Attachments to Section 4.2

advertisement
NOTES:
LEGEND:
1.
ALL DIMENSION ARE IN mm UNLESS
OTHERWISE STATED.
2.
C
THIS DRAWING TO BE READ IN CONJUNCTION
WITH SPECIFICATIONS.
T
PROGRAMMABLE TIMER WITH RS 232 INTERFACE UNIT
3. ALL ARCHITECTURE DETAILS TO ARCH’S
APPROVAL.
C/W BYPASS SWITCH (SETTING 7pm TO 7am)
RAMPS
6. ALTERNATE CIRCUITING SHALL BE PROVIDED
FOR ALL LIGHTING.
RCCB
RESIDUAL CURRENT CIRCUIT BREAKER
7. CONTRACTOR TO DESIGN THE ELECTRICAL
*SEE
8. OUTGOING CONTACTOR SHALL BE RATED
MINIATURE CIRCUIT BREAKER
APPROPRIATELY.
9. OUTGOING LIGHTING CIRCUIT BREAKER
DP
SHALL BE APPROPRIATELY DESIGN WITH
DOUBLE POLE
MINIMUM RATING OF 10A SPN MCB 10KA.
S
PERFORMANCE
TO
LI
GHT FI
TTI
NG
TECHNI
CAL SPECI
FI
CATI
ON
MCB
SPARE
COVERED
FOR
LI
GHT
HEAVY DUTY UPVC PIPES
LATEST SS CP5.
COVERED
FI
TTI
NG
ARMOURED CABLE IN
WI
TH
HEAVY DUTY UPVC PIPES
POB
PVC CABLES IN
RAMPS/LI
NKW AY
INSTALLATION IN ACCORDANCE WITH THE
SPARE
FOR
COMMENCEMENT OF INSTALLATION.
COVERED
FI
TTI
NG
CONTRACTOR SHOULD DO A SITE SURVEY
BEFORE WORK COMMENCEMENT.
TO THE S.O. FOR APPROVAL PRIOR TO
ISOLATOR
WI
TH
LI
GHT
4.
5. SINGLE LINE DIAGRAMS SHALL BE SUBMITTED
POB
COVERED
2A
MOTION SENSOR
LIGHTNING SURGE ARRESTOR
LSA
WEATHERPROOF JUNCTION BOX
BI
BI TERMINAL
NOTE
NO. 9
32A COMB BUSBAR
S
MIDNIGHT
PVC CABLES IN
TO 7am
HEAVY DUTY UPVC PIPES
C
CONTACTOR
INTELLIGENT
*SEE
LIGHTING
NOTE
CONTROL BOX
NO. 8
ARMOURED CABLE IN
HEAVY DUTY UPVC PIPES
*SEE
*SEE
NOTE
NOTE
NO. 9
NO. 9
32A COMB BUSBAR
32A COMB BUSBAR
7pm
7pm
TO 7am
TO 7am
32A DP
C
PROGRAMMABLE
TIMER
T
32A DP
C
CONTACTOR
CONTACTOR
PROGRAMMABLE
TIMER
T
2A
2A
BI
BI
BI TERMINAL
BI TERMINAL
40A DP
RCCB
(100mA)
40A DP
RCCB
(100mA)
LSA
LSA
DP MCB
DP MCB
32A
DP MCB
(TYPE B)
NEW DB
POB/LINKWAY
(10 KA)
(LTA COMPARTMENT)
NEW DB
BUS SHELTER/
TAXI STAND
32A
DP MCB
(TYPE B)
(10 KA)
(LTA COMPARTMENT)
LTA Endorsement :
32A DP
ISOLATOR
32A DP
ISOLATOR
kwh
POWER GRID
METER
32A
DP MCB (TYPE C)
(PROVIDED BY PG)
kwh
POWER GRID
METER
32A
DP MCB (TYPE C)
(PROVIDED BY PG)
RING CIRCUIT
SHALL BE LESS
BI
NEW
OG-BOX
E
BI SUPPLIED AND
INSTALLED BY PG
Project Title :
THAN 1 ohm
STANDARD INSTALLATION DETAILS
(PG COMPARTMENT)
FROM POWERGRID
Drawing Title :
TYPICAL SINGLE LINE DIAGRAM FOR NEW OG BOX
TYPICAL SINGLE LINE DIAGRAM - FOR NEW OG-BOX (POB/LINKWAY/TAXI STAND/BUS SHELTER)
(POB/LINKWAY/TAXI STAND/BUS SHELTER)
SCALE NTS
Designed
NURLY
NURLY
Checked
MALVIN HO
Scale
Drawn
NTS
JULI
Approved
MELVYN THONG
Date
1. REVISED LIGHT FITTING DESCRIPTION
A
DEC 2010
TAY K.C.
2. INCLUDE LEGEND AND REVISED NOTES.
ADRIAN CHEONG/
HADI WIJAYA
MELVYN
THONG
3. REVISED POB /LINKWAY INCOMMING ISOLATOR RATING TO
32A AND SPPG DP MCB FROM 63A TO 32A.
Rev.
Date
By
Description
JULY 2007
Drawing No. :
Rev.
L/ROAD/MES/SD/1002
Chk’d
App’d
CAD File Name:LROADMES-SD1002A.dgn
Sheet
A
1 of 1 A3
NOTES:
LEGEND:
1.
ALL DIMENSION ARE IN mm UNLESS
OTHERWISE STATED.
2.
C
THIS DRAWING TO BE READ IN CONJUNCTION
WITH SPECIFICATIONS.
T
PROGRAMMABLE TIMER WITH RS 232 INTERFACE UNIT
3. ALL ARCHITECTURE DETAILS TO ARCH’S
APPROVAL.
C/W BYPASS SWITCH (SETTING 7pm TO 7am)
2A
4.
CONTRACTOR SHOULD DO A SITE SURVEY
BEFORE WORK COMMENCEMENT.
5. SINGLE LINE DIAGRAMS SHALL BE SUBMITTED
TO THE S.O. FOR APPROVAL PRIOR TO
ISOLATOR
FOR ALL LIGHTING.
RCCB
RESIDUAL CURRENT CIRCUIT BREAKER
7. CONTRACTOR TO DESIGN THE ELECTRICAL
INSTALLATION IN ACCORDANCE WITH THE
LATEST SS CP5.
PERFORMANCE
TO
LI
GHT FI
TTI
NG
TECHNI
CAL SPECI
FI
CATI
ON
COMMENCEMENT OF INSTALLATION.
6. ALTERNATE CIRCUITING SHALL BE PROVIDED
MCB
8. OUTGOING LIGHTING CIRCUIT BREAKER
MINIATURE CIRCUIT BREAKER
SHALL BE APPROPRIATELY DESIGN WITH
MINIMUM RATING OF 10A SPN MCB 10KA.
DP
S
LSA
DOUBLE POLE
MOTION SENSOR
LIGHTNING SURGE ARRESTOR
WEATHERPROOF JUNCTION BOX
PVC CABLES IN
HEAVY DUTY UPVC PIPES
BI
BI TERMINAL
ARMOURED CABLE IN
HEAVY DUTY UPVC PIPES
*SEE
NOTE
SPARE COMPARTMENT
NO. 8
FOR INTELLIGENT LIGHTING CONTROL BOX
32A COMB BUSBAR
7pm TO
7am
32A DP
C
CONTACTOR
T
PROGRAMMABLE
TIMERS
2A
BI
40A DP
RCCB
(100mA)
LSA
DP MCB
NEW DB
BUS SHELTER/
TAXI STAND
32A
DP MCB (TYPE B)
(10KA)
SPARE COMPARTMENT
63A
DP ISOLATOR
kwh
POWER GRID
METER
63A
DP MCB (TYPE C)
(10KA)
kwh
POWER GRID
METER
32A
DP MCB (TYPE C)
(PROVIDED BY PG)
LTA Endorsement :
(PROVIDED BY PG)
BI
BI SUPPLIED AND
RING CIRCUIT
INSTALLED BY PG
NEW
OG-BOX
SHALL BE LESS
E
THAN 1 ohm
(PG COMPARTMENT)
Project Title :
FROM POWERGRID
STANDARD INSTALLATION DETAILS
TYPICAL SINGLE LINE DIAGRAM FOR NEW OG-BOX (BUS SHELTER / TAXI STAND )
SCALE: NTS
Drawing Title :
TYPICAL SINGLE LINE DIAGRAM FOR NEW OG-BOX
(BUS SHELTER/TAXI STAND)
Designed
NURLY
Scale
1. REVISED LIGHT FITTING DESCRIPTION
A
JUNE 2010
TAY K.C
Date
By
Description
MALVIN HO
Drawn
JULI
Approved
MELVYN THONG
Date
JULY 2007
Drawing No. :
2. INCLUDE LEGEND AND REVISED NOTES.
3. INCLUSION OF TAXI STAND REQUIREMENT.
Rev.
NTS
Checked
ADRIAN CHEONG/
HADI WIJAYA
MELVYN
THONG
Chk’d
App’d
Rev.
L/ROAD/MES/SD/1003
CAD File Name:
A
LROADMES-SD1003A.dgn Sheet 1 of 1 A3
NOTES:
LEGEND:
1.
ALL DIMENSION ARE IN mm UNLESS
OTHERWISE STATED.
2.
C
THIS DRAWING TO BE READ IN CONJUNCTION
WITH SPECIFICATIONS.
T
PROGRAMMABLE TIMER WITH RS 232 INTERFACE UNIT
3. ALL ARCHITECTURE DETAILS TO ARCH’S
APPROVAL.
