2014351 EstellADD2 Plans

advertisement
OHW
(908) 232 - 1232
AERIAL ELECTRIC CONDUCTORS
NEW POLE
OHW
NEW POLE
Garden State Underground
Utility Locator Service
NEW JERSEY
CITY OF ESTELL MANOR
PARTNER: GERALD S. BLACKMAN, AIA, PP, NCARB
ASSOCIATE: STEVEN J. BOLOGNO, RA
ATLANTIC COUNTY,
ESTELL MANOR PARK MANSION
VETERANS MUSEUM
GERALD S. BLACKMAN,
AIA, PP, NCARB
N.J. LIC. No. A1 17113
SITE ELECTRICAL PLAN
SCALE: 1" = 20'-0"
210 E. STREET ROAD
TELE # (215)322-7711
SUITE 2D
FAX # (215)322-7709
FEASTERVILLE, PA 19053
HOLSTEIN WHITE, INC.
1
CONSULTING ENGINEERS
OHW
EXISTING UTILITY POLE
PRINCIPAL: DANIEL A. SHOUSKY AIA, PP, NCARB
PRINCIPAL: PAUL A. KISS AIA, PP, NCARB
ELBA-6
CALL BEFORE YOU DIG !
NEW JERSEY STATUTE 2C:17-5 OF 1979
REQUIRES (3) WORKING DAYS NOTICE FOR
CONSTRUCTION PHASE AND (5) WORKING
DAYS IN DESIGN STAGE -- STOP CALL
FOUNDER: JOHN J. OLIVIERI (1956-1999)
WP
UNDERGROUND ELECTRIC CONDUCTORS
PROPOSED 10,000 GAL.
8' DIA. x 31'-6 1/2" Long
UNDERGROUND WATER
STORAGE TANK FOR
FIRE SUPPRESSION
WATER WELL
17 WEST KNIGHT AVENUE, SUITE 200, COLLINGSWOOD, NEW JERSEY 08108
PHONE: (856) 854-0580
FAX: (856) 854-0993
Vestibule
OHW
OHW
WELL PUMP, FIELD VERIFY
TERMINATION LOCATION
AND ELETRICAL
CHARACTERISTICS PRIOR
TO ROUGHPROPOSED
-IN
POTABLE
ARCHITECTS AND PLANNERS
www.olivieriarchitects.com
PROPOSED
500 G.P.D.
SEPTIC FIELD
BSMT.
ENT.
OSK Design Partners P.A.
OIL TANK
EXISTING
MANOR HOUSE
THIS PLAN IS NOT VALID UNLESS A RAISED SEAL IS AFFIXED HERETO
TANK
OHW
BRICK WALL
ROUTE GENERATOR
CONDUCTORS
UNDERGROUND TO
CRAWLSPACE
SEE NOTE #11
HWAY
IG
H
E
T
A
T
S
Y
E
S
NEW JER
#50
OHW
NATURAL GAS GENERATOR
MOUNTED ON CONCRETE
FOUNDATION, VERIFY
FINAL LOCATION WITH
OWNER AND ARCHITECT
PRIOR TO ROUGH-IN
PLAN IS DIAGRAMMATIC ONLY. VERIFY EXACT
LOCATIONS OF ALL EQUIPMENT AND SITE WORK
WITH OWNER, ARCHITECT, AND CIVIL ENGINEER
PRIOR TO COMMENCING WORK.!
!
CONTRACTOR SHALL BE RESPONSIBLE FOR
COORDINATION OF UNDERGROUND SERVICES
WITH OTHER CONTRACTORS AND UTILITY
COMPANIES.!
!
EXACT ROUTING AND TERMINATION POINTS OF
UNDERGROUND SERVICES SHALL BE VERIFIED
WITH THE UTILITY COMPANY AND OTHER
CONTRACTORS.!
!
IN ADDITION TO THE LENGTH SHOWN, THE
CONTRACTOR SHALL PROVIDE A UNIT PRICE PER
25'-0" OF RUN FOR SECONDARY ELECTRIC
SERVICE CONDUITS, RELATED TRENCHING, AND
BACKFILL.!
!
COORDINATE FINAL INTERCONNECTIONS TO EACH
UTILITY COMPANY, PROVIDE ALL MATERIALS AND
LABOR REQUIRED FOR SERVICE CONNECTIONS IN
ACCORDANCE WITH EACH UTILITY (POWER AND
COMMUNICATIONS) COMPANY SERVICE
STANDARDS. !
!
POSITION OUTDOOR FIXTURES, TYPE 'M1' AT
NIGHT TO ILLUMINATE TARGET AREA OF RANGE.
FIXTURE AIMING SHALL BE TO SATISFACTION OF
OWNER.!
!
UNLESS OTHERWISE NOTED, UNDERGROUND
ELECTRICAL AND COMMUNICATIONS CONDUITS
SHALL BE 24" MINIMUM BELOW GRADE.
UNDERGROUND CONDUITS SHALL BE SCHEDULE
40 PVC.!
!
PROVIDE, IN TRENCH CONTAINING ELECTRIC AND
COMMUNICATION DUCT SYSTEMS, AN
UNDERGROUND UTILITY MARKING TAPE. TAPE
SHALL BE BURIED 1 FOOT BELOW GRADE AND RUN
CONTINUOUS THE ENTIRE LENGTH OF DUCT
TRENCH. TAPE SHALL BE BRIGHTLY COLORED
RED POLYETHYLENE LONG LIFE TYPE WITH
PRINTED WARNING TO READ "CAUTION, BURIED
ELECTRIC LINE BELOW". !
!
PROVIDE ALL REQUIRED EXCAVATION TRENCHING,
BACKFILLING, COMPACTING IN ACCORD WITH THIS
DIVISION. !
!
PROVIDE APPROVED GROUNDING CONDUCTOR IN
ALL CONDUIT.!
!
IN ADDITION TO UNDERGROUND POWER
CONDUITS REQUIRED PER GENERATOR
MANUFACTURER. PROVIDE THE FOLLOWING
UNDERGROUND CONDUITS BETWEEN GENERATOR
ENCLOSURE AND BUILDING; (1) 1” CONDUIT FOR
BLOCK HEATER AND BATTERY CHARGER
CIRCUITS, (1) 1” CONDUIT FOR ANNUNCIATOR
CABLES AND ATS GENERATOR CONTROL WIRING.
SITE ELECTRICAL PLAN
SITE ELECTRICAL NOTES
1.!
!
!
!
!
2.!
!
!
!
!
3.!
!
!
!
!
4.!
!
!
!
!
!
5.!
!
!
!
!
!
!
6.!
!
!
!
!
7.!
!
!
!
!
!
8.!
!
!
!
!
!
!
!
!
!
9.!
!
!
!
10.!
!
!
11.
Jeffrey E. Holstein, P.E.
License No. NJ GE46443
Authorization NO; 2GA28143700
REVISIONS:
ADDEDUM #1 7-1-2014
DATE:
7-1-2014
SCALE:
AS NOTED
DRAWN BY: JAC
CHK'D BY:
ISSUED TO ATLANTIC COUNTY FOR REVIEW
1
06-21-2013
DRAWING ISSUE
No.
DATE
JEH
PROJECT No.
DA09057
E0.1
UH
1
D
C
C
PE
FS
FS
FS
C
C
C
TS
TS
TS
FIRE PUMP CONTROL PANEL SHALL!
BE INTERCONNECTED TO THE FIRE!
ALARM SYSTEM FOR THE FOLLOWING:!
PUMP RUNNING, PHASE LOSS, AND PHASE REVERSAL
53
23
D
D
PE
UH
1
PE
BASEMENT
WATER SOFTENER
001
61
49
D
TELECOM EQUIPMENT; PROVIDE!
3/4" X 8' X 4' PLYWOOD BACKBOARD
PE
NEW JERSEY
CITY OF ESTELL MANOR
ESTELL MANOR PARK MANSION
VETERANS MUSEUM
ATLANTIC COUNTY,
PARTNER: GERALD S. BLACKMAN, AIA, PP, NCARB
ASSOCIATE: STEVEN J. BOLOGNO, RA
PRINCIPAL: DANIEL A. SHOUSKY AIA, PP, NCARB
PRINCIPAL: PAUL A. KISS AIA, PP, NCARB
C
002
003
FOUNDER: JOHN J. OLIVIERI (1956-1999)
BASEMENT
CRAWLSPACE
17 WEST KNIGHT AVENUE, SUITE 200, COLLINGSWOOD, NEW JERSEY 08108
PHONE: (856) 854-0580
FAX: (856) 854-0993
VERIFY QUANTITY AND LOCATIONS!
OF FLOW AND TAMPER SWITCHES!
WITH FIRE SUPPRESSION VENDOR
ARCHITECTS AND PLANNERS
www.olivieriarchitects.com
PE
PE
OSK Design Partners P.A.
004
D
FIELD VERIFY LOCATION OF ALL WIRING DEVICES
WITH ARCHITECT PRIOR TO ROUGH-IN.!
!
COORDINATE INSTALLATION OF HVAC EQUIPMENT
WITH MECHANICAL CONTRACTOR. INSTALL AND
WIRE DISCONNECT SWITCHES FURNISHED BY
MECHANICAL CONTRACTOR.!
!
UNLESS OTHERWISE NOTED, ALL POWER SHALL
BE CIRCUITED TO PANEL 'ABB'.
THIS PLAN IS NOT VALID UNLESS A RAISED SEAL IS AFFIXED HERETO
CRAWLSPACE
D
BASEMENT - POWER PLAN
DRAWING NOTES
1.!
!
!
2.!
!
!
!
!
3.
GERALD S. BLACKMAN,
AIA, PP, NCARB
N.J. LIC. No. A1 17113
UC
CRAWLSPACE
005
PROVIDE (2) 2" PVC C. TO TELECOM UTILITY
TERMINATION POINT, COORDINATE LOCATION,
ROUTING, AND REQUIREMENTS WITH OWNERS
PHONE/DATA DESIGNER
210 E. STREET ROAD
TELE # (215)322-7711
SUITE 2D
FAX # (215)322-7709
FEASTERVILLE, PA 19053
HOLSTEIN WHITE, INC.
F
23
CONSULTING ENGINEERS
F F
21
Jeffrey E. Holstein, P.E.
