1214 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 23, NO. 3, MAY 2008 Three-Phase Three Level, Soft Switched, Phase Shifted PWM DC–DC Converter for High Power Applications Dharmraj V. Ghodke, Member, IEEE, Kishore Chatterjee, and B. G. Fernandes Abstract—A new three-phase, three-level dc to dc phase shifted pulsewidth modulation (PWM) converter is proposed for high power and high input voltage applications. Output voltage is controlled by incorporating phase shift PWM. Clocked gate signals of each leg are phase shifted by 2 3 from each other. Major features of the converter include: 1) outer two switches of each leg are turned on and off as zero voltage switching, 2) inner two switches of each leg are turned on and off as zero current switching, and 3) this is achieved without involving any extra passive or active components. The secondary side of the converter is of center tapped full-wave current tripler type. This results in an increase of ripple frequency by a factor of six, leading to a significant reduction in size of the output filter. In order to obtain behavioral and performance characteristics of the proposed converter topology, detailed analytical and simulation studies are carried out. Finally the viability of the scheme is confirmed through detailed experimental studies on a laboratory prototype developed for the purpose. Index Terms—High power dc to dc converter, soft switching, three-phase three-level (TPTL), zero voltage zero current switching (ZCS). I. INTRODUCTION VER the years single phase full-bridge (FB) and three-phase FB pulsewidth modulation (PWM) dc to dc soft switched converters have become popular in the field of dc to dc conversion system. For these converters metal oxide semiconductor field effect transistors (MOSFETs) are generally preferred over insulated gate bipolar transistors (IGBTs), because they can be operated at higher switching frequency and they do not have the problem of long tail current. However, these FB PWM soft switched converters are not suitable for switch mode power supply applications, where the input voltage is high. This is because the MOSFETs have to sustain high input dc link voltage. Moreover, service of auxiliary circuits is required to operate devices in soft switched mode. This requires extra components, devices and hence it O Manuscript received August 18, 2006; revised August 3, 2007. This paper was presented in part at the IEEE PESC’05, Recife, Brazil, June 12–17, 2005. Recommended for publication by Associate Editor J. Kolar. D. V. Ghodke is with the Laser System Engineering Division (LSED), Raja Ramanna Center for Advanced Technology, Indore 452013, India and also with the Department of Electrical Engineering, Indian Institute of Technology Bombay, Mumbai 400076, India (e-mail: dvghodke@cat.ernet.in). K. Chatterjee and B. G. Fernandes are with the Department of Electrical Engineering, Indian Institute of Technology Bombay, Mumbai 400076, India (e-mail: kishore@ee.iitb.ac.in; bgf@ee.iitb.ac.in). Color versions of one or more of the figures in this paper are available online at http://ieeexplore.ieee.org. Digital Object Identifier 10.1109/TPEL.2008.920881 leads to incurring additional cost while reducing the system reliability. In order to reduce the voltage stress to half of the input dc voltage, a three-level topology has been considered in [1] and [2] for inverter application and it has been used for realizing a dc to dc converter in [3]–[5]. The soft commutation is achieved by using phase shift PWM modulation [4], [5] which is having simple control structure and high power density can be achieved. However at high power levels, these components experience considerable current stress. In order to overcome this problem, topologies consisting of three-phase inverter coupled to a three-phase high frequency transformer followed by three-phase high frequency bridge-rectifier have been proposed [6]–[9]. This results in an increase in the input current and output current frequencies by a factor of three as compared to the full bridge converter. This also results in lower current rating for the components and also a considerable reduction in size for the isolation transformer. However, the devices experience high voltage stress and the control structure is also quite involved. In an effort to overcome the aforementioned limitations a new converter topology involving three-phase, three-level, (TPTL) phase shifted PWM converter involving six switches operating as zero voltage switching (ZVS) and six switches operating as zero current switching (ZCS) has been presented in this paper. It should be mentioned that in this case soft switching of the semiconductor devices is achieved without taking help from any additional auxiliary circuitry comprising of active or passive elements. In the proposed topology the output rectifier is a center tapped full wave current tripler [10], [11] producing either two or three-level output voltage depending on the operating duty cycle. This leads to considerable reduction in size of the output filter compared to that of the conventional full bridge topology. The principle of operation and exhaustive analytical studies for the proposed converter is presented. In order to obtain behavioral and performance characteristics of the converter, detailed simulation studies are carried out. Finally the viability of the scheme is confirmed through detailed experimental studies on a 6.6 kW laboratory prototype developed for the purpose. Finally, extension of the proposed converter for different output voltage and multiphase configurations has been illustrated. II. PROPOSED SOFT SWITCHED