND EXIT SIGNS USING PENDANTS SUPPORTED FROM SWIVEL HANGERS. PROVIDE PENDANT LENGTH REQUIRED TO SUSPEND
LUMINAIRE AT INDICATED HEIGHT.
12. INSTALL SURFACE MOUNTED LUMINAIRES AND EXIT SIGNS PLUMB AND ADJUST TO ALIGN WITH BUILDING LINES AND WITH EACH OTHER. SECURE TO PREVENT
MOVEMENT.
13. MAKE WIRING CONNECTIONS TO BRANCH CIRCUIT USING BUILDING WIRE WITH INSULATION SUITABLE FOR TEMPERATURE CONDITIONS WITHIN LUMINAIRE.
14. WHERE REMOTE BALLASTS OR DRIVERS ARE REQUIRED, INSURE ADEQUATE ACCESSIBILITY. UPSIZE CONDUCTORS BETWEEN LUMINAIRE AND BALLAST/DRIVER TO
ACCOMMODATE VOLTAGE DROP.
ST
PART 1 GENERAL
1.1 SUMMARY
A. ELECTRICAL SYSTEMS REQUIRED FOR THIS WORK INCLUDES LABOR, MATERIALS, EQUIPMENT, AND SERVICES NECESSARY TO COMPLETE INSTALLATION OF ELECTRICAL
WORK SHOWN ON DRAWINGS, SPECIFIED HEREIN OR REQUIRED FOR A COMPLETE OPERABLE FACILITY AND NOT SPECIFICALLY DESCRIBED IN OTHER SECTIONS OF THESE
SPECIFICATIONS. AMONG THE ITEMS REQUIRED ARE:
1. DISTRIBUTION EQUIPMENT SHOWN ON DRAWINGS.
2. FEEDERS TO DISTRIBUTION PANELS, HEATING, VENTILATING AND AIR CONDITIONING (HVAC) EQUIPMENT, OWNER-PROVIDED EQUIPMENT, AND OTHER EQUIPMENT AS
DETAILED.
3. BRANCH CIRCUIT WIRING FROM THE DISTRIBUTION PANELS FOR LIGHTING, RECEPTACLES, MOTORS, AND OTHER DETAILED CIRCUIT WIRING.
4. LUMINAIRES, CONTROL SWITCHES, RECEPTACLES, RELAYS, SUPPORTS AND OTHER ACCESSORY ITEMS.
5. WIRING AND POWER CONNECTIONS FOR MOTORS INSTALLED FOR HEATING, COOLING AND VENTILATION.
6. ARC-FLASH HAZARD ANALYSIS
B. FEES:
1. OBTAIN AND PAY FOR ELECTRICAL PERMITS, PLAN REVIEW, AND INSPECTIONS FROM LOCAL AUTHORITY HAVING JURISDICTION (AHJ).
1.2 DEFINITIONS
A. FOLLOWING IS A LIST OF ABBREVIATIONS GENERALLY USED IN THIS DIVISION:
1. ADA
AMERICANS WITH DISABILITIES ACT.
2. AHJ
AUTHORITY HAVING JURISDICTION.
3. CBC
CALIFORNIA BUILDING CODE.
4. CEC
CALIFORNIA ELECTRICAL CODE.
5. CFC
CALIFORNIA FIRE CODE.
6. CEC
T24
CALIFORNIA ENERGY CODE TITLE 24.
7. HVAC HEATING, VENTILATING AND AIR CONDITIONING.
8. IEEE
INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS.
9. IES
ILLUMINATING ENGINEERING SOCIETY
10. LEED
LEADERSHIP IN ENERGY AND ENVIRONMENTAL DESIGN
11. NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION.
12. NFPA
NATIONAL FIRE PROTECTION ASSOCIATION.
13. OSHA OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION.
14. UL
UNDERWRITERS LABORATORIES INC.
15. USGBC UNITED STATES GREEN BUILDING COUNCIL
B. PROVIDE: TO FURNISH AND INSTALL, COMPLETE AND READY FOR THE INTENDED USE.
C. FURNISH: SUPPLY AND DELIVER TO THE PROJECT SITE, READY FOR UNPACKING, ASSEMBLY AND INSTALLATION.
D. INSTALL: INCLUDES UNLOADING, UNPACKING, ASSEMBLING, ERECTING, INSTALLATION, APPLYING, FINISHING, PROTECTING, CLEANING AND SIMILAR OPERATIONS AT THE
PROJECT SITE AS REQUIRED TO COMPLETE ITEMS OF WORK FURNISHED BY OTHERS.
1.3 SUBMITTALS
A. OPERATION AND MAINTENANCE DOCUMENTATION: PROVIDE COPIES OF CERTIFICATES OF CODE AUTHORITY ACCEPTANCE, TEST DATA, PRODUCT DATA, GUARANTEES,
WARRANTIES, AND THE LIKE.
B. SHOP DRAWINGS: PROVIDE SHOP DRAWINGS WHICH INCLUDE PHYSICAL CHARACTERISTICS, ELECTRICAL CHARACTERISTICS, DEVICE LAYOUT PLANS, WIRING DIAGRAMS,
AND THE LIKE. PROVIDE PRODUCT SUBMITTALS AND SHOP DRAWINGS IN EITHER PAPER FORMAT OR ELECTRONIC FORMAT. ELECTRONIC FORMAT MUST BE SUBMITTED VIA
EMAIL OR FTP SITE. FOR PAPER HARDCOPY, PROVIDE ONE COMPLETE BINDER WITH TABBED DIVIDERS CONTAINING A SEPARATE SUBMITTAL FOR EACH SPECIFICATIONS
SECTION. FOR ELECTRONIC FORMAT, PROVIDE ONE ZIP FILE PER SPECIFICATION DIVISION CONTAINING A SEPARATE FILE FOR EACH SPECIFICATIONS SECTION. INDIVIDUAL
SUBMITTALS SENT PIECEMEAL IN A PER SPECIFICATION SECTION METHOD WILL BE RETURNED WITHOUT REVIEW OR COMMENT. COPY ARCHITECT ON ALL SUBMISSIONS.
1. IDENTIFY EACH SUBMITTAL IN DETAIL. NOTE WHAT DIFFERENCES, IF ANY, EXIST BETWEEN THE SUBMITTED ITEM AND THE SPECIFIED ITEM. FAILURE TO IDENTIFY THE
DIFFERENCES WILL BE CONSIDERED CAUSE FOR DISAPPROVAL. IF DIFFERENCES ARE NOT IDENTIFIED AND/OR NOT DISCOVERED DURING THE SUBMITTAL REVIEW
PROCESS, CONTRACTOR REMAINS RESPONSIBLE FOR PROVIDING EQUIPMENT AND MATERIALS THAT MEET THE SPECIFICATIONS AND DRAWINGS.
2. PROVIDE THE FOLLOWING INFORMATION FOR LIGHTING SUBMITTALS: INCLUDE ELECTRICAL RATINGS, DIMENSIONS, MOUNTING, MATERIAL, REQUIRED CLEARANCES,
TERMINATIONS, WIRING AND CONNECTION DIAGRAMS, PHOTOMETRIC DATA, DIFFUSERS, LOUVERS, BALLAST TYPE AND QUANTITIES, LAMP TYPE AND QUANTITIES.
3. PROVIDE SAMPLES OF NFPA 70E COMPLIANT ARC FLASH HAZARD LABELING FOR ELECTRICAL EQUIPMENT.
4. MAXIMUM OF TWO REVIEWS OF COMPLETE SUBMITTAL PACKAGE. ARRANGE FOR ADDITIONAL REVIEWS AND/OR EARLY REVIEW OF LONG-LEAD ITEMS; BEAR COSTS OF
THESE ADDITIONAL REVIEWS AT ENGINEER'S HOURLY RATES. INCOMPLETE SUBMITTAL PACKAGES/SUBMITTALS WILL BE RETURNED TO CONTRACTOR WITHOUT
REVIEW.
C. RECORD DRAWINGS: SHOW CHANGES AND DEVIATIONS FROM THE DRAWINGS. INCLUDE WRITTEN ADDENDUM AND CHANGE ORDER ITEMS. MAKE CHANGES TO
DRAWINGS IN ELECTRONIC FORMAT. OBTAIN ELECTRONIC COPY FROM ARCHITECT, USE THE SAME VERSION OF AUTOCAD TO PREPARE RECORD DRAWINGS AS WAS USED
BY THE ARCHITECT. PROVIDE ELECTRONIC COPY AND HARD COPY TO ENGINEER FOR REVIEW.
1.4 QUALITY ASSURANCE
A. CONFORM TO THE LATEST ADOPTED VERSION OF THE CALIFORNIA ELECTRIC CODE (CEC), WITH LOCAL AMENDMENTS.
B. FURNISH PRODUCTS LISTED BY UNDERWRITERS LABORATORIES INC. (UL) OR OTHER TESTING FIRM ACCEPTABLE TO AHJ.
C. USE MANUFACTURER'S PUBLISHED TESTING AND ADJUSTING PROCEDURES TO ADJUST SENSORS' TIME DELAY, DAYLIGHT SENSITIVITY, AND PASSIVE INFRARED
SENSITIVITY TO SATISFACTION OF THE OWNER.
D. REGULATORY REQUIREMENTS:
1. PROVIDE LUMINAIRES ACCEPTABLE TO CODE AUTHORITY FOR APPLICATION AND LOCATION AS INDICATED.
2. COMPLY WITH APPLICABLE ANSI STANDARDS.
3. COMPLY WITH APPLICABLE NEMA STANDARDS.
4. PROVIDE LUMINAIRES AND LAMPHOLDERS THAT COMPLY WITH UL STANDARDS AND HAVE BEEN LISTED AND LABELED FOR LOCATION AND USE INDICATED BY A
TESTING AGENCY ACCEPTABLE BY THE AHJ (E.G. UL, ETL, AND THE LIKE).
5. COMPLY WITH CEC AS APPLICABLE TO INSTALLATION AND CONSTRUCTION OF LUMINAIRES.
6. COMPLY WITH FALLOUT AND RETENTION REQUIREMENTS OF CBC FOR DIFFUSERS, BAFFLES, AND LOUVERS.
7. PROVIDE SIMILAR LAMPS AND BALLASTS FROM COMMON MANUFACTURER (E.G. ALL FLUORESCENT LAMPS FROM OSRAM/SYLVANIA, AND ALL MR LAMPS FROM USHIO)
UNLESS INDICATED OTHERWISE IN THE LUMINAIRE SCHEDULE.
1.5 SEQUENCING AND SCHEDULING
A. FOR THE PROPER EXECUTION OF THE WORK, COOPERATE WITH OTHER CRAFTS AND CONTRACTS AS NEEDED.
B. TO AVOID INSTALLATION CONFLICTS, THOROUGHLY EXAMINE THE COMPLETE SET OF CONTRACT DOCUMENTS. RESOLVE CONFLICTS PRIOR TO INSTALLATION.
C. PRIOR TO INSTALLATION OF FEEDERS TO EQUIPMENT REQUIRING ELECTRICAL CONNECTIONS, EXAMINE THE MANUFACTURER'S SHOP DRAWINGS, WIRING DIAGRAMS,
PRODUCT DATA, AND INSTALLATION INSTRUCTIONS. VERIFY THAT THE ELECTRICAL CHARACTERISTICS DETAILED IN THE CONTRACT DOCUMENTS ARE CONSISTENT WITH
THE ELECTRICAL CHARACTERISTICS OF THE ACTUAL EQUIPMENT BEING INSTALLED.
1.6 WARRANTY
A. GUARANTEE ELECTRICAL WORK AGAINST FAULTY MATERIAL OR WORKMANSHIP FOR A PERIOD OF ONE YEAR FROM THE DATE OF FINAL COMPLETION BY THE OWNER.
B. BALLAST MANUFACTURER'S WARRANTY: NOT LESS THAN 5 YEARS FOR ELECTRONIC TYPE BALLASTS, BASED ON DATE OF SUBSTANTIAL COMPLETION. INCLUDE NORMAL
COST OF LABOR FOR REPLACEMENT OF BALLAST.
C. LINEAR T8 AND T5 LAMP AND BALLAST COMBINATION WARRANTY: PROVIDE BALLAST AND LAMP COMBINATIONS WHICH WILL RESULT IN WRITTEN FACTORY WARRANTY
COVERING LAMPS FOR 3 YEARS AND BALLASTS FOR 5 YEARS, BASED ON DATE OF SUBSTANTIAL COMPLETION.
D. LAMP WARRANTY: 30 DAYS FOR INCANDESCENT, 12 MONTHS FOR COMPACT FLUORESCENT, 36 MONTHS FOR FLUORESCENT AND 12 MONTHS FOR HID LAMPS.
E. LED WARRANTY: LED SYSTEMS AND COMPLETE LUMINAIRES MUST HAVE MANUFACTURER'S WARRANTY OF 3 YEARS FROM DATE OF SUBSTANTIAL COMPLETION, INCLUDING
DRIVERS.
PART 2 PRODUCTS
2.1 MATERIALS
A. BASE CONTRACT UPON FURNISHING MATERIALS AS SPECIFIED. MATERIALS, EQUIPMENT, AND FIXTURES USED FOR CONSTRUCTION ARE TO BE NEW, LATEST PRODUCTS
AS LISTED IN MANUFACTURER'S PRINTED CATALOG DATA AND ARE TO BE UL APPROVED OR HAVE ADEQUATE APPROVAL OR BE ACCEPTABLE BY STATE, COUNTY, AND CITY
AUTHORITIES. EQUIPMENT/FIXTURE SUPPLIER IS RESPONSIBLE FOR OBTAINING STATE, COUNTY, AND CITY ACCEPTANCE ON EQUIPMENT/FIXTURE NOT UL APPROVED OR
NOT LISTED FOR INSTALLATION.
B. INCLUDE SPECIAL FEATURES, FINISHES, ACCESSORIES, AND OTHER REQUIREMENTS AS DESCRIBED IN THE CONTRACT DOCUMENTS REGARDLESS OF THE ITEM'S LISTED
CATALOG NUMBER.
C. PROVIDE INCIDENTALS NOT SPECIFICALLY MENTIONED HEREIN OR NOTED ON DRAWINGS, BUT NEEDED TO COMPLETE THE SYSTEM OR SYSTEMS, IN A SAFE AND
SATISFACTORY WORKING CONDITION.
D. FIRESTOPPING FOAM SEALANT: FOAM SEALANT FOR USE AROUND CONDUIT PENETRATIONS TO PREVENT PASSAGE OF SMOKE, FIRE, TOXIC GAS OR WATER. MAINTAIN
SEAL BEFORE, DURING AND AFTER FIRE. IN AND AROUND CONDUIT FOR THERMAL BREAK AT PENETRATION OF BARRIER BETWEEN HEATED AND UNHEATED SPACES. HILTI,
3M, CHASE TECHNOLOGY CORPORATION CTC PR-855, FIRE FOAM, THOMAS & BETTS, OR APPROVED EQUIVALENT.
2.2 RACEWAYS
A. RIGID METAL CONDUIT (RMC): HOT-DIP GALVANIZED AFTER THREAD CUTTING. MANUFACTURED IN CONFORMANCE WITH UL 6, ANSI C80.1. UNIFORM FINISH COAT WITH
CHROMATE FOR ADDED PROTECTION. MANUFACTURERS: ALLIED TUBE & CONDUIT, BECK MANUFACTURING WL, PICOMA, OR APPROVED EQUIVALENT.
B. ELECTRICAL METALLIC TUBING (EMT): STEEL GALVANIZED TUBING. MANUFACTURED IN CONFORMANCE WITH UL 797, ANSI C80.3. MANUFACTURERS: ALLIED TUBE &
CONDUIT, BECK MANUFACTURING WL, PICOMA, OR APPROVED EQUIVALENT.
C. FLEXIBLE METAL CONDUIT (FMC): INTERLOCKED STEEL CONSTRUCTION. MANUFACTURED IN CONFORMANCE WITH UL 1. MANUFACTURERS: AFC CABLE SYSTEMS INC.,
ELECTRI-FLEX COMPANY, INTERNATIONAL METAL HOSE, OR APPROVED EQUIVALENT.
D. SURFACE METAL RACEWAY SYSTEMS
1. LARGE COMPARTMENT, MULTI CHANNEL SURFACE RACEWAY:
a. POWER: PROVIDE 20 AMP, MULTI-OUTLET RACEWAY AS INDICATED ON DRAWINGS. WIREMOLD 5500 SERIES OR APPROVED EQUIVALENT.
b. SIGNAL: BLANK COVER WITH OUTLETS AS INDICATED ON DRAWINGS. WIREMOLD 5500 SERIES OR APPROVED EQUIVALENT.
2. PROVIDE PREWIRED RECEPTACLES AS NOTED ON DRAWINGS.
3. PROVIDE ENDCAPS, CORNER JOINTS, TEES, TRANSITION FITTINGS, AND THE LIKE, FOR A COMPLETE INSTALLATION.
4. FINISH: GRAY.
E. CONDUIT FITTINGS:
1. BUSHINGS: INSULATED TYPE FOR THREADED RIGID, CONDUIT OR RACEWAY CONNECTORS WITHOUT FACTORY INSTALLED PLASTIC THROAT CONDUCTOR PROTECTION.
MANUFACTURERS: THOMAS & BETTS 1222 SERIES, O-Z GEDNEY B SERIES, OR APPROVED EQUIVALENT.
2. GROUND BUSHINGS: INSULATED GROUNDING TYPE FOR THREADED RIGID, CONDUIT OR RACEWAY CONNECTORS. MANUFACTURERS: O-Z GEDNEY BLG SERIES OR
APPROVED EQUIVALENT.
3. RACEWAY CONNECTORS AND EMT COUPLINGS:
a. STEEL CONNECTORS, COUPLINGS, AND CONDUIT BODIES WITH ZINC ELECTROPLATE.
b. CONNECTOR LOCKNUTS ARE ZINC ELECTROPLATED STEEL, WITH THREADS MEETING ASTM TOLERANCES.
c. CONNECTOR THROATS HAVE FACTORY INSTALLED PLASTIC INSERTS PERMANENTLY INSTALLED. FOR NORMAL CABLE OR CONDUCTOR EXITING ANGLES FROM
RACEWAY, THE CABLE JACKET OR CONDUCTOR INSULATION BEARS ONLY ON PLASTIC THROAT INSERT.
4. EXPANSION/DEFLECTION FITTINGS:
a. EMT: USE O_Z GEDNEY TYPE TX, OR APPROVED EQUIVALENT.
b. RMC: USE O_Z GEDNEY TYPE AX, DX AND AXDX, OR APPROVED EQUIVALENT.
2.3 WIRES AND CABLES
A. COPPER, 600 VOLT RATED THROUGHOUT. CONDUCTORS 14AWG TO 10AWG, SOLID. CONDUCTORS 8AWG AND LARGER, STRANDED. PHASE COLOR TO BE CONSISTENT AT
FEEDER TERMINATIONS; A-B-C, TOP TO BOTTOM, LEFT TO RIGHT, FRONT TO BACK. CONDUCTORS 3AWG AND LARGER, MINIMUM INSULATION RATING OF 75C. INSULATION
TYPES THWN, THHN OR XHHW. MINIMUM INSULATION RATING OF 90C FOR BRANCH CIRCUITS. MANUFACTURERS: CAROL, GENERAL CABLE, OKONITE, SOUTHWIRE, OR
APPROVED EQUIVALENT.
2.4 CONNECTORS
A. COPPER PADS: DRILLED AND TAPPED FOR MULTIPLE CONDUCTOR TERMINALS.
B. LUGS: COMPRESSION TYPE FOR USE WITH STRANDED BRANCH CIRCUIT OR CONTROL CONDUCTORS; MECHANICAL LUGS NOT ACCEPTABLE. MANUFACTURERS:
ANDERSON, ILSCO, PANDUIT, THOMAS & BETTS, 3M, OR APPROVED EQUIVALENT.
C. CONDUCTOR BRANCH CIRCUITS: WIRE NUTS WITH INTEGRAL SPRING CONNECTORS FOR CONDUCTORS 18 THROUGH 8AWG. PUSH-IN TYPE CONNECTORS WHERE
CONDUCTORS ARE NOT REQUIRED TO BE TWISTED TOGETHER ARE NOT ACCEPTABLE. MANUFACTURERS: 3M, IDEAL, OR APPROVED EQUIVALENT.
D. FLUORESCENT LUMINAIRE DISCONNECT: POLYCARBONATE HOUSING, TIN-PLATED BRASS CONTACTS, INSULATED 18AWG, FACTORY-INSTALLED SOLID COPPER LEADS,
105C TEMPERATURE RATING, UL94-V2 FLAMMABILITY, 4A, 600V. CEC ARTICLE 410 COMPLIANT. FINGER-SAFE LINE SIDE. PUSH-AND-CLICK CONNECTOR. THOMAS & BETTS
STA-KON, LITHONIA OR APPROVED EQUIVALENT.
