3. ELECTRICAL EQUIPMENT AND COMPONENTS SHALL BE LOCATED AT OR ABOVE BASE
FLOOD ELEVATION OR GRADE ELEVATION, WHICHEVER IS HIGHER AS PER IBC 1612.1.
4. PANELS, SWITCHBOARDS, MOTOR CONTROL CENTERS ARE TO BE FULLY RATED. - NO
SERIES RATED EQUIPMENT IS ALLOWED.
5.
6.
7.
8.
COMPLETELY BOND AND GROUND ENTIRE ELECTRICAL SYSTEM IN ACCORDANCE WITH
NFPA 70 AND THE CURRENT NEC ADOPTED BY THE LOCAL AUTHORITY HAVING
JURISDICTION ARTICLE 250 IN IT'S ENTIRETY.
CONTRACTOR TO COORDINATE ALL UTILITY SERVICE REQUIREMENTS WITH LOCAL UTILITY
SERVICE PROVIDER FOR ALL UTILITIES REQUIRED BY OWNER/CLIENT (ELECTRICAL, PHONE,
CABLE, DATA. ETC.) AND PROVIDE A FULL INSTALL INCLUDING CONDUIT IN ACCORDANCE
WITH RESPECTIVE UTILITY'S REQUIREMENTS.
PROVIDE MONITORED SECURITY SYSTEM APPROVED BY THE CITY OF KENNER.
COORDINATE WITH TENANT PRIOR TO BIDDING. KEYPADS, MOTION DETECTORS, AND
CONTACTS HAVE BEEN SHOWN ON THESE PLANS.
CONTRACTOR IS RESPONSIBLE FOR COORDINATION WITH GENERAL CONTRACTOR ON THE
APPLICATION FOR PERMIT AND REMITTANCE OF ALL FEES. IN ADDITION, CONTRACTOR TO
PROVIDE FINAL INSPECTION CERTIFICATE.
9. INCLUDE THE COSTS TO INCORPORATE ALL CODES AND ORDINANCE REQUIREMENTS INTO
THE BASE BID AND INSTALLATION OF WORK FOR THIS PROJECT. NO ADDITIONAL FUNDS
WILL BE ALLOCATED FOR WORK TO CONFORM TO REGULATIONS AND REQUIREMENTS
AND/OR TO OBTAIN APPROVAL OF WORK.
53. ALL TERMINATIONS SHALL BE LISTED FOR 75 DEGREES C UNLESS OTHERWISE NOTED.
29. BATTERY BACKED SOUNDER BASE SMOKE DETECTORS TO BE INSTALLED IN ACCORDANCE
WITH NFPA 72 IN ITS ENTIRETY.
30. UPON COMPLETION OF THE PROJECT, THE CONTRACTOR SHALL PROVIDE A COMPLETE
SET OF THE DRAWINGS USED STRICTLY FOR MARK-UPS WHICH SHALL INCLUDE ALL
REVISIONS, SKETCHES, ETC., REQUIRED DURING CONSTRUCTION. CONTRACTOR SHALL
INSURE THAT ALL CIRCUITRY IS SHOWN AS WIRED IN THE FIELD AND HAS ACCURATE
HOMERUN DESIGNATIONS. THE CONTRACTOR SHALL MARK THESE DRAWINGS RED FOR
ADDITIONS AND GREEN FOR DELETIONS TO INDICATE EXACT, AS INSTALLED CONDITIONS.
31. UPON DOCUMENTED APPROVAL OF THE ARCHITECT, MOUNTING HEIGHTS MAY BE
ADJUSTED. LENGTH OF RECEPTACLES SHALL RUN VERTICALLY. DO NOT MOUNT OUTLETS
BACK TO BACK ON OPPOSITE SIDES OF PARTITIONS.
32. CONTRACTOR SHALL VISIT THE SITE OF THE PROPOSED WORK TO UNDERSTAND THE
COMPLEXITY, RESTRICTIONS, AND ALL THE REQUIREMENTS TO PERFORM WORK OF THESE
DOCUMENTS IN SAID FACILITY. NO ADDITIONAL COMPENSATION SHALL BE ALLOWED TO
THE SUCCESSFUL BIDDER FOR FAILURE TO BE SO INFORMED.
33. RACEWAYS AND OUTLETS PASSING THROUGH OR INSTALLED IN FIRE RATED
CONSTRUCTION SHALL BE SEALED WITH U.L LISTED FIRE RATED SEALANT SYSTEM IN
ACCORDANCE WITH SEALANT MANUFACTURERS' RECOMMENDATIONS. WHERE ELECTRICAL
RACEWAYS ARE INSTALLED THROUGH RATED FLOORS OR WALLS, THE CONTRACTOR
SHALL PROVIDE APPROPRIATE FITTINGS APPROVED BY ALL REQUIRED LOCAL AUTHORITIES
FOR THE INTENDED APPLICATION. REFER TO ARCHITECTURAL DRAWINGS FOR ADDITIONAL
INFORMATION.
34. RECESSED FIXTURES IN FIRE RATED CEILINGS AND RETURN AIR PLENUMS SHALL BE RATED
FOR THE FIRE RATING OF THE CEILING OR SHALL BE FULLY ENCLOSED IN A FIRE RATED
HOUSING ACCEPTABLE TO AUTHORITY HAVING JURISDICTION.
35. MAINTAIN FIRE RATING OF WALLS, FLOORS, AND CEILINGS WHEN PERFORMING WORK AND
INSTALLING DEVICES, BOXES, ETC. USE FIRE CAULK, "PUTTY PADS," OR OTHER APPROVED
AND APPROPRIATE METHODS TO MAINTAIN RATING.
39. ALL BATTERIES ASSOCIATED WITH TENANT, OWNER OR CONTRACTOR PROVIDED
EQUIPMENT TO BE INSTALLED IN BUILDING SHALL BE NON-GASSING SEALED MAINTENANCE
FREE TYPE. SUBMIT SPECIFICATIONS TO ENGINEER FOR APPROVAL. BATTERY BANKS
WHICH EXCEED 500 LBS. SHALL BE SUBMITTED TO STRUCTURAL ENGINEER FOR
APPROVAL. EQUIPMENT TO BE INSTALLED IN BUILDING WITH BATTERIES THAT DON'T MEET
THIS REQUIREMENT WILL REQUIRE SPECIAL PERMISSION BY THE OWNER BEFORE THE
EQUIPMENT CAN BE INSTALLED IN THE BUILDING.
12. PROVIDE TAMPER PROOF RECEPTACLES IN ACCORDANCE WITH NEC 406.12 FOR ALL
DWELLING UNIT RECEPTACLES EXCEPT FOR THOSE LOCATED IN ATTICS OR THOSE
LOCATED MORE THAN 5'-6" AFF.
40. SIZING OF MOTOR-RELATED ELECTRICAL COMPONENTS, INCLUDING FEEDERS, BRANCH
CIRCUITS AND OVERCURRENT PROTECTION ARE BASED ON RATINGS INDICATED. VERIFY
"ACTUALLY INSTALLED" MOTOR AND APPLIANCE RATINGS AND LOADS AND PROVIDE
CORRECTLY SIZED MOTOR-RELATED ELECTRICAL COMPONENTS. REFLECT ALL CHANGES IN
THE RECORD DRAWINGS. COORDINATE WITH ELECTRICAL ENGINEER IF NECESSARY.
13. PROVIDE ARC FAULT CIRCUIT INTERRUPTERS TYPE CIRCUIT BREAKERS IN DWELLING UNITS
FOR ALL 15 AND 20 AMPERE, 120 VOLT, CONVENIENCE RECEPTACLE CIRCUITS FOR
FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS,
BEDROOMS, SUNROOMS, RECREATION ROOMS, CLOSETS, HALLWAYS, OR SIMILAR
ROOMS OR AREAS.
14. MULTI-WIRE BRANCH CIRCUITS SHALL BE PROVIDED WITH A COMMON DISCONNECT AT
THE SOURCE. THE DISCONNECT SHALL BE EITHER A MULTI-POLE CIRCUIT BREAKER OR
INDIVIDUAL CIRCUIT BREAKERS WITH HANDLE TIES.
15. CONTRACTOR SHALL PROVIDE ALL NECESSARY TESTING EQUIPMENT (INCLUDING 24VDC
SYSTEM) AND PERSONNEL FOR MAKING TEST. ALL TEST SHALL BE MADE IN THE
PRESENCE OF THE OWNER OR A REPRESENTATIVE THEREOF. WHEN TEST RESULTS ARE
NOT SATISFACTORY, THE CONTRACTOR SHALL MAKE ALL NECESSARY ADJUSTMENTS
AND/OR CHANGES AND SHALL NOTIFY OWNER THAT HE IS READY FOR ANOTHER TEST.
CONTRACTOR SHALL REPEAT TEST OR TESTS WHICH DISCLOSED FAULTY OR DEFECTIVE
WORK OR EQUIPMENT AND SHALL MAKE SUCH ADDITIONAL TESTS AS OWNER DEEMS
NECESSARY.
16. PROVIDE COMPLETE INSTALLATION, INCLUDING ALL MINOR ITEMS. THIS INCLUDES
ELECTRICAL, PHONE, CABLE, DATA, AS WELL AS ANY OTHER SYSTEMS SHOWN IN THESE
DRAWINGS. PROVIDE ALL MOUNTING HARDWARE FOR LIGHTING FIXTURES AND OTHER
ELECTRICAL EQUIPMENT REQUIRED FOR A COMPLETE INSTALL.
