Offshore Substation Earthing, Bonding and Lightning Protection technical standards ETS-04 Rev. 3 Document no. 56361/10, Case 10/4054 - ETS-04 v. 3 Revision survey Document title Earthing, Bonding and Lightning Protection Document no. 56361-10 Target group Fabrications Contractors and Designer for Offshore substations. Revision 1 2 Document status Approved Approved after review Writer Init N/A xomo Reviewer Date Init 12.10.09 N/A POD,XBOH, 26.10.12 SGH, POB, JEJ Approver Date Init 12.10.09 SGH 26.10.2012 SGH Date 18.09.12 Minor alterations, type errors, rephrases' e.t.c where the meaning of the text is left unchanged are not shown. Appendix no. and description None Document no. 56361/10, Case 10/4054 - ETS-04 v. 3 Revision Table of contents 1. Scope 4 2.1 2.2 References Statutory Regulations Codes and Standards 4 4 4 3.1 3.2 Definitions and Abbreviations Definitions Abbreviations 4 4 5 2. 3. 4. Technical Requirements 4.1 Earthing and bonding 4.1.1 General 4.1.2 Earth electrode 4.1.3 Earthing 4.1.4 Equipotential Bonding 4.2 Lightning 4.2.1 General 4.2.2 Lightning damage protection 4.2.3 Equipment requiring protection 5. 5 5 5 5 8 9 10 10 10 11 5.1 Certificates / Data books General 11 11 6.1 6.2 Appendix A: Overall earthing and bonding principles LV systems B: Bonding principles for structure and equipment 12 12 13 6. Document no. 56361/10, Case 10/4054 - ETS-04 v. 3 1. Scope This technical standard specifies the basic requirements for the earthing, bonding and lightning protection to be established on an offshore located transformer platform (Substation) for offshore wind power farms established in the Danish offshore sector. 2. References 2.1 Statutory Regulations 2.2 2006/95/EC Low Voltage Directive (LVD). 2004/108/EC EMC Directive. Codes and Standards DS/EN 50164 IEC 60092 IEC 60364 IEC 61000 IEC 61892 IEC 62305 DNV-OS-J201 DEFU Recommendations Nr. 25 Lightning Protection Components. Electrical installations in ships. Low voltage electrical installations - Protection for safety and protection against electric shock. Electromagnetic compatibility (EMC). Mobile and fixed offshore units – Electrical installations. Protection against lightning. Offshore Substation for Wind Farms. Lightning protection of wind turbines. 3. Definitions and Abbreviations 3.1 Definitions Shall: Verbal form used to indicate requirements to be strictly followed in order to conform to the standard and from which no deviation is permitted, unless accepted by all parties. Should: Verbal form used to indicate that among several possibilities one is recommended as particularly suitable, without mentioning or excluding others, or that a certain course of action is preferred but not necessarily required. May: Verbal form used to indicate a course of action permissible within the limits of the standard. Document no. 56361/10, Case 10/4054 - ETS-04 v. 3 4/13 3.2 Can: Verbal form used for statements of possibility and capability, whether material, physical or casual. Abbreviations ABA CCTV HVAC LEMP LPS LPZ SCADA PE UPS “Automatisk Brand Alarm system” Automatic fire alarm system Closed Circuit Television Heating, Ventilation and Air Conditioning Lightning electromagnetic impulse Lightning protection system Lightning protection zone Supervisory control and data acquisition Protective earth Uninterruptible Power Supply 4. Technical Requirements 4.1 Earthing and bonding The earthing and bonding shall comply with the Low Voltage Directive 2006/95/EC, IEC 60364, IEC 61892 and DEFU 25. Further, ref. clause 4.2.1, IEC 62305 shall be adhered to. 4.1.1 General To ensure safety of personnel and apparatus in case of electrical equipment failures, and to prevent fires, mechanical damage or malfunction resulting from lightning or static electricity, proper earthing and equipotential bonding shall be made. The earthing system shall comprise main earth electrodes, main earth bus, branch conductors and connectors. If the unit has separate modules, every single module shall have its own individual main earth electrodes, main earth bus, branch conductors and connectors. Extraneous conductive parts of all the modules shall be tied together by means of connections to the common equipotential bonding system. The bonding shall be such as to give a substantially equal potential and a sufficiently low earth-fault loop impedance to ensure correct operation of protective relays. 