Technical Reference Conduit Capacity Chart Conduit Size 1/2 3/4 I.D., inches .622 .824 1.049 1.380 1.610 2.067 2.469 3.068 3.548 4.026 4.506 5.047 1 1 1/4 1 1/2 2 2 1/2 3 3 1/2 4 4 1/2 5 Permissible Area* 0.12 0.21 0.34 0.60 0.82 1.34 1.92 2.95 3.96 5.09 6.38 8.00 15 9 6 5 3 3 2 2 1 1 1 1 – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – 27 17 12 8 6 5 4 3 3 2 2 1 1 1 1 1 1 – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – 44 28 19 14 11 8 7 5 4 4 3 3 2 2 2 1 1 1 1 1 1 1 1 – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – 76 48 33 24 19 15 12 10 8 7 6 5 4 4 3 3 3 2 2 2 2 1 1 1 1 1 1 1 1 1 1 – – – – – – – – – – – – – – – – – – – – – – – – – – 103 66 46 33 25 20 16 13 11 9 8 7 6 5 5 4 4 3 3 3 2 2 2 2 2 1 1 1 1 1 1 1 1 1 1 1 1 – – – – – – – – – – – – – – – – – – – – 170 109 75 55 42 33 27 22 18 16 13 12 10 9 8 7 6 6 5 5 4 4 4 3 3 3 3 2 2 2 2 2 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 – – – – – – – – 243 156 108 79 60 48 39 32 27 23 19 17 15 13 12 10 9 8 8 7 6 6 5 5 4 4 4 4 3 3 3 3 3 2 2 2 2 2 2 2 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 376 240 167 122 94 74 60 49 41 35 30 26 23 20 18 16 15 13 12 11 10 9 8 8 7 7 6 6 5 5 5 4 4 4 4 3 3 3 3 3 3 2 2 2 2 2 2 2 2 2 2 1 1 1 1 1 1 503 322 223 164 125 99 80 66 55 47 41 35 31 27 24 22 20 18 16 15 13 12 11 11 10 9 8 8 7 7 6 6 6 5 5 5 5 4 4 4 4 3 3 3 3 3 3 3 2 2 2 2 2 2 2 2 2 648 414 288 211 162 128 103 85 72 61 52 46 40 35 32 28 25 23 21 19 18 16 15 14 13 12 11 10 10 9 8 8 8 7 7 6 6 6 5 5 5 5 4 4 4 4 4 3 3 3 3 3 3 3 3 2 2 812 519 360 265 203 160 129 107 90 76 66 57 50 44 40 35 32 29 26 24 22 20 19 17 16 15 14 13 12 11 11 10 10 9 8 8 8 7 7 7 6 6 6 5 5 5 5 4 4 4 4 4 4 3 3 3 3 1018 652 452 332 254 201 163 134 113 96 83 72 63 56 50 45 40 36 33 30 28 26 24 22 20 19 18 16 15 14 14 13 12 11 11 10 10 9 9 8 8 8 7 7 7 6 6 6 6 5 5 5 5 5 4 4 4 Cable O.D. Cable Area inch Sq. inch 0.100 0.125 0.150 0.175 0.200 0.225 0.250 0.275 0.300 0.325 0.350 0.375 0.400 0.425 0.450 0.475 0.500 0.525 0.550 0.575 0.600 0.625 0.650 0.675 0.700 0.725 0.750 0.775 0.800 0.825 0.850 0.875 0.900 0.925 0.950 0.975 1.000 1.025 1.050 1.075 1.100 1.125 1.150 1.175 1.200 1.225 1.250 1.275 1.300 1.325 1.350 1.375 1.400 1.425 1.450 1.475 1.500 0.008 0.012 0.018 0.024 0.031 0.040 0.049 0.059 0.071 0.083 0.096 0.110 0.126 0.142 0.159 0.177 0.196 0.216 0.238 0.260 0.283 0.307 0.332 0.358 0.385 0.413 0.442 0.472 0.503 0.535 0.567 0.601 0.636 0.672 0.709 0.747 0.785 0.825 0.866 0.908 0.950 0.994 1.039 1.084 1.131 1.179 1.227 1.277 1.327 1.379 1.431 1.485 1.539 1.595 1.651 1.709 1.767 Important Note: This conduit capacity chart is to be used as a general guideline. Because local codes can vary from the National Electrical Code, West Penn Wire cannot be held responsible for this information as it pertains to your installation. Proper conduit fill is the sole responsibility of the installer and it is your responsibility to see that your installation will pass local codes. * Permissible Area to be occupied (sq. in.) based on the NEC standard of 40% fill, which applies to three or more non-lead covered cables installed in the same conduit. 183