License No. NJ GE46443
Authorization NO; 2GA28143700
REVISIONS:
1
BASEMENT - !
POWER PLAN
SCALE: 1/4" = 1'-0"
DATE:
7-1-2014
SCALE:
AS NOTED
DRAWN BY: JAC
CHK'D BY:
ISSUED TO ATLANTIC COUNTY FOR REVIEW
1
06-21-2013
DRAWING ISSUE
No.
DATE
JEH
PROJECT No.
DA09057
E1.0
F5
E
ELBA-7
ELCU
E
ELBA-7
F5
NEW JERSEY
CITY OF ESTELL MANOR
PARTNER: GERALD S. BLACKMAN, AIA, PP, NCARB
ASSOCIATE: STEVEN J. BOLOGNO, RA
ATLANTIC COUNTY,
ESTELL MANOR PARK MANSION
VETERANS MUSEUM
ARCHITECTS AND PLANNERS
www.olivieriarchitects.com
PRINCIPAL: DANIEL A. SHOUSKY AIA, PP, NCARB
PRINCIPAL: PAUL A. KISS AIA, PP, NCARB
ELCU
003
FOUNDER: JOHN J. OLIVIERI (1956-1999)
002
CRAWLSPACE
17 WEST KNIGHT AVENUE, SUITE 200, COLLINGSWOOD, NEW JERSEY 08108
PHONE: (856) 854-0580
FAX: (856) 854-0993
BASEMENT
OSK Design Partners P.A.
004
FIELD VERIFY LOCATION OF ALL WIRING DEVICES
WITH ARCHITECT PRIOR TO ROUGH-IN.!
!
FIELD VERIFY EXACT LOCATIONS OF ALL LIGHTING
FIXTURES WITH ARCHITECT PRIOR TO ROUGH-IN.!
!
UNLESS OTHERWISE NOTED ALL LIGHTING SHALL
BE CIRCUITED TO PANEL 'ABB'.!
!
EMERGENCY LIGHTING AND EXIT SIGNS SHALL BE
CONNECTED TO LINE SIDE OF LOCAL LIGHTING
CONTROL.!
THIS PLAN IS NOT VALID UNLESS A RAISED SEAL IS AFFIXED HERETO
CRAWLSPACE
BASEMENT - LIGHTING PLAN
DRAWING NOTES
1.!
!
!
2.!
!!
!
3.!
!
!
4.
GERALD S. BLACKMAN,
AIA, PP, NCARB
N.J. LIC. No. A1 17113
CRAWLSPACE
005
CONSULTING ENGINEERS
HOLSTEIN WHITE, INC.
001
210 E. STREET ROAD
TELE # (215)322-7711
SUITE 2D
FAX # (215)322-7709
FEASTERVILLE, PA 19053
BASEMENT
Jeffrey E. Holstein, P.E.
License No. NJ GE46443
Authorization NO; 2GA28143700
REVISIONS:
1
BASEMENT - !
LIGHTING PLAN
SCALE: 1/4" = 1'-0"
DATE:
7-1-2014
SCALE:
AS NOTED
DRAWN BY: JAC
CHK'D BY:
ISSUED TO ATLANTIC COUNTY FOR REVIEW
1
06-21-2013
DRAWING ISSUE
No.
DATE
JEH
PROJECT No.
DA09057
E1.1
24
WP
10
20
57
32
28
WP
WP
WP
WP
WP
NEW JERSEY
CITY OF ESTELL MANOR
ATLANTIC COUNTY,
CU
5
CU
4
CU
3
FIELD VERIFY LOCATION OF ALL WIRING DEVICES
WITH ARCHITECT PRIOR TO ROUGH-IN.!
!
COORDINATE INSTALLATION OF HVAC EQUIPMENT
WITH MECHANICAL CONTRACTOR. INSTALL AND
WIRE DISCONNECT SWITCHES FURNISHED BY
MECHANICAL CONTRACTOR.!
!
UNLESS OTHERWISE NOTED, ALL POWER SHALL
BE CIRCUITED TO PANEL 'ABB'.
ESTELL MANOR PARK MANSION
VETERANS MUSEUM
CU
2
CU
1
FIRST FLOOR - POWER PLAN
DRAWING NOTES
1.!
!
!
2.!
!
!
!
!
3.
ELBA-5
10
F
E
E
ELBA-5
PARK
E
ELBA-5
ADMINISTRATION
110
25
25
27
FIRE ALARM REMOTE ANNUNCIATOR
27
F
29
F
29
D
F
ACCESSIBLE ENTRY
F
F F
VESTIBULE
29
29
TYPE 'A'
PE
ELBA-5
107
ENTRY HALL
D
PE
E
D
STAIR #1
PE
37
CLOSET
29
AHU
1
JAN.
S1-1
102D
29
E
29
MECHANICAL
ELBA-5
D
112
F
F
31
FIRE ALARM CONTROL PANEL
ELBA-2
33
39
D
47
+
KITCHENETTE
D
F F
MEETING ROOM
D
TYPE 'A'
PE
37
105
PE
12
111
B1
S
D
D
HAND DRYER
PE
113
D
114
17
FU_COLD
FIXT_CODE
FU_TOTAL
FU_WASTE
FU_HOT
12
D
TOILET
ROOM
ROOM
PE
57
17
D
SM
115
C C
F
10
INTERCONNECT TO !
LIGHTING CONTROL
WP
N.J. LIC. No. A1 17113
ELEV.
AH
5
EQUIP.
SM
C
PANEL 'ABB'
GERALD S. BLACKMAN,
AIA, PP, NCARB
4
F
PE
SM
45
PANEL ELBA
F
ELBA-1
ELBA-1
2
+
12
+
TOILET
43
33
12
PE
ATS-1
STORAGE
F
E1-1
F
2
EF
1
12
F
F
HAND DRYER
33
D
D
F
AREA
33
104
VAPORTIGHT FLUORESCENT!
PIT LIGHT
ELEVATOR
108
D
PANEL 'ABA'
F
TYPE 'A'
33
DINING / DISPLAY
18
6
CLOSET
109
31
EXHIBIT
AHU
2
LOCATED IN PIT
41
REF
M
F
PE
FU_COLD
31
FU_TOTAL
31
FU_HOT
33
33
FIXT_CODE
8
16
ROOM
PE
F
FU_WASTE
WP
ELBA-5
PE
F F
D
103
6
SLEEVE SERVICE ENTRANCE CONDUCTORS THROUGH WALL
EF
1
M
ELEVATOR POWER
10
WP
ELEVATOR CAB LIGHTING
CT CABINET AND UTILITY METERING
UE
TYPE 'A'
EXHIBIT
35
D
TYPE 'A'
PE
AREA
35
INTERCONNECT TO!
LIGHTING CONTROL
106
PARTNER: GERALD S. BLACKMAN, AIA, PP, NCARB
ASSOCIATE: STEVEN J. BOLOGNO, RA
WP
27
PRINCIPAL: DANIEL A. SHOUSKY AIA, PP, NCARB
PRINCIPAL: PAUL A. KISS AIA, PP, NCARB
PE
27
CONSULTING ENGINEERS
D
101
25
210 E. STREET ROAD
TELE # (215)322-7711
SUITE 2D
FAX # (215)322-7709
FEASTERVILLE, PA 19053
25
F F
HOLSTEIN WHITE, INC.
TYPE 'A'
THIS PLAN IS NOT VALID UNLESS A RAISED SEAL IS AFFIXED HERETO
MEETING ROOM
PE
FOUNDER: JOHN J. OLIVIERI (1956-1999)
GENERATOR BACKED CIRCUIT
D
TYPE 'A'
ARCHITECTS AND PLANNERS
www.olivieriarchitects.com
100
OSK Design Partners P.A.
ENTRY RAMP
27
17 WEST KNIGHT AVENUE, SUITE 200, COLLINGSWOOD, NEW JERSEY 08108
PHONE: (856) 854-0580
FAX: (856) 854-0993
3 #12 & 1 #12G., 3/4"C. to AHU-5
27
25
TO UTILITY COMPANY TRANSFORMER
35
Jeffrey E. Holstein, P.E.
License No. NJ GE46443
35
Authorization NO; 2GA28143700
35
REVISIONS:
1
FIRST FLOOR - !
POWER PLAN
SCALE: 1/4" = 1'-0"
DATE:
7-1-2014
SCALE:
AS NOTED
DRAWN BY: JAC
CHK'D BY:
ISSUED TO ATLANTIC COUNTY FOR REVIEW
1
06-21-2013
DRAWING ISSUE
No.
DATE
JEH
PROJECT No.
DA09057
E2.0
1
F6
3
F6
3
F6
MEETING ROOM
101
ELBA-7
7
F8
7
F8
ELCU
E
1
F2
F2
1
3
F7
ELCU
ELBA-7
7
F7
ELCU
ELCU
R
E
R
ELBA-3
7
R
19
ELCU
F2
3
F2
3
ELBA-7
F2
F8
3
7
3
3
ELCU
E1
3
ELBA-3
5
5
F6
5
F6
5
F6
F6
R
ENTRY HALL
ELCU
E1
R
E
5
ELBA-7
F3
F6
3
3
F1
19
R
F10
F1
F2
LIGHTING REACTIVATION!
SWITCH #1
5
SD
F6
5
ELBA-3
E
F1
E
17
ELBA-7
E2
E1
E
ELCU
ELCU
107
ELCU
103
R
E
VESTIBULE
7
ELBA-7
F1
110
E
F2
E
CEMETERY
OFFICE
1
E
F9
ELBA-3
F1
ELCU
ELBA-7
1
F3
R
E
F3
R
5
3
F1
JAN. CLOS.
