Oct 01, 2014 Oct 01, 2014 Oct 01, 2014 Oct 01, 2014 Oct 01, 2014 Oct 01, 2014 Oct 01, 2014 Oct 01, 2014 Oct 01, 2014 Oct 01, 2014 Oct 01, 2014 Oct 01, 2014 3. ELECTRICAL EQUIPMENT AND COMPONENTS SHALL BE LOCATED AT OR ABOVE BASE FLOOD ELEVATION OR GRADE ELEVATION, WHICHEVER IS HIGHER AS PER IBC 1612.1. 4. PANELS, SWITCHBOARDS, MOTOR CONTROL CENTERS ARE TO BE FULLY RATED. - NO SERIES RATED EQUIPMENT IS ALLOWED. 5. 6. 7. 8. COMPLETELY BOND AND GROUND ENTIRE ELECTRICAL SYSTEM IN ACCORDANCE WITH NFPA 70 AND THE CURRENT NEC ADOPTED BY THE LOCAL AUTHORITY HAVING JURISDICTION ARTICLE 250 IN IT'S ENTIRETY. CONTRACTOR TO COORDINATE ALL UTILITY SERVICE REQUIREMENTS WITH LOCAL UTILITY SERVICE PROVIDER FOR ALL UTILITIES REQUIRED BY OWNER/CLIENT (ELECTRICAL, PHONE, CABLE, DATA. ETC.) AND PROVIDE A FULL INSTALL INCLUDING CONDUIT IN ACCORDANCE WITH RESPECTIVE UTILITY'S REQUIREMENTS. PROVIDE MONITORED SECURITY SYSTEM APPROVED BY THE CITY OF KENNER. COORDINATE WITH TENANT PRIOR TO BIDDING. KEYPADS, MOTION DETECTORS, AND CONTACTS HAVE BEEN SHOWN ON THESE PLANS. CONTRACTOR IS RESPONSIBLE FOR COORDINATION WITH GENERAL CONTRACTOR ON THE APPLICATION FOR PERMIT AND REMITTANCE OF ALL FEES. IN ADDITION, CONTRACTOR TO PROVIDE FINAL INSPECTION CERTIFICATE. 9. INCLUDE THE COSTS TO INCORPORATE ALL CODES AND ORDINANCE REQUIREMENTS INTO THE BASE BID AND INSTALLATION OF WORK FOR THIS PROJECT. NO ADDITIONAL FUNDS WILL BE ALLOCATED FOR WORK TO CONFORM TO REGULATIONS AND REQUIREMENTS AND/OR TO OBTAIN APPROVAL OF WORK. 53. ALL TERMINATIONS SHALL BE LISTED FOR 75 DEGREES C UNLESS OTHERWISE NOTED. 29. BATTERY BACKED SOUNDER BASE SMOKE DETECTORS TO BE INSTALLED IN ACCORDANCE WITH NFPA 72 IN ITS ENTIRETY. 30. UPON COMPLETION OF THE PROJECT, THE CONTRACTOR SHALL PROVIDE A COMPLETE SET OF THE DRAWINGS USED STRICTLY FOR MARK-UPS WHICH SHALL INCLUDE ALL REVISIONS, SKETCHES, ETC., REQUIRED DURING CONSTRUCTION. CONTRACTOR SHALL INSURE THAT ALL CIRCUITRY IS SHOWN AS WIRED IN THE FIELD AND HAS ACCURATE HOMERUN DESIGNATIONS. THE CONTRACTOR SHALL MARK THESE DRAWINGS RED FOR ADDITIONS AND GREEN FOR DELETIONS TO INDICATE EXACT, AS INSTALLED CONDITIONS. 31. UPON DOCUMENTED APPROVAL OF THE ARCHITECT, MOUNTING HEIGHTS MAY BE ADJUSTED. LENGTH OF RECEPTACLES SHALL RUN VERTICALLY. DO NOT MOUNT OUTLETS BACK TO BACK ON OPPOSITE SIDES OF PARTITIONS. 32. CONTRACTOR SHALL VISIT THE SITE OF THE PROPOSED WORK TO UNDERSTAND THE COMPLEXITY, RESTRICTIONS, AND ALL THE REQUIREMENTS TO PERFORM WORK OF THESE DOCUMENTS IN SAID FACILITY. NO ADDITIONAL COMPENSATION SHALL BE ALLOWED TO THE SUCCESSFUL BIDDER FOR FAILURE TO BE SO INFORMED. 33. RACEWAYS AND OUTLETS PASSING THROUGH OR INSTALLED IN FIRE RATED CONSTRUCTION SHALL BE SEALED WITH U.L LISTED FIRE RATED SEALANT SYSTEM IN ACCORDANCE WITH SEALANT MANUFACTURERS' RECOMMENDATIONS. WHERE ELECTRICAL RACEWAYS ARE INSTALLED THROUGH RATED FLOORS OR WALLS, THE CONTRACTOR SHALL PROVIDE APPROPRIATE FITTINGS APPROVED BY ALL REQUIRED LOCAL AUTHORITIES FOR THE INTENDED APPLICATION. REFER TO ARCHITECTURAL DRAWINGS FOR ADDITIONAL INFORMATION. 34. RECESSED FIXTURES IN FIRE RATED CEILINGS AND RETURN AIR PLENUMS SHALL BE RATED FOR THE FIRE RATING OF THE CEILING OR SHALL BE FULLY ENCLOSED IN A FIRE RATED HOUSING ACCEPTABLE TO AUTHORITY HAVING JURISDICTION. 35. MAINTAIN FIRE RATING OF WALLS, FLOORS, AND CEILINGS WHEN PERFORMING WORK AND INSTALLING DEVICES, BOXES, ETC. USE FIRE CAULK, "PUTTY PADS," OR OTHER APPROVED AND APPROPRIATE METHODS TO MAINTAIN RATING. 39. ALL BATTERIES ASSOCIATED WITH TENANT, OWNER OR CONTRACTOR PROVIDED EQUIPMENT TO BE INSTALLED IN BUILDING SHALL BE NON-GASSING SEALED MAINTENANCE FREE TYPE. SUBMIT SPECIFICATIONS TO ENGINEER FOR APPROVAL. BATTERY BANKS WHICH EXCEED 500 LBS. SHALL BE SUBMITTED TO STRUCTURAL ENGINEER FOR APPROVAL. EQUIPMENT TO BE INSTALLED IN BUILDING WITH BATTERIES THAT DON'T MEET THIS REQUIREMENT WILL REQUIRE SPECIAL PERMISSION BY THE OWNER BEFORE THE EQUIPMENT CAN BE INSTALLED IN THE BUILDING. 12. PROVIDE TAMPER PROOF RECEPTACLES IN ACCORDANCE WITH NEC 406.12 FOR ALL DWELLING UNIT RECEPTACLES EXCEPT FOR THOSE LOCATED IN ATTICS OR THOSE LOCATED MORE THAN 5'-6" AFF. 40. SIZING OF MOTOR-RELATED ELECTRICAL COMPONENTS, INCLUDING FEEDERS, BRANCH CIRCUITS AND OVERCURRENT PROTECTION ARE BASED ON RATINGS INDICATED. VERIFY "ACTUALLY INSTALLED" MOTOR AND APPLIANCE RATINGS AND LOADS AND PROVIDE CORRECTLY SIZED MOTOR-RELATED ELECTRICAL COMPONENTS. REFLECT ALL CHANGES IN THE RECORD DRAWINGS. COORDINATE WITH ELECTRICAL ENGINEER IF NECESSARY. 13. PROVIDE ARC FAULT CIRCUIT INTERRUPTERS TYPE CIRCUIT BREAKERS IN DWELLING UNITS FOR ALL 15 AND 20 AMPERE, 120 VOLT, CONVENIENCE RECEPTACLE CIRCUITS FOR FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROOMS, RECREATION ROOMS, CLOSETS, HALLWAYS, OR SIMILAR ROOMS OR AREAS. 14. MULTI-WIRE BRANCH CIRCUITS SHALL BE PROVIDED WITH A COMMON DISCONNECT AT THE SOURCE. THE DISCONNECT SHALL BE EITHER A MULTI-POLE CIRCUIT BREAKER OR INDIVIDUAL CIRCUIT BREAKERS WITH HANDLE TIES. 15. CONTRACTOR SHALL PROVIDE ALL NECESSARY TESTING EQUIPMENT (INCLUDING 24VDC SYSTEM) AND PERSONNEL FOR MAKING TEST. ALL TEST SHALL BE MADE IN THE PRESENCE OF THE OWNER OR A REPRESENTATIVE THEREOF. WHEN TEST RESULTS ARE NOT SATISFACTORY, THE CONTRACTOR SHALL MAKE ALL NECESSARY ADJUSTMENTS AND/OR CHANGES AND SHALL NOTIFY OWNER THAT HE IS READY FOR ANOTHER TEST. CONTRACTOR SHALL REPEAT TEST OR TESTS WHICH DISCLOSED FAULTY OR DEFECTIVE WORK OR EQUIPMENT AND SHALL MAKE SUCH ADDITIONAL TESTS AS OWNER DEEMS NECESSARY. 16. PROVIDE COMPLETE INSTALLATION, INCLUDING ALL MINOR ITEMS. THIS INCLUDES ELECTRICAL, PHONE, CABLE, DATA, AS WELL AS ANY OTHER SYSTEMS SHOWN IN THESE DRAWINGS. PROVIDE ALL MOUNTING HARDWARE FOR LIGHTING FIXTURES AND OTHER ELECTRICAL EQUIPMENT REQUIRED FOR A COMPLETE INSTALL. 17. DRAWINGS ARE DIAGRAMMATICAL. ALL ELECTRICAL EQUIPMENT LOCATIONS ARE APPROXIMATE ONLY. FOR ALL MEASUREMENTS, USE ARCHITECTURAL, MECHANICAL OR OTHER RESPECTIVE DIVISION'S PLANS AND FIELD SURVEYS. COORDINATE WITH AIR CONDITIONING WORK, CABINET WORK, PARTITION WORK, ETC., WHEN REQUIRED. LAYOUT OF EQUIPMENT, ACCESSORIES, SPECIALTIES, WIRING AND CONDUIT SYSTEMS ARE STRICTLY DIAGRAMMATIC UNLESS SPECIFICALLY DIMENSIONED, AND DO NOT INDICATE EVERY REQUIRED FITTING, ELBOW, TRANSITION, JUNCTION BOX OR SIMILAR ITEMS THAT ARE REQUIRED FOR A COMPLETE INSTALLATION. 18. PROVIDE ALL REQUIRED OVERCURRENT AND DISCONNECTION MEANS FOR EQUIPMENT SPECIFIED BY OTHER DISCIPLINES, WHETHER SPECIFICALLY INDICATED ON THESE DRAWINGS OR NOT. DEVICE WILL HAVE APPROPRIATE SIZE, NUMBER OF POLES AND NEMA RATING FOR INTENDED APPLICATION. 38. GANGABLE BOXES ARE NOT TO BE USED. LAMP CFL 200W F2 WALL MOUNT FLUORESCENT COOPER 22DW1T53UEB FLUOR T5 F3 VANITY LIGHT COOPER 60024WT5/2/14120V* FLUOR T5 54. ALL CABLE SHALL BE COPPER UNLESS OTHERWISE NOTED. 55. BRANCH CIRCUITS WITH UNMARKED CONDUCTOR AMOUNTS AND SIZES SHALL DEFAULT TO 2#12,#12G,1/2"C. 56. CONTRACTOR TO COORDINATE ALL UTILITY SERVICE REQUIREMENTS WITH LOCAL UTILITY SERVICE PROVIDER. (ELECTRICAL, PHONE, CATV, ECT.) F4 57. PRIOR TO ROUGHING-IN ANY WIRING OR DEVICES, CONFIRM EXACT LOCATIONS WITH ARCHITECT/OWNER. 58. ALL BRANCH CIRCUITRY INSTALLATION AND LOADING SHALL COMPLY WITH CURRENT NEC. F4A 59. NO MORE THEN (10) DUPLEX OUTLETS ARE ALLOWED ON A 20A BRANCH CIRCUIT. 60. DO NOT LOAD LIGHTING BRANCH CIRCUITS MORE THAN 80%. 61. WHERE NEW LIGHTS OR RECEPTACLES ARE DESIGNATED TO BE CONNECTED TO AN EXISTING CIRCUIT, CONTRACTOR SHALL TRACE EXISTING CIRCUIT TO DETERMINE CIRCUIT LOADING. THE LOAD ON A 20 AMP CIRCUIT SHALL NOT EXCEED 16 AMPS (80%). WHERE THIS CANNOT BE ACHIEVED, CONTRACTOR SHALL CONTACT THE ENGINEER FOR ALTERNATIVE CIRCUITING INSTRUCTIONS. F4B F5 * FINISH TO BE SELECTED BY ARCHITECT 6" RECESSED CAN COOPER HALO HALO 6" RECESSED CAN, IC RATED FOR DIRECT INSULATION CONTACT, STANDARD LAMP BASE, PROVIDE WITH CFL LAMP, WHITE BAFFLE AND TRIM. 6" RECESSED CAN COOPER HALO HALO 6" RECESSED CAN, IC RATED FOR DIRECT INSULATION CONTACT, STANDARD LAMP BASE, PROVIDE WITH CFL LAMP, WHITE SHOWER LENS. 6" RECESSED CAN COOPER HALO HALO 6" RECESSED CAN, IC RATED FOR DIRECT INSULATION CONTACT, SUITABLE FOR ANGLED MOUNTING, STANDARD LAMP BASE,PROVIDE WITH CFL LAMP, WHITE BAFFLE AND TRIM. KITCHEN PENDANT PROGRESS LIGHTING P5078-09 CFL 26W CFL 26W CFL 26W 62. ARCHITECT BASE DRAWINGS HAVE PREFERENCE. ALL DISCREPANCIES WITH BASE DRAWINGS IN ELECTRICAL SET TO BE CLARIFIED WITH CONTRACTOR, ARCHITECT AND ELECTRICAL ENGINEER. F6 STAIR PENDANT COOPER 10640P1ST5/3/21120NA *COORDINATE FABRIC SELECTION WITH ARCHITECT FLUOR 63W 63. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN FOR CEILING TYPES AND EXACT LOCATION OF ALL FIXTURES. VERIFY CEILING TYPES WITH ARCHITECT PRIOR TO ORDERING LIGHT FIXTURES TO ENSURE COMPATIBLE FIXTURE TRIMS AND MOUNTING HARDWARE. F7 GROUND MOUNTED FLOOD LIGHT PROVIDE STANDARD 2 LAMP FLOOD LIGHT WITH WIRE GUARDS REPAIR MOUNTING AND CONDUIT AS NECESSARY INCAND (2) 100W F8 SURFACE MOUNTED FLUORESCENT LITHONIA 11432REWH FLUOR (4) 32W SURFACE MOUNTED FLUORESCENT LITHONIA 11432REWH FLUOR (4) 32W F8 EMERGENCY LIGHT ATLITE PC1-10 BLAKE MICHAEL HOSLI License No. 38688 43. SHOP DRAWINGS SHALL BE SUBMITTED FOR APPROVAL TO ARCHITECT PRIOR TO CONSTRUCTION FOR PANELBOARDS, CIRCUIT BREAKERS, LIGHT FIXTURES, TRANSFORMERS, DISCONNECT SWITCHES, CONTROL DEVICES, WIRING DEVICES AND SPEAKER/BACK BOXES CORD SETS FOR ELECTRICAL EQUIPMENT (DRYER, KITCHEN EQUIPMENT). OPERATION AND MAINTENANCE MANUALS SHALL BE SUBMITTED FOR PANELBOARDS, TRANSFORMERS, LIGHT FIXTURES WITH EMERGENCY BATTERY PACKS AND ANY OTHER EQUIPMENT UNDER THIS CONTRACT REQUIRING REGULAR OPERATION OR MAINTENANCE. 44. CONTRACTOR SHALL CAREFULLY INVESTIGATE STRUCTURAL CONDITIONS, WALL AND CHASE LOCATIONS AND ROOM FINISHES AND MAKE ACTUAL MEASUREMENTS ON THE JOB SO THAT ALL ELECTRICAL EQUIPMENT SUCH AS PANELBOARDS, SWITCHES, RECEPTACLES, LIGHTING FIXTURES, FIRE ALARM STATIONS, HORNS, ANNUNCIATORS, CONDUITS AND ACCESSORIES SHALL HAVE ADEQUATE CLEARANCES AS REQUIRED BY NEC AND BY THE MANUFACTURER'S REQUIRED INSTALLATION PRACTICES. ALL EQUIPMENT SHALL BE CONNECTED IN A WAY THAT ALLOWS AMPLE MAINTENANCE SPACE AND PASSAGE SPACE. 45. A WARRANTY PERIOD OF ONE YEAR FROM THE DATE OF ACCEPTANCE OF FINAL COMPLETION OF THE PROJECT SHALL APPLY TO ALL ELECTRICAL EQUIPMENT FURNISHED AND TO ANY ELECTRICAL WORK FURNISHED UNDER THESE SPECIFICATIONS. CONTRACTOR SHALL REPAIR OR REPLACE ANY DEFECTS IN WORKMANSHIP, DESIGN OR MATERIALS AT HIS OWN EXPENSE. WARRANTY WORK SHALL BE PERFORMED WITHIN A REASONABLE TIMEFRAME AS SOON AS POSSIBLE AFTER THE DISCREPANCY IS NOTICED. 20. IF A CONFLICT OCCURS BETWEEN DRAWINGS AND/OR SPECIFICATIONS, BID THE GREATER QUANTITY AND/OR QUALITY. 47. PROVIDE TYPEWRITTEN PANELBOARD SCHEDULES TO PANELBOARD DOORS DEPICTING THE FINAL AS-BUILT CONDITIONS AT PROJECT COMPLETION. INDICATE DEVICE AND ROOM I CA L E NG I N EE 2014/10/02 42. PROVIDE INTEGRAL CONTROL TRANSFORMERS WITH OVERCURRENT PROTECTION AS REQUIRED FOR MECHANICAL EQUIPMENT. SEE MECHANICAL DRAWINGS FOR ADDITIONAL INFORMATION AND REQUIREMENTS. 19. ALL ADJUSTABLE FIXTURES SHALL BE LOCATED AND PROPERLY AIMED AS DIRECTED BY THE ARCHITECT OR LIGHTING DESIGNER. ALL AIMING OF BUILDING FACADE LIGHTING SHALL BE PERFORMED BY CONTRACTOR AT NIGHT. ADJUSTABLE SUSPENDED FIXTURES HUNG WITH CHAIN OR CABLE SHALL HAVE SLACK IN THE SUPPORT AVAILABLE TO MOVE THE FIXTURE AS DIRECTED BY ARCHITECT OR LIGHTING DESIGNER. PROFESSINAL ENGINEER IN ATLITE LC2-R-U 41. PROVIDE HACR TYPE CIRCUIT BREAKERS FOR HVAC EQUIPMENT. VERIFY SIZE WITH MECHANICAL EQUIPMENT SUPPLIER AND/OR MANUFACTURER. 46. CONTRACTOR SHALL CONTINUOUSLY MAINTAIN ADEQUATE PROTECTION OF STORED MATERIALS AND INSTALLED WORK. ALL FIXTURES AND EQUIPMENT SHALL BE TIGHTLY COVERED WITH SHEET POLYETHYLENE OR WATERPROOF TARPAULIN AND PROTECTED AGAINST DIRT, RUST, MOISTURE, CHEMICAL AND MECHANICAL INJURY REGARDLESS OF LOCATION. MATERIALS SHALL NOT BE STORED DIRECTLY ON EARTH ON IN AREAS WHERE THEY WILL BE SUBJECT TO PHYSICAL INJURY FROM VEHICLE TRAFFIC OR CONSTRUCTION EQUIPMENT. CONDUIT OPENINGS SHALL BE CAPPED OR PLUGGED DURING INSTALLATION. KEEP STOCK OF MATERIAL AND EQUIPMENT STORED ON THE PREMISES IN A NEAT AND ORDERLY MANNER. OF LOU I S I TE AN A T TR UNIVERSAL EXIT SIGN WITH HEADS 2011 by Linfield, Hunter & Junius, Inc. CFL 26W A 11. PROVIDE GROUND FAULT CIRCUIT INTERRUPTERS TYPE RECEPTACLES FOR ALL 15 AND 20 AMPERE, 120 VOLT, CONVENIENCE RECEPTACLES IN BATHROOMS, KITCHEN AREAS, EXTERIOR AND WITHIN 6 FOOT OF ALL SINKS. IN DWELLING UNITS PROVIDE GROUND FAULT CIRCUIT INTERRUPTERS TYPE RECEPTACLES FOR ALL 15 AND 20 AMPERE, 120 VOLT, CONVENIENCE RECEPTACLES IN BATHROOMS, OUTLETS ABOVE THE KITCHEN COUNTER, HVAC LOCATIONS, OUTDOOR OUTLETS, AND WITHIN 6 FOOT OF ALL SINKS IN LAUNDRY, UTILITY AND WET BAR LOCATIONS. 37. "F" CLIPS AND OTHER "OLD WORK" STYLE BOXES ARE NOT TO BE USED. CATALOG HUNTER 52060 EC 36. PROVIDE CONDUIT SEALING FITTINGS ON THE EXTERIOR SIDE OF THE CONDUIT ENTRIES INTO ALL COOLERS, FREEZERS AND REFRIGERATED SPACES TO PREVENT CONDENSATION FROM FORMING IN ELECTRICAL CONDUITS AT THE THERMAL TRANSITION BOUNDARIES. DESCRIPTION FAN WITH LIGHT KIT 52" EL 10. WORKMANSHIP TO MEET N.E.C.A. GUIDELINES. PUT INTO OPERATION AND TEST ALL ELECTRICAL EQUIPMENT. ALL CIRCUITS SHALL BE TESTED BY CONTRACTOR FOR PROPER VOLTAGE AND PHASE ROTATION; CONTINUITY; PROPER POLARITY; PROPERLY FUNCTIONING GROUND FAULT INTERRUPTERS AND OTHER OUTLETS AND EQUIPMENT; AND FOR ELECTRICAL ISOLATION OF ALL UNGROUNDED CONDUCTORS FROM GROUND AND FROM THE CONDUIT SYSTEM. CONTRACTOR SHALL BALANCE THE LOADS ON EACH PANEL TO WITHIN 15% BETWEEN MAXIMUM AND MINIMUM CURRENTS. TAG F1 3608 18th Street, Suite 200 Metairie, Louisiana 70002 SUBMIT EQUIPMENT INFORMATION FOR ENGINEER REVIEW FOR PANELBOARDS, DISCONNECTS, RECEPTACLES, SWITCHES, PLATES, CONDUIT, LIGHTING FIXTURES, SMOKE DETECTORS, SECURITY SYSTEM DEVICES, ETC. 52. EXISTING CONDITIONS TAKEN OFF OF BUILDING PLANS. CONTRACTOR SHALL VERIFY EXISTING CONDITIONS IN FIELD PRIOR TO CONSTRUCTION. FIXTURE SCHEDULE IN G 2. 28. PROVIDE EXPANSION AND DEFLECTION FITTINGS FOR CONDUITS CROSSING EXPANSION JOINTS. PROVIDE BONDING JUMPERS FOR ALL EXPANSION FITTINGS. 51. COORDINATE PHASING AS DIRECTED BY ARCHITECTURAL DRAWINGS AND THE GENERAL CONTRACTOR. MAKE ALL TEMPORARY CONNECTIONS NECESSARY ACCORDING TO ELECTRICAL DEMOLITION NOTES. R THE TERM "PROVIDE" MEANS TO FURNISH AND INSTALL. 27. RACEWAYS PENETRATING THROUGH ANY ROOF SHALL HAVE ROOF PITCH POCKETS AND FLASHING WITH CAULKING AND PIPE SLEEVE. INSTALLATION SHALL BE WATERTIGHT. ROOF MOUNTED CONDUIT SYSTEMS SHALL BE INSTALLED ON SYNTHIC RECYCLED RUBBER SUPPORT BASES SPACED TO MEET NEC REQUIREMENTS FOR THE SIZE OF THE CONDUIT. APPROVED BY DATE: 10/1/2014 1. 