Motor Controllers 600 Volts or Less Installation And Maintenance Instruction Manual Storage 1. An indoor motor controller, which is not installed and energized immediately, should be stored in a clean dry place where a uniform temperature prevents condensation. Preferably, it should be stored in a heated building, with adequate air circulation and protected from dirt and water. Motor controllers should be stored where they are not subject to mechanical damage. 2. An indoor motor controller that must be stored outdoors should be securely covered for protection from weather conditions and dirt. Temporary electrical heating should be installed to prevent condensation approximately 150 watts is adequate for the average motor controllers size and environment. All loose packing or flammable materials should be removed before energizing space heaters. 3. An unenergized outdoor motor controller should be kept dry internally by installing temporary heating or by energizing self -contained space heaters. Handling The following guidelines are provided to help avoid personal injury and equipment damage during handling, and to facilitate moving the motor controller at the job site. 1. Follow the manufacturer’s handling instructions for the specific equipment. 2. Handle the motor controller, with care, to avoid damage to components and to the enclosure or its finish. 3. Keep the motor controller in an up right position unless otherwise specifically permitted by the manufacturer. 4. Know the capabilities of the moving means available to handle the weight of the motor controller. 5. When the motor controller is received, unpack it sufficiently to inspect for concealed damage and to determine that the shipment is complete and correct. 6. If the motor controller is to by stored for any length of tome, prior to installation restore the packing for protection during that period. Where conditions permit, leave the packing intact until the motor controller is at its final installation position. When packing is removed, cover the top and openings of the equipment during the construction period to protect them against dust and debris. Installation 1. Conduits should be installed to prevent moisture or water from entering entering and accumulating within the enclosure. All conduits (including stubs) should be bonded to the motor controller. All conduits should be located in the areas recommended by the manufacturer to avoid cable interference with structural members and live components. 2. Care should be exercised to make sure that the lugs which have been provided are suitable for use with the type of cables being installed in the motor controller. 3. If crimp lugs are used, crimp with the tools recommended by the lug manufacturers. 4. Care should be exercised in stripping insulation from the conductors to prevent the conductor from nick or ring. For aluminum, clean all oxide from the stripped portion and at once apply inhibiting compound. All screw lugs should be tightened; use the manufacturer’s torque values, if furnished. 5. Provisions should be made to locate conductors in the motor controller to avoid physical damage and to avoid overheating. The conductors should be secured in order to withstand available short-circuit currents. Follow the manufacturer’s instructions for lacing or bracing cables. The largest practical bending radius should be maintained to avoid damaging the insulation and to avoid causing terminals to loosen. 6. All incoming and outgoing control connections should be made in accordance with the motor controller manufacturer’s schematic and wiring diagrams. 7. Installation of cables should be done at temperatures above freezing to prevent cable insulation from cracking or splitting due to cold, unless the cable is suitable for installation at temperatures below freezing. Energizing Equipment 1. In order to minimize risk, damage, or both, there should be no load on the motor controller when it is energized. Turn off all of the downstream loads, including those such as distribution equipment and other devices which are remote from the motor controller. 2. The equipment should be energized in sequence by starting at the source end of the system and working towards the load end. In other words, energize the main devices, and then the branch circuit devices. With barriers (if applicable) in place, and doors closed and latched, turn the devices on with a firm positive motion. Protective devices that are not quick-acting should not be “teased” into the closed position. 3. After all disconnect devices have been closed, loads such as lighting circuits, starters, contactors, heaters, and motors, may be turned on. Preventive Maintenance 1. EXTERNAL CARE. Enclosures do not require any maintenance in a clean, dry , and noncorrosive atmosphere. Enclosures in a marginal atmosphere should be inspected periodically for excessive dust and dirt accumulation as well as corrosive conditions. The more contaminated the atmosphere, the more frequently the inspections should be conducted. Any accumulation should be removed with a vacuum cleaner or manually cleaned during maintenance shutdown periods for the equipment. Badly corroded enclosures should be properly cleaned and refinished as required for extended service. 