102
7
F8
E1
ELBA-7
9
19
ELCU
9
F2
F2
F1
F2
11
11
ELBA-7
ELCU
R
17
R
E
E
7
F9
17
E1
F2
11
CLOSET
17
F5
108
R
F2
17
F1
F5
F3
DINING / DISPLAY
MEETING ROOM
EXHIBIT
AREA
9
104
9
11
KITCHENETTE
F2
ELCU
105
F7
E1
F2
11
STORAGE
109
R
19
111
E
17
ELBA-7
F1
F10
3
F7
11
F2
THIS PLAN IS NOT VALID UNLESS A RAISED SEAL IS AFFIXED HERETO
3
NEW JERSEY
CITY OF ESTELL MANOR
ESTELL MANOR PARK MANSION
VETERANS MUSEUM
ATLANTIC COUNTY,
PARTNER: GERALD S. BLACKMAN, AIA, PP, NCARB
ASSOCIATE: STEVEN J. BOLOGNO, RA
F6
PRINCIPAL: DANIEL A. SHOUSKY AIA, PP, NCARB
PRINCIPAL: PAUL A. KISS AIA, PP, NCARB
1
FOUNDER: JOHN J. OLIVIERI (1956-1999)
F9
17 WEST KNIGHT AVENUE, SUITE 200, COLLINGSWOOD, NEW JERSEY 08108
PHONE: (856) 854-0580
FAX: (856) 854-0993
FIRST FLOOR - LIGHTING PLAN
19
ARCHITECTS AND PLANNERS
www.olivieriarchitects.com
FIELD VERIFY LOCATION OF ALL WIRING DEVICES
WITH ARCHITECT PRIOR TO ROUGH-IN.!
!
FIELD VERIFY EXACT LOCATIONS OF ALL LIGHTING
FIXTURES WITH ARCHITECT PRIOR TO ROUGH-IN.!
!
UNLESS OTHERWISE NOTED ALL LIGHTING SHALL
BE CIRCUITED TO PANEL 'XIX'.!
!
EMERGENCY LIGHTING AND EXIT SIGNS SHALL BE
CONNECTED TO LINE SIDE OF LOCAL LIGHTING
CONTROL.
OSK Design Partners P.A.
DRAWING NOTES
1.!
!
!
2.!
!
!
!
!
3.!
!
!
4.!
!
!
5.!
!
!
6.!
!
!
!
7.
GERALD S. BLACKMAN,
AIA, PP, NCARB
N.J. LIC. No. A1 17113
ELCU
11
F2
R
E
F1
F2
F2
F9
ELCU
TOILET
ROOM
113
9
17
ELBA-7
TOILET17
ROOM
ELCU
F5
R
E
F1
E
114
F5
FIXT_CODE
FU_TOTAL
FU_WASTE
FU_HOT
FU_COLD
E3
115
ELBA-1
FIXT_CODE
FU_TOTAL
FU_WASTE
FU_COLD
FU_HOT
ELEV.
EQUIP.
ELCU
E1
E1
E
19
F11
(TYP)
F8
19
F8
19
ELBA-7
F8
E3
13
13
T1
T1
F11
(TYP)
ELCU
ELBA-7
13
F11
(TYP)
19
ELCU
EXHIBIT
AREA
R
13
E
F1
F9
ELBA-7
13
CONSULTING ENGINEERS
9
ELBA-7
17
11
F6
F11
R
(TYP)
15
E
210 E. STREET ROAD
TELE # (215)322-7711
SUITE 2D
FAX # (215)322-7709
FEASTERVILLE, PA 19053
9
F6
HOLSTEIN WHITE, INC.
19
F1
106
T2
T2
15
19
T1
15
F11
F11
(TYP)
(TYP)
T1
Jeffrey E. Holstein, P.E.
License No. NJ GE46443
Authorization NO; 2GA28143700
F8
19
F9
19
F8
F9
19
REVISIONS:
1
FIRST FLOOR - !
LIGHTING PLAN
SCALE: 1/4" = 1'-0"
DATE:
7-1-2014
SCALE:
AS NOTED
DRAWN BY: JAC
CHK'D BY:
ISSUED TO ATLANTIC COUNTY FOR REVIEW
1
06-21-2013
DRAWING ISSUE
No.
DATE
JEH
PROJECT No.
DA09057
E2.1
D
13
23
PE
23
201
D
11
13
13
PE
TYPE 'A'
23
F
F
23
F
15
15
23
15
F F
F F
F F
VESTIBULE
HALL
STAIR #1
200D
202
S1-2
EXHIBIT AREA/
WORK ROOM
PE
206
STAIR #1
S1-1
PANEL 'A2A'
15
WP
F
8
23
F
F
17
D
21
25
PE
TYPE 'A'
CLASSROOM/
D
MEETING ROOM
PE
25
CLOSET
21
205A
ELEVATOR
203
D
TYPE 'A'
PE
D
D
PE
17
17
25
F
D
EF
1
17
MEETING ROOM
19
PE
E1-2
NEW JERSEY
CITY OF ESTELL MANOR
ATLANTIC COUNTY,
ESTELL MANOR PARK MANSION
VETERANS MUSEUM
N.J. LIC. No. A1 17113
205
TOILET
HAND DRYER
ROOM
5
17
CLASSROOM/
21
+
17
PE
GERALD S. BLACKMAN,
AIA, PP, NCARB
SM
209
35
FD
21
FIXT_CODE
FU_TOTAL
FU_WASTE
FU_HOT
FU_COLD
21
INTERCONNECT TO LIGHTING CONTROL
CONSULTING ENGINEERS
PE
D
PARTNER: GERALD S. BLACKMAN, AIA, PP, NCARB
ASSOCIATE: STEVEN J. BOLOGNO, RA
13
PRINCIPAL: DANIEL A. SHOUSKY AIA, PP, NCARB
PRINCIPAL: PAUL A. KISS AIA, PP, NCARB
11
210 E. STREET ROAD
TELE # (215)322-7711
SUITE 2D
FAX # (215)322-7709
FEASTERVILLE, PA 19053
11
EXHIBIT AREA
FOUNDER: JOHN J. OLIVIERI (1956-1999)
TYPE 'A' CLASSROOM/
EXHIBIT AREA
13
204
PE
CLASSROOM/
HOLSTEIN WHITE, INC.
D
TYPE 'A'
11
THIS PLAN IS NOT VALID UNLESS A RAISED SEAL IS AFFIXED HERETO
13
17 WEST KNIGHT AVENUE, SUITE 200, COLLINGSWOOD, NEW JERSEY 08108
PHONE: (856) 854-0580
FAX: (856) 854-0993
SECOND FLOOR - POWER PLAN
11
11
ARCHITECTS AND PLANNERS
www.olivieriarchitects.com
FIELD VERIFY LOCATION OF ALL WIRING DEVICES
WITH ARCHITECT PRIOR TO ROUGH-IN.!
!
COORDINATE INSTALLATION OF HVAC EQUIPMENT
WITH MECHANICAL CONTRACTOR. INSTALL AND
WIRE DISCONNECT SWITCHES FURNISHED BY
MECHANICAL CONTRACTOR.!
!
FIELD VERIFY EXACT LOCATIONS OF ALL LIGHTING
FIXTURES WITH ARCHITECT PRIOR TO ROUGH-IN.!
!
UNLESS OTHERWISE NOTED, ALL POWER SHALL
BE CIRCUITED TO PANEL 'A2A'.
OSK Design Partners P.A.
DRAWING NOTES
1.!
!
!
2.!
!
!
!
!
3.!
!
!
4.
Jeffrey E. Holstein, P.E.
License No. NJ GE46443
Authorization NO; 2GA28143700
REVISIONS:
1
SECOND FLOOR - !
POWER PLAN
SCALE: 1/4" = 1'-0"
DATE:
7-1-2014
SCALE:
AS NOTED
DRAWN BY: JAC
CHK'D BY:
ISSUED TO ATLANTIC COUNTY FOR REVIEW
1
06-21-2013
DRAWING ISSUE
No.
DATE
JEH
PROJECT No.
DA09057
E3.0
R
1
R
1
F1
F1
F1
1
R
1
R
F1
1
R
F1
R
F1
7
7
F1
R
3
3
202
ELBA-9
3
ELCU
E1
R
E
R
E
WORK ROOM
HALL
R
3
ELCU
R
7
ELBA-9
7
R
F1
F1
ELCU
R
E
E
F1
F1
3
ELBA-9
3
3
F3
F1
ELBA-9
3
206
R
E
3
3
E1
E1
F1
3
200ELCU
ELCU
F1
3
VESTIBULE
ABB-7
ELBA-9
R
F1
F3
R
7
R
F1
ABB-7
R
F3
R
F1
F1
F1
R
E
5
F1 ELBA-9
CLOSET
205A
MECHANICAL
ROOM
5
5
ELCU
R
R
R
F1
F1
208
ELCU
R
7
207
205
209
5
R
R
5
R
F1
5
R
F1
5
5
F1
7
F1
ELBA-9
CORRIDOR
OFFICE
TOILET
ROOM
R
E
F1
OFFICE
203
3
5
5
5
R
7
F1
ELEVATOR
E1-2
NEW JERSEY
CITY OF ESTELL MANOR
ATLANTIC COUNTY,
PARTNER: GERALD S. BLACKMAN, AIA, PP, NCARB
ASSOCIATE: STEVEN J. BOLOGNO, RA
F1
OFFICE
204
1
R
R
3
R
F1
OFFICE
201
ABB-7
1
1
R
F1
PRINCIPAL: DANIEL A. SHOUSKY AIA, PP, NCARB
PRINCIPAL: PAUL A. KISS AIA, PP, NCARB
F1
FOUNDER: JOHN J. OLIVIERI (1956-1999)
1
R
3
R
F1
17 WEST KNIGHT AVENUE, SUITE 200, COLLINGSWOOD, NEW JERSEY 08108
PHONE: (856) 854-0580
FAX: (856) 854-0993
1
1
R
THIS PLAN IS NOT VALID UNLESS A RAISED SEAL IS AFFIXED HERETO
1
F10
ESTELL MANOR PARK MANSION
VETERANS MUSEUM
SECOND FLOOR - LIGHTING PLAN
37
F10
ARCHITECTS AND PLANNERS
www.olivieriarchitects.com
37
FIELD VERIFY LOCATION OF ALL WIRING DEVICES
WITH ARCHITECT PRIOR TO ROUGH-IN.!
!
FIELD VERIFY EXACT LOCATIONS OF ALL LIGHTING
FIXTURES WITH ARCHITECT PRIOR TO ROUGH-IN.!
!
UNLESS OTHERWISE NOTED ALL LIGHTING SHALL
BE CIRCUITED TO PANEL 'A2A'.!
!