C/W BYPASS SWITCH (SETTING 7pm TO 7am)
RAMPS
6. ALTERNATE CIRCUITING SHALL BE PROVIDED
FOR ALL LIGHTING.
RCCB
RESIDUAL CURRENT CIRCUIT BREAKER
7. CONTRACTOR TO DESIGN THE ELECTRICAL
*SEE
MCB
8. CONTRACTOR IS RESPONSIBLE TO REPLACE
MINIATURE CIRCUIT BREAKER
ITEM MARKED * TO 32A RATING.
9. OUTGOING CONTACTOR SHALL BE RATED
DP
DOUBLE POLE
APPROPRIATELY.
10. OUTGOING LIGHTING CIRCUIT BREAKER
S
SHALL BE APPROPRIATELY DESIGN WITH
MOTION SENSOR
MINIMUM RATING OF 10A SPN MCB 10KA.
LIGHTNING SURGE ARRESTOR
LSA
WEATHERPROOF JUNCTION BOX
SPARE
COVERED
FOR
LI
GHT
HEAVY DUTY UPVC PIPES
LATEST SS CP5.
COVERED
FI
TTI
NG
ARMOURED CABLE IN
WI
TH
HEAVY DUTY UPVC PIPES
POB
PVC CABLES IN
RAMPS/LI
NKW AY
INSTALLATION IN ACCORDANCE WITH THE
SPARE
FOR
COMMENCEMENT OF INSTALLATION.
COVERED
FI
TTI
NG
CONTRACTOR SHOULD DO A SITE SURVEY
BEFORE WORK COMMENCEMENT.
TO THE S.O. FOR APPROVAL PRIOR TO
ISOLATOR
WI
TH
LI
GHT
4.
5. SINGLE LINE DIAGRAMS SHALL BE SUBMITTED
POB
COVERED
2A
BI
BI TERMINAL
NOTE
NO. 10
32A COMB BUSBAR
S
MIDNIGHT
PVC CABLES IN
TO 7am
HEAVY DUTY UPVC PIPES
C
INTELLIGENT
CONTACTOR
*SEE
LIGHTING
NOTE
CONTROL BOX
NO. 9
ARMOURED CABLE IN
HEAVY DUTY UPVC PIPES
*SEE
NOTE
NO. 10
32A COMB BUSBAR
7pm
TO 7am
32A DP
C
CONTACTOR
PROGRAMMABLE
TIMER
T
2A
BI
BI TERMINAL
*SEE
40A DP
RCCB
(100mA)
NOTE
NO. 10
LSA
DP MCB
EXISTING
DBO BUS SHELTER
32A
DP MCB
(TYPE B)
NEW OG-BOX
POB/LINKWAY
(10 KA)
LTA Endorsement :
63A * (SEE NOTE 8)
DP ISOLATOR
kwh
POWER GRID
METER
63A * (SEE NOTE 8)
DP MCB (TYPE C)
(10KA)
32A DP
ISOLATOR
kwh
POWER GRID
METER
32A
DP MCB (TYPE C)
(PROVIDED BY PG)
(PROVIDED BY PG)
RING CIRCUIT
Project Title :
SHALL BE LESS
BI
EXISTING
OG-BOX
E
BI SUPPLIED AND
THAN 1 ohm
INSTALLED BY PG
STANDARD INSTALLATION DETAILS
(PG COMPARTMENT)
FROM POWERGRID
Drawing Title :
TYPICAL SINGLE LINE DIAGRAM FOR EXISTING OG-BOX (DBO BUS SHELTER /POB /LINKWAY)
TYPICAL SINGLE LINE DIAGRAM FOR EXISTING OG-BOX
(DBO BUS SHELTER/POB/LINKWAY)
SCALE: NTS
Designed
NURLY
Scale
1. REVISED LIGHT FITTING DESCRIPTION
JUNE 2010
Date
Approved
MELVYN THONG
Date
JULY 2007
Drawing No. :
Rev.
TAY K.C
3. REVISED POB /LINKWAY INCOMMING ISOLATOR RATING TO
32A AND SPPG DP MCB FROM 63A TO 32A.
Rev.
MALVIN HO
Drawn
JULI
2. INCLUDE LEGEND AND REVISED NOTES.
A
Checked
By
Description
ADRIAN CHEONG/
HADI WIJAYA
MELVYN
THONG
Chk’d
App’d
A
L/ROAD/MES/SD/1004
CAD File Name: LROADMES-SD1004A.dgn
Sheet
of
A3
Depth = min 450mm
Depth = min 450mm
ABLOY
3273-A
SUPPORT FOR INTELLIGENT
LIGHTING DETECTION SYSTEM
CONTROLLER
Back
EXTERNAL FRONT DOOR
EXTERNAL BACK DOOR
Front
INTELLIGENT
LIGHTING
DETECTION
SYSTEM
CONTROLLER
FOR POB
Lock
mi
n
100mm HEAVY DUTY UPVC PIPE
FOR BUS SHELTER/TAXI STAND
ELECTRICAL DISTRIBUTION
Back
PARTITION
Front
-
100
B
-
Depth =
2
2 NOS 100mm HEAVY DUTY UPVC
LEAD IN C/W 90^ LONG BEND PIPES
FOR POWER GRID INCOMING CABLING
450 mm
100mm HEAVY DUTY UPVC PIPE
FOR POB/LINKWAY ELECTRICAL
DISTRIBUTION
Back
FIX PLATE
1
-
SUPPORT FOR BREAKER
GLASS
PARTITION
EXTERNAL FRONT DOOR
Front
50mm HEAVY DUTY UPVC PIPE
FOR BUS SHELTER ADVERTISING PANEL
REMOVABLE
PLATE
EXTERNAL FRONT DOOR
A
-
PLAN VIEW
ELEVATION 1
ELEVATION 2
Overall Length = min 1320mm
Qualified Person Endorsement :
Overall Length = min 1320mm
200
200
70
70
70
420
560
Depth = min 450mm
70
Std= 235
Std= 235
T’wood= 230
T’wood= 230
82.5
ABLOY
3273-A
Std Casing=560
188
UV STABILISED
POLYCARBONATE
POB/
LINKWAY
INTELLIGENT
LIGHTING
DETECTION
SYSTEM
CONTROLLER
FOR POB
GRID
1 KWH
1 KWH
METER
METER
SUPPORT FOR
INTELLIGENT
LIGHTING
DETECTION
SYSTEM
CONTROLLER
EXTERNAL
FRONT
DOOR
SUPPORT
FOR BREAKER
PARTITION
BUS SHELTER/
TAXI STAND
T’
wood= 300
Lock
Lock
Lock
FIX PLATE
UV STABILISED
POLYCARBONATE
POWER
GRID
Overal
lHei
ght = m i
n 1300m m
Overal
lHei
ght = m i
n 1300m m
188
POWER
BI Supply
and Installed
By PG
LTA Endorsement :
Front
ABLOY
3273-A
Back
ABLOY
3273-A
138
T’
wood= 300
138
EXTERNAL
FRONT
DOOR
PARTITION
REMOVABLE PLATE
REMOVABLE PLATE
27.5
280
280
T’wood= 230
T’wood= 230
Project Title :
REMOVABLE PLATE
27.5
STANDARD INSTALLATION DETAILS
2 NOS 100mm HEAVY DUTY UPVC
LEAD IN C/W 90^ LONG BEND PIPES
FOR POWER GRID INCOMING CABLING
PLINTH C/W OPENING
FOR CABLE ENTRY
SECTION B-B
Drawing Title :
TYPICAL DETAIL OF POB/LINKWAY/
100mm HEAVY DUTY UPVC PIPE
FOR POB/LINKWAY ELECTRICAL
DISTRIBUTION
EXTERNAL VIEW
EXTERNAL BACK VIEW
50mm HEAVY DUTY
UPVC PIPE FOR BUS
SHELTER ADVERTISING
PANEL
INTERNAL SIDE VIEW
INTERNAL FRONT VIEW
100mm HEAVY DUTY
UPVC PIPE FOR BUS
SHELTER/TAXI STAND
ELECTRICAL DISTRIBUTION
BUS SHELTER/TAXI STAND/OG-BOX
SECTION A-A
Designed
TYPICAL DETAIL OF POB / LINKWAY / BUS SHELTER / TAXI STAND / OG-BOX
NURLY
SCALE: NTS
Scale
1. INCLUSION OF TAXI STAND OG-BOX REQUIREMENT.
N.T.S.
Checked
MALVIN HO
Drawn
JULI
Approved
MELVYN THONG
Date
JULY 2007
2.ADD SPACE TO HOUSE INTELLIGENT LIGHTING DETECTION
A
JUNE 2012
CHING
SYSTEM CONTROLLER INSIDE OG-BOX.
ANGELINE
HADI
WIJAYA
ADRIAN
CHEONG
Drawing No. :
Rev.
3.ADD PROVISION OF 50mm HEAVY DUTY UPVC PIPE FOR
L/ROAD/MES/SD/1006
INTELLIGENT LIGHTING DETECTION SYSTEM.
Rev.