26. ALL ELECTRICAL DISTRIBUTION EQUIPMENT SHALL BE OF THE SAME MANUFACTURER, INCLUDING: PANELBOARDS, DISCONNECTS, ETC. 50. THESE DRAWINGS HAVE BEEN COORDINATED WITH MECHANICAL AND PLUMBING DRAWINGS. ELECTRICAL CONTRACTOR TO COORDINATE FUSE, CIRCUIT BREAKER, WIRE, CONDUIT, DISCONNECT, ETC. SIZES WITH MANUFACTURERS' RECOMMENDATIONS OF EQUIPMENT AND UNITS ACTUALLY INSTALLED AND MODIFY AS NECESSARY TO ACCOMMODATE. CHECKED BY 6. 25. ALL WORK SHALL BE PROPERLY SUPPORTED FROM THE BUILDING STRUCTURE IN AN APPROVED MANNER WITH A SUPPORT DEVICE THAT IS LISTED FOR THE USE AND FASTENED TO BUILDING CONSTRUCTION WITH APPROVED SUPPORTS LISTED FOR USE. PROJ. NO. 12-23 DATE 10/02/2014 SHEET NO. OF SHEETS DRAWN BY 3. 4. 5. 49. NO INSTALLATION WILL BE CONSIDERED COMPLETE UNTIL THE PROPER OPERATION OF ALL ELECTRICAL EQUIPMENT HAS BEEN DEMONSTRATED TO THE SATISFACTORY OF THE OWNER OR ITS AUTHORIZED REPRESENTATIVE. ALSO, ANY RECORD DRAWINGS, BOOKS NECESSARY TO MAINTAIN OR REPLACE ANY CONTRACTOR SUPPLIED MATERIAL SHALL BE COMPILED AND PRESENTED TO THE OWNER IN A FORM SUITABLE FOR REPRODUCTION. THIS SHEET 24. ALL ELECTRICAL DEVICES SHOWN BEING LOCATED IN EXISTING WALLS SHALL BE CONCEALED AND NOT SURFACE MOUNTED. WALLS MODIFIED TO ACCOMMODATE SAID DEVICES SHALL BE PATCHED AFTER INSTALLATION ACCORDING TO ARCHITECTURAL SPECIFICATIONS. THE NATIONAL ELECTRICAL CODE (NEC) (CURRENT EDITION ADOPTED BY AHJ). ENTERGY (OR RESPECTIVE UTILITY PROVIDER) -CUSTOMER INSTALLATION STANDARDS FOR ELECTRIC SERVICE. NFPA - NATIONAL FIRE PROTECTION ASSOCIATION NFPA-101, LIFE SAFETY CODE. NFPA - NATIONAL FIRE PROTECTION ASSOCIATION NFPA-72, FIRE ALARM CODE. NFPA 90A STANDARD FOR THE INSTALLATION OF AIR CONDITIONING AND VENTILATING SYSTEMS. NFPA 90B STANDARD FOR THE INSTALLATION OF WARM AIR HEATING AND AIR CONDITIONING SYSTEMS. OSHA CODE OF FEDERAL REGULATIONS (FOR CONSTRUCTION PRACTICES). ANSI HANDICAPPED CODE-A117.1. APPLICABLE STATE AND LOCAL CODES/ORDINANCES. CBM - CERTIFIED BALLAST MANUFACTURER IPCEA - INSULATED POWER CABLE ENGINEERS' ASSOCIATION FM - FACTORY MUTUAL ETL - ELECTRICAL TESTING LABORATORIES IES - ILLUMINATING ENGINEERING SOCIETY NECA APPLICABLE HEALTH CODES IBC PROFESSIONAL ENGINEERS, ARCHITECTS AND SURVEYORS 1. 2. 23. RACEWAYS AND CABLES SHALL BE INSTALLED CONCEALED UNLESS OTHERWISE NOTED. 48. AT THE END OF EACH WORK DAY, THE CONTRACTOR SHALL REMOVE ALL DEBRIS, SURPLUS MATERIALS OR FOREIGN MATTER CAUSED BY THE PERFORMANCE OF ELECTRICAL WORK ON THE PREMISES. UPON COMPLETION OF THE WORK THE CONTRACTOR SHALL BE RESPONSIBLE FOR LEAVING THE PREMISES IN A CLEAN CONDITION. LINFIELD, HUNTER & JUNIUS, INC. 22. INSTALL EQUIPMENT SO THAT CLEAR WORKING SPACE REQUIREMENTS OF THE NEC ARE MET. REFER TO NEC 110.26. S WORK PERFORMED UNDER THE ELECTRICAL INSTALLATION SHALL BE IN ACCORDANCE WITH STANDARDS LISTED BELOW OF THE LATEST APPLICABLE EDITION ADOPTED BY THE AUTHORITY HAVING JURISDICTION. WHERE THESE SPECIFICATIONS ARE MORE STRINGENT, THEY SHALL TAKE PRECEDENCE. IN CASE OF CONFLICT, OBTAIN A DECISION FROM THE ARCHITECT. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. FILE: P:\LinfieldHunter&Junius\14-098_CommunityResourceCenter\Design Documents\Drawings\Electrical\E-001 SYMBOLS, NOTES, & RISER.dwg NAME LOCATION. 21. COORDINATE ELECTRICAL WORK WITH ALL OTHER TRADES PRIOR TO SUBMITTING A BID. CITY OF KENNER - CONVERSION OF ANNE WASHINGTON COMMUNITY CENTER TIME: 6:10 PM ELECTRICAL NOTES: P 'F1' PHOTO CELL 4'-0" RECEPTACLES WALL ABOVE COUNTER WITHOUT BACKSPLASH ABOVE COUNTER WITH BACKSPLASH 1'-6" 0'-8" ABOVE TOP OF COUNTER 0'-4" ABOVE TOP OF BACKSPLASH TELEPHONE DESK/TABLE WALL TELEPHONE ABOVE COUNTER ABOVE COUNTER WALL ABOVE COUNTER ABOVE COUNTER 1'-6" 4'-8" 0'-8" 0'-4" 1'-6" 0'-8" 0'-4" (SWITCH MODIFIIER) THREE WAY SWITCH OR DIMMER 120V. DUPLEX RECEPTACLE WALL / FLOOR MOUNTED DATA OUTLETS 120V. QUADRUPLEX RECEPTACLE WALL / FLOOR MOUNTED SPECIAL RECEPTICAL (TYPE AS NOTED) J ELECTRICAL EQUIPMENT 40,000 AMPS <40,000 AMPS DEVICE KAIC RATING N/A 42 KAIC ABOVE TOP OF COUNTER ABOVE TOP OF BACKSPLASH 6'-6" TO TOP OF ENCLOSURE 6'-6" TO TOP OF ENCLOSURE 6'-6" TO TOP OF ENCLOSURE TV CABLE OUTLET WALL 1'-6" CONTROL/SECURITY DOOR ACCESS KEYPAD CCTV CAMERA CCTV MONITOR 3'-10" 0'-6" BELOW CEILING LEVEL COORDINATE WITH OWNER ENTERGY POLE MTD TRANSFORMERS OVHD SERVICE CONNECT ACCORDING TO UTILITY STANDARDS GROUND FAULT CIRCUIT INTERRUPTER RECEPTACLE UC UNDER COUNTER REFRIGERATOR WP WEATHERPROOF TR 2014/10/02 P1 TELEPHONE OUTLET WITH PLATE DATA OUTLET WITH PLATE #2/0 GND TO BUILDING STEEL & MAIN COLD WATER PIPE NO MORE THEN 5' FROM PIPE ENTRY INTO BUILDING. CABLE TV DROP CCTV CAMERA - EXTERIOR MOTION DETECTOR KEYPAD WC WINDOW CONTACT DC DOOR CONTACT EE 400A/2P 400AF SE RATED N3R FIRE ALARM SMOKE DETECTOR WITH SOUNDER BASE KEY L E NG I N 3-#600,#2G 3 1/2"C. CU CIRCUIT HOMERUN MD I CA CITY OF KENNER - CONVERSION OF ANNE WASHINGTON COMMUNITY CENTER GFI S AFF ABOVE FINISHED FLOOR 3-#600 3 1/2"C. CU PROFESSINAL ENGINEER IN EC ABOVE COUNTER OF LOU I S I TE AN A T BLAKE MICHAEL HOSLI License No. 38688 RECEPTACLE MODIFIERS AC 2011 by Linfield, Hunter & Junius, Inc. ABOVE TOP OF COUNTER ABOVE TOP OF BACKSPLASH A PANELBOARD - FLUSH MOUNTED WITHOUT BACKSPLASH WITH BACKSPLASH UTILITY SERVICE BASED ON 100KVA SIZE XFMR. P1 SAFETY SWITCH PANELBOARD COMMUNICATIONS CABINET JUNCTION BOX DISCONNECT, SIZE NOTED WITHOUT BACKSPLASH WITH BACKSPLASH SHORT CIRCUIT AVAILABLE 3608 18th Street, Suite 200 Metairie, Louisiana 70002 WALL SWITCHES AND DIMMERS DEVICE NAME EL FILE: P:\LinfieldHunter&Junius\14-098_CommunityResourceCenter\Design Documents\Drawings\Electrical\E-001 SYMBOLS, NOTES, & RISER.dwg SWITCHES DESIGNATES FIXTURE TYPE - SEE LIGHTING FIXTURE SCHEDULE NORMAL SWITCH - TOGGLE 3 6'-6" 0'-8" ABOVE TOP OF MIRROR CENTER BETWEEN FRAME & CEILING 7'-0" (SEE ACHITECTURAL DETAIL) IN G BATTERY POWERED EMERGENCY LIGHT WALL MOUNTED, SCONCE WALL MOUNTED, ABOVE MIRROR WALL MOUNTED, ABOVE DOOR WALL MTD,ABOVE STAIR LANDING OR STEPS IN SOFFIT R CEILING MOUNTED EXIT SIGN - SHADED AREAS INDICATE FACES - WHEN SHOWN ARROWS INDICATE DIRECTION OF EXIT - BATTERY OR EM. GEN. WALL MOUNTED EXIT SIGN - SHADED AREAS INDICATE FACES - WHEN SHOWN ARROWS INDICATE DIRECTION OF EXIT - BATTERY OR EM. GEN. LIGHTING FIXTURES INTERIOR METAL COLD WATER PIPE 3/4"X10' CU-BR GROUND ROD DRIVEN 10'-0" INTO GROUND APPROVED BY WALL BRACKET FIXTURE TABLE 1 - SHORT CIRCUIT FAULT TABLE CHECKED BY WALL WASHER FIXTURE THE CONTRACTOR SHALL COORDINATE THE MOUNTING HEIGHT OF ALL FIXTURES, DEVICES, AND OUTLETS WITH ALL DRAWINGS. SPECIAL MOUNTING HEIGHTS SHOWN ON THE DRAWINGS SHALL TAKE PRECEDENCE OVER THOSE GIVEN BELOW. ALL MOUNTING HEIGHTS ARE FROM FINISHED FLOOR TO CENTERLINE OF DEVICE, UNLESS NOTED OTHERWISE. PROJ. NO. 12-23 DATE 10/02/2014 SHEET NO. OF SHEETS DRAWN BY SURFACE OR RECESSED DOWNLIGHT (TYPE DETERMINES MOUNTING) THIS SHEET PENDANT LIGHT TYPICAL MOUNTING HEIGHTS S SURFACE, SUSPENDED OR RECESSED FLUORESCENT (TYPE DETERMINES MOUNTING) PROFESSIONAL ENGINEERS, ARCHITECTS AND SURVEYORS LINFIELD, HUNTER & JUNIUS, INC. 6:10 PM TIME: DATE: 10/1/2014 ELECTRICAL LEGEND 1 EX. P2 D HORN AC D R J UC P PHOTOCELL DATE: 10/1/2014 D GFI/AC R D D D D D D D AC AC UC D AC R AC R R GFI/AC R D D D R IN WALL CABINET D D R UC AC D D D D DATA CABINET R R 2011 by Linfield, Hunter & Junius, Inc. 3608 18th Street, Suite 200 Metairie, Louisiana 70002 1 PROFESSIONAL ENGINEERS, ARCHITECTS AND SURVEYORS TIME: EX. P2 LINFIELD, HUNTER & JUNIUS, INC. 6:12 PM COMM BACKBOARD 2 (2) 125A METERS & DISC. D R R DD X2 R D X2 R R DD R BLAKE MICHAEL HOSLI License No. 38688 D X9 EC R PROFESSINAL ENGINEER IN TR R R R R A R OF LOU I S I TE AN A T S R D IN G D DDD GFI/AC R R EL I CA L E NG I N R EE 2014/10/02 D X3 D D D D D D D D KEYED NOTES: GENERAL SHEET NOTES: 1 EXISTING PANEL TO BE DEMOLISHED. JUNCTION BOX AND EXTEND ALL REUSED CIRCUITS TO NEW PANEL LOCATION ON FIRST FLOOR - REFER TO NEW PLAN. 1. ALL SHOWN OBJECTS ARE EXISTING. OBJECTS MARKED WITH A "R" ARE TO BE RELOCATED WHERE SHOWN ON NEW PLANS. OBJECTS MARKED WITH A "D" ARE TO BE DEMOLISHED. 2 EXISTING TWO METER SERVICE TO BE DEMOLISHED. SINGLE METER AND DISCONNECT TO BE PROVIDED. REFER TO NEW PLAN AND ONE LINE DIAGRAM. 2. ALL INTERIOR LIGHTING IS TO BE DEMOLISHED AND CIRCUITS FREED FOR NEW LIGHTING. SOME SWITCHING LOCATIONS SHALL BE MAINTAINED AS SHOWN ON NEW PLANS. 3. ALL ELECTRICAL DEVICES NOT SHOWN TO BE REUSED ARE TO BE DEMOLISHED. JUNCTION BOX AND MAINTAIN CIRCUIT CONTINUITY TO ANY DEVICES ON SAME CIRCUIT NOT DEMOLISHED. THIS INCLUDES BUT IS NOT LIMITED TO RECEPTACLES, COMMUNICATIONS OUTLETS, SWITCHES, EXIT SIGNS, EMERGENCY LIGHTS, LIGHTING, DISCONNECTS, ETC. EC TO PROVIDE A FULLY FUNCTIONING AND CODE COMPLIANT SYSTEM AT PROJECT COMPLETION. GENERAL SHEET NOTES: 4. ALL PHONE AND DATA BRANCH LOCATIONS ARE TO BE DEMOLISHED. 5. ALL EMERGENCY LIGHTING AND EXIT SIGNS TO BE DEMOLISHED. NEW LOCATIONS OF NEW SIGNS AND EMERGENCY LIGHTING SHOWN ON NEW PLANS. CHECKED BY D P PROJ. NO. 12-23 DATE 10/02/2014 SHEET NO. OF SHEETS DRAWN BY D THIS SHEET R APPROVED BY D CITY OF KENNER - CONVERSION OF ANNE WASHINGTON COMMUNITY CENTER FILE: P:\LinfieldHunter&Junius\14-098_CommunityResourceCenter\Design Documents\Drawings\Electrical\E-101 EXISTING CONDITIONS.dwg R ENTRANCE CORRIDOR (BELOW) F4 F4 REPLAMP AND REPLACE TRIM WITH EXTERIOR GRADE TRIM F5 KITCHEN/ F4 DINING 33 TO SIGN CIRCUIT DATE: 10/1/2014 TO 2ND FLOOR P1:7 F4 F4 LIVING ROOM / DINING 102 P1:9 OFFICE/ CHECK-IN F8 101 EXIST. MECH. ROOM (UNDER STAIRS) 105 F6 TO 1ST FLOOR F4 F4 F5 F4 F4 203 P PHOTOCELL F3 F2 F1 F4A F4 F4 F4 EF-3 EXIST. SKYLIGHT BATHROOM 202 P1:13 F4 F4 F4 F4 F2 F3 F4A 3 F1 P1:11 BATHROOM EF-1 106 F4 STAIRWELL 219 F8 3 F2 F3 EF-5 BEDROOM #1 107 F4 F4 BATHROOM 218 BEDROOM #4 (ADA) 118 F1 CORRIDOR 200 F4 F1 F4 F4 CLOSET/ LAUNDRY 207 F2 LIVING ROOM/ BEDROOM 217 CLOSET F1 EF-4 F4 F4A CLOSET/ LAUNDRY 208 F4 BATHROOM 209 F4 OF LOU I S I TE AN A T F4 CLOSET 117 F4 F4 F5 F1 F4 F4 F4 F3 F8 EXIST. MECH. ROOM 114 KITCHEN/ DINING 212 F2 F5 F5 EXIST. MECH. CLOSET 214 3 F4 F4 F5 F4 EXIST. MECH. CLOSET 213 P E 1 E KEYED NOTES: 1 EXISTING FLOOD LIGHTS TO BE RELAMPED BY ELECTRICAL CONTRACTOR. 2 EXISTING METAL HALIDE WALL MOUNT FIXTURE TO BE RELAMPED BY ELECTRICAL CONTRACTOR. 3 EXISTING CIRCUIT FOR SIGN MOUNTED LIGHT - UTILIZE CIRCUIT AND FEED FROM PANEL AS INDICATED. PROVIDE PHOTOCELL AT LIGHT FIXTURE. E E 1 GENERAL SHEET NOTES: 1. DASHED OBJECTS OR OBJECTS MARKED WITH AN "E" ARE EXISTING. 2. ALL REUSED LIGHTING SWITCH LOCATIONS ARE TO BE REPLACED WITH NEW SWITCHES AND DEVICE PLATES. 3. LUMINAIRE SWITCHING AND LAYOUT HAVE BEEN SHOWN ON THESE PLANS. DO NOT LOAD LIGHTING CIRCUITS MORE THAN 80% OF THEIR CAPACITY. 4. EXIT SIGNS AND EMERGENCY LIGHTS ARE TO BE FED FROM THE NEAREST 20A LIGHTING CIRCUIT AHEAD OF ANY SWITCHES. 5. RECESSED FIXTURES IN FIRE RATED CEILINGS AND RETURN AIR PLENUMS SHALL BE RATED FOR THE FIRE RATING OF THE CEILING OR SHALL BE FULLY ENCLOSED IN A FIRE RATED HOUSING ACCEPTABLE TO AUTHORITY HAVING JURISDICTION. 6. FEED SMOKE DETECTORS FROM NEAREST UNSWITCHED 120V GENERAL LIGHTING CIRCUIT. DETECTORS WITHIN A SINGLE UNIT ARE TO BE CONNECTED TOGETHER SO THAT A DETECTION AT ONE DEVICE ACTIVATES THE OTHER. EE 2014/10/02 3 LAUNDRY ROOM 113 CLOSET/ LAUNDRY 215 L E NG I N F4 F4 F5 I CA F4 F4 F4 PROFESSINAL ENGINEER IN TR LIVING ROOM/ BEDROOM 211 F2 F4 F4A BLAKE MICHAEL HOSLI License No. 38688 F4 F1 EF-2 F4 F3 F4 F4 KITCHEN/ DINING 216 BATHROOM (ADA) 111 F4 EC F4 BEDROOM #3 115 CLOSET 210 EL F1 CLOSET 116 F4 F2 CITY OF KENNER - CONVERSION OF ANNE WASHINGTON COMMUNITY CENTER CORRIDOR 112 A S F4 BEDROOM #2 110 2011 by Linfield, Hunter & Junius, Inc. BEDROOM 205 F4A F4 F4 109 F4 CLOSET 206 F2 F1 F4 3 KITCHEN 119 CLOSET 108 LIVING ROOM 201 F4 F4 FILE: P:\LinfieldHunter&Junius\14-098_CommunityResourceCenter\Design Documents\Drawings\Electrical\E-201 LIGHTING & FIRE ALARM.dwg F5 IN G F2 R CLOSET 103 F4 3608 18th Street, Suite 200 Metairie, Louisiana 70002 F6 APPROVED BY RELAMP EXISTING FIXTURE E CHECKED BY 1 PROJ. NO. 12-23 DATE 10/02/2014 SHEET NO. OF SHEETS DRAWN BY ENTRANCE CORRIDOR 100 1 MECH. ROOM 204 THIS SHEET 6:14 PM TIME: E 3 3 3 2 2 PROFESSIONAL ENGINEERS, ARCHITECTS AND SURVEYORS 3 EXIST. MECH. ROOM 104 LINFIELD, HUNTER & JUNIUS, INC. F7 GFI/AC J UC R DC KITCHEN/ DINING LIVING ROOM / DINING 102 4 R GFI/AC 2 GFI/AC GFI/AC GFI/AC R R R MD P1:6 STAIRWELL 219 P1:12/14 P1:4 3#8,#10G 3/4"C R KITCHEN 4 119 R INTERIOR SECURITY SIREN BEDROOM 205 14-50R BATHROOM 218 WC WC WC WC R P1:36/38 3#10,#10G 3/4"C LIVING ROOM/ BEDROOM 217 R CLOSET 109 R R CLOSET 116 R R R P1:39/41 3#6,#8G 1"C LAUNDRY ROOM P1:20/22 113 P1:35/37 2#8,#10G 3/4"C P1:43/45 3#10,#10G 3/4"C 60A 30A P1:24/26 3#10,#10G 3/4"C 48"AFF GFI 14-30R 3#10,#10G 3/4"C P1:18 GFI/AC N3R 1 20A 20A 30AF 30AF WP/GFI GFI DC 1 P1:31/33 2#8,#10G 3/4"C CU-3 EXIST. MECH. ROOM 114 AHU-1 P1:58 2#10,#10G 3/4"C 1 SINGLE CIRCUIT WIREWAY FEEDING BOTH DISCONNECTS. 2 EXISTING ACTIVE CAMERAS AT BUILDING EXTERIOR AND NEW MONITOR LOCATION. COORDINATE WITH TENANT TO RELOCATE CAMERA EQUIPMENT AND FEEDS TO CHECK-IN OFFICE 101 AND KEEP ACTIVE. CLEAN AND SERVICE CAMERAS TO ENSURE PROPER WORKING ORDER PRIOR TO PROJECT COMPLETION. 3 ALL COMMUNICATIONS LINES HOMERUN TO THIS LOCATION. TERMINATE ALL LINES ONTO COMMUNICATIONS BACKBORAD AND COORDINATE ENTIRE INSTALL WITH SERVICE PROVIDER. COORDINATE WITH TENANT'S IT DIRECTOR FOR ANY ADDITIONAL REQUIREMENTS TO THIS ROOM AND INCLUDE IN THE BASE BID. 5 RECEPTACLE FOR ABOVE STOVE MICROWAVE HOOD. COORDINATE FINAL RECEPTACLE LOCATION IN THE FIELD WITH THE GENERAL CONTRACTOR AND MICROWAVE HOOD INSTALLATION REQUIREMENTS. I CA L E NG I N P1:46 GFI P1:48/50 3#10,#10G 3/4"C 14-30R GFI/AC P1:1/3 3#8,#10G 3/4"C KITCHEN/ DINING 212 P1:64 EXIST. MECH. AHU-4 CLOSET 214 60A 14-50R 4 P1:66 DC P1:55/57 3#8,#10G 3/4"C EXIST. MECH. CLOSET 213 AHU-3 60A 48"AFF UC J EE 2014/10/02 GFI/AC P1:51/53 3#8,#10G 3/4"C CU-1 KEYED NOTES: 4 TR GFI/AC 48"AFF PROFESSINAL ENGINEER IN P1:5 P1:56 CLOSET/ LAUNDRY 215 N3R 20A 25A 30AF 30AF CU-2 J UC GFI/AC P1:62 14-50R P1:52/54 3#8,#10G 3/4"C 4 GFI BATHROOM (ADA) 111 KITCHEN/ DINING 216 48"AFF P1:60 LIVING ROOM/ BEDROOM 211 EC R OF LOU I S I TE AN A T BLAKE MICHAEL HOSLI License No. 38688 EL R GFI/AC P1:16 P1:40/42 3#10,#10G 3/4"C R R CLOSET/ LAUNDRY 208 WC R WC R 48"AFF GFI 14-30R GFI 48"AFF CLOSET/ LAUNDRY 207 A WC CLOSET 117 BEDROOM #3 115 GFI/AC CLOSET 210 WC BEDROOM #2 110 P1:34 BATHROOM 209 R CORRIDOR 112 2011 by Linfield, Hunter & Junius, Inc. CORRIDOR 200 R R CLOSET 206 GFI/AC BEDROOM #4 (ADA) 118 R FILE: P:\LinfieldHunter&Junius\14-098_CommunityResourceCenter\Design Documents\Drawings\Electrical\E-301 POWER & COMMUNICATION.dwg GFI/AC 48"AFF IN G GFI/AC BEDROOM #1 107 UC J S R R P1:10 LIVING ROOM 201 P1:44 GENERAL SHEET NOTES: 1. DASHED OBJECTS OR OBJECTS MARKED WITH AN "E" ARE EXISTING. 