Journal of International Council on Electrical Engineering Vol. 4, No. 1, pp.74~79, 2014 http://dx.doi.org/10.5370/JICEE.2014.4.1.074 A Voltage Stability Analysis Method of Multi-infeed HVDC Power Systems Shao Yao†, Tang Yong*, Zhang Jian* and Li Baiqing* Abstract – According to the Chinese power network planning, the risk of voltage instability at the receiving-end AC power system will be increased significantly, where there will be more HVDC systems feeding into a same AC grid in the future. At present, the effective voltage stability analysis methods of multi-infeed DC (MIDC) system are few, the most widely used method with most research results is the multi-infeed short-circuit ratio (MISCR) index at home and abroad. The deficiency of MISCR index is pointed out. The relationship between multi-infeed interaction factor (MIIF) and the voltage stability of the receiving-end AC system is discussed. Then a new method joint MIIF and MISCR indexes to evaluate the voltage stability of MIDC system is put forward. Finally, simulation tests and analysis results of a large actual grid prove the feasibility and good performance of the proposed new method. Keywords: Multi-infeed DC power system (MIDC), Voltage stability, Multi-Infeed Interaction Factor (MIIF), Multi-Infeed Short Circuit Ratio (MISCR) Reference [5] proposes a novel structure-related index, i.e. the transient voltage supporting index (TVSI) to evaluate the interaction strength of the DC terminals, and it still is a derivative of the concept of short-circuit ratio. However, MISCR index is a relatively macroscopic structural indicator. In some cases, it’s insufficient of using MISCR to determine the voltage stability of MIDC systems. In this paper, the defect of using MISCR method to determine the MIDC system voltage stability is pointed out based on a completely symmetrical two-infeed DC system. The relationship between multi-infeed interaction factor (MIIF) and the voltage stability of MIDC system is studied. Then based on the above analysis, a new method using MIIF and MISCR indexes to determine the voltage stability of MIDC system is put forward. Finally, detailed analysis and simulation tests are carried out in a large actual grid. 1. Introduction There With the orderly constructions of China's power grid, many UHV/EHV DC systems will be fed into the East China Receiving-end Power Grid, where several of the DC systems are located in the vicinity of each other. In multiinfeed DC (MIDC) systems, if the electrical couplings between inverter stations are close and the dynamic reactive power supports of the receiving-end AC system are insufficient, when there are serious contingencies happening in the AC system, the risk of the whole system voltage collapse caused by simultaneous DC commutation failure will increase[1]-[10]. At present, many voltage stability analysis methods of MIDC system are derived from the research results of AC system or single-infeed DC system, and the most widely used method is multi-infeed short-circuit ratio (MISCR) method. References [3]–[4] propose the definitions of MISCR respectively. In [3], Node impedance matrix elements are used to describe the effect of DC links, and in [4], the change rate of voltage at converter buses after reactive power disturbance is applied to indicate the interactions between them. Reference [8] proves the consistency of these two definitions based on a decoupled model of MIDC system and gives the index of MISCR for determining the strength of receiving-end AC system. 