17. DRAWINGS ARE DIAGRAMMATICAL. ALL ELECTRICAL EQUIPMENT LOCATIONS ARE
APPROXIMATE ONLY. FOR ALL MEASUREMENTS, USE ARCHITECTURAL, MECHANICAL OR
OTHER RESPECTIVE DIVISION'S PLANS AND FIELD SURVEYS. COORDINATE WITH AIR
CONDITIONING WORK, CABINET WORK, PARTITION WORK, ETC., WHEN REQUIRED. LAYOUT
OF EQUIPMENT, ACCESSORIES, SPECIALTIES, WIRING AND CONDUIT SYSTEMS ARE
STRICTLY DIAGRAMMATIC UNLESS SPECIFICALLY DIMENSIONED, AND DO NOT INDICATE
EVERY REQUIRED FITTING, ELBOW, TRANSITION, JUNCTION BOX OR SIMILAR ITEMS THAT
ARE REQUIRED FOR A COMPLETE INSTALLATION.
18. PROVIDE ALL REQUIRED OVERCURRENT AND DISCONNECTION MEANS FOR EQUIPMENT
SPECIFIED BY OTHER DISCIPLINES, WHETHER SPECIFICALLY INDICATED ON THESE
DRAWINGS OR NOT. DEVICE WILL HAVE APPROPRIATE SIZE, NUMBER OF POLES AND
NEMA RATING FOR INTENDED APPLICATION.
38. GANGABLE BOXES ARE NOT TO BE USED.
LAMP
CFL
200W
F2
WALL MOUNT FLUORESCENT
COOPER
22DW1T53UEB
FLUOR
T5
F3
VANITY LIGHT
COOPER
60024WT5/2/14120V*
FLUOR
T5
54. ALL CABLE SHALL BE COPPER UNLESS OTHERWISE NOTED.
55. BRANCH CIRCUITS WITH UNMARKED CONDUCTOR AMOUNTS AND SIZES SHALL DEFAULT
TO 2#12,#12G,1/2"C.
56. CONTRACTOR TO COORDINATE ALL UTILITY SERVICE REQUIREMENTS WITH LOCAL UTILITY
SERVICE PROVIDER. (ELECTRICAL, PHONE, CATV, ECT.)
F4
57. PRIOR TO ROUGHING-IN ANY WIRING OR DEVICES, CONFIRM EXACT LOCATIONS WITH
ARCHITECT/OWNER.
58. ALL BRANCH CIRCUITRY INSTALLATION AND LOADING SHALL COMPLY WITH CURRENT NEC.
F4A
59. NO MORE THEN (10) DUPLEX OUTLETS ARE ALLOWED ON A 20A BRANCH CIRCUIT.
60. DO NOT LOAD LIGHTING BRANCH CIRCUITS MORE THAN 80%.
61. WHERE NEW LIGHTS OR RECEPTACLES ARE DESIGNATED TO BE CONNECTED TO AN
EXISTING CIRCUIT, CONTRACTOR SHALL TRACE EXISTING CIRCUIT TO DETERMINE CIRCUIT
LOADING. THE LOAD ON A 20 AMP CIRCUIT SHALL NOT EXCEED 16 AMPS (80%). WHERE
THIS CANNOT BE ACHIEVED, CONTRACTOR SHALL CONTACT THE ENGINEER FOR
ALTERNATIVE CIRCUITING INSTRUCTIONS.
F4B
F5
* FINISH TO BE SELECTED BY ARCHITECT
6" RECESSED CAN
COOPER HALO
HALO 6" RECESSED CAN, IC RATED FOR DIRECT INSULATION
CONTACT, STANDARD LAMP BASE, PROVIDE WITH CFL LAMP,
WHITE BAFFLE AND TRIM.
6" RECESSED CAN
COOPER HALO
HALO 6" RECESSED CAN, IC RATED FOR DIRECT INSULATION
CONTACT, STANDARD LAMP BASE, PROVIDE WITH CFL LAMP,
WHITE SHOWER LENS.
6" RECESSED CAN
COOPER HALO
HALO 6" RECESSED CAN, IC RATED FOR DIRECT INSULATION
CONTACT, SUITABLE FOR ANGLED MOUNTING, STANDARD LAMP
BASE,PROVIDE WITH CFL LAMP, WHITE BAFFLE AND TRIM.
KITCHEN PENDANT
PROGRESS LIGHTING
P5078-09
CFL
26W
CFL
26W
CFL
26W
62. ARCHITECT BASE DRAWINGS HAVE PREFERENCE. ALL DISCREPANCIES WITH BASE
DRAWINGS IN ELECTRICAL SET TO BE CLARIFIED WITH CONTRACTOR, ARCHITECT AND
ELECTRICAL ENGINEER.
F6
STAIR PENDANT
COOPER
10640P1ST5/3/21120NA
*COORDINATE FABRIC SELECTION WITH ARCHITECT
FLUOR
63W
63. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN FOR CEILING TYPES AND EXACT
LOCATION OF ALL FIXTURES. VERIFY CEILING TYPES WITH ARCHITECT PRIOR TO ORDERING
LIGHT FIXTURES TO ENSURE COMPATIBLE FIXTURE TRIMS AND MOUNTING HARDWARE.
F7
GROUND MOUNTED FLOOD LIGHT
PROVIDE STANDARD 2 LAMP FLOOD LIGHT WITH WIRE GUARDS
REPAIR MOUNTING AND CONDUIT AS NECESSARY
INCAND
(2) 100W
F8
SURFACE MOUNTED FLUORESCENT LITHONIA
11432REWH
FLUOR
(4) 32W
SURFACE MOUNTED FLUORESCENT LITHONIA
11432REWH
FLUOR
(4) 32W
F8
EMERGENCY LIGHT
ATLITE
PC1-10
BLAKE MICHAEL HOSLI
License No. 38688
43. SHOP DRAWINGS SHALL BE SUBMITTED FOR APPROVAL TO ARCHITECT PRIOR TO
CONSTRUCTION FOR PANELBOARDS, CIRCUIT BREAKERS, LIGHT FIXTURES,
TRANSFORMERS, DISCONNECT SWITCHES, CONTROL DEVICES, WIRING DEVICES AND
SPEAKER/BACK BOXES CORD SETS FOR ELECTRICAL EQUIPMENT (DRYER, KITCHEN
EQUIPMENT). OPERATION AND MAINTENANCE MANUALS SHALL BE SUBMITTED FOR
PANELBOARDS, TRANSFORMERS, LIGHT FIXTURES WITH EMERGENCY BATTERY PACKS AND
ANY OTHER EQUIPMENT UNDER THIS CONTRACT REQUIRING REGULAR OPERATION OR
MAINTENANCE.
44. CONTRACTOR SHALL CAREFULLY INVESTIGATE STRUCTURAL CONDITIONS, WALL AND
CHASE LOCATIONS AND ROOM FINISHES AND MAKE ACTUAL MEASUREMENTS ON THE
JOB SO THAT ALL ELECTRICAL EQUIPMENT SUCH AS PANELBOARDS, SWITCHES,
RECEPTACLES, LIGHTING FIXTURES, FIRE ALARM STATIONS, HORNS, ANNUNCIATORS,
CONDUITS AND ACCESSORIES SHALL HAVE ADEQUATE CLEARANCES AS REQUIRED BY
NEC AND BY THE MANUFACTURER'S REQUIRED INSTALLATION PRACTICES. ALL EQUIPMENT
SHALL BE CONNECTED IN A WAY THAT ALLOWS AMPLE MAINTENANCE SPACE AND
PASSAGE SPACE.
45. A WARRANTY PERIOD OF ONE YEAR FROM THE DATE OF ACCEPTANCE OF FINAL
COMPLETION OF THE PROJECT SHALL APPLY TO ALL ELECTRICAL EQUIPMENT FURNISHED
AND TO ANY ELECTRICAL WORK FURNISHED UNDER THESE SPECIFICATIONS.
CONTRACTOR SHALL REPAIR OR REPLACE ANY DEFECTS IN WORKMANSHIP, DESIGN OR
MATERIALS AT HIS OWN EXPENSE. WARRANTY WORK SHALL BE PERFORMED WITHIN A
REASONABLE TIMEFRAME AS SOON AS POSSIBLE AFTER THE DISCREPANCY IS NOTICED.
20. IF A CONFLICT OCCURS BETWEEN DRAWINGS AND/OR SPECIFICATIONS, BID THE GREATER
QUANTITY AND/OR QUALITY.
47. PROVIDE TYPEWRITTEN PANELBOARD SCHEDULES TO PANELBOARD DOORS DEPICTING
THE FINAL AS-BUILT CONDITIONS AT PROJECT COMPLETION. INDICATE DEVICE AND ROOM
I CA
L E NG I N
EE
2014/10/02
42. PROVIDE INTEGRAL CONTROL TRANSFORMERS WITH OVERCURRENT PROTECTION AS
REQUIRED FOR MECHANICAL EQUIPMENT. SEE MECHANICAL DRAWINGS FOR ADDITIONAL
INFORMATION AND REQUIREMENTS.