2.5 BOXES
A. LUMINAIRE OUTLET: 4-INCH OCTAGONAL BOX, 1-1/2 INCHES DEEP WITH 3/8-INCH LUMINAIRE STUD IF REQUIRED. PROVIDE RAISED COVERS ON BRACKET OUTLETS AND ON
CEILING OUTLETS. MANUFACTURER: HUBBELL, THOMAS & BETTS, OR APPROVED EQUIVALENT.
B. DEVICE OUTLET: INSTALLATION OF ONE OR TWO DEVICES AT COMMON LOCATION, MINIMUM 4-INCH SQUARE, MINIMUM 1-1/2 INCHES DEEP. SINGLE- OR TWO-GANG FLUSH
DEVICE RAISED COVERS. MANUFACTURER: HUBBELL, THOMAS & BETTS, OR APPROVED EQUIVALENT.
C. MULTIPLE DEVICES: THREE OR MORE DEVICES AT COMMON LOCATION. INSTALL ONE-PIECE GANG BOXES WITH ONE-PIECE DEVICE COVER, ONE DEVICE PER GANG.
D. MASONRY BOXES: OUTLETS IN CONCRETE. MANUFACTURER: HUBBELL, THOMAS & BETTS, OR APPROVED EQUIVALENT.
E. CONSTRUCTION: FOR INTERIOR LOCATIONS, PROVIDE GALVANIZED STEEL OUTLET WIRING BOXES, OF THE TYPE, SHAPE AND SIZE, INCLUDING DEPTH OF BOX, TO SUIT
EACH RESPECTIVE LOCATION AND INSTALLATION; CONSTRUCTED WITH STAMPED KNOCKOUTS IN BACK AND SIDES, AND WITH THREADED HOLES WITH SCREWS FOR
SECURING BOX COVERS OR WIRING DEVICES. PROVIDE OUTLET BOX ACCESSORIES FOR EACH INSTALLATION, INCLUDING MOUNTING BRACKETS, WALLBOARD HANGERS,
EXTENSION RINGS, LUMINAIRE STUDS, CABLE CLAMPS AND METAL STRAPS FOR SUPPORTING OUTLET BOXES, COMPATIBLE WITH OUTLET BOXES BEING USED AND
MEETING REQUIREMENTS OF INDIVIDUAL WIRING SITUATIONS.
F. JUNCTION AND PULL BOXES: ANSI 49 GRAY ENAMEL PAINTED SHEET STEEL JUNCTION AND PULL BOXES, WITH SCREW-ON COVERS; OF THE TYPE SHAPE AND SIZE, TO SUIT
EACH RESPECTIVE LOCATION AND INSTALLATION; WITH WELDED SEAMS AND EQUIPPED WITH STEEL NUTS, BOLTS, SCREWS AND WASHERS. INSTALL JUNCTION BOXES
ABOVE ACCESSIBLE CEILINGS FOR DROPS INTO WALLS FOR RECEPTACLE OUTLETS FROM OVERHEAD. INSTALL JUNCTION BOXES AND PULL BOXES TO FACILITATE THE
INSTALLATION OF CONDUCTORS AND LIMITING THE ACCUMULATED ANGULAR SUM OF BENDS BETWEEN BOXES, CABINETS AND APPLIANCES TO 270 DEGREES.
MANUFACTURER: B-LINE, HOFFMAN, OR APPROVED EQUIVALENT.
G. BOX EXTENSION ADAPTER: INSTALL OVER FLUSH WALL OUTLET BOXES TO PERMIT FLEXIBLE RACEWAY EXTENSION FROM FLUSH OUTLET TO FIXED OR MOVABLE
EQUIPMENT. MANUFACTURER: BELL 940 SERIES, RED DOT IHE4 SERIES, OR APPROVED EQUIVALENT.
2.8 SUPPORTING DEVICES
A. HANGERS, SUPPORTS, THREADED ROD AND FASTENERS: CORROSION-RESISTANT MATERIALS OF SIZE AND TYPE ADEQUATE TO CARRY THE LOADS OF EQUIPMENT AND
CONDUIT, INCLUDING WEIGHT OF WIRE IN CONDUIT. MANUFACTURERS: B-LINE, KINDORF, SUPERSTRUT, UNISTRUT, OR APPROVED EQUIVALENT.
B. ANCHORS: CORROSION-RESISTANT MATERIALS OF SIZE AND TYPE ADEQUATE TO CARRY THE LOADS OF EQUIPMENT AND CONDUIT, INCLUDING WEIGHT OF WIRE IN
CONDUIT. MANUFACTURERS: ANCHOR IT, EPCON SYSTEM, HILTI-HIT SYSTEM, POWER FAST SYSTEM, OR APPROVED EQUIVALENT.
C. CONCRETE INSERTS: CAST IN CONCRETE FOR SUPPORT FASTENERS FOR LOADS UP TO 800 LBS. MANUFACTURERS: B-LINE, KINDORF, SUPERSTRUT, UNISTRUT, OR
APPROVED EQUIVALENT.
D. PIPE STRAPS: TWO-HOLE GALVANIZED OR MALLEABLE IRON.
E. LUMINAIRE CHAIN: CAMPBELL CHAIN 75031 OR APPROVED EQUIVALENT, 90 LB. TEST WITH STEEL HOOKS.
2.9 ELECTRICAL IDENTIFICATION
A. NAMEPLATES: ENGRAVING STOCK MELAMINE OR LAMICOID PLASTIC LAMINATE, FEDERAL SPECIFICATION L-P-387, IN THE SIZE AND THICKNESSES INDICATED, ENGRAVED
WITH ENGRAVER'S STANDARD LETTER STYLE, MINIMUM 1/2-INCH HIGH LETTERS, BLACK WITH WHITE CORE (LETTER COLOR), PUNCHED FOR MECHANICAL FASTENING
EXCEPT WHERE ADHESIVE MOUNTING IS NECESSARY BECAUSE OF SUBSTRATE. PROVIDE 1/8-INCH THICK MATERIAL. USE SELF TAPPING STAINLESS STEEL SCREWS.
MANUFACTURER: B&I NAMEPLATES, INTELLICUM, JBR ASSOCIATES, OR APPROVED EQUIVALENT.
B. LABELS: ADHESIVE TAPE WITH 18 POINT BLACK LETTERS ON CLEAR BACKGROUND. USE ONLY FOR IDENTIFICATION OF INDIVIDUAL WALL SWITCHES AND RECEPTACLES,
CONTROL STATIONS, AND TELECOMMUNICATION OUTLETS. INDICATE DEVICE NAME, SOURCE PANEL, AND SOURCE CIRCUITS. DO NOT PROVIDE DYMO TAPE STYLE LABELS.
MANUFACTURER: KROY, BRADY, OR APPROVED EQUIVALENT.
C. CONDUCTOR NUMBERS: VINYL-CLOTH SELF-ADHESIVE TYPE WIRE MARKERS. EACH CONDUCTOR AT PULLBOXES, PANELBOARDS, OUTLET BOXES, JUNCTION BOXES, AND
EACH LOAD CONNECTION. BRANCH CIRCUIT OR FEEDER NUMBERS AS INDICATED ON DRAWINGS AND SOURCE PANEL. MANUFACTURER: BRADY, PANDUIT, SUMITOMO, OR
APPROVED EQUIVALENT.
D. BRANCH CIRCUIT SCHEDULES: PROVIDE BRANCH CIRCUIT IDENTIFICATION SCHEDULES, TYPEWRITTEN, CLEARLY FILLED OUT, TO IDENTIFY LOAD CONNECTED TO EACH
CIRCUIT AND LOCATION OF LOAD. NUMBERS TO CORRESPOND TO NUMBERS ASSIGNED TO EACH CIRCUIT BREAKER POLE POSITION.
E. RELAY PANEL SCHEDULE: PROVIDE TYPEWRITTEN SCHEDULE TO IDENTIFY THE INCOMING CIRCUIT, THE CONTROLLED LOAD, AND THE CONTROLLING DEVICES FOR EACH
RELAY.
F. CIRCUIT BREAKER IDENTIFICATION: PROVIDE PERMANENT IDENTIFICATION NUMBER IN OR ON PANELBOARD DEAD-FRONT ADJACENT TO EACH CIRCUIT BREAKER POLE
POSITION. HORIZONTAL CENTERLINE OF ENGRAVED NUMBERS TO CORRESPOND WITH CENTERLINE OF CIRCUIT BREAKER POLE POSITION.
2.10 GROUNDING MATERIALS
A. TELECOMMUNICATIONS GROUNDING BUSBAR (TGB): 1/4-INCH THICK BY 4-INCH HIGH BY 12-INCH LONG COPPER GROUND BAR WITH INSULATORS THAT MEET ANSI
J-STD-607-A SPECIFICATIONS. UL 467 LISTED. HOLE PATTERNS IN BUSSBAR TO ACCOMMODATE TWO-HOLE LUGS. MANUFACTURERS: CHATSWORTH, ERICO, SQUARE D,
PANDUIT OR APPROVED EQUIVALENT.
B. GROUNDING ELECTRODE CONDUCTOR: SOFT-DRAW BARE STRANDED CONDUCTOR FOR WIRE SIZES LARGER THAN #10 AWG BARE. SOLID COPPER FOR WIRE SIZES #10
AWG AND SMALLER.
C. EQUIPMENT GROUNDING CONDUCTOR: GREEN INSULATED, INSULATION TYPE TO MATCH THAT OF ASSOCIATED FEEDER OR BRANCH CIRCUIT WIRING, SIZE AS INDICATED
ON DRAWINGS.
2.11 OVERCURRENT PROTECTIVE DEVICES
A. FUSES: DUAL ELEMENT, TIME DELAY, CURRENT LIMITING, NONRENEWABLE TYPE, REJECTION FEATURE. UL CLASS J 1/10 TO 600 AMP, UL CLASS L, ABOVE 600 AMPS.
PROVIDE FUSE PULLERS FOR COMPLETE RANGE OF FUSES. MANUFACTURERS: BUSSMANN, GOULD-SHAWMUT, LITTELFUSE, OR APPROVED EQUIVALENT.
B. MOLDED CASE CIRCUIT BREAKERS:
1. ONE, TWO OR THREE-POLE BOLT ON, SINGLE HANDLE COMMON TRIP, AS INDICATED ON DRAWINGS.
2. OVERCENTER TOGGLE-TYPE MECHANISM, QUICK-MAKE, QUICK-BREAK ACTION. TRIP INDICATION IS BY HANDLE POSITION.
3. CALIBRATE FOR OPERATION IN 40C AMBIENT TEMPERATURE.
4. 15 TO 150 AMP BREAKERS: PERMANENT TRIP UNIT CONTAINING INDIVIDUAL THERMAL AND MAGNETIC TRIP ELEMENTS IN EACH POLE.
5. 151 TO 400 AMP BREAKERS: VARIABLE MAGNETIC TRIP ELEMENTS. PROVIDE PUSH-TO-TRIP BUTTON ON COVER ON BREAKER FOR MECHANICAL TRIPPING.
6. GREATER THAN 400 AMP: ELECTRONIC TRIP TYPE WITH ADJUSTMENTS FOR LONG-TIME, INSTANTANEOUS, AND SHORT-TIME FUNCTIONS. PROVIDE GROUND FAULT
FUNCTION FOR BREAKERS GREATER THAN 400 AMPS.
7. PROVIDE HANDLE MECHANISMS THAT ARE LOCKABLE IN THE OPEN (OFF) POSITION.
8. MANUFACTURERS: EATON ELECTRICAL, GENERAL ELECTRIC, SIEMENS, SQUARE D, OR APPROVED EQUIVALENT.
2.12 CONTROL DEVICES
A. EMERGENCY LIGHTING RELAY:
1. UL924 LISTED FOR CONNECTED LOAD OF 10 AMPS AT 277 VOLT OR 120 VOLT.
2. UL RATED N.C. CONTACTS, MINIMUM 10 AMPS RATING. INTEGRAL SURGE PROTECTION.
3. TWO SEPARATE STATUS EMERGENCY LIGHTING INDICATORS FOR TROUBLESHOOTING:
a. AMBER LED INDICATES PRESENCE OF NORMAL UTILITY POWER.
b. RED LED INDICATES PRESENCE OF UNSWITCHED EMERGENCY POWER.
4. MANUAL AND/OR AUTOMATIC DIAGNOSTIC TESTING FEATURE.
5. MANUFACTURER: NINE 24 BLTC-R, BODINE, WATTSTOPPER, OR APPROVED EQUIVALENT.
2.13 LUMINAIRES
A. LUMINAIRES: REFER TO DESCRIPTION AND MANUFACTURERS IN LUMINAIRE SCHEDULE.
B. WHERE RECESSED LUMINAIRES ARE INSTALLED IN CAVITIES INTENDED TO BE INSULATED, PROVIDE IC RATED LUMINAIRES OR OTHER CODE APPROVED INSTALLATION.
C. UL LABEL LUMINAIRES INSTALLED UNDER CANOPIES, ROOF OR OPEN PORCHES, AND SIMILAR DAMP OR WET LOCATIONS, AS SUITABLE FOR DAMP OR WET LOCATIONS.
D. SUSPENDED LUMINAIRES: PROVIDE MINIMUM 24-INCH ADJUSTABILITY IN AIRCRAFT CABLE LENGTH WHERE USED.
E. RECESSED LUMINAIRES: FRAME COMPATIBLE WITH CEILING MATERIAL INSTALLED AT PARTICULAR LUMINAIRE LOCATION. PROVIDE PROPER FACTORY TRIM AND FRAME
FOR LUMINAIRE TO FIT LOCATION AND CEILING MATERIAL. VERIFY WITH ARCHITECTURAL REFLECTED CEILING PLAN PRIOR TO SUBMITTALS.
F. FINISHES: MANUFACTURER'S STANDARD FINISH (UNLESS OTHERWISE INDICATED) OVER CORROSION RESISTANT PRIMER. WHITE OR SPECULAR FINISH WITH NOT LESS
THAN 85 PERCENT REFLECTANCE FOR INTERIOR LUMINAIRES.
G. LIGHT TRANSMITTING COMPONENTS: PLASTIC DIFFUSERS, MOLDED OR EXTRUDED OF 100 PERCENT VIRGIN ACRYLIC. PRISMATIC ACRYLIC, EXTRUDED, FLAT DIFFUSERS,
0.125-INCH OVERALL THICKNESS, UNLESS OTHERWISE NOTED.
H. FLUORESCENT LUMINAIRES:
1. PROVIDE OPEN LAMP FLUORESCENT LUMINAIRES WITHOUT DIFFUSERS OR GUARDS WITH TURRET TYPE, SPRING LOADED SOCKETS.
2. TO FACILITATE MULTILEVEL LAMP SWITCHING, WIRE LAMPS WITHIN LUMINAIRE WITH OUTERMOST LAMP AT BOTH SIDES OF LUMINAIRE ON THE SAME BALLAST, THE
NEXT INWARD PAIR ON ANOTHER BALLAST AND SO ON TO INNERMOST LAMP (OR PAIR OF LAMPS).
2.14 BALLASTS
A. BALLASTS, GENERAL:
1. PROVIDE BALLASTS UL RATED FOR SPECIFIED LAMPS,.
2. THERMAL PROTECTION: INTERNAL UL CLASS `P' WITH AUTOMATIC RESET.
3. SOUND RATINGS: CLASS 'A'. WHERE NOT AVAILABLE AS STANDARD PRODUCT FROM ANY SPECIFIED MANUFACTURER, PROVIDE QUIETEST RATING AVAILABLE.
4. TOTAL HARMONIC DISTORTION: NOT TO EXCEED 20 PERCENT OF THE INPUT CURRENT UNLESS OTHERWISE INDICATED.
5. INPUT VOLTAGE: PROVIDE UNIVERSAL VOLTAGE BALLAST MATCHING BRANCH CIRCUIT SUPPLY VOLTAGE.
6. PROVIDE QUANTITY OF BALLASTS TO PROVIDE SWITCHING AS INDICATED ON DRAWINGS. PROVIDE FACTORY PRINTED WIRING DIAGRAM ON BALLAST HOUSING.
7. COMPLY WITH FCC RULES AND REGULATIONS PART 18, CLASS A CONCERNING GENERATION OF BOTH ELECTROMAGNETIC INTERFERENCE AND RADIO FREQUENCY
INTERFERENCE.
B. BALLASTS FOR LINEAR FLUORESCENT LAMPS:
1. POWER FACTOR: MINIMUM 97 PERCENT.
2. DO NOT PROVIDE MAGNETIC FLUORESCENT BALLASTS.
3. LINEAR T8 BALLASTS: ANTI-STRIATION CIRCUITRY, AND UL TYPE CC RATED FOR ARC PROTECTION. COMPLIANT WITH NEMA/CEE HIGH PERFORMANCE T8 LIGHTING
SYSTEM SPECIFICATIONS AND LISTED WITH NEMA PREMIUM ELECTRONIC BALLAST PROGRAM.
4. NON-DIMMING ELECTRONIC:
a. TANDEM WIRING BETWEEN LUMINAIRES MAY BE USED TO MINIMIZE THE NUMBER OF BALLASTS WHILE ACCOMPLISHING THE SWITCHING REQUIREMENTS SHOWN
ON DRAWINGS. PROVIDE LABEL IN LAMP COMPARTMENT OF LUMINAIRE TO IDENTIFY THE FUNCTION OF BALLAST. LABEL SHALL NOT BE VISIBLE FROM ROOM.
b. PROVIDE BALLASTS THAT MEET REQUIREMENTS OF UL 935, ANSI C82.11 AND BEAR THE APPROPRIATE UL LABEL. PROVIDE BALLASTS THAT WITHSTAND INPUT
POWER LINE TRANSIENTS AS DEFINED IN ANSI C62.41, CATEGORY-A AND IEEE 587.
c. PROVIDE SERIES WIRED PROGRAMMED START BALLAST UNLESS NOTED ON DRAWINGS.
d. HIGH FREQUENCY OPERATION: NOT LESS THAN 42KHZ.
e. INTEGRAL END OF LAMP LIFE DETECTION AND SHUTDOWN CIRCUIT WITH AUTOMATIC RESET.
f. LAMP CREST FACTOR: MAXIMUM 1.7 FOR PROGRAMMED RAPID START BALLASTS AND MAXIMUM 1.85 OR LESS FOR INSTANT START BALLASTS.
g. AVERAGE BALLAST FACTOR (BF): MINIMUM 88 PERCENT OR AS INDICATED IN THE LUMINAIRE SCHEDULE.
h. PROVIDE 0 DEGREE FAHRENHEIT MINIMUM STARTING TEMPERATURE BALLASTS FOR LUMINAIRES INSTALLED WHERE EXPOSED TO ANTICIPATED AMBIENT
TEMPERATURE LESS THAN 55 DEGREES FAHRENHEIT.
i.
MANUFACTURERS: PHILIPS, UNIVERSAL LIGHTING TECHNOLOGIES, OSRAM/SYLVANIA, OR APPROVED EQUIVALENT.
5. DIMMING ELECTRONIC:
a. MEET REQUIREMENTS OF NON-DIMMING ELECTRONIC BALLASTS.
b. DO NOT USE TANDEM WIRING BETWEEN LUMINAIRES.
c. BALLAST STARTS LAMP AT ANY PRESET LIGHT OUTPUT SETTING AND PROVIDE CONTINUOUS, SQUARE LAW DIMMING FROM 100 PERCENT TO SPECIFIED LOW-END
OUTPUT.
d. MANUFACTURERS: LUTRON, PHILIPS, OSRAM SYLVANIA, OR APPROVED EQUIVALENT.
2.15 LAMPS
A. PROVIDE LAMPS FOR LUMINAIRES. PROVIDE LAMP CATALOGED FOR SPECIFIED LUMINAIRE TYPE.
B. MANUFACTURERS: OSRAM/SYLVANIA, GENERAL ELECTRIC, PHILIPS, VENTURE, USHIO (MR ONLY), OR APPROVED EQUIVALENT UNLESS SPECIFIC MANUFACTURER IS
INDICATED IN THE LUMINAIRE SCHEDULE.
C. INCANDESCENT: NOT ALLOWED UNLESS NOTED IN LUMINAIRE SCHEDULE.
D. FLUORESCENT:
1. PROVIDE 4100K FLUORESCENT LAMPS UNLESS NOTED IN LUMINAIRE SCHEDULE.
2. LINEAR FLUORESCENT:
a. T-8: BI-PIN BASE, TRI-PHOSPHOR COATED. INITIAL 3100 LUMEN OUTPUT. CRI EQUAL TO OR EXCEEDING 85. 36000 HOURS RATED ON 3 HOUR SWITCHING CYCLE
AND 42000 HOURS RATED ON 12 HOUR SWITCHING CYCLES WHEN USED WITH PROGRAMMED START BALLAST. COMPATIBLE WITH DIMMING BALLASTS. LENGTH AND
WATTAGE AS INDICATED IN THE LUMINAIRE SCHEDULE.