EMERGENCY LIGHTING AND EXIT SIGNS SHALL BE
CONNECTED TO LINE SIDE OF LOCAL LIGHTING
CONTROL.
OSK Design Partners P.A.
DRAWING NOTES
1.!
!
!
2.!
!
!
3.!
!
!
4.
GERALD S. BLACKMAN,
AIA, PP, NCARB
N.J. LIC. No. A1 17113
5
R
F1
F1
R
FD
FIXT_CODE
FU_TOTAL
FU_WASTE
FU_HOT
CONSULTING ENGINEERS
HOLSTEIN WHITE, INC.
FU_COLD
210 E. STREET ROAD
TELE # (215)322-7711
SUITE 2D
FAX # (215)322-7709
FEASTERVILLE, PA 19053
F1
Jeffrey E. Holstein, P.E.
License No. NJ GE46443
Authorization NO; 2GA28143700
REVISIONS:
1
SECOND FLOOR - !
LIGHTING PLAN
SCALE: 1/4" = 1'-0"
DATE:
7-1-2014
SCALE:
AS NOTED
DRAWN BY: JAC
CHK'D BY:
ISSUED TO ATLANTIC COUNTY FOR REVIEW
1
06-21-2013
DRAWING ISSUE
No.
DATE
JEH
PROJECT No.
DA09057
E3.1
27
F
27
31
39
29
F F
D
D
F
D
F
F
ATTIC
ATTIC
300
F F
D
ATTIC
301
F
ATTIC
307
D
D
306
LOCATED TOP!
OF STAIRS
F
F
27
D
D
D
F
D
F
STAIR #1
D
F
39
S1-2
F
F
39
29
AHU
4
27
ATTIC
D
27
33
F
29
305
D
ATTIC
D
F
D
F
303
D
F
TOP OF SHAFT WITHIN 2' OF SPRINKLER HEAD
PE
NEW JERSEY
CITY OF ESTELL MANOR
ATLANTIC COUNTY,
ESTELL MANOR PARK MANSION
VETERANS MUSEUM
THIRD FLOOR - POWER PLAN
N.J. LIC. No. A1 17113
ATTIC
F
304
HOLSTEIN WHITE, INC.
D
D
29
D
F
29
39
F
GERALD S. BLACKMAN,
AIA, PP, NCARB
CONSULTING ENGINEERS
D
27
210 E. STREET ROAD
TELE # (215)322-7711
SUITE 2D
FAX # (215)322-7709
FEASTERVILLE, PA 19053
AHU
3
PARTNER: GERALD S. BLACKMAN, AIA, PP, NCARB
ASSOCIATE: STEVEN J. BOLOGNO, RA
F
F
PRINCIPAL: DANIEL A. SHOUSKY AIA, PP, NCARB
PRINCIPAL: PAUL A. KISS AIA, PP, NCARB
D
D
FOUNDER: JOHN J. OLIVIERI (1956-1999)
309
17 WEST KNIGHT AVENUE, SUITE 200, COLLINGSWOOD, NEW JERSEY 08108
PHONE: (856) 854-0580
FAX: (856) 854-0993
ATTIC
308
ARCHITECTS AND PLANNERS
www.olivieriarchitects.com
ATTIC
F
THIS PLAN IS NOT VALID UNLESS A RAISED SEAL IS AFFIXED HERETO
D
FIELD VERIFY LOCATION OF ALL WIRING DEVICES
WITH ARCHITECT PRIOR TO ROUGH-IN.!
!
COORDINATE INSTALLATION OF HVAC EQUIPMENT
WITH MECHANICAL CONTRACTOR. INSTALL AND
WIRE DISCONNECT SWITCHES FURNISHED BY
MECHANICAL CONTRACTOR.!
!
UNLESS OTHERWISE NOTED, ALL POWER SHALL
BE CIRCUITED TO PANEL 'A2A'.
OSK Design Partners P.A.
DRAWING NOTES
1.!
!
!
2.!
!
!
!
!
3.
Jeffrey E. Holstein, P.E.
License No. NJ GE46443
Authorization NO; 2GA28143700
REVISIONS:
1
THIRD FLOOR - !
POWER PLAN
SCALE: 1/4" = 1'-0"
DATE:
7-1-2014
SCALE:
AS NOTED
DRAWN BY: JAC
CHK'D BY:
ISSUED TO ATLANTIC COUNTY FOR REVIEW
1
06-21-2013
DRAWING ISSUE
No.
DATE
JEH
PROJECT No.
DA09057
E4.0
F1
ATTIC
ATTIC
ATTIC
307
306
R
9
F1
ELCU
E6
ATTIC
9
300
R
F1
ELBA-9
9
9
ELBA-9
R
E
F1
301
9
R
F1
ELCU
R
E
F1
9
R
F1
E1
E5
9
R
ATTIC
ELCU
R
E
9
ELBA-9
F1
ATTIC
305
F1
302
9
R
9
F1
R
ATTICF1
303
LIGHTING REACTIVATION!
SWITCH #2
R
9
F1
9
R
F1
NEW JERSEY
CITY OF ESTELL MANOR
ESTELL MANOR PARK MANSION
VETERANS MUSEUM
THIRD FLOOR - LIGHTING PLAN
ATLANTIC COUNTY,
PARTNER: GERALD S. BLACKMAN, AIA, PP, NCARB
ASSOCIATE: STEVEN J. BOLOGNO, RA
R
E
ELBA-9
9
PRINCIPAL: DANIEL A. SHOUSKY AIA, PP, NCARB
PRINCIPAL: PAUL A. KISS AIA, PP, NCARB
F1
ELCU
FOUNDER: JOHN J. OLIVIERI (1956-1999)
9
R
17 WEST KNIGHT AVENUE, SUITE 200, COLLINGSWOOD, NEW JERSEY 08108
PHONE: (856) 854-0580
FAX: (856) 854-0993
309
F1
ARCHITECTS AND PLANNERS
www.olivieriarchitects.com
ATTIC
308
R
THIS PLAN IS NOT VALID UNLESS A RAISED SEAL IS AFFIXED HERETO
ATTIC
9
FIELD VERIFY LOCATION OF ALL WIRING DEVICES
WITH ARCHITECT PRIOR TO ROUGH-IN.!
!
FIELD VERIFY EXACT LOCATIONS OF ALL LIGHTING
FIXTURES WITH ARCHITECT PRIOR TO ROUGH-IN.!
!
UNLESS OTHERWISE NOTED ALL LIGHTING SHALL
BE CIRCUITED TO PANEL 'A2A'.!
!
EMERGENCY LIGHTING AND EXIT SIGNS SHALL BE
CONNECTED TO LINE SIDE OF LOCAL LIGHTING
CONTROL.
OSK Design Partners P.A.
DRAWING NOTES
1.!
!
!
2.!
!
!
3.!
!
!
4.
GERALD S. BLACKMAN,
AIA, PP, NCARB
N.J. LIC. No. A1 17113
ATTIC
R
CONSULTING ENGINEERS
210 E. STREET ROAD
TELE # (215)322-7711
SUITE 2D
FAX # (215)322-7709
FEASTERVILLE, PA 19053
304
F1
HOLSTEIN WHITE, INC.
9
Jeffrey E. Holstein, P.E.
License No. NJ GE46443
Authorization NO; 2GA28143700
REVISIONS:
1
THIRD FLOOR - !
LIGHTING PLAN
SCALE: 1/4" = 1'-0"
DATE:
7-1-2014
SCALE:
AS NOTED
DRAWN BY: JAC
CHK'D BY:
ISSUED TO ATLANTIC COUNTY FOR REVIEW
1
06-21-2013
DRAWING ISSUE
No.
DATE
JEH
PROJECT No.
DA09057
E4.1
Emergency Neutral
(WHITE 18AWG)
Top of Highest Electrical Safety Disconnect Switches, Magnetic Motor Starters and Contactors
4'-6"
Wall Mounted Telephones and Pay Stations (3'-6" at Handicap Locations)
3'-6"
Normal Power Sense
(BLACK 18AWG)
Emergency Power In
(BLACK 12AWG)
Fire Alarm Pull Stations
3'-4"
Wall Mounted Electrical Device Lighting Switches
2'-0"
Electrical Receptacles in Mechanical Spaces, Electrical and Elevator Rooms
1'-6"
Cut jumper loop
to use with
Normally Closed
-Test Switch
-Fire Alarm Panel
-Security Panel
-Other
NORMAL
POWER
EMAERGENCY
POWER
PUSH
TO TEST
REMOTE
ACTIVATION
CIR.#
Electrical Receptacles, Television Outlets, Telephone Outlets, and Computer Outlets
0'-0"
Finished Floor
Mounting Heights to center of outlets unless otherwise noted. In masonry construction the mounting heights shall be used for!
reference to the nearest block or brick coursing. !
The above mounting heights shall be adhered to unless specifically noted or detailed on the Architectural drawings or
specifications.
ELECTRICAL SYMBOLS
Emergency Line
4-600MCM & 1# 1/0G, 4"C.
400AF!
400AT
N
SERVICE
ENTRANCE RATED
225AF!
225AT
PANEL ABA
Emergency Neutral
Electrical Panel
D
400 AMP BUS
225AF!
225AT
125AF!
100AT
208/120V - 3Ø - 4W - 22K AIC
2
225AF!
225AT
EMERGENCY LIGHT
CONTROL UNIT (ELCU-200)
D
SCALE: N.T.S.
NOTE #4
N
4# 4 & 1# 10G, 2-1/2"C.
F
N
4# 4 & 1# 10G, 2-1/2"C.
E
(2)N.O.
SWITCH POSITITION SIGNAL
2# 12, 3/4" CONDUIT
PHOTOCELL
CONTROL!
PANEL
30
1
!
SINGLE LINE DIAGRAM
NOT TO SCALE
ABB-7
SPARE
ABB-19
SPARE
SPARE
SPARE
INTERIOR LIGHTING
FIELD VERIFY ELEVATOR DISCONNECT
LOCATION AND FINAL CONNECTIONS
TO CONTROLLER WITH ELEVATOR
VENDOR PRIOR TO ROUGH-IN
TIMECLOCK
CIRCUIT #2
F
Fire Alarm Manual Pull Station
Circuit Number
S1
S2
OVERRIDE!