19. ALL ADJUSTABLE FIXTURES SHALL BE LOCATED AND PROPERLY AIMED AS DIRECTED BY
THE ARCHITECT OR LIGHTING DESIGNER. ALL AIMING OF BUILDING FACADE LIGHTING
SHALL BE PERFORMED BY CONTRACTOR AT NIGHT. ADJUSTABLE SUSPENDED FIXTURES
HUNG WITH CHAIN OR CABLE SHALL HAVE SLACK IN THE SUPPORT AVAILABLE TO MOVE
THE FIXTURE AS DIRECTED BY ARCHITECT OR LIGHTING DESIGNER.
PROFESSINAL ENGINEER
IN
ATLITE
LC2-R-U
41. PROVIDE HACR TYPE CIRCUIT BREAKERS FOR HVAC EQUIPMENT. VERIFY SIZE WITH
MECHANICAL EQUIPMENT SUPPLIER AND/OR MANUFACTURER.
46. CONTRACTOR SHALL CONTINUOUSLY MAINTAIN ADEQUATE PROTECTION OF STORED
MATERIALS AND INSTALLED WORK. ALL FIXTURES AND EQUIPMENT SHALL BE TIGHTLY
COVERED WITH SHEET POLYETHYLENE OR WATERPROOF TARPAULIN AND PROTECTED
AGAINST DIRT, RUST, MOISTURE, CHEMICAL AND MECHANICAL INJURY REGARDLESS OF
LOCATION. MATERIALS SHALL NOT BE STORED DIRECTLY ON EARTH ON IN AREAS WHERE
THEY WILL BE SUBJECT TO PHYSICAL INJURY FROM VEHICLE TRAFFIC OR CONSTRUCTION
EQUIPMENT. CONDUIT OPENINGS SHALL BE CAPPED OR PLUGGED DURING INSTALLATION.
KEEP STOCK OF MATERIAL AND EQUIPMENT STORED ON THE PREMISES IN A NEAT AND
ORDERLY MANNER.
OF LOU I S I
TE
AN
A
T
TR
UNIVERSAL EXIT SIGN WITH HEADS
2011 by Linfield, Hunter & Junius, Inc.
CFL
26W
A
11. PROVIDE GROUND FAULT CIRCUIT INTERRUPTERS TYPE RECEPTACLES FOR ALL 15 AND 20
AMPERE, 120 VOLT, CONVENIENCE RECEPTACLES IN BATHROOMS, KITCHEN AREAS,
EXTERIOR AND WITHIN 6 FOOT OF ALL SINKS. IN DWELLING UNITS PROVIDE GROUND
FAULT CIRCUIT INTERRUPTERS TYPE RECEPTACLES FOR ALL 15 AND 20 AMPERE, 120
VOLT, CONVENIENCE RECEPTACLES IN BATHROOMS, OUTLETS ABOVE THE KITCHEN
COUNTER, HVAC LOCATIONS, OUTDOOR OUTLETS, AND WITHIN 6 FOOT OF ALL SINKS IN
LAUNDRY, UTILITY AND WET BAR LOCATIONS.
37. "F" CLIPS AND OTHER "OLD WORK" STYLE BOXES ARE NOT TO BE USED.
CATALOG
HUNTER
52060
EC
36. PROVIDE CONDUIT SEALING FITTINGS ON THE EXTERIOR SIDE OF THE CONDUIT ENTRIES
INTO ALL COOLERS, FREEZERS AND REFRIGERATED SPACES TO PREVENT CONDENSATION
FROM FORMING IN ELECTRICAL CONDUITS AT THE THERMAL TRANSITION BOUNDARIES.
DESCRIPTION
FAN WITH LIGHT KIT 52"
EL
10. WORKMANSHIP TO MEET N.E.C.A. GUIDELINES. PUT INTO OPERATION AND TEST ALL
ELECTRICAL EQUIPMENT. ALL CIRCUITS SHALL BE TESTED BY CONTRACTOR FOR PROPER
VOLTAGE AND PHASE ROTATION; CONTINUITY; PROPER POLARITY; PROPERLY FUNCTIONING
GROUND FAULT INTERRUPTERS AND OTHER OUTLETS AND EQUIPMENT; AND FOR
ELECTRICAL ISOLATION OF ALL UNGROUNDED CONDUCTORS FROM GROUND AND FROM
THE CONDUIT SYSTEM. CONTRACTOR SHALL BALANCE THE LOADS ON EACH PANEL TO
WITHIN 15% BETWEEN MAXIMUM AND MINIMUM CURRENTS.
TAG
F1
3608 18th Street, Suite 200
Metairie, Louisiana 70002
SUBMIT EQUIPMENT INFORMATION FOR ENGINEER REVIEW FOR PANELBOARDS,
DISCONNECTS, RECEPTACLES, SWITCHES, PLATES, CONDUIT, LIGHTING FIXTURES, SMOKE
DETECTORS, SECURITY SYSTEM DEVICES, ETC.
52. EXISTING CONDITIONS TAKEN OFF OF BUILDING PLANS. CONTRACTOR SHALL VERIFY
EXISTING CONDITIONS IN FIELD PRIOR TO CONSTRUCTION.
FIXTURE SCHEDULE
IN
G
2.
28. PROVIDE EXPANSION AND DEFLECTION FITTINGS FOR CONDUITS CROSSING EXPANSION
JOINTS. PROVIDE BONDING JUMPERS FOR ALL EXPANSION FITTINGS.
51. COORDINATE PHASING AS DIRECTED BY ARCHITECTURAL DRAWINGS AND THE GENERAL
CONTRACTOR. MAKE ALL TEMPORARY CONNECTIONS NECESSARY ACCORDING TO
ELECTRICAL DEMOLITION NOTES.
R
THE TERM "PROVIDE" MEANS TO FURNISH AND INSTALL.
27. RACEWAYS PENETRATING THROUGH ANY ROOF SHALL HAVE ROOF PITCH POCKETS AND
FLASHING WITH CAULKING AND PIPE SLEEVE. INSTALLATION SHALL BE WATERTIGHT.
ROOF MOUNTED CONDUIT SYSTEMS SHALL BE INSTALLED ON SYNTHIC RECYCLED RUBBER
SUPPORT BASES SPACED TO MEET NEC REQUIREMENTS FOR THE SIZE OF THE CONDUIT.
APPROVED BY
DATE: 10/1/2014
1.
26. ALL ELECTRICAL DISTRIBUTION EQUIPMENT SHALL BE OF THE SAME MANUFACTURER,
INCLUDING: PANELBOARDS, DISCONNECTS, ETC.
50. THESE DRAWINGS HAVE BEEN COORDINATED WITH MECHANICAL AND PLUMBING
DRAWINGS. ELECTRICAL CONTRACTOR TO COORDINATE FUSE, CIRCUIT BREAKER, WIRE,
CONDUIT, DISCONNECT, ETC. SIZES WITH MANUFACTURERS' RECOMMENDATIONS OF
EQUIPMENT AND UNITS ACTUALLY INSTALLED AND MODIFY AS NECESSARY TO
ACCOMMODATE.
CHECKED BY
6.
25. ALL WORK SHALL BE PROPERLY SUPPORTED FROM THE BUILDING STRUCTURE IN AN
APPROVED MANNER WITH A SUPPORT DEVICE THAT IS LISTED FOR THE USE AND
FASTENED TO BUILDING CONSTRUCTION WITH APPROVED SUPPORTS LISTED FOR USE.
PROJ. NO.
12-23
DATE
10/02/2014
SHEET NO.
OF
SHEETS
DRAWN BY
3.
4.
5.
49. NO INSTALLATION WILL BE CONSIDERED COMPLETE UNTIL THE PROPER OPERATION OF ALL
ELECTRICAL EQUIPMENT HAS BEEN DEMONSTRATED TO THE SATISFACTORY OF THE
OWNER OR ITS AUTHORIZED REPRESENTATIVE. ALSO, ANY RECORD DRAWINGS, BOOKS
NECESSARY TO MAINTAIN OR REPLACE ANY CONTRACTOR SUPPLIED MATERIAL SHALL BE
COMPILED AND PRESENTED TO THE OWNER IN A FORM SUITABLE FOR REPRODUCTION.
THIS SHEET
24. ALL ELECTRICAL DEVICES SHOWN BEING LOCATED IN EXISTING WALLS SHALL BE
CONCEALED AND NOT SURFACE MOUNTED. WALLS MODIFIED TO ACCOMMODATE SAID
DEVICES SHALL BE PATCHED AFTER INSTALLATION ACCORDING TO ARCHITECTURAL
SPECIFICATIONS.
THE NATIONAL ELECTRICAL CODE (NEC) (CURRENT EDITION ADOPTED BY AHJ).
ENTERGY (OR RESPECTIVE UTILITY PROVIDER) -CUSTOMER INSTALLATION STANDARDS FOR
ELECTRIC SERVICE.
NFPA - NATIONAL FIRE PROTECTION ASSOCIATION NFPA-101, LIFE SAFETY CODE.
NFPA - NATIONAL FIRE PROTECTION ASSOCIATION NFPA-72, FIRE ALARM CODE.
NFPA 90A STANDARD FOR THE INSTALLATION OF AIR CONDITIONING AND VENTILATING
SYSTEMS.
NFPA 90B STANDARD FOR THE INSTALLATION OF WARM AIR HEATING AND AIR
CONDITIONING SYSTEMS.
OSHA CODE OF FEDERAL REGULATIONS (FOR CONSTRUCTION PRACTICES).
ANSI HANDICAPPED CODE-A117.1.
APPLICABLE STATE AND LOCAL CODES/ORDINANCES.