DC TO DC CONVERTER A. Power Circuit Configuration The power circuit configuration of TPTL dc to dc converter is shown in Fig. 1. Each leg is having four switches, two clamping diodes and one coupling flying capacitor. Considering the first leg top and bottom switches S1 and S4 are controlled by signals 0885-8993/$25.00 © 2008 IEEE Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY BOMBAY. Downloaded on December 31, 2008 at 01:46 from IEEE Xplore. Restrictions apply. GHODKE et al.: TPTL, SOFT SWITCHED, PHASE SHIFTED PWM DC–DC CONVERTER 1215 Fig. 1. Proposed three-phase three-level (TPTL) soft switched dc to dc converter. A and and inner switches S2 and S3 are controlled by signals B and respectively. The same logic is followed for the other two legs of the converter. Duty cycle of 0.5 is maintained for each switch. A short turn on delay is introduced to eliminate cross conduction. Signals A and B (similarly signals C & D and E & F of other phases) are having uniform phase shift from each other in a range of 0 to 120 in order to control the output voltage. Further, the switching signals of the adjacent legs (A, C, and E) are phase shifted by 120 with respect to each other. Three high frequency single-phase transformers, with star connected primary, are employed to obtain the required isolation between primary and secondary side. At the secondary side, three single-phase, center tapped full wave rectifiers are connected in ) across parallel through three-output filter inductors a common output filter capacitance . The three centre tapped rectifiers are being fed by three single phase transformers. Three primary windings of these three transformers are connected to the three legs of three level inverter. Output current of the rectifier is the sum of the output currents of three single-phase center tapped full wave rectifiers. As there exists a 120 phase difference among the transformer secondary voltages, the frequency of the full-wave output voltage is six times to that of the inverter frequency. The junction of diodes, D1 and D2, D3 and D4, and D5 and D6 are all connected together to form the common node point, . B. Principle of Operation In order to achieve output voltage control while realizing ZVS for outer switches (S1 and S4) and ZCS for inner switches (S2 and S3), a phase shifted PWM (PSPWM) is adopted for each phase. The switch-timing diagram for the range of duty cycle, from 0 to 1/3 is shown in Fig. 2, for the range of from 1/3 to 2/3 is shown in Fig. 4 and for the range of from 2/3 to 1 is shown in Fig. 6. Following assumptions are made for the purpose of analysis. All power devices except the outer switches of each leg are considered ideal. Outer switches of each leg (S1 and < D <1/3. Fig. 2. Switch-timing diagram for duty cycle 0 S4, S5 and S8, S9 and S12) are considered along with its parasitic capacitance. Capacitors C1 and C2 are large enough to be treated as voltage sources having a magnitude of 2. Flying capacitors C3-C5 are large enough to be treated 2. as a voltage sources having magnitude of Effect of magnetizing inductance of the three-phase high frequency transformer has been neglected. Output filter inductors are large enough to be treated as constant current sources during a switching period, so that each filter inductor carries current of magnitude 3. Operating modes for 0 1/3: Mode-1 ( to ), [Fig. 2] and [Fig. 3(a)]: Before the initiation of this mode, the switches S1, S3, S6, S8, S9, and S11 are on, so the node points, and are all connected to the dc link mid point, . As a result the primary voltages of the transformer are zero. Moreover, the primary current of transformer-B is carried by the primary winding of transformer-C therefore, primary current of transformer-A is zero. As all the primary winding voltages of the transformer is zero, output current of each filter inductor present in the secondary side of the transformer, is free-wheeling through output rectifying diodes, D7–D12. Mode-1 is initiated when switch S3 is turned off and Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY BOMBAY. Downloaded on December 31, 2008 at 01:46 from IEEE Xplore. Restrictions apply. 1216 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 23, NO. 3, MAY 2008 switch S2 is turned on at . As a result starts increasing and starts decreasing. The switch S2 turns on as ZCS, due to presence of transformer leakage reactance in series with it. is less than As long as primary current of transformer-A, the corresponding reflected secondary load current , rectifying diodes D7 and D8, continue to conduct. This leads to clamping of both the primary and secondary winding voltages of the transformer to zero. The current flows from the positive dc rail to the leakage inductance of the phase-A transformer. Then it flows through two equal leakage inductances of phase-B and phase-C of the transformers. These currents then finally terminate at positive plate of capacitor, C4 and negative plate of capacitor C5. The potential of positive plate of C4 and nega2 respective to the negative dc rail, tive plate of C5 are both Hence positive plate of C4 and negative plate of C5 and negative plate of C1 are all having the same potential. The effective inductance present in the current path is (3L )/2, therefore (1) this mode ends when current at and becomes equal to the reflected load 0. therefore (2) Mode-2 ( to ), [Fig. 2] and [Fig. 3(b)]: After instant, power from the primary side of the transformer is transferred to the load. Diode D8 turns off and D7 carries one third of the 2. As priload current. Primary voltage of transformer-A is mary currents of transformer B and transformer