E. LED (LIGHT EMITTING DIODE):
1. LED MANUFACTURER WILL INCLUDE, BUT NOT BE LIMITED TO, LIGHT SOURCE, LUMINAIRE, POWER SUPPLY AND CONTROL INTERFACE WITH ADDED COMPONENTS AS
NEEDED FOR COMPLETE AND FUNCTIONING SYSTEM.
2. COMPLY WITH ANSI CHROMATICITY STANDARD FOR CLASSIFICATIONS OF COLOR TEMPERATURE. SEE LUMINAIRE SCHEDULE FOR SPECIFIED LED LAMP COLOR AND
COLOR TEMPERATURE. UL OR ETL LISTED AND LABELED.
3. LUMINAIRE TESTING PER IESNA LM-79 AND LM-80 PROCEDURES.
4. LAMP LIFE FOR WHITE LEDS: 50,000 PLUS HOURS WITH LAMP FAILURE OCCURRING WHEN LED PRODUCES 70 PERCENT OF INITIAL RATED LUMENS.
5. LAMP LIFE FOR COLOR LEDS: 30,000 PLUS HOURS WITH LAMP FAILURE OCCURRING WHEN LED PRODUCES 50 PERCENT OF ITS INITIAL RATED LUMENS.
6. PROVIDE SHOP DRAWINGS, WITH LED SYSTEMS BASED ON LUMEN OUTPUT AT 70 PERCENT LUMEN DEPRECIATION FOR WHITE LEDS AND 50 PERCENT LUMEN
DEPRECIATION FOR COLOR LEDS. INITIAL LUMENS FOR ALL COLORS OF LEDS MUST BE LISTED INDIVIDUALLY.
7. LED DRIVERS: REVERSE POLARITY PROTECTION, OPEN CIRCUIT PROTECTION, REQUIRE NO MINIMUM LOAD. MINIMUM 80% EFFICIENCY. CLASS A NOISE RATING.
8. DIMMING: LED SYSTEM CAPABLE OF FULL AND CONTINUOUS DIMMING.
9. LED LIGHT SOURCE MANUFACTURERS: NICHIA, CREE, OSRAM/SYLVANIA, GE LUMINATION OR APPROVED EQUIVALENT.
REG I
ELECTRICAL SPECIFICATIONS
RN
O F CA L I F O
Revisions
No. Description
Date
Scale
N.T.S
2016.01.14
Date
Nov.06,
2015
Job No.
15-57
ELECTRICAL SPECIFICATIONS (continued)
.
ER
ST
J
E 19203
EXP. 6-30-16
E
A
TE
LE
C T R I CA
L
IA
REG I
NEER
NO
GI
EN
F ESS I ON
PRO
AL
V I D MA
A
I
D
ED
ST
SECTION 269000 - BUILDING LIGHTING ACCEPTANCE TESTING AND DOCUMENTATION
PART 1 GENERAL
1.1 SCOPE OF WORK
A. THIS SECTION DESCRIBES THE ACCEPTANCE TESTING AND DOCUMENTATION OF THE LIGHTING SYSTEM(S) AND OUTLINES THE DUTIES AND RESPONSIBILITIES OF THE CONTRACTING TEAM FOR
ACCEPTANCE TESTING.
B. SUPPLY THE ACCEPTANCE REQUIREMENTS TO PRODUCTS, EQUIPMENT AND SYSTEMS PROVIDED UNDER THIS DIVISION, WHERE INDICATED ON PLANS, AND WHERE REQUIRED BY CALIFORNIA
TITLE 24 REQUIREMENTS.
C. ENGAGE THE SERVICES OF A FIRM SPECIALIZING IN COMMISSIONING OF LIGHTING SYSTEMS OR SHALL SUBMIT CONTRACTOR QUALIFICATIONS FOR REVIEW BY ARCHITECT WHERE TESTING AND
DOCUMENTATION IS TO BE PERFORMED BY CONTRACTOR.
1.2 THE COMMISSIONING TEAM
A. FORM THE COMMISSIONING TEAM OF:
1. ELECTRICAL CONTRACTOR'S REPRESENTATIVE
2. LIGHTING CONTROLS MANUFACTURER'S REPRESENTATIVE
3. INSPECTOR OF RECORD
4. OWNER'S STAFF REPRESENTATIVE
PART 2 PRODUCTS
2.1 DUTIES OF THE TEAM
A. THE DUTIES OF THE TEAM ARE AS OUTLINED IN THE TITLE 24 REQUIREMENTS AND SUMMARIZED BELOW:
1. PLAN, ORGANIZE AND IMPLEMENT THE ACCEPTANCE TESTING PROCESS AND WITHIN 1 MONTH OF THE AWARD OF THE CONTRACT, SUBMIT THE NAMES AND ADDRESSES OF THE TESTING
TEAM MEMBER(S).
2. THE ACCEPTANCE TESTING TEAM SHALL SUBMIT A COMPLETE DESCRIPTION OF THE TESTING PROCEDURES AND SYSTEMS TO BE TESTED TO THE ARCHITECT FOR REVIEW.
3. THE ACCEPTANCE TESTING TEAM SHALL COORDINATE TESTS OF SYSTEMS AND EQUIPMENT AND ASSEMBLE DOCUMENTATION RELATED TO TESTS. SUBMIT DOCUMENTATION RELATIVE TO
TESTS AND PROPOSED PROCEDURES TO DESIGN ENGINEER FOR REVIEW PRIOR TO SUBMITTING DOCUMENTATION TO AUTHORITY HAVING JURISDICTION (AHJ). TEAM RESPONSIBLE FOR
PERFORMING DATA ANALYSIS, CALCULATION OF PERFORMANCE INDICES AND CROSSCHECKING OF RESULTS WITH THE REQUIREMENTS OF TITLE 24 AND THE CONTRACT DOCUMENTS. THE
INSTALLING CONTRACTOR OR AGENT RESPONSIBLE FOR TESTING AND DOCUMENTATION SHALL RECORD THEIR STATE OF CALIFORNIA CONTRACTOR'S LICENSE NUMBER OR THEIR STATE OF
CALIFORNIA PROFESSIONAL REGISTRATION LICENSE NUMBER ON EACH CERTIFICATE OF ACCEPTANCE FOR SUBMITTAL.
4. RESPONSIBLE FOR SUBMITTING CERTIFICATE OF ACCEPTANCE INCLUDING PAPER AND ELECTRONIC COPIES OF MEASUREMENTS AND MONITORING RESULTS AND SUPPORTING
DOCUMENTATION TO THE AHJ. WHERE AHJ QUESTIONS RESULTS OR REQUIRES ADDITIONAL TESTING, COMPLETE ADDITIONAL TESTING AND PROVIDE REQUIRED DOCUMENTATION AT NO
ADDITIONAL COST TO THE OWNER.
2.2 TIME SCHEDULE
A. DETERMINE THE TIME PERIOD OF THE COMMISSIONING OF THE SYSTEMS BY THE GENERAL CONTRACTOR AND ACCEPTANCE TESTING TEAM. IT IS IMPORTANT TO NOTE THAT AHJ WILL NOT
RELEASE A FINAL CERTIFICATE OF OCCUPANCY UNTIL A CERTIFICATE OF ACCEPTANCE IS SUBMITTED THAT DEMONSTRATES THAT THE SPECIFIED SYSTEMS AND EQUIPMENT HAVE BEEN SHOWN
TO BE PERFORMING IN ACCORDANCE WITH THE TITLE 24 STANDARDS.
2.3 ACCEPTANCE TESTING - PHASE I - DOCUMENTATION
A. TEAM SHALL ASSEMBLE DOCUMENTATION SHOWING LIGHTING FIXTURE LOCATIONS, LIGHTING CONTROL DEVICE LOCATIONS, CONTROL SEQUENCES AND NOTES.
B. PER TITLE 24 REQUIREMENTS, TEAM SHALL PROVIDE RECORD DRAWINGS TO BUILDING OWNER WITHIN 90 DAYS OF RECEIVING A FINAL OCCUPANCY PERMIT (REFER TO OTHER SPECIFICATION
SECTIONS FOR REQUIREMENTS ON RECORD DRAWINGS.)
C. PER TITLE 24 REQUIREMENTS, TEAM SHALL PROVIDE OPERATING AND MAINTENANCE MANUALS TO THE BUILDING OWNER (REFER TO OTHER SPECIFICATION SECTIONS FOR REQUIREMENTS ON
OPERATION AND MAINTENANCE MANUALS.)
2.4 ACCEPTANCE TESTING - PHASE II - INSPECTION AND TESTING
A. TEAM SHALL REVIEW THE INSTALLATION, PERFORM ACCEPTANCE TESTING AND DOCUMENT RESULTS FOR THE FOLLOWING SYSTEMS:
1. OCCUPANCY SENSORS
2. MANUAL DAYLIGHT CONTROLS
3. AUTOMATIC DAYLIGHT CONTROLS
B. REVIEW OF INSTALLATION SHALL CONFIRM LIGHTING FIXTURES AND LIGHTING CONTROLS ARE PROPERLY LOCATED, IDENTIFIED, CALIBRATED, AND SET POINTS AND SCHEDULES PROGRAMMED
PER CONTRACT DOCUMENT REQUIREMENTS.
2.5 ACCEPTANCE TESTING - PHASE III - CERTIFICATION
A. TEAM SHALL DOCUMENT OPERATING AND MAINTENANCE INFORMATION, COMPLETE INSTALLATION CERTIFICATE, AND INDICATE TEST RESULTS ON THE CERTIFICATE OF ACCEPTANCE, AND
SUBMIT THE CERTIFICATE TO THE AHJ PRIOR TO RECEIVING FINAL OCCUPANCY PERMIT. TEAM SHALL SUBMIT FORMS LTG-1-A THROUGH LTG-3-A AS REQUIRED BY TITLE 24 REQUIREMENTS.
PART 3 EXECUTION
3.1 ACCEPTANCE TESTS AND DOCUMENTATION
A. REFER TO CALIFORNIA TITLE 24, NON-RESIDENTIAL MANUAL FOR SPECIFIC TESTING PROCEDURES AND DOCUMENTATION REQUIREMENTS.
Architecture Interiors Planning
3.6 FIELD QUALITY CONTROL
A. TESTS: CONDUCT TESTS OF EQUIPMENT AND SYSTEMS TO DEMONSTRATE COMPLIANCE WITH REQUIREMENTS SPECIFIED IN THIS DIVISION. REFER TO INDIVIDUAL SPECIFICATION SECTIONS FOR
REQUIRED TESTS. DOCUMENT TESTS AND INCLUDE IN CLOSEOUT DOCUMENTS. DURING SITE EVALUATIONS BY ARCHITECT, PROVIDE AN ELECTRICIAN WITH TOOLS TO REMOVE AND REPLACE
TRIMS, COVERS, DEVICES, AND THE LIKE, SO THAT A PROPER EVALUATION OF THE INSTALLATION CAN BE PERFORMED.
B. TEST CONDUCTOR INSULATION ON FEEDERS OF 100 AMP AND GREATER FOR CONFORMITY WITH 1000 VOLT MEGOHMMETER. USE INSULATED CABLE ENGINEERS ASSOCIATION TESTING
PROCEDURES. MINIMUM INSULATION RESISTANCE ACCEPTABLE IS 1 MEGOHM FOR SYSTEMS 600 VOLTS AND BELOW. NOTIFY ARCHITECT IF INSULATION RESISTANCE IS LESS THAN 1 MEGOHM
C. LIGHTING SYSTEM CONTROL TESTING AND COMMISSIONING:
1. TEST LIGHTING CONTROLS TO ENSURE THAT CONTROL DEVICES, COMPONENTS, EQUIPMENT AND SYSTEMS ARE CALIBRATED, ADJUSTED AND OPERATE IN ACCORDANCE WITH DRAWINGS
AND SPECIFICATIONS. PROVIDE FUNCTIONAL TESTING OF SEQUENCES OF OPERATION TO ENSURE OPERATION IN ACCORDANCE WITH DRAWINGS AND SPECIFICATIONS. PROVIDE
COMPLETE REPORT OF TEST PROCEDURES AND RESULTS TO ENGINEER AND INSERT APPROVED COPY INTO PROJECT CLOSEOUT DOCUMENTS.
2. TESTING SHALL INCLUDE:
a. DAYLIGHT AUTOMATIC CONTROLS.
b. OCCUPANT SENSING AUTOMATIC CONTROLS.
c. AUTOMATIC TIME AND OVERRIDE CONTROLS FOR INTERIOR LIGHTING.
D. VERIFY ELECTRICAL CHARACTERISTICS OF EQUIPMENT PRIOR TO INSTALLATION OF CONDUITS AND WIRING FOR EQUIPMENT.
E. COORDINATE HVAC VOLTAGE REQUIREMENTS WITH DRAWINGS AND EQUIPMENT SUBMITTALS PRIOR TO ROUGH IN.
F. WIRING DEVICE TESTS: TEST WIRING DEVICES TO ENSURE ELECTRICAL CONTINUITY OF GROUNDING CONNECTIONS, AND AFTER ENERGIZING CIRCUITRY, TO DEMONSTRATE COMPLIANCE WITH
REQUIREMENTS. TEST RECEPTACLES FOR LINE TO NEUTRAL, LINE TO GROUND AND NEUTRAL TO GROUND FAULTS. CORRECT DEFECTIVE WIRING.
G. USE MANUFACTURER'S PUBLISHED TESTING AND ADJUSTING PROCEDURES TO ADJUST SENSORS TIME DELAY, DAYLIGHT SENSITIVITY, AND PASSIVE INFRARED SENSITIVITY TO SATISFACTION OF
THE OWNER.
H. FOCUS AND ADJUST FLOODLIGHTS, SPOTLIGHTS AND OTHER ADJUSTABLE LUMINAIRES, WITH ARCHITECT, AT SUCH TIME OF DAY OR NIGHT AS REQUIRED. ALIGN LUMINAIRES THAT ARE NOT
STRAIGHT AND PARALLEL/PERPENDICULAR TO STRUCTURE. POSITION EXIT SIGN DIRECTIONAL ARROWS AS INDICATED.
I.
VERIFICATION OF CONDITIONS: VERIFY CEILING CONSTRUCTION, RECESSING DEPTH AND OTHER CONSTRUCTION DETAILS PRIOR TO RELEASE OF LUMINAIRE FOR SHIPMENT.
3.7 CLEANING
A. REMOVE DIRT AND DEBRIS CAUSED BY THE EXECUTION OF THE ELECTRICAL WORK. LEAVE THE ENTIRE ELECTRICAL SYSTEM INSTALLED IN CLEAN, DUST-FREE AND PROPER WORKING ORDER.
B. THOROUGHLY CLEAN EXPOSED PORTIONS OF EQUIPMENT, REMOVING TEMPORARY LABELS AND TRACES OF FOREIGN SUBSTANCES. THROUGHOUT WORK, REMOVE CONSTRUCTION DEBRIS AND
SURPLUS MATERIALS ACCUMULATED DURING WORK.
C. WHERE FINISH OF LUMINAIRES OR ENCLOSURES IS DAMAGED, TOUCH UP FINISH WITH MATCHING PAINT IN ACCORDANCE TO MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
INSTRUCTIONS.
D. CLEAN PAINT SPLATTERS, DIRT, DUST, FINGERPRINTS, AND DEBRIS FROM LUMINAIRES.
RN
O F CA L I F O
END OF ELECTRICAL SPECIFICATIONS
Revisions
No. Description
Date
Scale
N.T.S
2016.01.14
Date
Nov.06,
2015
Job No.
15-57
TRUE NORTH
W
4
1
A.
THE CONTRACTOR SHALL COORDINATE ALL ELECTRICAL
SERVICE INSTALLATION AND/OR DEMOLITION WITH PG&E..
B.
PROVISIONS SHALL BE MADE TO DISCONNECT EXISTING
SERVICE EQUIPMENT AND RECONNECT NEW SERVICE
EQUIPMENT WITH MINIMAL POWER DISRUPTION.
C.
COORDINATE EXACT LOCATIONS OF ALL ARCHITECTURAL,
MECHANICAL, PLUMBING, LANDSCAPING AND CIVIL
EQUIPMENT WITH ARCHITECTURAL, MECHANICAL,
PLUMBING, LANDSCAPING AND CIVIL DRAWINGS.
D.
CIRCUIT ALL DEVICES ON THIS SHEET TO PANELBOARD
P2A/P2B, UNLESS OTHERWISE NOTED.
E.
SIZE FUSES FOR ALL FUSED SWITCHES PER SUPPLIED
EQUIPMENT MANUFACTURER'S RECOMMENDATIONS.
F.
CERTAIN FEEDER AND BRANCH CIRCUIT WIRE SIZES HAVE
BEEN OVERSIZED TO COMPENSATE FOR VOLTAGE DROP.
SPLICE WIRES TO COMPATIBLE SIZES FOR TERMINATION,
ADJACENT TO EQUIPMENT CONNECT AS REQUIRED.
G.
CONTRACTOR SHALL SIZE ALL IN GRADE PULL BOXES PER
APPLICABLE CODE OR STANDARD, OR FOR THEIR
CONVENIENCE FOR PULLING WIRE, WHICHEVER IS
LARGER.
1
J
J
(R)
J
P2B-72
S
BUILDING NORTH
E
Architecture Interiors Planning
GENERAL NOTES
P2B-72
2
J
P2B-80/82/84
2
J
2.
INSTALL OWNER FURNISHED CHARGING STATION.
PROVIDE PULL BOX FOR ELECTRIC VEHICLE
CHARGING STATION N16 AT STALL, USING 208V, 3PH (3)
#8 +(1) #10 GND INSIDE 1" CONDUIT CIRCUIT AS
SHOWN. PROVIDE 50A/3P CONTACTOR WITH RELAY
CONNECTION TO A TORK DIGITAL TIME SWITCH. TIME
SWITCH SHALL ACTIVATE RELAY TO CLOSE
CONTACTOR AND PROVIDE POWER TO THE EV
CHARGING STATION. COORDINATE WITH AUTHORITY
REPRESENTATIVE FOR PROGRAMMING OF TIME
CLOCK SCHEDULE.
3.
(E) LIGHTS TO REMAIN.
4.
RELOCATE (E) IRRIGATION CONTROLLER. EXTEND
CONDUIT AND WIRE TO NEW LOCATION AS REQUIRED.
REFER TO ARCHITECTURAL PLAN FOR EXACT
LOCATION.
5.
COORDINATE WITH SITE CONTRACTOR TO LOWER (E)
SITE PULL BOX TO NEW GRADE. ADJUST BOX, RING,
LID, AND CONDUITS AS REQUIRED TO LOWER BOX
APPROXIMATELY 6" (MOVING FROM CURB HEIGHT TO
ASPHALT HEIGHT. REFER TO ARCHITECTURAL SITE
WORK PLANS FOR ADDITIONAL INFORMATION.
.
ST
PROVIDE 120V, 1PH DEDICATED CIRCUIT FOR
MOTORIZED GATE. CIRCUIT AS SHOWN AND INSTALL
PER MANUFACTURER INSTRUCTIONS. USING # (2) #12
+(1) #12 +(1) #12 GND INSIDE CONDUIT 3/4".
J
E
A
TE
LE
C T R I CA
L
IA
REG I
1.
NEER
SHEET NOTES
NO
(E)
#
E 19203
EXP. 6-30-16
ST
EXISTING
BUILDING
F ESS I ON
PRO
AL
V I D MA
A
I
D
ED
GI
EN
ER
P2B-74/76/78
RN
O F CA L I F O
3 TYP
(E)
(E)
(E)
(E)
(E)
Revisions
No. Description
Date
3/32" = 1'-0"
33 LAS COLINAS LANE
Scale
3/32" = 1'-0"
2016.01.14
Date
Nov.06,
2015
Job No.
15-57
A.
#
IN AREAS INDICATED TO BE RENOVATED, REMOVE THAT PORTION OF THE EXISTING
ELECTRICAL INSTALLATION INCLUDING, BUT NOT LIMITED TO, ALL LIGHT FIXTURES,
RECEPTACLES, MOTOR/EQUIPMENT CONNECTIONS, WIRING, CONDUITS AND
APPURTENANCES. ALL UNUSED WIRING AND EXPOSED CONDUIT SHALL BE
REMOVED BACK TO POINT OF CONCEALMENT, UNLESS OTHERWISE NOTED.
B.
WHERE CONDUIT TO BE REMOVED ENTERS CONCRETE (OR SIMILAR) FLOORS AND
WALLS, THE CONDUIT MAY BE ABANDONED IN THE CONCRETE. REMOVE CONDUIT
FAR ENOUGH INTO THE CONCRETE TO ALLOW FOR THE INSTALLATION OF NORMAL
THICKNESS OF FINISH MATERIAL.
C.