Date
Drawn
By
Description
Designed
By
Chk’d
App’d
CAD File Name :LROADMES-SD1006A.dgn
Sheet
A
1 of 1
A4
1
2
3
7500
750
EARTH PIT
(TOTAL RESISTANCE < 10ohm)
(LOCATION TO BE DETERMINED
ON SITE & TO SO APPROVAL)
3000
1500
3000
1500
A
L/ER373/AR/TD/5003
MS ANGLE ROOF FASCIA TO ENGR’S DTL
300
750
1500
EARTH PIT
(TOTAL RESISTANCE < 10ohm)
2
L/ER373/AR/TD/5003
(LOCATION TO BE DETERMINED
ON SITE & TO SO APPROVAL)
1500
LOCATION OF ADVERTISEMENT
PANEL TO BE DETERMINED ON
SITE
POWDER COATED ALUM. ’F’ TYPE CAPPING
NEW OG BOX
A
(IP55) LOCATION
DOWN CONDUCTOR
SHALL BE SUBJECTED
M.S. RHS POST BELOW (C1)
TO SITE CONDITIONS
ROOF CAPPING @ 1500mm C/C TO
AND POWERGRID’S APPROVAL
MFR’S DTL
MIN. 10mm THK. ALUM. HONEY COMB
FALL
FALL
3
2700
3000
L/ER373/AR/TD/5003
3
ROOF PANEL COMPLETE WITH MIN. 1mm THK
TOP PANEL AND 0.7mm THK UNDERSIDE
PANEL TO SO’S APPROVAL
3
ADVERTISEMENT
PANEL
BUS SHELTER ADDRESS PLATE TO FACE
ONCOMING TRAFFIC IN ACCORDANCE TO
LTA ARCHITECTURAL DESIGN CRITERIA
DRAWING NO. L/CFADC/AR/BS/0005
LATEST REVISION
1NO. 50mm HEAVY DUTY
UPVC PIPE C/W PULL WIRES
FROM OG-BOX TO ADVERTISING
PANEL
DETAIL "1"
NTS
TYPICAL LIGHTNING PROTECTION SYSTEM (ROOF PLAN)
SCALE 1:50
1
750
ARMOURED CABLE IN
1 NO. 100mm HEAVY DUTY
UPVC PIPE
ARMOURED CABLE IN
1 NO. 100mm HEAVY3DUTY
UPVC PIPE
2
7500
3000
3000
A
2
L/ER373/AR/TD/5003
L/ER373/AR/TD/5003
ARMOURED CABLE IN
1 NO. 100mm HEAVY DUTY
UPVC PIPE
ARMOURED CABLE IN
1 NO. 100mm HEAVY DUTY
UPVC PIPE
750
300
ROOF EAVES ABOVE
NOTICE BOARD WITH ALUM. FRAME C/W
4mm THK. TEMPERED GLASS
A
NEW
OG BOX
750 (CLEAR)
M.S. RHS POST (C1)
PVC CABLE IN 25mm
HEAVY DUTY UPVC PIPE
ALUM. BENCH
2 NOS. 100mm HEAVY DUTY
UPVC HEAD-IN 90 LONG BEND
PIPES FOR SP POWERGRID’S
INCOMING CABLE
ALUM. BENCH
LITTER BIN BY OTHERS
300
3
L/ER373/AR/TD/5003
3000
2700
1400
1 NO. 50mm HEAVY DUTY
UPVC PIPE C/W PULL WIRES
FROM 0G-BOX TO ADVERTISING PANEL
FALL
PROPOSED LIGHT FITTING (IP65)
TO M&E SPECIFICATION
FALL
PROPOSED LIGHT FITTING (IP65)
TO M&E SPECIFICATION
CONC. SLAB COMPLETE WITH 25mm THK
GRANOLITHIC FINISHES TO SO’S APPROVAL
1 NO. ELECTRICAL PIPE WITH
DRAW WIRES FOR ADVERTISEMENT
PANEL TO BE LOCATED AT THE
DOWNSTREAM EDGE OF BUS SHELTER
(SEE DETAIL "1")
200 WIDE YELLOW LINE IN HOT APPLIED
THERMOPLASTIC ROAD MARKING MATERIALS
125
MI
N.600
LTA Endorsement :
200
LINE OF ROAD KERB OR ROAD RESERVE LINE
A
1
-
L/ER373/AR/TD/5003
Project Title :
TYPICAL LIGHTING LAYOUT PLAN
STANDARD INSTALLATION DETAILS
Drawing Title :
TYPICAL LIGHTING AND LIGHTNING PROTECTION
SYSTEM FOR BUS SHELTER
Designed
NURLY
0
0.5
1
1.5
2
Scale
2.5 Metres
1:50
Checked
MALVIN HO
Drawn
JULI
Approved
MELVYN THONG
Date
JULY 2007
Drawing No. :
Scale 1:50
A
Rev.
DEC 2010
Date
TAY K.C
By
REVISED DETAILS
Description
ADRIAN CHEONG/
HADI WIJAYA
MELVYN
THONG
Chk’d
App’d
Rev.
A
L/ROAD/MES/SD/1007
CAD File Name:LROADMES-SD1007A.dgn
Sheet
1 of 1
A3
1
PROPOSED LIGHT
FITTING (IP65) TO
M&E SPECIFICATION
2
3
7500
750
3000
3000
1500
1500
BUS SHELTER ADDRESS PLATE TO FACE
ONCOMING TRAFFIC IN ACCORDANCE TO
LTA ARCHITECTURAL DESIGN CRITERIA
DRAWING NO. L/CFADC/AR/BS/0005
LATEST REVISION
BONDING DETAILS TO
ROOF SPECIALIST’S
REQUIREMENTS
750
1500
1500
POWDER COATED ALUM. ’F’ TYPE CAPPING
MS ANGLE ROOF FASCIA (T1)
200
M.S. SHS (R2)
PROPOSED LIGHT
FITTING (IP65) TO
M&E SPECIFICATION
–2388
2300
LITTER BIN BY OTHERS
CONC. SLAB COMPLETE WITH 25mm THK
ALUM. BENCH
GRANOLITHIC FINISHES TO SO’S APPROVAL
450
450 (BENCH)
EARTH PIT
NEW OG BOX (IP54)
LOCATION SHALL BE SUBJECTED
TO SITE CONDITIONS AND SP
POWERGRID’S APPROVAL
–2692
1000
2170
NOTICE BOARD WITH ALUM. FRAME
C/W 4mm THK. TEMPERED GLASS
(SHALL ALLOW CLEAR MOUNTING
OF POSTERS OF SIZE 940 X 940,
TO BE IN FULL UNOBSTRUCTED
VIEW THROUGH THE FRONT
GLASS PANEL OF 900 X 900)
ALUM. BENCH
150
BONDING TO
STRUCTURE
COLUMN (MIN.
150mm ABOVE
GROUND)
SEE DETAIL ’2’
PROPOSED LIGHT M.S. ’C’ CHANNEL RAFTER (R1)
FITTING (IP65) TO LIGHT FITTING TO M&E SPECS
M&E SPECIFICATION
1000
M.S. RHS POST (C1)
970
CONCEALED
PVC CABLE
IN 25mm
HEAVY DUTY
UPVC PIPE
1000
FFL
SEE DETAIL ’3’
EARTH PIT
SEE DETAIL ’3’
ARMOURED CABLE IN
1 NO. 100mm HEAVY DUTY
UPVC PIPE
CONCEALED JUNCTION BOX FOR
CABLE CONNECTION
ARMOURED CABLE IN
1 NO. 100mm HEAVY DUTY
UPVC PIPE
CONCEALED JUNCTION BOX FOR
CABLE CONNECTION
BONDING TO STRUCTURE
COLUMN (MIN. 150mm
ABOVE GROUND)
SEE DETAIL ’3’
ELEVATION PLAN
2 NOS 100mm HEAVY DUTY UPVC
PIPES LEAD IN 90 LONG BEND PIPES
FOR SP POWERGRID INCOMING CABLING
SCALE 1:50
A
3000
300
MIN. 600
2700
H
HOT DIP
GALVANISED COVER
CONCEALED
JUNCTION BOX
BONDING DETAILS TO
ROOF SPECIALIST’S
REQUIREMENTS
-
EARTH ROD CLAMP
INCLUSIVE OF LIGHTNING
PROTECTION EARTH LABEL
50
GROUND LEVEL
B-BOND
PROPOSED LIGHT FITTING
(IP65) TO M&E SPECIFICATION
M8 ALUMINIUM COPPER BOLT
TO STEEL SUPPORT POST
CONCRETE HAUNCH
ALL AROUND
25mm x 3mm COPPER TAPE
–2692
–2534
CONCEALED PVC CABLE
IN 25mm HEAVY DUTY
UPVC PIPE
LTA Endorsement :
2300
–2388
BONDING TO STRUCTURE
COLUMN (MIN. 150mm ABOVE
GROUND)SEE DETAIL ’2’
ALUMINIUM OR
STEEL SUPPORT POST
CONCEALED JUNCTION BOX
FOR CABLE CONNECTION
SEE DETAIL ’3’
200 (MI
N.)
EARTH
PIT
450
300
COUPLING
50mm HEAVY DUTY UPVC
PIPE C/W 25mm X 3mm
COPPER CONDUCTOR TAPE
EARTH ROD
H
ROAD
(min. 2 Nos. 1.8m LENGTH,
16mm DIA COPPER)
DETAIL 3
Scale: N.T.S.
-
SECTION H-H
DETAIL 2
TYPE 1 - ELEVATION OF LIGHTNING
BONDING TO STEEL SUPPORT POST
Project Title :
Scale: N.T.S.
STANDARD INSTALLATION DETAILS
Scale: N.T.S.
Drawing Title :
SECTION PLAN
TYPICAL ELECTRICAL INSTALLATION DETAILS FOR
BUS SHELTER
SCALE NTS
Designed
NURLY
Scale
0
0.5
1
1.5
2
2.5 Metres
1:50
Checked
MALVIN HO
Drawn
JULI
Approved
MELVYN THONG
Date
JULY 2007
Drawing No. :
Scale 1:50
A
Rev.