2. OBJECTS INDICATED WITH A "R" ARE TO BE RELOCATED FROM CURRENT NEARBY LOCATION. 3. ALL POWER AND COMMUNICATION DEVICES AND PLATES - EVEN IF SHOWN IN EXISTING LOCATIONS - ARE TO BE REPLACED WITH NEW PLATES AND DEVICES. 4. RECEPTACLES WITH HOMERUNS SHOWN ARE TO BE FED FROM NEW CIRCUITS FROM THE PANEL WITH THE INDICATED BREAKER AND WIRE. 5. ALL RECEPTACLES TO REMAIN ARE TO BE REPLACED WITH NEW RECEPTACLES AND PLATES. 6. MATCH RECEPTACLE CONFIGURATION FOR SPECIALTY RECEPTACLES WITH EQUIPMENT INTENDED TO BE CONNECTED. APPROVED BY P1:8 WC WC BATHROOM 106 EWH-1 CU-4 P1:32 R 100A P1:27/29 NF 2#3,#8G 1 1/4"C EXTERIOR SECURITY SIREN 48'AFF BATHROOM 202 EXIST. SKYLIGHT GFI/AC CLOSET 108 P1:23/25 3#8,#10G 3/4"C P1:30 CHECKED BY 5 203 PROJ. NO. 12-23 DATE 10/02/2014 SHEET NO. SECURITY PANEL LOCATION. OF SHEETS DRAWN BY KEY 3608 18th Street, Suite 200 Metairie, Louisiana 70002 P1:47/49 3#8,#10G 3/4"C NEW PANEL P1 OFFICE/ CHECK-IN 101 WC THIS SHEET TIME: DC DATE: 10/1/2014 WC P1:28 GFI/AC 2 WC EXIST. MECH. ROOM (UNDER STAIRS) 105 60A 2 EXTERIOR SECURITY SIREN MECH. ROOM 204 AHU-2 WC ENTRANCE CORRIDOR (BELOW) CLOSET 103 P1:2 NEW METER AND SE RATED FUSED DISCONNECT CITY OF KENNER - CONVERSION OF ANNE WASHINGTON COMMUNITY CENTER ENTRANCE CORRIDOR 100 M PROFESSIONAL ENGINEERS, ARCHITECTS AND SURVEYORS COMM BACKBOARD 3 KEY 6:16 PM WC LINFIELD, HUNTER & JUNIUS, INC. EXIST. MECH. ROOM 104 RETURN AIR GRILLE AND AIR QUANTITY. (24x24 FACE) SQUARE THROAT ELBOWS WITH TURNING VANES EXHAUST GRILLE AND AIR QUANTITY. (24x24 FACE) RADIUS ELBOW LAMINAR FLOW SUPPLY DIFFUSER AND AIR QUANTITY. (24x24 FACE) TRANSITION DATE: 10/1/2014 LINEAR DIFFUSER AND AIR QUANTITY. (24x24 FACE) SUPPLY, RETURN AND EXHAUST GRILLE (12x12 FACE) OR EXHAUST DUCT DOWN BRANCH DUCT CONNECTION, STRAIGHT TEE AND ROUND TRUNK. BRANCH DUCT CONNECTION, CONICAL TEE AND ROUND TRUNK. OR EXHAUST DUCT UP RHC-XX RETURN DUCT DOWN REHEAT COIL WITH IDENTIFICATION RETURN DUCT UP SUPPLY DUCT DOWN B FLEXIBLE DUCT BD B0D BOP BTUH G H BACKDRAFT DAMPER BOTTOM OF DUCT BOTTOM OF PIPE BRITISH THERMAL UNIT PER HOUR (BTU/H) SUPPLY DUCT UP RETURN AIR DUCT WITH SOUND BOOT RECESSED FIRE HOSE CABINET SURFACED MOUNTED FIRE HOSE CABINET FHC FHC DG FD FD SD SD DUCT-MOUNTED FIRE DAMPER C DUCT-MOUNTED SMOKE DAMPER DOOR GRILLE FSD FSD DUCT-MOUNTED FIRE/SMOKE DAMPER UNDERCUT AT DOOR EXISTING EQUIPMENT TO REMAIN FILE: P:\LinfieldHunter&Junius\14-098_CommunityResourceCenter\Design Documents\Drawings\Mechanical\M-000 MECHANICAL LEGEND.dwg SD NAME NEW EQUIPMENT WITH IDENTIFICATION CV-# TERMINAL BOX WITH IDENTIFICATION NUMBER, CONSTANT AIR VOLUME, AIRFLOW SETTINGS. TERMINAL BOX WITH IDENTIFICATION ASSOCIATED AHU, ASSOCIATED ROOM #, TOTAL AIRFLOW SETTINGS. TERMINAL BOX WITH IDENTIFICATION NUMBER, VARIABLE AIR VOLUME, MINIMUM AND MAXIMUM AIRFLOW SETTINGS. VAV-AHU VAV-# TERMINAL BOX WITH IDENTIFICATION NUMBER, VARIABLE AIR VOLUME, COOLING ONLY, MINIMUM AND MAXIMUM AIRFLOW SETTINGS. VAV-CC-# TERMINAL BOX WITH IDENTIFICATION NUMBER, CONSTANT AIR VOLUME, COOLING ONLY, AIRFLOW SETTINGS. CV-CC-# SD T X DUCT-MOUNTED SMOKE DETECTOR THERMOSTAT & SYSTEM DESIGNATION H HUMIDISTAT TS TEMPERATURE SENSOR HS RELATIVE HUMIDITY SENSOR CHS CHILLED WATER SUPPLY CHR CHILLED WATER RETURN HWS HOT WATER SUPPLY HWR HOT WATER RETURN CWS CONDENSER WATER SUPPLY CWR CONDENSER WATER RETURN SRV-# FOS FUEL OIL SUPPLY FOR FUEL OIL RETURN EXHAUST AIR ROOF VENT OR FAN ERV-# LOUVERED ROOF VENT SPIN-IN VOLUME DAMPER M M MVD MOTORIZED DAMPER RS REFRIGERANT SUCTION RL REFRIGERANT LIQUID RD REFRIGERANT DISCHARGE RHG REFRIGERANT HOT GAS BYPASS LPC LOW PRESSURE CONDENSATE PCR PUMPED CONDENSATE RETURN PUMP MVD MANUAL VOLUME DAMPER ELBOW UP 24x12 24x12 RIGID DUCTWORK AND SIZE. DIMENSIONS ARE INSIDE CLEAR COMPRESSED AIR CENTERLINE COMBUSTION AIR CAPACITY CATCH BASIN COOLING COIL CEILING DIFFUSER CONDENSATE DRAIN CAP FOR FUTURE CUBIC FEET PER HOUR CUBIC FEET PER MINUTE CHILLER CHILLED WATER SUPPLY CHILLED WATER RETURN CAST IRON CONDENSER CONDENSING CONTINUED/CONTINUOUS CIRCULATING PUMP COOLING TOWER COOLING TOWER RETURN COOLING TOWER SUPPLY CUBIC CONTROL VALVE DB DDC DIA DIFF DIM DMPR DOAS DRY BULB TEMP (DEG F) DIRECT DIGITAL CONTROL DIAMETER DIFFUSER DIMENSION DAMPER DEDICATED OUTSIDE AIR SYSTEM DOWN DIFFERENTIAL PRESSURE CONTROL DAMPER DIFFERENTIAL PRESSURE SWITCH DRAWING DRYER EXHAUST DN DP DPR DPS DWG DX STEAM STEAM CONDENSATE SUPPLY AIR ROOF VENT OR FAN D C/A C/L CA CAP CB CC CD CD CFF CFH CFM CH CHR CHS CI CND COND CONT CP CT CTR CTS CU CV E E/A ECO EER EF EFF EJ ELEC ELEV EMER EMR ENT EOM ERD ERV ESP ET EVAP EWC EWH EX EXH EXT EXHAUST AIR EXTERIOR CLEANOUT ENERGY EFFICIENCY RATIO EXHAUST FAN EFFICIENCY EXPANSION JOINT ELECTRICAL ELEVATION EMERGENCY ELEVATOR MACHINE ROOM ENTERING END OF MAIN DRIP EMERGENCY ROOF DRAIN ENERGY RECOVERY VENTILATOR EXTERNAL STATIC PRESSURE EXPANSION TANK EVAPORATOR ELECTRIC WATER COOLER ELECTRIC WATER HEATER EXTERIOR EXHAUST EXTERNAL I GA GALV GND GPM GPH GV GAUGE (GAGE) GALVANIZED GROUND GALLONS PER MINUTE GALLONS PER HOUR GATE VALVE N NIC NK N/O NOM NTS O O&M O/A OC OD OS&Y OXY OZ P HB HC HD HEPA HOSE BIBB HEATING COIL HEAD HIGH EFFICIENCY PARTICULATE AIR HHC HEATING COIL (HOT WATER) HOA HAND-OFF-AUTO HORIZ HORIZONTAL HPS HIGH PRESSURE STEAM HTR HEATER HP HORSEPOWER HWB HOT WATER BOILER HWH HOT WATER HEATER HWR HEATING WATER RETURN HWS HEATING WATER SUPPLY HX HEAT EXCHANGER IAQ IAW IBC IBO ID IN INV IRI INDOOR AIR QUALITY IN ACCORDANCE WITH INSTALLED BY CONTRACTOR INSTALLED BY OWNER INSIDE DIAMETER INCHES INVERT INDUSTRIAL RISK INSURERS K KW KX KILOWATT KITCHEN EXHAUST L LB LF LPG LPS LRA LVG POUND LINEAR FEET LIQUID PETROLEUM GAS LOW PRESSURE STEAM LOCKED ROTOR AMPS LEAVING M MAX MB MCA MCC MD MECH MEP MER MERV MFR MIN MPS MVD-1 MVD-2 MVD-3 MAXIMUM MOP BASIN MAXIMUM CURRENT AMPS MOTOR CONTROL CENTER MOTORIZED DAMPER MECHANICAL MECHANICAL, ELECTRICAL, PLUMBING MECHANICAL ROOM MINIMUM EFFICIENCY REPORTING VALUE MANUFACTURER MINIMUM MEDIUM PRESSURE STEAM MANUAL VOLUME DAMPER (STANDARD LEAKAGE TYPE) MANUAL VOLUME DAMPER (LOW LEAKAGE TYPE) MANUAL VOLUME DAMPER (HIGH PERFORMANCE TYPE) N NATL N/C NC NFPA R S NITROGEN NATURAL NORMALLY CLOSED NOISE CRITERIA NATIONAL FIRE PROTECTION ASSOCIATION NOT IN CONTRACT NECK NORMALLY OPEN NOMINAL NOT TO SCALE OPERATION AND MAINTENANCE OUTSIDE AIR ON CENTER OUTSIDE DIAMETER OUTSIDE STEM & YOKE OXYGEN OUNCES (PRESSURE) P PC PCHR PUMP PUMPED CONDENSATE PRIMARY CHILLED WATER RETURN PCHS PRIMARY CHILLED WATER SUPPLY PD PRESSURE DROP PHWR PRIMARY HOT WATER RETURN PHWS PRIMARY HOT WATER SUPPLY PRESS PRESSURE PROP PROPELLER PRV PRESSURE REDUCING VALVE PSI POUNDS PER SQUARE INCH PTAC PACKAGED TERMINAL A/C PVC POLYVINYL CHLORIDE R RELIEF R/A RETURN AIR RECIRC RECIRCULATE REF REFERENCE RH RELATIVE HUMIDITY RND ROUND RO REVERSE OSMOSIS RPM REVOLUTIONS PER MINUTE RTD RESISTANCE TEMPERATURE DETECTOR RTU ROOFTOP UNIT S/A SD SEER SF SHR SHT SP SPEC STD SYS SUPPLY AIR SMOKE DAMPER SEASONAL ENERGY EFFICIENCY RATIO SUPPLY AIR FAN SENSIBLE HEAT RATIO SHEET STATIC PRESSURE SPECIFICATION STANDARD SYSTEM T U V TAB T&P TD TEMP TK TOD TOP TP TSTAT TX TXF TYP TESTING AND BALANCING TEMPERATURE AND PRESSURE TEMPERATURE DIFFERENCE TEMPERATURE TANK TOP OF DUCT TOP OF PIPE TOTAL PRESSURE THERMOSTAT TOILET EXHAUST TOILET EXHAUST FAN TYPICAL UG UH UL UR UNDERGROUND UNIT HEATER UNDERWRITERS LISTED URINAL V VAC VAV VD VEL VENT VERT VFD VI VOJ VENT VACUUM VENTILATION VARIABLE AIR VOLUME VOLUME DAMPER VELOCITY VENTILATION VERTICAL VARIABLE FREQUENCY DRIVE VIBRATION ISOLATOR VERIFY ON JOB W/ W/O W WB WC WFM WG WMS WPD WITH WITHOUT WATER WET BULB (DEG F) WATER COLUMN WATER FLOW METER WATER GAUGE WIRE MESH SCREEN WATER PRESSURE DROP ALL WORK SHALL COMPLY WITH THE LATEST STATE AND CITY CODES INCLUDING BUT NOT LIMITED TO THE FOLLOWING: A. B. C. D. E. F. G. H. 2. INTERNATIONAL MECHANICAL CODE - 2012 INTERNATIONAL FUEL GAS CODE - 2012 INTERNATIONAL BUILDING CODE - 2012 ANSI/ASHRAE/IESNA 90.1 - 2007 THE CONTRACT DOCUMENTS ALL REQUIREMENTS OF THE STATE FIRE MARSHAL INSURING AGENCY ALL REQUIREMENTS OF THE AUTHORITIES HAVING JURISDICTION. PROVIDE ALL MATERIAL AND EQUIPMENT AND PERFORM ALL LABOR REQUIRED TO INSTALL COMPLETE AND OPERABLE MECHANICAL SYSTEMS AS INDICTED ON THE DRAWINGS, AS SPECIFIED AND AS REQUIRED BY CODE. 3. DRAWINGS ARE SCHEMATIC IN NATURE AND SHALL NOT BE SCALED. THE CONTRACTOR IS RESPONSIBLE FOR COORDINATING EXACT ROUTING OF ALL SERVICES WITH SITE CONDITIONS, EXISTING CONDITIONS AND WITH WORK OF ALL OTHER TRADES. 4. CONTRACTOR SHALL VISIT THE SITE AND BECOME FAMILIAR WITH THE PROJECT SCOPE AND CONSTRAINTS, UTILITY CONNECTIONS, AND ALL BUILDING SERVICES, PRIOR TO SUBMITTING BID. 5. ALL THERMOSTATS, HUMIDISTATS, OCCUPANCY SENSORS, AND CARBON DIOXIDE SENSORS SHALL BE LOCATED ON THE NEAREST WALL TO LOCATION INDICATED. LOCATIONS OF THERMOSTATS SHALL BE APPROVED BY THE ARCHITECT, WHERE POSSIBLE LOCATE ABOVE LIGHT SWITCH. UNLESS OTHERWISE SHOWN, LOCATE ALL ROOM THERMOSTATS AND HUMIDISTATS 4'-0" (CENTERLINE) ABOVE THE FINISHED FLOOR. 6. EQUIPMENT SHOWN ON THE PLANS AND ELEVATIONS ILLUSTRATE THE GENERAL ARRANGEMENT AND SPACE ALLOCATIONS. THE CONTRACTOR SHALL VERIFY THE SPACE REQUIREMENTS FOR EACH SYSTEM COMPONENT USING MANUFACTURER'S CERTIFIED SHOP DRAWINGS AND MAKE THE NECESSARY ADJUSTMENTS IN EQUIPMENT PLACEMENT AND CONNECTION IN ORDER TO ACCOMMODATE THE EXACT EQUIPMENT TO BE INSTALLED. CONTRACTOR SHALL LOCATE EQUIPMENT FOR READY AND SAFE ACCESS FOR FUTURE MAINTENANCE AND REPAIRS. 7. DETAILS ILLUSTRATED ON THE DRAWINGS SHALL BE APPLIED IN ALL CASES WHERE THE FEATURE OCCURS IN THE SYSTEM DESIGN. 8. CONTRACTOR SHALL COORDINATE WITH ARCHITECT PRIOR TO CUTTING ANY OPENING IN THE STRUCTURE. 9. COORDINATE ANY DEVICE REQUIRING AN ACCESS PANEL WITH THE ARCHITECT. 10. CONTRACTOR SHALL PROVIDE MINIMUM 6-INCH DEEP CONCRETE HOUSEKEEPING PADS BENEATH FLOOR-MOUNTED AIR HANDLING UNITS, BOILERS, PUMPS, WATER HEATERS, AND GRADE-MOUNTED CONDENSING UNITS. PAD SHALL EXTEND MINIMUM 4-INCHES BEYOND EDGE OF EQUIPMENT ON ALL SIDES. 11. SUPPORTS, ANCHOR BOLTS, AND HANGERS FOR ALL EQUIPMENT SPECIFIED IN DIVISION 15 OR 23 SHALL CONFORM TO THE SPECIFICATIONS. MISCELLANEOUS STEEL BRACING SUPPORTS AND REINFORCING STEEL NEEDED TO SUPPORT EQUIPMENT SPECIFIED IN DIVISION 15 OR 23 SHALL BE FURNISHED AS PART OF SCOPE OF WORK OF DIVISION 15 OR 23. 12. ALL PENETRATIONS THROUGH RATED WALLS, FLOORS, AND PARTITIONS MUST BE INSTALLED AND FIRESAFED TO MEET UL FIRE RESISTANCE LISTING DETAILS FOR THE PENETRATION. 13. SMOKE DETECTORS SHALL BE LOCATED AS INDICATED ON THE MECHANICAL PLANS AND IN CONFORMANCE WITH NFPA 90A-2009, NFPA 72 - 2010, INTERNATIONAL MECHANICAL CODE-2009 AND ALL OTHER REQUIREMENTS OF THE AUTHORITIES HAVING JURISDICTION. DUCTWORK: 14. UNLESS OTHERWISE NOTED, ALL DUCTWORK IS OVERHEAD, TIGHT TO THE UNDERSIDE OF THE STRUCTURE, WITH SPACE FOR INSULATION IF REQUIRED. 15. CERTAIN ITEMS SUCH AS RISES AND DROPS IN DUCTWORK, ACCESS DOORS, AND VOLUME DAMPERS ARE INDICATED ON THE CONTRACT DOCUMENTS FOR CLARITY AND SHALL NOT BE INTERPRETED AS THE EXTENT OF THE REQUIREMENTS FOR THESE ITEMS. 16. CONTRACTOR SHALL VERIFY CLEARANCE REQUIREMENTS AND ROUTING OF DUCTWORK BEFORE FABRICATION BEGINS, AS DUCT RISES AND DROPS MAY BE NECESSARY DUE TO FIELD CONDITIONS. 18. ALL SUPPLY AIR DUCTWORK SHALL BE PROVIDED WITH 1" THICKNESS, 3.0 LB/CU. FT. NOMINAL DENSITY, ELASTOMERIC FOAM DUCT LINING, UNLESS OTHERWISE NOTED. KENT A. POYSER REG. No. 37788 REGISTERED 19. ALL DUCTWORK DIMENSIONS, AS SHOWN ON DRAWINGS, ARE INTERNAL CLEAR DIMENSIONS AND DUCT SIZE SHALL BE INCREASED TO COMPENSATE FOR DUCT LINING THICKNESS. IN 20. IF DUCTWORK CONFLICTS WITH PIPING, STEEL, LIGHT FIXTURES ETC. DUCTWORK SHALL BE SET UP AND DOWN. 21. SEALANT SHALL BE APPLIED TO LONGITUDINAL SEAMS IN THE SHOP DURING FABRICATION. FIELD APPLY SEALANT TO TRANSVERSE SEAMS AND CONNECTIONS TO BRANCH WORK AND AIR OUTLETS. 22. RADIUS ELBOWS SHALL BE USED IN ALL DUCT OFFSETS (HORIZONTAL OR VERTICAL). MITERED ELBOWS WITHOUT TURNING VANES ARE NOT ACCEPTABLE. 23. PROVIDE ACCESS DOORS IN DUCTWORK FOR THE OPERATION, ADJUSTMENT, AND MAINTENANCE OF ALL FANS, DAMPERS, AND MECHANICAL EQUIPMENT. ACCESS IS REQUIRED BELOW ALL DAMPERS AND ABOVE CEILING EQUIPMENT. 24. ALL EXISTING SUPPLY AND RETURN AIR DUCTWORK AND ASSOCIATED SOUND ATTENUATORS SHALL BE CLEANED THOROUGHLY. 25. PROVIDE VOLUME DAMPERS AT ALL DUCT BRANCHES, SPLITS, AND TAKE-OFFS. VOLUME DAMPERS IN BRANCH DUCTS SHALL BE LOCATED AS FAR AS POSSIBLE FORM AIR OUTLET OR INLET TO REDUCE NOISE AND TURBULENCE. DO NOT INSTALL DAMPERS AT REGISTERS OR DIFFUSERS. 26. ALL VOLUME DAMPERS IN INACCESSIBLE CEILINGS SHALL BE CABLE OPERATED. 27. PROVIDE ALL SUPPLY AIR, RETURN AIR AND EXHAUST AIR DUCT ELBOWS WITH SINGLE THICKNESS TURNING VANES. 28. CEILING DIFFUSERS, REGISTERS AND GRILLES SHALL BE LOCATED AS SHOWN ON THE ARCHITECTURAL REFLECTED CEILING PLAN. DIFFUSERS, REGISTERS AND GRILLES SHALL BE FURNISHED WITH MOUNTING FRAMES AND FEATURES IN ACCORDANCE WITH THE CEILING TYPE. 29. AIR INTAKES SHALL BE MINIMUM 10 FEET FROM ALL EXHAUST FAN OUTLETS AND PLUMBING VENTS THROUGH ROOF. W 30. ALL TRANSFER DUCTS SHALL BE SIZED AT A MAXIMUM OF 500 FPM. PROVIDE 1" ACOUSTICAL LINING. 31. INSTALL SUPPLY DUCT MOUNTED SMOKE DETECTORS AT AIR HANDLING UNITS WITH A CAPACITY GREATER THAN 2000 CFM. DEVICES SHALL BE WIRED BY FIRE ALARM CONTRACTOR. PIPING: 32. PIPING CONNECTIONS TO AIR HANDLING UNIT COILS AND MAJOR EQUIPMENT SHALL BE FABRICATED WITH ISOLATION VALVES, FLANGES, AND/OR UNIONS POSITIONED TO ALLOW REMOVAL AND SERVICE OF THE COMPONENT PARTS. 33. CONDENSATE DRAIN DISCHARGE LINE FROM AIR CONDITIONING UNITS SHALL CONNECT TO NEAREST FLOOR DRAIN. 34. WHENEVER REMOVING PIPING, DUCTWORK, ETC... REMOVE IT AND CAP IT OFF AT THE MAIN. BRANCH PIPE CONNECTION TEE-OUTLET DOWN 1. 