SWITCHES
ABB-1
ABB-11
ABB-3
ABB-13
ABB-5
ABB-15
ABB-9
ABB-17
SPARE
SPARE
SPARE
SPARE
NOTES:
! !
! !
1.! PROVIDE INTERMATIC ELECTRONIC TIME SWITCH
! MODEL #ET70415C FOR LIGHTING CONTROL.
! PROVIDE MOMENTARY CONTACT TOGGLE TYPE
! TIMECLOCK OVERRIDE SWITCHES AS INDICATED
! ON PLANS.!
! !
2.! OVERRIDE SWITCH COVERPLATES SHALL BE
! ENGRAVED "LIGHTING OVERRIDE". !
! !
3.! CONNECT EMERGENCY LIGHTS AND EXIT SIGNS
! TO LINE SIDE OF LIGHTING CONTROLS.!
! !
4.! COORDINATE WITH OWNER AND PROGRAM
! TIMECLOCK TO OWNER'S SCHEDULE.!
! !
5.! LIGHTING SHALL FLASH ONCE 5 MINUTES PRIOR
! TO SHUTDOWN BY TIMECLOCK. !
! !
6.! ACTIVATION OF LIGHTING OVERRIDE SHALL YIELD
! AN ADDITIONAL 1 HOUR OF LIGHTING.!
! !
7. OVERRIDE SWITCHES SHALL BE INTERCONNECTED TO TIMECLOCK FOR OVERRIDE OF
EACH TIMECLOCK CIRCUIT AS DIRECTED BY
MANUFACTURER.
Controlling Switch Designation
a
Lighting Fixture
A1
Fixture Type
Night Light
NL
Single Pole Switch
Unfused Disconnect Switch
3
Three Way Switch
Fused Disconnect Switch
Fire Alarm Control Panel
Duplex Receptacle - 125V, 2P, 3W
Motor
Quadraplex Receptacle!
- 125V, 2P, 3W
Floor Outlet with Devices Indicated
AFF
MULTIPOLE!
CONTACTOR
C
Emergency Lighting Fixture
E
5
Fire Alarm Flashing Light
MULTIPOLE!
CONTACTOR
C
NOTE #4
PANEL!
'ELBA'
REFER TO SINGLE LINE
DIAGRAM NOTE #5
TIMECLOCK
CIRCUIT #1
200A!
!
175A
E
E
Fire Alarm Horn
F
SITE & BUILDING LIGHTING
JOCKEY!
PUMP
FIRE AND JOCKEY PUMP CONTROLLER
SHALL BE FURNISHED BY FIRE
SUPPRESSION CONTRACTOR
Exit Sign !
- Ceiling or Wall Mounted
PROVIDE 120 VOLT, 20 AMP CONTROL
CIRCUIT, ABC-2
3
FIRE!
PUMP
PANEL!
'A2A'
15
(2) 125/3!
SPACES
3# 3/0 & 1# 3/0G, 2"C.
4# 4 & 1# 10G, 2-1/2"C.
GROUND /
NEUTRAL
BOND
4# 2 & 1# 8G, 1-1/2"C.
E
4# 4/0 & 1# 4G, 2-1/2"C.
N
PANEL!
'ABB'
E
Incandescent, Fluorescent or High !
Intensity Discharge Lighting Fixture
Automatic Detector
[ Detector Control Function ]!
D - Duct Mounted, Smoke Ionization!
F - Thermal, Fixed Temperature!
FR - Thermal, Combination Rate of!
Rise Plus Fixed Temperature!
PE - Smoke PhotoElectric!
R - Thermal, Rate of Rise!
S - Area Smoke, Ionization!
SS - Single Station
GFI Duplex Receptacle!
- 125V, 2P, 3W
Above Finished Floor
Communication System Outlet
ELCU
Emergency Lighting Control Unit
+
Single Pole, Center Off Momentary
Contact Switch
Device Mounted Above Counter Top
TV
Television Outlet
SM
Manual Motor Switch
WP
Weatherproof
Solid Connection to Equipment
GERALD S. BLACKMAN,
AIA, PP, NCARB
N.J. LIC. No. A1 17113
SERVICE ENTRANCE!
EQUIPMENT
EXTERIOR WALL
N
NEW JERSEY
Top of Back-Mounted Wall Exit Signs (Not Mounted Above Doors)
6'-0"
CITY OF ESTELL MANOR
Top of Flush and Surface Mounted Electrical Panelboards and Communication System Cabinets
6'-3"
ATLANTIC COUNTY,
Normal Neutral
(WHITE 18AWG)
Emergency
Lighting
PARTNER: GERALD S. BLACKMAN, AIA, PP, NCARB
ASSOCIATE: STEVEN J. BOLOGNO, RA
Emergency Power Out
(RED 12AWG)
UTILITY COMPANY !
3# 2 & 1# 8G., 2"C
Fire Alarm Illuminated Flashing Lights (Lowest of the two Heights)
6'-6"
PRINCIPAL: DANIEL A. SHOUSKY AIA, PP, NCARB
PRINCIPAL: PAUL A. KISS AIA, PP, NCARB
Normal
Switched Sense
(RED 18AWG)
4-600MCM, 4"C.
G
Warning and Signaling Fixtures/Signs
6'-8" or 6" Below
Finished Ceiling
FOUNDER: JOHN J. OLIVIERI (1956-1999)
"Switching"
Line
UTILITY COMPANY TRANSFORMER!
208/120V-3Ø-4W SECONDARY!
SERVICE
3# 2 & 1# 8G., 2"C. CONCRETE ENCASED
AS REQUIRED BY NEC ARTICLE 695
Pendant Hung Industrial and Strip Lighting Fixtures
Center Above!
Door or Window!
Opening
GROUNDING ELECTRODE SYSTEM SHALL!
BE PROVIDED IN ACCORDANCE WITH THE!
NATIONAL ELECTRIC CODE, ARTICLE 250.50!
!
PROVIDE WATER PIPE GROUND CONNECTION!
ON STREET SIDE OF WATER METER.
210 E. STREET ROAD
TELE # (215)322-7711
SUITE 2D
FAX # (215)322-7709
FEASTERVILLE, PA 19053
Normal Neutral
4-600MCM, 4"C.
8'-6"
17 WEST KNIGHT AVENUE, SUITE 200, COLLINGSWOOD, NEW JERSEY 08108
PHONE: (856) 854-0580
FAX: (856) 854-0993
E
M METER
Battery Lighting Units and Remote Wall Mounted Lighting Heads (Or 1'-0" Below Finised Ceiling)
HOLSTEIN WHITE, INC.
125AF!
60AT
Normal Lighting
ELCU 11
CONSULTING ENGINEERS
WEATHERPROOF!
LEVEL III SOUND !
ATTENUATED !
ENCLOSURE
Wall-Mounted Clocks, Program Bells, Fire Alarm Gongs and Horns
10'-0"
ELBA-7
LIGHTING FIXTURE
NORMAL LIGHTING CIRCUIT
"Sensing"
Line
9" Below!
Finished Ceiling
SINGLE LINE DIAGRAM
125AF!
100AT
NEW 3-PHASE AERIAL SERVICE
FROM OVERHEAD UTILITY
WIRES AT STREET
Normal Line
EMERGENCY LIGHTING CIRCUIT
ESTELL MANOR PARK MANSION
VETERANS MUSEUM
OUTDOOR NATURAL GAS !
GENERATOR !
60KW / 75 KVA !
208/120V-3Ø-4W-60HZ
ELECTRICAL STANDARD MOUNTING HEIGHTS
INDICATED ON PLANS AS THE FOLLOWING:
On/Off Control Device
·
Relay
·
Powerpack
·
Wall Switch
ARCHITECTS AND PLANNERS
www.olivieriarchitects.com
GENERATOR SHALL BE AS
MANUFACTURED BY
CUMMIS, MTU, CATERPILLER
UNLESS OTHERWISE NOTED, ALL DEVICES AND
SPACES ARE 3 POLE.!
!
UNLESS OTHERWISE NOTED, ALL CONDUCTORS
SHALL BE COPPER, TYPE THW, RATED 75ºC.!
!
ELECTRICAL CONTRACTOR SHALL CONNECT LOAD
TO MAINTAIN BALANCE LOAD IN METER CENTER.!
!
PROVIDE (1) NORMALLY OPEN AND (1) NORMALLY
CLOSED AUXILARY CONTACT FOR EMERGENCY
LOWERING PROVISION. CONTACT SHALL MONITOR
DEVICE STATUS (I.E. TRIPPED OR OPEN) AND BE
INTERCONNECTED TO THE ELEVATOR
CONTROLLER. PROVIDE 2#12 IN 3/4"C. BETWEEN
CIRCUIT BREAKER AND ELEVATOR CONTROLLERS,
COORDINATE TERMINATION LOCATION IN
CONTROLLERS WITH ELEVATOR CONTRACTOR. !
!
INTERCONNECT FIRE PUMP CONTROLLER TO FIRE
ALARM SYSTEM TO MONITOR THE FOLLOWING:
PUMP RUNNING STATUS, LOSS OF PHASE STATUS,
AND PHASE REVERSAL.!
!
VERIFY FINAL SIZING OF FIRE AND JOCKEY PUMP
PRIOR TO RELEASING GENERATOR TO
MANUFACTURE.
OSK Design Partners P.A.
1.!
!
!
2.!
!
!
3.!
!
!
4.!
!
!
!
!
!
!
!
!
!
5.!
!
!
!
!
6.
THIS PLAN IS NOT VALID UNLESS A RAISED SEAL IS AFFIXED HERETO
SINGLE LINE DIAGRAM NOTES
GROUNDING ELECTRODE!
CONDUCTOR
3
NOT TO SCALE
Jeffrey E. Holstein, P.E.
License No. NJ GE46443
CONNECTIONS MADE!
WITHIN 5' OF POINT OF!
ENTRANCE OF PIPE
TIMECLOCK !
CONTROL DETAIL
Authorization NO; 2GA28143700
GRADE
METAL UNDERGROUND!
WATER PIPE, (WHERE AVAILABLE)
REVISIONS:
GROUND!