DEC 2010
Date
TAY K.C
By
REVISED DETAILS
Description
ADRIAN CHEONG/
HADI WIJAYA
MELVYN
THONG
Chk’d
App’d
Rev.
A
L/ROAD/MES/SD/1008
CAD File Name:
LROADMES-SD1008A.dgn
Sheet
1 of 1
A3
1
2
3
7500
750
3000
3000
1500
1500
750
1500
1500
BUS SHELTER ADDRESS PLATE TO FACE
ONCOMING TRAFFIC IN ACCORDANCE TO
LTA ARCHITECTURAL DESIGN CRITERIA
DRAWING NO. L/CFADC/AR/BS/0005
LATEST REVISION
POWDER COATED ALUM. ’F’ TYPE CAPPING
MS ANGLE ROOF FASCIA (T1)
200
M.S. SHS (R2)
1000
M.S. ’C’ CHANNEL RAFTER (R1)
1000
LIGHT FITTING TO M&E SPECS
NEW OG BOX
M.S. RHS POST (C1)
SHALL BE SUBJECTED
TO SITE CONDITIONS
AND POWERGRID’S APPROVAL
2 NOS 100mm HEAVY
LITTER BIN BY OTHERS
DUTY UPVC PIPES
CONC. SLAB COMPLETE WITH 25mm THK
ALUM. BENCH
LEAD IN 90 LONG
GRANOLITHIC FINISHES TO SO’S APPROVAL
450
BEND PIPES FOR
POWERGRID INCOMING
ALUM. BENCH
150
450 (BENCH)
970
NOTICE BOARD WITH ALUM. FRAME
C/W 4mm THK. TEMPERED GLASS
(SHALL ALLOW CLEAR MOUNTING
OF POSTERS OF SIZE 940 X 940,
TO BE IN FULL UNOBSTRUCTED
VIEW THROUGH THE FRONT
GLASS PANEL OF 900 X 900)
–2388
2170
2300
–2692
1000
(IP55) LOCATION
CABLING
FFL
6m PVC EARTH BONDING CABLE
6m PVC EARTH
IN 25mm HEAVY DUTY UPVC PIPE
BONDING CABLE IN
25mm HEAVY
DUTY UPVC PIPE
TYPICAL EQUIPOTENTIAL BONDING DETAILS
FOR BUS SHELTER
LTA Endorsement :
Scale 1:50
Project Title :
STANDARD INSTALLATION DETAILS
Drawing Title :
TYPICAL EQUIPOTENTIAL BONDING DETAILS
FOR BUS SHELTER
Designed
NURLY
Scale
1:50
Checked
MALVIN HO
Drawn
JULI
Approved
MELVYN THONG
Date
JULY 2007
Drawing No. :
A
Rev.
DEC 2010
Date
TAY K.C
By
REVISED DETAIL
Description
ADRIAN CHEONG/
HADI WIJAYA
MELVYN
THONG
Chk’d
App’d
Rev.
L/ROAD/MES/SD/1009
CAD File Name:LROADMES-SD1009A.dgn
Sheet
A
1 of 1 A3
2800
2800
370
2060
370
370
2060
WITH MIN. 1mm THK. TOP PANEL TO SO’S APPROVAL
–384
MIN. 10mm THK. ALUM. HONEY COMB ROOF PANEL COMPLETE
WITH MIN. 1mm THK. TOP PANEL TO SO’S APPROVAL
12
´ OF POB DECK
´ OF POB DECK
AND ROOF
AND ROOF
CHS HOT-DIPPED GALVANISED M.S. MEMBER
CHS HOT-DIPPED GALVANISED M.S. MEMBER
TO ENGR’S DETAIL COMPLETE WITH SPRAY
COATING FINISH TO SO’S APPROVAL
MIN. 40
TO ENGR’S DETAIL COMPLETE WITH SPRAY
COATING FINISH TO SO’S APPROVAL
2200
100
1100
2200
FFL OF
POB DECK
TYPICAL CROSS BEAM
700
UPVC PIPE SEALED
WITH APPROVED
SEALANT TO PREVENT
WATER INGRESS
TYPICAL CROSS BEAM
FALL
FALL
TO ENGR’S DETAIL
75
75
TO ENGR’S DETAIL
75
675
MEMBRANE TO SO’S APPROVAL
DETAIL X
150
750
PLANTING TROUGH WITH WATERPROOFING
15
15
150
MEMBRANE TO SO’S APPROVAL
1000 (VARI
ES)
PLANTING TROUGH WITH WATERPROOFING
675
750
855
675
700
FALL
75
1000 (VARI
ES)
BI-METALLIC BOND/CLAMP AND ALUMINIUM CONDUCTOR TAPE
BOLTED ON BEARING PLATE CONCRETE SURFACE
PAINTED OVER TO PREVENT ALUMINIUM TAPE
TO HAVE DIRECT CONTACT WITH CONCRETE SURFACE
(SEE DETAIL X)
100
855
1100
15mm S.S. ROD AT NOT MORE THAN 100mm CLEAR
BI-METALLIC BOND/CLAMP AND ALUMINIUM CONDUCTOR TAPE
BOLTED ON BEARING PLATE CONCRETE SURFACE
PAINTED OVER TO PREVENT ALUMINIUM TAPE
TO HAVE DIRECT CONTACT WITH CONCRETE SURFACE
(SEE DETAIL X)
FALL
BI-METALLIC BOND/CLAMP AND
ALUMINIUM CONDUCTOR TAPE
BOLTED ON BEARING PLATE.
CONCRETE SURFACE PAINTED OVER
TO PREVENT ALUMINIUM TAPE
TO HAVE DIRECT CONTACT
WITH CONCRETE SURFACE
45mm S.S. RAILING
15mm S.S. ROD AT NOT MORE THAN 100mm CLEAR
675
MIN. 40
1800
145
45mm S.S. RAILING
145
MIN. 40
2200
1800
PURPOSE MADE BOND
CONTRACTOR TO ENSURE THAT BONDED
IN ACCORDANCE TO SS 555 REQUIREMENTS
CHS HOT-DIPPED GALVANISED M.S. POST
–2584
–2584
TO ENGR’S DETAIL COMPLETE WITH SPRAY
COATING FINISH TO SO’S APPROVAL
2200
TO ENGR’S DETAIL COMPLETE WITH SPRAY
COATING FINISH TO SO’S APPROVAL
PURPOSE MADE BOND
CONTRACTOR TO ENSURE THAT BONDED
IN ACCORDANCE TO SS 555 REQUIREMENTS
CHS HOT-DIPPED GALVANISED M.S. POST
FFL OF
POB DECK
EQ
MIN. 10mm THK. ALUM. HONEY COMB ROOF PANEL COMPLETE
12
MIN. 40
370
EQ
EQ
–384
EQ
20mm THK PRECASTED GRANOLITHIC
20mm THK PRECASTED GRANOLITHIC
CHIPPING FINISHED TO S.O’S APPROVAL
CHIPPING FINISHED TO S.O’S APPROVAL
625
625
Y
-
25
10x10mm CHAMFER
25
10x10mm CHAMFER
25mm x 3mm
ALUMINIUM TAPE
RC COLUMN TO ENGR’S DETAIL WITH
RC COLUMN TO ENGR’S DETAIL WITH
20mm THK PRECASTED GRANOLITHIC
CHIPPING FINISHED TO S.O’S APPROVAL
20mm THK PRECASTED GRANOLITHIC
CHIPPING FINISHED TO S.O’S APPROVAL
M5 COUNTERSUNK BOLT
NUT INSERT
LIGHTNING
PROTECTION
BI-METALLIC
CONNECTOR
EQ
TEST
EQ
BOX
25mm x 3mm
COPPER TAPE
25
STAINLESS STEEL
COVER PLATE
Y
25mm x 3mm ALUMINIUM CONDUCTOR TAPE
ENCASED IN 50mm HEAVY DUTY UPVC PIPE
ELEVATION VIEW
(WITH COVER)
ELEVATION VIEW
(WITHOUT COVER)
EQ
5700 (MI
N.)
5400 (MI
N.)
25
-
EQ
25mm x 3mm ALUMINIUM CONDUCTOR TAPE
ENCASED IN 50mm HEAVY DUTY UPVC PIPE
25
150mm x 150mm TEST LINK BOX
AT 1500mm HEIGHT FROM
GROUND LEVEL (SURFACE MOUNT)
IN ACCORDANCE TO SS 555 REQUIREMENTS
(SEE TYPICAL LIGHTNING PROTECTION
TEST BOX AT POB)
25
150mm x 150mm TEST LINK BOX
AT 1500mm HEIGHT FROM
GROUND LEVEL (SURFACE MOUNT)
IN ACCORDANCE TO SS 555 REQUIREMENTS
(SEE TYPICAL LIGHTNING PROTECTION
TEST BOX AT POB)
ENCASED HEAVY
DUTY UPVC PIPES
25mm x 3mm
ALUMINIUM TAPE
STAINLESS STEEL
COVER PLATE
BI-METALLIC
CONNECTOR
1700
25mm x 3mm
COPPER TAPE
1500
50mm PVC PIPE FOR LIGHTING CIRCUITS
1700
LTA Endorsement :
R.C. COLUMN
ENCASED HEAVY
DUTY UPVC PIPES
25mm x 3mm COPPER CONDUCTOR TAPE
ENCASED IN 50mm HEAVY DUTY UPVC PIPE
TO OG BOX TO M&E SPECIFICATIONS
1500
25mm x 3mm COPPER CONDUCTOR TAPE
ENCASED IN 50mm HEAVY DUTY UPVC PIPE
SECTION Y-Y
EARTH PIT
(TOTAL EARTH RESISTANCE 10ohms)
R.C. GRATING
FOOTPATH LEVEL
EARTH PIT
(TOTAL EARTH RESISTANCE 10ohms)
FOOTPATH LEVEL
ROAD LEVEL
600
R.C. GRATING
TYPICAL LIGHTNING PROTECTION
TEST BOX AT POB
EARTH ROD
200
TO ROADSIDE DRAIN
600
ROAD LEVEL
EARTH ROD
Project Title :
200
TO ROADSIDE DRAIN
PILE CAP TO ENGR’S DETAIL
STANDARD INSTALLATION DETAILS
PILE CAP TO ENGR’S DETAIL
FOR COVERED POB (NON-EXPRESSWAY)
Drawing Title :
FOR COVERED POB (EXPRESSWAY)
TYPICAL LIGHTNING PROTECTION SYSTEM
FOR COVERED PEDESTRIAN OVERHEAD BRIDGE
Designed
NURLY
A
Rev.