17. FLEXIBLE DUCTWORK RUNS SHALL BE LIMITED TO 5'-0" AT THE END OF BRANCH DUCTWORK. ELBOW DOWN DUCT TEE WITH SPLITTER DAMPER GENERAL: 35. ALL PIPING SYSTEMS SHALL BE ADEQUATELY SUPPORTED FROM "BUILDING" STRUCTURE AND BE PROVIDED WITH IDENTIFICATION LABELS EVERY 20 FEET. ABBREVIATION LIST IS GENERAL IN NATURE, NOT ALL ABBREVIATIONS ARE NECESSARILY USED IN THIS PROJECT. NOTES ARE GENERAL IN NATURE, NOT ALL NOTES ARE NECESSARILY USED IN THIS PROJECT. TEE-OUTLET UP OR OR BRANCH DUCT CONNECTION, RECTANGULAR OR ROUND BRANCH WITH MANUAL VOLUME DAMPER AND RECTANGULAR TRUNK. SPLITTER WITH SPLIT SIZES SHOWN POINT OF CONNECTION, NEW TO EXISTING PIPE REDUCER GATE VALVE DUCT WITH INTERNAL LINER, DUCT SIZE SHOWN ON PLANS ARE INSIDE CLEAR DIMENSIONS 2011 by Linfield, Hunter & Junius, Inc. FRESH AIR FURNISHED BY CONTRACTOR FURNISHED BY OWNER FLEXIBLE CONNECTION FAN COIL UNIT FIRE DAMPER FLOOR DRAIN FINISHED FLOOR FINISHED FULL LOAD AMPS FLEXIBLE FLOOR FACTORY MUTUAL FINS PER INCH FEET PER MINUTE FIRE SMOKE DAMPER FEET FUTURE FACE VELOCITY 3608 18th Street, Suite 200 Metairie, Louisiana 70002 TIME: SPLITTER WITH SPLIT SIZES SHOWN F/A FBC FBO FC FCU FCW FD FF FIN FLA FLEX FLR FM FPI FPM FSD FT FUT FV APPROVED BY 1S100 RISE OR DROP IN ELEVATION F CHECKED BY R/D R/D ABS ABSOLUTE A/C AIR CONDITIONING UNIT ACCU AIR COOLED CONDENSING UNIT ACH AIR CHANGES PER HOUR ACY ACETYLENE ADA AMERICAN DISABILITIES ACT AF AIR FILTER AFF ABOVE FINISHED FLOOR AFM AIR FLOW METER AHJ AUTHORITIES HAVING JURISDICTION AHP AIR HORSEPOWER AHU AIR HANDLING UNIT AMB AMBIENT AMP AMPERE ANSI AMERICAN NATIONAL STANDARDS INSTITUTE APD AIR PRESSURE DROP AO AIR OUTLET AS AIR SEPARATOR ASHRAE AMERICAN SOCIETY OF HEATING, REFRIGERATING, AND AIR CONDITIONING ENGINEERS ASME AMERICAN SOCIETY OF MECHANICAL ENGINEERS AV AIR VENT AUTO AUTOMATIC AVD AUTOMATIC VOLUME DAMPER PROJ. NO. 12-23 DATE 10/02/2014 SHEET NO. POINT OF DEMOLITION SYMBOL LIST IS GENERAL IN NATURE, NOT ALL SYMBOLS ARE NECESSARILY USED IN THIS PROJECT. OF SHEETS DRAWN BY DUCT ACCESS DOOR A THIS SHEET AD DESCRIPTION PROFESSIONAL ENGINEERS, ARCHITECTS AND SURVEYORS SUPPLY DIFFUSER AND AIR QUANTITY. (SHADED AREA INDICATES NO THROW IN THIS DIRECTION) (24x24 FACE) SYMBOL MECHANICAL GENERAL NOTES LINFIELD, HUNTER & JUNIUS, INC. DESCRIPTION 4:55 PM SYMBOL MECHANICAL ABBREVIATIONS CITY OF KENNER - CONVERSION OF ANNE WASHINGTON COMMUNITY CENTER MECHANICAL LEGEND ESP MOTOR VOLT/PH AHU-1 1,060 0.5" 0.33 HP 208/1 30 9.6 2 AHU-2 600 0.5" 0.33 HP 208/1 24 7.7 AHU-3 550 0.5" 0.33 HP 208/1 30 AHU-4 600 0.5" 0.33 HP 208/1 24 MCA MOCP MANUFACTURER MODEL WEIGHT REMARKS 240/1 53/25 60/25 TRANE TEM3A0B30 140 LBS 1, 2 1 240/1 42 45 TRANE TEM3A0B24 140 LBS 1 7.7 1 240/1 42 45 TRANE TEM3A0B24 140 LBS 1 7.7 1 240/1 42 45 TRANE TEM3A0B24 140 LBS 1 kW STAGES VOLTS/PH REMARKS: 1. FURNISH WITH TOP DISCHARGE, BOTTOM RETURN, PLENUM STAND, AND 7-DAY PROGRAMMABLE THERMOSTAT. 2. TWO (2) ELECTRICAL CIRCUITS SHALL BE REQUIRED. MARK TONS OF COOLING REFRIGERANT SEER CU-1 2.5 R-410A CU-2 1.5 CU-3 CU-4 COOLING ELECTRICAL MANUFACTURER MODEL WEIGHT REMARKS 240/1 TRANE 4TTB3030 175 LBS 1 20 240/1 TRANE 4TTB3018 130 LBS 1 10.4 20 240/1 TRANE 4TTB3018 130 LBS 1 10.4 20 240/1 TRANE 4TTB3018 130 LBS 1 MCA MOCP VOLTS/PH - 13.0 25 18.0 MBH - 10.4 13.0 18.0 MBH - 13.0 18.0 MBH - MIN CAPACITY EVAP TEMP 13.0 30.0 MBH R-410A 13.0 1.5 R-410A 1.5 R-410A AMBIENT REMARKS: 1. FURNISH WITH FIELD INSTALLED DRIER, FIELD INSTALLED SIGHT GLASS, SERVICE VALVES, SUCTION LINE ACCUMULATOR, HIGH PRESSURE SWITCH, START KIT, CYCLE PROTECTOR, AND THERMOSTATIC EXPANSION VALVE. AIR FLOW MIN MAX MAX APD IN WG SQUARE - 125 0.100 CEILING SURFACE 12x12 S-2 LOUVERED FACE - 130 0.100 WALL 10x8 T-1 LOUVERED FACE - 130 0.100 WALL R-1 LOUVERED FACE - 1400 0.05 R-2 LOUVERED FACE - 1400 0.05 MARK TYPE S-1 MOUNTING FACE SIZE NECK SIZE MAX NC DAMPER FINISH MANUFACTURER MODEL REMARKS 20 OPD - TITUS TMS-AA 1 8x6 20 OPD - TITUS 300FL 1 10x8 8x6 20 NONE - TITUS 301FL 1 CEILING 36 x 18 34 x 16 20 NONE - TITUS 350FL 1 CEILING 36 x 18 34 x 16 20 NONE - TITUS 350FL 1 REMARKS: 1. PROVIDE FULL RANGE OF MANUFACTURER'S COLORS FOR COLOR SELECTION BY ARCHITECT. KENT A. POYSER REG. No. 37788 LOUVER SCHEDULE REGISTERED MARK SIZE CFM S.P. IN. W.C. MAX VELOCITY (FPM) MINIMUM FREE AREA MANUFACTURER MODEL SERVES REMARKS L-1 24"W x 18"H 300 >0.10 500 1.07 GREENHECK EHH-601 AHU-1 1, 2 L-2 24"W x 12"H 75 >0.10 500 0.53 GREENHECK EHH-601 AHU-1 1, 2 L-3 24"W x 12"H 300 >0.10 500 0.53 GREENHECK EHH-601 AHU-1 1, 2 L-4 24"W x 12"H 300 >0.10 500 0.53 GREENHECK EHH-601 AHU-1 1, 2 IN EXHAUST FAN SCHEDULE MARK CFM S.P. IN. W.C. INLET DB VOLTS/ PH HP/ WATTS MANUFACTURER MODEL WEIGHT REMARKS EF-1 75 0.3 41 115/1 54W GREENHECK SP-B80 15 LBS 1 EF-2 75 0.3 41 115/1 54W GREENHECK SP-B80 15 LBS 1 EF-3 75 0.3 41 115/1 54W GREENHECK SP-B80 15 LBS 1 EF-4 75 0.3 41 115/1 54W GREENHECK SP-B80 15 LBS 1 EF-5 75 0.3 41 115/1 54W GREENHECK SP-B80 15 LBS 1 REMARKS: 1. FURNISH WITH DESIGNER GRILLE AND HOODED WALL CAP. CHECKED BY 1. FURNISH WITH BIRD SCREEN AND OPPOSED BLADE DAMPER. 2. COORDINATE LOUVER COLOR WITH ARCHITECT. APPROVED BY REMARKS: PROJ. NO. 12-23 DATE 10/02/2014 SHEET NO. OF SHEETS DRAWN BY FILE: P:\LinfieldHunter&Junius\14-098_CommunityResourceCenter\Design Documents\Drawings\Mechanical\M-001 MECHANICAL SCHEDULES.dwg AIR DEVICE SCHEDULE THIS SHEET DATE: 10/1/2014 CONDENSING UNIT SCHEDULE (OUTDOOR UNIT) 2011 by Linfield, Hunter & Junius, Inc. CFM 3608 18th Street, Suite 200 Metairie, Louisiana 70002 ELECTRIC HEAT PROFESSIONAL ENGINEERS, ARCHITECTS AND SURVEYORS LINFIELD, HUNTER & JUNIUS, INC. FAN COOLING TMBH MARK CITY OF KENNER - CONVERSION OF ANNE WASHINGTON COMMUNITY CENTER TIME: 4:54 PM AIR HANDLING UNIT SCHEDULE (INDOOR UNIT) S-1 75 S-2 75 EF-5 AHU-2 BATHROOM S-1 50 218 S-2 75 LIVING ROOM/ BEDROOM 217 CONNECT OUTSIDE AIR LOUVER L-2 TO RETURN AIR PLENUM AT BASE OF UNIT. BALANCE TO 100 CFM. CONNECT OUTSIDE AIR LOUVER L-3 TO RETURN AIR PLENUM AT BASE OF UNIT. BALANCE TO 100 CFM. CONNECT OUTSIDE AIR LOUVER L-4 TO RETURN AIR PLENUM AT BASE OF UNIT. BALANCE TO 100 CFM. KENT A. POYSER REG. No. 37788 REGISTERED S-1 100 T-1 - S-1 115 AHU-4 S-1 125 T CONNECT RETURN AIR GRILLE TO RETURN AIR PLENUM AT BASE OF UNIT. LINE RETURN AIR PLENUM WITH 1/2" ACOUSTICAL DUCT LINER. PROVIDE 4" DRYER EXHAUST VENT THROUGH THE EXTERIOR WALL AND AND FINISH WITH HOODED WALL CAP. 2011 by Linfield, Hunter & Junius, Inc. BATHROOM 209 PLAN NOTES: CONNECT OUTSIDE AIR LOUVER L-1 TO RETURN AIR PLENUM AT BASE OF UNIT. BALANCE TO 250 CFM. EF-4 BEDROOM #4 (ADA) 118 S-1 125 S-2 75 KITCHEN/ DINING 216 LIVING ROOM/ BEDROOM 211 T S-1 125 AHU-3 CORRIDOR 112 KITCHEN/ DINING 212 EF-2 BATHROOM (ADA) 111 BEDROOM #3 115 S-1 75 S-1 50 S-1 125 R-2 - S-1 115 T-1 - BEDROOM #2 110 S-1 125 R-2 - IN LAUNDRY ROOM 113 16x10 SA AHU-3 AHU-1 AHU-4 L-4 R-1 - L-1 L-3 CU-4 CU-3 CU-2 CU-1 APPROVED BY THERMOSTATS SHALL BE MOUNTED AT 48" A.F.F. UNLESS OTHERWISE NOTED. S-1 115 CHECKED BY 8. T-1 - S-1 115 PROJ. NO. 12-23 DATE 10/02/2014 SHEET NO. OF SHEETS DRAWN BY SIZE AND ROUTE REFRIGERANT PIPING PER REQUIREMENTS AND RECOMMENDATIONS BY EQUIPMENT MANUFACTURER. T-1 - S-1 75 S-1 50 S-1 75 KITCHEN 119 BEDROOM #1 107 S-1 75 CORRIDOR 200 S-1 50 THIS SHEET 7. T BEDROOM 205 8x6 SA S-1 100 BATHROOM 106 CITY OF KENNER - CONVERSION OF ANNE WASHINGTON COMMUNITY CENTER ALL DIFFUSERS AND GRILLES SHALL BE FURNISHED WITH OPPOSED BLADE DAMPERS. S-1 75 EF-1 REFER TO THE ARCHITECTURAL REFLECTED CEILING PLANS FOR CEILING GRID ROOM LAYOUTS AND COORDINATE ALL GRILLES, REGISTERS, AND DIFFUSERS WITH CORRESPONDING REFLECTED CEILING PLANS. 6. LIVING ROOM / DINING 102 16x10 SA 5. S-1 75 STAIRWELL 219 BECAUSE OF THE LIMITED SPACE AVAILABLE TO INSTALL ALL OF THE MECHANICAL WORK, COORDINATION BETWEEN THE VARIOUS TRADES IS OF THE UTMOST IMPORTANCE. 4. IF THE HEATING CONTRACTOR DOES NOT CLEARLY UNDERSTAND THESE PLANS, OR IS NOT SURE OF THEIR MEANING, HE SHOULD OBTAIN THE ENGINEER'S WRITTEN EXPLANATION AND INTERPRETATION, PRIOR TO SUBMITTING HIS BID, SINCE THE HEATING CONTRACTOR WILL BE HELD RIGIDLY TO THE INTERPRETATION OF THE ENGINEER. LIVING ROOM 201 S-1 75 16x10 SA EF-3 OFFICE/ CHECK-IN 101 3608 18th Street, Suite 200 Metairie, Louisiana 70002 8x6 SA 8x6 SA S-1 50 12x10 SA 3. S-1 100 T CONTRACTOR TO COORDINATE ALL DEMOLITION & NEW CONSTRUCTION WITH THE PROJECT CONSTRUCTION MANAGER AND ALL OTHER TRADES PER PROJECT AREA PHASING. ALL ELBOWS, FITTINGS, ETC. IN PIPING AND DUCTWORK ARE NOT NECESSARILY INDICATED TO CLEAR ALL EXISTING AND NEW JOB OBSTRUCTIONS. S-2 100 AHU-1 12x10 SA 2. S-1 75 KITCHEN/ DINING 203 PROFESSIONAL ENGINEERS, ARCHITECTS AND SURVEYORS LINFIELD, HUNTER & JUNIUS, INC. THE OWNER SHALL MAINTAIN ALL SALVAGE RIGHTS OF EQUIPMENT AND MATERIALS REMOVED. ALL EQUIPMENT AND MATERIALS NOT CLAIMED BY THE OWNER SHALL BE REMOVED FROM THE PREMISES BY THE CONTRACTOR. THESE PLANS ARE DIAGRAMMATIC IN NATURE SINCE THEY REFLECT ONLY THE AVAILABLE INFORMATION OBTAINED FROM EXISTING PLANS, SPECIFICATIONS, AND FIELD SURVEYS. THE EXACT LOCATION OF EXISTING DUCTWORK, PIPING, AND EQUIPMENT MAY DEVIATE FROM THE LOCATION INDICATED ON THESE DRAWINGS. THE CONTRACTOR SHALL BE PREPARED TO MAKE SOME ALTERATIONS TO NEW AND/OR EXISTING SERVICES TO FIT ACTUAL JOB CONDITIONS. S-1 75 S-2 100 BATHROOM 202 1. ENTRANCE CORRIDOR 100 R-2 - ALL EXISTING MECHANICAL ITEMS SHALL BE REMOVED, INCLUDING AIR HANDLING UNITS, CONDENSING UNITS, CONTROLS, REFRIGERANT PIPING, DUCTWORK, DIFFUSERS, AND ACCESSORIES. GENERAL MECHANICAL NOTES: FILE: P:\LinfieldHunter&Junius\14-098_CommunityResourceCenter\Design Documents\Drawings\Mechanical\M-201 MECHANICAL PLANS.dwg 12x10 SA 16x10 SA 5. ENTRANCE CORRIDOR (BELOW) IF THE HEATING CONTRACTOR DOES NOT CLEARLY UNDERSTAND THESE PLANS, OR IS NOT SURE OF THEIR MEANING, HE SHOULD OBTAIN THE ENGINEER'S WRITTEN EXPLANATION AND INTERPRETATION, PRIOR TO SUBMITTING HIS BID, SINCE THE HEATING CONTRACTOR WILL BE HELD RIGIDLY TO THE INTERPRETATION OF THE ENGINEER. 12x10 SA DATE: 10/1/2014 4. AHU-2 12x10 SA 3. L-2 12x10 SA 2. THESE PLANS ARE DIAGRAMMATIC IN NATURE SINCE THEY REFLECT ONLY THE AVAILABLE INFORMATION OBTAINED FROM EXISTING PLANS, SPECIFICATIONS, AND FIELD SURVEYS. THE EXACT LOCATION OF EXISTING DUCTWORK, PIPING, AND EQUIPMENT MAY DEVIATE FROM THE LOCATION INDICATED ON THESE DRAWINGS. THE CONTRACTOR SHALL BE PREPARED TO MAKE SOME ALTERATIONS TO NEW AND/OR EXISTING SERVICES TO FIT ACTUAL JOB CONDITIONS. 12x10 SA 1. 12x10 SA TIME: 4:53 PM GENERAL DEMOLITION NOTES: * L W ** SUPPORT FANS W/ METAL STRAPS FROM STRUCTURE ABOVE WALL CAP USE THIS WITH RECTANGULAR DUCT USE THIS WITH ROUND DUCT TAKEOFF'S ENTRY FITTING: L= 1/4 W, (4" MIN.) (MAY ALSO BE PARALLEL FLOW FITTING) EXH DUCT-SEE PLANS FOR SIZE ** EXTERIOR WALL * = BRANCH TO INDIVIDUAL DIFFUSER OR GRILLE 4 SCALE: NTS CEILING MOUNTED EXHAUST FAN DETAIL SCALE: NTS KENT A. POYSER REG. No. 37788 REGISTERED IN SEE SPECIFIATIONS FOR PIPING MATERIAL. OPEN VENT FIELD POWER SUPPLY CONN FIELD CONTROL SUPPLY CONN. FULL CONN. SIZE PIPE MIN. 1 1/4 " X ELEVATE A/C UNIT SUFFICIENT DISTANCE ABOVE FLOOR OR ROOF TO ALLOW FOR INSTALLATION OF TRAP WITH ADEQUATE DIMENSIONS TO WITHSTAND SYSTEM OPERATING PRESSURE. COORDINATE WITH DETAIL FOR A UNIT MOUNTING. ELBOW NOTES: -FOLLOW MFR'S INSTRUCTIONS FOR INSTALLATION OF SUPPLY DIFFUSER IN CEILING -SEE SPECIFICATIONS FOR DUCT SUPPORTS, FABRICATION AND INSTALLATION BOTTOM 4" THICK MINIMUM CONCRETE MOUNTING PAD ELASTOMERIC ISOLATION PADS, FOUR (4) PER CONDENSING UNIT 3 CONDENSING UNIT MOUNTING DETAIL 6" MIN. SCALE: NTS COOLING COIL CONDENSATE DRAIN SCALE: NTS SHEET METAL SCREW (TYPICAL) PIPE SUPPORT, MAX. SPACING OF PIPE SUPPORTS 4'-0" TOTAL HEIGHT OF TRAP= X+H+ ( 1 1/2 x PIPE DIAMETER ) FOR DRAW THRU UNITS FOR BLOW THRU UNITS X= MIN. 1/2 H (PREFERRED X=H) X= FAN STATIC PRESSURE +1" H= NEGATIVE STATIC PRESSURE +1" H= MIN. 1" 2 SPIN-IN FITTING WITH MANUAL VOLUME DAMPER (NO EXTRACTOR USED) SECURING STRAP PANDUIT (OR EQUAL) SLOPE CONDENSATE PIPING @1/8" PER FOOT TO ROOF DRAIN TURN PIPE DOWN AT NEAREST FLOOR DRAIN, UNLESS SHOWN OTHERWISE ON PLANS. SUPPLY DUCT CEILING 1 SUPPLY DIFFUSER WITH INSULATED BACK PANEL DUCTWORK CONNECTION TO SUPPLY DIFFUSER (FLEX DUCT) SCALE: NTS CHECKED BY TEE H PROJ. NO. 12-23 DATE 10/02/2014 SHEET NO. OF SHEETS DRAWN BY NOTE: THIS SHEET FLEXIBLE DUCT MAXIMUM FLEXIBLE DUCT LENGTH 6'-0" APPROVED BY UNION TEE CITY OF KENNER - CONVERSION OF ANNE WASHINGTON COMMUNITY CENTER 3" "TAP-OUT" EITHER SIDE OR BOTTOM OF DUCT. TOP "TAP-OUT" IS NOT ACCEPTABLE DRAIN PAN CONNECTION CLEAN-OUT PLUG TOTAL HEIGHT FILE: P:\LinfieldHunter&Junius\14-098_CommunityResourceCenter\Design Documents\Drawings\Mechanical\M-301 MECHANICAL DETAILS.dwg ** = SUBMAIN, BRANCHMAIN , OR BRANCH. LOW PRESSURE DUCT VOLUME DAMPER REQUIREMENTS 2011 by Linfield, Hunter & Junius, Inc. CEILING ASSEMBLY REFER TO ARCH DWGS FOR TYPE EXHAUST GRILLE, INTEGRAL WITH FAN 5 3608 18th Street, Suite 200 Metairie, Louisiana 70002 SPIN-IN FITTING WITH MANUAL VOLUME DAMPER PROFESSIONAL ENGINEERS, ARCHITECTS AND SURVEYORS DATE: 10/1/2014 TYPICAL MANUAL VOLUME DAMPER LINFIELD, HUNTER & JUNIUS, INC. 4:51 PM TIME: MAIN SUPPLY RETURN OR EXHAUST DUCT F. MATERIAL EXPOSED WITHIN DUCTS OR PLENUMS SHALL HAVE A FLAME-SPREAD INDEX OF NOT MORE THAN 25 AND A SMOKE-DEVELOPED RATING OF NOT MORE THAN 50 IN ACCORDANCE WITH SECTION 102 (A), IMC (675 IAC 18-1). G. DRAWINGS (PLANS, SCHEMATICS, AND DIAGRAMS) INDICATE GENERAL LOCATION AND ARRANGEMENT OF PIPING, DUCTWORK, AND EQUIPMENT. THE LOCATIONS AND ARRANGEMENT TAKE INTO CONSIDERATION PIPE SIZING AND FRICTION LOSS, EXPANSION, PUMP SIZING, AND OTHER DESIGN PARAMETERS. CLEARANCES ABOVE CEILINGS IN CERTAIN AREAS ARE LIMITED AND NECESSITATE DUCTWORK AND/OR PIPING ROUTINGS. WHERE POSSIBLE, PIPING, DUCTWORK, AND EQUIPMENT SHALL BE INSTALLED AS INDICATED. CHANGES REQUIRED TO MEET ARCHITECTURAL AND STRUCTURAL CONDITIONS ARE TO BE APPROVED BY THE ENGINEER. NEW PIPING, DUCTWORK, ETC. SHALL BE SUPPORTED FROM THE BUILDING STRUCTURE ONLY, AND NOT FROM ANY NEW OR EXISTING EQUIPMENT, DUCTWORK, ETC. A. THE MECHANICAL CONTRACTOR SHALL FURNISH AND INSTALL NEW AIR HANDLING UNITS AS SHOWN AND DETAILED ON THE DRAWINGS. THE NEW AIR HANDLING UNITS SHALL BE AS MANUFACTURED BY THE TRANE COMPANY, YORK INTERNATIONAL, OR CARRIER CORPORATION. B. ALL SHEET METAL DUCTWORK SHALL BE G-90 COATED GALVANIZED STEEL CONFORMING TO ASTM A653 AND A924 STANDARDS OF GAUGE AND REINFORCEMENT. DUCTWORK SHALL BE AIRTIGHT (5% LEAKAGE). FABRICATE ELBOWS WITH CENTERLINE RADIUS EQUAL TO 1.5 TIMES THE DUCT WIDTH IN THE PLANE OF THE TURN UNLESS SPECIFICALLY NOTED OTHERWISE; ALL ELBOWS SHALL BE FABRICATED WITH FACTORY MANUFACTURED TURNING VANES. LIMIT C. DUCT DIMENSIONS ARE "FREE AREA" AND SHALL NOT BE REDUCED. ALL SUPPLY AIR RECTANGULAR, ROUND, AND OVAL DUCT SHALL BE WRAPPED EXTERNALLY WITH 1-1/2" THICK FLEXIBLE FIBERGLASS INSULATION IN CONCEALED LOCATIONS (IN CHASES AND ABOVE CEILINGS). ALL MIXED AIR DUCTWORK SHALL BE WRAPPED EXTERNALLY WITH 1-1/2" THICK FLEXIBLE FIBERGLASS INSULATION. RETURN DUCT AND EXHAUST DUCT NEED NOT BE INSULATED OR LINED. USE 2" RIGID FIBER BOARD EXTERNAL INSULATION FOR ALL SUPPLY DUCTWORK LOCATED IN THE MECHANICAL ROOMS AND FOR ALL OUTSIDE AIR INTAKE DUCTWORK. D. MINERAL-FIBER BLANKET INSULATION SHALL BE SECURED WITH ADHESIVE AND ANCHOR PINS AND SPEED WASHERS ON EACH SIDE AND BOTTOM OF HORIZONTAL DUCTS AND ALL SIDES OF VERTICAL DUCTS. INSTALL ANCHOR PINS AND SPEED WASHERS SPACED 16" O.C. EACH WAY, AND 3" MAX. FROM INSULATION JOINTS. APPLY ADDITIONAL PINS AND CLIPS TO HOLD INSULATION TIGHTLY AGAINST SURFACE AT CROSS BRACING. ANCHOR PINS MAY BE OMITTED FROM TOP SURFACE OF HORIZONTAL, RECTANGULAR DUCTS AND PLENUMS. E. MAXIMUM STRAIGHT LENGTH OF FLEX DUCT SHALL BE 6'-0". F. FLEXIBLE DUCT SHALL NOT BE USED IN PLACE OF ELBOWS. G. SUPPLY AIR DUCT TAKEOFFS SHALL NOT BE PLACED CLOSER THAN 12" FROM THE END OF A TRUNK OR LESS THAN 24" DOWNSTREAM FROM AN ELBOW. H. INSTALL INSULATION PRODUCTS ON SPECIFIED DUCTWORK, PIPING, AND EQUIPMENT IN ACCORDANCE WITH MANUFACTURER'S WRITTEN INSTRUCTIONS AND IN ACCORDANCE WITH RECOGNIZED INDUSTRY PRACTICES TO ENSURE THAT THE INSULATION SERVES ITS INTENDED PURPOSE. 