C are less than reflected secondary current, voltages across windings of transis virformer B and transformer C are zero. Thus the node tually at same potential as that of node . Primary windings of , where n is turns the transformers B and C will carry ratio of the transformer. Mode-3 ( to ) [Fig. 2] and [Fig. 3(c)]: At , S1 is turned off. The primary current of transformer-A, charges and discharges via flying capacitor C3. This happens and .The capacitor and limit the rate as of rise of voltage across S1, thereby rendering it the property of effectively is in series with L1, ZVS. During this mode, and L1 can be treated as a constant current source. Hence, the primary current is . Voltages across and can be expressed as (3) (4) At a result rises to and decays down to zero. As and are having the same potential. Therefore, (5) Where, Mode-4 ( to ), [Fig. 2] and [Fig. 3(d)]: From instant , body diode of S4 starts conducting and this provides zero 0. A small difference voltage turn-on condition for S4 as in voltage between the mid point potential and the voltage on C3 will get applied across leakage inductance of the primary to decrease. If is not decreased winding, which causes to zero, switching of other leg forces it to zero. As is less than the reflected secondary current, diode D7 and D8 start conducting simultaneously and therefore clamps both the primary and secondary voltage of the transformer to zero. The above switching sequence gets repeated for S7 and S8 during to ; and for S10 and S9 during to . 2/3 Mode: Operating modes for 1/3 Mode-1 ( to ) [Fig. 4] and [Fig. 5(a)]: Before the initiation of this mode, switches S1, S3, S6, S8, S11, and S12 are , and are connected to the mid on, so the node points, is connected to the point of the dc link, N and the node point -ve rail of the dc link. As a result voltage across transformer-A 2 is applied across the priand transformer-B is zero and and mary winding of transformer-C. Hence, node points are at same potential. Primary windings of transformer-B and and transformer-C are carrying current 0. The currents through filter inductors, L1 and L2 are free-wheeling through the respective output rectifying diodes, D7–D10 and the current flowing through the filter inductor L3, 3 which is carried by D12. Mode-1 is initiated when S3 is is . The switch S2 turns turned off and S2 is turned on at on as ZCS, due to presence of transformer leakage reactance in series with it. As long as the primary current of transformer-A, is less than the corresponding reflected secondary load cur, rectifying diodes D7 and D8 continue to conduct. rent This leads to clamping of both the primary and secondary volt2 is applied across ages of the transformer-A to zero. as a result rises linearly in the direction and at the same starts decresing. The expression for for this mode time is given as (6) becomes equal to the reflected load current and At becomes zero. The duration of this mode is therefore (7) Mode-2 ( to ) [Fig. 4] and [Fig. 5(b)]: In mode-1, the is equal to primary current of the transformer-C, and is carried by S11 and S12. From onwards, primary curalso becomes equal to as a rent of transformer-A, result D8 turns off and D7 carries one third of load current. The voltage applied across the primary winding of transformer-A is 2 and voltage across transformer-B is zero. Therefore node, is at same potential as that of N, and nodes and are connected to ve rail and ve rail of the dc link voltage respectively. As a result the primary winding of transformer-B will carry the difference of ripple currents of the two filter inductors which is negligible (around 0.02 p.u to 0.03 p.u) from all practical considerations, even though devices S6 & S8 are ON. In this mode leg-B is not carrying any current, therefore if whenever S6 is switched off or S7 is switched on subsequently they will do so as ZCS. Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY BOMBAY. Downloaded on December 31, 2008 at 01:46 from IEEE Xplore. Restrictions apply. GHODKE et al.: TPTL, SOFT SWITCHED, PHASE SHIFTED PWM DC–DC CONVERTER 1217 (a) (b) (c) (d) Fig. 3. (a) Equivalent circuit for mode-1. (b) Equivalent circuit for mode-2. (c) Equivalent circuit for mode-3. (d) Equivalent circuit for mode-4. Mode-3 ( to ) [Fig. 4] and [Fig. 5(c)]: At , S12 is charges turned off. The primary current of transformer-C, and discharges , limiting the rate of rise of voltage across S12 thereby imparting it the property of ZVS. Leakage is in series with L3. As L3 inductance of transformer-C, is large enough, primary current magnitude remains almost con. The voltage across rises linearly and the stant at decays linearly whose expressions are voltage across (8) (9) At rises to 2 and decays to zero. The pois 2. The interval of this mode is, tential of the node, therefore (10) where Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY BOMBAY. Downloaded on December 31, 2008 at 01:46 from IEEE Xplore. Restrictions apply. 