JUNE 2012
Date
CHING
Drawn
By
TO AMEND TO LATEST STANDARD FOR LIGHTNING PROTECTION
HADI
TAY K.C.
WIJAYA
SYSTEM AND REVISED DETAILS.
Description
Designed
By
Chk’d
Checked
MALVIN HO
Scale
Drawn
NTS
JULI
Approved
MELVYN THONG
Date
JULY 2007
Drawing No. :
ADRIAN
CHEONG
Rev.
L/ROAD/MES/SD/1010
A
App’d
CAD File Name:LROADMES-SD1010A.dgn
Sheet
1 of 1 A4
APPLICABLE RANGE 2700 TO 3600
RAILING TO
ENGR’S DETAIL
VARIES DEPEND ON SITE
300
VARIES DEPEND ON SITE
300
300
VARIES DEPEND ON SITE
300
MIN. 10mm THK. ALUM. HONEYCOMB ROOF
PANEL COMPLETE WITH MIN. 1 mm THK
TOP PANEL TO SO’S APPROVAL
BI-METALLIC BOND/CLAMP AND
ALUMINIUM CONDUCTOR TAPE
BOLTED ON BEARING PLATE.
CONCRETE SURFACE PAINTED OVER
TO PREVENT ALUMINIUM TAPE
TO HAVE DIRECT CONTACT
WITH CONCRETE SURFACE
MIN. 10mm THK. ALUM. HONEY
BONDING DETAILS TOCOMB
NEW
ROOF
SPECIALIST
ROOF PANEL
COMPLETE
WITH MIN. 1mm THK. TOP PANEL
REQUIREMENT. CONTRACTOR TO ENSURE
THAT BONDED IN ACCORDANCE TO LATEST SS 555.
TO SO’S APPROVAL
CONVENTIONAL BALLAST
TO SPECIFICATION
LIGHT FITTING TO COMPLY
WITH THE AUTHORITY’S
SPECIFICATIONS
M.S. ’C’ CHANNEL RAFTER TO ENGR’S DETAIL
M.S. ANGLE ROOF FASCIA TO ENGR’S DETAIL
M.S. SUPPORT POST TO ENGR’S DETAIL
ELECTRICAL CABLE CONCEALED IN PVC
FLEXIBLE CONDUIT IN SUPPORT POST
MI
N.2100
MIN.40
12mm THK MS BEARING
PLATE WITH 90 ANGLE
WITH BOLTS/NUTS TO
ENGR’S DETAIL
NEW 45mm S.S. RAILNG COMPLETE WITH
NEW 45mm S.S. RAILNG AND
S.S. FLAT BAR AT REGULAR INTERVAL AND
S.S. ROD AT NOT MORE THAN 100mm CLEAR
HARDRAIL COMPLETE WITH
25 x 3mm ALUMINIUM
TAPE
S.S. FLAT BAR
AT REGULAR
NOT MORE
THAN 100mm CLEAR
BOND TO SUPPORT
POST.
EQ
CONTRACTOR TO ENSURE THAT THE NEW
LIGHTNING PROTECTION SYSTEM FOR
THE NEW COVERED POB AND RAILING ARE
ELECTRICALLY CONTINUOUS.
(REFER TO DETAIL 1)
MI
N.2100
1100
INTERVAL AND S.S. ROD AT
EXISTING POB DECK
EQ
EQ
EQ
1100
FFL
NEW 25mm x 3 mm
ALUMINIUM TAPE
800
DETAIL 1
N.T.S.
EXISTING PLANTING TROUGHS
FFL
EXISTING POB STAIRCASE
& COLUMN
HOT DIP
GALVANISED COVER
TYPICAL SECTION OF POB STAIRCASE
EARTH ROD CLAMP
INCLUSIVE OF LIGHTNING
PROTECTION EARTH LABEL
50
50mm HEAVY
DUTY UPVC PIPES
TO VERIFY ON SITE FOR ACTUAL WIDTH OF STAIRCASE
REFER TO SECTION OF POB DECK FOR ANNOTATION
SCALE 1:20
25mm x 3mm
ALUMINIUM TAPE
GROUND LEVEL
STAINLESS STEEL
COVER PLATE
CONCRETE HAUNCH
ALL AROUND
TYPICAL SECTION OF POB DECK
ROOF EAVE TO EXTEND AT NOT MORE THAN HALF THE WIDTH OF PLANTING TROUGH
TO VERIFY ON SITE FOR ACTUAL WIDTH OF POB DECK
BI-METALLIC
CONNECTOR
25 x 3mm ALUMINIUM TAPE
SCALE 1:20
REFER TO DETAIL ’2’
M.S. SUPPORT POST
EQ
EQ
EQ
45mm S.S. RAILING
TO SO’S APPROVAL
TO SO’S APPROVAL
EQ
25 x 3mm COPPER TAPE ENCASED IN
50mm HEAVY DUTY UPVC PIPE
M.S. SUPPORT POST TO ENGR’S DETAIL
45
50mm HEAVY DUTY UPVC
PIPE C/W 25mm X 3mm
COPPER CONDUCTOR TAPE
30
25mm x 3mm
COPPER TAPE
HEAVY DUTY UPVC PIPE
COUPLING
45mm S.S. HANDRAIL
1100
SPACING OF POSTS AT REGULAR INTERVAL TO ENGR’S DETAIL
TO ENGR’S DETAIL
800
150mm x 150mm TEST LINK BOX
AT 1500mm HEIGHT FROM
GROUND LEVEL (SURFACE MOUNT)
(LATEST SS 555)
ENCASED 50mm HEAVY
DUTY UPVC PIPES
EARTH ROD
(min. 2 Nos. 1.8m LENGTH,
16mm DIA COPPER)
45mm S.S. RAILING
100
EARTH PIT REFER TO DETAIL ’3’
(TOTAL EARTH RESISTANCE <10ohms>
6mm THK S.S. FLAT BAR
15mm S.S. ROD AT NOT MORE THAN
100mm CLEAR TO SO’S APPROVAL
15mm S.S. ROD AT NOT
MORE THAN 100mm CLEAR
855
6mm THK S.S. FLAT BAR TO SO’S APPROVAL
EARTHING ROD
LTA Endorsement :
6mm THK. S.S. FLAT BAR TO BE WELDED
TO S.S. PLATE TO ENGR’S DETAIL
6mm THK S.S. FLAT BAR
DETAIL 3
DETAIL 2
100
1100
GROUND LEVEL
FFL
REFER TO ENGR’S DWG. FOR
MOUNTING DETAILS
TYPICAL LIGHTNING PROTECTION SYSTEM
N.T.S.
N.T.S.
TYPICAL ELEVATION OF RAILING ON POB STAIRCASE
SCALE 1:20
TYPICAL ELEVATION OF RAILING ON POB DECK
FOR NEW ROOF OVER EXISTING PEDESTRIAN
SCALE 1:20
OVERHEAD BRIDGE
Project Title :
SCALE 1 : 50
STANDARD INSTALLATION DETAILS
Drawing Title :
TYPICAL LIGHTNING PROTECTION SYSTEM
FOR NEW ROOF OVER EXISTING PEDESTRIAN
OVERHEAD BRIDGE
Designed
NURLY
Scale
NTS
Checked
MALVIN HO
Drawn
JULI
Approved
MELVYN THONG
Date
JULY 2007
Drawing No. :
A
Rev.
JUNE
2012 DEC
CHING
A
2010
Rev.
Date
Drawn
Date
By
TO AMEND TO LATEST STANDARD FOR LIGHTNING PROTECTION
MELVYN
HADI
ADRIAN
TAY K.C.ADRIAN CHEONG/
TAY K.C
WIJAYA
CHEONG
THONG
HADI WIJAYA
SYSTEM.
By
Description
Description
Designed
By
Chk’d
App’d
Rev.
L/ROAD/MES/SD/1011
CAD File Name:LROADMES-SD1011A.dgn
Sheet
A
1 of 1 A4
750
–81
ALUM. ROOF CAPPING FOR ROOF PANEL
TO MFR’S DETAIL
MIN. 10mm THK. ALUM. HONEYCOMB ROOF PANEL
M.S. ANGLE ROOF FASCIA TO ENGR’S DETAIL
COMPLETE WITH MIN. 1mm THK. TOP PANEL
TO SO’S APPROVAL
PVC CABLE CONCEALED IN PVC COATED
FLEXIBLE STEEL CONDUIT TO M&E DWG. & SPEC.