2. Evaluation indexes of MIDC system 2.1 Evaluation index for determining the strength of the receiving-end AC system Historically, an index known as Short Circuit Ratio (SCR) was defined and intended to indicate the ac system strength at the ac/dc interconnection point with respect to the power rating of the single-infeed DC system. And generally think, the higher the value of SCR, the stronger the strength of receiving-end AC system, and the smaller the probability of system voltage instability [1]-[7]. In multi-infeed DC system, considering the interactions between DCs, MISCR is defined as: † Corresponding Author: China Electric Power Research Institute, Haidian District, Beijing 100192, China (yaoshao@epri.sgcc.com) * China Electric Power Research Institute, Haidian District, Beijing 100192, China Received: November 19, 2013; Accepted: January 6, 2014 74 Shao Yao, Tang Yong, Zhang Jian and Li Baiqing M ISCR i = Saci Pdeqi approximately zero, and each DC can be seen as a singleinfeed DC system. Simulations in [10] show that, for MIIFji>0.6, the interaction between two DC systems is so strong and the converters can be considered to be on the same bus as regards to commutation failure (CF) behavior. (1) where, i is the number of DC converter station; Saci is the ac short-circuit capacity at the i-th converter ac bus. Peqi is the equivalent DC power considering the impacts of other DC systems. If the number of DC systems is m, through the Thevenin equivalent method, (1) is extended to: M ISCR i = Saci = Pdeqi 3. Relationship between MIIF and voltage stability of receiving-end AC system 3.1 Test system model U N2 i / | Zeqii | PdNi + n ∑ j =1, j ≠ i | Zeqij / Zeqii | PdNj 1 = | Z eqii | PdNi + m ∑ j =1, j ≠ i In order to analyze the relationship between MIIF and voltage stability of multi-infeed DC system, a completely symmetrical test system of two DC infeeds connected through a tie line (z12) is adopted. The circuit is shown in Figure 1. Each DC system uses a standard control strategy of constant current control at the rectifier and constant extinction angle control at the inverter end respectively. The parameters of each DC system are exactly the same. The synthesis load mode, in which an impedance (40%) and an induction motor (60%) are connected in parallel, is used. And the resistances of AC lines are ignored. (2) | Z eqij | PdNj where: UNi is the nominal voltage at the i-th converter bus; PdNi, PdNj are the DC power ratings of the i-th, j-th DC system, respectively; Zeq is the equivalent node impedance matrix of the AC system seen from the ac converter buses; Zeqij is the ith , jth of matrix Zeq; Zeqii is the ith , ith of matrix Zeq. Based on the value of multi-infeed critical SCR (MCSCR) and the indexes of SCR proposed by IEEE, reference[8] recommends indexes of MSCR as follows: (1) very weak system: MSCRi<2; (2) weak system: 2<MSCRi<3; (3) strong system: MSCRi >3. 3.2 Relationship between MIIF and voltage stability With the other parameters remaining constant, only changing the value of z12, the relationship between MIIF and MISCR of the above test system are listed in Table 1. 2.2 Evaluation index for determining the interaction strength between DC systems γ1 According to [4]–[9], an index known as MIIF, which can be used to provides a first level indication of the degree of the electrical coupling or interaction between two dc systems, has been proposed as the ratio between the voltage changes at inverter ac bus j and i due to a reactive ac power change at inverter ac bus i, and given by: X cI1 U&1 1: nI1 I&1 DC1 Qc1 Z12 X cI2 γ2 1: nI2 I&2 U& 2 Z load 2 DC2 M IIFji = ΔU j ΔU i Z load 1 Qc 2 (3) Fig. 1. A schematic diagram of the test system with two DC infeed. where, ΔU j is the observed voltage change at bus j for a small induced voltage change at bus i; ΔU i is about 1% voltage change at bus i. Obviously, 0≤MIIFji≤1, the larger MIIFji or MIIFij is, the stronger the interaction strength between DC i and DC j will be. Reference [4] indicates that if MIIFji is less than 0.15 when the transmission power of DC i and DC j is similar, the interaction between the two DC systems is Table 1. MIIF and MISCR of the test system with two DC infeed No. 1 2 3 4 75 z12(p.u.) 1.31 0.631 0.131 0.001 MIIF21 0.393 0.488 0.686 0.990 MISCR 1 3.23 3.23 3.23 3.23 MISCR2 3.23 3.23 3.23 3.23 Design and Analysis of a Magnetless Flux-Switching DC-Excited Machine for Wind Power Generation Seen from