1218 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 23, NO. 3, MAY 2008 C. Switching Behavior of Outer and Inner Switches The outer switches operate as ZVS. The ZVS operation of outer switches is explained by considering switches S1 and S4. The remaining outer switches, S5, S8 and S9, S12 will also behave in similar fashion. When S1 is turned off, the switch , thereby charging this capaccurrent flows through the . This charging and itor and discharging other capacitor discharging current mainly depends on the phase inductance, which consists of the transformer leakage inductance and reflected dc filter inductance of each phase. If the total phase inductance is large enough, the switches can achieve ZVS with fairly low load current. The outer switches are turned off at the end of power transfer mode, and the reflected load current in and discharges . The enthe primary winding charges ergy stored in the large dc filter inductor is responsible for introducing this duration of charging and discharging so that the switches operate as ZVS. As the switches are turned on while the body-diodes are conducting, they do so at zero voltage and zero current condition. However, turn-on losses will be incurred if the snubber capacitors are not fully discharged when the switches are turned on. This can be avoided if it is ensured that the load draws a minimum current, having magnitude (11) < D <2/3. Fig. 4. Switch-timing diagram for duty cycle 1/3 Mode-4 ( to ) [Fig. 4] and [Fig. 5(d)]: From the instant , body diode of S9 conducts which provides zero voltage turn with respect on condition for S9 as the potential of the node is zero. Node is connected to the dc to the node, and are connected to the node, . The prirail and node is less than the reflected load mary current of transformer-C, current. As a result D11 and D12 conduct simultaneously. This clamps both the primary and secondary voltages of the transformer-C to zero. The above switching sequence is repeated for S6 and S7 to , wherein S6 is turned off and S7 is turned on during at zero current. Similarly during to , S1 is turned off and S4 is turned on as ZVS. During to , S11 is turned off and to S8 is S10 is turned on as a ZCS. And finally, during turned off and S5 is turned on as a ZVS. 1: The switch-timing diaOperating modes for 2/3 1 is shown in Fig. 6. gram for the range of duty cycle, 2/3 There are 12 operating modes in a switching half cycle. Output voltage becomes nearly independent of the duty cycle variation and remains almost constant. It is not a usable range of operation for closed loop control, so the switching states are not explained in detail. The inner switches operate as ZCS. The ZCS operation of inner switches is explained by considering the example of switches S2 and S3. The remaining inner switches, S6, S7 and S10, S11 will also behave in similar fashion. While turning on, the leakage inductance of transformer which is in series with the switch helps to turn it on as ZCS. Moreover, this ZCS behavior of the switch is independent of the reflected load current at the primary side of the transformer. Current carried by a conducting switch depends on currents of other two phases. When the upper switch of one phase and the lower switch of remaining phase are on, the current flowing through the switch becomes zero thereby accomplishing ZCS condition for the switches while they are getting turned off. Hence ZCS condition for the switches has been achieved without involving any additional resetting circuit. The necessary condition for accomplishing ZCS is that the reflected load current should be higher than the magnetizing current of the transformer and also the current flowing through the filter inductance should be continuous. D. Steady State Transfer Characteristic 2/3: The output voltage waveform For Duty Cycle, 0 2/3 is shown in Fig. 7. Voltage apof the rectifier for 0 plied across any one of the output filter inductors, (L1–L2) in a switching cycle is (12) Defining as Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY BOMBAY. Downloaded on December 31, 2008 at 01:46 from IEEE Xplore. Restrictions apply. GHODKE et al.: TPTL, SOFT SWITCHED, PHASE SHIFTED PWM DC–DC CONVERTER 1219 (a) (b) (c) (d) < D < 2/3]. (b) Equivalent circuit for mode-2, [1/3 < D < 2/3]. (c) Equivalent circuit for mode-3, [1=3 < D < < D < 2/3]. Fig. 5. (a) Equivalent circuit for mode-1, [1/3 2/3]. (d) Equivalent circuit for mode-1, [1/3 Considering 0 hence (14) The average of the sum of the any one of the filter inductor voltage, which is the output voltage is given by (13) and Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY BOMBAY. Downloaded on December 31, 2008 at 01:46 from IEEE Xplore. Restrictions apply. 1220 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 23, NO. 3, MAY 2008 Fig. 8. Controller configuration for the proposed TPTL dc to dc converter. For Duty Cycle, 2/3 1: If the device capacitance and leakage inductance of the transformer are neglected the output voltage for this range of duty cycle variation can be shown as (16) As the output voltage is independent of duty cycle in this mode, this mode does not have any significance so far as closed loop control of the converter is concerned. E. Control Strategy Fig. 6. Switch-timing diagram for duty cycle 2/3 The schematic block diagram of the controller for the proposed TPTL dc to dc converter is shown in Fig. 8. It consists of a single voltage controller loop, three phase shift PWM controllers (UCC3895N), 660 kHz oscillator, divide by three-ripple counter, clock distribution and phase synchronization circuit. The single voltage controller loop feeds the compensated error to the PWM controllers. This signal is voltage common for the three PWM controllers. The distribution logic block synchronizes the ramp signals of PWM IC’s for phase shift control so that the clock pulse for each PWM controller is having an 120 phase shift from each other. < D <1. F. TPTL Small Signal Model Fig. 7. Rectified output voltage of the three phases of the converter for 0 D <2/3. < which on simplification leads to (15) The power stage of the proposed TPTL phase shift dc to dc converter along with the transformer and rectifiers can be replaced by three equivalent pulsating sources, ( and ) as illustrated in Fig. 9(a). The frequency of each source is 2 , where, is