CBM - CERTIFIED BALLAST MANUFACTURER
IPCEA - INSULATED POWER CABLE ENGINEERS' ASSOCIATION
FM - FACTORY MUTUAL
ETL - ELECTRICAL TESTING LABORATORIES
IES - ILLUMINATING ENGINEERING SOCIETY
NECA
APPLICABLE HEALTH CODES
IBC
PROFESSIONAL ENGINEERS, ARCHITECTS
AND SURVEYORS
1.
2.
23. RACEWAYS AND CABLES SHALL BE INSTALLED CONCEALED UNLESS OTHERWISE NOTED.
48. AT THE END OF EACH WORK DAY, THE CONTRACTOR SHALL REMOVE ALL DEBRIS,
SURPLUS MATERIALS OR FOREIGN MATTER CAUSED BY THE PERFORMANCE OF
ELECTRICAL WORK ON THE PREMISES. UPON COMPLETION OF THE WORK THE
CONTRACTOR SHALL BE RESPONSIBLE FOR LEAVING THE PREMISES IN A CLEAN
CONDITION.
LINFIELD, HUNTER & JUNIUS, INC.
22. INSTALL EQUIPMENT SO THAT CLEAR WORKING SPACE REQUIREMENTS OF THE NEC ARE
MET. REFER TO NEC 110.26.
S
WORK PERFORMED UNDER THE ELECTRICAL INSTALLATION SHALL BE IN ACCORDANCE WITH
STANDARDS LISTED BELOW OF THE LATEST APPLICABLE EDITION ADOPTED BY THE AUTHORITY
HAVING JURISDICTION. WHERE THESE SPECIFICATIONS ARE MORE STRINGENT, THEY SHALL
TAKE PRECEDENCE. IN CASE OF CONFLICT, OBTAIN A DECISION FROM THE ARCHITECT.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
FILE: P:\LinfieldHunter&Junius\14-098_CommunityResourceCenter\Design Documents\Drawings\Electrical\E-001 SYMBOLS, NOTES, & RISER.dwg
NAME LOCATION.
21. COORDINATE ELECTRICAL WORK WITH ALL OTHER TRADES PRIOR TO SUBMITTING A BID.
CITY OF KENNER - CONVERSION OF
ANNE WASHINGTON COMMUNITY CENTER
TIME:
6:10 PM
ELECTRICAL NOTES:
P
'F1'
PHOTO CELL
4'-0"
RECEPTACLES
WALL
ABOVE COUNTER WITHOUT BACKSPLASH
ABOVE COUNTER WITH BACKSPLASH
1'-6"
0'-8" ABOVE TOP OF COUNTER
0'-4" ABOVE TOP OF BACKSPLASH
TELEPHONE
DESK/TABLE
WALL TELEPHONE
ABOVE COUNTER
ABOVE COUNTER
WALL
ABOVE COUNTER
ABOVE COUNTER
1'-6"
4'-8"
0'-8"
0'-4"
1'-6"
0'-8"
0'-4"
(SWITCH MODIFIIER) THREE WAY SWITCH OR DIMMER
120V. DUPLEX RECEPTACLE WALL / FLOOR MOUNTED
DATA OUTLETS
120V. QUADRUPLEX RECEPTACLE WALL / FLOOR MOUNTED
SPECIAL RECEPTICAL (TYPE AS NOTED)
J
ELECTRICAL EQUIPMENT
40,000 AMPS
<40,000 AMPS
DEVICE KAIC
RATING
N/A
42 KAIC
ABOVE TOP OF COUNTER
ABOVE TOP OF BACKSPLASH
6'-6" TO TOP OF ENCLOSURE
6'-6" TO TOP OF ENCLOSURE
6'-6" TO TOP OF ENCLOSURE
TV CABLE OUTLET
WALL
1'-6"
CONTROL/SECURITY
DOOR ACCESS KEYPAD
CCTV CAMERA
CCTV MONITOR
3'-10"
0'-6" BELOW CEILING LEVEL
COORDINATE WITH OWNER
ENTERGY POLE MTD
TRANSFORMERS
OVHD SERVICE
CONNECT ACCORDING TO
UTILITY STANDARDS
GROUND FAULT CIRCUIT INTERRUPTER RECEPTACLE
UC
UNDER COUNTER REFRIGERATOR
WP
WEATHERPROOF
TR
2014/10/02
P1
TELEPHONE OUTLET WITH PLATE
DATA OUTLET WITH PLATE
#2/0 GND TO BUILDING STEEL &
MAIN COLD WATER PIPE NO
MORE THEN 5' FROM PIPE ENTRY
INTO BUILDING.
CABLE TV DROP
CCTV CAMERA - EXTERIOR
MOTION DETECTOR
KEYPAD
WC
WINDOW CONTACT
DC
DOOR CONTACT
EE
400A/2P
400AF
SE RATED
N3R
FIRE ALARM SMOKE DETECTOR WITH SOUNDER BASE
KEY
L E NG I N
3-#600,#2G
3 1/2"C. CU
CIRCUIT HOMERUN
MD
I CA
CITY OF KENNER - CONVERSION OF
ANNE WASHINGTON COMMUNITY CENTER
GFI
S
AFF
ABOVE FINISHED FLOOR
3-#600
3 1/2"C. CU
PROFESSINAL ENGINEER
IN
EC
ABOVE COUNTER
OF LOU I S I
TE
AN
A
T
BLAKE MICHAEL HOSLI
License No. 38688
RECEPTACLE MODIFIERS
AC
2011 by Linfield, Hunter & Junius, Inc.
ABOVE TOP OF COUNTER
ABOVE TOP OF BACKSPLASH
A
PANELBOARD - FLUSH MOUNTED
WITHOUT BACKSPLASH
WITH BACKSPLASH
UTILITY SERVICE
BASED ON 100KVA SIZE XFMR.
P1
SAFETY SWITCH
PANELBOARD
COMMUNICATIONS CABINET
JUNCTION BOX
DISCONNECT, SIZE NOTED
WITHOUT BACKSPLASH
WITH BACKSPLASH
SHORT CIRCUIT
AVAILABLE
3608 18th Street, Suite 200
Metairie, Louisiana 70002
WALL SWITCHES AND DIMMERS
DEVICE NAME
EL
FILE: P:\LinfieldHunter&Junius\14-098_CommunityResourceCenter\Design Documents\Drawings\Electrical\E-001 SYMBOLS, NOTES, & RISER.dwg
SWITCHES
DESIGNATES FIXTURE TYPE - SEE LIGHTING FIXTURE SCHEDULE
NORMAL SWITCH - TOGGLE
3
6'-6"
0'-8" ABOVE TOP OF MIRROR
CENTER BETWEEN FRAME & CEILING
7'-0"
(SEE ACHITECTURAL DETAIL)
IN
G
BATTERY POWERED EMERGENCY LIGHT
WALL MOUNTED, SCONCE
WALL MOUNTED, ABOVE MIRROR
WALL MOUNTED, ABOVE DOOR
WALL MTD,ABOVE STAIR LANDING OR STEPS
IN SOFFIT
R
CEILING MOUNTED EXIT SIGN - SHADED AREAS INDICATE FACES - WHEN
SHOWN ARROWS INDICATE DIRECTION OF EXIT - BATTERY OR EM. GEN.
WALL MOUNTED EXIT SIGN - SHADED AREAS INDICATE FACES - WHEN
SHOWN ARROWS INDICATE DIRECTION OF EXIT - BATTERY OR EM. GEN.
LIGHTING FIXTURES
INTERIOR
METAL COLD WATER PIPE
3/4"X10' CU-BR GROUND ROD
DRIVEN 10'-0" INTO GROUND
APPROVED BY
WALL BRACKET FIXTURE
TABLE 1 - SHORT CIRCUIT FAULT TABLE
CHECKED BY
WALL WASHER FIXTURE
THE CONTRACTOR SHALL COORDINATE THE MOUNTING HEIGHT OF ALL FIXTURES, DEVICES, AND OUTLETS WITH ALL
DRAWINGS. SPECIAL MOUNTING HEIGHTS SHOWN ON THE DRAWINGS SHALL TAKE PRECEDENCE OVER THOSE
GIVEN BELOW. ALL MOUNTING HEIGHTS ARE FROM FINISHED FLOOR TO CENTERLINE OF DEVICE, UNLESS NOTED
OTHERWISE.
PROJ. NO.
12-23
DATE
10/02/2014
SHEET NO.
OF
SHEETS
DRAWN BY
SURFACE OR RECESSED DOWNLIGHT
(TYPE DETERMINES MOUNTING)
THIS SHEET
PENDANT LIGHT
TYPICAL MOUNTING HEIGHTS
S
SURFACE, SUSPENDED OR RECESSED FLUORESCENT
(TYPE DETERMINES MOUNTING)
PROFESSIONAL ENGINEERS, ARCHITECTS
AND SURVEYORS
LINFIELD, HUNTER & JUNIUS, INC.
6:10 PM
TIME:
DATE: 10/1/2014
ELECTRICAL LEGEND
1
EX. P2
D
HORN
AC
D
R J UC
P PHOTOCELL
DATE: 10/1/2014
D
GFI/AC
R
D
D
D
D
D
D D
AC AC
UC
D
AC
R
AC
R
R
GFI/AC
R
D
D
D
R
IN WALL
CABINET
D
D R
UC
AC
D
D
D
D
DATA
CABINET
R
R
2011 by Linfield, Hunter & Junius, Inc.