WHEN THE WORK NECESSITATES RELOCATION OF EXISTING CONDUIT, WIRING, OR
ELECTRICAL EQUIPMENT, THE CONTRACTOR SHALL PERFORM ALL WORK AND MAKE
ALL NECESSARY CHANGES TO EXISTING WORK AS MAY BE REQUIRED TO LEAVE
THE COMPLETED WORK IN A FINISHED AND WORKMANLIKE CONDITION TO THE
ENTIRE SATISFACTION OF THE ENGINEER.
D.
WHERE ELECTRICAL SYSTEMS PASS THROUGH THE RENOVATED AREAS TO SERVE
OTHER PORTIONS OF THE PREMISES, THEY SHALL BE SUITABLY RELOCATED AND
THE SYSTEM RESTORED TO NORMAL OPERATION. WHERE DURATION OF
PROPOSED OUTAGES CANNOT BE TOLERATED BY THE OWNER, PROVIDE
TEMPORARY CONNECTION AS REQUIRED TO MAINTAIN SERVICE WITH THE MINIMUM
DISRUPTION POSSIBLE.
E.
SHEET NOTES
TRUE NORTH
F.
WHILE PERFORMING CONNECTIONS AND/OR ALTERATIONS TO EXISTING
ELECTRICAL WORK, TAKE EXTREME CARE TO PROTECT ALL EXISTING EQUIPMENT
FROM DIRT, DEBRIS, AND DAMAGE. ALL DAMAGE TO SUCH EQUIPMENT SHALL BE
REPAIRED AND/OR EQUIPMENT REPLACED AT THE CONTRACTOR'S EXPENSE.
1.
REMOVE ALL ELECTRICAL, TELECOM, DATA, AND
ASSOCIATED DEVICES IN THIS AREA, UON THAT A
DEVICE IS TO REMAIN. REFER TO GENERAL NOTES FOR
MORE INFORMATION.
G.
ALL REMOVAL WORK SHALL BE PERFORMED IN A NEAT AND WORKMANLIKE MANNER
AND SHALL BE EXECUTED WITH THE LEAST POSSIBLE DISTURBANCE TO THE
BUILDING.
2.
(E) DEVICES IN THIS AREA TO REMAIN, UON TO BE
REMOVED.
3.
REMOVE (E) DATA WIRING FROM THIS DEVICE BACK TO
THE (E) TELE/DATA BACKBOARD. PROVIDE NEW DATA
WIRING AS SHOWN ON ELECTRICAL FLOOR PLANS. (E)
WIRING MAY BE USED TO PULL NEW WIRING TO
DEVICE.
H.
ALL EXISTING ELECTRICAL MATERIALS NOT REUSED AND NOT SALVAGED BY THE
OWNER SHALL BECOME THE PROPERTY OF THE CONTRACTOR AND SHALL BE
DISPOSED OF IN A PROPER MANNER OFF OF THE PROJECT SITE. CARE SHOULD BE
TAKEN TO DISPOSE OF HAZARDOUS MATERIALS PER REQUIRED GUIDELINES.
I.
ANY ELECTRICAL WORK, WHICH WILL INTERFERE WITH THE NORMAL USE OF THE
BUILDING IN ANY MANNER, SHALL BE DONE AT SUCH TIME OR TIMES AS SHALL BE
MUTUALLY AGREED UPON BETWEEN THE CONTRACTOR AND THE OWNER'S
REPRESENTATIVE.
J.
(E) AND (D) DEVICE LOCATIONS AND CIRCUITS ARE BASED ON PRELIMINARY FIELD
OBSERVATIONS AND ARE SHOWN FOR REFERENCE ONLY. NOT ALL DEVICES TO
REMAIN OR BE REMOVED MAY BE SHOWN. CONTRACTOR SHALL VISIT SITE PRIOR
TO BIDDING AND VERIFY ALL REQUIRED DEMOLITION, RELOCATION, AND
PROTECT-IN-PLACE WORK AS MAY BE REQUIRED.
4.
RELOCATE (E) WATER HEATER. REFER TO FLOOR
PLANS FOR ADDITIONAL INFORMATION.
5.
(E) FLOOR MOUNTING STUDS FOR FLOOR MOUNTED
4-POST DATA RACK SHALL BE REUSED TO ANCHOR
NEW DATA RACK. REFER TO FLOOR PLANS FOR MORE
INFORMATION.
6.
REMOVE EXISTING ROOF MOUNTED EXHAUST FAN.
RETAIN EXISTING CONDUIT AND WIRE FOR REUSE.
PROVIDE NEW CONDUIT AND WIRE TO MATCH EXISTING
TO EXTEND CIRCUIT TO NEW FAN LOCATION. REFER TO
MECHANICAL DRAWINGS FOR MORE INFORMATION.
W
S
BUILDING NORTH
E
Architecture Interiors Planning
GENERAL DEMOLITION NOTES
WHERE REMOVAL WORK IS PERFORMED, THE CONTRACTOR SHALL REPAIR ALL
BUILDING SURFACES DAMAGED BY SUCH WORK. PROVIDE FINISHES TO MATCH
EXISTING ADJACENT SURFACES.
(E) MSB DIST
(E) MSB METER/MAIN
(E) DIST PNL DP1
(E) PNL P1A/P1B
(E)
2
(E)
(E)
(E)
(E)
(E) PNL L1
TS
P1B-55
(E)
(E) PNL OSL
T (E) 150KVA XFMR
ON ROOF OF ELEC RM
(E)
P1A-26/28/30
(E)
(E) TELEPHONE MPOE
(E)
2
2
(E)
(E)
(E)
(E)
2
2
(D)
(D)
(D)
(D)
P1B-69
P1B-71
(E)
P1B-61
4
(D)
(D)
(D)
5
(D)
2
(E)
(E)
UP
(E)
P1B-47
(E)
(D)
P1A-29
P1A-29
3
P1B-47
P1B-56
(E)
(E)
(D)
2
(E)
P1A-27
P1A-33
(D)
1
P1A-29
(D)
P1A-35
(D)
(D)
P1A-27
P1A-31
(D)
P1A-29
(D)
(D)
P1A-33 P1A-27
(D)
(D)
P1A-35
(D)
P1B-53
P1A-31
(D)
(D)
(E)
P1B-53
(E)
P1B-53
P1B-53
(E)
P1B-53
J
J
(E)
J
IA
REG I
(E)
2
2
J
P2B-45
(E)
3
J
(E)
(D)
(E)
2
(E)
J
(E)
(E)
P2B-43
(E)
(D) (D)
(D)
(E)
3
2
2
(D)
3
(D)
2
(E)
J
1
(E)
(E)
(E)
(E)
J
(E)
(E)
(D)
(D)
(D)
3
(D)
(D)
(D)
(D)
(E)
(E)
P1B-45
P1A-29
P1B-47
(D)
P1B-43
(E)
(E) (E)
(E)
(E)
P1A-29
RN
O F CA L I F O
(E)
(D)
(D)
L
(E)
(E)
2
2
C T R I CA
(E)
J
(E)
P1A-25
(E)
(E)
(E)
LE
1
(D)
2
(D)
P1A-31
(D)
J
J
P1B-51
(D)
3
3
3
(E)
J
(E)
(E)
J
(E)
J
P2B-53
P2B-53
3
(E)
(D)
(E)
2
J
(E)
2
(E)
(E)
P1B-47
J
(E)
(E)
TE
(E)
3
J
(E)
(E)
(E)
A
(E)
(E)
J
(E)
(E)
(E)
P2B-47
(D)
P2B-49
(E)
P2B-49
(ON ROOF) 6
(E)
(E)
3
(D)
DN
P2B-45
(E)
(E)
(D)
2
P1A-25
P1A-35
(D)
J
(E)
P1A-14
P1A-33
(D)
J
2
(D)
(E)
(E)
(E)
(E)
P2B-45
(E)
J
(E)
P1A-31
(D)
3
(D)
P2B-55/57 (D)
J
3
(E)
(E)
2
3
(E) (E)
(E)
(E)
(E)
(E)
2
P1B-47
(E)
DN
2
(E)
(E)
(D)
(E)
J
(E)
(E)
P2B-59/61
(E)
(E)
2
(E)
P1B-73
(D)
(E)
P1B-73
(E)
P1B-47
(D)
(E)
2
3
(D)
(E)
E
3
3
.
ST
P1B-73
2
(E)
UP
(E)
P1B-69
(E)
(E)
P1B-69
(E)
(R)
1
P1B-69
(E)
(E)
(E)
(ON ROOF)
E 19203
EXP. 6-30-16
ST
(E)
P2A-46
P1B-75
(E) (D) P2A-44
(E)
P1B-73 P1B-73
(D)
(E) (E)
(E)
(E)
(D)
(D)
P1B-75
P1B-73
P1B-75
(D) (E) (E)
(D)
(E)
P2B-67/69
(E)
P2B-63/65
(D)
(E)
P1B-73
P1B-73
1
2
2
(E)
(E)
3
3
(E)
(E)
(E) PNL P2A/P2B
6
J
NEER
P1B-69
(E) TELE/DATA
BACKBOARD
(E)
NO
(E) SECURITY EQUIP
F ESS I ON
PRO
AL
V I D MA
A
I
D
ED
GI
EN
ER
(E)
J
J
J (E)
1
3
Revisions
3
J
J
P1B-53
J
J
(E)
J
(E)
J
3
No. Description
(E)
(E)
(E)
WP
(E)
Date
WP
3
1/8" = 1'-0"
1/8" = 1'-0"
Scale
1/8" = 1'-0"
2016.01.14
Date
Nov.06,
2015
Job No.
15-57
A.
IN AREAS INDICATED TO BE RENOVATED, REMOVE THAT PORTION OF THE EXISTING
ELECTRICAL INSTALLATION INCLUDING, BUT NOT LIMITED TO, ALL LIGHT FIXTURES,
RECEPTACLES, MOTOR/EQUIPMENT CONNECTIONS, WIRING, CONDUITS AND
APPURTENANCES. ALL UNUSED WIRING AND EXPOSED CONDUIT SHALL BE REMOVED
BACK TO POINT OF CONCEALMENT, UNLESS OTHERWISE NOTED.
F.
G.
B.
WHERE CONDUIT TO BE REMOVED ENTERS CONCRETE (OR SIMILAR) FLOORS AND
WALLS, THE CONDUIT MAY BE ABANDONED IN THE CONCRETE. REMOVE CONDUIT FAR
ENOUGH INTO THE CONCRETE TO ALLOW FOR THE INSTALLATION OF NORMAL
THICKNESS OF FINISH MATERIAL.
C.
WHEN THE WORK NECESSITATES RELOCATION OF EXISTING CONDUIT, WIRING, OR
ELECTRICAL EQUIPMENT, THE CONTRACTOR SHALL PERFORM ALL WORK AND MAKE ALL
NECESSARY CHANGES TO EXISTING WORK AS MAY BE REQUIRED TO LEAVE THE
COMPLETED WORK IN A FINISHED AND WORKMANLIKE CONDITION TO THE ENTIRE
SATISFACTION OF THE ENGINEER.
D.
WHERE ELECTRICAL SYSTEMS PASS THROUGH THE RENOVATED AREAS TO SERVE
OTHER PORTIONS OF THE PREMISES, THEY SHALL BE SUITABLY RELOCATED AND THE
SYSTEM RESTORED TO NORMAL OPERATION. WHERE DURATION OF PROPOSED
OUTAGES CANNOT BE TOLERATED BY THE OWNER, PROVIDE TEMPORARY CONNECTION
AS REQUIRED TO MAINTAIN SERVICE WITH THE MINIMUM DISRUPTION POSSIBLE.
E.
SHEET NOTES
#
H.
I.
J.
WHILE PERFORMING CONNECTIONS AND/OR ALTERATIONS TO EXISTING ELECTRICAL
WORK, TAKE EXTREME CARE TO PROTECT ALL EXISTING EQUIPMENT FROM DIRT,
DEBRIS, AND DAMAGE. ALL DAMAGE TO SUCH EQUIPMENT SHALL BE REPAIRED AND/OR
EQUIPMENT REPLACED AT THE CONTRACTOR'S EXPENSE.
ALL REMOVAL WORK SHALL BE PERFORMED IN A NEAT AND WORKMANLIKE MANNER
AND SHALL BE EXECUTED WITH THE LEAST POSSIBLE DISTURBANCE TO THE BUILDING.
ALL EXISTING ELECTRICAL MATERIALS NOT REUSED AND NOT SALVAGED BY THE
OWNER SHALL BECOME THE PROPERTY OF THE CONTRACTOR AND SHALL BE DISPOSED
OF IN A PROPER MANNER OFF OF THE PROJECT SITE. CARE SHOULD BE TAKEN TO
DISPOSE OF HAZARDOUS MATERIALS PER REQUIRED GUIDELINES.
ANY ELECTRICAL WORK, WHICH WILL INTERFERE WITH THE NORMAL USE OF THE
BUILDING IN ANY MANNER, SHALL BE DONE AT SUCH TIME OR TIMES AS SHALL BE
MUTUALLY AGREED UPON BETWEEN THE CONTRACTOR AND THE OWNER'S
REPRESENTATIVE.
(E) AND (D) DEVICE LOCATIONS AND CIRCUITS ARE BASED ON PRELIMINARY FIELD
OBSERVATIONS AND ARE SHOWN FOR REFERENCE ONLY. NOT ALL DEVICES TO REMAIN
OR BE REMOVED MAY BE SHOWN. CONTRACTOR SHALL VISIT SITE PRIOR TO BIDDING
AND VERIFY ALL REQUIRED DEMOLITION, RELOCATION, AND PROTECT-IN-PLACE WORK
AS MAY BE REQUIRED.
1.
LIGHT FIXTURES SHOWN (D) SHALL BE REMOVED
CAREFULLY TO ALLOW CONDUITS/WIRES TO BE
REUSED TO THE EXTENT POSSIBLE.
2.
(E) DEVICES IN THIS AREA TO REMAIN.
3.
REMOVE (E) SCONCE. RETAIN WIRING AND BACK BOX
FOR NEW SCONCE INSTALLATION.
4.
REMOVE (E) FIXTURES AND ASSOCIATED UNISTRUT
MOUNTING SYSTEM.
5.
UTILIZE (E) J-BOXES, CONDUIT, AND WIRE IN THIS
SPACE FOR CONNECTION OF NEW FIXTURES.
6.
NOT USED
7.
REMOVE HALOGEN MR-16 LAMP FROM FIXTURE AND
REPLACE WITH LED MR-16 OF EQUIVALENT LIGHT
OUTPUT. PROVIDE PHILIPS LED 10W (50W
INCANDESCENT EQUIVALENT) WITH 3000K CCT, 650
LUMEN OUTPUT, AND 82 CRI, MODEL # 432 401 OR
APPROVED EQUAL. PROVIDE QUANTITY OF LAMPS
NECESSARY TO REPLACE ALL (E) MR-16 LAMPS.
WHERE REMOVAL WORK IS PERFORMED, THE CONTRACTOR SHALL REPAIR ALL
BUILDING SURFACES DAMAGED BY SUCH WORK. PROVIDE FINISHES TO MATCH
EXISTING ADJACENT SURFACES.
1
TRUE NORTH
8.
REMOVE (E) LIGHTING AND CONTROLS IN THIS SPACE,
UON TO REMAIN.
9.
RELOCATE (E) 2x2 FIXTURES TO NEW CEILING GRID
RECONFIGURATION. TYPICAL (9) FIXTURES. SEE NEW
RCP FOR LOCATIONS.
W
S
BUILDING NORTH
10. REMOVE EXISTING WALL PACK.
11. RELOCATE (E) LIGHT FIXTURE. MAINTAIN EXISTING
CIRCUITING AND CONTROLS FOR RECONFIGURATION.
EXTEND CONDUIT AND WIRING AS REQUIRED TO
RESTORE TO A FULLY FUNCTIONAL STATE.
E
12. RELOCATE EXISTING LIGHT SWITCHES. SEE LIGHTING
PLAN FOR NEW LOCATION.
Architecture Interiors Planning
GENERAL DEMOLITION NOTES
10 TYP.
(D)
(E)
2
(E)
(E)
(E) (E)
(E)
(E)
(E)
(D)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
2
(E)
(E)
(E)
(E)
(E)
(E)
(D)
(D)
(D)
(D)
(D)
(E)
(E)
(R)
(E)
(E)
(D)
(D)
(D)
(D)
(D)
2
(E)
(E)
(R)
2
(E)
(E)
(E)
(E)
(D)
(D)
(D)
(E)
(E)
(D)
(E)
(E)
(D)
(D)
(D)
1 TYP
(D)
(D)
(D)
(D)
(D)
(E)
(E) (E)
(E)
(R)
(R)
(R)
(D)
(D)
(D)
(D)
(E)
(E)
(D)
(E)
(E)
(E)
(E)
7
(E)
(E)
7
(E) (E)
J
(E)
(E)
TYP OF 7
(E)
(E)
(E)
7
(E)
(E)
(E)
(E)
(E)
(E)
(E) (E)
(E)
2
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(D)
(E)
(D)
1
(D)
4
(E)
(D)
(E)
(E)
(E)
(D)
(D)
(E)
(D)
(E)
2
7
(E)
(E)
(E)
7
(E)
(E)
2
7
9
TYP.
(E)
(E)
(E)
(E)
(D)
(R)
(R)
(R)
(D)
(D)
(E)
(E)
(E)
(E)
(E)
7
(E)
(E)
(E)
(R)
(E)
(E)
(R)
(R)
(R)
(R)
(E)
(R)
(D)
(E)
(D)
(D)
(R)
(R)
Revisions
(E)
No. Description
(R)
(E)
(E)
(D)
(E)
(R) (R)
(E)
(E)
8
(E) (E)
(E)
TYP OF 7
(E)
2
(E)
(E)
(E)
12 TYP
(R)
J
(E)
(E)
2
(E)
(E)
(E)
(E)
2
(E)
(E)
(R)
(E)
RN
O F CA L I F O
(E)
(E)
(E)
(D)
(D)
(E)
(E)
(E)
(D)
3
5
L
(E)
(E)
7
(E)
(E)
2
(E)
(E)
(E)
(E)
2
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
C T R I CA
(E) (E)
(E)
(E)
(E)
(E)
(E)
(E)
(D)
(R)
(E)
(E)
7
(D)
(E)
2
2
(E)
(E)
LE
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
12 TYP
(E)
(E)
(E)
(E)
(E)
(E)
(E)
TE
2
2
(E)
(E)
(E)
(D)
(E)
3
(E)
(E)
(E)
(D)
(D)
(D)
(D)
X1
(D)
2
(R)
(E)
(D)
(E)
(E)
(D)
12 TYP (R) (R)
(R)
(E)
(E)
11
(E)
(E)
1
(E)
(E)
(R)
(E)
(D)
(E)
(D)
(E)
(E)
(E)
(E)
1
(D)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
8
2
(E)
(E)
(E)
(E)
(E)
(D)
(E)
(E)
(E)
(E)
(E)
7
2
(E)
(D)
(D)
(E) (E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
7
(E)
(E)
(E)
(E)
(D)
(E)
(E)
(E)
7
(E)
X1(D)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(R)
(E)
(E)
(E) (E)
(E)
(E)
(E)
(E)
(E)
(E)
(D)
11
(D) (D) (R)
(D) (D)
(R)
(D)
(E)
(D)
(E)
(E)
2
(D)
2
11
(D)
8
(E)
.
ST
E
ST
(D)
(D)
2
(D)
J
REG I
3
A
2
NEER
1
(E) (E)
(D)
E 19203
EXP. 6-30-16
(E)
(E)
NO
(E)
GI
EN
(E)
F ESS I ON
PRO
AL
V I D MA
A
I
D
ED
IA
(E)
ER
2
Date
(E)
(E)
11
(E)
1/8" = 1'-0"
1/8" = 1'-0"
Scale
1/8" = 1'-0"
2016.01.14
Date
Nov.06,
2015
Job No.
15-57
A.
B.
#
SEE ARCHITECTURAL DOCUMENTS FOR EXACT PLACEMENT OF ALL LIGHT FIXTURES,
EXPOSED CONTROL DEVICES AND LIGHT SWITCHES. VERIFY CEILING TYPE WITH
ARCHITECTURAL DOCUMENTS AND COORDINATE TRIMS. PROVIDE ALL REQUIRED
FIXTURE MOUNTING HARDWARE. COORDINATE FIXTURE TYPES WITH MOUNTING
SURFACE PRIOR TO ORDERING.
TRUE NORTH
F.
MOUNT WALL MOUNTED OCCUPANCY SENSORS AT 8'-0" ABOVE FINISHED FLOOR,
UNLESS OTHERWISE NOTED.
1.
(E) FIXTURES AND CONTROLS IN THIS AREA TO
REMAIN.
G.
CIRCUIT ALL LIGHT FIXTURES ON THIS SHEET TO PANELBOARD L1, UNLESS OTHERWISE
NOTED.
2.
INSTALL FIXTURE IN SAME LOCATION AS REMOVED
FIXTURE. RECONNECT TO (E) J-BOX AND CIRCUITRY.