switching frequency of the converter. These pulsating sources can be averaged over a switching cycle. As each pulsating source is in series with a large filter inductor, each of these sources can be replaced by a single source ,( and ) as shown in Fig. 9(b). The frequency of this equivalent source is . This equivalent source is in series with the equivalent filter inductance and and equivalent leakage inductance, , here 2/3 for 0 1/3 and 1 for 1/3 2/3. As is considerably small compared to , its effect can be neglected. The equivalent model of the system is shown in Fig. 9(e). Considering the equivalent series Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY BOMBAY. Downloaded on December 31, 2008 at 01:46 from IEEE Xplore. Restrictions apply. GHODKE et al.: TPTL, SOFT SWITCHED, PHASE SHIFTED PWM DC–DC CONVERTER 1221 Fig. 10. Simplified average model of TPTL. Fig. 9. Deduction of average model of TPTL. resistance of filter inductor and the output filter capacitor as shown in Fig. 10, the transfer function of the TPTL converter system s-domain can be expressed as Fig. 11. Open loop frequency response of TPTL. (17) where and (18) is load resistance, is output filter capaciwhere the is the equivalent series resistance of filter inductance, is equivalent series resistance of output filter capactance, is equivalent output filter inductor. The open loop freitor, quency response of the system is shown in Fig. 11. The param350 H, 1330 F, eters chosen for the purpose are 1.833 0.001 0.0167 600 V, 100 V. III. SIMULATION AND EXPERIMENTAL RESULTS To confirm the validity of the proposed scheme detailed simulation studies are carried out using MATLAB power system 800 V, blockset. The parameters chosen for simulation are 60 V, 6 kW 100 kHz. Simulation perfor2/3 are mance results for the range of duty cycle, 0 shown in Figs. 12 and 13. Fig. 12(a) shows the voltage across S2 (inner switch) and the current flowing through it and these quantities during turning on instant are shown on extended time scale in Fig. 12(b). It can be inferred from the aforementioned figures that S2 behaves as ZCS while turning on and turning off. Fig. 13(a) shows voltage across S1 (outer switch) and the current through it. When the device is turned off, the current flowing through it charges the snubber capacitor present across S1. While S1 is getting turned the current initially flows through the body diode of the device. Therefore, the device behaves as a ZVS during turn-on and turn-off transient. This behavior of the device is depicted in Fig. 13(a) and (b). It can be inferred from these figures that the inner switches of a leg of the converter are operated as ZCS and that the outer switches of a leg of the converter are operated as ZVS. In order to verify the viability of the scheme detailed experimental studies are carried out on a laboratory prototype developed for the purpose. The prototype is designed for an output power rating of 6.6 kW. The components selected for laboratory prototype are provided in Table I. The prototype is designed for an input voltage rating of 650 V having an output voltage control range between 90 to 110 V. The output current rating is 60 A. The switching frequency of the semiconductor devices is maintained at 110 kHz. Figs. 14 and 15 show the gate to source voltage and drain to source voltage of switch S1, while turning on and off, respectively. Once the voltage across switch has almost reached zero, gate to source voltage is applied, showing the ZVS turn on action for S1. During turning off transient, it can be seen from Fig. 15 that the drain to source voltage of the switch starts rising only after gate to source voltage of the switch has assumed zero value. Hence it can be inferred that S1 turns off in Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY BOMBAY. Downloaded on December 31, 2008 at 01:46 from IEEE Xplore. Restrictions apply. 1222 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 23, NO. 3, MAY 2008 (a) (a) (b) (b) Fig. 12. (a) Drain to source voltage and drain current for Switch S2. TR1: voltage across switch S2 (100 V/div.), TR2: Current through switch S2 (10 A/div.). (b) Drain to source voltage and drain current for Switch S2 while turning on. TR1: voltage across switch S2 (100 V/div.), TR2: Current through switch S2 (10 A/div.). ZVS mode. Figs. 16 and 17 show the drain to source voltage and drain current through switch S2 while turning on and off, respectively. Hence it can be inferred that S2 operates in ZCS mode during transition from off state to the on state and vice versa. Fig. 18 shows oscillogram records of one of the trans55 A former primary voltages and its winding current, at 95 V, while Fig. 19 shows the same set of waveand 10 A and 95. It can be verified from forms for the aforementioned waveforms that the idling and/or circulating currents of devices and the transformer windings are considerably low both for full load and light load conditions. The closed loop frequency response of the system obtained experimentally utilizing the laboratory prototype is depicted in Fig. 20. It can be Fig. 13. (a) Drain to source voltage and drain current for Switch S1. TR1: voltage across switch S1 (100 V/div.), TR2: Current through switch S1 (10 A/div.). (b) Drain to source voltage and drain current for Switch S2 while turning on. TR1: voltage across switch S2 (100 V/div.), TR2: Current through switch S2 (10 A/div.). observed that this experimentally obtained frequency response of the system matches closely with that obtained analytically (Fig. 11) [12]–[14]. The power loss distribution in the laboratory prototype of the converter estimated by