3608 18th Street, Suite 200
Metairie, Louisiana 70002
1
PROFESSIONAL ENGINEERS, ARCHITECTS
AND SURVEYORS
TIME:
EX. P2
LINFIELD, HUNTER & JUNIUS, INC.
6:12 PM
COMM
BACKBOARD
2
(2) 125A
METERS
& DISC.
D
R
R
DD
X2
R
D
X2
R
R
DD
R
BLAKE MICHAEL HOSLI
License No. 38688
D
X9
EC
R
PROFESSINAL ENGINEER
IN
TR
R
R
R
R
A
R
OF LOU I S I
TE
AN
A
T
S
R
D
IN
G
D DDD GFI/AC
R
R
EL
I CA
L E NG I N
R
EE
2014/10/02
D
X3
D
D
D
D
D
D
D
D
KEYED NOTES:
GENERAL SHEET NOTES:
1
EXISTING PANEL TO BE DEMOLISHED. JUNCTION BOX AND EXTEND ALL REUSED CIRCUITS TO NEW PANEL
LOCATION ON FIRST FLOOR - REFER TO NEW PLAN.
1.
ALL SHOWN OBJECTS ARE EXISTING. OBJECTS MARKED WITH A "R" ARE TO BE RELOCATED WHERE SHOWN ON
NEW PLANS. OBJECTS MARKED WITH A "D" ARE TO BE DEMOLISHED.
2
EXISTING TWO METER SERVICE TO BE DEMOLISHED. SINGLE METER AND DISCONNECT TO BE PROVIDED.
REFER TO NEW PLAN AND ONE LINE DIAGRAM.
2.
ALL INTERIOR LIGHTING IS TO BE DEMOLISHED AND CIRCUITS FREED FOR NEW LIGHTING. SOME SWITCHING
LOCATIONS SHALL BE MAINTAINED AS SHOWN ON NEW PLANS.
3.
ALL ELECTRICAL DEVICES NOT SHOWN TO BE REUSED ARE TO BE DEMOLISHED. JUNCTION BOX AND MAINTAIN
CIRCUIT CONTINUITY TO ANY DEVICES ON SAME CIRCUIT NOT DEMOLISHED. THIS INCLUDES BUT IS NOT
LIMITED TO RECEPTACLES, COMMUNICATIONS OUTLETS, SWITCHES, EXIT SIGNS, EMERGENCY LIGHTS,
LIGHTING, DISCONNECTS, ETC. EC TO PROVIDE A FULLY FUNCTIONING AND CODE COMPLIANT SYSTEM AT
PROJECT COMPLETION.
GENERAL SHEET NOTES:
4.
ALL PHONE AND DATA BRANCH LOCATIONS ARE TO BE DEMOLISHED.
5.
ALL EMERGENCY LIGHTING AND EXIT SIGNS TO BE DEMOLISHED. NEW LOCATIONS OF NEW SIGNS AND
EMERGENCY LIGHTING SHOWN ON NEW PLANS.
CHECKED BY
D
P
PROJ. NO.
12-23
DATE
10/02/2014
SHEET NO.
OF
SHEETS
DRAWN BY
D
THIS SHEET
R
APPROVED BY
D
CITY OF KENNER - CONVERSION OF
ANNE WASHINGTON COMMUNITY CENTER
FILE: P:\LinfieldHunter&Junius\14-098_CommunityResourceCenter\Design Documents\Drawings\Electrical\E-101 EXISTING CONDITIONS.dwg
R
ENTRANCE
CORRIDOR
(BELOW)
F4
F4
REPLAMP AND REPLACE TRIM WITH EXTERIOR
GRADE TRIM
F5
KITCHEN/
F4 DINING
33
TO SIGN
CIRCUIT
DATE: 10/1/2014
TO 2ND
FLOOR
P1:7
F4
F4
LIVING
ROOM
/
DINING
102
P1:9
OFFICE/
CHECK-IN
F8 101
EXIST. MECH.
ROOM
(UNDER
STAIRS)
105
F6
TO 1ST
FLOOR
F4
F4
F5
F4
F4
203
P PHOTOCELL
F3
F2
F1
F4A
F4
F4
F4
EF-3
EXIST. SKYLIGHT
BATHROOM
202
P1:13
F4
F4
F4
F4
F2
F3
F4A
3
F1
P1:11
BATHROOM
EF-1
106
F4
STAIRWELL
219
F8
3
F2
F3
EF-5
BEDROOM
#1
107
F4
F4
BATHROOM
218
BEDROOM
#4
(ADA)
118
F1
CORRIDOR
200
F4
F1
F4
F4
CLOSET/
LAUNDRY
207
F2
LIVING
ROOM/
BEDROOM
217
CLOSET
F1
EF-4
F4
F4A
CLOSET/
LAUNDRY
208
F4
BATHROOM
209
F4
OF LOU I S I
TE
AN
A
T
F4
CLOSET
117
F4
F4
F5
F1
F4
F4
F4
F3
F8
EXIST. MECH.
ROOM
114
KITCHEN/
DINING
212
F2
F5
F5
EXIST.
MECH.
CLOSET
214
3
F4
F4
F5
F4
EXIST.
MECH.
CLOSET
213
P
E
1 E
KEYED NOTES:
1
EXISTING FLOOD LIGHTS TO BE RELAMPED BY ELECTRICAL CONTRACTOR.
2
EXISTING METAL HALIDE WALL MOUNT FIXTURE TO BE RELAMPED BY ELECTRICAL CONTRACTOR.
3
EXISTING CIRCUIT FOR SIGN MOUNTED LIGHT - UTILIZE CIRCUIT AND FEED FROM PANEL AS INDICATED.
PROVIDE PHOTOCELL AT LIGHT FIXTURE.
E
E
1
GENERAL SHEET NOTES:
1. DASHED OBJECTS OR OBJECTS MARKED WITH AN "E" ARE EXISTING.
2. ALL REUSED LIGHTING SWITCH LOCATIONS ARE TO BE REPLACED WITH NEW SWITCHES AND DEVICE PLATES.
3. LUMINAIRE SWITCHING AND LAYOUT HAVE BEEN SHOWN ON THESE PLANS. DO NOT LOAD LIGHTING CIRCUITS
MORE THAN 80% OF THEIR CAPACITY.
4. EXIT SIGNS AND EMERGENCY LIGHTS ARE TO BE FED FROM THE NEAREST 20A LIGHTING CIRCUIT AHEAD OF ANY
SWITCHES.
5. RECESSED FIXTURES IN FIRE RATED CEILINGS AND RETURN AIR PLENUMS SHALL BE RATED FOR THE FIRE RATING
OF THE CEILING OR SHALL BE FULLY ENCLOSED IN A FIRE RATED HOUSING ACCEPTABLE TO AUTHORITY HAVING
JURISDICTION.
6. FEED SMOKE DETECTORS FROM NEAREST UNSWITCHED 120V GENERAL LIGHTING CIRCUIT. DETECTORS WITHIN
A SINGLE UNIT ARE TO BE CONNECTED TOGETHER SO THAT A DETECTION AT ONE DEVICE ACTIVATES THE OTHER.
EE
2014/10/02
3
LAUNDRY
ROOM
113
CLOSET/
LAUNDRY
215
L E NG I N
F4
F4
F5
I CA
F4
F4
F4
PROFESSINAL ENGINEER
IN
TR
LIVING
ROOM/
BEDROOM
211
F2
F4
F4A
BLAKE MICHAEL HOSLI
License No. 38688
F4
F1
EF-2
F4
F3
F4
F4
KITCHEN/
DINING
216
BATHROOM
(ADA)
111
F4
EC
F4
BEDROOM
#3
115
CLOSET
210
EL
F1
CLOSET
116
F4
F2
CITY OF KENNER - CONVERSION OF
ANNE WASHINGTON COMMUNITY CENTER
CORRIDOR
112
A
S
F4
BEDROOM
#2
110
2011 by Linfield, Hunter & Junius, Inc.
BEDROOM
205
F4A
F4
F4 109
F4
CLOSET
206
F2
F1
F4
3
KITCHEN
119
CLOSET
108
LIVING
ROOM
201
F4
F4
FILE: P:\LinfieldHunter&Junius\14-098_CommunityResourceCenter\Design Documents\Drawings\Electrical\E-201 LIGHTING & FIRE ALARM.dwg
F5
IN
G
F2
R
CLOSET
103
F4
3608 18th Street, Suite 200
Metairie, Louisiana 70002
F6
APPROVED BY
RELAMP
EXISTING
FIXTURE
E
CHECKED BY
1
PROJ. NO.
12-23
DATE
10/02/2014
SHEET NO.
OF
SHEETS
DRAWN BY
ENTRANCE
CORRIDOR
100
1
MECH. ROOM
204
THIS SHEET
6:14 PM
TIME:
E
3
3
3
2
2
PROFESSIONAL ENGINEERS, ARCHITECTS
AND SURVEYORS
3
EXIST. MECH.
ROOM
104
LINFIELD, HUNTER & JUNIUS, INC.