Table 1, with the decrease of z12, MIIF21 is increasing, but MISCR1 and MISCR2 are remaining unchanged. This is a special case which will be explained as follows. The test system shown in Fig. 1 can be equivalent to Fig. 2 under steady-state operation. M ISCR1 = = E&1 z1 γ1 zc 2 z12 + z2 z12 + z2 zc 2 PdN1 + z2 zc 2 PdN2 1 Z 22 PdN2 + Z 21 PdN1 I&2d zc1 z12 + z1 z12 + z1 zc1 PdN2 + z1 zc1 PdN1 E& 2 z2 γ2 z1 + z2 + z12 z1 z12 + 2 z2 (8) M ISCR 2 = z1 + z2 + z12 z2 z12 + 2 z1 (9) And z1=z2, then Fig. 2. A simplified model of the test system with two DC infeed. M ISCR1 = In the test system, Y and Z are defined as the equivalent node impedance matrix and node admittance matrix seen from the ac converter buses, respectively: ⎤ − z12−1 −1 ⎥ z + zc−21 + z12 ⎦ (4) −1 2 ⎤ z12−1 ⎥ z + zc−11 + z12−1 ⎦ (5) −1 1 )( ) ( ) Y = z1−1 + zc−11 z2−1 + zc−21 + z1−1 + z2−1 + zc−11 + zc−21 z12−1 Substituting the elements of (5) into (2), MISCR can be rewritten as follows: MIIF=0.393 MIIF=0.488 MIIF=0.686 MIIF=0.990 MIIF=0.393 MIIF=0.488 MIIF=0.686 MIIF=0.393 MIIF=0.990 1.1 DC2 power (MW) 0.9 1,000 0.8 0.7 0.6 (10) MIIF=0.488 MIIF=0.686 MIIF=0.990 1,500 1,500 1 z1 + z1 + z12 1 = = M ISCR 2 z1 z12 + 2 z1 z1 As can be seen from (10), as long as the equivalent impedances of AC system remain unchanged, MISCRs will always be constant values. Assuming there is a 3-phase fault occurring at bus 1 of the AC tie line at 0.2s, and the line jumps at 0.3s after the fault. Curves of voltages and DC powers are as shown in Figure 3. As can be seen from Fig. 3, with the increase of MIIF21, the transient voltage stability of the receiving-end AC system is deteriorated significantly. Even if the strength of AC system is strong (MISCR1 =MISCR2=3.23), when MIIF21 reaches a critical value, a serious AC disturbance may cause the whole system to voltage instability. where: ( Y M ISCR1 = zc 2 1 ⎡ z2−1 + zc−21 + z12−1 ⎢ Y ⎣ z12−1 (7) z1 zc1 z12 Under the base of DC nominal power and nominal voltage at the converter bus, (6) and (7) can be rewritten by: z12 Z= Y In the actual power system, there is y1 yc1 , y2 yc 2 . zc1 ⎡ z −1 + zc−11 + z12−1 Y =⎢ 1 −1 − z12 ⎣ (6) z2 zc 2 z12 M ISCR 2 = = I&1d 1 Z11 PdN1 + Z12 PdN2 500 0.5 1,000 500 0.4 0 0 0.3 0.2 0 1 2 3 4 (a) bus voltage 5 6 0 1 2 3 4 5 (b) DC1 power at inverter side 6 0 1 2 4 5 (c) DC2 power at inverter side Fig. 3. Simulation results when changing the interaction between DC systems. 76 3 6 Shao Yao, Tang Yong, Zhang Jian and Li Baiqing between these DCs in addition to Shaox and Zhex inverter stations. Overall, the interactions between DC inverter stations fed into East China power grid are not great. 4. The voltage stability analysis method joint MIIF and MISCR According to the analysis results of the previous section, it’s not comprehensive enough of simply using MISCR to determine the voltage stability of MIDC system. We should consider both factors of MIIF and MISCR. Therefore, this paper presents a new voltage stability analysis method with use of MIIF and MISCR: for a MIDC system, if MISCRs at the ac inverter buses are high and MIIFs between DCs are small, the voltage stability of the MIDC system is good; if MISCRs at the ac inverter buses are small and MIIFs between DCs are high, the voltage stability of the MIDC system is poor. For a same MIDC system, the greater the MIIFs are, the higher the probability of system voltage instability is. And the local power grids with high MIIF between fed DCs are weak areas responsible to voltage collapse in a power system. Jiangsu Power Grid Xuzh Nanj Taizh Jint Liy Zhengp Huain Suzh Tongl Shanghai Power Grid Anhui Power Grid Hux Wann Huax Zheb Fengj Shaox Zhex Nanq Fengx Zhezh Zhejiang Power Grid Fig. 4. 1000 kV network structure of East China power grid with 10 DC infeed in 2015. 