-106 OPTION BOARD White Paper What is the -106? Modern industrial and commercial automation processes require an increased need to connect to complex devices, traditionally requiring more panel space. Horner Automation Group has reduced the cost and complexity of this traditional system with I/O hardware that provides more flexibility and high levels of on-board I/O density. THE TRADITIONAL APPROACH -106 I/O Option Board n n The traditional programmable logic controller requires addon modules to handle more than a few basic connections. It’s I/O usually has the ability to support some discrete physical relays or analog sensor inputs that are either 4-20 mA or 0-10 mV. Because sensors like thermocouples, RTDs or load cells themselves require a wider variety of analog inputs, extra hardware is necessary to translate between the sensor and the controller. A thermocouple is a good example of this limitation in the traditional PLC. Thermocouples work on the material properties of metals. In the thermocouple, two metals are joined together at a point, and as the temperature varies, so does the very small voltages created between where the two metals connect. Thermocouples used in industrial settings can measure wide temperature ranges up to thousands of degrees. In a traditional PLC, the thermocouple signal would need to be translated by extra hardware into a signal the controller can handle. THE HORNER MODEL 6 SOLUTION -105 I/O Option Board (jumpers highlighted) Horner’s most recent I/O option, the -106 board, offers a more efficient way of distributing control by allowing a wide variety of field inputs to be connected directly to the controller. With six configurable analog inputs mounted directly to the controller, most process inputs can be captured, reducing the need for remote I/O or signal conditioners. The -106 has six (6) analog inputs, four (4) analog outputs, twelve (12) digital inputs, and twelve (12) digital outputs. These inputs are universal for such measures as voltage (0-10, 0-60mV), current (0-20, 4-20mA), thermocouples, and RTD (PT100, PT1000). 1 59 S. State Ave. Indianapolis, Indiana 46201 | US website: www.heapg.com | (+1) 877-665-5666 EU website: www.horner-apg.com | (+353) 21-4321266 Configurable analog inputs are particularly beneficial for process automation systems with multiple sensors for maintaining temperature, pressure or measuring weights. Building Automation n Improve occupant comfort n Economical operation systems n Reduce energy consumption Previous I/O options, such as the -105 I/O board, required configuring jumpers inside the unit along with properly configuring Horner’s I/O software, Cscape. With the -106 I/O board, the jumpers are no longer necessary. Instead, the board itself contains a dual-processor layout with electronic switches, and each channel can be directly configured to each sensor through Cscape. This approach resulted from a collaboration of Horner Automation Systems product development engineers and industry partners. Material Handling n Minimize HMI inefficiencies n Track/log/catalog data n Increase overall productivity Oil and Gas n Maximize capacity utilization n Rationalize assets n Maintain emission standards Renewable Energy n Data logging, remote access n Sunlight and UV protection n Durable, robust controllers Water/Wastewater n Operate chlorination systems n Station pump control n Remote water well controls Cscape hardware configuration window SPRING TERMINALS Because the -106 I/O board needs to make multiple connections, the spring clamp terminals are ideal for space and ease of installation. The spring clamp terminals also are less susceptible to vibration and changes in temperature than screw-type terminals, which require closer monitoring to ensure connectivity as the screws may loosen over time. On the -106 I/O board, each spring clamp terminal can hold one connector. Horner controllers include the -106 option, as well as previously released I/O options detailed in the following pages. 2 59 S. State Ave. Indianapolis, Indiana 46201 | US website: www.heapg.com | (+1) 877-665-5666 EU website: www.horner-apg.com | (+353) 21-4321266 -106 I/O The Model 6 I/0 features twelve (12) DC Inputs, twelve (12) DC outputs, with high performance, six (6) highly configurable Analog Inputs, and four (4) Analog Outputs. The DC Inputs are 12/24Vdc compatible, and can be software configured for Positive Logic (sinking), or Negative Logic (sourcing). Two of the inputs (H1-H2) can be used for high-speed functions up to 500kHz. The 12/24VDC Outputs feature Electronic Short Circuit protection, and support currents up to 0.5A per point, and 4A total. Two of the DC Outputs can be used for high speed functions (PWM or PTO). The output frequency is limited by the switching capability of the output drivers (about 10kHz), although an optional accessory (HE-XHSQ) can be added to provide parallel output drivers supporting frequencies up to 200kHz. The 2 high resolution Analog Inputs can be configured for 4-20mA, 0-10V, or 0-100mV at 14bit resolution. They also can be configured for 16-bit temperature measurement – supporting Thermocouples or RTDs with 0.05°C resolution. The Analog Outputs are sourcing, and can be configured for 4-20mA or 0-10V at 14-bit resolution. Each Analog Input or Output channel can be configured independently for maximum flexibility. 