following the procedure presented in [15] while the converter is delivering 60A of load current at 95 V is shown in Fig. 21. The overall estimated efficiency of the prototype is 92.03%. The measured efficiency of the converter 95 V and as a function of the output current at 650 V, is shown in Fig. 22. The efficiency at full load condition 60 A and 95 V) is 91.5% and maximum effi( ciency of 92.2% occurs when the converters delivers 45 A of Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY BOMBAY. Downloaded on December 31, 2008 at 01:46 from IEEE Xplore. Restrictions apply. GHODKE et al.: TPTL, SOFT SWITCHED, PHASE SHIFTED PWM DC–DC CONVERTER 1223 TABLE I COMPONENTS USED IN THE LABORATORY PROTOTYPE Fig. 14. Drain to source voltage and gate to source voltage for Switch S1, while 95 V, I 55 A.TR1: Gate to source voltage for turning on, when V switch S1 (10 V/div.), R2: voltage across switch S1 (100 V/div.). = = load current. Photograph of the laboratory prototype of the proposed converter is shown in Fig. 23. ZVS condition of outer devices is load current dependent, and it is lost during light load condition. The ZVS soft switching behavior for the outer switches of the proposed converter is very similar to that of full-bridge phase shift converter presented in [16]. Therefore the same analysis presented in [16] can be extended for the proposed converter, and the minimum load current to achieve ZVS for the laboratory prototype of the converter utilizing the aforementioned analysis is found to be 12.6 A. Similar to the full-bridge phase shifted converter presented in [16], the converter proposed in this paper exploits the leakage inductance of the transformer to achieve ZVS for the outer switches. Hence extension of the ZVS characteristic of the concerned converter switches over a wide range of load can be achieved by Fig. 15. Drain to source voltage and gate to source voltage for Switch S1, while 95 V, I 55 A.TR1: Gate to source voltage turning off, when V for switch S1 (10 V/div.), TR2: voltage across switch S1 (100 V/div.). = = connecting external inductances in conjunction with the transformers [4], [16], [17]. In order to achieve ZCS condition for the concerned switches of the proposed converter, the following two conditions have to be satisfied: first the reflected load current should be higher than the magnetizing current of transformer and secondly, the current flowing through the filter inductor is should be continuous. The peak magnetizing current given by (19) Therefore, the peak magnetizing current for the prototype of the proposed converter is around 0.886 A, In order to have the magnetizing current less than reflected current, the minimum load current has to be more than 5.32A. The minimum load current for achieving the condition of continuous current flow through Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY BOMBAY. Downloaded on December 31, 2008 at 01:46 from IEEE Xplore. Restrictions apply. 1224 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 23, NO. 3, MAY 2008 Fig. 16. Drain to source voltage and drain current for Switch S2, while turning 95 V, I 55 A, TR1: Current through switch S2 on, when V (4 A/div.), TR2: voltage across switch S2 (100 V/div.). = = Fig. 17. Drain to source voltage and drain current for Switch S2, while turning 95 V, I 55 A, TR1: Current through switch S2 off, when V (4 A/div), TR2: voltage across switch S2 (100 V/div.). = = Fig. 18. Voltage across primary-A winding of transformer and it’s current for 95 V, I 55 A, TR1: voltage across one of the transformer priV mary (100 V/div.), TR2: Current through same transformer primary (10 A/div.). = = Fig. 19. Voltage across primary-A winding of transformer and it’s current for 95 V, I 10 A, TR1: voltage across one of the transformer priV mary (100 V/div.), TR2: Current through same transformer primary (2 A/div.). = = the output filter inductor can be shown to be (very similar to basic buck regulator) (20) Therefore, the minimum load current required to make the filter inductor current continuous conduction mode is 1.578 A. Hence if load current is more than 5.32 A, ZCS condition of the concerned switches of the laboratory prototype of the proposed converter will be satisfied. The ZCS range can be increased by increasing the magnetizing inductance of the transformer. Fig. 20. Experimentally obtained open loop frequency response of TPTL. Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY BOMBAY. Downloaded on December 31, 2008 at 01:46 from IEEE Xplore. Restrictions apply. GHODKE et al.: TPTL, SOFT SWITCHED, PHASE SHIFTED PWM DC–DC CONVERTER 1225 by slightly modifying the output rectifier configuration. Several such possible configurations are depicted in Fig. 24. The converter configurations shown in Fig. 24(a) and (b) are having almost the same output voltage and current ratings as that of the proposed basic converter configuration. Fig. 24(a) is derived from the classical current tripler configuration while Fig. 24(b) is current hexa configuration formed with six-rectifier diode involving six-filter inductor. Here each diode and filter inductor current will be one sixth of the load current. Therefore, this configuration is suitable for applications where output current is high. A conventional configuration to negotiate this type of load would require paralleling of several diodes along with their balancing circuits which are very difficult to design. Configurations depicted in Fig. 24(c) and (d) are having twice the output voltage rating as that of the proposed basic converter configuration and hence they are suitable for medium voltage and medium current applications. Both