5. Simulation analysis MISCRs of the DC inverter stations are shown in Table 3. The results are shown that, MISCRs of Jint and Liy inverter stations are greater than 2 and less than 3, MISCRs of other inverter stations are greater than 3. Overall, East China receiving-end power grid is a strong system that its voltage stability supporting capacity to MIDC system is large. The simulation model which is based on the summer peak load operation mode in the planning of East China power grid in 2015 is shown in Fig. 4. There are a total of 10 DC systems fed into the East China power grid. By calculating, MIIFs between the 10 DC inverter stations are listed in Table 2. As seen from Table 2, MIIFs between the inverter stations fed into the same local power grid are greatly significantly greater than MIIFs between the inverter stations fed into different local power grids. And the interaction between Huax and Fengj inverter stations is high; the local power grid with the two DC infeed is voltage stability weak area. MIIFs between DCs fed into Zhejiang power grid between the other DCs are smaller than 0.15. Hence it can be approximated that there are no interactions Table 3. MISCRs of DCs in East China Power Grid DC Zhengp Jint Nanq Fengj Shaox MISCRi 3.43 2.09 3.64 3.22 3.26 DC Tongl Liy Huax Fengx Zhex MISCRi 2.73 2.10 3.61 3.87 3.98 In summary, according to the proposed analysis method, the voltage stability of East China receiving-end power system is good. And normal contingencies will not cause Table 2. MIIFs between DCs in East China Power Grid MIIFj,i inverter ac bus i Zhengp Tongl Jint Liy Nanq Huax Fengj Fengx Shaox Zhex Zhengp 1.00 0.26 0.18 0.28 0.03 0.15 0.08 0.09 0.10 0.04 Tongl 0.32 1.00 0.17 0.16 0.04 0.30 0.14 0.13 0.07 0.03 Jint 0.31 0.24 1.00 0.34 0.03 0.19 0.10 0.10 0.07 0.03 inverter ac bus j Nanq Huax 0.09 0.16 0.13 0.25 0.06 0.12 0.05 0.09 1.00 0.11 0.38 1.00 0.31 0.33 0.38 0.28 0.06 0.08 0.03 0.03 Liy 0.47 0.22 0.33 1.00 0.02 0.15 0.08 0.09 0.09 0.03 77 Fengj 0.13 0.18 0.09 0.08 0.14 0.52 1.00 0.39 0.09 0.04 Fengx 0.09 0.11 0.05 0.05 0.10 0.27 0.24 1.00 0.09 0.03 Shaox 0.13 0.07 0.05 0.07 0.02 0.09 0.06 0.10 1.00 0.22 Zhex 0.04 0.02 0.02 0.02 0.01 0.04 0.03 0.04 0.21 1.00 Design and Analysis of a Magnetless Flux-Switching DC-Excited Machine for Wind Power Generation the system to voltage instability. The results are further verified by simulation tool. Simulation results show that the transient voltage stability of East China power grid in the summer peak load operation mode in 2015 is very good. All unipolar block faults occurred in DC systems, single faults occurred in AC or DC system, three-phase permanent short-circuit fault, which causes the tripout of two circuits, occurred in UHVAC transmission line of receiving-end system and that occurred in the line near commutation buses of inverter stations and majority of DC bipolar block faults occurred in DC systems will not lead to transient voltage instability of East China receiving-end power grid. The voltage curves of inverter station commutation buses after three phase-to-ground N-2 faults occurring at 1000kV ac lines are shown in Fig. 5. As seen from Fig. 5, after the faults, bus voltages of the receiving-end AC system drop significantly. But with the fault clearing, bus voltages can restore to new stable values after a period of slight fluctuations. During the fault period, voltage stability at commutation buses in Huax and Fengj inverter stations are worse than the other commutation buses. The local power grid where Huax and Fengj DCs fed into is the voltage stability weak area. The conclusions are 泰泰-泰泰泰 浙浙泰-浙浙泰 泰泰泰-南南泰 西泰-浙浙泰 西泰- 泰泰 1 0.8 0.8 泰泰泰-南南泰 西泰-浙浙泰 西泰- 泰泰 西泰- 泰泰 泰泰-泰泰泰 浙浙泰-浙浙泰 1 /pu 母 0.8 0.6 0.4 0.4 0.2 0.2 0.2 0 0.5 1 (a) 泰泰泰-南南泰 西泰-浙浙泰 1.5 /s 2 2.5 0 3 0.5 Huax 1 1.5 /s 2 2.5 3 0 泰泰-泰泰泰 浙浙泰-浙浙泰 泰泰泰-南南泰 Taizh -Nanj UHV 西泰-浙浙泰 Hux-Zheb UHV 西泰- 泰泰 0.6 泰泰 西泰- UHV Hux-Suzh 泰泰-泰泰泰 Suzh -Taizh UHV 浙浙泰-浙浙泰 Zheb-Zhezh UHV /pu 0.8 0.6 1 1.5 /s (d) Tongl 2 2.5 3 2.5 3 泰泰-泰泰泰 浙浙泰-浙浙泰 西泰- 泰泰 0.8 0.6 0.4 0.2 0.2 0.2 2 1 0.4 0.4 1.5 /s (c) Nanq 母 Bus voltage 母 /pu(pu) 0.8 0.5 1 泰泰泰-南南泰 西泰-浙浙泰 1 0 0.5 (b) Fengj 1 /pu 泰泰-泰泰泰 浙浙泰-浙浙泰 0.6 0.6 0.4 母 (1) It’s not