2. OPENING ENCLOSURES. Foreign material, dirt, hardware, or debris should be removed from the outside top surfaces to avoid the risk of anything falling onto the equipment. Upon opening the cabinet or enclosure, equipment should be inspected for any dust, dirt , moisture or evidence of moisture, or other contamination. If any is found, the cause must be eliminated. This could indicate an incorrectly selected, deteriorated, or damaged enclosure: unsealed enclosure openings: internal condensation: condensate from an unsealed conduit: or improper operating procedures (e.g., operating with enclosure door or cover open). 3. CLEANING. Corroded or damaged parts should be replaced. Dirty, wet, or contaminated parts of equipment should also be replaced unless they can be cleaned effectively by vacuuming or wiping with dry cloth or soft brush. Use care to avoid damaging delicate parts. Compressed air is not recommended for cleaning because it may displace dirt, dust, or debris into other parts or equipment or damage delicate parts. Liquid cleaners, including spray cleaners, are not recommended unless specified by the equipment manufacturer, because of the risk of residues causing damage or interfering with electrical or mechanical functions. The inside bottom of the cabinet or enclosure should also be cleaned, including removal of any hardware or debris, so that any new or unusual wear or loss of parts occurring after the inspection may be more readily detected during subsequent maintenance. Ventilation passages should be kept open. If equipment depends on auxiliary cooling or heating, the temperature control system should be checked and repaired if necessary to assure proper functioning. Filters should be cleaned or replaced if necessary, based on inspection or the time interval recommended by the manufacturer. If dust or dirt has accumulated on heat sinks and /or components which generate heat, it should be removed carefully by vacuuming, wiping, or brushing, since such accumulation can reduce heat dissipation capability and lead to premature failures. 4. Busbar, Wiring, and Terminal Connections. Any loose busbar or terminal connection will cause overheating that will lead to equipment malfunction or failure. Loose bonding or grounding can compromise safety and/or function. Overheating in a bus or terminal connection will cause a discoloration in the busbar which can easily be spotted where connections are visible oftentimes too late to avoid replacement. An overheating busbar condition will feed on itself and lead to deterioration of the bus system as well as the equipment connected to the bus such as: protective devices, bus stabs, insulated leads, etc. Aluminum connections usually utilize parts that should not be cleaned with abrasives. Busbar and terminal connections should be inspected periodically to insure that all joints are properly tightened Proper torque tightness is a factor of bolt size, bolt type, and type of busbar and terminal material. Proper bolt tightness torque values for all type of joints involves should be available in manufacturer’s and instructional literature. Do not assume that busbar and terminal hardware, once tightened to proper torque values, remains tight indefinitely. Special attention should be given to busbars and terminal hardware, once tightened to proper torque values, remain tight indefinitely. Special attention should be given to busbars and terminal connections in equipment rooms where excessive vibration or heating/cooling cycles may cause more than normal loosening of bolted bus an terminal connections. Busbar support insulators and barriers should be inspected to ensure that they are free of contamination. Insulators should be periodically checked for cracks and signs of arc tracking. Defective units should be replaced. Loose mounting hardware should be tightened. Examine insulation on conductors for overheating or calling against metal edges that could progress into an insulation failure. Any damaged conductors should be replaced. Replacement conductors should be re-routed, braced or shielded if needed to avoid similar damage in future operation. Temporary wiring should be removed or replaced by permanent wiring. 