4.1.2 Earth electrode Platform support structure (jacket) can be made of concrete or steel. Both models can be assumed to establish a solid and effective earth electrode which applies to grounding and protection against lightning on the platform. Bonding using 95 mm2 copper wire shall be performed at bolted connections. If the foundation is made as a steel jacket, it will together with its piles into the seabed act as a solid and efficient earth electrode. Document no. 56361/10, Case 10/4054 - ETS-04 v. 3 5/13 If the foundation is made as steel mono piles, as figure 1, the steel tube is considered as a huge earth rod, and it is only necessary to make sufficient conductive and corrosion resistant connections between the pile and the tower bottom. As the monopole and the transition section is not directly connected, an equipotential bonding directly between the two sections in the bottom of the tower should be performed. For flexible connections between monopole and transition tower section, equal to least 95 mm2 Cu Corrosion and mechanical protection must be considered, e.g. use stainless steel. Fig. 1 Document no. 56361/10, Case 10/4054 - ETS-04 v. 3 6/13 If the foundation is made as a concrete structure (fig. 2a + 2b), reinforcement shall be performed as a continuous electrical network, and can be welded, bolted or securely tied together all the way from top to bottom. The connection point to the foundation earth shall be fixed earthing terminals of stainless steel located in the top of the structure. Concrete caissons Connections of Reinforcement in meshes, size 3-5 m, in top and bottom of foundation by welding or clamping Concrete caissons Tower flange bolt connected to the reinforcement bars Fig. 2a Tower flange bolt connected to the reinforcement bars Connections of Reinforcement in meshes, size 3-5 m, in top and bottom of foundation by welding or clamping Fig. 2b Document no. 56361/10, Case 10/4054 - ETS-04 v. 3 7/13 The connecting conductor from the foundation earth electrode to the steel bottom of the platform shall be installed at min. 4 connection points at the bottom of the lower deck. Each of these connections must be performed through copper wire 95 mm2 and be removable test connections to support structure (jacket). 4.1.3 Earthing Requirements and recommendations for system earthing, i.e. an intentional connection of the neutral point of the electrical power system to the structure are specified according to IEC 61892-2, Clause 5. The selection of methods of treating the neutral for a specific power system shall be based on technical and operational factors. The selection of neutral earthing method shall be based on one of the following methods: Directly earthed (TN-S system). Impedance earthed (IT system) Isolated (IT system) A summary of principal features of the neutral earthing methods are listed according to IEC 61892-2, Table 1. The earth reference points shall be earth bars. The earth bar for protective earth (PE) shall be located in all relevant technical rooms. The main earth bars shall be solidly earthed via connections to a minimum of two earth bosses for each earth bar, welded to the main platform structure. Earth cables for these connections shall at least be 95mm2 Cu. The earthing of the platform shall be designed for a short circuit current of at least 16kA for 1 sec. Exact level of short circuit current shall be established in detailed design. Earth bars shall be fabricated from copper and shall be prepared with suitable drilled holes for the required size and number of connections. The PE bar or the earth boss shall act as the main connection point for the following equipment: On site standby generator neutral point 33/0,4kV transformers neutral point UPS systems neutral point Earth bars in HV/MV and LV switchgear PE earth bars in instrument panels All other electrical equipment and electrical consumers shall be earthed via earth core in the supply cables. Document no. 56361/10, Case 10/4054 - ETS-04 v. 3 8/13 The PE earth bar shall act as the connection point for the individual instrument panel PE bars. The instrument panel PE bars shall act as earthing point for instrument cable screens and for spare/unused instrument cable cores. See section 6 appendix for further details. 