H.
PENDANT FIXTURES SHALL BE FREE TO SWING A MINIMUM OF 45 DEGREES FROM THE
VERTICAL IN ALL DIRECTIONS WITHOUT CONTACTING OBSTRUCTIONS, OTHERWISE
PROVIDE SEISMIC RESTRAINT.
SHEET NOTES
SEE DRAWING E-11 FOR LIGHT FIXTURE MOUNTING DETAILS.
3.
INSTALL NEW DOWN LIGHTS. EXTEND CONDUIT AND
WIRING FROM PREVIOUS TRACK LOCATION TO NEW
DOWNLIGHT LOCATIONS IN THIS AREA.
7.
CONNECT NEW FIXTURE TO CIRCUIT FEEDING (E)
PENDANT FIXTURES TO OPEN OFFICE EXTEND (E)
CONDUIT AND WIRE AS REQUIRED.
8.
RELOCATE (E) PENDANT TO THIS LOCATION. EXTEND
(E) CONDUIT AND WIRE AS REQUIRED.
W
S
BUILDING NORTH
9.
RELOCATED SWITCH BANK.
10. PROVIDE NEW SWITCH TO CONTROL (E) LIGHTING IN
THE AREA. MODIFY CURRENTLY AS REQUIRED.
C.
RUN ALL INTERIOR CONDUIT IN FINISHED INTERIOR AREAS CONCEALED UNLESS
OTHERWISE NOTED.
4.
PROVIDE NEW 0-10V DIMMING BALLAST FOR
RELOCATED FIXTURE.
D.
PROVIDE U.L. LISTED FIRE STOP ENCLOSURES FOR ALL RECESSED FIXTURES IN FIRE
RATED CEILINGS.
5.
MOUNT FIXTURE UNDER CABINET. INTERCEPT (E)
ROOM LIGHTING CIRCUIT AND CONNECT TO (E)
CIRCUIT.
E.
PROVIDE SINGLE PLATE WALL COVER FOR MULTIPLE SWITCHES. SEE DRAWINGS FOR
NUMBER OF SWITCHES IN SPECIFIC LOCATIONS.
6.
CONNECT NEW OR RELOCATED LIGHTING IN THIS
ROOM TO (E) CIRCUITRY. PROVIDE NEW CONDUIT,
AND WIRE AS REQUIRED EXTEND TO NEW FIXTURES.
E
11. COORDINATE LOCATION OF S3 LIGHT WITH BOARD
ROOM TABLE LOCATION BELOW. COORDINATE EXACT
LOCATION WITH OWNER PRIOR TO ROUGH IN AND
INSTALL, TYPICAL ALL S3 FIXTURES.
Architecture Interiors Planning
GENERAL NOTES
W2
2
TYP.
W2
U
6
R1
D
D1
S
S5
S5
S2
S5
a
11 TYP. a
S3
e S3
S5
Dd d
a
S3
a
e
c
S3
e U
S2
S2
S3
c
S2
c
c
c
S2
c
c S2
c S2
c
c
S4
c
c
c
S4
S4
b
c
U
IA
1
D1
S4
3
D1
b
c
Db Dc
3
c
Db
P2
P2
6
c
b
P2
b
b
(R)
S6
D
DRC
R1
a P
b
D
(R)
a
6
P
P
D
b
DRC
(R)
D
1
Revisions
(R)
(R)
P
DRC
D
D
D
6
1
b
R1
6
(R)
(R)
DRC
D
R1
DRC
6
b
D
D
(R)
R1
DRC R1
(R)
(R)
b
D
Da
R1
U
(R)
DRC
1
6
S6
3
3
Db
6
D1
9
TYP.
c
DRC
DRC
(R)
(R) (R)
(R)
1
S4
S2
S2
D1
S4
S2
c
c
S2
3
W1
Da
S2
D1
2
S2
c
S2
S2
c
1
b
S2
S2
U
3
3
c
S3
S2
P
D1
1
D1
e
c
1
S2
eU
c
S3 S2
(R)
(R)
c
e
S2
1
Dd
De
S4
S3
1
1
(R)
(R)
(R)
(R)
1
b
c S2
RN
O F CA L I F O
1
1
e
6
2
8
1
D
S2
L
W1
1
d
Da
Db
Dc
C T R I CA
U
D1
D1
1
W1
1
S1
9
R1
D1
LE
(R)
1
DRC
R1
6
S
1
1
R1
.
ST
D1 R1
1
S1
a
1
D
J
REG I
a
1
S1
(R)
D1
D
W2
S1
6
(R)
1
6
NEER
P1
NO
D1
1
6
TE
1
DRC
DRC
P1
E
A
S1 S1 S1 S1 S1 S1
1
P1
TYP.
2
6
E 19203
EXP. 6-30-16
ST
5
F ESS I ON
PRO
AL
V I D MA
A
I
D
ED
GI
EN
ER
1
P
6
6
No. Description
P
4
4
Date
TYP.
8
1/8" = 1'-0"
1/8" = 1'-0"
Scale
1/8" = 1'-0"
2016.01.14
Date
Nov.06,
2015
Job No.
15-57
A.
B.
C.
COORDINATE EXACT LOCATIONS OF ALL ARCHITECTURAL, MECHANICAL AND
PLUMBING EQUIPMENT WITH ARCHITECTURAL, MECHANICAL AND PLUMBING
DRAWINGS.
G.
CIRCUIT ALL DEVICES ON THIS SHEET TO PANELBOARD P2A/P2B, UNLESS
OTHERWISE NOTED.
H.
SIZE FUSES FOR ALL MECHANICAL AND PLUMBING EQUIPMENT PER
MANUFACTURER'S RECOMMENDATIONS.
D.
ALL NEW DATA WIRING AND ASSOCIATED PATCH PANELS, JACKS, AND OTHER
MISCELLANEOUS APPURTENANCES SHALL BE CAT6 FROM SYSTIMAX OR
APPROVED EQUAL.
MC CABLE MAY BE USED IN CONCEALED AREAS OF ABOVE ACCESSIBLE
CEILING. EMT AND WIRE SHALL BE USED IN ALL EXPOSED LOCATIONS AND
SHALL BE PAINTED TO MATCH SURFACE BEYOND.
I.
J.
SEE EQUIPMENT SCHEDULE ELECTRICAL REQUIREMENTS FOR CIRCUITING OF
EQUIPMENT AND REFER TO RISER DIAGRAMS AND DETAILS FOR ADDITIONAL
INFORMATION ON WIRING, LAYOUT AND CONNECTIONS. SEE MECHANICAL AND
PLUMBING DRAWINGS FOR ADDITIONAL INFORMATION.
F.
K.
2.
PROVIDE 50A/3P WELDING RECEPTACLE. CIRCUIT AS SHOWN WITH (4) #8 + (1)
#10G - 1" C. COORDINATE PLUG TYPE WITH OWNER'S EQUIPMENT.
5.
6.
COORDINATE EXACT LOCATION OF ALL FLOOR BOXES, CEILING BOXES, AND
NEW WALL MOUNT DEVICES WITH ARCHITECT AND AUTHORITY
REPRESENTATIVE PRIOR TO ROUGH IN AND INSTALLATION.
PROVIDE POWER 120V/24V TRANSFORMER AS REQUIRED TO POWER
VAV/BY-PASS DAMPERS, RESTROOM PLUMBING CONTROLS, DUCT SMOKE
DETECTORS, MAGNETIC DOOR HOLDERS AND FIRE SMOKE DAMPERS FOR
MECHANICAL EQUIPMENT. SEE DIAGRAMS ON MECHANICAL AND PLUMBING
DRAWINGS FOR CONNECTION TO MECHANICAL AND PLUMBING EQUIPMENT.
PROVIDE CIRCUIT FORM NEAREST AVAILABLE PANEL, UNLESS OTHERWISE
NOTED.
(E) DEVICES AND CIRCUIT IN THIS AREA TO REMAIN, UON.
4.
EXPOSED CONDUIT ROUTING SHOWN IS APPROXIMATE. ROUTE ALL CONDUITS
PARALLEL TO BUILDING STRUCTURAL ELEMENTS. PROVIDE JUNCTION BOXES
FOR LOW VOLTAGE DEVICE EVERY 180 DEGREES OF BENDS.
TRUE NORTH
1.
3.
ALL EXISTING FLOORBOX AND DEVICE LOCATIONS ARE SHOWN AS
APPROXIMATE. CONTRACTOR SHALL VERIFY EXACT LOCATIONS IN FIELD AND
COORDINATE WITH OWNER PRIOR TO COMMENCING WORK ON SITE AND
PRIOR TO FINAL SELECTION AND LAYOUT OF FURNITURE.
IN FINISHED INTERIOR AREAS, RUN ALL CONDUITS CONCEALED, UNLESS
OTHERWISE NOTED. PAINT ALL EXPOSED CONDUITS AND ELECTRICAL
EQUIPMENT. REFER TO ARCHITECTS PAINTING SECTION FOR REQUIREMENTS.
E.
SHEET NOTES
#
14. PROVIDE CONNECTION TO WATER COOLER. COORDINATE CONNECTION AND
INSTALLATION WITH MANUFACTURER REQUIREMENTS.
E
18. PROVIDE RECESSED J-BOX WITH (1) 1-1/2" C. AV TO CEILING MOUNTED
PROJECTOR J-BOX.
COIL A MINIMUM OF 20'-0" OF SPARE DATA CABLE AT THIS LOCATION FOR
EXTENSION TO MODULAR FURNITURE SYSTEM. COORDINATE WITH FURNITURE
MANUFACTURER FOR FINAL CONNECTION.
PROVIDE CEILING MOUNTED J-BOXES WITH (1) 3/4" C. POWER TO PANEL, (1) 1"
C. DATA TO IDF, AND (1) 1-1/2" C. AV TO WALL MOUNTED J-BOX FOR
PROJECTOR. COORDINATE EXACT LOCATION WITH AV REQUIREMENTS.
19. PROJECTION SCREEN CONTROLS LOCATION.
20. SAW CUT EXISTING SLAB TO FEED NEW FLOOR BOX FOR POWER, DATA, AND
FUTURE AV CONNECTIVITY. REFER TO DETAIL 2/E-11 FOR MORE INFORMATION.
ROUTE (1) 1-1/2" C. AV FROM FLOOR BOX TO J-BOX LOCATION AT STORAGE
ROOM WALL. PROVIDE 3/4" C. POWER FROM FLOOR BOX BACK TO PANEL
BOARD. PROVIDE 1" C. DATA FROM FLOOR BOX TO IDF.
21. STUB CONDUIT UP INTO WALL. ROUTE CONDUIT CONCEALED IN FURRED OUT
PORTION OF WALL. SEE ARCHITECTURAL DRAWINGS FOR MORE INFORMATION.
PROVIDE 3-PHASE CONNECTION TO MODULAR FURNITURE SYSTEM.
COORDINATE WHIP AND CONNECTION REQUIREMENTS WITH MANUFACTURE.
CIRCUIT AS SHOWN. SEE DETAIL 4/E-10 FOR MORE INFORMATION.
22. LOCATION FOR NEW ROOF MOUNTED EXHAUST FAN. PROVIDE NEW CONDUIT
AND WIRE TO MATCH EXISTING TO EXTEND EXISTING CIRCUIT AND RESTORE
CIRCUIT TO A FULLY FUNCTIONAL STATE. REUSE EXISTING CONDUIT AND WIRE
TO THE EXTENT POSSIBLE.
10. PROVIDE CONNECTION TO GARBAGE DISPOSAL. PROVIDE SWITCH ABOVE
COUNTER FOR CONTROL AND COORDINATE EXACT LOCATION WITH
ARCHITECT PRIOR TO PURCHASE AND INSTALL.
23. NEW CEILING FAN, CIRCUIT AS SHOWN WITH (3) #12 + (1) #12G - 3/4" C. PROVIDE
CONTROLS AT WALL LOCATION DETERMINED BY ARCHITECT. COORDINATE
EXACT LOCATION OF FAN AND CONTROLS PRIOR TO ROUGH IN AND INSTALL.
11. PROVIDE CEILING MOUNTED DATA PORT FOR WIRELESS ACCESS POINT.
(E) MSB DIST
(E) MSB METER/MAIN
(E) DIST PNL DP1
BUILDING NORTH
17. PROVIDE 120V CONNECTION TO MOTORIZED PROJECTION SCREEN. PROVIDE
SWITCH ON WALL TO CONTROL SCREEN. COORDINATE WITH ARCHITECT FOR
LOCATION OF SWITCH PRIOR TO ROUGH-IN AND INSTALL.
PROVIDE NEW DATA CABLING FROM NEW PATCH PANELS IN NEW IDF RACK TO
THIS (E) DATA LOCATION, QUANTITY AS INDICATED. PROVIDE NEW JACKS AND
FACEPLATES.
8.
S
16. PROVIDE RECESSED J-BOX WITH (1) 1-1/2" C. AV TO CEILING MOUNTED LCD
SCREENS J-BOX.
EXTEND EXISTING CONDUIT AND WIRE TO NEW WATER HEATER LOCATION AS
REQUIRED TO RESTORE TO A FULLY FUNCTIONAL STATE.
PROVIDE FULL HEIGHT 4-POST RACK AT THIS LOCATION. UTILIZE (E) IN-SLAB
MOUNTING HARDWARE TO SECURE RACK. SEE DETAIL 2/E-10.
27. PROVIDE 2-COMPARTMENT SURFACE MOUNTED RACEWAY, WIREMOLD SERIES
5400 OR APPROVED EQUAL, TO FEED POWER AND DATA DEVICES. ROUTE
RACEWAY UNDER WINDOWS. COORDINATE EXACT PLACEMENT OF POWER
AND DATA DEVICES WITH ARCHITECT AND AUTHORITY REPRESENTATIVE
PRIOR TO ROUGH IN AND INSTALL.
15. PROVIDE CEILING MOUNTED J-BOXES WITH (1) 3/4" C. POWER TO PANEL, (1) 1"
C. DATA TO IDF, AND (1) 1-1/2" C. AV TO WALL MOUNTED J-BOX FOR CEILING
MOUNTED LCD SCREENS.
PROVIDE CONDUIT DOWN COLUMN TO FEED DEVICES MOUNTED ALONG BACK
PANEL OF CASEWORK. REFER TO ARCHITECTURAL DOCUMENTS FOR
ADDITIONAL INFORMATION.
7.
9.
W
Architecture Interiors Planning
GENERAL NOTES
12. SAW CUT EXISTING SLAB TO FEED NEW FLOOR BOX FOR POWER, DATA, AND
FUTURE AV CONNECTIVITY. REFER TO DETAIL 2/E-11 FOR MORE INFORMATION.
ROUTE (1) 1-1/2" C. AV FROM FLOOR BOX TO J-BOX LOCATION AT STORAGE
ROOM WALL. PROVIDE 3/4" C. POWER FROM FLOOR BOX BACK TO PANEL
BOARD. PROVIDE 1" C. DATA FROM FLOOR BOX TO IDF.
24. NEW FAN COIL UNITS, AC-1 AND AC-2. CIRCUIT AS SHOWN WITH (3) #12 + (1)
#12G - 3/4" C. REFER TO MECHANICAL DRAWINGS FOR MORE INFORMATION.
13. PROVIDE RECESSED J-BOX WITH (1) 1-1/2" C. AV TO FLOOR BOX.
26. PROVIDE 120V/1 CONNECTION TO NEW EXHAUST FAN, EF-3. CIRCUIT WITH (2)
#12 + (1) #12G - 3/4" C TO THE SAME CIRCUIT AS EF-2.
25. NEW CONDENSING UNIT ON ROOF. CIRCUIT AS SHOWN WITH (3) #8 + (1) #10G 3/4" C. REFER TO MECHANICAL DRAWINGS FOR MORE INFORMATION.
2
(E) PNL P1A/P1B
(E)
(E)
P2B-55/57/59
(E)
(E) PNL L1
REG I
E 19203
EXP. 6-30-16
(E)
E
ST
A
2
1
NEER
(E) ROLL DOOR
DISCONNECT
NO
ST
(E)
P1A-26/28/30
(E)
(E) TELEPHONE MPOE
F ESS I ON
PRO
AL
V I D MA
A
I
D
ED
J
(E) PNL OSL
ER
T (E) 150KVA XFMR
GI
EN
TS
P1B-55
(E)
TE
LE
C T R I CA
L
IA
(E)
.
(E)
RN
O F CA L I F O
1
3
P2A-35
P2A-35
(E)
(E)
P2B-61/63/65
J
(EF-2 ON ROOF) 22
WP
P2B-45
(E)
4
+120" AFF
WAP
P1B-69
(E) TELE/DATA
BACKBOARD
(E)
(E) (E)
(E)
P2A-35
P1B-69
P1B-71
(E)
1
P1B-69
1
(E)
IDF
7
(E)
P1B-69
(E)
P2A-35
UP
1
(E)
(E)
1
P1B-47
13
J
(2)
J
J J
J
A-33
1
8
(2)
J
P1A-35
P1A-31
J
(6)
5
6
23
(6)
(E)
P1B-53
(E)
P1B-53
J
J
9
(E)
J
5
P1B-53
6
J (E)
5
24
J
(E)
1
J
WAP
(E)
1
(E)
1
(E)
(E)
P2B-43
P2B-43
(E)
(E)
P2B-43
9
Revisions
5
6
(6)
J
(E)
J
9
6
(6)
P2B-55/57/59 (8)
P2B-73/75/77
PANEL DP-1
9
WP
P2B-45
P2B-73
(2)
WAP
(E)
25 (CU-1 ON ROOF)
WAP
6
TYP 27
Date
6
(E)
(E)
No. Description
P2B-79/81/83
(6)
J
P2B-75
9
(E)
P2B-53
P2B-53
(E)
(E)
(2)
P2B-55
WAP
(2)
24
23
P2B-80/82
DN
6
(2)
J
(2)(E)
(E)
6
J
1
J
5
J
1
P2B-79/81/83
(6)
J
(2)
23
(E)
J
(E)
WAP
P2B-75
P2B-67/69/71
P2B-76/78
P2B-66/68/70
P1B-51
P1B-53
1
(E)
1
(E)
P1A-31 (2)
5
1
1
(E)
6
J
(E)
P1B-53
1
(E)
1
P2B-77
(2)
9
J
J
(E)
(E)
5
(E)
P1A-31 (2)
(E)
(E)
(2)
(E)
(E)
(2)
(E)
(E)
1
(E)
(E)
(E)
(E)
P2B-76/78
11 TYP
(E)
(E)
(2)
(E)
(E)
P2B-49
WP
(E)
P2B-45 P2B-49
(E)
1
(6)
23
(2)
(E)
(E)
(E)
(2)
6
P1B-56
(E)
(E)
(E)
P1B-45
5
P1B-47
P1B-43
(E)
(E) (E)
(E) (2)
(E)
1
P2B-61/63/65
P2B-76/78
(2)
15
(2)
(E)
P2B-77
(E)
10
(E)
DRYER
P2B-45
(E)
P2B-45
(E)
(E)
(EF-1 ON ROOF) 22
P2B-64
P2B-62
(2)
J
(2)
DN
J
5
J
(E)
5
(E)(2) (2)
5
5
(2)
J
(2)
5
(E)
(E) (E)
(E)
J
(E)
WAP
(2)
J
(E)
(E)
1
5
(E)
(E)
WAP
(E)
(6) (E)
P2B-62
1
J
J
12
(E)
WAP
9
P1B-47
P1A-35
J
(E)
(2)
(E)
P2A-33
P1B-47
(E)
(2)
J
J
P2B-74
P2A-29/31
A1S
P2A-33
P1B-47
P1A-31
20
P2A-33
P2A-33
(E)
1
(2)
(E)
1
P2B-62
12
J
(2)
(E) (E)P1B-75
J
17
19
P2A-44 (2)
14
(E)
1
(E)
(2)
(E)
(E)
P1A-35
P1A-35 (2)
P1
UP
P1B-47
P1A-35
(2)
P1A-31
(E)
(E)
18
(E)
(E)
(E)
(E)
P1B-73
WASHER
5
P2B-45
(E)
13
16
21
(E)
1
(E)
(2 )
P1B-73
5
P1B-75
(E) (E) (E) (E)
(2)
P1B-75
(E)
(E)
(E)
P1B-73
1
P1B-73
1
WAP
P1B-69
(E)
(E)
(E)
1
1
(2)
+120" AFF
P2A-46
WAP
(E)
(E)
P2A-35
(E) PNL P2A/P2B
(E)
(E)
WAP
26
(E) SECURITY EQUIP
(R)
(2)
J
P2B-80/82
J
P2B-76/78
(E)
J
(E)
(E)
J
P2B-55
(2)
P2B-55
(2)
P2B-57
P2B-57
(2)
P2B-57
P2B-57
(E)
(2)
P2B-57
J
(2)
J
(2)
J
P2B-57
P2B-57
(2)
(E)
5
6
P2B-57
5
(E)
WP
(E)
WP
6
Scale
1/8" = 1'-0"
2016.01.14
Date
Nov.06,
2015
Job No.