5. DISCONNECTS. Disconnects should be examined on both the line and load side for proper maintenance evaluation. Prior to initiating such an evaluation, the source side disconnect device should be opened and padlocked and tagged to avoid accidental energization by other personnel during maintenance operations. Never assume that a disconnect is in the open position because the handle mechanism is in the open position. Always double-check for safety. Disconnect switches generally have visible blade contacts and open-type disconnect. Excessive heat in a disconnect switch can lead to deterioration of the insulation and eventual failure of the device. Loose connections are the major source of excessive heat. Terminal and busbar connections as well as cable connections should be examined and tightened as required using the manufacturer’s torque recommendations. Any device having evidence of overheated conductors an carbonized insulation that could also be caused by arching should be replaced. Contacts should be examined for evidence of welding or excessive pitting. Damaged disconnects with any evidence of these failure signs should be replaced. Mechanism should be manually operated to ensure proper working condition. Factory lubricated mechanisms will sometimes dry out after a period of time in dry, heated atmospheres. Manufacturers’ maintenance literature should be followed for roper lubrication instructions. 6. FUSES-WARNING. Fuses are normally used in conjunction with disconnect switches. In no case should a dummy fuse copper slug, or length of wire ever be used as a proper fuse substitute even on a temporary basis. 7. CONTACTORS. Since contactors are the working portion of a motor controller, normal wear can be expected. Contacts and arc chutes of electromechanical contactors should be checked for excessive burning beads of molten material, and unusual erosion of the contact faces. Do not file or dress contacts unless recommended by the manufacturer. Replace excessively worn or pitted contacts with manufacturer recommended renewal parts, or replace the contactor. All contacts of multi-pole devices should be replaced simultaneously to avoid misalignment and uneven contact pressure. Arc chutes and arc hoods should be replaced if they are broken or deeply eroded. Easily dislodged dust or granules should be removed by vacuuming, wiping or light brushing. Insulting surfaces should not be scraped, sanded or filled. A noisy solenoid in a relay or contactor indicates failure to seat properly or a broken or loose shading coil. The cause should be determined and corrected to avoid overheating an coil damage. If a coil exhibits evidence of overheating (cracked, melted, or burned insulation), it should be replaced, after the cause of overheating has been detected and corrected. This could include the AC magnet symptoms described above, or any binding that keeps the magnet from seating properly when energized , or over voltage or under voltage conditions. If melted coil insulation has flowed onto other parts, they should be cleaned or replaced 8. MOTOR OVERLOAD RELAYS. Motor overload relays perform the vital supervisory function of monitoring the overload current conditions for the associated motor. The most commonly used overload relays employ a thermal element signed to interpret the overheating condition in the windings by converting the current in the motor leads to heat in the overload relay element. As the heat in the thermal element reaches predetermined amount, the control circuit to the magnetic contactor holding coil is interrupted and the motor branch circuit is opened. The two most common types of thermal elements in thermal overload relays employ either a bimetal or a melting alloy joint to initiate the opening action of the contactor. Heater elements are usually replaceable; however, if a trip or burnout of the element occurs, the cause of this trip or burnout should be identified and corrected. Replacement for the heater element with one of a higher rating should not be done without full consideration of the ambient temperature in without full consideration of the ambient temperature in which the motor operates, as well as all other motor data. Thermal overload relays are applied on the basic of motor full-load current and the motor service factor found on the motor rating nameplate. Complete records on all motors including motor full-load amps together with proper manufacturer’s heater selection an application charts should be included as a part of any maintenance file on motor starters. General heater application charts are usually secured inside the starter enclosure. Routine maintenance should include a check for loose terminal or heater connections and signs of overheating. Overheating can cause carbonization of the molding material creating potential breakdowns as well as possibly altering the calibration of the overload relay. Overload relay showing signs of excessive heating should be replaced. 