1.2 WORK INCLUDED A. THE MECHANICAL CONTRACTOR SHALL FURNISH ALL LABOR, MATERIAL, ACCESSORIES, TOOLS, ETC. TO COMPLETE THE HEATING, VENTILATING AND AIR CONDITIONING WORK AS INDICATED AND SPECIFIED. H. AIR DEVICES SHALL BE TYPE AND SIZE LISTED ON THE DRAWINGS, OR SIMILAR BY KRUEGER, PRICE, TUTTLE & BAILEY, OR NAILOR, SUBJECT TO COMPLIANCE WITH REQUIREMENTS. I. FLEXIBLE DUCT (AS NOTED ON DRAWINGS) SHALL BE RATED FOR LOW VELOCITY (1+ IN. W.G.). CONTRACTOR SHALL INSTALL FLEXDUCT PER MANUFACTURER'S RECOMMENDATIONS. MAXIMUM LENGTH SHALL NOT EXCEED 6'-0" WHERE SUPPLYING AN AIR DEVICE. 2.2 IDENTIFICATION FILE: P:\LinfieldHunter&Junius\14-098_CommunityResourceCenter\Design Documents\Drawings\Mechanical\M-401 MECHANICAL SPECIFICATIONS.dwg B. MECHANICAL WORK SHALL INCLUDE IN GENERAL TERMS, BUT NOT LIMITED TO THE FOLLOWING: 1. DEMOLITION OF ALL EXISTING MECHANICAL SYSTEMS, INCLUDING (BUT NOT LIMITED TO) ALL AIR HANDLING UNITS, CONDENSING UNITS, DUCTWORK, PIPING, CONTROLS, AND ACCESSORIES. 2. INSTALLATION OF NEW MECHANICAL SYSTEMS AS SHOWN ON THE DOCUMENTS. 1.3 SHOP DRAWINGS A. SUBMIT ONE ELECTRONIC COPY ON ALL EQUIPMENT FURNISHED UNDER THIS CONTRACT, INCLUDING AIR DISTRIBUTION DEVICES, AUTOMATIC FLOW CONTROL VALVES, MANUAL VOLUME DAMPERS AND MANUAL CIRCUIT SETTERS. B. ANY PRODUCT MANUFACTURER LISTED ON THE DRAWINGS OR IN THE PROJECT MANUAL AS A PRE-APPROVED EQUAL MUST BE SUBMITTED TO ENGINEER FOR APPROVAL NOT LESS THAN SEVEN DAYS PRIOR TO BID DATE. C. THE CONTRACTOR SHALL SUPPLY THREE COPIES OF OPERATIONS AND MAINTENANCE MANUALS (O&M), AND ONE COPY OF AS-BUILT DRAWINGS WHEN THE JOB IS COMPLETED. O&M MANUALS SHALL INCLUDE EQUIPMENT CUTS AND WIRING DIAGRAMS. 1.4 CUTTING AND PATCHING A. THIS CONTRACTOR SHALL CUT AND PATCH ALL HOLES IN THE INTERIOR PARTITIONS AND CEILINGS AS REQUIRED FOR THE INSTALLATION OF HIS WORK. G.C. SHALL BE RESPONSIBLE FOR CUTTING NEW OPENINGS IN OUTSIDE WALLS, FLOORS, AND FOR PATCHING ALL OPENINGS RESULTED BY MECHANICAL SCOPE OF WORK, EXCEPT PATCHING FIRE RATED PENETRATIONS. PATCHING SHALL MATCH EXISTING AREAS AND SHALL BE DONE BY WORKMEN SKILLED IN THE APPROPRIATE TRADE. A. ALL EQUIPMENT SHALL HAVE ENGRAVED, PLASTIC NAMEPLATES. PLASTIC NAMEPLATES SHALL BE BLUE IN COLOR, WITH WHITE LETTERING A MINIMUM OF 3/4" IN HEIGHT. NAMEPLATE SHALL IDENTIFY EQUIPMENT NAME AND NUMBER. (FOR EXAMPLE; "AIR HANDLING UNIT "5-AHU-2C") 2.3 REFRIGERANT PIPING A. INSTALL HANGERS, SUPPORTS, CLAMPS AND ATTACHMENTS TO SUPPORT PIPING PROPERLY FROM BUILDING STRUCTURE; COMPLY WITH MSS SP-69. ARRANGE FOR GROUPING OF PARALLEL RUNS OF HORIZONTAL PIPING TO BE SUPPORTED TOGETHER ON TRAPEZE HANGERS WHERE POSSIBLE. ALL PIPING HANGER AND SUPPORTS SHALL BE UL OR FM APPROVED. B. ALL PIPING SUPPORTS OR STRAPS SHALL HAVE A THERMAL SHIELD TO PREVENT CONDENSATION. I. WHEN BRAZING OR SOLDERING, REMOVE SOLENOID-VALVE COILS AND SIGHT GLASSES, VALVE STEMS, SEATS, AND PACKING, AND ACCESSIBLE INTERNAL PARTS OF REFRIGERANT SPECIALTIES. DO NOT APPLY HEAT NEAR EXPANSION-VALVE BULB. CLEAN ALL JOINTS BEFORE BRAZING. ALL BRAZING OPERATIONS SHALL BE PERFORMED USING DRY NITROGEN DRIFT PROCEDURE TO PREVENT EXCESS OXIDATION. B. INSTALL STEEL PIPE FOR SLEEVES SMALLER THAN 6 INCHES IN DIAMETER. INSTALL CAST-IRON WALL PIPES FOR SLEEVES 6 INCHES AND LARGER IN DIAMETER. ALL UNDERGROUND, EXTERIOR-WALL PIPE PENETRATIONS SHALL HAVE CAST-IRON WALL PIPES FOR SLEEVES. J. REFRIGERANT: R-410 C. LIMIT THE SIZE OF THE SPACE BETWEEN THE OPENING AND THE OUTSIDE OF THE DUCT OR PIPE TO 1" MAXIMUM. 1.7 COORDINATION OF WORK A. COORDINATE THE WORK WITH OTHER DISCIPLINES ON THE JOB. CLEARANCES ARE CRITICAL AND THERE SHALL BE COMPLETE COOPERATION BETWEEN ALL TRADES. THERE WILL BE NO EXTRA COSTS ALLOWED FOR THE INABILITY OF THIS CONTRACTOR TO COORDINATE HIS WORK WITH CABLE TRAYS AND OTHER EQUIPMENT/SYSTEMS PROVIDED BY OWNER/OTHER CONTRACTORS. B. ALL WORK SHALL BE DONE DURING NORMAL WORKING HOURS EXCEPT WHEN SPECIFICALLY AUTHORIZED BY THE OWNER OR WHEN IT MAY BENEFIT THE CONTRACTOR DIRECTLY. G. THE UNIT SHALL HAVE STANDARD 1 INCH THROWAWAY FILTERS AND SHALL BE SIZED AT 500 FPM MAX. H. THE MOTORS SHALL HAVE PLUS OR MINUS 10 PERCENT VOLTAGE UTILIZATION RANGE. THE MOTOR SHALL MEET NEMA PREMIUM EFFICIENCY SPECIFICATIONS, AND SHALL BE OPEN DRIP PROOF, WITH PERMANENTLY SEALED BALL BEARINGS, INTERNAL CURRENT AND THERMAL OVERLOAD PROTECTION, A 1.15 SERVICE FACTOR AND SHALL BE FACTORY INSTALLED AND WIRED TO THE UNIT. K. ALL PIPING SHALL BE TESTED AND FLUSHED PRIOR TO INSULATION AND ACCEPTANCE. SUCTION LINES SHALL BE TESTED AT 185 PSIG. HOT-GAS & LIQUID LINES SHALL BE TESTED AT 325 PSIG. L. PIPING INSTALLATION: INSTALL REFRIGERANT PIPING ACCORDING TO ASHRAE 15. REFRIGERANT PIPING SHALL BE SUPPORTED BY THE FLOOR, WALLS OR CEILING ONLY. 1. 2. 3. 4. 5. INSTALL SO THAT INSULATION MAY BE APPLIED WHERE REQUIRED. INSTALL HORIZONTAL SUCTION LINES WITH UNIFORM SLOPE OF .4% DOWNWARD TO COMPRESSORS. INSTALL TRAPS AND DOUBLE RISERS WHERE REQUIRED TO ENTRAIN OIL IN VERTICAL RUNS. LIQUID LINES MAY BE INSTALLED LEVEL. PROVIDE BYPASS AROUND ALL MOISTURE-LIQUID INDICATORS. PROVIDE ALL PIPING, VALVES AND FITTINGS NECESSARY TO INSTALL BYPASS. 6. REPLACEABLE CORE-FILTER DRYERS SHALL HAVE ISOLATION VALVES AND VALVED BYPASS. 7. REFRIGERANT VALVES SHALL BE INSTALLED ACCORDING TO MANUFACTURE RECOMMENDATIONS. 8. MOUNT THERMOSTATIC EXPANSION VALVES IN ANY POSITION, CLOSE TO EVAPORATOR. 9. CHARGE AND PURGE SYSTEMS, AFTER TESTING, AND DISPOSE OF REFRIGERANT FOLLOWING ASHRAE 15 PROCEDURES. 10. INSTALL HORIZONTAL HOT-GAS DISCHARGE PIPING WITH UNIFORM DOWNWARD SLOPE AWAY FROM COMPRESSOR. M. ALL REFRIGERANT PIPING SHALL BE INSTALLED IN ACCORDANCE WITH THE UNIT MANUFACTURERS SPECIFIC REQUIREMENTS, BASED ON THE EQUIPMENT SELECTED. MECHANICAL CONTRACTOR SHALL PROVIDE MANUFACTURER APPROVED REFRIGERANT PIPING SUBMITTALS, INCLUDING ACCURATE PIPING DIAGRAM (PIPING LENGTH & ELEVATION CHANGES CLEARLY SHOWN), PIPE SIZES AND CONTROL DEVICES, TO THE ENGINEER FOR APPROVAL. 2.7 CEILING / IN-LINE FAN A. FURNISH AND INSTALL DUCT MOUNTED, DIRECT DRIVEN, CENTRIFUGAL INLINE FAN. B. FAN SHALL BE UL LISTED (UL 705). FAN SHALL BEAR THE AMCA CERTIFIED RATINGS SEAL FOR SOUND AND AIR PERFORMANCE. PART 3 PERFORMANCE BALANCING A. A COMPLETE AIR TEST AND BALANCE SHALL BE PERFORMED IN ACCORDANCE WITH NEBB OR AABC NATIONAL STANDARDS FOR FIELD MEASUREMENTS AND INSTRUMENTATION. MECHANICAL CONTRACTOR SHALL CHANGE BELTS AND SHEAVES ON AIR HANDLING EQUIPMENT AS DIRECTED BY BALANCING CONTRACTOR IF REQUIRED TO ACHIEVE DESIGN PARAMETERS AT NO ADDITIONAL COST TO THE OWNER. B. TEST AND BALANCE THE AIR DISTRIBUTION WITHIN 5% OF THE DESIGN. TEST AND BALANCE THE WATER SYSTEM TO WITHIN 5% OF THE DESIGN. C. IT IS THE BALANCING CONTRACTOR'S RESPONSIBILITY UPON FINDING ANY DEFICIENCIES IN THE SYSTEM DUCTWORK OR PIPING TO IMMEDIATELY BRING IT TO THE ATTENTION OF THE ENGINEER. D. CHECK ALL DEVICES IN THE CONTROL SYSTEM FOR FUNCTION AND CALIBRATION. E. PREPARE FOUR COPIES OF THE FINAL WRITTEN REPORT. F. THE BALANCING CONTRACTOR SHALL BE PREPARED TO DEMONSTRATE TO THE OWNER AND THE ENGINEERS THAT THE ACTUAL CONDITIONS MATCH THE BALANCE REPORT. ALL T & B WORK SHALL BE CONDUCTED WITH EQUIPMENT OPERATING UNDER OPTIMAL DESIGN CONDITIONS. ALL SYSTEMS SHALL BE FULLY INSTALLED, OPERATIONAL AND PROGRAMMED PRIOR TO THE T & B CONTRACTOR BEGINNING THE TESTING PROCEDURES. THE T & B CONTRACTOR SHALL RECEIVE A COPY OF THE "SYSTEM PRE-COMMISSION CERTIFICATION", SIGNED AND DATED BY BOTH THE GENERAL CONTRACTOR AND THE TEMPERATURE CONTROL CONTRACTOR, PRIOR TO SCHEDULING ANY TEST/BALANCING WORK. THIS CERTIFICATION IS TO VERIFY THAT ALL NEW AND EXISTING (MODIFIED) SYSTEMS ARE READY FOR FINAL TESTING AND COMMISSIONING BY THE T & B FIRM AS PER THE SCOPE OF THE PROJECT. THE FOLLOWING GUIDELINES FOR EACH SYSTEM SHALL BE FOLLOWED (NOT ALL EQUIPMENT IS LISTED): 1. AIR HANDLING UNITS AND AIR OUTLETS: C. THE FAN HOUSING SHALL BE MINIMUM 20 GAUGE GALVANIZED STEEL AND ACOUSTICALLY INSULATED. BLOWER AND MOTOR ASSEMBLY SHALL BE MOUNTED TO A MINIMUM 14 GAUGE REINFORCING CHANNEL AND SHALL BE REMOVABLE FROM HOUSING. D. MOTOR SHALL BE MOUNTED ON RUBBER-IN-SHEAR VIBRATION ISOLATORS. UNIT SHALL BE SUPPLIED WITH INTEGRAL WIRING BOX AND RECEPTACLE. THE OUTLET DUCT COLLAR SHALL INCLUDE A REINFORCED ALUMINUM DAMPER WITH CONTINUOUS ALUMINUM HINGE ROD AND BRASS BUSHINGS. AN INLET DUCT COLLAR SHALL BE PROVIDED TO ACCOMMODATE A SLIP-FIT DUCT CONNECTION. A. FURNISH AND INSTALL NEW CONDENSING UNITS AS SHOWN AND SCHEDULED ON THE DRAWINGS. B. THE CONDENSING UNITS SHALL BE UL LISTED AND SHALL BE CERTIFIED AND RATED IN ACCORDANCE WITH ARI STANDARD 210/240. C. THE CASING SHALL BE CONSTRUCTED OF 18 GAUGE ZINC COATED HEAVY GAUGE, GALVANIZED STEEL. EXTERIOR SURFACES SHALL BE CLEANED, PHOSPHATIZED AND FINISHED WITH A WEATHER-RESISTANT BAKED ENAMEL FINISH. UNITS SHALL HAVE REMOVABLE END PANELS WHICH ALLOW ACCESS TO ALL MAJOR COMPONENTS AND CONTROLS. D. REFRIGERATION SYSTEM SHALL HAVE AN INTEGRAL SUBCOOLING CIRCUIT, LIQUID AND SUCTION GAS LINE SERVICE VALVES WITH GAUGE PORTS. E. EACH COMPRESSOR SHALL BE A DIRECT-DRIVE HERMETIC TYPE WITH CENTRIFUGAL OIL PUMP AND PROVIDE POSITIVE LUBRICATION TO ALL MOVING PARTS. MOTORS SHALL BE SUCTION COOLED AND SHALL OPERATE WITHIN PLUS OR MINUS OF 10 PERCENT OF NAMEPLATE VOLTAGE. THE UNITS SHALL BE PROVIDED WITH CRANKCASE HEATERS, INTERNAL TEMPERATURE AND CURRENT-SENSITIVE MOTOR OVERLOADS. COMPRESSORS SHALL BE MOUNTED ON SPRING ISOLATION. EXTERNAL HIGH AND LOW CUTOUT DEVICES SHALL BE PROVIDED. F. CONDENSER COIL SHALL BE 3/8" COPPER TUBES MECHANICALLY BONDED TO ALUMINUM PLATE FINS. FACTORY PRESSURE TESTED TO 425 PSIG AIR PRESSURE. PROVIDE HAIL PROTECTION CONDENSER COIL GUARD. G. CONDENSER FAN SHALL BE DIRECT-DRIVE, STATICALLY AND DYNAMICALLY BALANCED PROPELLER FAN WITH ALUMINUM BLADES AND STEEL HUB. MOTORS SHALL HAVE BUILT IN CURRENT AND THERMAL OVERLOAD PROTECTION. H. CONDENSING UNITS SHALL BE COMPLETELY FACTORY WIRED. CONTROL WIRING SHALL BE 24-VOLT INCLUDING FUSING AND TRANSFORMER. THE FOLLOWING OPTIONS SHALL BE INCLUDED: VIBRATION ISOLATION, TIME DELAY RELAY, ANTI-SHORT-CYCLE TIMER. THE T & B CONTRACTOR SHALL PROVIDE A DIAGRAM OF EACH AHU, PROVIDE A STATIC PROFILE ACROSS EACH COMPONENT (FILTERS, COIL, ETC.), AND PROVIDE TOTAL STATIC PRESSURE ACROSS EACH UNIT. THE T & B CONTRACTOR SHALL BALANCE THE AIRFLOW RATE FOR EACH AIR SYSTEM TO WITHIN 10% OF DESIGN. FOR ALL NEW AND MODIFIED-EXISTING AIR HANDLING UNITS, THE T & B CONTRACTOR SHALL ADJUST THE OUTSIDE AIR DAMPER AND RETURN AIR DAMPER POSITIONS TO ACHIEVE TOTAL DESIGN AIRFLOW RATE UNDER BOTH SUMMER COOLING MODE (MINIMUM OUTSIDE AIR WITH MECHANICAL COOLING ON) AND WINTER ECONOMIZER MODE (100% OUTSIDE AIR WITH MECHANICAL COOLING LOCKED OUT). FOR EACH FAN, INCLUDE THE FOLLOWING DESIGN AND ACTUAL DATA IN THE FINAL REPORT: A. SYSTEM IDENTIFICATION B. MAKE AND MODEL NUMBER C. MANUFACTURER'S SERIAL NUMBER D. SHEAVE DIAMETER/BORE (INCHES) KENT A. POYSER REG. No. 37788 REGISTERED INCLUDE THE FOLLOWING MOTOR DATA: A. MAKE B. HORSEPOWER C. VOLTS, PHASE D. FULL LOAD AMPERAGE AND SERVICE FACTOR IN INCLUDE DESIGN AND ACTUAL TEST VALUES FOR THE FOLLOWING: A. TOTAL SUPPLY, RETURN AND OUTSIDE AIRFLOW RATES (CFM) B. TOTAL SYSTEM STATIC PRESSURE (INCHES W.G.) C. FAN RPM D. DISCHARGE STATIC PRESSURE (INCHES W.G.) E. SUCTION STATIC PRESSURE (INCHES W.G.) F. COOLING COIL STATIC PRESSURE DIFFERENTIAL (INCHES W.G.) G. OUTSIDE/RETURN AIR DAMPER LOCATION H. AVERAGE FACE VELOCITY ACROSS COIL (FPM) I. DESIGN AND ACTUAL AIRFLOW AT EACH SUPPLY AND RETURN AIR OUTLET (CFM) J. OUTSIDE AIR, RETURN AIR, AND SUPPLY AIR TEMPERATURES (DEG F.) 3.3 REPORTING THE T & B CONTRACTOR SHALL PREPARE FOUR COPIES OF THE FINAL WRITTEN T & B REPORT. THE REPORT SHALL INCLUDE SCHEMATIC LAYOUTS OF ALL AIR DISTRIBUTION SYSTEMS. THE DIAGRAMS SHALL INCLUDE AIRFLOW RATES (CFM) AND LOCATIONS. THE T & B CONTRACTOR SHALL BE PREPARED TO DEMONSTRATE TO THE OWNER AND THE ENGINEERS THAT THE ACTUAL CONDITIONS MATCH THE BALANCE REPORT. UPON COMPLETION OF THE WORK, THE T & B CONTRACTOR SHALL SIGN, DATE, AND FILL OUT THEIR PORTION OF THE "SYSTEM ACCEPTANCE SIGN OFF SHEET", INDICATING ALL APPLICABLE SYSTEMS ARE APPROVED FOR OWNER ACCEPTANCE. I. UNIT MANUFACTURER SHALL FURNISH REPLACEABLE CORE FILTER DRYER FOR EACH CONDENSING UNIT, FOR FIELD INSTALLATION AS SHOWN ON THE DETAILS. 2.9 LOUVERS A. THE MECHANICAL CONTRACTOR SHALL FURNISH AND INSTALL LOUVERS AS SHOWN ON THE DRAWINGS. THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR MEASURING AND CUTTING THE OPENINGS AND COORDINATING ACTUAL SIZE OF LOUVERS WITH MECHANICAL CONTRACTOR PRIOR TO ORDER. THE LOUVERS SHALL BE 6" DEEP, .081 EXTRUDED ALUMINUM FRAME & BLADES, 55% OR HIGHER FREE AREA, DRAINABLE, FIXED LOUVERS. PROVIDE TEST DATA ON A 4'X4' UNIT SHOWING THE LOUVER CONFORMS TO THE DATA SIMILAR TO THE LOUVER SPECIFIED. B. ALL LOUVERS SHALL BE POTTORFF, RUSKIN, AMERICAN WARMING, OR GREENHECK, SUBJECT TO COMPLIANCE WITH REQUIREMENTS SPECIFIED. 2.4 DRAIN PIPING C. LOUVERS' COLOR SELECTION FOR KYNAR FINISH SHALL BE SUBMITTED TO THE ARCHITECT FOR APPROVAL. C. THIS CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING AND RELOCATING ANY MINOR INTERFERENCE TO INCLUDE CONDUITS, HANGERS, ETC. AS THE BASE BID OF THIS PROJECT. A. DRAIN PIPING SHALL BE TYPE L COPPER PIPE WITH WROUGHT COPPER FITTINGS. 