IG Series - Intermatic

advertisement
IG Series
Surge Protective Devices
Project:
IG Series
Surge Protective Devices
Location:
Product Type:
Contact/Phone:
The IG Series Surge Protective Devices are designed for a variety of
Model #:
Type 1 and Type 2 applicatons. Type 1 applications include outdoor
installations before service entrances and utility meter cabinets. Type 2
applications include installations after service entrances. CSA listed to
ANSI/UL 1449 3rd edition, the IG series is approved for residential/light
commercial services (AC power, telephone and/or cable).
Features
• Green LED indicates surge protection status
• ON LED indicates device is energized and providing protection
• OFF LED indicates device may still be energized but protection is
diminished and the unit should be replaced
Ratings
IG1300-2T-1C3: • Six modes of surge protection
(L1-N, L2-N, L1-G, L2-G, N-G, L1-L2)
• Provides protection for two telephone lines
(analog phone line, modem, or DSL) and one coax line (cable TV, cable internet, or satellite TV)
• CSA listed to UL 1449 3rd Edition
• Type 3R outdoor rainproof enclosure for indoor/
outdoor installations (9.38" H x 5.25" W x 4.0" D)
• Wire configuration: L1, L2, N, GND
• Limited 5-year warranty
IG1300-4T-2C3: • Six modes of surge protection
(L1-N, L2-N, L1-G, L2-G, N-G, L1-L2)
• Provides protection for four telephone lines (analog phone line, modem, or DSL) and two coax lines
(cable TV, cable internet, or satellite TV)
• CSA listed to UL 1449 3rd Edition
• Type 3R outdoor rainproof enclosure for indoor/
outdoor installations (9.38" H x 5.25" W x 4.0" D)
• SPD wire configuration: L1, L2, N, GND
• Limited 5-year warranty
IG1240RC3:• Six modes of surge protection
(L1-N, L2-N, L1-G, L2-G, N-G, L1-L2)
• CSA listed to ANSI/UL 1449 3rd Edition
• Type 3R outdoor rainproof enclosure for
indoor/outdoor installations
• Plastic housing (4.20" H x 4.20" W x 3.33" D)
• SPD wire configuration: L1, L2, N, GND
• Limited 5-year warranty
IG3240RC3:
IG1300-2T-1C3
IG1300-4T-2C3
IG1240RC3
• Six modes of surge protection
(L1-N, L2-N, L1-G, L2-G, N-G, L1-L2)
• CSA listed to ANSI/UL 1449 3rd Edition
• Type 3R outdoor rainproof enclosure for
indoor/outdoor installations
• Metal housing (6.28" H x 4.40" W x 3.71" D)
• Wire configuration: L1, L2, N, GND
• Limited 10-year warranty
IG3240RC3
Surge Protection
HVACR
IG Series
Model
Number
Service Voltage
Phase
Leads#/
Length
Nominal
Discharge
Current
Gauge
SSCR
MCOV
VPR
L-N, L-L, L-G, N-G
SPD Type 2 2
IG1300-2T-1C3
120/240 VAC
2
4/24"
12
20 kA
50 kA
150 L-N, N-G
300 L-L, L-G
700 L-N, 1200 L-L,
1200 L-G, 700 N-G
IG1300-4T-2C3
120/240 VAC
2
4/24"
12
20 kA
50 kA
150 L-N, N-G
300 L-L, L-G
700 L-N, 1200 L-L,
1200 L-G, 700 N-G
SPD Type 1 or 2
IG1240RC3
120/240 VAC
2
4/30"
12
20 kA
50 kA
150 L-N, N-G
300 L-L, L-G
700 L-N, 1200 L-L,
1200 L-G, 700 N-G
IG3240RC3
120/240 VAC
2
4/30"
12
20 kA
50 kA
150 L-N, N-G
300 L-L, L-G
700 L-N, 1200 L-L,
1200 L-G, 700 N-G
SCCR = Short Circuit Current Rating
MCOV = Maximum Continuous Operation Voltage
VPR = Voltage Protection Rating
SPD Type 1= applications include outdoor installations before service entrances and
utility meter cabinets
SPD Type 2= applications include installatons after service entrances
Specification
The Surge Protective Device shall be listed by CSA to ANSI/UL 1449 3rd Edition for Type 1 and Type 2 locations. The
Surge Protective Device shall provide protection between each phase conductor and ground. The Maximum
Continuous Operating Voltage (MCOV) shall be a minimum of ____volts AC between phase and ground. When subjected
to the ANSI / UL 1449 3rd Edition 20kA test impulses, the Voltage Protection Rating shall be no greater than 700 volts
Line to Neutral, 1200 volts Line to Line. The Surge Protective Device shall employ Large MOV technology and provide
individual component thermal protection and monitoring, utilizing a green LED status indicator. The failure of a
single component turns the LED OFF. The IG1240RC3 rainproof housing shall be constructed of UV resistant
polycarbonate, or material of equal strength and UV resistance, and tested to UL Type 3R standards for outdoor use. A
one half inch polycarbonate threaded nipple and metal locknut shall be provided. Leads shall be 12 gauge minimum and
24 inches in length. The IG3240RC3 rainproof housing shall be formed of 18 gauge powder coated sheet metal tested
to UL Type 3R standards for outdoor use. (A one half inch threaded nipple and metal locknut shall be provided). Leads
shall be 12 gauge minimum and 24 inches in length. The Surge Protective Device shall carry a 5-year product warranty
(IG3240RC3 10-year warranty) and also carry a $__________ connected equipment coverage warranty for five years on
appliances and electronics.
Diagrams
Main Breaker
2-Pole, 20A circuit
breaker shown
Line
Line
240 VAC
120 VAC
Neutral
BLACK
120 VAC
120 VAC 120 VAC
BLACK
WHITE
A=Black (Line)
B=Black (Line)
C=Neutral (White)
D= Green (Ground)
Surge Protection
Ground
GREEN
www.intermatic.com
A=Black (Line)
B=Black (Line)
C=Neutral (White)
D=Green (Ground)
Download