comprehensive enough of only using MISCR index to determine the voltage stability of systems with multiple DC infeed. Both factors of MIIF and MISCR indexes should be considered. (2) MIIF, which is an evaluation index of the degree of voltage interaction between two DC links, can reflect the voltage stability weak areas of receiving-end system: the local power grid with high MIIF between fed DC links is weak area responsible to voltage collapse in a power system. (3) A new method joint MIIF and MISCR to evaluate the voltage stability of systems with multiple DC infeed is proposed: for a MIDC system, if MISCRs at the ac inverter commutation buses are high and MIIFs between DCs are small, the voltage stability of the /pu 1 6. Conclusion 母 Bus voltage /pu(pu) 母 泰泰泰-南南泰 西泰-浙浙泰 exactly the same with the results concluded from Table 2. Obviously, the simulation results prove the accuracy of the proposed new method united MIIF and MISCR indexes to evaluate the voltage stability of systems with multiple DC infeed. 0 0.5 1 1.5 s /s (e) Jint 2 2.5 3 0 0.5 1 1.5 /s 2 2.5 3 (f) Shaox Fig. 5. Voltage curves of inverter station commutation buses after three phase-to-ground N-2 fault occurring at 1000 kV ac lines in East China power grid. 78 Shao Yao, Tang Yong, Zhang Jian and Li Baiqing MIDC system is good; if MISCRs at the ac inverter commutation buses are small and MIIFs between DCs are high, the voltage stability of the MIDC system is poor. For a same MIDC system, the greater the MIIFs are, the higher the probability of system voltage collapse is. Theoretical analysis and simulation results of a large actual grid prove the accuracy of the proposed new method. SHAO YAO is currently an engineer in the Electric Power Research Institute of China. Her research interests are power system voltage stability and control, AC/DC systems characteristics analysis TANG YONG is a research fellow engineer in the Electric Power Research Institute of China. His research interests are power system simulation and analysis, voltage stability and control, load modeling and simulation. References ZHANG JIAN is a senior engineer in the Electric Power Research Institute of China. His research interest is power system analysis and control. [1] Tang Yong. Power System Voltage Stability Analysis. Beijing: Science Press, 2011: 28. [2] Shao Yao, Tang Yong. Current situation of research on multi-infeed AC/DC power systems. Power System Technology, 2009, 33(17): 24-30. [3] Paulo F D T, Bernt B, Gunnar A. Multiple infeed short circuit ratio-aspects related to multiple HVDC into one AC network. IEEE PES Transmission and Distribution Conference & Exhibition: Asia and Pacific. Dalian, China: IEEE, 2005: 1-4. [4] CIGRE Working Group B4.41. Systems with multiple DC infeed. Paris: CIGRE, 2008. [5] Xiaoming Jin, Baorong Zhou, Lin Guang, et a1. HVDC-interaction-strength index for systems with multiple HVDC infeed. CIGRE, Paris, 2010. [6] Lin Weifang, Tang Yong, Bu Guangquan. Study on voltage stability of multi-infeed HVDC power transmission system. Power System Technology, 2008, 32(11): 7-12. [7] Hong Chao, Rao Hong. The index parameters for analyzing multi-infeed HVDC systems. Southern Power System Technology, 2008, 2(4): 37-41. [8] Lin Weifang, Tang Yong, Bu Guangquan. Study on voltage stability of multi-infeed HVDC power transmission system. Proceedings of the CSEE, 2008, 28(31): 1-8. [9] Nayak R N, Sasmal R P. AC/DC Interactions in multiinfeed HVDC scheme: a case study. IEEE Power Conference, India, 2006: 5pp. [10] Ebrahim Rahimi, A. M. Gole, J. B. Davies, et al. Commutation failure analysis in mulit-infeed HVDC systems. IEEE Transactions on Power Delivery, 2011, 26(1): 378-384. [11] Tang Yong, Bu Guangquan, Hou Junxian, et al. PSDBPA Transient Stability Program User Manual. Beijing: China Electric Power Research Institute, 2008. LI BAIQING is research fellow engineer in the Electric Power Research Institute of China. His research interest is power system analysis and control. 79