3 59 S. State Ave. Indianapolis, Indiana 46201 | US website: www.heapg.com | (+1) 877-665-5666 EU website: www.horner-apg.com | (+353) 21-4321266 -105 I/O The Model 5 features twelve (12) DC Inputs, twelve (12) DC outputs, with high performance, and two (2) highly configurable Analog Inputs, and two (2) Analog Outputs. The DC Inputs are 12/24Vdc compatible, and can be jumpered for Positive Logic (sinking), or Negative Logic (sourcing). Two of the inputs (H1-H2) can be used for high-speed functions up to 500kHz. The 12/24VDC Outputs feature Electronic Short Circuit protection, and support currents up to 0.5A per point, and 4A total. Two of the DC Outputs can be used for high speed functions (PWM or PTO). The output frequency is limited by the switching capability of the output drivers (about 10kHz), although an optional accessory (HE-XHSQ) can be added to provide parallel output drivers supporting frequencies up to 200kHz. The two high resolution Analog Inputs can be configured for 4-20mA, 0-10V, or 0-100mV at 14bit resolution. They also can be configured for 16-bit temperature measurement – supporting Thermocouples or RTDs with 0.05°C resolution. The Analog Outputs are sourcing, and can be configured for 4-20mA or 0-10V at 14-bit resolution. Each Analog Input or Output channel can be configured independently for maximum flexibility. -103 and -104 I/O The Model 3 features twelve (12) DC Inputs, twelve (12) DC outputs, and two (2) Analog Inputs. The Model 4 increases the I/O count up to 24 DC Inputs, with sixteen (16) DC Outputs and two (2) Analog Inputs. The DC Inputs are 12/24Vdc compatible, and can be jumpered for Positive Logic (sinking), or Negative Logic (sourcing). Two of the inputs (H1-H2) can be used for high-speed functions up to 500 kHz. The 12-bit Analog Inputs can be jumpered for voltage (0-10V) or current (4-20mA) on a channel by channel basis. The 12/24VDC Outputs feature Electronic Short Circuit protection, and support currents up to 0.5A per point, and 4A total. Two of the DC Outputs can be used for high speed functions (PWM or PTO). The output frequency is limited by the switching capability of the output drivers (about 10kHz), although an optional accessory can be added to provide parallel output drivers supporting frequencies up to 200kHz. -102 I/O The Model 2 features twelve (12) DC Inputs, six (6) Relay outputs, and four (4) Analog Inputs. The DC Inputs are 12/24Vdc compatible, and can be jumpered for Positive Logic (sinking), or Negative Logic (sourcing). Two of the inputs (H1-H2) can be used for high-speed functions up to 500kHz. The 12-bit Analog Inputs can be jumpered for voltage (0-10V) or current (4-20mA) on a channel by channel basis. The Relay outputs are isolated, supporting AC and DC voltages, with output currents of up to 3A/relay, 5A total. 4 59 S. State Ave. Indianapolis, Indiana 46201 | US website: www.heapg.com | (+1) 877-665-5666 EU website: www.horner-apg.com | (+353) 21-4321266 FAQ Q: IS THE ELECTRONIC SWITCHING IN THE I/O BOARD AS RELIABLE AS SETTING JUMPERS? A:Yes. All Horner I/O boards are rigorously tested to Horner’s specifications, which go above and beyond industry standards. Q:IS THERE A DIFFERENCE IN PRICE BETWEEN THE -106 AND OTHER MODELS WITH JUMPERS? A: Boards with jumpers are traditionally less expensive. Q: CAN I SIMPLY SWITCH OUT MY OLD I/O BOARDS TO -106 BOARDS FOR AN UPGRADE? A: No. Each I/O board is an option ordered from the factory. The boards are not field installable. Q:WHY ARE THERE SPRING CONNECTORS ON THE MODEL 6 INSTEAD OF SCREW CONNECTORS LIKE THE PREVIOUS MODELS? A:Mostly this was a matter of space. We packed more into the -106 I/O board, but spring clamp terminals also offer added benefits. Spring clamp terminals are less susceptible to vibration and changes in temperature than screw-type terminals, which require closer monitoring to ensure connectivity as the screws may loosen over time. 5 59 S. State Ave. Indianapolis, Indiana 46201 | US website: www.heapg.com | (+1) 877-665-5666 EU website: www.horner-apg.com | (+353) 21-4321266