15-57
1/8" = 1'-0"
1/8" = 1'-0"
3
WIRE:
4
MLO
BUS:
225A
VOLTAGE:
SURFACE
10,000
MOUNT:
AIC:
PANEL L1
480/277V
PHASE:
3
WIRE:
4
MAIN:
MLO
BUS:
100A
MOUNT:
SURFACE
35,000
AIC:
PHASE
CKT
1
2
BKR
(E) 20/1
R
A
MEZZ REC
PHASE
NOTES
R
(E) CUBES BY WEST ENTRANCE
B
R
(E) 20/1
3
4
(E) 20/1
R
B
MEZZ REC
(E) CUBES BY WEST ENTRANCE
C
R
(E) 20/1
5
6
(E) 20/1
R
C
CORD DROPS
(E) CUBES IN FRONT OF ELEV
A
R
(E) 20/1
7
8
WH
A
(E) CUBES IN FRONT OF ELEV
B
R
(E) 20/1
9
10
WH
B
(E) CUBES IN FRONT OF ELEV
C
R
(E) 20/1
11
12
WH
C
(E) CUBES NEXT TO TOWER
A
R
(E) 20/1
13
14
(E) 20/1
R
A
(E) FRIDGE
(E) CUBES NEXT TO TOWER
B
R
(E) 20/1
15
16
(E) 20/1
R
B
(E) SPARE (NOT TURNED OFF)
(E) CUBES NEXT TO TOWER
C
R
(E) 20/1
17
18
(E) 20/1
R
C
(E) SPARE (NOT TURNED OFF)
(E) CUBES UNDER PATIO
A
R
(E) 20/1
19
20
R
A
(E) CUBES UNDER PATIO
B
R
(E) 20/1
21
22
R
B
(E) CUBES UNDER PATIO
C
R
(E) 20/1
23
24
R
C
(E) COUNTER REC
A
R
(E) 20/1
25
26
R
A
(E) MICROWAVE
B
R
(E) 20/1
27
28
R
B
(E) TOASTER OVEN
C
R
(E) 20/1
29
30
R
C
REC BOARD ROOM
A
1200
R
(E) 20/1
31
32
R
A
REC BOARD ROOM
B
800
R
(E) 20/1
33
34
R
B
REC BOARD ROOM FLOOR BOX
(E) IRRIGATION CONTROLLER
C
400
R
(E) 20/1
35
36
R
C
A
R
(E) 20/1
37
38
(E) 20/1
R
A
(E) EQUIPMENT
B
R
39
40
(E) 20/1
R
B
(E) EQUIPMENT
C
R
41
42
(E) 20/1
R
C
(E) EQUIPMENT
(E) WATER FOUNTAIN
A
R
(E) 20/1
43
a
44
(E) 20/1
L
A
(E) LUNCH RM LTG 2ND FLR
(E) TIME CLOCK
B
R
(E) 20/1
45
b
46
(E) 20/1
L
B
(E) TRACK LTG 2ND FLR
(E) GFCI RR
C
R
(E) 20/1
47
c
48
(E) 20/1
R
C
(E) RR 2ND FLR
(E) OFFICE REC
A
R
(E) 20/1
49
a
50
(E) 20/1
R
A
(E) SPARE (NOT TURNED OFF)
(E) PATIO REC GFCI
B
R
(E) 20/1
51
52
(E) 20/1
L
B
(E) ENTRANCE TOWER LTG
(E) CONF RM REC
C
R
(E) 20/1
53
c
54
(E) 20/1
R
C
(E) SPARE (NOT TURNED OFF)
(E) ELEC RM REC
A
R
(E) 20/1
55
a
56
(E) 20/1
R
A
(E) COLUMN QUAD REC
(E) SUMP PUMP
B
M
(E) 20/1
57
58
(E) 20/1
L
B
(E) ELEC RM LTG
(E) WAREHOUSE REC
C
R
(E) 20/1
59
60
(E) 20/1
L
C
(E) NIGHT LIGHT
(E) LOBBY REC
A
R
(E) 20/1
61
62
(E) 20/1
R
A
(E) 1ST FLR RR
(E) EAST WAREHOUSE WALL REC
B
R
(E) 20/1
63
64
(E) 20/1
R
B
(E) SPARE (NOT TURNED OFF)
(E) EAST WAREHOUSE WALL REC
C
R
(E) 20/1
65
66
(E) 20/1
L
C
(E) UNDER BRIDGE LTG, CONF RM
(E) ELEV CONTROL
A
R
(E) 20/1
67
a
68
(E) 20/1
L
A
(E) STRIP LTG
(E) SERVER RM REC
B
R
(E) 20/1
69
b
70
(E) 20/1
L
B
(E) STRIP LTG
(E) ELEV PIT REC AND LTG
C
R
(E) 20/1
71
72
(E) 20/1
L
C
(E) TIME CLOCK - EXT POLE LTG
VOLTAGE:
(E) FRONT OFFICE REC
A
R
(E) 20/1
73
74
(E) 20/1
L
A
(E) TIME CLOCK - EXT POLE LTG
PHASE:
3
(E) FRONT OFFICE REC
B
R
(E) 20/1
75
76
(E) 20/1
L
B
(E) MONUMENT SIGN
WIRE:
4
(E) FA SPRINKLER
C
R
(E) 20/1
77
c
78
(E) 20/1
L
C
(E) MONUMENT SIGN
(E) 30A SERVER REC
A
R
(E) 30/1
79
a
80
(E) 20/1
L
A
(E) EXT POLE LTG
(E) 30A SERVER REC
B
R
(E) 30/1
81
b
82
(E) 20/1
L
B
(E) EXT POLE LTG
L
(E) 20/1
83
c
b
a
c
84
(E) 30/3
(E) 40/3
(E) 30/3
(E) 20/1
L
C
NOTES
(E) WAREHOUSE AIR AND HEAT
(E) EQUIPMENT
(E) PALLET JACK CHARGER
(E) EQUIPMENT
b)
PHASE B:
800 VA
7 AMPS
SUBFED CONNECTED:
0.0 KVA
0.0 AMPS
'L' DENOTES LIGHTING LOAD
e)
d)
'WH' DENOTES WATER HEATER LOAD
f)
2.4 KVA
6.7
PANEL IS IEM
ALL (E) INFORMATION IS TAKEN FROM PANEL LABELING
CONTRACTOR SHALL FIELD VERIFY ACCURACY OF CIRCUITS
SCHEDULE NOTES
1
######
VOLTAGE:
PANEL P2A/P2B
208/120V
PHASE:
3
WIRE:
4
LOAD
(E) CLG CONF RM
1
VA
2
R
A
(E) EF
C
L
(E) 20/1
5
6
(E) PORTICO LTG
A
L
(E) 20/1
7
8
9
C
(E) WALL PACKS
(E) 2ND FLR OFFICE LTG
A
L
(E) 20/1
13
14
(E) 20/1
L
A
(E) WAREHOUSE EGRESS LTG
(E) LTG
B
L
(E) 20/1
15
16
(E) 20/1
L
B
(E) LOBBY EGRESS LTG
(E) WEST STAIR LTG
C
L
(E) 20/1
17
18
(E) 20/1
L
C
(E) FRONT OFFICE LTG
(E) 2ND FLR LTG
A
L
(E) 20/1
19
20
M
A
(E) 2ND FLR HALL LTG
B
L
(E) 20/1
21
22
M
B
(E) LTG
C
L
(E) 20/1
23
24
M
C
(E) EMS SUPPLY POWER
A
L
(E) 20/1
25
26
(E) 20/1
L
A
(E) EMERG LTG
SPACE
B
27
28
(E) 20/1
L
B
(E) FRONT OFFICE LTG
SPACE
C
29
30
C
SPACE
SPACE
A
31
32
A
SPACE
SPACE
B
33
34
B
SPACE
SPACE
C
35
36
C
SPACE
SPACE
A
37
38
A
SPACE
SPACE
B
39
40
B
SPACE
SPACE
C
41
42
C
SPACE
LOAD
0 AMPS
CONNECTED:
0.0 KVA
0.0 AMPS
PHASE B:
0 VA
0 AMPS
SUBFED CONNECTED:
0.0 KVA
0.0 AMPS
PHASE C:
0 VA
0 AMPS
DEMAND:
0.0 KVA
0.0
c)
'WH' DENOTES WATER HEATER LOAD
d)
PANEL IS IEM
PANEL OSL
PHASE
VA
4
(E) 20/1
L
B
(E) LTG
(E) LTG
C
L
(E) 20/1
5
6
(E) 20/1
L
C
(E) LTG
SPACE
A
7
8
A
SPACE
SPACE
B
9
10
B
SPACE
SPACE
SPACE
A
13
14
A
SPACE
SPACE
B
15
16
B
SPACE
SPACE
C
17
18
C
SPACE
SPACE
A
19
20
A
SPACE
SPACE
B
21
22
B
SPACE
SPACE
C
23
24
C
SPACE
SPACE
A
25
26
A
SPACE
SPACE
B
27
28
B
SPACE
SPACE
C
29
30
C
SPACE
SPACE
A
31
32
A
SPACE
SPACE
B
33
34
B
SPACE
SPACE
C
35
36
C
SPACE
SPACE
A
37
38
A
SPACE
B
39
40
B
SPACE
BUS:
225A
SPACE
C
41
42
C
SPACE
LOAD
NOTES
R
(E) 20/1
9
10
(E) 20/1
R
B
(E) LOAD
(E) LOAD
C
R
(E) 20/1
11
12
(E) 20/1
R
C
(E) LOAD
(E) FLOOR REC
A
R
(E) 20/1
13
14
(E) 20/1
R
A
(E) LOAD
(E) PHOTO BOOTH
B
R
(E) 20/1
15
16
(E) 20/1
R
B
(E) LOAD
(E) PHOTO BOOTH
C
R
(E) 20/1
17
18
(E) 20/1
R
C
(E) LOAD
A
R
19
20
(E) 20/1
R
A
(E) LOAD
B
R
21
22
(E) 20/1
R
B
(E) LOAD
C
R
23
24
(E) 20/1
R
C
(E) LOAD
A
R
25
26
(E) 20/1
R
A
(E) LOAD
VOLTAGE:
B
R
27
28
(E) 20/1
R
B
(E) LOAD
PHASE:
3
29
30
(E) 20/1
R
C
(E) LOAD
WIRE:
4
0.0 KVA
0.0 AMPS
PHASE B:
0 VA
0 AMPS
SUBFED CONNECTED:
0.0 KVA
0.0 AMPS
PHASE C:
0 VA
0 AMPS
DEMAND:
0.0 KVA
0.0
a
b)
'L' DENOTES LONG CONTINUOUS LOAD
PANEL DP1
208/120V
R
B
(E) LOAD
R
20/1
35
36
(E) 20/1
R
C
(E) LOAD
400
R
20/1
37
38
(E) 20/1
R
A
(E) LOAD
B
400
R
20/1
39
40
(E) 20/1
R
B
(E) LOAD
CUBICLES - 1ST FLR
(E) REC AND RR GFCI
C
400
R
41
42
(E) 20/1
R
C
(E) LOAD
A
R
20/1
(E) 20/1
43
a
44
(E) 20/1
A
REC
(E) REC AND EAST WALL COUNTER
B
R
(E) 20/1
45
b
46
(E) 20/1
B
REC
(E) DISPOSAL
C
R
(E) 20/1
47
c
48
(E) 20/1
C
REC
(E) REC COUNTER
A
R
(E) 20/1
49
a
50
(E) 20/1
A
CONF REC
(E) MENS RR GFCI
B
R
(E) 20/1
51
52
(E) 20/1
B
CONF REC
C
(E) RECS
C
R
(E) 20/1
53
c
54
(E) 20/1
C
REC
A
4200
a
56
(E) 20/1
A
REC
B
4200
R
58
(E) 20/1
B
REC
60
(E) 20/1
C
REC
62
20/1
R
400
A
REC KITCHEN
64
20/1
R
800
B
DISPOSAL
PHASE A:
66
20/1
R
400
C
CUBICLES - 1ST FLR
400
R
20/1
59
A
400
R
20/1
61
2
CUBICLES - 1ST FLR
B
400
R
20/1
63
2
CUBICLES - 1ST FLR
C
400
R
20/1
65
2
CUBICLES - 1ST FLR
A
400
R
20/1
67
a
68
20/1
R
400
A
CUBICLES - 1ST FLR
2
CUBICLES - 1ST FLR
B
400
R
20/1
69
b
70
20/1
R
400
B
CUBICLES - 1ST FLR
CUBICLES - 1ST FLR
C
400
R
20/1
71
72
20/1
R
400
C
EXT REC, GATE
CUBICLES - 2ND FLR
A
400
R
20/1
73
74
20/1
R
800
A
WASHER
b
a
CUBICLES - 2ND FLR
B
400
R
20/1
75
76
CUBICLES - 2ND FLR
C
400
R
20/1
77
c
78
CUBICLES - 2ND FLR
A
400
R
20/1
79
a
80
CUBICLES - 2ND FLR
B
400
R
20/1
81
b
82
CUBICLES - 2ND FLR
C
400
R
20/1
83
c
84
20/2
15/2
20/1
M
100
B
M
100
C
M
150
A
M
150
B
C
NOTES
PHASE
VA
BKR
A
(E)
150/3
B
C
A
(E) PANEL P2A/P2B
(E) PANEL P1A/P1B
CONDENSING UNIT - CU-1
R
BUS:
600A
CEILING FANS
CKT
1
2
3
4
5
6
7
8
9
10
BKR
50/3
PHASE
R
VA
3600
RN
O F CA L I FO
I
SURFACE
35,000
R
3600
B
R
3600
C
R
3600
A
R
3600
B
LOAD
EV CHARGER
C
R
11
12
R
3600
C
A
R
13
14
R
4800
A
B
R
15
16
R
4800
B
R
17
18
R
4800
C
R
19
20
R
4800
A
21
22
R
4800
B
R
23
24
R
4800
C
175 AMPS
CONNECTED:
PHASE B:
21,000 VA
21,000 VA
175 AMPS
SUBFED CONNECTED:
0.0 KVA
PHASE C:
16,800 VA
140 AMPS
DEMAND:
34.4 KVA
DIST PNL IS IEM WITH CUTLET HAMMER BREAKERS
c)
(E)
200/3
40/2
50/3
50/3
50/3
NOTES
A
R
GENERAL NOTES
a)
'R' DENOTES RECEPTACLE LOAD
b)
(E)
200/3
CKT
B
C
EV CHARGER
Revisions
No. Description
Date
WELDING REC
WELDING REC
58.8 KVA
163.3 AMPS
0.0 AMPS
95.6
ALL (E) INFORMATION IS TAKEN FROM PANEL LABELING
CONTRACTOR SHALL FIELD VERIFY ACCURACY OF CIRCUITS
SCHEDULE NOTES
1
FAN COILS - FC-1 AND FC-2
SPARE
65 AMPS
CONNECTED:
20.1 KVA
55.8 AMPS
PHASE B:
37 AMPS
SUBFED CONNECTED:
0.0 KVA
0.0 AMPS
PHASE C:
7,900 VA
66 AMPS
DEMAND:
15.3 KVA
GENERAL NOTES
'R' DENOTES RECEPTACLE LOAD
SCHEDULE NOTES
PROVIDE NEW BREAKER FOR DRYER AND CIRCUIT WITH (3) # 8 + (1) # 10GL - 1"C. PROVIDE RECEPTACLE TO MATCH OWNER EQUIPMENT
1
REMOVE (E) 30A/2P CIRCUIT BREAKER IN THIS SPACE AND PROVIDE NEW BREAKER AS SHOWN.
LOAD
(E) SPARE
7,750 VA
4,450 VA
PHASE A:
600A MCB
AIC:
(E) 20/1
C
MAIN:
MOUNT:
34
CUBICLES - 1ST FLR
L
SCHEDULE NOTES
33
CUBICLES - 1ST FLR
C T R I CA
CONTRACTOR SHALL FIELD VERIFY ACCURACY OF CIRCUITS
20/1
2
LE
ALL (E) INFORMATION IS TAKEN FROM PANEL LABELING
(E) LOAD
2
E
GENERAL NOTES
A
c
E 19203
EXP. 6-30-16
E
CONNECTED:
R
57
FESS I ON
PRO
AL
I D MA
V
A
I
D
ED
AT
0 AMPS
(E) 20/1
20/1
NOTES
0 VA
32
20/1
SURFACE
35,000
PHASE A:
31
R
100A
SURFACE
10,000
B
R
(E) LTG
C
(E) LOAD
400
A
12
(E) ROOF GFCI REC
A
L
11
A
B
VA
C
R
CUBICLES - 1ST FLR
2
BKR
(E) 20/1
SPACE
(E) 20/1
CUBICLES - 1ST FLR
1
3
8
2
BUS:
LOAD
(E) 20/1
7
55
MLO
PHASE
L
(E) 20/1
CUBICLES - 1ST FLR
CKT
B
R
A
CKT
(E) LTG
A
CUBICLES - 1ST FLR
MAIN:
MOUNT:
L
(E) STORAGE RM LTG
1000
CONTRACTOR SHALL FIELD VERIFY ACCURACY OF CIRCUITS
A
(E) LOAD
C
ALL (E) INFORMATION IS TAKEN FROM PANEL LABELING
(E) LTG
C
REC CONF, WAREHOUSE
e)
BKR
(E) 20/1
R
R
(E) 480V DOCK LIFTS
0 VA
480/277V
(E) 20/1
600
(E) 20/3
PHASE A:
'M' DENOTES MOTOR LOAD
6
B
(E) WALL PACKS
L
5
REC KITCHEN
B
(E) 20/1
(E) 20/1
R
L
12
R
3600
10
11
C
A
(E) EMERG LTG
(E) 20/1
(E) OFFICE REC
50/2
A
L
(E) EF
R
L
(E) 20/1
C
B
3600
(E) 20/1
(E) FRONT OFFICE PENDANTS
R
C
C
L
(E) 20/1
DRYER
WH
(E) WATER HEATER
B
4
(E) 20/2
B
(E) 20/1
3
(E) 60/3
WH
(E) 20/3
(E) FRONT OFFICE PENDANTS
(E) 20/1
2
2
(E) WAREHOUSE HIGHBAYS
R
400
a
4
SPACE
PHASE
BKR
(E) 20/1
3
B
(E) LOAD
1
CKT
(E) 20/1
(E) OFFICE REC
(E) DISHWASHER
1
CKT
R
BKR
(E) 20/1
VA
L
A
MLO
MOUNT:
PHASE
A
B
WH
MAIN:
AIC:
NOTES
(E) WAREHOUSE HIGHBAYS
NOTES
LOAD
NEER
6.7 AMPS
'M' DENOTES MOTOR LOAD
2
PHASE
VA
NO
2.4 KVA
c)
1
L
BKR
ST
CONNECTED:
GENERAL NOTES
a)
'R' DENOTES RECEPTACLE LOAD
CKT
A
NOTES
(E) EXT POLE LTG
DEMAND:
CKT
BKR
(E) 20/1
AIC:
10 AMPS
3 AMPS
VA
SCHEDULE NOTES
1,200 VA
400 VA
PHASE
GENERAL NOTES
a)
'L' DENOTES LONG CONTINUOUS LOAD
PHASE A:
PHASE C:
LOAD
(E) WAREHOUSE HIGHBAYS
GI
EN
C
(E) 20/2
(E) 30/3
VA
LOAD
A
(E) FRONT CAN LTG
b)
CKT
BKR
(E) 20/1
(E) LOAD
VA
TE
R
LOAD
(E) CUBES BY WEST ENTRANCE
REG I
S
NOTES
Architecture Interiors Planning
PHASE:
MAIN:
A
PANEL P1A/P1B
208/120V
J.
VOLTAGE:
42.5
Scale
N.T.S
2016.01.14
Date
Nov.06,
2015
Job No.
15-57
Architecture Interiors Planning
(E) PG&E XFMR
NEMA 3R WITH PAD
(E) SWITCHBOARD 'MSB'
IN ELECTRICAL ROOM
M (E)
(E) 600A
(E) 225A
(E) 100A
(E) 100A
(E) 100A
(E) 100A
(E)
REMOTE
LOCATION
CTRL
(E) PNL-OSL
IN ELEC.
ROOM
JUNCTION BOX
(E) PNL-MECH
IN ELEC.
ROOM
(E) PNL-L1
IN ELEC.
ROOM
TOP FEED MODULE
MAIN
BREAKER
NEUTRAL
BUILDING SERVICE
CABINETT
(E) ELEVATOR
IN ELEVATOR CONTROL
ROOM
15 OR 20 AMP
CIRCUIT
BREAKERS
L1
(E) T1 XFMR 150 KVA
WALL OR CEILING
METAL CONDUIT
IN ROOF OF ELECTRICAL ROOM
L2 L3
(E)
.