M.S. ’C’ CHANNEL RAFTER TO ENGR’S DETAIL
G.I. CONDUIT ALONG BACK OF M.S. FASCIA
FOR PVC CABLES TO M&E DWG. & SPEC.
ALUM FLASHING PIECE BOLTED AT BOTH END
LIGHT FITTING TO M&E SPEC & SHALL NOT PROTRUDE FROM M.S. RAFTER /
CONTRACTOR TO PROPOSE FIXING BRACKET FOR LIGHT FITTING
50 x 50 x 3 ALUM ANGLE PLATE
M.S. ANGLE ROOF FASCIA TO ENGR’S DETAIL
M.S. RHS POST @ 3000 mm C/C TO ENGR’S DETAIL
M.S. ’C’ CHANNEL RAFTER TO ENGR’S DETAIL
MIN. 10mm THK. ALUM. HONEYCOMB ROOF PANEL
COMPLETE WITH MIN. 1mm THK. TOP PANEL
TO SO’S APPROVAL
LIGHT FITTING TO M&E SPEC & SHALL NOT PROTRUDE FROM M.S. RAFTER /
CONTRACTOR TO PROPOSE FIXING BRACKET FOR LIGHT FITTING
PVC CABLE CONCEALED IN PVC COATED
FLEXIBLE STEEL CONDUIT IN SUPPORT POST
M.S. RHS POST @ 3000 mm C/C TO ENGR’S DETAIL
ALUM. ROOF CAPPING FOR ROOF PANEL
TO MFR’S DETAIL
750
SECTION C-C
SECTION
C-C
´
M.S. RHS POST @ 3000 mm C/C TO ENGR’S DETAIL
´
PVC COATED FLEXIBLE STEEL CONDUIT
FOR INCOMING CABLES TO M&E DETAIL
LIGHT FITTING TO M&E SPEC
OPENING FOR INCOMING CABLES COVERED
(DESIGN TO REFER TO ARCH DWG)
BY POST CAPPING
(TO BE PROVIDED AT 1ST & LAST POST ONLY)
SECTION B-B
SECTION J-J
TYPICAL LONGITUDINAL CROSS SECTION AT ROOF WITH LEVEL DIFFERENCE
TYPICAL LONGITUDINAL CROSS SECTION AT ROOF WITH LEVEL DIFFERENCE
A
Qualified Person Endorsement :
K
MIN. 10mm THK. ALUM. HONEYCOMB ROOF
-
PANEL COMPLETE WITH MIN. 1mm THK.
TOP PANEL TO SO’S APPROVAL
300
S/S SCREW
S/S SCREW
MIN. 10mm THK. ALUM. HONEYCOMB ROOF PANEL COMPLETE
C
WITH MIN. 1mm THK.TOP PANEL TO SO’S APPROVAL
-
3 FALL
ISOLATOR / BONDING TAPE BETWEEN
ALUM. ROOF FRAME & M.S. MEMBER
ISOLATOR / BONDING TAPE BETWEEN
ALUM. ROOF FRAME & M.S. MEMBER
3
Y
-
150
LTA Endorsement :
3
BONDING DETAILS TO
ROOF SPECIALIST’S REQUIREMENTS.
M8 COPPER BOLT
TO STEEL SUPPORT POST
K
-
25mm x 3mm COPPER TAPE
LIGHT FITTING TO M&E SPEC & SHALL NOT PROTRUDE FROM M.S. RAFTER /
C
CONTRACTOR TO PROPOSE FIXING BRACKET FOR LIGHT FITTING
-
STEEL SUPPORT POST
G.I. CONDUIT ALONG BACK OF M.S. FASCIA
FOR PVC CABLES TO M&E DWG. & SPEC.
PVC CABLE CONCEALED IN PVC COATED
FLEXIBLE STEEL CONDUIT IN SUPPORT POST
Y
-
M.S. RHS POST @ 3000 mm C/C TO ENGR’S DETAIL
SECTION Y-Y
M.S. ’C’ CHANNEL RAFTER @ 3000 mm C/C TO ENGR’S DETAIL
2100 (MI
N.) (NTS)
750
DETAIL X
1500
DETAIL 1
ALUM. ROOF CAPPING FOR ROOF PANEL TO MFR’S DETAIL
Project Title :
GASKET
´
´
M.S. ANGLE ROOF FASCIA
PVC CABLE + 2.5m EARTH CABLE
IN PVC COATED FLEXIBLE STEEL CONDUIT
MIN. 10mm THK. ALUM. HONEYCOMB ROOF PANEL
COMPLETE WITH MIN. 1mm THK. TOP PANEL
TO SO’S APPROVAL
TO ENGR’S DETAIL
TERMINAL BLOCK CONNECTOR
MOUNTED ON TEAKWOOD BLOCK
STANDARD INSTALLATION DETAILS
TEAKWOOD FOR MOUNTING
OPENING FOR INCOMING CABLES COVERED
SEE DETAIL X
BY POST CAPPING
(TO BE PROVIDED AT 1ST & LAST POST ONLY)
B
B
40
-
FLAT BAR TO SUPPORT TEAKWOOD BLOCK
-
CABLE GLAND FOR ARMOURED CABLE
100
ISOLATOR / BONDING TAPE BETWEEN
M.S. ANGLE ROOF FASCIA
ALUM. ROOF FRAME & M.S. MEMBER
TO ENGR’S DETAIL
100
40
MS RHS TO ENGR’S DETAIL
FFL
10
500
EARTH PIT
FOR LIGHTNING
PROTECTION SYSTEM
(TOTAL EARTH
RESISTANCE
<10 ohms)
C1 WELDED ALL-ROUND TO
300x300x20 THK MS PLATE
Drawing Title :
LIGHT FITTING MOUNTING BRACKET TO CONTRACTOR PROPOSAL
10mm THK NON SHRINK GROUT
M.S. ’C’ CHANNEL RAFTER TO ENGR’S DETAIL
TYPICAL CABLE ENTRY DETAIL AND
LIGHT FITTING TO M&E SPEC. & SHALL NOT PROTRUDE FROM M.S. RAFTER /
LIGHTNING PROTECTION SYSTEM
CONTRACTOR TO PROPOSE FIXING BRACKET FOR LIGHT FITTING
FOR SINGLE POST COVERED LINKWAY
SECTION K-K
Scale 1:5
25mm x 3mm
COPPER TAPE
IN 50mm HEAVY DUTY
UPVC PIPE
Designed
REF. DWG. NO. L/STLLW/AR/STD/1002
CONC. SLAB TO ENGR’S DTL COMPLETE WITH
20mm THK GRANOLITHIC FINISHES TO SO’S APPROVAL
SALIM
Checked
ADRIAN CHEONG/
MALVIN HO
Approved
MELVYN THONG
RC FOOTING TO ENGR’S DETAIL
Scale
MS BASE PLATE TO ENGR’S DETAIL
ARMOURED CABLE IN 100mm HEAVY DUTY UPVC PIPE
N.T.S.
Drawn
JULI
Date
JAN 2010
FROM OG BOX TO FIRST LIGHTING POINT
Drawing No. :
1. INCLUSION OF TAXI STAND OG-BOX REQUIREMENT.
A
JUNE 2012
CHING
2.AMENDMENT TO LIGHTNING PROTECTION SYSTEM.
ANGELINE
TYPICAL CROSS SECTION FOR SINGLE POST COVERED LINKWAY
Rev.
Date
Drawn
By
Description
Designed
By
HADI
WIJAYA
ADRIAN
CHEONG
Chk’d
App’d
Rev.
L/ROAD/MES/SD/1012
CAD File Name :LROADMES-SD1012A.dgn
Sheet
A
1 of 1
A4
BONDING TO UPPER ROOF
LIGHTNING PROTECTION SYSTEM
(BONDING DETAILS TO ROOF
SPECIALIST’S REQUIREMENTS)
SEE DETAIL 1
3
5
4
6
7
8
9
750
750
3000
3000
3000
3000
3000
1500
BONDING DETAILS TO
ROOF SPECIALIST’S
REQUIREMENTS
SEE DETAIL 1
1500
750
1500
1500
1500
1500
1500
ALUM FLASHING PIECE
BONDING TO
STRUCTURE COLUMN
(MIN 150mm ABOVE
FLOOR LEVEL)
SEE DETAIL 2
M.S. RHS POST TO ENGR’S DETAIL
M.S. RHS POST TO ENGR’S DETAIL
1200
–2352
M.S. ANGLE ROOF FASCIA
FFL
EARTH
PIT
150
FFL
EARTH
PIT
FFL
BONDING TO STRUCTURE
COLUMN (MIN 150mm
ABOVE FLOOR LEVEL)
SEE DETAIL 2
–2107
PANEL TO MFR’S DETAIL
2100
(MI
N.2100 CLEAR)
2100 (MI
N.)
L/ER187/AR/TD/3006
ALUM. ROOF CAPPING FOR ROOF
(CLEAR)
EARTH
PIT
1500
E
TOP PANEL TO SO’S APPROVAL
TO ENGR’S DETAIL
OG BOX
1500
–2352
PANEL COMPLETE WITH MIN. 1mm THK.