F7
GFI/AC
J UC
R
DC
KITCHEN/
DINING
LIVING
ROOM
/
DINING
102
4
R
GFI/AC
2
GFI/AC
GFI/AC GFI/AC
R
R
R
MD
P1:6
STAIRWELL
219
P1:12/14 P1:4
3#8,#10G
3/4"C
R
KITCHEN 4
119
R
INTERIOR
SECURITY
SIREN
BEDROOM
205
14-50R
BATHROOM
218
WC
WC
WC
WC
R
P1:36/38
3#10,#10G
3/4"C
LIVING
ROOM/
BEDROOM
217
R
CLOSET
109
R
R
CLOSET
116
R
R
R
P1:39/41
3#6,#8G
1"C
LAUNDRY
ROOM
P1:20/22
113
P1:35/37
2#8,#10G
3/4"C
P1:43/45
3#10,#10G
3/4"C
60A 30A
P1:24/26
3#10,#10G
3/4"C
48"AFF
GFI
14-30R
3#10,#10G
3/4"C
P1:18
GFI/AC
N3R 1
20A 20A
30AF 30AF
WP/GFI
GFI
DC
1
P1:31/33
2#8,#10G
3/4"C
CU-3
EXIST. MECH.
ROOM
114
AHU-1
P1:58
2#10,#10G
3/4"C
1
SINGLE CIRCUIT WIREWAY FEEDING BOTH DISCONNECTS.
2
EXISTING ACTIVE CAMERAS AT BUILDING EXTERIOR AND NEW MONITOR LOCATION. COORDINATE WITH
TENANT TO RELOCATE CAMERA EQUIPMENT AND FEEDS TO CHECK-IN OFFICE 101 AND KEEP ACTIVE. CLEAN
AND SERVICE CAMERAS TO ENSURE PROPER WORKING ORDER PRIOR TO PROJECT COMPLETION.
3
ALL COMMUNICATIONS LINES HOMERUN TO THIS LOCATION. TERMINATE ALL LINES ONTO
COMMUNICATIONS BACKBORAD AND COORDINATE ENTIRE INSTALL WITH SERVICE PROVIDER. COORDINATE
WITH TENANT'S IT DIRECTOR FOR ANY ADDITIONAL REQUIREMENTS TO THIS ROOM AND INCLUDE IN THE
BASE BID.
5
RECEPTACLE FOR ABOVE STOVE MICROWAVE HOOD. COORDINATE FINAL RECEPTACLE LOCATION IN THE
FIELD WITH THE GENERAL CONTRACTOR AND MICROWAVE HOOD INSTALLATION REQUIREMENTS.
I CA
L E NG I N
P1:46
GFI
P1:48/50
3#10,#10G
3/4"C
14-30R
GFI/AC
P1:1/3
3#8,#10G
3/4"C
KITCHEN/
DINING
212
P1:64
EXIST.
MECH. AHU-4
CLOSET
214
60A
14-50R
4
P1:66
DC
P1:55/57
3#8,#10G
3/4"C
EXIST.
MECH.
CLOSET
213
AHU-3
60A
48"AFF
UC
J
EE
2014/10/02
GFI/AC
P1:51/53
3#8,#10G
3/4"C
CU-1
KEYED NOTES:
4
TR
GFI/AC
48"AFF
PROFESSINAL ENGINEER
IN
P1:5
P1:56
CLOSET/
LAUNDRY
215
N3R
20A 25A
30AF 30AF
CU-2
J UC
GFI/AC
P1:62
14-50R
P1:52/54
3#8,#10G
3/4"C
4
GFI
BATHROOM
(ADA)
111
KITCHEN/
DINING
216
48"AFF
P1:60
LIVING
ROOM/
BEDROOM
211
EC
R
OF LOU I S I
TE
AN
A
T
BLAKE MICHAEL HOSLI
License No. 38688
EL
R
GFI/AC
P1:16
P1:40/42
3#10,#10G
3/4"C
R
R
CLOSET/
LAUNDRY
208
WC
R
WC
R
48"AFF
GFI
14-30R
GFI
48"AFF
CLOSET/
LAUNDRY
207
A
WC
CLOSET
117
BEDROOM
#3
115
GFI/AC
CLOSET
210
WC
BEDROOM
#2
110
P1:34
BATHROOM
209
R
CORRIDOR
112
2011 by Linfield, Hunter & Junius, Inc.
CORRIDOR
200
R
R
CLOSET
206
GFI/AC
BEDROOM
#4
(ADA)
118
R
FILE: P:\LinfieldHunter&Junius\14-098_CommunityResourceCenter\Design Documents\Drawings\Electrical\E-301 POWER & COMMUNICATION.dwg
GFI/AC 48"AFF
IN
G
GFI/AC
BEDROOM
#1
107
UC
J
S
R
R
P1:10
LIVING
ROOM
201
P1:44
GENERAL SHEET NOTES:
1. DASHED OBJECTS OR OBJECTS MARKED WITH AN "E" ARE EXISTING.
2. OBJECTS INDICATED WITH A "R" ARE TO BE RELOCATED FROM CURRENT NEARBY LOCATION.
3. ALL POWER AND COMMUNICATION DEVICES AND PLATES - EVEN IF SHOWN IN EXISTING LOCATIONS - ARE TO BE
REPLACED WITH NEW PLATES AND DEVICES.
4. RECEPTACLES WITH HOMERUNS SHOWN ARE TO BE FED FROM NEW CIRCUITS FROM THE PANEL WITH THE
INDICATED BREAKER AND WIRE.
5. ALL RECEPTACLES TO REMAIN ARE TO BE REPLACED WITH NEW RECEPTACLES AND PLATES.
6. MATCH RECEPTACLE CONFIGURATION FOR SPECIALTY RECEPTACLES WITH EQUIPMENT INTENDED TO BE
CONNECTED.
APPROVED BY
P1:8
WC
WC
BATHROOM
106
EWH-1
CU-4
P1:32
R
100A P1:27/29
NF
2#3,#8G
1 1/4"C
EXTERIOR
SECURITY
SIREN
48'AFF
BATHROOM
202
EXIST. SKYLIGHT
GFI/AC
CLOSET
108
P1:23/25
3#8,#10G
3/4"C
P1:30
CHECKED BY
5
203
PROJ. NO.
12-23
DATE
10/02/2014
SHEET NO.
SECURITY PANEL LOCATION.
OF
SHEETS
DRAWN BY
KEY
3608 18th Street, Suite 200
Metairie, Louisiana 70002
P1:47/49
3#8,#10G
3/4"C
NEW
PANEL P1
OFFICE/
CHECK-IN
101
WC
THIS SHEET
TIME:
DC
DATE: 10/1/2014
WC
P1:28
GFI/AC
2
WC
EXIST. MECH.
ROOM
(UNDER
STAIRS)
105
60A
2
EXTERIOR
SECURITY
SIREN
MECH. ROOM
204
AHU-2
WC
ENTRANCE
CORRIDOR
(BELOW)
CLOSET
103
P1:2
NEW METER
AND SE
RATED FUSED
DISCONNECT
CITY OF KENNER - CONVERSION OF
ANNE WASHINGTON COMMUNITY CENTER
ENTRANCE
CORRIDOR
100
M
PROFESSIONAL ENGINEERS, ARCHITECTS
AND SURVEYORS
COMM
BACKBOARD
3
KEY
6:16 PM
WC
LINFIELD, HUNTER & JUNIUS, INC.
EXIST. MECH.
ROOM
104
RETURN AIR GRILLE AND AIR
QUANTITY. (24x24 FACE)
SQUARE THROAT ELBOWS WITH
TURNING VANES
EXHAUST GRILLE AND AIR QUANTITY.
(24x24 FACE)
RADIUS ELBOW
LAMINAR FLOW SUPPLY DIFFUSER
AND AIR QUANTITY. (24x24 FACE)
TRANSITION
DATE: 10/1/2014
LINEAR DIFFUSER AND AIR
QUANTITY. (24x24 FACE)
SUPPLY, RETURN AND EXHAUST
GRILLE (12x12 FACE)
OR
EXHAUST DUCT DOWN
BRANCH DUCT CONNECTION,
STRAIGHT TEE AND ROUND TRUNK.
BRANCH DUCT CONNECTION,
CONICAL TEE AND ROUND TRUNK.
OR
EXHAUST DUCT UP
RHC-XX
RETURN DUCT DOWN
REHEAT COIL WITH IDENTIFICATION
RETURN DUCT UP
SUPPLY DUCT DOWN
B
FLEXIBLE DUCT
BD
B0D
BOP
BTUH
G
H
BACKDRAFT DAMPER
BOTTOM OF DUCT
BOTTOM OF PIPE
BRITISH THERMAL UNIT PER
HOUR (BTU/H)
SUPPLY DUCT UP
RETURN AIR DUCT WITH SOUND
BOOT
RECESSED FIRE HOSE
CABINET
SURFACED MOUNTED FIRE
HOSE CABINET
FHC
FHC
DG
FD
FD
SD
SD
DUCT-MOUNTED FIRE DAMPER
C
DUCT-MOUNTED SMOKE DAMPER
DOOR GRILLE
FSD
FSD
DUCT-MOUNTED FIRE/SMOKE DAMPER
UNDERCUT AT DOOR
EXISTING EQUIPMENT TO REMAIN
FILE: P:\LinfieldHunter&Junius\14-098_CommunityResourceCenter\Design Documents\Drawings\Mechanical\M-000 MECHANICAL LEGEND.dwg
SD
NAME
NEW EQUIPMENT WITH
IDENTIFICATION
CV-#
TERMINAL BOX WITH IDENTIFICATION
NUMBER, CONSTANT AIR VOLUME,
AIRFLOW SETTINGS.