ER
ST
J
A
TE
LE
C T R I CA
L
IA
REG I
NEER
E
WALL MOUNTED
NO
E 19203
EXP. 6-30-16
ST
GROUND
BAR
(E) DIST. BOARD 'DP1'
F ESS I ON
PRO
AL
V I D MA
A
I
D
ED
GI
EN
BLACK (L1)
RED (L2)
BLUE (L3)
GREEN (GND)
GREEN/YELLOW (1S0 GND)
WHITE (N1)
GRAY/WHITE (N3)
GRAY (N2)
RN
O F CA L I F O
(E) 600A
CONNECT EITHER
TOP FEED OR BASE
FEED (SHOWN)
GROUND
(E) 200A
(E) 200A
(E) 150A
BOND TO CABNET
BASE FEED MODULE
BLACK (L1)
FLEXIBLE CONDUIT
RED (L2)
BLUE (L3)
GREEN (GND)
GREEN/YELLOW (ISO GND)
WHITE (N1)
GRAY/WHITE (N3)
GRAY (N2)
WALL OR FLOOR
METAL CONDUIT
1
WALL OR FLOOR
JUNCTION BOX
4
(E) PNL-P1A-P2B
ELEC. ROOM
LEVEL 1
(E) PNL-P2A-P2B
STORAGE ROOM
LEVEL 2
(E) PNL
IN ROOF
ELECTRICAL SIGLE LINE DIAGRAM
NTS
FURNITURE FEED POWER WIRING & CONTROLS
NTS
LIGHTING
LOAD (a)
CHATSWORTH 90"H X 19", 48 RMU FOUR
POST HEAVY DUTY, UNIVERSAL OPEN
RACK
LIGHTING
LOAD (b)
LMRC-213
DIMMING ROOM
CONTROLLER
LIGHTING
LOAD (b)
NEUTRAL WHT
HOT BLK
120/277V
(2) TOP AND BOTTOM
GROUNDING LUGS
0-10VDC DIMMING
BALLAST REQUIRED.
FIBER PATCH PANELS, QUANTITY AS
REQUIRED
CAT 6 CABLE TO NEW DATA JACK, SEE PLANS
Revisions
No. Description
Date
(X)
LMSW-105
SCENE SWITCH
LMRJ SERIES PRE-TERMINATED
CABLES OR CAT5E. FREE TOPOLOGY
& SPLITTER ACCEPTABLE
LMLS-105 ON/OFF
PHOTOSENSOR
FOR QUANTITY AND LOCATION. (X)
DESIGNATES QUANTITY OF DATA JACKS AND
CABLES REQUIRED AT A GIVEN LOCATION.
48-PORT PATCH PANELS, QUANTITY AS
REQUIRED
LEVITON 49252-P02 HORIZONTAL CABLE
MANAGEMENT, COMBO FRONT & REAR,
ONE PER PATCH PANEL, TYP.
POE PATCH PANELS, QUANTITY AS REQUIRED
72" MAX.
LMLS-105 ON/OFF
PHOTOSENSOR
(AS NEEDED)
DLM OCCUPANCY
SENSOR
NEMA 5-20R
DUAL CIRCUIT VERTICAL
POWER STRIP
(2) PER FLOOR RACK,
TYP.
LMDM-101 DIMMING SWITCHES
WITH LMSW-105 SCENE SWITCH
ACTIVE NETWORK EQUIPMENT, FURNISHED
BY OWNER, INSTALLED BY CONTRACTOR
DETAIL NOTES:
FINISHED FLOOR
RJ45
(TYP.)
EXISTING EXPANSION
ANCHOR BOLTS, 3 1/2" MIN.
EMBEDMENT EACH CORNER
19"
FRONT VIEW
5
DLM DIMMING DIAGRAM
NTS
2
A.
COORDINATE WITH OWNER FOR EXACT
PLACEMENT OF NETWORK EQUIPMENT
B.
PROVIDE ALL FIBER OPTIC AND COPPER
CONNECTORS, PUNCHDOWN BLOCKS, GROMMETS,
HORIZONTAL WIRE MANAGEMENT, SHELF
BRACKETS, CABLE SPLICE KITS, MOUNTING
HARDWARE, ETC. NECESSARY FOR 100% FULLY
FUNCTIONAL AND TESTED INSTALLATION.
C.
ALL EQUIPMENT, JACKS, AND WIRING SHALL
BE RATED FOR USE WITH CAT6 CABLE, MINIMUM.
D.
MANUFACTURER FOR ALL PATCH PANELS,
WIRING, AND JACKS SHALL BE SYSTIMAX OR
APPROVED EQUAL.
FLOOR MOUNTED IDF AND MDF RACK
NOT TO SCALE
Scale
N.T.S
2016.01.14
Date
Nov.06,
2015
Job No.
15-57
WOOD BLOCKING AS REQUIRED - ALL
AROUND
FOR ACCESSIBLE CEILINGS, STUB LEVEL AND TO
WITHIN 2' OF J-HOOKS. FOR GYP BOARD CEILINGS
CONDUITS SHALL BE ROUTED TO MDF/IDF OR
ACCESSIBLE CEILING LOCATION WITH J-HOOKS
(E) 2X WOOD JOISTS
2 X 4 BLOCKING. AT TWO
SIDES MIN TO FASTEN
BLOCKING TO CEILING JOISTS.
WITH 2-16d NAILS OR EQUIVALENT
EACH END. (TYP)
ROOF STRUCTURE,
OR NEXT FLOOR
NYLON BUSHING,
TYP.
PROVIDE 1/4" EYE SCREW WITH
MIN 1" THREADED LENGTH IN
BOTTOM CHORD
3/4" C. MIN.,
(2) #12 GAGE HANGER
WIRE CONNECT TO
STRUCTURE ABOVE
2-GANG J- BOX WITH
SINGLE GANG PLASTER RING,
FACE PLATE & JACKS,
TYP.
CONDITION AT
(E) TRUSS JOIST
(2) #10 SCREWS, FOUR TOTAL
2 X 4 BLOCKING W/ SIMPSON
U24 JOIST HANGAR OR EQUIVALENT
EACH END
LAMP HOLDER
FIXTURE SUPPORT, ROUTE
FIXTURE HANGER WIRE TO
STRUCTURE AS REQUIRED
TWO PER ASSEMBLY
DETAIL NOTES:
SECTION VIEW
JUNCTION BOX AND/OR
TRANSFORMER/BALLAST ASSEMBLY
PLAN
+18"AFF,
UON
FINISHED FLOOR
1. SEE FLOOR PLANS FOR QUANTITY
AND LOCATION OF TELE/DATA/CATV
OUTLET BOXES.
FACEPLATE COLOR AS
DIRECTED BY THE ARCHITECT
CONDITION 2 - INSTALLED IN (E) TRUSS JOISTS
6
FIXTURE REFLECTOR
RECESSED FIXTURE MOUNTING
VERIFY VOICE JACK
REQUIREMTS WITH
SPECIFICATIONS,
TYP.
FINISHED CEILING
DATA
TELE
3.
SCALE: NONE
CAT 6 JACK,
TYP.
GREEN CAT 6, TYP.
DOWNLIGHT FIXTURE MOUNTING
3
BLUE CAT 6, TYP.
TO PUNCH DOWN
BLOCK OR IDF
PROVIDE (4) PORT FACEPLATE, TYP.
4. LABEL ALL FACEPLATES PER SCHOOL
DISTRICT STANDARDS OR DIRECTION (NO
EXCEPTIONS).
TO IDF
5. PROVIDE BLANKS COVERS FOR ALL
UNUSED PORTS.
BLANK
SCALE: NONE
2. TERMINATE AND TEST ALL
TELEPHONE, DATA AND CATV JACKS BACK
TO MDF/IDF AND TO ACTIVE HEADEND
EQUIPMENT.
WALL MOUNTED
OCCUPANCY
SENSOR
E
FOR BUILDING WALL CONSTRUCTION
SEE ARCHITECTURAL DRAWINGS
96"
SWITCH
1
SURFACE MOUNTED FIXTURE
90"
ST
FRONT VIEW
NEER
E 19203
EXP. 6-30-16
WOOD BUILDING STUDS
CATV AND
RECEPTACLE
F ESS I ON
PRO
AL
V I D MA
A
I
D
ED
NO
LABEL POCKETS WITH
CLEAR PLASTIC COVER,
TYP.
GI
EN
6. FOR NEW DATA PORT LOCATIONS IN
EXISTING WALLS, A CUT IN BOX MAY BE
USED, AND WIRING MAY BE FISHED
THROUGH THE EXISTING WALL WITHOUT
THE USE OF CONDUIT. LOCATIONS IN NEW
WALLS SHALL UTILIZE CONDUIT AS
SHOWN.
A
TE
LE
C T R I CA
L
IA
(2) 2 X 4 SLEEPERS AT EACH
SIDE OF DIAGONAL WEB MEMBERS
ER
3/8" DIA MACHINE BOLTS THROUGH SLEEPERS
SECTION
LIGHT FIXTURE, MOUNT BOTTOM
OF FIXTURE FLUSH WITH BOTTOM
OF TRUSS
.
3/8" DIA MACHINE BOLTS THROUGH SLEEPERS
PROVIDE 1/4" EYE SCREW WITH
MIN 2" PENETRATION.
ST
(2) 2 X 4 SLEEPERS AT EACH
SIDE OF DIAGONAL WEB MEMBERS
MIN 1"
J
CONDITION 1 - INSTALLED IN 2X FRAMING
T-BAR CEILING
Architecture Interiors Planning
(E) 2X JOIST, SEE ADJACENT
DETAIL FOR CONDITION AT
(E) TRUSS JOIST
SECURE TO BLOCKING WITH (4) # 10
WOOD SCREWS WITH FLAT WASHER.
PENETRATE 1 1/4" INTO (N) BLOCKING
OR (E) JOISTS.
REG I
PLASTER OR GYPSUM BOARD
CEILING FINISH - REMOVE TO
INSTALL BLOCKING AS
REQUIRED & REPLACE
J-HOOKS, 4' O.C. MIN., 12" MAX. SAG
FOR LOW VOLTAGE CABLING,
TYP.
RN
O F CA L I F O
TELE/DATA/CATV OUTLET DETAIL
SCALE: NONE
RECEPT
DATA / VOICE
RECEPTACLE
48"
48" (REFER TO
CBC 1136a FOR
SPECIAL APPLICATION)
52"
PROVIDE SIMPSON L50 CLIPS ON
TOP AND BOTTOM OF BLOCKING.
SECURE TO BLOCKING WITH 10
PENNY CUT NAILS
FL-500P-4 C LIFT UP LID
PROVIDE FLOOR BOX WITH (2) 20 AMP DUPLEX
RECEPTACLES & (2) TELE/DATA FACEPLATES & JACKS. SEE
POWER & SIGNAL FLOOR PLANS AND AUDIOVISUAL PLANS
FOR QUANTITY AND TYPE OF JACKS REQUIRED.
15"
PROVIDE BLANKS FACEPLATE FOR UNUSE OPENINGS AND
BLANKS FOR UNUSED PORTS.
7
TYPICAL MOUNTING HEIGHTS
DETAIL NOTES:
SCALE: NONE
A.
ALL PART NUMBERS SHOWN ARE FSR
PRODUCTS, NO EQUAL.
B.
SEE FLOOR PLANS FOR QUANTITY AND SIZE
AND ROUTING OF CONDUITS.
C.
SEE SYSTEM DIAGRAMS, POWER & SIGNAL
PLANS & SPECIFICATIONS, AND AUDIOVISUAL
CONSULTANT'S PLANS & SPECIFICATIONS FOR
QUANTITY AND LAYOUT OF RECEPTACLES,
DATA, VIDEO, AUDIO, AND AUDIOVISUAL
SYSTEM CONNECTORS. PROVIDE ALL FITTINGS
AND MISCELLAEOUS HARDWARE FOR A NEAT,
FINISHED AND PROFESSIONAL INSTALLTION.
NO LOSE CABLING OR CONNECTORS
PERMITTED.
D.
ALL OPENINGS SHALL BE CONCEALED WITH A
FACEPLATE OR BLANK PORT JACK, NO
EXCEPTIONS.
E.
ALL FLOOR BOX DOORS SHALL BE INSTALLED
WITH HINGE SIDE FACING FRONT OF STAGE.
PROVIDE 1/4" EYE SCREW WITH
MIN 2" PENETRATION. SEE 3/- SIMILAR.
4 - #10 WOOD SCREWS WITH FLAT WASHER,
4 PER FIXTURE PENETRATE 1 1/4" INTO BLOCKING
BLOCKING TO BUILDING STUDS
STRUCTURE
WIRE TO SUPPORT "T-BAR"
CEILING GRID BY OTHERS (TYP)
4
TWO ADDITIONAL #12 GA SLACK WIRE AT
OPPOSITE CORNERS OF FIXTURE W/ FOUR (4)
TURNS FOR EACH #12 WIRE IN 1-1/2" DISTANCE.
(BY ELECTRICAL CONTRACTOR)
"T-BAR" CLIPS
WALL FIXTURE MOUNTING ON WOOD STUDS
LIGHT FIXTURE
SCALE: NONE
(12) 1" & 1-1/4"
CONDUIT KNOCKOUTS
GROUND TERMINAL
STRUCTURE
ISO VIEW
LAG SCREW 3/8" DIA
2" PENETRATION
ENCLOSURE TOP IS TO
BE PLUMB, LEVEL AND
FLUSH WITH THE FINISHED
CONCRETE SURFACE.
CEILING GRID SYSTEM BY OTHERS
POWER FEED
8
ADDRESS ALL RECEPTACLES AND JACK PER SCHOOL
DISTRICT'S ADDRESSING CONVENTION. TYPICAL.
2' X 2' GRID FIXTURE MOUNTING
TEMPORARY CONSTRUCTION COVER TO BE
REPLACED BY FINISH COVER PRIOR TO CARPET
INSTALLATION. CARPET IS TO BE CUT TO
TOUCH THE SIDES OF THE RAISED TRIM.
4" SQUARE
CEILING
Revisions
5" LONG ADJUSTMENT
SCREWS PROVIDED IN
THE PAN KIT.
FL-GRD4 CONCRETE
POUR PAN
No. Description
Date
SCALE: NONE
4x6 BLOCKING WITH U46 JOIST HANGER
EACH END
WOOD SPACER BETWEEN
STRIPPING
LOCK NUTS (BY
FIXTURE COMPANY)
(E) 2X WOOD FRAMING (SIMILAR
AT TRUSS JOIST)
1 GANG / 2 GANG
POWER / DATA
CROSS BAR (BY
FIXTURE COMPANY)
TUBULAR PENDANT
(BY FIXTURE COMPANY)
CONCRETE
SLAB
4 GANG
AV
CANOPY
WOOD STRIPPING
CANOPY FASTENER
(BY FIXTURE COMPANY)
PROVIDE SIMPSON L50 CLIPS ON
EACH SIDE OF BLOCKING. SECURE
TO BLOCKING WITH 10 PENNY
CUT NAILS. SEE 6/1, CONDITION 2 (SIM)
FOR SUPPORT OF 4X6 AT TRUSS JOIST
GRAVEL FILL
LOCK NUT
GRADE
FASTENING SCREW
ACOUSTIC TILE,
GYPSUM BOARD OR
PLASTER
PROVIDE 1/4" WOOD SCREW WITH FLAT
WASHER WITH MIN 2" PENETRATION.
SECURE TO BLOCKING, ONE EACH
CORNER
GLASS GLOBE
SECTION VIEW
SURFACE MOUNTED
FIXTURE
9
SURFACE FIXTURE MOUNTING
SCALE: NONE
5
PENDANT FIXTURE MOUNTING
SCALE: NONE
2
FSR FL-500-P4 CONCRETE POUR FLOOR BOX DETAIL
SCALE: NONE
Scale
N.T.S
2016.01.14
Date
Nov.06,
2015
Job No.
15-57
SIMSON U24 HANGER OR
EQUIVALENT EACH END
1
4
Architecture Interiors Planning
2" EMBED.
121x121x16GAx121"
(MIN)
1
4
EYESCREW
THREADED
ROD
2x4 MIN ADDED
BLOCKING WHERE (E)
FRAMING DOES NOT
ALIGN WITH
HANGER/WIRE/STRAP
STRAP
WIRE
(CABLE SIMILAR)
.
ST
J
E
ST
CABLE OR WIRE
AT TRUSS
INTERSECTIONS
1
4"
SCREW
(1"MIN EMBED)
P
TE
LE
C T R I CA
L
RN
O F CA L I F O
STRAP
W/ FOLD
C END
AT CENTERLINE
OF BOTTOM
CHORD
P
NEER
E 19203
EXP. 6-30-16
A
1
4
NO
F ESS I ON
PRO
AL
V I D MA
A
I
D
ED
GI
EN
ER
SCALE: NONE
REG I
1
SUPPORT FORM 2x FRAMING & SUPPLEMENTAL BLOCKING
IA
2" MIN
TYP
1
4
16GA x 121"
MIN BENT
PLATE
P
(MAX PERMISSABLE LOAD, P = 20#)
2
SUPPORT FROM TRUSS JOISTS
SCALE: NONE
(E) TRUSS JOIST
3
8
2x4 MIN
2-2x4
(EACH SIDE OF
DIAG WEB MEMBERS)
3x4 MIN
WITH SIMPSON U34
OR EQUIV. EACH END
3x4 MIN
Revisions
No. Description
Date
P = 100#
MAX
ADDED BLOCKING WHERE FRAMING IS NOT ALIGHED WITH
SUPPORT LOCATION OR P > 20#
3
SUPPORT FROM TRUSS JOISTS - CON'TD
SCALE: NONE
Scale
N.T.S
2016.01.14
Date
Nov.06,
2015
Job No.
15-57
STATE OF CALIFORNIA
INDOOR LIGHTING
CEC-NRCC-LTI-01-E (Revised 06/13)
CALIFORNIA ENERGY COMMISSION
LUMINAIRE SCHEDULE+F2:OF2:O14
Indoor Lighting
(Page 1 of 5)
Project Name: Open Space Authority
LAMP
WATTS
LAMP
TYPE
D1
26
LED
BALLAST TYPE
VOLTS
DESCRIPTION
MOUNTING
MANUFACTURER
REMARKS
Climate Zone:
Conditioned Floor Area :
Unconditioned Floor Area :
ELECTRONIC
DIMMING DRIVER
120/277
RECESSED 6" DIAMETER LED DOWNLIGHT. 20 GAUGE
DIE-FORMED GALVANIZED STEEL HOUSING. EXTRUDED
ALUMINUM HEATSIN K. LOW IRIDESCENT ALUMINUM
REFLECTOR WITH CLEAR, SEMI-SPECULAR FINISH. 0-10V
DIMMING CAPABILITIES.
RECESSED
HE WILLIAM S
1. COORDINATE VOLTAGE WITH EXISTING
LED60-PH20-835-EDD* FIXTURES BEING REMOVED. SOME FIXTURES
PH OR APPROVED
MAY BE 120V, WHILE OTHERS MAY BE 277V.
EQUAL
2. COORDINATE CEILING MOUNTING CONDITION
WITH PLANS. PROVIDE T-BAR MOUNTING OR GYP
BOARD MOUNTING AS REQUIRED.
General Information
Building Type:
X Nonresidential
Relocatable Public Schools
Phase of Construction:
New Construction
Method of Compliance:
Complete Building
Hotel/Motel
Unconditioned Spaces
Conditioned Spaces
Addition
X
X Alteration
Area Category
Tailored
Architecture Interiors Planning
FIXTURE
CODE
Date Prepared: 1/4/16
LIGHTING COMPLIANCE DOCUMENTS (select yes for each document included)
P1
P2
13.8/FT
14
LED
LED
ELECTRONIC
DIMMING DRIVER
ELECTRONIC
DIMMING DRIVER
120/277
120/277
LINEAR LED PENDANT. 20 GAUGE DIE-FORMED STEEL
HOUSING WITH INTEGRAL JOINER SYSTEM. FLAT
ENDCAPS. HIGH OUTPUT UPLIGHT, HIGH OUTPUT
DOWNLIGHT. FULLY ADJUSTABLE AIRCRAFT CABLE
MOUNTING. WHITE FINISH. 0-10V DIMMING CAPABILITIES.
DECORATIVE 6" DIAMETER X 8" TALL LED PENDANT.
EXTRUDED WHITE ACRYLIC HOUSING WITH MATTE FINISH.
0-10V DIMMING CAPABILITIES.
PENDANT CABLE
PENDANT CABLE
FINELIGHT SERIES S16
S16LEDID-DCO-8-3E-H
O-HO-3500K-SC-120/27
7-FA-FE-C1 OR
APPROVED EQUAL
BORDEN LIGHTING
345-LED1/14-120/277-S
AL-STEM-0-10VDIM OR
APPROVED EQUAL
1. COORDINATE VOLTAGE WITH EXISTING
FIXTURES BEING REMOVED. SOME FIXTURES
MAY BE 120V, WHILE OTHERS MAY BE 277V.