ROD(S)
4
GROUNDING
ELECTRODE SYSTEM
NOT TO SCALE
DATE:
7-1-2014
SCALE:
AS NOTED
DRAWN BY: JAC
CHK'D BY:
ISSUED TO ATLANTIC COUNTY FOR REVIEW
1
06-21-2013
DRAWING ISSUE
No.
DATE
JEH
PROJECT No.
DA09057
E5.0
1.1
0.5
1.1
0.9
1.9
1.9
1.5
0.6
0.6
Description
Elevator Pit and Machine Room
Cemetary Office 110 Lighting
Cemetary Office 110 Receptacles
Basement and First Floor Lighting
Second Floor and Attic Lighting
Spare
Spare
Spare
Space
16.7
60A MCB
22 KAIC
Load - KW
A
B
0.3
0.1
PANEL
Cir.
No.
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
39
41
Total
2.6
2.3
2.4
7.3
Wire
Size
#12
#12
#12
#12
#12
#12
#12
#12
#12
#12
#12
#12
#12
#12
#12
#12
#12
#12
#12
#12
#12
Description
Meeting Room 101 Lighting
Meeting Room 101 Lighting
Room 102 and 103 Lighting
Exterior Porch Lighting
Exhibit Area 104 Lighting
Meeting Room 105 Lighting
Exhibit Area 105 Overhead Lighting
Exhibit Area 105 Lighting
Room 107, 109, 113, 114, 108, 111 Lighting
Exterior Flood Lighting
Telecom Equipment Receptacle
Basement Receptacles
Meeting Room 101 Receptacles
Meeting Room 101 Receptacles
Rooms 103, 102 Receptacles
Meeting Room 105 Receptacles
Exhibit Area 104 Receptacles
Exhibit Area 106 Receptacles
Rooms 107, 109 Receptacles
Kitchenette Countertop Receptacle
Kitchenette Refridgerator
PANEL
13.4
15.6
14.0
43.0
Wire
Size
#12
#12
#12
#12
#12
#12
#12
Description
Hand Dryer Room 113
Hand Dryer Room 114
Kitchenette Microwave
UH-1 (Basement 002)
UH-1 (Basement 001)
CU-5/AHU-5
Basement Water Softener
Spare
Spare
Spare
Spare
Spare
Spare
Space
Space
Space
Space
Space
5.5
4.8
4.5
14.8
Load Summary by Type
Connected Appliance
Connected Lighting
Connected Motor
Connected Heating
Connected Air Conditioning
Total
1.3
1.3
1.1
225A MCB
22 KAIC
Load - KW
A
B
1.0
1.0
1.8
1.8
A
0.4
Load - KW
B
1.3
C
0.4
0.4
0.7
0.7
0.9
1.3
1.2
1.7
0.5
1.1
1.9
2.2
0.4
2.2
0.4
0.9
2.4
2.4
1.1
2.4
1.3
0.7
2.4
2.4
1.3
2.4
0.9
0.4
0.2
6.1
1.0
6.0
43.0
225A MLO
22 KAIC
Load - KW
A
B
1.5
1.5
7.7
9.6
A
0.5
Description
C
0.5
1.2
0.5
1.5
1.5
1.5
1.5
1.3
1.3
0.5
4.3
14.8
208/120V - 3Ø - 4W
Section 1 of 2
Wire
Cir.
Size
Bkr.
Bathroom 113, 114 Receptacles
#12
20/1
Elevator Equipment Room 115 Receptacle
#12
20/1
Rooms 108, 111 Receptacles
#12
20/1
Front Porch Receptacle
#12
20/1
Outdoor Receptacles
#12
20/1
Meeting Room 105 Receptacles
#12
20/1
Spare
#12
20/1
AHU-1
#12
20/1
AHU-2
#12
20/1
CU-1
#8
40/2
CU-2
#8
40/2
CU-3
#8
40/2
CU-4
#8
40/2
Spare
20/1
Spare
20/1
Spare
20/1
Spare
20/1
42 POLE
C
4.0
KW
KW
KW
KW
KW
KW
0.5
0.5
Recessed
x Surface
Double Panel
x Ground Bus
Insulated
Ground Bus
8.0
Load - KW
B
Cir.
No.
2
4
6
8
10
12
14
16
18
Total
Options and Accessories - (X) Indicates Selection
x Feed Through Lugs
Subfeed Main Lugs
Split Bus
Contactor Controlled
Top
Bottom
KW
KW
KW
KW
KW
KW
Cir.
Bkr.
20/1
20/1
20/3
-
Description
0.2
1.0
Wire
Size
#12
#12
#10
-
1.3
42 POLE
C
Fire Alarm Control Panel
Fire Pump Control Panel
Well Pump
Space
Space
Space
Space
Options and Accessories - (X) Indicates Selection
Feed Through Lugs
Subfeed Main Lugs
Split Bus
Contactor Controlled
Top
Bottom
KW
KW
KW
KW
KW
KW
0.5
5.0
Phase (KW)
A
B
C
Total
Description
C
1.3
0.5
Recessed
x Surface
Double Panel
x Ground Bus
Insulated
Ground Bus
208/120V - 3Ø - 4W
Load - KW
B
0.5
7.3
Load Summary by Type
Connected Appliance
Connected Lighting
Connected Motor
Connected Heating
Connected Air Conditioning
Total
ABB
Cir.
Bkr.
20/1
20/1
20/1
20/2
20/2
20/2
20/1
20/1
20/1
20/1
20/1
20/1
20/1
A
0.5
1.1
5.8
Phase (KW)
A
B
C
Total
0.0
Options and Accessories - (X) Indicates Selection
Feed Through Lugs
Subfeed Main Lugs
Split Bus
Contactor Controlled
Top
Bottom
0.3
Load Summary by Type
Connected Appliance
Connected Lighting
Connected Motor
Connected Heating
Connected Air Conditioning
Total
ABB
Cir.
Bkr.
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
0.0
18 POLE
C
0.5
0.8
Phase (KW)
A
B
C
Total
0.0
KW
KW
KW
KW
KW
KW
20/1
20/1
20/1
20/1
Battery Charger
Block Heater
Remote Annunicator Panel
Space
Space
Space
Space
Space
Space
Space
Space
Space
Space
Space
Space
Space
Space
Space
Space
Space
Space
Recessed
x Surface
x Double Panel
x Ground Bus
Insulated
Ground Bus
208/120V - 3Ø - 4W
Section 2 of 2
Wire
Cir.
Size
Bkr.
#12
20/1
#12
20/1
#12
20/1
0.5
Options and Accessories - (X) Indicates Selection
x Feed Through Lugs
Subfeed Main Lugs
Split Bus
Contactor Controlled
Top
Bottom
Cir.
No.
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
Total
Recessed
x Surface
x Double Panel
x Ground Bus
Insulated
Ground Bus
Cir.
No.
44
46
48
50
52
54
56
58
60
62
64
66
68
70
72
74
76
78
80
82
84
Total
Determine and pay any and all charges required by Power Company. Have electrical service available when required by construction
schedule.!
!
Verify locations of existing underground services in the area of construction. Verify existing locations of underground electrical services,
natural gas piping, water services and sanitary piping which may affect work.!
!
Lay out all work from approved building and property lines and benchmarks. Verify and be responsible for the correctness of all
measurements in connection with work. Any change made in major overall dimensions as shown which affect the physical size, shape, or
location of any part of the Work, whether due to field check or changes due to the use of equipment of a manufacturer other than that
used as the basis of design shall not cause any interference with other work.!
!
Electrical equipment shall not interfere in any way with other material or equipment and shall provide adequate working space; see
Requirements for Electrical Installations, Article 110 and other related articles of the National Electrical Code.!
!
Provide materials, equipment, supplies and labor necessary as required to adequately support, brace and strengthen all equipment and
materials furnished as part of this work.!
!
Locations are subject to changes that may be necessary to avoid obstacles in building construction. Verify all dimensions and conditions
at site. Check layout for sizes and clearances, and provide so that the apparatus and material may be installed and operated
satisfactorily in space provided. Install equipment and raceways to preserve headroom and to keep openings and passageways clear.!
!
Protect all conduit, fittings, panelboards, switchgear, transformers and other equipment before and during installation and keep clean.!
!
Identify each panelboard, transformer, and other electrical equipment as to nature, service and purpose, by means of permanently
attached, approved size, laminated phenolic nameplates.!
!
Fully coordinate installation, wiring and connection of service and distribution systems with the owner and Atlantic City Electric.!
!
Coordinate with Power Company; inform them of the proposed work; obtain their approval before beginning work; comply with their
requirements for details of installation and materials used.!
!
Where sleeves containing a single conduit penetrate FIRE RATED walls, floors, partitions or slabs, fill and seal conduit to the sleeve with
a 1-part intumescent caulk/putty sealant creating a fire stop equal to or exceeding fire rating of construction material being penetrated.
Fire sealant shall prevent spread of flame, smoke, air and water through the sleeve and shall pass 3 hour test per ASTM E814 and UL
1479. Fire sealant shall be installed in accordance with manufacturer's written instructions. Where sleeves containing multiple conduits
or multiple cables penetrate FIRE RATED walls, floors, partitions, or slabs, fill and seal spaces between the conduits or cables and the
sleeve with 2-part intumescent foam sealant creating a fire stop equal to or exceeding fire rating of construction material being
penetrated. Fire sealant shall prevent spread of flame, smoke, air and water through the sleeve and shall pass 3 hour test per ASTMA
E814 and UL 1479. Fire sealant shall be installed in accordance with manufacturer's written instructions. Where sleeves penetrate
exterior walls, fill and seal ends around conduits and/or cables with duct sealant compound equal to Solorite KN--1146, or Link Seal.
Install seals in accordance with the manufacturer's recommendations to provide air tightness above ground and hydrostatic sealing below
grade. Caulking or other type mastic is not acceptable. Where wiring devices are placed in fire rated construction, fire rating of installed
assembly shall meet or exceed the rating of the construction.!
!
Telephone, data, CCTV, and security cabling shall be by owner's communications and security contractors. Obtain a copy of owners low
voltage plans and provide box, conduit, and pull strings to facilitate installation of low voltage devices by others.!
!
Provide for each voice and data outlet a 4x4 outlet box with pullstring to accessible ceiling space. In non-fishable construction, provide
3/4” conduit with pullstring between outlet box and accessible ceiling space.!
!