TERMINAL BOX WITH
IDENTIFICATION ASSOCIATED
AHU, ASSOCIATED ROOM #,
TOTAL AIRFLOW SETTINGS.
TERMINAL BOX WITH
IDENTIFICATION NUMBER,
VARIABLE AIR VOLUME, MINIMUM
AND MAXIMUM AIRFLOW SETTINGS.
VAV-AHU
VAV-#
TERMINAL BOX WITH IDENTIFICATION
NUMBER, VARIABLE AIR VOLUME,
COOLING ONLY, MINIMUM AND
MAXIMUM AIRFLOW SETTINGS.
VAV-CC-#
TERMINAL BOX WITH IDENTIFICATION
NUMBER, CONSTANT AIR VOLUME,
COOLING ONLY, AIRFLOW SETTINGS.
CV-CC-#
SD
T
X
DUCT-MOUNTED SMOKE DETECTOR
THERMOSTAT & SYSTEM DESIGNATION
H
HUMIDISTAT
TS
TEMPERATURE SENSOR
HS
RELATIVE HUMIDITY SENSOR
CHS
CHILLED WATER SUPPLY
CHR
CHILLED WATER RETURN
HWS
HOT WATER SUPPLY
HWR
HOT WATER RETURN
CWS
CONDENSER WATER SUPPLY
CWR
CONDENSER WATER RETURN
SRV-#
FOS
FUEL OIL SUPPLY
FOR
FUEL OIL RETURN
EXHAUST AIR ROOF VENT OR FAN
ERV-#
LOUVERED ROOF VENT
SPIN-IN VOLUME DAMPER
M
M
MVD
MOTORIZED DAMPER
RS
REFRIGERANT SUCTION
RL
REFRIGERANT LIQUID
RD
REFRIGERANT DISCHARGE
RHG
REFRIGERANT HOT GAS BYPASS
LPC
LOW PRESSURE CONDENSATE
PCR
PUMPED CONDENSATE RETURN
PUMP
MVD
MANUAL VOLUME DAMPER
ELBOW UP
24x12
24x12
RIGID DUCTWORK AND SIZE.
DIMENSIONS ARE INSIDE CLEAR
COMPRESSED AIR
CENTERLINE
COMBUSTION AIR
CAPACITY
CATCH BASIN
COOLING COIL
CEILING DIFFUSER
CONDENSATE DRAIN
CAP FOR FUTURE
CUBIC FEET PER HOUR
CUBIC FEET PER MINUTE
CHILLER
CHILLED WATER SUPPLY
CHILLED WATER RETURN
CAST IRON
CONDENSER
CONDENSING
CONTINUED/CONTINUOUS
CIRCULATING PUMP
COOLING TOWER
COOLING TOWER RETURN
COOLING TOWER SUPPLY
CUBIC
CONTROL VALVE
DB
DDC
DIA
DIFF
DIM
DMPR
DOAS
DRY BULB TEMP (DEG F)
DIRECT DIGITAL CONTROL
DIAMETER
DIFFUSER
DIMENSION
DAMPER
DEDICATED OUTSIDE AIR
SYSTEM
DOWN
DIFFERENTIAL PRESSURE
CONTROL DAMPER
DIFFERENTIAL PRESSURE
SWITCH
DRAWING
DRYER EXHAUST
DN
DP
DPR
DPS
DWG
DX
STEAM
STEAM CONDENSATE
SUPPLY AIR ROOF VENT OR FAN
D
C/A
C/L
CA
CAP
CB
CC
CD
CD
CFF
CFH
CFM
CH
CHR
CHS
CI
CND
COND
CONT
CP
CT
CTR
CTS
CU
CV
E
E/A
ECO
EER
EF
EFF
EJ
ELEC
ELEV
EMER
EMR
ENT
EOM
ERD
ERV
ESP
ET
EVAP
EWC
EWH
EX
EXH
EXT
EXHAUST AIR
EXTERIOR CLEANOUT
ENERGY EFFICIENCY RATIO
EXHAUST FAN
EFFICIENCY
EXPANSION JOINT
ELECTRICAL
ELEVATION
EMERGENCY
ELEVATOR MACHINE ROOM
ENTERING
END OF MAIN DRIP
EMERGENCY ROOF DRAIN
ENERGY RECOVERY
VENTILATOR
EXTERNAL STATIC PRESSURE
EXPANSION TANK
EVAPORATOR
ELECTRIC WATER COOLER
ELECTRIC WATER HEATER
EXTERIOR
EXHAUST
EXTERNAL
I
GA
GALV
GND
GPM
GPH
GV
GAUGE (GAGE)
GALVANIZED
GROUND
GALLONS PER MINUTE
GALLONS PER HOUR
GATE VALVE
N
NIC
NK
N/O
NOM
NTS
O O&M
O/A
OC
OD
OS&Y
OXY
OZ
P
HB
HC
HD
HEPA
HOSE BIBB
HEATING COIL
HEAD
HIGH EFFICIENCY PARTICULATE
AIR
HHC
HEATING COIL (HOT WATER)
HOA
HAND-OFF-AUTO
HORIZ HORIZONTAL
HPS
HIGH PRESSURE STEAM
HTR
HEATER
HP
HORSEPOWER
HWB HOT WATER BOILER
HWH HOT WATER HEATER
HWR HEATING WATER RETURN
HWS HEATING WATER SUPPLY
HX
HEAT EXCHANGER
IAQ
IAW
IBC
IBO
ID
IN
INV
IRI
INDOOR AIR QUALITY
IN ACCORDANCE WITH
INSTALLED BY CONTRACTOR
INSTALLED BY OWNER
INSIDE DIAMETER
INCHES
INVERT
INDUSTRIAL RISK INSURERS
K
KW
KX
KILOWATT
KITCHEN EXHAUST
L
LB
LF
LPG
LPS
LRA
LVG
POUND
LINEAR FEET
LIQUID PETROLEUM GAS
LOW PRESSURE STEAM
LOCKED ROTOR AMPS
LEAVING
M MAX
MB
MCA
MCC
MD
MECH
MEP
MER
MERV
MFR
MIN
MPS
MVD-1
MVD-2
MVD-3
MAXIMUM
MOP BASIN
MAXIMUM CURRENT AMPS
MOTOR CONTROL CENTER
MOTORIZED DAMPER
MECHANICAL
MECHANICAL, ELECTRICAL,
PLUMBING
MECHANICAL ROOM
MINIMUM EFFICIENCY
REPORTING VALUE
MANUFACTURER
MINIMUM
MEDIUM PRESSURE STEAM
MANUAL VOLUME DAMPER
(STANDARD LEAKAGE TYPE)
MANUAL VOLUME DAMPER
(LOW LEAKAGE TYPE)
MANUAL VOLUME DAMPER
(HIGH PERFORMANCE TYPE)
N
NATL
N/C
NC
NFPA
R
S
NITROGEN
NATURAL
NORMALLY CLOSED
NOISE CRITERIA
NATIONAL FIRE PROTECTION
ASSOCIATION
NOT IN CONTRACT
NECK
NORMALLY OPEN
NOMINAL
NOT TO SCALE
OPERATION AND MAINTENANCE
OUTSIDE AIR
ON CENTER
OUTSIDE DIAMETER
OUTSIDE STEM & YOKE
OXYGEN
OUNCES (PRESSURE)
P
PC
PCHR
PUMP
PUMPED CONDENSATE
PRIMARY CHILLED WATER
RETURN
PCHS PRIMARY CHILLED WATER
SUPPLY
PD
PRESSURE DROP
PHWR PRIMARY HOT WATER RETURN
PHWS PRIMARY HOT WATER SUPPLY
PRESS PRESSURE
PROP PROPELLER
PRV
PRESSURE REDUCING VALVE
PSI
POUNDS PER SQUARE INCH
PTAC PACKAGED TERMINAL A/C
PVC
POLYVINYL CHLORIDE
R
RELIEF
R/A
RETURN AIR
RECIRC RECIRCULATE
REF
REFERENCE
RH
RELATIVE HUMIDITY
RND
ROUND
RO
REVERSE OSMOSIS
RPM
REVOLUTIONS PER MINUTE
RTD
RESISTANCE TEMPERATURE
DETECTOR
RTU
ROOFTOP UNIT
S/A
SD
SEER
SF
SHR
SHT
SP
SPEC
STD
SYS
SUPPLY AIR
SMOKE DAMPER
SEASONAL ENERGY EFFICIENCY
RATIO
SUPPLY AIR FAN
SENSIBLE HEAT RATIO
SHEET
STATIC PRESSURE
SPECIFICATION
STANDARD
SYSTEM
T
U
V
TAB
T&P
TD
TEMP
TK
TOD
TOP
TP
TSTAT
TX
TXF
TYP
TESTING AND BALANCING
TEMPERATURE AND PRESSURE
TEMPERATURE DIFFERENCE
TEMPERATURE
TANK
TOP OF DUCT
TOP OF PIPE
TOTAL PRESSURE
THERMOSTAT
TOILET EXHAUST
TOILET EXHAUST FAN
TYPICAL
UG
UH
UL
UR
UNDERGROUND
UNIT HEATER
UNDERWRITERS LISTED
URINAL
V
VAC
VAV
VD
VEL
VENT
VERT
VFD
VI
VOJ
VENT
VACUUM VENTILATION
VARIABLE AIR VOLUME
VOLUME DAMPER
VELOCITY
VENTILATION
VERTICAL
VARIABLE FREQUENCY DRIVE
VIBRATION ISOLATOR
VERIFY ON JOB
W/
W/O
W
WB
WC
WFM
WG
WMS
WPD
WITH
WITHOUT
WATER
WET BULB (DEG F)
WATER COLUMN
WATER FLOW METER
WATER GAUGE
WIRE MESH SCREEN
WATER PRESSURE DROP
ALL WORK SHALL COMPLY WITH THE LATEST STATE AND CITY CODES INCLUDING BUT NOT LIMITED TO THE FOLLOWING:
A.