820
–2107
SEE DETAIL 2
1500
–81
1500
MIN. 10mm THK. ALUM. HONEY COMB ROOF
M.S. ANGLE ROOF FASCIA
TO ENGR’S DETAIL
200
750
–81
(MI
N.2100 CLEAR)
–245
BONDED TO
EXISTING
STRUCTURE
1500
–2107
1500
3000
750
1500
750
BONDING DETAILS TO
ROOF SPECIALIST’S
REQUIREMENTS
SEE DETAIL 1
10
3000
–245
2
(MI
N.2100 CLEAR)
1
SEE DETAIL 3
SEE DETAIL 3
OG BOX ON CONC. PLINTH TO M&E DTLS
(LOCATION TO BE DETERMINED ON SITE &
FRONT ELEVATION
WITH LEVEL DIFFERENCE
FRONT ELEVATION (LIGHTNING
PROTECTION
SYSTEM SHALL BE APPLIED FOR ALL TYPE OF LINKWAY)
TO POWERGRID’S APPROVAL)
Scale 1:50
Scale 1:100
1
2
750
1500
BONDING DETAILS TO
ROOF SPECIALIST’S
REQUIREMENTS
SEE DETAIL 1
1500
1500
1500
6
3000
1500
1500
7
3000
1500
1500
3000
1500
1500
750
1500
BONDING DETAILS TO
ROOF SPECIALIST’S
REQUIREMENTS
SEE DETAIL 1
PANEL COMPLETE WITH MIN. 1mm THK.
TOP PANEL TO SO’S APPROVAL
–245
ALUM. ROOF CAPPING FOR ROOF
PANEL TO MFR’S DETAIL
200
M.S. ANGLE ROOF FASCIA
820
TO ENGR’S DETAIL
(CLEAR)
2100 (MI
N.)
BONDING TO STRUCTURE COLUMN
(MIN 150mm ABOVE FLOOR LEVEL)
SEE DETAIL 2
M.S. RHS POST TO ENGR’S DETAIL
OG BOX
150
1200
(MI
N.2100 CLEAR)
5
3000
MIN. 10mm THK. ALUM. HONEY COMB ROOF
–2107
–2352
4
3000
1500
BONDING TO STRUCTURE COLUMN
(MIN 150mm ABOVE FLOOR LEVEL)
SEE DETAIL 2
3
3000
EARTH
PIT
SEE DETAIL 3
FFL
OG BOX ON CONC. PLINTH TO M&E DTLS
EARTH
PIT
(LOCATION TO BE DETERMINED ON SITE &
TO POWERGRID’S APPROVAL)
FRONT
ELEVATION
1 (WITHOUT
LEVEL DIFFERENCE)
FRONT
ELEVATION
1
SEE DETAIL 3
Scale
1:50
Scale 1:100
E
-
HOT DIP
GALVANISED COVER
H
EARTH ROD CLAMP
INCLUSIVE OF LIGHTNING
PROTECTION EARTH LABEL
50
-
ALUMINIUM TAPE
GROUND LEVEL
M8 STAINLESS STELL BOLT
B-BOND
BI-METALLIC
CONNECTOR
CONCRETE HAUNCH
ALL AROUND
M8 ALUMINIUM COPPER BOLT
TO STEEL SUPPORT POST
LTA Endorsement :
M8 COPPER BOLT
25mm x 3mm COPPER TAPE
COPPER TAPE
B-BOND
ALUMINIUM OR
LIGHTNING PROTECTION SYSTEM LAYOUT
PLAN
STEEL SUPPORT POST
COUPLING
50mm HEAVY DUTY UPVC
PIPE C/W 25mm X 3mm
COPPER CONDUCTOR TAPE
Scale 1:50
ALUMINIUM OR STEEL
SUPPORT POST
EARTH ROD
Project Title :
(min. 2 Nos. 1.8m LENGTH,
16mm DIA COPPER)
H
STANDARD INSTALLATION DETAILS
-
E
-
SECTION H-H
SECTION E-E
DETAIL 1
ELEVATION OF BONDING FROM
ROOF TO STEEL SUPPORT POST
Scale: N.T.S.
DETAIL 2
TYPE 1 - ELEVATION OF LIGHTNING
BONDING TO STEEL SUPPORT POST
DETAIL 3
Scale: N.T.S.
Drawing Title :
Scale: N.T.S.
TYPICAL LIGHTNING PROTECTION SYSTEM
FOR COVERED LINKWAY
Scale: N.T.S.
Scale: N.T.S.
Designed
NURLY
0 0.5
1 1.5
2
3
4
5 Metres
Checked
MALVIN HO
Scale
Drawn
1:100
JULI
Approved
MELVYN THONG
Date
JULY 2007
Drawing No. :
A
DEC 2010
TAY K.C
REVISED DETAILS
Scale 1:100
Rev.
Date
By
Description
ADRIAN CHEONG/
HADI WIJAYA
MELVYN
THONG
Chk’d
App’d
Rev.
L/ROAD/MES/SD/1014
CAD File Name:LROADMES-SD1014A.dgn
Sheet
A
1 of 1 A3
LIGHT FIXTURE TO M&E SPECIFICATION
LIGHT FIXTURE TO M&E SPECIFICATION
2800
370
2800
2060
EQ
370
370
1
2
145
675
2200
700
100
WEATHERPROOF
JUNCTION BOX
150
75
675
150
750
100
900 (VARI
ES)
750
MIN. 40
1800
855
1100
700
75
2200
75
15
MIN. 40
2200
145
1100
MIN. 40
855
675
75
1800
–2584
PVC CABLE IN PVC COATED
FLEXIBLE CONDUIT FOR LIGHTING
MIN. 40
675
EQ
–384
–384
1
2
2200
–2584
370
EQ
PVC CABLE IN PVC COATED
FLEXIBLE CONDUIT FOR LIGHTING
900 (VARI
ES)
2060
EQ
END OF POB
15
625
CABLES IN PIPE SLEEVE
625
25
WEATHERPROOF
JUNCTION BOX
25
PVC CABLE
IN GI CONDUIT
EQ
EQ
WEATHERPROOF
JUNCTION BOX
25
25
EQ
5680 (MI
N.5400)
25
EQ
5680 (MI
N.5400)
25
PVC CABLE IN
100mm HD uPVC PIPE
ENCASED IN COLUMN
ARMOURED CABLE IN 100mm
H.D uPVC PIPE FROM OG BOX
1500
1000
MI
N.300
Project Title :
200
ROAD LEVEL
200
FOOTPATH LEVEL
ROAD LEVEL
600
FOOTPATH LEVEL
600
1700
1500
1000
1700
MI
N.300
LTA Endorsement :
STANDARD INSTALLATION DETAILS
ARMOURED CABLE IN 100mm
H.D uPVC PIPE FROM OG BOX
Drawing Title :
TYPICAL LIGHTING SYSTEM
FOR NEW COVERED POB
TYPICAL LIGHTING SYSTEM FOR NEW POB
TYPICAL LIGHTING SYSTEM
AND NEW ROOF OVER EXISTING POB
FOR NEW ROOF OVER EXISTING POB
Designed
TAY K.C
SCALE 1 : 50
SCALE 1 : 50
0
0.5
1
1.5
2
Scale
1:50
2.5 Metres
Checked
ADRIAN CHEONG/
HADI WIJAYA
Drawn
CNV
Approved
MELVYN THONG
Date
NOV 2010
Drawing No. :
Rev.
L/ROAD/MES/SD/1015
Scale 1:50
Rev.
Date
By
Description
Chk’d
App’d
CAD File Name:LROADMES-SD1015-.dgn
Sheet
-
1 of 1 A3
LEGEND:
COLUMN MOUNTED
LIGHT FITTING TO M&E
SPECIFICATION
COLUMN MOUNTED
LIGHT FITTING
PROPOSED HIGH COVERED LINKWAY
2400
4200
-
5400
600
A
CONNECT TO
LINKWAY
LIGHTINGS
COLUMN MOUNTED
LIGHT FITTING
PROPOSED LOCATION OF
ALUM WEATHER SHIELD
600
CONNECT TO
LINKWAY
LIGHTINGS
16200
ROOF PLAN (HIGH COVERED LINKWAY)
Scale: N.T.S.
COLUMN MOUNTED
LIGHT FITTING
COLUMN MOUNTED
LIGHT FITTING
5400
600
4200
600
PROPOSED HIGH COVER LINWAY CURVED
ROOF TO HAVE THE SAME RADIUS AS
THE 2.4m WIDE COVERED LINKWAY
COLUMN MOUNTED
LIGHT FITTING
LTA Endorsement :
COLUMN MOUNTED
LIGHT FITTING
MI
N.5400
ISOMETRIC VIEW
PROPOSED ALUM WEATHER SHIELD AT BOTH
END OF HIGH COVER LINKWAY
PVC CABLE IN
100mm HD uPVC PIPE
ENCASED IN COLUMN
3400
PVC CABLE IN
100mm HD uPVC PIPE
ENCASED IN COLUMN
COLUMN MOUNTED
LIGHT FITTING
2400
PROPOSED 2.4m WIDE COVERED LINKWAY
Project Title :
PVC CABLE IN
100mm HD uPVC PIPE
ENCASED IN COLUMN
JUNCTION BOX
JUNCTION BOX
STANDARD INSTALLATION DETAILS
ARMOURED CABLE IN 100mm
H.D uPVC PIPE FROM OG BOX
Drawing Title :
SECTION A-A
TYPICAL LIGHTING SYSTEM FOR
HIGH COVERED LINKWAY
Scale: N.T.S.
FRONT VIEW
SIDE VIEW
Designed
TAY K.C
Scale
TYPICAL COLUMN MOUNTED LIGHT FITTING
NTS
Checked
ADRIAN CHEONG/
HADI WIJAYA
Drawn
JULI
CNV
Approved
MELVYN THONG
Date
NOV 2010
Drawing No. :
Scale: N.T.S.