Provide for each CCTV location a 4x4 outlet box with pullstring to accessible ceiling space. In non-fishable construction, provide 3/4”
conduit with pullstring between outlet box and accessible ceiling space. Provide weatherproof gasketed cover plates for outdoor locations.!
!
120 Volt Switches shall be quiet toggle type with totally enclosed case, rated 20 ampere, specification grade, color as selected by
Architect.!
!
Dimmable switches shall be 120 volt switches rated for load controlled (i.e. incandescent, magnetic or electronic low voltage, fan speed,
or fluorescent). Switch shall be dimmable thru the entire range from 0 to 100%, with preset control and seperate on-off switch. Switches
shall be as manufactured by Lutron, Levition, or Pass & Seymour. Care shall be taken when derating switches for installation in
multi-gang switch boxes. Install switches with highest loads on outside of boxes to minimize the quantity of cooling fins (sides) removed.
Contractor shall be responsible to ensure quantity of sides removed does not derate switch below required capacity. Multiple switch
boxes shall be provided as required to maintain ratings of switches. All switches shall be installed in accordance with manufacturers
instructions.!
!
Standard duplex receptacles shall be polarized, duplex, parallel blade, U-grounding slot, specification grade, rated 20 amperes, 125 volts,
style and color as selected by Architect.!
!
GFI receptacles shall be 125V, 20 amp rated, as manufactured by Leviton or equal, style and color as selected by Architect. Trip
threshold and time shall be as required for the application in accordance with the NEC.!
!
Plates for Flush Devices shall be stype and color as selected by Architect.!
!
Contactors shall be permanent magnetic latched, electrically operated, mechanically-held type with number of poles and current rating as
shown. Operating coils shall be 120 volts as required. Contactors shall be housed in NEMA Type 1 enclosures with knockouts and
provisions for padlocking or incorporated in branch circuit or distribution panelboards as indicated. Provide hand-off-automatic switch in
cover to facilitate safe maintenance. Contactors shall be UL listed for switching 208 volt ballast inductive loads. Install, completely wire
and connect all systems in accordance with details on Drawings and manufacturer's instructions.!
!
Furnish and install all lighting fixtures specified on these plans, or by other consultants. Provide all interior and exterior lighting fixtures
complete with sockets, reflectors, diffusers, shades, holders, lamps, ballasts, protective devices and all other required appurtenances.
Prior to ordering lighting fixtures, verify exact type of ceiling to be used for each space. Coordinate with Division 15 to avoid conflicts
between lighting fixtures and Mechanical and Plumbing piping, ductwork, supports, fittings and equipment. Furnish to other trades,
plaster frames, trim rings, etc., where required.!
!
Motor and circuit disconnect means shall be a horsepower rated safety switch or a circuit breaker, each sized for the applied load and
system voltage having an interrupting capacity not less than maximum available short-circuit current of circuit on which applied.
Disconnects shall be sized in accordance with NEC and NEMA requirements. Safety switches shall be cartridge fuse type or unfused, as
required. Manual toggle type motor switches with overload protection may be used as motor disconnects for fractional horsepower
motors provided they meet NEC requirements including padlock provision. Safety switches shall be quick-make, quick-break and NEMA
Heavy Duty, Type HD. Disconnect enclosures: NEMA 1, NEMA 3R, NEMA 4 to suit application.!
!
Provide new Addressable Fire Alarm system as manufactured by Edwards. The system shall include, but not limited to: control panel,
dialer, alarm initiating and indicating peripheral devices, conduit, wire and accessories required to furnish a complete operational system.
The equipment and installation shall comply with the current provision of the National Fire Protection Association Standards, 70, 72, and
all local codes. All equipment shall be UL listed. Flashing lights shall be ADA approved, candela as required by location. Contractor shall
use equipment manufacturer or manufacturers representative for all system testing and programming.!
!
FIRE ALARM SUBMITTAL REQUIREMENTS: In addition, the contractor shall prepare a Fire Alarm system submittal to fulfill the
requirements of the local Fire Marshall. Submit (3) sets of Signed and Sealed plans prepared by a professional engineer or certified Fire
Protection Engineer for Fire Marshall review. The submittal shall include the following: Scaled plans indicating Fire Alarm work, Project
Name and Address, Square footage, Fire Alarm symbols list, Device matrix showing description and quantity of devices, Equipment Cut
sheets, Wiring information including size, type, and all point to point wire runs, Fire Alarm Riser diagram including initiating and
annunciating devices, Battery calculations and proposed battery capacity, and voltage drop calculations.!
!
Provide PVC conduit buried 30 inches minimum below finished grade, or as otherwise indicated, for services and feeders.!
!
Provide underground ducts in a straight line. Pockets where water can accumulate in conduits will not be permitted.!
!
All underground conduits shall be watertight. Dope threads of steel conduit before joining. PVC conduits shall be chemically bonded
around entire circumference of the conduit at each joint. Provide minimum length of 6 feet of rigid steel conduit when entering or running
under manholes, transformer pads, at building walls or foundations and on both sides of roads. Conduits under roads shall be rigid steel.!
!
Contractor shall include in his bid Unit Prices for each of the following:!
A. Each type of receptacle, including coverplate connected to area circuit. !
B. Voice outlet box with conduit and pullstring.!
C. Each type of switch, including coverplate connected to area circuit.!
D. 20/1 Homerun to Local Branch Circuit Panel.!
!
Circuit breakers used as elevator disconnects shall be listed, and shall capable of locking the breaker in the open position. The locking
provision shall remain in place with or without the lock installed. Portable means for adding a lock shall not be permitted.!
!
Electrical contractor shall ensure all electrical plans are furnished to the Elevator Contractor for inclusion with submission to Elevator
Inspector for review.!
!
Electrical contractor shall work closely with Elevator contractor to ensure work in areas under Elevator Inspector juristiction are approved
prior to installation. Make modifications as required to meet the requirements of the Elevator Inspector.!
!
Floor Outlets shall be provided as follows: Type A: Provide Legrand Evolution series 6AT with quadraplex receptacle. Data and AV
outlets shall be provided by Owners Low voltage contractor.2!
NEW JERSEY
35.!
!
!
36.!
!
!
37.!
!
!
!
!
38.!
!
!
39.!
!
!
40.!
!
!
!
41.!
!
42.!
!
!
43.!
!
44.!
!
!
45.!
!
!
!
!
!
!
!
!
!
!
!
!
46.!
!
!
47.!
!
!
48.!
!
!
49.!
!
!
50.!
!
!
!
!
!
!
!
50.!
!
!
51.!
!
!
52.!
!
53.!
!
!
!
!
!
54.!
!
!
!
!
!
55.!
!
!
!
!
!
!
56.!
!
!
!
!
!
57.!
!
!
!
!
!
!
58.!
!
59.!
!
60.!
!
!
!
61.!
!
!
!
!
!
62.!
!
!
63.!
!
!
64.!
!
!
65.
CITY OF ESTELL MANOR
0.9
Contractor shall provide all labor, materials, tools, apparatus and equipment required to complete his work in accordance with the contract
documents, codes, laws and ordinances, and accepted trade procedures.!
!
The contractor by his acceptance of the contract guarantees that all work installed shall be free from all defects in workmanship and
materials and that all apparatus furnished by him shall develop the capacities and characteristics specified. He further guarantees that if,
during a period of one (1) year from the date of the certificate of completion and acceptance of the work, any such defects in
workmanship, material or performance appear, such defects shall be remedied by him without cost to the owner. If the contractor fails to
remedy the defects as outlined within a reasonable length of time, to be specified in a notice from the owner's authorized representative
to the contractor, the owner will have such work done, and he will charge the cost to the contractor.!
!
The contractor shall visit the site before he submits his proposal. He shall examine all existing conditions which affect the work. The
submission of the proposal shall be considered evidence that this requirement has been fulfilled. No extra payment will be allowed for
additional work made necessary by the failure to visit the site.!
!
Electrical equipment shall be installed in a neat and workmanlike manner in accordance with latest and best practices of the trade. Only
mechanics skilled in this type of Work shall be employed and utilized by Contractor for this Division in the execution of this Work.!
!
The contract drawings are diagrammatic and indicate the general arrangement of all systems and work included in the contract. The
contract drawings are not to be scaled. The architectural contract drawings and details together with the other contract documents shall
be examined for all dimensional information.!
!
The contractor shall, without additional costs to the owner, make reasonable modifications in the layout of his work in order to prevent
conflicts with the work of other trades or for the proper execution of his work.!
!
The contractor shall provide and maintain in good order a complete set of blueline prints of the contract drawings. As the work
progresses, the actual location of all work shall be clearly recorded, including all changes to the contract and equipment size and type.
These prints shall be available at the site for inspection at all times. At the conclusion of the work, the contractor shall, at his own
expense, obtain a set of reproducibles of the original contract drawings, and utilizing the symbols on the contract drawings, shall
incorporate all "as built" data in a clearly legible and reproducible manner. All schedules shall be corrected to indicate "as built"
conditions. All revisions shall be incorporated on these reproducibles including all sketches and written directives. All concealed
equipment, mainfeeders, pull and junction boxes, etc. shall be dimensionally located from the building structure. As a condition for
acceptance of the work, the "as built" reproducibles and one (1) set of prints shall be signed, dated and delivered to the engineer.!
!
The contractor shall supply all labor required to perform all work which may be claimed by trade organizations within his jurisdiction. All
work shall be performed without any additional cost to the owner irregardless of which section of the contract documents the work is
described. The contractor shall be responsible to verify with all local organizations the extent of any collective bargaining agreements
and/or any jurisdictional decisions rendered regarding disputes between the respective trades, and provide and install his work in
accordance with the accepted trade practice in the area.!
!
The entire installation shall conform with all pertinent codes and regulations of the local, municipal, county, state, and federal authorities,
The National Board of Fire Underwriters, the codes of the International Codes Council, the codes of the National Fire Protective
Association, the New Jersey Uniform Construction Codes, and all other regulatory bodies having jurisdiction. All materials and equipment
shall bear the stamps or seals of the NFPA, ASME, NEMA, IEEE, UL and other recognized industry regulatory groups.!
!