1.8 PLANS AND SPECIFICATIONS 2.5 PIPE INSULATION 2.10 ELECTRICAL MOTORS FOR HVAC EQUIPMENT A. THESE SPECIFICATIONS AND PLANS ARE MUTUALLY EXPLANATORY AND ANYTHING DESCRIBED OR SHOWN ON ONE, BUT NOT ON THE OTHER, SHALL BE CONSIDERED ON BOTH. A. INSTALL INSULATION PRODUCTS ON SPECIFIED PIPING IN ACCORDANCE WITH MANUFACTURER'S WRITTEN INSTRUCTIONS, AND IN ACCORDANCE WITH RECOGNIZED INDUSTRY PRACTICES, TO INSURE THAT THE INSULATION SERVES ITS INTENDED PURPOSE. FOR ALL PIPING INSULATION, A CONTINUOUS VAPOR RETARDER MUST BE MAINTAINED. THE INSULATION SHALL BE APPLIED WITH A CONTINUOUS, UNBROKEN MOISTURE AND VAPOR SEAL. ALL INSULATION JOINTS, SEAMS, FITTINGS AND PENETRATION LOCATIONS (I.E. P/T PORTS, VALVE STEMS, HEAT TRACE WIRING, ETC.) SHALL BE PROPERLY SEALED. IF RIGID INSERTS ARE REQUIRED, BETWEEN PIPE AND INSULATION SHIELDS, THEY SHALL BE OF EQUAL THICKNESS TO THE ADJACENT INSULATION AND SHALL BE VAPOR SEALED. A. MOTORS SHALL COMPLY WITH THIS SECTION EXCEPT WHEN STRICTER REQUIREMENTS ARE SPECIFIED IN HVAC EQUIPMENT SCHEDULES AND SECTIONS. B. SHOULD ERROR OR DISCREPANCY APPEAR ON THE PLANS OR SPECIFICATION, IT SHALL BE REFERRED TO THE ENGINEER BEFORE BIDDING. F. THERMAL PROTECTION: COMPLY WITH NEMA MG 1 REQUIREMENT FOR THERMALLY PROTECTED MOTORS. 3.2 TESTING AND BALANCING I. THE UNIT SHALL BE FURNISHED WITH A 7-DAY PROGRAMMABLE THERMOSTAT CAPABLE OF CONTROLLING BOTH THE AIR HANDLING UNIT AND ASSOCIATED CONDENSING UNIT. 2.8 CONDENSING UNITS A. INSTALL SLEEVES FOR PIPES PASSING THROUGH CONCRETE AND MASONRY WALLS AND CONCRETE FLOOR AND ROOF SLABS. SEAL ALL PIPE PENETRATIONS USING SLEEVES AND MECHANICAL SLEEVE SEALS. SELECT SLEEVE SIZE TO ALLOW FOR ADEQUATE CLEAR SPACE, BETWEEN SLEEVE AND PIPE (OR PIPE INSULATION), FOR INSTALLATION OF MECHANICAL SLEEVE SEALS AND FIRE-STOPPING MATERIALS. B. CAULKING: A SYNTHETIC ELASTOMER THAT IS UL CLASSIFIED FIRE STOP. F. THE UNIT SHALL BE FURNISHED WITH ELECTRICAL HEATING ELEMENTS AS SPECIFIED AND DETAILED ON THE DRAWINGS. COORDINATE POWER REQUIREMENTS WITH THE ELECTRICAL CONTRACTOR. E. PIPE FITTINGS SHALL BE WROUGHT COPPER STREAMLINED PATTERN COPPER FITTINGS (ASTM B 16.22). H. THERMOSTATIC EXPANSION VALVES MAY BE SOLDERED USING HARRIS STAY BRITE #8. A. FURNISH AND INSTALL CAULKING AND SEALANT FOR ALL PIPING PASSING THROUGH ALL PARTITION WALLS WHETHER CONCEALED IN CHASES, ABOVE CEILINGS OR EXPOSED. E. REFRIGERANT COOLING COILS SUCTION AND LIQUID LINE CONNECTIONS SHALL BE CLEARLY LABELED ON THE OUTSIDE OF THE UNIT. COILS SHALL BE BURST TESTED TO 450 PSIG AND PROOF TESTED TO 300 PSIG AIR PRESSURE UNDER WATER. AFTER TESTING, INSIDES OF COILS ARE TO BE DRIED, ALL CONNECTIONS ARE TO BE SEALED AND COIL SHALL BE SHIPPED WITH A CHARGE OF DRY NITROGEN. SUCTION HEADERS SHALL BE CONSTRUCTED OF COPPER TUBING. SUCTION CONNECTIONS SHALL PENETRATE UNIT CASINGS TO ALLOW FOR SWEAT CONNECTIONS TO REFRIGERANT LINES. COILS SHALL HAVE EQUALIZING VERTICAL DISTRIBUTORS SIZED ACCORDING TO THE CAPACITIES OF THE COILS. F. MOTOR SHALL MEET NEMA PREMIUM EFFICIENCY SPECIFICATIONS, AND SHALL BE OPEN DRIP PROOF TYPE WITH PERMANENTLY LUBRICATED SEALED BEARINGS AND BUILT-IN THERMAL OVERLOAD PROTECTION. 1.5 SLEEVES E. MOTORS SHALL HAVE A MINIMUM SERVICE FACTOR OF 1.15. 3.1 GENERAL INFORMATION D. THE FAN SHALL BE FORWARD CURVED, CENTRIFUGAL BLOWER TYPE EQUIPPED WITH AN ADJUSTABLE SPEED V-BELT DRIVE. THE FAN SHALL BE DYNAMICALLY BALANCED AND SHALL HAVE PERMANENTLY SEALED BALL BEARINGS. D. PIPING SHALL BE TYPE ACR, ASTM B 280, DRAWN TEMPER HARD COPPER TUBE. B. PROVIDE ASBESTOS FREE SMOKE AND FIRE TIGHT SEALS FOR ANY OPENING THROUGH FIRE RATED WALLS, FLOORS, CHASES OR CEILINGS USED AS PASSAGE FOR MECHANICAL COMPONENTS SUCH AS PIPING, CONDUIT OR DUCTWORK. 1.6 CAULKING AND SEALANT C. THE DRAIN PAN SHALL BE SLOPED IN BOTH DIRECTIONS AND SHALL BE FULLY DRAINABLE. THE COILS SHALL MOUNT ABOVE THE DRAIN PAN AND NOT IN THE PAN. THE PAN SHALL HAVE A 3/4 INCH CONNECTION AND AN AUXILIARY CONNECTION, BOTH OF WHICH SHALL BE TIED TOGETHER FOR DRAINAGE. THE UNIT SHALL BE FURNISHED WITH A CONDENSATE OVERFLOW SWITCH, INSTALLED IN THE DRAIN PAN, TO SHUT DOWN THE UNIT TO PREVENT THE CONDENSATE DRAIN PAN FROM OVERFLOWING. E. WHEEL SHALL BE CENTRIFUGAL FORWARD CURVED TYPE, CONSTRUCTED OF GALVANIZED STEEL. WHEEL SHALL BE BALANCED IN ACCORDANCE WITH AMCA STANDARD 204-96. G. ALL COPPER-BRONZE AND COPPER-STEEL JOINTS MUST BE BRAZED ACCORDING TO AWS'S BRAZING HANDBOOK, CHAPTER "PIPE AND TUBE". USE AWS A5.8 CLASS BAG-5, CADMIUM-FREE SILVER ALLOY BRAZING FILLER METAL (SAFETY-SILV 45 WITH STAY-SILV WHITE BRAZING FLUX). C. CUT SLEEVES TO LENGTH FOR MOUNTING FLUSH WITH BOTH SURFACES, EXCEPT WHEN INSTALLED IN FLOORS OF MECHANICAL EQUIPMENT AREAS, OR OTHER WET AREAS, WHERE THE SLEEVES SHALL BE EXTENDED 2 INCHES ABOVE THE FINISHED FLOOR LEVEL. EXTEND CAST-IRON SLEEVE FITTINGS BELOW FLOOR SLAB AS REQUIRED TO SECURE CLAMPING RINGS. D. MOTORS SHALL COMPLY WITH IEEE 841 FOR SEVERE-DUTY MOTORS. B. THE UNIT CASING SHALL BE 18 GAUGE GALVANIZED STEEL WITH 1 INCH 1.5 LB DENSITY INSULATION. THE FAN ACCESS SHALL BE ON BOTH SIDES OF THE UNIT BY ACCESS PANELS. THE COIL ACCESS SHALL BE ON BOTH SIDES. C. ANYTIME THE PIPING MATERIAL CHANGES FROM A FERROUS TO A NONFERROUS MATERIAL, A DIELECTRIC CONNECTION MUST BE MADE, REGARDLESS OF SIZE. F. ALL COPPER JOINTS MUST BE BRAZED ACCORDING TO AWS'S BRAZING HANDBOOK, CHAPTER "PIPE AND TUBE". USE HARRIS STAY-SILV 15 (14.5 - 15.5% SILVER) BRAZING FILLER METAL AND COMPLY WITH ANSI/AWS A5.8 CLASS BCUP5. C. MOTORS SHALL COMPLY WITH ENERGY EFFICIENCY AS DEFINED IN NEMA MG 1 (PREMIUM EFFICIENCY) UNLESS OTHERWISE INDICATED. 2011 by Linfield, Hunter & Junius, Inc. A. METAL DUCTS SHALL BE CONSTRUCTED AND INSTALLED IN ACCORDANCE WITH THE LATEST EDITION OF THE SMACNA "HVAC DUCT CONSTRUCTION STANDARDS", UNLESS SPECIFICALLY INSTRUCTED OTHERWISE ON THE DRAWINGS. CONSTRUCT FROM STANDARD COMMERCIAL GRADE GALVANIZED STEEL. ALL NEW SUPPLY, RETURN, EXHAUST, AND OUTSIDE AIR DUCTWORK SHALL COMPLY WITH PRESSURE CLASS FOR 1" W.G. SEAL ALL TRANSVERSE AND LONGITUDINAL SEAMS. 3608 18th Street, Suite 200 Metairie, Louisiana 70002 DATE: 10/1/2014 E. CONTRACTOR SHALL INSTALL CONSTRUCTION FILTERS ON ALL AIR DISTRIBUTION EQUIPMENT SERVING NEW OR REMODELED AREAS TO ENSURE THAT COILS AND INTERNAL COMPONENTS ARE PROTECTED. BY COMPLETION OF THE PROJECT THE M.C. SHALL REPLACE CONSTRUCTION FILTERS WITH NEW FILTERS. M.C. SHALL PROVIDE TEMPORARY FABRIC FILTERS WRAPPED OVER ALL NEW AND EXISTING SUPPLY AIR GRILLES, CONNECTED TO THE DISTRIBUTION DUCTWORK IN ALL AREAS AFFECTED BY CONSTRUCTION. 2.6 AIR HANDLING UNITS APPROVED BY D. DURING REMOVAL OF ITEMS SO INDICATED, CAUTION SHALL BE USED TO PREVENT DAMAGE TO ANY EQUIPMENT HAVING SALVAGE VALUE. ALL REUSABLE SALVAGED MATERIAL SHALL REMAIN PROPERTY OF THE OWNER AND BE RETAINED FOR HIS INSPECTION. ONLY ITEMS INSPECTED AND REJECTED BY THE OWNER SHALL BE DISPOSED OF BY THE CONTRACTOR. ALL OTHER ITEMS SHALL BE TURNED OVER AND DEPOSITED AS DIRECTED BY THE OWNER. 2.1 DUCTWORK AND DUCT ACCESSORIES 2. CAPACITY AND TORQUE CHARACTERISTICS: SUFFICIENT TO START, ACCELERATE AND OPERATE CONNECTED LOADS AT DESIGNATED SPEEDS, AT INSTALLED ALTITUDE AND ENVIRONMENT, AND WITHOUT EXCEEDING NAMEPLATE RATINGS OR CONSIDERING SERVICE FACTOR. CHECKED BY C. MECHANICAL CONTRACTOR SHALL PAY FOR ALL PERMITS AS WELL AS LICENSE AND INSPECTION FEES REQUIRED FOR HIS WORK. C. THE CONDENSATE DRAIN SHALL HAVE 3/4" FLEXIBLE ELASTOMERIC INSULATION (INTERIOR AND EXTERIOR). SELF-SEALING FLEXIBLE ELASTOMERIC INSULATION WILL NOT BE ACCEPTED. PROJ. NO. 12-23 DATE 10/02/2014 SHEET NO. C. KEEP ONE SET OF PLANS AND SPECIFICATIONS IN GOOD CONDITION ON THE JOB AT ALL TIMES. OF SHEETS DRAWN BY B. IF THE MECHANICAL CONTRACTOR ELECTS TO USE EQUIPMENT OTHER THAN THE NAMED BASIS OF DESIGN, ANY ADDITIONAL COSTS ASSOCIATED WITH ELECTRICAL, GENERAL, AND MECHANICAL MODIFICATIONS REQUIRED SHALL BECOME HIS ULTIMATE RESPONSIBILITY. THIS MUST BE IDENTIFIED PRIOR TO THE BID SO THAT THERE WILL BE NO ADDITIONAL COSTS TO THE OWNER AFTER THE BID. PART 2 PRODUCTS 1. DUTY: CONTINUOUS DUTY AT AMBIENT TEMPERATURE OF 104 DEGREES F AND AT ALTITUDE OF 3300 FEET ABOVE SEA LEVEL. THIS SHEET A. PERTINENT FEDERAL, STATE AND LOCAL REGULATIONS AND REQUIREMENTS OF NATIONAL BOARD OF THE FIRE UNDERWRITERS AND NATIONAL ELECTRICAL CODE ARE HEREBY MADE PART OF THIS CONTRACT. REQUIREMENTS OF AUTHORITY HAVING LOCAL JURISDICTION SHALL SUPERSEDE ALL OTHER REQUIREMENTS. A. THE MECHANICAL CONTRACTOR SHALL GUARANTEE ALL EQUIPMENT, ACCESSORIES, WORKMANSHIP, AND MATERIAL FURNISHED BY HIM FOR A PERIOD OF ONE YEAR FROM FINAL ACCEPTANCE AGAINST ALL DEFECTS. PROFESSIONAL ENGINEERS, ARCHITECTS AND SURVEYORS TIME: 4:48 PM 1.1 GENERAL B. CHARACTERISTICS: B. REFRIGERANT SUCTION (AND HOT GAS) PIPING: 1" FLEXIBLE ELASTOMERIC INSULATION (INTERIOR AND EXTERIOR). SELF-SEALING FLEXIBLE ELASTOMERIC INSULATION WILL NOT BE ACCEPTED. LINFIELD, HUNTER & JUNIUS, INC. PART 1 GENERAL 1.9 GUARANTEE CITY OF KENNER - CONVERSION OF ANNE WASHINGTON COMMUNITY CENTER MECHANICAL SPECIFICATIONS 6. FIXTURES, EQUIPMENT, CONNECTIONS, AND PIPING SHALL BE FURNISHED AND INSTALLED TO MEET OR EXCEED STATE AND LOCAL CODES AND REQUIREMENTS. 7. 8. 9. 10. 11. 12. 13. 14. 15. FURNISH AND INSTALL WATER HAMMER ARRESTORS IN COLD WATER LINES AT CONNECTIONS TO FLUSH VALVES, QUICK CLOSING VALVES, AND AT ALL HOT AND COLD WATER CONNECTIONS TO FIXTURES. PLUMBING VENTS AND STACKS THROUGH ROOF SHALL BE INSTALLED A MINIMUM OF 10'-0" CLEAR OF A/C OUTSIDE AIR INTAKES, CLINICAL AIR COMPRESSOR INTAKES, OR WINDOWS IN STRUCTURE. PENETRATIONS THROUGH PARTITIONS AND FLOORS SHALL BE SLEEVED AND SEALED TO MAINTAIN INTEGRITY OF PARTITION AND FLOOR RATING. DRAWINGS ARE SCHEMATIC IN NATURE. CONTRACTOR IS RESPONSIBLE FOR COORDINATING EXACT ROUTING OF ALL SERVICES WITH EXISTING CONDITIONS AND WITH ALL OTHER TRADES. ORIENT FLUSH VALVE HANDLES ASSOCIATED WITH BARRIER-FREE WATER CLOSETS ON WIDE SIDE OF STALL TO COMPLY WITH ADA REQUIREMENTS. PROVIDE INSULATION KIT FOR SUPPLIES, DRAIN PIPING AND TRAP FOR ALL HANDICAP ACCESSIBLE LAVATORIES AND SINKS. INSULATION KIT SHALL BE EQUAL TO TRUEBRO MODEL 103 (WHITE). WHERE PROTECTIVE SKIRT UNDER FIXTURES IS PROVIDED, INSULATION OF PIPING IS NOT REQUIRED. CONTRACTOR SHALL COORDINATE WITH PHASING REQUIREMENTS PROVIDED BY ARCHITECT/OWNER. TEMPORARY SERVICES SHALL BE PROVIDED FOR ANY AREA SERVED BY ANOTHER AREA IF DEMOLITION OF EXISTING SERVICE IS NECESSARY. COORDINATE ALL PLUMBING WORK WITH PHASING PLAN AS REQUIRED TO COMPLETE COMPLETE WORK. EXISTING SERVICES INDICATED ON THESE DRAWINGS WERE DERIVED FROM EXISTING DRAWINGS AND LIMITED FIELD OBSERVATIONS. THESE DRAWINGS MAY NOT BE ALL INCLUSIVE OF SERVICES THAT EXIST IN THE PROJECT AREA. CONTRACTOR SHALL VERIFY SERVICES, LOCATIONS, TYPE, AND SIZE PRIOR TO ANY BIDDING, PRICING, OR CONSTRUCTION. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL WORK INVOLVING DEMOLITION TIE-INS AND ROUTING CONFLICTS WITH EXISTING CONDITIONS. ANY DEVIATIONS IMPACTING WORK SHOWN ON THESE DOCUMENTS SHALL BE REPORTED TO THE ARCHITECT FOR COORDINATION PRIOR TO CONSTRUCTION. PROVIDE ISOLATION BALL VALVES AT BRANCH LINES SERVING EACH ROOM WITH PLUMBING FIXTURES SUCH THAT EACH ROOM MAY BE INDIVIDUALLY ISOLATED. ACCESS SHALL BE PROVIDED. 16. 17. EXISTING TIE-IN POINTS ARE APPROXIMATE, FIELD VERIFY ACTUAL TIE-IN POINTS AND PROVIDE PIPING RUNS AS REQUIRED FOR TIE-INS, PRIOR TO BIDDING. 18. ALL SANITARY SEWER, STORM DRAIN, AND GREASE WASTE PIPING SHOWN SHALL BE RUN BELOW FLOOR, UNLESS NOTED OTHERWISE. 19. ALL CW, HW, HWR, NATURAL GAS, FIRE PROTECTION, AND VENT PIPING SHOWN SHALL BE RUN ABOVE CEILING, UNLESS NOTED OTHERWISE. 20. PROVIDE ALL PLUMBING FIXTURES AND EQUIPMENT WITH ACCESSIBLE STOPS. 21. UNLESS OTHERWISE NOTED, ALL DRAINS SHALL BE INSTALLED AT THE LOW POINT OF ROOFS, AREAWAYS, FLOOR, ETC. 22. ALL CLEANOUTS SHALL BE THE FULL SIZE OF THE PIPE FOR PIPE SIZES 6 IN AND SMALLER, AND SHALL BE 6 IN FOR PIPE SIZES LARGER THAN 6 IN. 23. PROVIDE SHUTOFF VALVES IN ALL DOMESTIC WATER PIPING SYSTEM BRANCHES IN WHICH BRANCH PIPING SERVES TWO OR MORE FIXTURES. NOTES ARE GENERAL IN NATURE, NOT ALL NOTES ARE NECESSARILY USED IN THIS PROJECT. PIPE AND FITTING SCHEDULE TYPE WASTE AND VENT ICE MAKER AP ACCESS PANEL INV INVERT AV ACID VENT IW INDIRECT WASTE AW ACID WASTE JS JANITORS SINK BEH BEHIND KS KITCHEN SINK BFP BACKFLOW PREVENTER KW KILOWATT BMS BUILDING MANAGEMENT SYSTEM LxWxH LENGTH x WIDTH x HEIGHT BOP BOTTOM OF PIPE LAV LAVATORY BT BATHTUB LBS POUNDS BTUH BRITISH THERMAL UNITS PER HOUR LDR LEADER CL CENTERLINE LWT LEAVING WATER TEMPERATURE CLG CEILING MB MOP BASIN SANITARY SEWER ABOVE CM COFFEE MAKER MBH 1000 BRITISH THERMAL UNITS PER HOUR SANITARY SEWER BELOW CO CLEANOUT MECH. MECHANICAL CODP CLEAN OUT DECK PLATE MGCV MASTER GAS CONTROL VALVE CONT. CONTINUATION MH MANHOLE COTG CLEAN OUT TO GRADE MICV METER INLET CONTROL VALVE COWP CLEAN OUT WALL PLATE MOCV COYB CLEANOUT IN YARD BOX CP EXISTING PIPING TO BE REMOVED NEW PIPING DOMESTIC COLD WATER PIPING EXISTING EQUIPMENT TO BE DEMOLISHED DOMESTIC HOT WATER PIPING DOMESTIC HOT WATER PIPING AT INDICATED SERVICE TEMPERATURE XX 1 DOMESTIC HOT WATER RECIRCULATION CD NEW EQUIPMENT WITH IDENTIFICATION CONDENSATE DRAIN PIPING PUMP BACKFLOW PREVENTER GW GREASE WASTE ELBOW UP AW ACID WASTE ABOVE ELBOW DOWN METER OUTLET CONTROL VALVE AW ACID WASTE BELOW BRANCH PIPE CONNECTION MS MOP SINK AV ACID VENT TEE-OUTLET DOWN CONTROL PANEL NIC NOT IN CONTRACT G NATURAL GAS PIPING TEE-OUTLET UP CWTP TRAP PRIMER COLD WATER LINE NFGH NON FREEZE GROUND HYDRANT DOUBLE CHECK DETECTOR ASSEMBLY NFWH NON FREEZE WALL HYDRANT TEMPERED WATER PIPE REDUCER DCDA DCV DOUBLE CHECK VALVE NO NUMBER FLOOR CLEANOUT GATE VALVE DCW DOMESTIC COLD WATER NTS NOT TO SCALE GLOBE VALVE DF DRINKING FOUNTAIN OD OVERFLOW DRAIN EXTERIOR CLEANOUT (SEE SCHEDULE SPECIFICATIONS) DFU DRAINAGE FIXTURE UNIT(S) OFCI OWNER FURNISHED CONTRACTOR INSTALLED DHW DOMESTIC HOT WATER OS&Y OUTSIDE SCREW & YOKE DHWR DOMESTIC HOT WATER RETURN OSD OPEN SITE DRAIN DN DOWN PD PRESSURE DROP DR DRAIN PG PRESSURE GAUGE DW DISHWASHER PLMB PLUMBING DWG DRAWING PO PLUGGED OUTLET ECO EXTERIOR CLEANOUT POE POINT OF ENTRY EL ELEVATION PRV PRESSURE REDUCING VALVE ES/EW EMERGENCY SHOWER/EYEWASH PS PANTRY SINK EWC ELECTRIC WATER COOLER PSIG POUNDS PER SQUARE INCH GAGE EWH ELECTRIC WATER HEATER RD ROOF DRAIN EWT ENTERING WATER TEMPERATURE REF REFRIGERATOR EX EXISTING RPM REVOLUTIONS PER MINUTE F FAHRENHEIT RPZ REDUCED PRESSURE ZONE BFP ASSEMBLY FAI FRESH AIR INLET SA SHOCK ABSORBER FCO FLOOR CLEANOUT SE SEWAGE EJECTOR FD FLOOR DRAIN SH SHOWER FFD FUNNEL FLOOR DRAIN SK SINK FFE FINISHED FLOOR ELEVATION SS SANITARY SEWER FMS FACILITY MANAGEMENT SYSTEM SD STORM DRAIN FPWH FREEZE PROOF WALL HYDRANT SP SUMP PUMP FS FLOOR SINK TD TERRACE/TRENCH DRAIN FSP FIRE STAND PIPE TP TRAP PRIMER FT FOOT, FEET TW TEMPERED WATER FU FIXTURE UNIT(S) TYP TYPICAL G GAS UON UNLESS OTHERWISE NOTED GT GREASE TRAP UR URINAL GPH GALLONS PER HOUR V VENT GPM GALLONS PER MINUTE VB VACUUM BREAKER GPR GAS PRESSURE REGULATOR V/Ph/Hz VOLTS/PHASE/HERTZ GT GREASE TRAP VFD VARIABLE FREQUENCY DRIVE GW GREASY