1. PILOT AND MISCELLANEOUS CONTROL DEVICES. Pilot and other control devices consist of the control accessories normally employed with motor starters and include: push buttons, selector switches, indicating lights, timers, auxiliary relays, etc. Routine maintenance checks on these types of devices generally include the following: (a) Check for loose wiring (b) Check for proper mechanical operation of operators and contact blocks. (c) Inspection of contacts (when exposed) (d) Check for signs of overheating (e) replacement of pilot lamps 10. INTERLOCKS. A contactor or starter may be provided with auxiliary contacts that permit interlocking with other devices as well as serve other position indicating functions. Proper maintenance of these electrical auxiliary contacts include the following: (a) Check for loose wiring (b) Check for proper mechanical operation and alignment with the contactor (c) Inspection of contacts (when exposed) Mechanical interlocks can be classified in two categorized according to their application: safety and functional performance. Safety interlocks are designed to protect operating personnel by preventing accidental contact with energized conductors and the hazards of electrical shock. Functional interlocks, such as those found on reversing contactors, are designed to prevent the inadvertent closing of parallel contactors wired to provide alternate motor operating conditions. Mechanical interlocks should be examined to ensure that the interlock is free to operate and bearing surfaced are free to operate and that bearing surfaces are free to perform their intended function. Interlocks showing signs of excessive wear and deformation should be replaced. Several types of locking or interlocking features are used. A primary disconnect mechanism is usually mounted directly on the disconnect device. It is mechanically interlocked with the door to ensure that the door is held closed with the disconnect in the “ON” position. A maintenance check should be made to ensure that the adjustment is correct and that the interlock is providing proper engagement. Disconnect operation mechanisms are provided with padlocked “OFF” position for personnel safety. Most disconnects are equipped with defeater mechanism that can be operated to release door interlock mechanisms with the disconnect device in the “ON” position. The use of the release mechanism should be limited to qualified maintenance and operating personnel. MAINTENANCE OF MOTOR CONTROLLER AFTER A FAULT CONDITION In a motor branch circuit which has been properly installed, coordinated and in service prior to the fault, opening of the branch-circuit short-circuit protector, etc.) indicates a fault condition in excess of operating overload. This fault condition must be corrected and the necessary branch circuit. It is recommended that the following general procedures be observed by qualified personnel in the inspection and repair of the motor controller involved in the fault. Manufacturers’ service instructions should also be consulted for additional details. Caution: It must be understood that all inspections and tests are to e made on controller and equipment which tests are to be made on controllers and equipment which are deenergized, disconnected and isolated so that accidental contact cannot be made with live parts and so that all plant sofety procedures will be observed. 1. ENCLOSURE. Substantial damage to the enclosure such as deformation, displacement of parts or burning, requires replacement of the entire enclosure. 2. CIRCUIT BREAKERS. Examine the enclosure interior and the circuit breaker for evidence of possible damage. If evidence of damages mot apparent, the breaker may be reset and turned “ON.” If it is suspected that the circuit breaker is opened several short-circuit faults or if signs of possible deterioration beyond normal wear and tear, such as overheating, contact blade or jaw putting, insulation breakage or charring, the switch must be replaced. 3. DISCONNECT SWITCH. The external operating handle must be capable of opening the switch. If the handle fails to open the switch or if visual inspection after opening indicates deterioration beyond normal wear and tear, such as overheating, contact blade or jaw pitting, insulation breakage or charring, the switch must be replace 4.FUSE HOLDRS. Deterioration of fuse holders or their insulation mounts requires their replacement. 5. TERMINALS AND INERNAL CONDUCTORS. Indications of arcing or overheating, or both, such as discoloration and melting of insulation require the replacement of damaged parts. 6. CONTACTOR. Contacts showing heat damage, displacement of metal, or loss of adequate wear allowance require replacement of the contacts and, where applicable, the contact springs. If deterioration extends beyond the contacts, such as binding in the guides or evidence of insulation damage, the damaged parts of the entire contactor must be replaced. 7. OVERLOAD RELAYS. If burnout of the current element of an overload relay has occurred, the complete overload relay must e replaced. Any indication that an arc has struck and/or any indication of burning of the insulation of the overload relay also requires replacement of the overload relay. If there is no visual indication of damages that would require replacement to the overload relay, the relay must be electrically or mechanically tripped to verify proper functioning of the overload relay contact(s). 8. RETURN TO SERVICE. Before returning the controller to service, checks must be made for tightness of electrical connections and for the absence of short circuit, grounds an leakage. All equipment enclosures must be closed and secured before the branch circuit is energized. INGERSOLL-RAND REMOTE MOTOR STARTER 600 VOLTS OR LESS INSTALLATION AND MAINTENANCE INSTRUCTION MANUAL