The contractor shall give all necessary notices, obtain all permits, pay all governmental taxes, fees and other costs in connection with his
work. He shall file all necessary plans, and prepare all other documents including additional detailed plans that are required for
compliance with all applicable laws, ordinances, rules and regulations.!
!
Before starting any work under this Contract, file for inspection with the Middle Department Inspection Agency or other certified Agency.
Upon completion of the work, furnish Electrical Certificates from said Agency for all Electrical equipment and systems installed or
furnished and installed as part of the work.!
!
The contractor shall at all times keep the premises free from the accumulation of waste materials or rubbish caused by his employees or
work. At the completion of the work, he shall remove all superfluous materials, equipment and debris resulting from the work.!
!
All feeder wiring shall be soft drawn copper of 98% conductivity, installed in code conforming metallic raceways or cable assemblies. All
wiring shall be copper, thermoplastic covered insulated Type 75° C. THW or 90° C. Type THHN, 600 volt rating. Wire No. 8 AWG and
smaller shall be solid. Wire larger than No. 8 shall be stranded.!
!
All wiring shall be insulated copper conductors installed in code conforming raceways or cable assemblies.!
!
All wiring shall be run concealed wherever possible. All exposed conduit shall be EMT or rigid steel as required. Flexible conduit shall be
smooth liquidtight with appropriate fittings. Conduit drops from above ceiling shall be structurally secured and supported. Cable
assemblies used for branch circuits shall not be run exposed. Cable assemblies shall be permitted exposed for final connections to
Mechanical and Plumbing equipemnt and shall be limited to 6 feet total length, routing shall not interfere with equipment workspace.!
!
Where conductors connect directly to equipment, the insulation temperature rating of the conductor shall meet or exceed the equipment
temperature rating.!
!
Where dimmers are provided, install a separate neutral conductor for each branch circuit.!
!
Color code conductors to designate neutral conductor and phases.!
!
Exercise great care in maintaining a uniform and consistent arrangement of phase conductors on all systems. Throughout the entire
wiring systems, each phase conductor must always be in the same physical position with respect to the other phase wires at equipment
terminals.!
!
Grounding shall comply with Article 250 of NEC and to approval of local Underwriters inspection authorities.!
!
Panelboards shall be dead front type with plated aluminum bus, bolt-on breakers, fully rated neutral bus and grounding bus block. Cabinet
shall be code gauge galvanized steel, NEMA 1, minimum 20” wide, 5-3/4”deep. Cover shall have door and trim and adjustable clamps,
gray baked finish, and tumbler type key lock. Directories shall be typed. “Spaces” shall be fully bussed and drilled, ready for breaker
installation.!
!
Circuit Breakers shall be molded case, bolted, thermal magnetic trip in each pole, enclosure-compensated to carry full rated load at 40°C.,
trip-free handles shall clearly indicate trip, on and off condition, quick-make and quick-break action. Lugs approved for copper and
aluminum conductors and compression type. Ground Fault type breakers shall be provided with thermal and magnetic protection, UL
Class A, 5 milliampere ground fault sensitivity, where required. Circuit breakers used as switches in 120 and 277 volt circuits feeding
incandescent, fluorescent, and/or HID fixtures shall be approved for such use and marked "SWD", per NEC. Circuit breakers serving
Heating and Air Conditioning equipment shall be HACR rated.!
!
Provide all labor, materials and equipment required to provide electric power to meet the requirements for heating, ventilating,
air-conditioning and plumbing systems. Fully coordinate installation of electrical wiring and equipment with installation of electrically
operated mechanical equipment provided by the Mechanical and Plumbing Contractors. Install disconnect switches, motor starters, and
control transformers furnished by Mechanical and Plumbing Contractors. Provide final equipment electrical terminations. All internal
equipment wiring shall be by manufacturer.!
!
Test equipment, including panelboards and all other equipment and wiring for unintended grounds, short circuits, open circuits, continuity,
current leakage, and that equipment will operate as specified. Test feeders for insulation resistance; for load balance of the final
installation, and for overall operation of systems. Furnish labor and material required for making such tests and make corrections
necessary to balance the load and to obtain proper operation.!
!
Where existing facilities are being altered, disconnect and remove or relocate all existing electrical work that interferes with or is
necessary because of new construction as specified, shown or required.!
!
Perform alterations and additions to present electrical systems with a minimum interruption in the operation of these systems. Obtain
written clearance from Owner for such interruptions and schedule same at whatever time specified in writing by Owner.!
!
Circuit breakers made spare due to demolition shall be set in off position and labeled 'SPARE'.!
!
Where specified or required, extend existing systems or tie into same to provide a complete coordinated electrical system to satisfaction
of Owner and Architect.!
!
Perform all work necessary to permit operation of all existing systems during the construction period. Provide and maintain applicable
approved temporary wiring to meet this requirement.!
!
Demolish and remove existing electrical equipment, feeders and conduit no longer required by new construction.!
!
Perform alteration of utilities and services in accordance with the rules, regulations and requirements of the involved utility companies and
regulatory agencies having jurisdiction.!
!
Arrange and pay for the relocation, disconnection or removal of existing utilities and services where shown and where such utilities or
services interfere with new construction, whether shown or not. Provide all excavation, backfilling and paving, manholes, and cables
required by such work.!
!
Fully coordinate installation, wiring and connection of service and distribution systems with the owner, Atlantic City Electric and all
contractors.!
!
Coordinate with Power Company; inform them of the proposed work; obtain their approval before beginning work; comply with their
requirements for details of installation and materials used.
ATLANTIC COUNTY,
1.1
0.2
1.!
!
!
2.!
!
!
!
!
!
!
3.!
!
!
!
4.!
!
!
5.!
!
!
!
6.!
!
!
7.!
!
!
!
!
!
!
!
!
8.!
!
!
!
!
!
9.!
!
!
!
!
10.!
!
!
!
11.!
!
!
!
12.!
!
!
13.!
!
!
!
14.!
!
15.!
!
!
!
!
16.!
!
!
17.!
!
18.!
!
19.!
!
!
!
20.!
!
21.!
!
!
!
!
22.!
!
!
!
!
!
!
23.!
!
!
!
!
!
24.!
!
!
!
!
25.!
!
!
26.!
!
!
27.!
!
28.!
!
!
29.!
!
!
30.!
!
31.!
!
!
32.!
!
!
!
33.!
!
!
34.
PARTNER: GERALD S. BLACKMAN, AIA, PP, NCARB
ASSOCIATE: STEVEN J. BOLOGNO, RA
0.7
6.1
ELECTRICAL SPECIFICATIONS
Cir.
No.
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
Total
PRINCIPAL: DANIEL A. SHOUSKY AIA, PP, NCARB
PRINCIPAL: PAUL A. KISS AIA, PP, NCARB
1.1
1.1
Cir.
Bkr.
FOUNDER: JOHN J. OLIVIERI (1956-1999)
Wire
Size
#12
#12
#12
#12
#12
Total
Cir.
No.
43
45
47
49
51
53
55
57
59
61
63
65
67
69
71
73
75
77
79
81
83
Total
0.4
5.8
Wire
Size
Space
Space
Space
Space
Space
Space
Space
Space
Space
Space
Space
Space
Space
Space
Space
Space
Space
Space
Spare
Spare
Spare
0.4
Load Summary by Type
Connected Appliance
Connected Lighting
Connected Motor
Connected Heating
Connected Air Conditioning
Total
ELBA
Cir.
Bkr.
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
C
GERALD S. BLACKMAN,
AIA, PP, NCARB
N.J. LIC. No. A1 17113
CONSULTING ENGINEERS
Cir.
No.
1
3
5
7
9
11
13
15
17
A
Description
210 E. STREET ROAD
TELE # (215)322-7711
SUITE 2D
FAX # (215)322-7709
FEASTERVILLE, PA 19053
PANEL
4.8
5.8
6.1
16.7
C
208/120V - 3Ø - 4W
Load - KW
B
0.2
4.8
Phase (KW)
A
B
C
Total
42 POLE
ESTELL MANOR PARK MANSION
VETERANS MUSEUM
Offices 201, 204 Lighting
Rooms 200, 202 Lighting
Room 203, 209, and 205 Lighting
Rooms 206, 207, 208 Lighting
Attic Lighting
Office 201 Receptacles
Office 204 Receptacles
Rooms 200, 202 Receptacles
Office 203 Receptacles
Toilet Room 209 Receptacle
Office 205 Receptacles
Workroom 206 Receptacles
Rooms 207, 208 Receptacles
Attic 305-309 Receptacles
Attic 300, 302, 303, 304 Receptacles
AHU-3
AHU-4
Hand Dryer Room 209
Flood Lighting Second Floor
Attic 301 Receptacles
Spare
125A MLO
22 KAIC
Load - KW
A
B
0.3
0.1
ARCHITECTS AND PLANNERS
www.olivieriarchitects.com
Description
17 WEST KNIGHT AVENUE, SUITE 200, COLLINGSWOOD, NEW JERSEY 08108
PHONE: (856) 854-0580
FAX: (856) 854-0993
Wire
Size
#12
#12
#12
#12
#12
#12
#12
#12
#12
#12
#12
#12
#12
#12
#12
#12
#12
#12
#12
#12
HOLSTEIN WHITE, INC.
A2A
Cir.
Bkr.
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
20/1
OSK Design Partners P.A.
Cir.
No.
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
39
41
Total
THIS PLAN IS NOT VALID UNLESS A RAISED SEAL IS AFFIXED HERETO
PANEL
Jeffrey E. Holstein, P.E.
License No. NJ GE46443
Authorization NO; 2GA28143700
REVISIONS:
DATE:
7-1-2014
SCALE:
AS NOTED
DRAWN BY: JAC
CHK'D BY:
ISSUED TO ATLANTIC COUNTY FOR REVIEW
1
06-21-2013
DRAWING ISSUE
No.
DATE
JEH
PROJECT No.
DA09057
E5.1
e
w
Je
r
s
e
y
S
t
a
t
e
H
i
18
18
18
10-WAY
DISTRIBUTION BOX
TREE TO BE
REMOVED (typ.)
18
IUS
' RAD
(typ.)
18
150
17
g
h
w
a
y
17
17
17
17
17
17
DS
AN
TL
WE FER
F
BU
FRONT
TOP
SIDE
, NCARB
0'
15
#
5
0
5"