4.1.4 Equipotential Bonding Bonding shall be made locally in close proximity to the items which require bonding. Normally bonding connections shall be made by bolted connections to steel pads (earth bosses) which shall be welded to the steel deck or structure. Every bonding connection to earth shall be of copper or other corrosion resistant material and shall be securely installed and protected where necessary against damage and also against galvanic corrosion. Connections shall be secured against becoming loose due to vibration. All equipment bonding connections shall be made with suitable compression cable lugs. Equipment and items to be bonded shall include: All metallic components of the structure which is not welded to the platform main structure Metallic enclosures of electrical equipment Metallic doors Stairs, ladders and railings Steel cable ladders and trays Piping systems Tanks and vessels Packaged units Not insulated earthing connections (connectors/ bolts) shall be sealed in such a way that corrosion is avoided. Minimum cross section in the local earthing shall be copper wire 10 mm2 due to mechanical strength. Consumers can be earthed either through supply cable or through local cable earthing. Local earthing is preferred. See section 6 appendix for further details. Document no. 56361/10, Case 10/4054 - ETS-04 v. 3 9/13 4.2 Lightning Lightning protection shall be made in accordance with IEC 61892 and lightning protection components shall be in accordance with DS/EN 50164. Although the IEC 62305 primarily concerns buildings and structures on shore, it shall be used for the transformer platform as the basis for the assessment of the lightning zones and protective devices. 4.2.1 General As the platform will be exposed to lightning, precautions shall be made to prevent damage to the structures and the equipment on the platform. Earthing and bonding are important means to reduce the impact of lightning, hence the relevant recommendations of IEC 62305-4 clause 5 shall be taken into consideration for the design and implementation of earthing and bonding in clause 4.1 of this standard. 4.2.2 Lightning damage protection When evaluating the requirements for lightning damage protection, the worst case scenarios shall be used as the design basis. The platform shall be divided into lightning protection zones (LPZ) as described in IEC 62305-1. Where an LPZ is defined, bonding shall be provided for all metal parts and services (e.g. metal pipes/conduits, cable ladders/trays, bridges between modules etc.) penetrating the boundary of the LPZ. The lightning protection systems (LPS) shall be designed in order to ensure that no major equipment is exposed to a direct lightning flash. This can be achieved either by designing the main and secondary structure in a way so that it protects the equipment, or by installing air-termination systems. As the lightning electromagnetic impulse (LEMP) can be very damaging to electrical and electronic systems, protection against LEMP shall also be provided. It shall be ensured that the LEMP severity in a particular lightning protection zone will not exceed the LEMP withstand level of the equipment to be protected. The protection of electrical and electronic equipment located in equipment rooms should be a combination of the following: Bonding of all metallic components (i.e. pipes and cable armouring) which enters from an outer zone to an inner zone Installation of surge protective devises on all cables entering an inner zone from the roof of the platform. Equipment enclosures acting as magnetic shields Document no. 56361/10, Case 10/4054 - ETS-04 v. 3 10/13 Outdoor cable installations and equipment for lighting, small power, navigation aids e.t.c shall, as far as practicable, be installed in areas where there is no risk of the cables and equipment to be hit by direct flashes. Furthermore, the formation of cable loops, or metallic loops such as pipe work, in proximity to down conductors shall be avoided. Cables in close proximity to down conductors shall be installed in metal pipes. 4.2.3 Equipment requiring protection The equipment that needs protection against lightning damage is: Electrical: 132/33/33kV main transformer 132kV switchgear 33kV switchgear 33/0.4kV utility transformers 400V main utility switchgear 400V on site standby generator 400V emergency switchgear Lighting and small power distribution board AC/DC UPS systems and distribution boards HVAC systems Electronic: SCADA panels Communication panels ABA system Antennas Weather station Navigation aids CCTV system VHF radio communication Navigation aids control panel and power package 5. Certificates / Data books 5.1 General N/A Document no. 56361/10, Case 10/4054 - ETS-04 v. 3 11/13 6. Appendix 6.1 A: Overall earthing and bonding principles LV systems Document no. 56361/10, Case 10/4054 - ETS-04 v. 3 12/13 6.2 B: Bonding principles for structure and equipment Document no. 56361/10, Case 10/4054 - ETS-04 v. 3 13/13