configurations are of classical current tripler type. Fig. 24(e) and (f) are conventional three-phase full wave bridge rectifiers with single output filter inductors. The voltage rating for these configurations is almost four times that of the proposed basic configuration and hence they are suitable for high voltage low current applications. In addition to these modifications, the primary connection of the star connected transformer can be changed to delta for increasing the output voltage rating of the converter. Output voltage for topology shown in Fig. 24(a) and (b) can be derived on similar line given in Section II-C1 Fig. 21. Estimated loss distribution of TPTL dc to dc converter (in watts). (21) Fig. 22. Efficiency versys load current for the proposed converter (for V 650 V, V 95 V). = = On similar line the output voltage for topology shown in Fig. 24(c) and (d) can be derived to be (22) And the output voltage for topology shown in Fig. 24(e) and (f) can be derived to be (23) B. Multiphase Configuration The three-phase dc to dc converter topology with phase shifted controller can be extended to multiphase topology as shown in Fig. 25 by adding more number of inverter legs along with it’s own phase shift controller maintaining proper phase shifted clocked signal. In this case, the frequency of the input current pulsations would be n times and the frequency of the than output voltage seen by the output filter capacitor is 2 that of a single phase topology [3]–[5], [19], [20]. Fig. 23. Prototype of a 6.6 kW three-phase three-level dc to dc converter. V. CONCLUSION IV. EXTENSION OF TPTL CONVERTER CONFIGURATIONS A. Secondary Rectifier Configurations for Different Voltages The aforementioned TPTL topology discussed so far is suitable for low voltage and high current applications. Loads requiring higher voltage for the same output power can be handled A new soft-switched, TPTL dc to dc converter with phaseshift PWM converter is proposed. It has been shown that this topology is particularly suitable for high output as well as high input voltages. The proposed converter is having the following performance features: 1) low switching losses over a wide range of load, 2) low idling and circulating currents, resulting in low conduction losses in switching devices and low copper losses Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY BOMBAY. Downloaded on December 31, 2008 at 01:46 from IEEE Xplore. Restrictions apply. 1226 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 23, NO. 3, MAY 2008 Fig. 24. TPTL secondary rectifier configurations for different output voltages (same transformer can be used, as volt-second product of primary winding of transformer remains same). on a 6.6 kW laboratory prototype developed for the purpose. It has been shown that the proposed TPTL converter topology can be extended to several multiphase configurations. Additional suggestions are also provided to employ different output rectifier configurations for effectively generating various levels of output voltages. ACKNOWLEDGMENT The authors would like to thank M. O. Ittoop, A. Sharma, K. M. Krishnan, and B. K. Arya, for their help. REFERENCES Fig. 25. TPTL extension to multiphase configuration for dc to dc converter. in the transformers, 3) additional passive or active auxiliary circuits are not required to realize ZVS or ZCS, 4) reduced duty cycle loss is achieved thereby increasing the effective control range, and 5) presence of the center tapped full wave rectifier at the three phase transformer secondary side and -connection on primary side, halves the output voltage, without increasing the turns ratio of transformer. As a result of the aforementioned merits, the proposed dc to dc converter can accept high input voltage while negotiating loads requiring low output voltage and high currents. Detailed steady state analysis of the converter is presented. Effectiveness of the proposed converter is confirmed through detailed simulation studies. Viability of the proposed scheme is verified by performing detailed experimental studies [1] A. Nabae, I. Takahashi, and H. Akagi, “A new neutral point clamped PWM inverter,” IEEE Trans. Ind. Appl., vol. IA-17, no. 5, pp. 518–523, Sep./Oct. 1981. [2] Y. Kim, B. S. Seo, and D. S. Hyun, “A novel structure of multilevel high voltage source inverter,” in Proc. IEE 5th Eur. Conf. Power Electron. Appl., Sep. 1993, vol. 7, pp. 132–137. [3] J. R. Pinheiro and I. Barbi, “The three-level ZVS-PWM DC-to-DC converter,” IEEE Trans. Power Electron., vol. 8, no. 4, pp. 486–492, Oct. 1993. [4] F. Canales, P. Barbosa, J. Burdio, and F. C. Lee, “A zero voltage switching three-level dc–dc converter,” in Proc. IEEE INTELEC’00, 2000, pp. 512–517. [5] Y. Jang and M. M. Jovanovic, “A new three-level soft-switched converter,” IEEE Trans. Power Electron., vol. 20, no. 1, pp. 75–81, Jan. 2005. [6] P. D. Ziogas, A. R. Prasad, and S. Manias, “Analysis and design of a three phase off-line DC/DC converter with high frequency isolation,” in Proc. IEEE Ind. Appl. Soc. Annu. Meeting, 1988, pp. 813–820. [7] A. K. S. Bhat and R. L. Zheng, “A three-phase series-parallel resonant converter-analysis, design, simulation, and experimental results,” IEEE Trans. Ind. Appl., vol. 32, no. 4, pp. 951–960, Jul./Aug. 1996. [8] R. W. De Doncker, D. M. Divan, and M. H. Kheraluwala, “A threephase soft-switched high-power-density DC/DC converter for highpower applications,” IEEE Trans. Ind. Appl., vol. 27, no. 1, pp. 63–73, Jan./Feb. 1991. [9] D. S. Oliveira and I. Barbi, “A three-phase ZVS PWM DC/DC converter with asymmetrical duty cycle for high power applications,” in Proc. IEEE Power Electron. Spec. Conf., 2003, vol. 2, pp. 616–621. Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY BOMBAY. Downloaded on December 31, 2008 at 01:46 from IEEE Xplore. Restrictions apply. GHODKE et al.: TPTL, SOFT SWITCHED, PHASE SHIFTED PWM DC–DC CONVERTER [10] J. Zhou, M. Xu, and F. C. Lee, “A novel current-tripler dc–dc converter,” in Proc. IEEE Power Electron. Spec. Conf., 2003, vol. 3, pp. 1373–1378. [11] S. Kim, “New multiple dc–dc converter topology with a high frequency zig-zag transformer,” in Proc. IEEE Appl. Power Electron. Conf. Expo, 2004, vol. 1, pp. 654–660. [12] F. Canales, P. Barbosa, and F. C. Lee, “A zero-voltage and zero-current switching three-level DC/DC converter,” IEEE Trans. Power Electron., vol. 17, no. 6, pp. 898–904, Nov. 2002. [13] D. V. Ghodke and K. Muralikrashan, “Zvzcs dual, two-transistor forward Dc-Dc converter with peak voltage of Vin/2, high input and high power application,” in Proc. IEEE Power Electron. Spec. Conf., 2002, vol. 4, pp. 1853–1858. [14] X. Ruan and B. Li, “Zero-voltage and zero-current-switching PWM hybrid full-bridge three-level converter,” in Proc. IEEE Power Electron. Spec. Conf., 2002, vol. 4, pp. 1847–1852. [15] J. Minibock, J. W. Kolar, and H. Ertl, “Design and experimental analysis of a 10 kW dual 400/48 V interleaved two-transistor dc–dc forward converter system supplied by a VIENNA rectifier i,” in Proc. Int. Conf. Power Conv. Intell. Motion (PCIM), Jun. 6–8, 2000, [CD ROM]. [16] R. Redl, N. O. Sokal, and L. Balogh, “A novel soft-switching fullbridge DC/DC converter: analysis, design considerations, and experimental results at 1.5 kW, 100 kHz,” IEEE Trans. Power Electron, vol. 6, no. 3, pp. 408–418, Jul. 1991. [17] E. Deschamps and I. Barbi, “A flying-capacitor ZVS PWM 1.5 kW DC-to-DC converter with half of the input voltage across the switches,” IEEE Trans. Power Electron, vol. 15, no. 5, pp. 855–860, Sep. 2000. [18] A. R. Prasad, P. D. Ziogas, and S. Manais, “Analysis and design of a three-phase offline dc–dc converter with high-frequency isolation,” IEEE Trans. Ind. Appl., vol. 28, no. 4, pp. 824–832, Jul./Aug. 1992. [19] D. de Souza Oliveira and I. Barbi, Jr., “A three-phase ZVS PWM dc–dc converter with asymmetrical duty cycle for high power applications,” IEEE Trans. Power Electron., vol. 20, no. 2, pp. 370–377, Mar. 2005. [20] F. Canales, P.M. Barbosa, and F.C. Lee, “A zero-voltage and zerocurrent-switching three-level dc–dc converter,,” in IEEE Proc. Appl. Power Electron. Conf. Expo, New Orleans, LA, 2000, pp. 314–320. 1227 Kishore Chatterjee was born in Calcutta, India, in 1967. He received the B.E. degree in power electronics from the Maulana Azad College of Technology, Bhopal, India, in 1990, the M.E. degree in power electronics from Bengal Engineering College, Howrah, India, in 1992, and the Ph.D. degree in power electronics from the Indian Institute of Technology, Kanpur, in 1998. From 1997 to 1998, he was a Senior Research Associate at the Indian Institute of Technology, Kanpur, where he was involved with a project on power factor correction and active power filtering, which was being sponsored by the Central Board of Irrigation and Power, India. He was an Assistant Professor in the Department of Electrical Engineering, Indian Institute of Technology, Bombay, since 1998 and has been as Associate Professor there since 2005. His current research interests are modern var compensators, active power filters, utilityfriendly converter topologies, and induction motor drives. B. G. Fernandes received the B.Tech. degree from Mysore University, Mysore, India, in 1984, the M.Tech. degree from the Indian Institute of Technology, Kharagpur, in 1989, and the Ph.D. degree from the Indian Institute of Technology, Bombay, in 1993. He then joined the Department of Electrical Engineering, Indian Institute of Technology, Kanpur, as an Assistant Professor. In 1997, he joined Department of Electrical Engineering, Indian Institute of Technology, Bombay, where he is currently Professor. His current research interests are in permanent magnet machines, high-performance ac drives, quasi-resonant link converter topologies, and power electronic interfaces for nonconventional energy sources. Dharmraj V. Ghodke (M’07) was born in Solapur, Maharashatra, India, on October, 20, 1968. He received the B.E. degree in electrical engineering from W.C.E Sangali, Shivaji University Kolhapur, India, in 1991, and is currently pursuing the Ph.D. degree in power electronics at the Indian Institute of Technology Bombay, Mumbai, India. After graduation he joined 35th Batch Training School, Department of Atomic Energy, Bhabha Atomic Research Center, Mumbai. After training in 1992, he joined the Center for Advanced Technology (CAT), Indore, India, as Scientific Officer. Here, he demonstrated the first indigenous solid state pulsed modulator for copper vapor laser, a replacement of thyratron based modulator. He also designed and developed various low voltage and high voltage isolated switch mode power supply, capacitor charging power supply, trigger and driver units, power ranging from 1 W to 11 kW for lasers and control applications a replacement of linear power supply. His specialty areas includes high frequency, high power switch mode and solid state pulse power supply, auxiliary controllers and circuits for laser applications. His current research interest includes simulation and digital controller of PWM active UPF rectifiers, active filters, and ac to dc and dc to dc converters, for high power applications. Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY BOMBAY. Downloaded on December 31, 2008 at 01:46 from IEEE Xplore. Restrictions apply.