WASTE VO VALVED OUTLET GWH GAS WATER HEATER VTR VENT TO ROOF HB HOSE BIB WB WET BULB HC HANDICAPPED WC WATER CLOSET HLAV HANDICAPPED LAVATORY WCO WALL CLEANOUT HP HORSEPOWER W/D CLOTHES WASHER/DRYER HPG HIGH PRESSURE GAS WG WATER GAGE FITTINGS LOCATION 15" AND SMALLER STD. WT. C.I. HUBLESS STD. NO-HUB COUPLINGS ABOVE GRADE AND BELOW GRADE HR HOUR WH WALL HYDRANT 15" AND SMALLER STD. WT. C.I. HUB AND SPIGOT HT HOUSE TRAP WHA WATER HAMMER ARRESTOR STD. WT. C.I. HUB AND SPIGOT BELOW GRADE (16 MIL WRAPPED) HTR HEATER WM WATER METER ALL SIZES SCHEDULE 40 PVC SCHEDULE 80 PVC ABOVE GRADE AND BELOW GRADE HUR HANDICAPPED URINAL WPD WATER PRESSURE DROP TYPE "L" HARD COPPER HVAC HEATING, VENTILATION & AIR CONDITIONING WSFU WATER SUPPLY FIXTURE UNIT ALL SIZES WROUGHT COPPER ABOVE GRADE HWC HANDICAPPED WATER CLOSET ALL SIZES TYPE "K" HARD COPPER WROUGHT COPPER, SILVER BRAZED BELOW GRADE (16 MIL WRAPPED) HWH HOT WATER HEATER HWT HOT WATER STORAGE TANK ALL SIZES TYPE "M" HARD COPPER ABOVE GRADE EXISTING EQUIPMENT TO REMAIN VENT PIPING MATERIAL WROUGHT COPPER EXISTING PIPING TO REMAIN ABBREVIATION LIST IS GENERAL IN NATURE, NOT ALL ABBREVIATIONS ARE NECESSARILY USED IN THIS PROJECT. TW BUTTERFLY VALVE WALL CLEANOUT 2011 by Linfield, Hunter & Junius, Inc. IM SIZE DOMESTIC WATER CONDENSATE DRAIN ABOVE FINISHED FLOOR 3608 18th Street, Suite 200 Metairie, Louisiana 70002 COORDINATE WATER, WASTE, VENT, AND STORM WATER PIPING WITH OTHER TRADES TO AVOID SPACING OR ROUTING PROBLEMS. AFF BALL VALVE CONTROL VALVE, 2 WAY CONTROL VALVE, 3 WAY DETAIL NO. CHECK VALVE STRAINER SHEET ON WHICH DETAIL IS LOCATED STRAINER AND BLOWDOWN VALVE PLUG COCK/ BALANCING VALVE/ GAS COCK SPECIFIC NOTE DESIGNATION CIRCUIT SETTER PRESSURE REDUCING VALVE POINT OF DISCONNECT GAS PRESSURE REGULATOR UNION KENT A. POYSER REG. No. 37788 FLEXIBLE CONNECTOR POINT OF CONNECTION, NEW TO EXISTING REGISTERED PIPE CAP IN GAUGE AND GAUGE COCK THERMOMETER VALVE WITH BLIND FLANGE VACUUM INLET T NATURAL GAS OUTLET STEAM TRAP THERMOSTATIC EXPANSION VALVE FLOOR OR AREA DRAIN CLEAN OUT IN YARD BOX FLOOR SINK TRAP PRIMER ROOF DRAIN WATER HAMMER ARRESTOR OVERFLOW ROOF DRAIN ES/EW EMERGENCY SHOWER / EYEWASH INDIRECT WASTE RECEPTOR EEW EMERGENCY EYEWASH FLOOR CLEAN OUT SYMBOL LIST IS GENERAL IN NATURE, NOT ALL SYMBOLS ARE NECESSARILY USED IN THIS PROJECT. APPROVED BY 5. INVERT ELEVATION CHECKED BY CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING MOUNTING OF ALL PLUMBING FIXTURES. THIS WORK SHALL INCLUDE BUT NOT BE LIMITED TO PROVIDING WALL CARRIERS AND COORDINATING FIXTURES WITH CASEWORK. IE PROJ. NO. 12-23 DATE 10/02/2014 SHEET NO. OF SHEETS DRAWN BY CONTRACTOR SHALL COORDINATE EQUIPMENT CONNECTIONS WITH EQUIPMENT DRAWINGS AND SUPPLIER. INSTALL EQUIPMENT AND MAKE FINAL CONNECTIONS, FURNISHING CUTOFF VALVES, P-TRAPS, P.R.V'S, BACKFLOW PREVENTERS, AND PIPING AS REQUIRED. CONTRACTOR SHALL BE RESPONSIBLE FOR IDENTIFYING ANY CONFLICTS BETWEEN THESE DOCUMENTS AND EQUIPMENT CUT SHEETS PRIOR TO CLOSING IN WALLS AND CEILINGS. AREA DRAIN THIS SHEET PROVIDE ALL MATERIAL AND EQUIPMENT AND PERFORM ALL LABOR REQUIRED TO INSTALL COMPLETE AND OPERABLE MECHANICAL SYSTEMS AS INDICTED ON THE DRAWINGS, AS SPECIFIED AND AS REQUIRED BY CODE. AD PROFESSIONAL ENGINEERS, ARCHITECTS AND SURVEYORS 4. LOUISIANA PLUMBING CODE - 2013 INTERNATIONAL BUILDING CODE - 2012 NATIONAL ELECTRICAL CODE - 2008 NFPA 70 - 2014 NFPA 72 - 2013 THE CONTRACT DOCUMENTS ALL REQUIREMENTS OF THE STATE FIRE MARSHAL INSURING AGENCY ALL REQUIREMENTS OF THE AUTHORITIES HAVING JURISDICTION. PLUMBING LEGEND LINFIELD, HUNTER & JUNIUS, INC. DATE: 10/1/2014 3. FILE: P:\LinfieldHunter&Junius\14-098_CommunityResourceCenter\Design Documents\Drawings\Plumbing\P-000 PLUMBING LEGEND.dwg ALL WORK SHALL COMPLY WITH THE LATEST STATE AND CITY CODES INCLUDING BUT NOT LIMITED TO THE FOLLOWING: A. B. C. D. E. F. G. H. I. 2. PLUMBING ABBREVIATIONS CITY OF KENNER - CONVERSION OF ANNE WASHINGTON COMMUNITY CENTER 1. TIME: 9:48 PM PLUMBING GENERAL NOTES FIBERGLASS BATHTUB 4-PIECE TUB/SHOWER ENCLOSURE WITH GRAB BARS, FOLDING SEAT, PRESSURE BALANCED MIXING VALVE PRE-PIPED TO SUPPLY ELBOW, CHROME PLATED SHOWER HEAD, CHROME PLATED DRAIN. BT-2 BATH TUB ACRYLIC HANDICAP BATHTUB WITH HANDICAP SEAT WITH STAINLESS STEEL GRAB BARS, SINGLE HAND PRESSURE BALANCING MIXING SHOWER UNIT, HAND SHOWER HEAD, 60" FLEXIBLE METAL HOSE, MOUNTING WALL BRACKET, TUB SPOUT AND CHROME FINISHED DRAIN. SH-1 SHOWER S-1 SINK DOUBLE BOWL 25" X 22" X 10" DEEP L-1 LAVATORY SELF-RIMMING VITREOUS CHINA, ROUND BOWL, SELF-RIMMING WITH OVERFLOW, DOME LEVER FAUCET WITH 4" CENTERS, POP-UP DRAIN, WHITE FINISH. WC-1 WATER CLOSET FLOOR MOUNT TANK TYPE VITREOUS CHINA, TANK TYPE, TWO-PIECE, FLOOR MOUNT, ELONGATED BOWL, FULLY GLAZED 2" TRAP-WAY, 1.6 GAL PER FLUSH, WHITE FINISH. TOTO CST716 CARUSOE CLOSE COUPLED TOILET McGUIRE LFBV2166CC WC-2 WATER CLOSET FLOOR MOUNT TANK TYPE - ADA VITREOUS CHINA, TANK TYPE, TWO-PIECE, ADA HEIGHT, FLOOR MOUNT, ELONGATED BOWL, FULLY GLAZED 2" TRAP-WAY, 1.6 GAL PER FLUSH, WHITE FINISH. TOTO CST716 CARUSOE CLOSE COUPLED TOILET McGUIRE LFBV2166CC FLOOR DRAIN FCO FLOOR CLEANOUT IMB-1 ICE MAKER BOX MB-1 MOP BASIN 24x24 ACCEPTABLE EQUALS ACCESSORIES ZURN Z7000-S8 BARRIER FREE 4ETSF6030A165 DCW DHW VENT SAN. 1/2" 1/2" 2" 3" 1/2" 1/2" 2" 3" 1/2" 1/2" 2" 2" STERLING ACCORD 71140115 ZURN Z7120-SS-LH-HW Z700-T4 32"x32" 2-PIECE FIBERGLASS SHOWER WITH CHROME FINISHED CENTER DRAIN DRAIN, AND PRESSURE BALANCE SHOWER VALVE WITH STANDARD SHOWER HEAD. MAAX GALLERY SERIES 6714556 ZURN Z7121-SS-LH 18 GAUGE STAINLESS STEEL DOUBLE COMPARTMENT SELF-RIMMING SINK, BRUSHED FINISH, 3-1/2" DRAIN OPENING, THREE HOLE PUNCH, HEAVY DUTY SOUND COATED UNDERSIDE. ELKAY SLPF2522104 ELKAY LK2477CR McGUIRE LFBV2165CC AMERICAN STANDARD & JUST 1/2" 1/2" 2" 2" ZURN Z5120 ZURN Z81103-XL-P McGUIRE LFBV2165CC AMERICAN STANDARD & ELJER 1/2" 1/2" 2" 2" TOTA SS114 SOFTCLOSE SEAT AMERICAN STANDARD, ELJER, & KOHLER 1" --- 3" 4" TOTA SS114 SOFTCLOSE SEAT AMERICAN STANDARD, ELJER, & KOHLER 1" --- 3" 4" ZURN Z415B JR SMITH, WADE, & WATTS 1/2" --- 3" 3" ZURN Z1400-VP JR SMITH & WATTS 1/2" --- 3" 3" OATEY 38608 SIOUX CHIEF & IPS 1/2" --- JR SMITH, WADE, & WATTS 1/2" 1/2" ROUND FLOOR DRAIN WITH DURA-COATED CAST IRON BODY AND 3" BOTTOM OUTLET,COMBINATION INVERTIBLE MEMBRANE CLAMP AND ADJUSTABLE COLLAR WITH SEEPAGE SLOTS AND "TYPE B" POLISHED NICKEL BRONZE, LIGHT-DUTY STRAINER FD-1 TRIM ADJUSTABLE POLISHED BRONZE FLOOR CLEANOUT, DURA-COATED CAST IRON BODY WITH GAS AND WATER TIGHT ADS TAPERED THREAD PLUG, ROUND SECURED TOP, VANDAL PROOF SCREWS, NO HUB CONNECTION 1 4 TURN BRASS HAMMER BALL VALVE, COPPER SWEAT, STANDARD PACK 24x24 HIGH-DENSITY COMPOSITE, MOLDED MOP BASIN, 10" DEEP, INTEGRAL STAINLESS STEEL DRAIN ASSEMBLY AND STRAINER, WALL MOUNTED FAUCET WITH PAIL HOOK. ZURN Z1996-24 AMERICAN STANDARD & ELJER ZURN Z843M2 ZURN Z8800LR-PC --- 2011 by Linfield, Hunter & Junius, Inc. BATH TUB REFERENCE PRODUCT 3608 18th Street, Suite 200 Metairie, Louisiana 70002 BT-1 DESCRIPTION PROFESSIONAL ENGINEERS, ARCHITECTS AND SURVEYORS FIXTURE LINFIELD, HUNTER & JUNIUS, INC. FAUCETS / FITTINGS MARK --- 2" 2" ELECTRIC WATER HEATER SCHEDULE MARK CHECK VALVE (TYP.) EWH-1 STORAGE CAPACITY SYSTEM AND/OR SERVICE TYPE DOMESTIC HOT WATER TANK RELIEF VALVE SETTING GAL GAL/HR PSIG 120 91 150 ELECTIRCAL INPUT NO OF ELEMENTS 1 REFERENCE MODEL TOTAL kW kW PER ELEMENT VOLT PHASE FLA 24 24 240 1 - KENT A. POYSER REG. No. 37788 STATE CSB-120-24-SFE REGISTERED 112 IN THERMOSTATIC MIXING VALVE 3" COLD WATER SUPPLY MODEL LOCATION TMV-1 POWERS LF4M432 - INLET 3 4" OUTLET 1" CAPACITY MIN MAX 4 GPM 21 GPM PRESSURE DROP NOTES 5 PSI ROUGH BRONZE FINISH, EXPOSED MOUNTING FPWH @ 24" ABOVE FINISHED GRADE BUILDING EXTERIOR WALL CITY OF KENNER - CONVERSION OF ANNE WASHINGTON COMMUNITY CENTER UNION (TYP.) A.S.M.E. APPROVED TEMPERATURE AND PRESSURE RELIEF VALVE SLEEVE AND SEAL WATER-TIGHT GRADE DOMESTIC COLD WATER LINE TO BUILDING D DOMESTIC WATER LINE TO SITE POTABLE WATER MAIN FINISHED FLOOR RELIEF PIPE - ROUTE FULL SIZE TO NEAREST FLOOR SINK OR DRAIN DRAIN VALVE DCW OVERFLOW PAN UNDERGROUND VALVE WITH CAST IRON VALVE BOX 2 DOMESTIC WATER SERVICE ENTRY DETAIL SCALE: NTS 1 TANK TYPE WATER HEATER DETAIL SCALE: NTS CHECKED BY MANUFACTURER PROJ. NO. 12-23 DATE 10/02/2014 SHEET NO. OF SHEETS DRAWN BY MARK THIS SHEET SHUTOFF VALVE (TYP.) APPROVED BY THERMOSTATIC MIXING VALVE SCHEDULE DCW FILE: P:\LinfieldHunter&Junius\14-098_CommunityResourceCenter\Design Documents\Drawings\Plumbing\P-001 PLUMBING SCHEDULES.dwg DATE: 10/1/2014 TIME: 9:47 PM PLUMBING FIXTURE SCHEDULE IF THE PLUMBING CONTRACTOR DOES NOT CLEARLY UNDERSTAND THESE PLANS, OR IS NOT SURE OF THEIR MEANING, HE SHOULD OBTAIN THE ENGINEER'S WRITTEN EXPLANATION AND INTERPRETATION, PRIOR TO SUBMITTING HIS BID, SINCE THE PLUMBING CONTRACTOR WILL BE HELD RIGIDLY TO THE INTERPRETATION OF THE ENGINEER. 3. ALL EXISTING PLUMBING ITEMS SHALL BE REMOVED, INCLUDING EXISTING PLUMBING FIXTURES, WATER HEATER, WASTE PIPING, VENT PIPING, AND DOMESTIC WATER PIPING. 4. THE OWNER SHALL MAINTAIN ALL SALVAGE RIGHTS OF EQUIPMENT AND MATERIALS REMOVED. ALL EQUIPMENT AND MATERIALS NOT CLAIMED BY THE OWNER SHALL BE REMOVED FROM THE PREMISES BY THE CONTRACTOR. 5. THE PLUMBING CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CUTTING AND PATCHING OF CONCRETE SLAB FOR PIPING REMOVAL AND CAPPING AT ACTIVE MAINS. 6. THE PLUMBING CONTRACTOR SHALL BE RESPONSIBLE FOR ALL ROOF PATCHING WHEN REMOVING EXISTING PLUMBING VENTS. CONTRACTOR SHALL PATCH ROOF TO MATCH EXISTING. 7. CONTRACTOR TO COORDINATE ALL DEMOLITION & NEW CONSTRUCTION WITH THE PROJECT CONSTRUCTION MANAGER AND ALL OTHER TRADES PER PROJECT AREA PHASING. PLAN NOTES: 2011 by Linfield, Hunter & Junius, Inc. 2. 3608 18th Street, Suite 200 Metairie, Louisiana 70002 THESE PLANS ARE DIAGRAMMATIC IN NATURE SINCE THEY REFLECT ONLY THE AVAILABLE INFORMATION OBTAINED FROM EXISTING PLANS, SPECIFICATIONS, AND FIELD SURVEYS. THE EXACT LOCATION OF EXISTING DUCTWORK, PIPING, AND EQUIPMENT MAY DEVIATE FROM THE LOCATION INDICATED ON THESE DRAWINGS. THE CONTRACTOR SHALL BE PREPARED TO MAKE SOME ALTERATIONS TO NEW AND/OR EXISTING SERVICES TO FIT ACTUAL JOB CONDITIONS. PROFESSIONAL ENGINEERS, ARCHITECTS AND SURVEYORS 1. LINFIELD, HUNTER & JUNIUS, INC. DATE: 10/1/2014 TIME: 9:47 PM GENERAL DEMOLITION NOTES: REMOVE EXISTING DRINKING FOUNTAIN AND CAP DOMESTIC WATER, WASTE, AND VENT PIPING AT ACTIVE MAINS. REMOVE EXISTING LAVATORY AND CAP DOMESTIC WATER, WASTE, AND VENT PIPING AT ACTIVE MAINS. REMOVE EXISTING SINK AND CAP DOMESTIC WATER, WASTE, AND VENT PIPING AT ACTIVE MAINS. REMOVE EXISTING WATER HEATER AND ASSOCIATED DOMESTIC WATER PIPING. REMOVE EXISTING WATER CLOSET AND ASSOCIATED WASTE PIPING AND RISER, VENT PIPING AND RISER, AND DOMESTIC WATER. REMOVE EXISTING LAVATORY AND ASSOCIATED WASTE PIPING AND RISER, VENT PIPING AND RISER, AND DOMESTIC WATER. KENT A. POYSER REG. No. 37788 REMOVE EXISTING SINK AND ASSOCIATED WASTE PIPING AND RISER, VENT PIPING AND RISER, AND DOMESTIC WATER. REGISTERED PROJ. NO. 12-23 DATE 10/02/2014 SHEET NO. OF SHEETS DRAWN BY THIS SHEET CHECKED BY APPROVED BY IN REMOVE EXISTING BATHTUB AND ASSOCIATED WASTE PIPING AND RISER, VENT PIPING AND RISER, AND DOMESTIC WATER. CITY OF KENNER - CONVERSION OF ANNE WASHINGTON COMMUNITY CENTER FILE: P:\LinfieldHunter&Junius\14-098_CommunityResourceCenter\Design Documents\Drawings\Plumbing\P-101 PLUMBING DEMOLITION.dwg REMOVE EXISTING WATER CLOSET AND CAP DOMESTIC WATER, WASTE, AND VENT PIPING AT ACTIVE MAINS. LIVING ROOM / DINING 102 2" SS 3" V FD-1 STAIRWELL 219 LAV-1 ALL FINAL CONNECTION SIZES TO EQUIPMENT SHALL BE CONFIRMED PRIOR TO FABRICATION. WC-1 SH-1 3" VTR 4" SS DN KITCHEN 119 BATHROOM 106 S-1 4" SS 2" V 4" SS UP LAV-1 WC-1 2011 by Linfield, Hunter & Junius, Inc. BEDROOM 205 SH-1 BATHROOM 218 2" SS 3608 18th Street, Suite 200 Metairie, Louisiana 70002 2" V 3" SS 3" SS 4" SS LIVING ROOM 201 BATHROOM 202 2" V 3" VTR CORRIDOR 200 BEDROOM #4 (ADA) 118 BEDROOM #1 107 4" SS DN 3" V 4" SS WC-1 2" SS LAV-1 WMB-1 2" V BEDROOM #2 110 KENT A. POYSER REG. No. 37788 REGISTERED IN LIVING ROOM/ BEDROOM 211 BEDROOM #3 115 3" SS 3" SS 2" V 2" V 4" SS DN 3" V DN 3" V UP 4" SS UP 3" V UP APPROVED BY FD-1 WMB-1 2" V 3" V DN 3" SS CHECKED BY FD-1 4" SS UP LAV-1 LAUNDRY ROOM 113 PROJ. NO. 12-23 DATE 10/02/2014 SHEET NO. OF SHEETS DRAWN BY FD-1 S-1 BT-2 THIS SHEET 3" VTR 4" SS DN BATHROOM (ADA) 111 MB-1 4" SS 2" V 2" V WMB-1 4" SS 2" SS 3" SS 2" SS 2" V 2" V CORRIDOR 112 WC-2 3" V S-1 4" SS KITCHEN/ DINING 212 CITY OF KENNER - CONVERSION OF ANNE WASHINGTON COMMUNITY CENTER KITCHEN/ DINING 216 4" SS 2" SS 4" SS 4" SS UP 3" V BT-1 BATHROOM 209 3" V UP 2" SS 2" SS LIVING ROOM/ BEDROOM 217 2" V FILE: P:\LinfieldHunter&Junius\14-098_CommunityResourceCenter\Design Documents\Drawings\Plumbing\P-201 PLUMBING WASTE & VENT.dwg 3" V UP 4" SS 6. 3" SS UP 4" SS PROFESSIONAL ENGINEERS, ARCHITECTS AND SURVEYORS SH-1 ALL SANITARY SEWER LINES SHOWN SHALL BE RUN AT FLOOR BELOW. 3" SS DN LAV-1 WC-1 4. IF THE PLUMBING CONTRACTOR DOES NOT CLEARLY UNDERSTAND THESE PLANS, OR IS NOT SURE OF THEIR MEANING, HE SHOULD OBTAIN THE ENGINEER'S WRITTEN EXPLANATION AND INTERPRETATION, PRIOR TO SUBMITTING HIS BID, SINCE THE PLUMBING CONTRACTOR WILL BE HELD RIGIDLY TO THE INTERPRETATION OF THE ENGINEER. 5. S-1 EXISTING 4" SS 2" V 4" SS 3" SS KITCHEN/ DINING 203 4" SS BECAUSE OF THE LIMITED SPACE AVAILABLE TO INSTALL ALL OF THE MECHANICAL WORK, COORDINATION BETWEEN THE VARIOUS TRADES IS OF THE UTMOST IMPORTANCE. 4" SS DN 4" SS 3. 4" SS UP 3" VTR 3" V ALL ELBOWS, FITTINGS, ETC. IN PIPING ARE NOT NECESSARILY INDICATED TO CLEAR ALL EXISTING AND NEW JOB OBSTRUCTIONS. 3" VTR 3" V THESE PLANS ARE DIAGRAMMATIC IN NATURE SINCE THEY REFLECT ONLY THE AVAILABLE INFORMATION OBTAINED FROM EXISTING PLANS, SPECIFICATIONS, AND FIELD SURVEYS. THE EXACT LOCATION OF EXISTING DUCTWORK, PIPING, AND EQUIPMENT MAY DEVIATE FROM THE LOCATION INDICATED ON THESE DRAWINGS. THE CONTRACTOR SHALL BE PREPARED TO MAKE SOME ALTERATIONS TO NEW AND/OR EXISTING SERVICES TO FIT ACTUAL JOB CONDITIONS. 2. 3" SS GENERAL PLUMBING NOTES: 1. DATE: 10/1/2014 ENTRANCE CORRIDOR (BELOW) ENTRANCE CORRIDOR 100 LINFIELD, HUNTER & JUNIUS, INC. 9:46 PM TIME: FD-1 DCW DN DHW DN 112" DHW SH-1 1 " 2 4" 4" 1 " 2 DCW DCW 4" 3 DHW DCW UP DHW UP DHW BEDROOM #1 107 CORRIDOR 200 LIVING ROOM/ BEDROOM 217 3 4" DCW DN 3 " DHW DN 4 1 " 2 DCW DN 1 " 2 1 " 2 BT-1 BATHROOM 209 1 " 2 1 " 2 3 4" 3 4" 3 LAV-1 4" DCW 2011 by Linfield, Hunter & Junius, Inc. DCW DN BEDROOM #4 (ADA) 118 DCW UP DHW UP DCW DN DHW DN WC-1 1 " 2 DCW DN DHW DN 1 " 2 DCW 3 DCW UP 1 " 2 1 " 2 DCW UP DHW UP 4" 3 3 DCW UP DHW UP IMB-1 DHW 1 " 2 1 " 2 S-1 4" BATHROOM 218 BEDROOM 205 DCW 112" DCW 3 WC-1 DHW 114" DHW PROVIDE NEW INCOMING DOMESTIC WATER SERVICE. COORDINATE NEW WATER SERVICE AND METER WITH UTILITY COMPANY. 