2. MOUNT BOTTOM OF FIXTURE AT +8'-0" AFF.
1. COORDINATE VOLTAGE WITH EXISTING
FIXTURES BEING REMOVED. SOME FIXTURES
MAY BE 120V, WHILE OTHERS MAY BE 277V.
2. MOUNT BOTTOM OF FIXTURE AT +8'-0" AFF.
For detailed instructions on the use of this and all Energy Efficiency Standards compliance documents, refer to the Nonresidential Manual published by the California Energy Commission.
YES
NO
FORM
TITLE
X
Certificate of Compliance. All Pages required on plans for all submittals.
X
Lighting Controls, Certificate of Compliance, and PAF Calculation. All Pages required on plans for all submittals.
X
Indoor Lighting Power Allowance
X
Tailored Method Worksheets
X
Line Voltage Track Lighting Worksheets
Summary of Allowed Lighting Power
Conditioned and Unconditioned space Lighting must not be combined for compliance
S1
S2
6.1
33
LED
LED
ELECTRONIC
DIMMING DRIVER
ELECTRONIC
DIMMING DRIVER
120
120/277
SURFACE MOUNTED UNDER CABINET 22.25" LED LIGHT
WITH INTEGRAL DIMMING AND OCCUPANCY SENSOR.
SILVER FINISH.
SURFACE MOUNTED 5" DIAMETER LED CAN LIGHT.
XICATO REMOTE PHOSPHOR LED MODULE. SPECULAR
CLEAR ALZAK REFLECTOR CONE. WHITE HOUSING. WIDE
BEAM DISTRIBUTION. 0-10V DIMMING CAPABILITIES.
SURFACE
SURFACE
FINELITE EDGE
SERIES
UC-E-22"-S-PS-8W-OCC
OR APPROVED EQUAL
1. PROVIDE QUANTITY OF POWER SUPPLIES AND
CONNECTOR CABLES AS REQUIRED.
2. PROVIDE QUANTITY OF 22" SECTIONS OF
UNDERCABINET LIGHT TO MATCH LENGTH
SHOWN ON PLANS.
KURT VERSEN
1. COORDINATE VOLTAGE WITH EXISTING
L132-35-ES-WT-PC OR FIXTURES BEING REMOVED. SOME FIXTURES
APPROVED EQUAL
MAY BE 120V, WHILE OTHERS MAY BE 277V.
2. MOUNT BOTTOM OF FIXTURE FLUSH WITH
BOTTOM OF STRUCTURAL TRUSSES. PROVIDE
LENGTH OF STEM AS REQUIRED.
Indoor Lighting Power for Conditioned Spaces
Indoor Lighting Power for Unconditioned Spaces
Watts
+
1.
2.
2570.1
+
PORTABLE ONLY FOR OFFICES
3.
Watts
+
0
603.5
4.
=
Adjusted Installed Lighting Power (row 1 plus row 2 minus row 3)
3599.8
1966.6
603.5
Adjusted Installed Lighting Power
(row 1 minus row 3)
=
2996.3
STATE OF CALIFORNIA
INDOOR LIGHTING
SURFACE
KURT VERSEN
1. COORDINATE VOLTAGE WITH EXISTING
L136-35-ES-WT-PC OR FIXTURES BEING REMOVED. SOME FIXTURES
APPROVED EQUAL
MAY BE 120V, WHILE OTHERS MAY BE 277V.
2. MOUNT BOTTOM OF FIXTURE FLUSH WITH
BOTTOM OF STRUCTURAL TRUSSES. PROVIDE
LENGTH OF STEM AS REQUIRED.
3. MOUNT FIXTURES ABOVE BOARD ROOM TABLE.
COORDINATE EXACT LOCATION WITH OWNER
AND ARCHITECT PRIOR TO ROUGH IN AND
INSTALL.
CEC-NRCC-LTI-01-E (Revised 06/13)
Indoor Lighting
5.
6.
3599.8
120/277
SURFACE MOUNTED LED WALL WASHER. WHITE
HOUSING. CANOPY MOUNT WITH A FULLY ADJUSTABLE
YOKE. 0-10V DIMMING CAPABILITY.
SURFACE
TIMES SQUARE
WX30-9535-W-120/277CM4-010 OR
APPROVED EQUAL
1. COORDINATE VOLTAGE WITH EXISTING
FIXTURES BEING REMOVED. SOME FIXTURES
MAY BE 120V, WHILE OTHERS MAY BE 277V.
2. MOUNT FIXTURE SUCH THAT BOTTOM OF
FIXTURE EXTENDS 2" BELOW THE BOTTOM OF
THE STRUCTURAL TRUSSES SO THE FIXTURE
CAN BE ADJUSTED WITHOUT INTERFERENCE
FROM THE TRUSSES.
NO
Form/Title
X
X
33
LED
ELECTRONIC
DIMMING DRIVER
120/277
RECESSED LED CAN LIGHT WALL WASHER. SPECULAR
ALZAK CONE. WHITE TRIM. 0-10V DIMMING CAPABILITY.
RECESSED
R1
31
36
LED
LED
ELECTRONIC
DIMMING DRIVER
ELECTRONIC
DIMMING DRIVER
UNV
UNV
2' DIAMETER SURFACE MOUNTED LENSED LED LIGHT.
SPUN ALUMINUM OUTER HOUSING WITH MATTE WHITE
POWDER COATED FINISH. FROSTED ACRYLIC LENS. 0-10V
DIMMING CAPABILITY.
RECESSED 2' X 2' LED TROFFER. MATTE WHITE
REFLECTOR AND HOUSING WITH ROUNDED, FROSTED
ACRYLIC LENS. 0-10V DIMMING CAPABILITIES.
SURFACE
RECESSED
LE
C T R I CA
L
RN
O F CA L I F O
multipurpose room, or a theater to be recognized for compliance.
X
KURT VERSEN
1. COORDINATE VOLTAGE WITH EXISTING
A5250-20-35-27-FMR4- FIXTURES BEING REMOVED. SOME FIXTURES
WT OR APPROVED
MAY BE 120V, WHILE OTHERS MAY BE 277V.
EQUAL
2. AIM FIXTURES TOWARDS NEAREST WALL.
3. PROVIDE 0-10V DIMMING BALLAST IN LIEU OF
LUTRON ECOSYSTEM BALLAST.
HE WILLIAMS
1. MOUNT FIXTURE IN EXISTING J-BOX
RNDS-2-L25/835-FXA-DI LOCATIONS. REUSE EXISTING BACKBOX,
M-UNV OR APPROVED CONDUIT, AND WIRE TO THE EXTENT POSSIBLE.
EQUAL
TE
X
X
YES
S6
ST
A
X
S5
E 19203
EXP. 6-30-16
E
for compliance.
NEER
ELECTRONIC
DIMMING DRIVER
F ESS I ON
PRO
AL
V I D MA
A
I
D
ED
NO
LED
Date Prepared: 1/4/16
GI
EN
41.4
(Page 2 of 5)
Project Name: Open Space Authority
YES
S4
CALIFORNIA ENERGY COMMISSION
IA
SURFACE MOUNTED 5" DIAMETER LED CAN LIGHT.
XICATO REMOTE PHOSPHOR LED MODULE. SPECULAR
CLEAR ALZAK REFLECTOR CONE. WHITE HOUSING.
NARROW BEAM DISTRIBUTION. 0-10V DIMMING
CAPABILITIES.
ER
120/277
.
ELECTRONIC
DIMMING DRIVER
ST
LED
J
33
REG I
S3
NO
Form/Title
X
X
X
HE WILLIAMS
LT-22-L34/835-AF-DIMUNV OR APPROVED
EQUAL
STATE OF CALIFORNIA
X1
6
LED
ELECTRONIC
DRIVER
UNV
UNIVERSAL MOUNT LED EXIT SIGN WITH INTEGRAL
BATTERY PACK AND DUAL EMERGENCY LIGHTS. MOLDED
THERMOPLASTIC HOUSING. LED MR16 LAMPS. GREEN
LETTERING. 90 MINUTE RUN TIME.
UNIVERSAL
EMERGILITE
1. MOUNT BOTTOM OF FIXTURE AT 8'-0" AFF.
W-PR-1224H-4-G-2-LJ
OR APPROVED EQUAL
INDOOR LIGHTING
CEC-NRCC-LTI-01-E (Revised 06/13)
CALIFORNIA ENERGY COMMISSION
Indoor Lighting
(Page 3 of 5)
Project Name: Open Space Authority
W1
14
LED
ELECTRONIC
DIMMING DRIVER
UNV
INTERIOR LED WALL SCONCE. SOLID ALUMINUM FINISH.
WHITE ACRYLIC SHIELDING WITH MATTE FINISH. ADA
COMPLIANT.
WALL MOUNTED
Date Prepared: 1/4/16
BORDEN LIGHTING
1. MOUNT FIXTURE IN EXISTING FIXTURE
508-LED2/7-UNV-SAL LOCATION. REUSE EXISTING BACKBOX, CONDUIT,
OR APPROVED EQUAL AND WIRE TO THE EXTENT POSSIBLE.
A separate Lighting Schedule Must Be Filled Out for Conditioned and Unconditioned Spaces. Installed Lighting Power listed on this Lighting Schedule is only for:
W2
34
LED
ELECTRONIC
DIMMING DRIVER
UNV
EXTERIOR TRAPEZOIDAL LED WALL PACK. TYPE II, WIDE
THROW OPTIC DISTRIBUTION. INTEGRAL AUTOMATIC
PROFILE DIMMING. NATURAL ALUMINUM PAINT FINISH.
INTEGRAL PHOTOCELL CONTROLS.
WALL MOUNTED
PHILIPS GARDCO 100 1. MOUNT FIXTURE IN EXISTING FIXTURE
LINE LED
LOCATION. REUSE EXISTING BACKBOX, CONDUIT,
101L-APD-2-35LA-NW-U AND WIRE TO THE EXTENT POSSIBLE.
NIV-NP-PCB-WS OR
APPROVED EQUAL
A. INDOOR LIGHTING SCHEDULE and FIELD INSPECTION ENERGY CHECKLIST
X The actual indoor lighting power listed on this page and on the next page includes all installed permanent and planned portable lighting systems.
X When Area Category Method or Tailored Method is used for compliance, list each different type of luminaire by each different function area on separate lines
Revisions
No. Description
of this compliance form.
Date
shall not be traded between offices having different lighting systems.
Office Portable Luminaire Schedule
A
Complete Luminaire Description (i.e., LED, under
cabinet, furniture mounted
direct/indirect)
Accountabl e
Watts
Office Installed Portable Luminaire Watts Per Square Foot
B
Watts per
Luminaire
C
D
Installed
portable
luminaire watts
in this office
(B x C )
E
F
H
G
Watts per
square foot (D enter zero;
/E)
Field
Inspector
Office Location
I
J
Identify Office area in which these
portable luminaires are installed
ExG
Total installed portable luminaire watts that are greater than 0.3 watts per square foot per office:
Scale
N.T.S
2016.01.14
Date
Nov.06,
2015
Job No.
15-57
STATE OF CALIFORNIA
STATE OF CALIFORNIA
INDOOR LIGHTING
INDOOR LIGHTING
CEC-NRCC-LTI-01-E (Revised 06/13)
CALIFORNIA ENERGY COMMISSION
CEC-NRCC-LTI-01-E (Revised 06/13)
Indoor Lighting
(Page 4 of 5)
Project Name: Open Space Authority
CALIFORNIA ENERGY COMMISSION
Indoor Lighting
Date Prepared: 1/4/16
(Page 5 of 5)
Project Name: Open Space Authority
Date Prepared: 1/4/16
DOCUMENTATION AUTHOR'S DECLARATION STATEMENT
1. I certify that this Certificate of Compliance documentation is accurate and complete.
Documentation Author Name: J. DAVID MAINO
Documentation Author Signature:
Company: INTEGRAL GROUP
Signature Date:
Address: 1084 FOXWORTHY AVE, SUITE 150
CEA/ HERS Certification Identification (if applicable):
City/State/Zip: SAN JOSE, CA 95118
Phone: 408-448-6300
C. INDOOR LIGHTING SCHEDULE and FIELD INSPECTION ENERGY CHECKLIST
Installed Watts
Luminaire Schedule
A
B
C
Location
D
E
F
Field Inspector 1
G
H
RESPONSIBLE PERSON'S DECLARATION STATEMENT
How wattage was
determined
Complete Luminaire Description (i.e, 3 lamp fluorescent troffer,
F32T8, one dimmable electronic ballast)
Primary Function area in which these
luminaires are installed
D1
Recessed LED downlight
26
X
13
338
General lighting for hallways
P1
Linear LED pendant
55.1
X
3
165.3
Conference rm lighting
P2
Decorative LED pendant
14
X
3
42
Reception table lighting
S1
Undercabinet LED light
6.1
X
10
61
Task lighting
S2
Surface mounted LED can light
33
X
24
792
General lighting for board room
S3
Surface mounted LED can light
33
X
8
264
Board room table lighting
S4
Surface mounted LED can light wallwasher
41.4
X
7
289.8
Wall lighting for board room
S5
Recessed LED can light wallwasher
33
X
4
132
Wall lighting for board room
S6
Surface mounted LED lensed fixture
31
X
2
62
Conference rm lighting
R1
Recessed 2'x2' LED troffer
ADA compliant LED wall Sconce
36
X
11
396
Office lighting
14
X
28
2570.1
Stair lighting
W1
2
INSTALLED WATTS PAGE TOTAL:
Pass
Architecture Interiors Planning
A separate Lighting Schedule Must Be Filled Out for Conditioned and Unconditioned Spaces. Installed Lighting Power listed on this Lighting Schedule is only for:
Fail
I certify the following under penalty of perjury, under the laws of the State of California:
1. The information provided on this Certificate of Compliance is true and correct.
2. I am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design or system design identified on this Certificate of Compliance (responsible designer).
3. The energy features and performance specifications, materials, components, and manufactured devices for the building design or system design identified on this Certificate of Compliance conform to the requirements of
Title 24, Part 1 and Part 6 of the California Code of Regulations.
4. The building design features or system design features identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance documents, worksheets, calculations, plans
and specifications submitted to the enforcement agency for approval with this building permit application.
5. I will ensure that a completed signed copy of this Certificate of Compliance shall be made available with the building permit(s) issued for the building, and made available to the enforcement agency for all applicable
inspections. I understand that a completed signed copy of this Certificate of Compliance is required to be included with the documentation the builder provides to the building owner at occupancy.
Responsible Designer Name: J. DAVID MAINO
Responsible Designer Signature:
Company: INTEGRAL GROUP
Date Signed:
Address: 1084 FOXWORTHY AVE, SUITE 150
License: E19203
City/State/Zip: SAN JOSE, CA 95118
Phone: 408-448-6300
Enter sum total of all pages into
STATE OF CALIFORNIA
STATE OF CALIFORNIA
CEC-NRCC-LTI-02-E (Revised 06/13)
CEC-NRCC-LTI-02-E (Revised 06/13)
CALIFORNIA ENERGY COMMISSION
CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE
CERTIFICATE OF COMPLIANCE
(Page 2 of 5)
(Page 1 of 5)
Project Name: Open Space Authority
Project Name: Open Space Authority
Date Prepared: 1/4/16
Date Prepared: 1/4/16
.
ST
J
E
ST
A
with Section 130.4(b).
LE
C T R I CA
L
RN
O F CA L I F O
MANDATORY AND PRESCRIPTIVE INDOOR LIGHTING CONTROL SCHEDULE, PAF CALCULATION, and FIELD INSPECTION CHECKLIST
X
X
TE
IA
REG I
E 19203
EXP. 6-30-16
A separate document must be filled out for Conditioned and Unconditioned Spaces. This page is used only for the following:
X
NEER
X
NO
Control Requirements
NO
F ESS I ON
PRO
AL
V I D MA
A
I
D
ED
GI
EN
YES
ER
Before an occupancy permit is granted for a newly constructed building or area, or a new lighting system serving a building, area, or site is operated for normal use, indoor lighting
controls serving the building, area, or site shall be certified as meeting the Acceptance Requirements for Code Compliance in accordance with Section 130.4.(a). The controls required
PAF Credit Calculation 2
A Track Lighting Supplementary Overcurrent Protection Panel shall be installed in accordance with Section 110.9 and Section 130.3. Additionally, an Installation Certificate shall be
installed in accordance with Section 130.4(b).
X
Standards Complying With 1
Section 130.1.
X
Lighting Control Schedule
A
All luminaires shall be functionally controlled with manually switched ON and OFF lighting controls in accordance with Section 130.1(a).
X
General lighting shall be separately controlled from all other lighting systems in an area. Floor and wall display, window display, case display, ornamental, and special effects lighting
shall each be separately controlled on circuits that are 20 amps or less. When track lighting is used, general, display, ornamental, and special effects lighting shall each be separately
controlled; in accordance with Section 130.0(a)4.
B
C
Type/ Description of Lighting Control
(i.e.: occupancy sensor, automatic time
switch, dimmer, automatic daylight,
#
of Units
D
E
F
G
H
I
J
K
L
M
N
O
Location in Building
X
X
X
Lighting in all Daylit Zones shall be controlled in accordance with the requirements in Section 130.1(d) and daylit zones are shown on the plans.
X
Lighting power in buildings larger than 10,000 square feet shall be capable of being automatically reduced in response to a Demand Responsive Signal in accordance with Section
130.1(e).
Registration Number:
Registration Date/Time:
BOARD ROOM
OCC. SENSOR, DAYLIGHT CONTROLS
1
X
X
X
X
E
N/A
X
1477.8
0.25
369.45
X
OFFICES
OCC. SENSOR, DAYLIGHT CONTROLS
3
X
X
X
X
E
N/A
X
144
0.25
36
X
CONFERENCE ROOMS
OCC. SENSOR, DAYLIGHT CONTROLS
3
X
X
X
X
E
N/A
X
341.3
0.25
85.325
X
WORK ROOM
OCC. SENSOR
1
X
X
X
N/A
E
N/A
N/A
61
0.25
15.25
X
HALLWAY
OCC. SENSOR
2
X
X
X
N/A
E
N/A
N/A
390
0.25
97.5
X
HERS Provider:
Registration Number:
Registration Date/Time:
HERS Provider:
STATE OF CALIFORNIA
STATE OF CALIFORNIA
INDOOR LIGHTING POWER ALLOWANCE
CEC-NRCC-LTI-02-E (Revised 06/13)
CEC-NRCC-LTI-03-E (Revised 06/13)
CALIFORNIA ENERGY COMMISSION
CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE
CERTIFICATE OF COMPLIANCE
(Page 3 of 5)
Project Name: Open Space Authority
(Page 1 of 4)
Project Name: Open Space Authority
Date Prepared: 1/4/16
Date Prepared: 1/4/16
INSTALLED WATTS PAGE TOTAL: 2570.1
IF MULTIPLE PAGES ARE USED, ENTER SUM TOTAL OF ALL PAGES HERE:
LOWED LIGHTING POWER (Chose Method)
A separate page must be filled out for Conditioned and Unconditioned Spaces. This page is only for:
A. SUMMARY TOTALS OF LIGHTING POWER ALLOWANCES
DOCUMENTATION AUTHOR'S DECLARATION STATEMENT
1. I certify that this Certificate of Compliance documentation is accurate and complete.
Documentation Author Name: J. DAVID MAINO
Documentation Author Signature:
Company: INTEGRAL GROUP
Signature Date:
Address: 1084 FOXWORTHY AVE, SUITE 150
CEA/ HERS Certification Identification (if applicable):
City/State/Zip: SAN JOSE, CA 95118
Phone: 408-448-6300
X If using Area Category Method, Tailored Method, or a combination of Area Category and Tailored Method for compliance, use only the total in column (b) as the total
allowed building watts
(a)
(b)
Revisions
No. Description
Date
3599.8
RESPONSIBLE PERSON'S DECLARATION STATEMENT
B. COMPLETE BUILDING METHOD LIGHTING POWER ALLOWANCE
A
B
C
WATTS PER (ft2)
COMPLETE BLDG.
AREA
X
Documentation Author Name: J. DAVID MAINO
Responsible Designer Signature:
Company: INTEGRAL GROUP
Date Signed:
Address: 1084 FOXWORTHY AVE, SUITE 150
License: E19203
City/State/Zip: SAN JOSE, CA 95118
Phone: 408-448-6300
D
ALLOWED WATTS
=
Total Area:
Registration Number:
Registration Date/Time:
Total Watts. Enter Total Watts into section A, row 1 (Above on this page)
Watts
HERS Provider:
CORRIDOR .
450
OFFICE (< 250 SF) .
445
CONFERENCE .
Registration Number:
Registration Date/Time:
2704.8
HERS Provider:
Scale
N.T.S
2016.01.14
Date
Nov.06,
2015