ADRIAN CHEONG/
HADI WIJAYA
Rev.
Date
By
Description
Chk’d
Rev.
L/ROAD/MES/SD/1016
App’d
CAD File Name:LROADMES-SD1016-.dgn
Sheet
-
1 of 1 A3
LEGEND:
EARTH PIT
(TOTAL RESISTANCE < 10ohm)
(LOCATION TO BE DETERMINED
ON SITE & TO SO APPROVAL)
EARTH PIT
(TOTAL RESISTANCE < 10ohm)
(LOCATION TO BE DETERMINED
ON SITE & TO SO APPROVAL)
600
A
EARTH PIT
-
DC
DC
DC
DOWN CONDUCTOR
BONDING
5400
4200
BONDING
2400
PROPOSED HIGH COVERED LINKWAY
PROPOSED LOCATION OF
ALUM WEATHER SHIELD
600
BONDING
16200
ROOF PLAN (HIGH COVERED LINKWAY)
E
-
Scale: N.T.S.
5400
600
4200
600
PROPOSED HIGH COVER LINWAY CURVED
ROOF TO HAVE THE SAME RADIUS AS
THE 2.4m WIDE COVERED LINKWAY
BONDING DETAILS TO ROOF
SPECIALIST’S REQUIREMENT
ALUMINIUM TAPE
M8 STAINLESS STELL BOLT
BI-METALLIC
CONNECTOR
PROPOSED ALUM WEATHER SHIELD AT BOTH
END OF HIGH COVER LINKWAY
SEE DETAIL 1
M8 COPPER BOLT
MI
N.5400
SEE DETAIL 1
COPPER TAPE
B-BOND
BONDING DETAILS TO ROOF
SPECIALIST’S REQUIREMENT
2400
SEE DETAIL 2
ALUMINIUM OR STEEL
SUPPORT POST
PROPOSED 2.4m WIDE COVERED LINKWAY
E
EARTH PIT
-
SECTION A-A
Scale: N.T.S.
SEE DETAIL 3
SECTION E-E
DETAIL 1
ELEVATION OF BONDING FROM ROOF TO
STEEL SUPPORT POST
H
Scale: N.T.S.
-
Scale: N.T.S.
HOT DIP
GALVANISED COVER
LTA Endorsement :
EARTH ROD CLAMP
INCLUSIVE OF LIGHTNING
PROTECTION EARTH LABEL
50
B-BOND
M8 ALUMINIUM COPPER BOLT
TO STEEL SUPPORT POST
GROUND LEVEL
CONCRETE HAUNCH
ALL AROUND
25mm x 3mm COPPER TAPE
Project Title :
ALUMINIUM OR
STEEL SUPPORT POST
STANDARD INSTALLATION DETAILS
H
-
SECTION H-H
DETAIL 2
TYPE 1 - ELEVATION OF LIGHTNING
BONDING TO STEEL SUPPORT POST
Scale: N.T.S.
COUPLING
50mm HEAVY DUTY UPVC
PIPE C/W 25mm X 3mm
COPPER CONDUCTOR TAPE
Drawing Title :
TYPICAL LIGHTNING PROTECTION SYSTEM FOR
HIGH COVERED LINKWAY
EARTH ROD
(min. 2 Nos. 1.8m LENGTH,
16mm DIA COPPER)
Designed
TAY K.C
Scale
NTS
Checked
ADRIAN CHEONG/
HADI WIJAYA
Drawn
CNV
Approved
MELVYN THONG
Date
NOV 2010
Drawing No. :
Scale: N.T.S.
DETAIL 3
Scale: N.T.S.
THONG
Rev.
Date
By
Description
Chk’d
App’d
Rev.
L/ROAD/MES/SD/1017
CAD File Name:LROADMES-SD1017-.dgn
Sheet
-
1 of 1 A3
4.5mm ALUMINIUM CHEQUERED PLATE
WITH RETRACTABLE HANDLE
UNDERGROUND PIPE
WITH HAUNCH END
GROUND LEVEL
50
2800
300
50
QUICK RELEASE COUPLING FOR
EQ
FOR INFORMATION ONLY
Rev.
Description
By
Chk’d
WATER WAGON CONNECTION
OVERFLOW PIPE TO
NEAREST OPEN DRAIN
UNDERGROUND PIPE
1
2
–384
Date
OVERFLOW PIPE TO
300
EQ
370
400
2060
50
38mm (1INCH)
370
WITH HAUNCH END
X
1000
NEAREST OPEN DRAIN
-
50
COUPLING INLET
STAINLESS STEEL OR
MIN. 40
145
1800
675
HOT-DIPPED GALVANISED
*25mm STAINLESS STEEL PIPE WITH
*3mm HOLES AT 400mm APART
CENTRE TO CENTRE ALONG THE
BOTTOM OF THE PIPE AND SHOULD
BE FIXED TO THE INNER WALL OF
THE PLANTER TROUGH THAT ABUT THE
PLATFORM AND ABOVE THE SOIL LEVEL
2200
CONCRETE FILLED
32mm STAINLESS STEEL PIPE
PIPING SUPPORTS
DETAIL A
SECTION X-X
SCALE NTS
SCALE NTS
700
END CAP
END CAP
3mm HOLE
100
75
3mm HOLE
NOTE:
400mm
75
400mm
1. NUMBER OF HOLES SHOWN ARE INDICATIVE ONLY (NOT ACTUAL NUMBER).
150
675
750
900 (VARI
ES)
MIN. 40
855
1100
2200
–2584
CONCRETE FILLED
15
625
25mm STAINLESS STEEL PIPE
25mm STAINLESS STEEL PIPE
WITH 3mm HOLES AT
WITH 3mm HOLES AT
400mm APART C/C ALONG
400mm APART C/C ALONG
THE BOTTOM OF THE PIPE
25
THE BOTTOM OF THE PIPE
END CAP
END CAP
SHOULD BE FIXED TO THE
SHOULD BE FIXED TO THE
INNER WALL OF THE TROUGH
INNER WALL OF THE TROUGH
THAT ABUTS THE PLATFORM
THAT ABUTS THE PLATFORM
AND ABOVE THE SOIL LEVEL
EQ
AND ABOVE THE SOIL LEVEL
38mm (1INCH)
QUICK RELEASE COUPLING
FOR WATER WAGON
CONNECTION
(UNDERGROUND)
B
*32mm STAINLESS
STEEL PIPE
*32mm STAINLESS
STEEL PIPE
*32mm STAINLESS STEEL PIPE RISER
*32mm STAINLESS STEEL PIPE RISER
5680 (MI
N.5400)
25
-
ISOLATION VALVE AT
ISOLATION VALVE AT
1500mm ABOVE GROUND
1500mm ABOVE GROUND
38mm (1 1/2 INCH)
QUICK RELEASE COUPLING
FOR WATER WAGON
CONNECTION
AT 1000mm
ABOVE GROUND
*32mm STAINLESS
STEEL PIPE RISER
ISOMETRIC DIAGRAM WITH
SURFACE COUPLING INLET
EQ
32mm STAINLESS STEEL PIPE
BURIED UNDERGROUND
SCALE NTS
ISOMETRIC DIAGRAM WITH
UNDERGROUND COUPLING INLET
SCALE NTS
25
2 NOS. OF ISOLATION VALVE
FOR 2 NOS. OF EXPOSED *32mm
STAINLESS STEEL PIPE AT
1500mm ABOVE GROUND
Qualified Person Endorsement :
32mm STAINLESS STEEL PIPE
ISOLATION VALVE AT 1500mm
ABOVE GROUND
2 NOS. *32mm STAINLESS
STEEL PIPE RISER
R.C. COLUMN
1000
50
200
FOOTPATH LEVEL
EXISTING ROAD LEVEL
FACING ROAD
200
150
80
2000
600
200
600
SEE DETAIL A
EXISTING GROUND LEVEL
250 x 250 HANDICAPPED SIGN
FACING PAVEMENT
ROAD LEVEL
LTA Endorsement :
COUPLING INLET
1500
1000
1700
MI
N.300
2000
Project Title :
TYPICAL LAYOUT COUPLING INLET AT 1000mm ABOVE GROUND
SCALE NTS
STANDARD INSTALLATION DETAILS
NOTE : FOR LESS THAN 8m RADIUS FROM COLUMN OF POB TO THE MIDPOINT
OF LAYBY SUBJECT TO APPROVAL BY NATIONAL PARKS BOARD
*32mm STAINLESS STEEL
PIPE BURIED UNDERGROUND
Drawing Title :
*50mm GALVANISED
STEEL PIPE SLEEVE
TYPICAL IRRIGATION INSTALLATION DETAILS
AND SECTIONS FOR NEW POB
TYPICAL SECTION OF PEDESTRIAN OVERHEAD BRIDGE
SECTION A - A
Designed
Checked
SECTION B-B
VERON
LIM KWEE CHEW /
TAN BOON TONG
SCALE 1:20
Scale
Drawn
SCALE 1 : 20
NOTE : FOR MORE THAN 8m RADIUS FROM COLUMN AT POB TO THE MIDPOINT
OF LAYBY SUBJECT TO APPROVAL BY NATIONAL PARKS BOARD
AS SHOWN
CNV
Approved
MELVYN THONG
Date
JAN 2011
Drawing No. :
Rev.
-
L/ROAD/MES/SD/2001
FOR INFORMATION ONLY
Rev.
Date
By
Description
Chk’d
App’d
CAD File Name :LROADMES-SD2001-.dgn
Sheet
1 of 1
A1