1 " 2 114" DCW DCW DN 3 " DHW DN 4 LAV-1 112" 112" DCW 4" DCW DCW DN 3 PLAN NOTES: KITCHEN 119 1 " 2 4" 1 " 2 1 " 2 SH-1 EWH-1 WC-1 LAV-1 3 ALL FINAL CONNECTION SIZES TO EQUIPMENT SHALL BE CONFIRMED PRIOR TO FABRICATION. DCW UP 3608 18th Street, Suite 200 Metairie, Louisiana 70002 TMV-1 DCW DN 4" DCW DN 3 " DHW DN 4 DCW 1 " 2 4" 1 " 2 DCW 1 " 2 DCW DN 3 " DHW DN 4 3 4" DHW 4" 3 DCW DN LIVING ROOM / DINING 102 DHW 1 " 2 3 4" 3 BATHROOM 202 3 DCW LIVING ROOM 201 WC-1 SH-1 1 " 2 DCW UP " 4 DHW UP 4" LAV-1 4" DHW BECAUSE OF THE LIMITED SPACE AVAILABLE TO INSTALL ALL OF THE MECHANICAL WORK, COORDINATION BETWEEN THE VARIOUS TRADES IS OF THE UTMOST IMPORTANCE. 3 3 3 IMB-1 STAIRWELL 219 DCW UP DCW DN 1 " 2 WMB-1 3 4" 3 DHW 4" DHW KENT A. POYSER REG. No. 37788 REGISTERED DCW DN DHW DN 1 " 2 1 " 2 DCW DN 1 " 2 S-1 1 " 2 1 " 2 3 DCW UP DHW UP 4" 4" DHW DCW DCW UP LAV-1 IMB-1 3 IMB-1 1 " 2 DCW DN 3 1 " 2 1 " 2 DCW DN DHW DN 4" DCW DN " 4 DHW DN LAUNDRY ROOM 113 DCW DN DHW DN WMB-1 1 " 2 1 " 2 DCW DN DHW DN 1 " 2 DCW UP 1 " 2 1 " 2 DCW DN DHW DN 1 " 2 1 " 2 DCW UP DHW UP APPROVED BY 1 " 2 BT-2 BATHROOM (ADA) 111 DHW 4" CHECKED BY KITCHEN/ DINING 212 WMB-1 DCW UP DHW UP 3 4" 4" PROJ. NO. 12-23 DATE 10/02/2014 SHEET NO. OF SHEETS DRAWN BY 3 1 " 2 1 " 2 3 THIS SHEET DCW DN DHW DN 3 DHW 1 " 2 1 " 2 MB-1 1 " 2 S-1 DCW DCW DCW DN DHW DN 4" 1 " 2 1 " 2 1 " 2 DCW DN 1 " 2 3 1 " 2 CORRIDOR 112 DHW WC-2 BEDROOM #3 115 1 " 2 KITCHEN/ DINING 216 IN CITY OF KENNER - CONVERSION OF ANNE WASHINGTON COMMUNITY CENTER BEDROOM #2 110 DCW LIVING ROOM/ BEDROOM 211 DCW UP DHW UP 1" DHW 1 " 2 1 " 2 1" DCW FILE: P:\LinfieldHunter&Junius\14-098_CommunityResourceCenter\Design Documents\Drawings\Plumbing\P-301 PLUMBING DOMESTIC WATER.dwg 1 " 2 ALL ELBOWS, FITTINGS, ETC. IN PIPING ARE NOT NECESSARILY INDICATED TO CLEAR ALL EXISTING AND NEW JOB OBSTRUCTIONS. 4. IF THE PLUMBING CONTRACTOR DOES NOT CLEARLY UNDERSTAND THESE PLANS, OR IS NOT SURE OF THEIR MEANING, HE SHOULD OBTAIN THE ENGINEER'S WRITTEN EXPLANATION AND INTERPRETATION, PRIOR TO SUBMITTING HIS BID, SINCE THE PLUMBING CONTRACTOR WILL BE HELD RIGIDLY TO THE INTERPRETATION OF THE ENGINEER. 5. S-1 4" 1 " 2 DCW DN DHW DN DCW UP DHW UP PROFESSIONAL ENGINEERS, ARCHITECTS AND SURVEYORS LINFIELD, HUNTER & JUNIUS, INC. 1 " 2 1 " 2 1 " 2 1 " 2 KITCHEN/ DINING 203 3 THESE PLANS ARE DIAGRAMMATIC IN NATURE SINCE THEY REFLECT ONLY THE AVAILABLE INFORMATION OBTAINED FROM EXISTING PLANS, SPECIFICATIONS, AND FIELD SURVEYS. THE EXACT LOCATION OF EXISTING DUCTWORK, PIPING, AND EQUIPMENT MAY DEVIATE FROM THE LOCATION INDICATED ON THESE DRAWINGS. THE CONTRACTOR SHALL BE PREPARED TO MAKE SOME ALTERATIONS TO NEW AND/OR EXISTING SERVICES TO FIT ACTUAL JOB CONDITIONS. DCW 3. ENTRANCE CORRIDOR 100 1 " 2 2. 112" DCW 9:45 PM TIME: GENERAL PLUMBING NOTES: 1. DATE: 10/1/2014 ENTRANCE CORRIDOR (BELOW) B. IF THE CONTRACTOR ELECTS TO USE EQUIPMENT OTHER THAN THE NAMED BASIS OF DESIGN, ANY ADDITIONAL COSTS ASSOCIATED WITH ELECTRICAL, GENERAL, AND MECHANICAL MODIFICATIONS REQUIRED SHALL BECOME HIS ULTIMATE RESPONSIBILITY. THIS MUST BE IDENTIFIED PRIOR TO THE BID SO THAT THERE WILL BE NO ADDITIONAL COSTS TO THE OWNER AFTER THE BID. B. PROVIDE DIELECTRIC JOINTS OR UNIONS AT DISSIMILAR METALS. C. INSTALL PIPE ESCUTCHEONS ON EACH PIPE PENETRATION THROUGH FLOORS, WALLS, PARTITIONS, AND CEILINGS WHERE PENETRATIONS ARE EXPOSED TO VIEW AND ON EXTERIOR OF BUILDING. C. CONTRACTOR SHALL PAY FOR ALL PERMITS AS WELL AS LICENSE AND INSPECTION FEES REQUIRED FOR HIS WORK. D. MATERIAL EXPOSED WITHIN PLENUMS SHALL HAVE A FLAME-SPREAD INDEX OF NOT MORE THAN 25 AND A SMOKE-DEVELOPED RATING OF NOT MORE THAN 50 IN ACCORDANCE WITH SECTION 102 (A), IMC (675 IAC 18-1). N. INSTALL VALVES WHERE REQUIRED FOR PROPER OPERATION OF PIPING AND ISOLATION OF EACH PIECE OF EQUIPMENT. LOCATE VALVES TO MAKE THEM ACCESSIBLE AND SO THAT SEPARATE SUPPORT(S) CAN BE PROVIDED WHEN NECESSARY. INSTALL VALVES WITH STEMS ORIENTED UPWARD WHERE POSSIBLE, BUT NEVER DOWNWARD FROM HORIZONTAL PLANE. WHERE INSULATION IS INDICATED, INSTALL EXTENDED STEM VALVES ARRANGED IN PROPER MANNER TO RECEIVE INSULATION. 2.2 WASTE AND VENT PIPING AND SPECIALTIES O. INSTALL INSULATION PRODUCTS ON SPECIFIED PIPING AND EQUIPMENT IN ACCORDANCE WITH MANUFACTURER'S WRITTEN INSTRUCTIONS AND IN ACCORDANCE WITH RECOGNIZED INDUSTRY PRACTICES TO ENSURE THAT THE INSULATION SERVES ITS INTENDED PURPOSE. A. WASTE AND VENT PIPING: ALL WASTE AND VENT PIPING SHALL BE PVC. ALL ABOVE GROUND WASTE AND VENT PIPING SHALL BE NO HUB JOINTS AND ALL BELOW GRADE WASTE AND VENT PIPING SHALL BE PVC. P. DO NOT CONCEAL ANY WORK UNTIL SYSTEM HAS BEEN TESTED AND INSPECTED. NOTIFY OWNERS REPRESENTATIVE 48 HOURS BEFORE INSPECTION AND TESTING. B. INSTALL PIPE ESCUTCHEONS ON EACH PIPE PENETRATION THROUGH FLOORS, WALLS, PARTITIONS, AND CEILINGS WHERE PENETRATIONS ARE EXPOSED TO VIEW AND ON EXTERIOR OF BUILDING. 1.2 WORK INCLUDED A. THE CONTRACTOR SHALL FURNISH ALL LABOR, MATERIAL, ACCESSORIES, TOOLS, ETC. TO COMPLETE THE PLUMBING WORK AS INDICATED AND SPECIFIED. B. PLUMBING WORK SHALL INCLUDE IN GENERAL TERMS, BUT NOT LIMITED TO THE FOLLOWING: PROVIDE NEW DOMESTIC WATER, WASTE, AND VENT SYSTEMS TO NEW PLUMBING FIXTURES. OBTAIN EXACT LOCATION OF ALL EQUIPMENT FROM THE ARCHITECTURAL DRAWINGS. 1.3 SHOP DRAWINGS A. SUBMIT FIVE (5) COPIES OR ELECTRONIC FORMAT ON ALL EQUIPMENT FURNISHED UNDER THIS CONTRACT. B. ANY PRODUCT MANUFACTURER LISTED ON THE DRAWINGS OR IN THE PROJECT MANUAL AS A PRE-APPROVED EQUAL MUST BE SUBMITTED TO ENGINEER FOR APPROVAL NOT LESS THAN SEVEN DAYS PRIOR TO BID DATE. C. THE CONTRACTOR SHALL SUPPLY THREE COPIES OF OPERATIONS AND MAINTENANCE MANUALS (O&M), AND ONE COPY OF AS-BUILT DRAWINGS WHEN THE JOB IS COMPLETED. O&M MANUALS SHALL INCLUDE EQUIPMENT CUTS AND WIRING DIAGRAMS. 1.4 CUTTING AND PATCHING A. THIS CONTRACTOR SHALL CUT AND PATCH ALL HOLES IN THE INTERIOR PARTITIONS AND CEILINGS AS REQUIRED FOR THE INSTALLATION OF HIS WORK. G.C. SHALL BE RESPONSIBLE FOR CUTTING NEW OPENINGS IN OUTSIDE WALLS, FLOORS, AND FOR PATCHING ALL OPENINGS RESULTED BY MECHANICAL SCOPE OF WORK, EXCEPT PATCHING FIRE RATED PENETRATIONS. PATCHING SHALL MATCH EXISTING AREAS AND SHALL BE DONE BY WORKMEN SKILLED IN THE APPROPRIATE TRADE. B. PROVIDE ASBESTOS FREE SMOKE AND FIRE TIGHT SEALS FOR ANY OPENING THROUGH FIRE RATED WALLS, FLOORS, CHASES OR CEILINGS USED AS PASSAGE FOR MECHANICAL COMPONENTS SUCH AS PIPING, CONDUIT OR DUCTWORK. C. INSTALL HANGERS, SUPPORTS, CLAMPS AND ATTACHMENTS TO SUPPORT PIPING PROPERLY FROM BUILDING STRUCTURE; COMPLY WITH MSS SP-69. ARRANGE FOR GROUPING OF PARALLEL RUNS OF HORIZONTAL PIPING TO BE SUPPORTED TOGETHER ON TRAPEZE HANGERS WHERE POSSIBLE. ALL PIPING HANGERS AND SUPPORTS SHALL BE UL OR FM APPROVED. CONTRACTOR SHALL USE GALVANIZED OR PAINTED UNISTRUTS FOR PIPING SUPPORTS. THE USE OF NON-PAINTED BLACK STEEL PIPING SUPPORTS SHALL NOT BE ALLOWED. ALL COPPER PIPING SHALL BE SUPPORTED WITH COPPER COATED OR ISOLATED HANGERS. D. ALL SEWER PIPING SHALL BE SUPPORTED NOT LESS THAN 5'-0" APART IN CONFORMANCE TO LOCAL CODE COMPLIANCE. 2.3 PIPE INSULATION A. INSTALL INSULATION PRODUCTS ON SPECIFIED PIPING IN ACCORDANCE WITH MANUFACTURER'S WRITTEN INSTRUCTIONS, AND IN ACCORDANCE WITH RECOGNIZED INDUSTRY PRACTICES, TO INSURE THAT THE INSULATION SERVES ITS INTENDED PURPOSE. FOR ALL PIPING INSULATION, A CONTINUOUS VAPOR RETARDER MUST BE MAINTAINED. THE INSULATION SHALL BE APPLIED WITH A CONTINUOUS, UNBROKEN MOISTURE AND VAPOR SEAL. ALL INSULATION JOINTS, SEAMS, FITTINGS AND PENETRATION LOCATIONS (I.E. P/T PORTS, VALVE STEMS, HEAT TRACE WIRING, ETC.) SHALL BE PROPERLY SEALED. IF RIGID INSERTS ARE REQUIRED, BETWEEN PIPE AND INSULATION SHIELDS, THEY SHALL BE OF EQUAL THICKNESS TO THE ADJACENT INSULATION AND SHALL BE VAPOR SEALED. B. INSTALL PVC JACKETS OVER ALL EXTERIOR PIPING/INSULATION, INCLUDING OVER THE ELBOWS. PVC JACKETS SHALL BE SECURED AS PER THE MANUFACTURER'S RECOMMENDATIONS. IF PVC TAPE IS USED, IT SHALL BE APPLIED ACCORDING TO THE MANUFACTURER'S INSTRUCTIONS. ALL JOINTS SHALL BE SEALED COMPLETELY ALONG THE LONGITUDINAL SEAMS, AND BE INSTALLED SO AS TO SHED WATER. ALL CIRCUMFERENTIAL JOINTS SHALL BE SEALED BY USE OF PREFORMED BUTT STRIPS, A MINIMUM OF 2" WIDE, OR A MINIMUM 2" OVERLAP, AND SHALL BE COMPLETELY WEATHER SEALED. RIGID INSERTS/PIPE SUPPORTS SHALL NOT PENETRATE THE PVC JACKET. JACKETS SHALL BE INSTALLED SO THAT ALL RAW EDGES, ENDS AND SURFACES OF THE INSULATION BELOW ARE PROTECTED. KENT A. POYSER REG. No. 37788 C. DOMESTIC COLD AND HOT WATER PIPING INSULATION SHALL BE 3/4" FLEXIBLE ELASTOMERIC INSULATION. ALL EXPOSED WATER PIPING SHALL BE INSULATED WITH 3/4" FLEXIBLE ELASTOMERIC WITH UV RESISTANT COATING. REGISTERED 1.5 SLEEVES D. SANITARY SEWER PIPING SHALL BE INSULATED WITH 3/4" FLEXIBLE ELASTOMERIC OR EQUAL. A. INSTALL SLEEVES FOR PIPES PASSING THROUGH CONCRETE AND MASONRY WALLS AND CONCRETE FLOOR AND ROOF SLABS. SEAL ALL PIPE PENETRATIONS USING SLEEVES AND MECHANICAL SLEEVE SEALS. SELECT SLEEVE SIZE TO ALLOW FOR ADEQUATE CLEAR SPACE, BETWEEN SLEEVE AND PIPE (OR PIPE INSULATION), FOR INSTALLATION OF MECHANICAL SLEEVE SEALS AND FIRE-STOPPING MATERIALS. 2.4 DOMESTIC WATER HEATERS B. INSTALL STEEL PIPE FOR SLEEVES SMALLER THAN 6 INCHES IN DIAMETER. INSTALL CAST-IRON WALL PIPES FOR SLEEVES 6 INCHES AND LARGER IN DIAMETER. ALL UNDERGROUND, EXTERIOR-WALL PIPE PENETRATIONS SHALL HAVE CAST-IRON WALL PIPES FOR SLEEVES. A. FURNISH AND INSTALL WATER HEATERS WITH CAPACITIES AS SHOWN ON PLANS, AS MANUFACTURED BY A.O. SMITH, STATE, OR APPROVED EQUAL. C. CUT SLEEVES TO LENGTH FOR MOUNTING FLUSH WITH BOTH SURFACES, EXCEPT WHEN INSTALLED IN FLOORS OF MECHANICAL EQUIPMENT AREAS, OR OTHER WET AREAS, WHERE THE SLEEVES SHALL BE EXTENDED 2 INCHES ABOVE THE FINISHED FLOOR LEVEL. EXTEND CAST-IRON SLEEVE FITTINGS BELOW FLOOR SLAB AS REQUIRED TO SECURE CLAMPING RINGS. B. WATER HEATERS SHALL BE LISTED BY UNDERWRITERS LABORATORIES AND MEETS THE THERMAL EFFICIENCY AND STANDBY LOSS REQUIREMENTS OF THE U.S. DEPARTMENT OF ENERGY AND CURRENT EDITION OF ASHRAE/IESNA 90.1. IN B. CAULKING: A SYNTHETIC ELASTOMER THAT IS UL CLASSIFIED FIRE STOP. "HILTI" FIRESTOPPING SHALL BE EXCLUSIVELY USED FOR ALL PENETRATIONS SEALS. C. LIMIT THE SIZE OF THE SPACE BETWEEN THE OPENING AND THE OUTSIDE OF THE DUCT OR PIPE TO 1" MAXIMUM. 1.7 COORDINATION OF WORK A. COORDINATE THE WORK WITH OTHER DISCIPLINES ON THE JOB. CLEARANCES ARE CRITICAL AND THERE SHALL BE COMPLETE COOPERATION BETWEEN ALL TRADES. THERE WILL BE NO EXTRA COSTS ALLOWED FOR THE INABILITY OF THIS CONTRACTOR TO COORDINATE HIS WORK WITH CABLE TRAYS AND OTHER EQUIPMENT/SYSTEMS PROVIDED BY OWNER/OTHER CONTRACTORS. B. ALL WORK SHALL BE DONE DURING NORMAL WORKING HOURS EXCEPT WHEN SPECIFICALLY AUTHORIZED BY THE OWNER OR WHEN IT MAY BENEFIT THE CONTRACTOR DIRECTLY. C. THIS CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING AND RELOCATING ANY MINOR INTERFERENCE TO INCLUDE CONDUITS, HANGERS, ETC. AS THE BASE BID OF THIS PROJECT. 1.8 PLANS AND SPECIFICATIONS A. THESE SPECIFICATIONS AND PLANS ARE MUTUALLY EXPLANATORY AND ANYTHING DESCRIBED OR SHOWN ON ONE, BUT NOT ON THE OTHER, SHALL BE CONSIDERED ON BOTH. B. SHOULD ERROR OR DISCREPANCY APPEAR ON THE PLANS OR SPECIFICATION, IT SHALL BE REFERRED TO THE ENGINEER BEFORE BIDDING. C. KEEP ONE SET OF PLANS AND SPECIFICATIONS IN GOOD CONDITION ON THE JOB AT ALL TIMES. 1.9 GUARANTEE A. THE CONTRACTOR SHALL GUARANTEE ALL EQUIPMENT, ACCESSORIES, WORKMANSHIP, AND MATERIAL FURNISHED BY HIM FOR A PERIOD OF ONE YEAR FROM FINAL ACCEPTANCE AGAINST ALL DEFECTS. CHECKED BY A. FURNISH AND INSTALL CAULKING AND SEALANT FOR ALL PIPING PASSING THROUGH ALL PARTITION WALLS WHETHER CONCEALED IN CHASES, ABOVE CEILINGS OR EXPOSED. APPROVED BY 1.6 CAULKING AND SEALANT PROJ. NO. 12-23 DATE 10/02/2014 SHEET NO. OF SHEETS DRAWN BY FILE: P:\LinfieldHunter&Junius\14-098_CommunityResourceCenter\Design Documents\Drawings\Plumbing\P-401 PLUMBING SPECIFICATIONS.dwg E. INSTALL HANGERS, SUPPORTS, CLAMPS AND ATTACHMENTS TO SUPPORT PIPING PROPERLY FROM BUILDING STRUCTURE; COMPLY WITH MSS SP-69. ARRANGE FOR GROUPING OF PARALLEL RUNS OF HORIZONTAL PIPING TO BE SUPPORTED TOGETHER ON TRAPEZE HANGERS WHERE POSSIBLE. ALL PIPING HANGERS AND SUPPORTS SHALL BE UL OR FM APPROVED. CONTRACTOR SHALL USE GALVANIZED OR PAINTED UNISTRUTS FOR PIPING SUPPORTS. THE USE OF NON-PAINTED BLACK STEEL PIPING SUPPORTS SHALL NOT BE ALLOWED. ALL COPPER PIPING SHALL BE SUPPORTED WITH COPPER COATED OR ISOLATED HANGERS. THIS SHEET DATE: 10/1/2014 E. DRAWINGS (PLANS, SCHEMATICS, AND DIAGRAMS) INDICATE GENERAL LOCATION AND ARRANGEMENT OF PIPING, DUCTWORK, AND EQUIPMENT. THE LOCATIONS AND ARRANGEMENT TAKE INTO CONSIDERATION PIPE SIZING AND FRICTION LOSS, EXPANSION, PUMP SIZING, AND OTHER DESIGN PARAMETERS. CLEARANCES ABOVE CEILINGS IN CERTAIN AREAS ARE LIMITED AND NECESSITATE DUCTWORK AND/OR PIPING ROUTINGS. WHERE POSSIBLE, PIPING, DUCTWORK, AND EQUIPMENT SHALL BE INSTALLED AS INDICATED. CHANGES REQUIRED TO MEET ARCHITECTURAL AND STRUCTURAL CONDITIONS ARE TO BE APPROVED BY THE ENGINEER. NEW PIPING, DUCTWORK, ETC. SHALL BE SUPPORTED FROM THE BUILDING STRUCTURE ONLY, AND NOT FROM ANY NEW OR EXISTING EQUIPMENT, DUCTWORK, ETC. D. INSTALL BALL VALVES AS SHOWN ON THE DRAWINGS AND AT ALL WATER PIPING TERMINATIONS FOR FIXTURE CONNECTION. VALVES SHALL BE RATED FOR 150 PSI STEAM WORKING PRESSURE, 600 PSI COLD WORKING PRESSURE, TWO-PIECE FULL PORT CONSTRUCTION, BRONZE BODY, CHROME PLATED BRASS BALL, REPLACEABLE TEFLON SEALS AND SEATS, BLOW PROOF STEAM, AND VINYL COVERED STEEL HANDLE. VALVES SHALL BE MANUFACTURED BY CONBRACO, NIBCO OR WATTS. 2011 by Linfield, Hunter & Junius, Inc. A. DOMESTIC HOT AND COLD WATER: INSTALL TYPE L DRAWN-TEMPER TUBING WITH WROUGHT COPPER FITTINGS AND 95/5 TIN/ANTIMONY SOLDER JOINTS. ALL DOMESTIC WATER PIPING SHALL BE TESTED TO 125 PSIG FOR TWO (2) HOURS WITHOUT LEAKAGE. 3608 18th Street, Suite 200 Metairie, Louisiana 70002 A. PERTINENT FEDERAL, STATE AND LOCAL REGULATIONS AND REQUIREMENTS OF NATIONAL BOARD OF THE FIRE UNDERWRITERS AND NATIONAL ELECTRICAL CODE ARE HEREBY MADE PART OF THIS CONTRACT. REQUIREMENTS OF AUTHORITY HAVING LOCAL JURISDICTION SHALL SUPERSEDE ALL OTHER REQUIREMENTS. 2.1 DOMESTIC WATER PIPING AND SPECIALTIES CITY OF KENNER - CONVERSION OF ANNE WASHINGTON COMMUNITY CENTER 9:44 PM TIME: 1.1 GENERAL PROFESSIONAL ENGINEERS, ARCHITECTS AND SURVEYORS PART 2 PRODUCTS PART 1 GENERAL LINFIELD, HUNTER & JUNIUS, INC. PLUMBING SPECIFICATIONS