B.
C.
D.
E.
F.
G.
H.
2.
INTERNATIONAL MECHANICAL CODE - 2012
INTERNATIONAL FUEL GAS CODE - 2012
INTERNATIONAL BUILDING CODE - 2012
ANSI/ASHRAE/IESNA 90.1 - 2007
THE CONTRACT DOCUMENTS
ALL REQUIREMENTS OF THE STATE FIRE MARSHAL
INSURING AGENCY
ALL REQUIREMENTS OF THE AUTHORITIES HAVING JURISDICTION.
PROVIDE ALL MATERIAL AND EQUIPMENT AND PERFORM ALL LABOR REQUIRED TO INSTALL COMPLETE AND OPERABLE MECHANICAL SYSTEMS AS INDICTED ON THE
DRAWINGS, AS SPECIFIED AND AS REQUIRED BY CODE.
3. DRAWINGS ARE SCHEMATIC IN NATURE AND SHALL NOT BE SCALED. THE CONTRACTOR IS RESPONSIBLE FOR COORDINATING EXACT ROUTING OF ALL SERVICES WITH
SITE CONDITIONS, EXISTING CONDITIONS AND WITH WORK OF ALL OTHER TRADES.
4.
CONTRACTOR SHALL VISIT THE SITE AND BECOME FAMILIAR WITH THE PROJECT SCOPE AND CONSTRAINTS, UTILITY CONNECTIONS, AND ALL BUILDING SERVICES, PRIOR
TO SUBMITTING BID.
5.
ALL THERMOSTATS, HUMIDISTATS, OCCUPANCY SENSORS, AND CARBON DIOXIDE SENSORS SHALL BE LOCATED ON THE NEAREST WALL TO LOCATION INDICATED.
LOCATIONS OF THERMOSTATS SHALL BE APPROVED BY THE ARCHITECT, WHERE POSSIBLE LOCATE ABOVE LIGHT SWITCH. UNLESS OTHERWISE SHOWN, LOCATE ALL
ROOM THERMOSTATS AND HUMIDISTATS 4'-0" (CENTERLINE) ABOVE THE FINISHED FLOOR.
6.
EQUIPMENT SHOWN ON THE PLANS AND ELEVATIONS ILLUSTRATE THE GENERAL ARRANGEMENT AND SPACE ALLOCATIONS. THE CONTRACTOR SHALL VERIFY THE SPACE
REQUIREMENTS FOR EACH SYSTEM COMPONENT USING MANUFACTURER'S CERTIFIED SHOP DRAWINGS AND MAKE THE NECESSARY ADJUSTMENTS IN EQUIPMENT
PLACEMENT AND CONNECTION IN ORDER TO ACCOMMODATE THE EXACT EQUIPMENT TO BE INSTALLED. CONTRACTOR SHALL LOCATE EQUIPMENT FOR READY AND
SAFE ACCESS FOR FUTURE MAINTENANCE AND REPAIRS.
7.
DETAILS ILLUSTRATED ON THE DRAWINGS SHALL BE APPLIED IN ALL CASES WHERE THE FEATURE OCCURS IN THE SYSTEM DESIGN.
8.
CONTRACTOR SHALL COORDINATE WITH ARCHITECT PRIOR TO CUTTING ANY OPENING IN THE STRUCTURE.
9.
COORDINATE ANY DEVICE REQUIRING AN ACCESS PANEL WITH THE ARCHITECT.
10. CONTRACTOR SHALL PROVIDE MINIMUM 6-INCH DEEP CONCRETE HOUSEKEEPING PADS BENEATH FLOOR-MOUNTED AIR HANDLING UNITS, BOILERS, PUMPS, WATER
HEATERS, AND GRADE-MOUNTED CONDENSING UNITS. PAD SHALL EXTEND MINIMUM 4-INCHES BEYOND EDGE OF EQUIPMENT ON ALL SIDES.
11. SUPPORTS, ANCHOR BOLTS, AND HANGERS FOR ALL EQUIPMENT SPECIFIED IN DIVISION 15 OR 23 SHALL CONFORM TO THE SPECIFICATIONS. MISCELLANEOUS STEEL
BRACING SUPPORTS AND REINFORCING STEEL NEEDED TO SUPPORT EQUIPMENT SPECIFIED IN DIVISION 15 OR 23 SHALL BE FURNISHED AS PART OF SCOPE OF WORK
OF DIVISION 15 OR 23.
12. ALL PENETRATIONS THROUGH RATED WALLS, FLOORS, AND PARTITIONS MUST BE INSTALLED AND FIRESAFED TO MEET UL FIRE RESISTANCE LISTING DETAILS FOR THE
PENETRATION.
13. SMOKE DETECTORS SHALL BE LOCATED AS INDICATED ON THE MECHANICAL PLANS AND IN CONFORMANCE WITH NFPA 90A-2009, NFPA 72 - 2010, INTERNATIONAL
MECHANICAL CODE-2009 AND ALL OTHER REQUIREMENTS OF THE AUTHORITIES HAVING JURISDICTION.
DUCTWORK:
14. UNLESS OTHERWISE NOTED, ALL DUCTWORK IS OVERHEAD, TIGHT TO THE UNDERSIDE OF THE STRUCTURE, WITH SPACE FOR INSULATION IF REQUIRED.
15. CERTAIN ITEMS SUCH AS RISES AND DROPS IN DUCTWORK, ACCESS DOORS, AND VOLUME DAMPERS ARE INDICATED ON THE CONTRACT DOCUMENTS FOR CLARITY
AND SHALL NOT BE INTERPRETED AS THE EXTENT OF THE REQUIREMENTS FOR THESE ITEMS.
16. CONTRACTOR SHALL VERIFY CLEARANCE REQUIREMENTS AND ROUTING OF DUCTWORK BEFORE FABRICATION BEGINS, AS DUCT RISES AND DROPS MAY BE NECESSARY
DUE TO FIELD CONDITIONS.
18. ALL SUPPLY AIR DUCTWORK SHALL BE PROVIDED WITH 1" THICKNESS, 3.0 LB/CU. FT. NOMINAL DENSITY, ELASTOMERIC FOAM DUCT LINING, UNLESS OTHERWISE
NOTED.
KENT A. POYSER
REG. No. 37788
REGISTERED
19. ALL DUCTWORK DIMENSIONS, AS SHOWN ON DRAWINGS, ARE INTERNAL CLEAR DIMENSIONS AND DUCT SIZE SHALL BE INCREASED TO COMPENSATE FOR DUCT LINING
THICKNESS.
IN
20. IF DUCTWORK CONFLICTS WITH PIPING, STEEL, LIGHT FIXTURES ETC. DUCTWORK SHALL BE SET UP AND DOWN.
21. SEALANT SHALL BE APPLIED TO LONGITUDINAL SEAMS IN THE SHOP DURING FABRICATION. FIELD APPLY SEALANT TO TRANSVERSE SEAMS AND CONNECTIONS TO
BRANCH WORK AND AIR OUTLETS.
22. RADIUS ELBOWS SHALL BE USED IN ALL DUCT OFFSETS (HORIZONTAL OR VERTICAL). MITERED ELBOWS WITHOUT TURNING VANES ARE NOT ACCEPTABLE.
23. PROVIDE ACCESS DOORS IN DUCTWORK FOR THE OPERATION, ADJUSTMENT, AND MAINTENANCE OF ALL FANS, DAMPERS, AND MECHANICAL EQUIPMENT. ACCESS IS
REQUIRED BELOW ALL DAMPERS AND ABOVE CEILING EQUIPMENT.
24. ALL EXISTING SUPPLY AND RETURN AIR DUCTWORK AND ASSOCIATED SOUND ATTENUATORS SHALL BE CLEANED THOROUGHLY.
25. PROVIDE VOLUME DAMPERS AT ALL DUCT BRANCHES, SPLITS, AND TAKE-OFFS. VOLUME DAMPERS IN BRANCH DUCTS SHALL BE LOCATED AS FAR AS POSSIBLE FORM
AIR OUTLET OR INLET TO REDUCE NOISE AND TURBULENCE. DO NOT INSTALL DAMPERS AT REGISTERS OR DIFFUSERS.
26. ALL VOLUME DAMPERS IN INACCESSIBLE CEILINGS SHALL BE CABLE OPERATED.
27. PROVIDE ALL SUPPLY AIR, RETURN AIR AND EXHAUST AIR DUCT ELBOWS WITH SINGLE THICKNESS TURNING VANES.
28. CEILING DIFFUSERS, REGISTERS AND GRILLES SHALL BE LOCATED AS SHOWN ON THE ARCHITECTURAL REFLECTED CEILING PLAN. DIFFUSERS, REGISTERS AND GRILLES
SHALL BE FURNISHED WITH MOUNTING FRAMES AND FEATURES IN ACCORDANCE WITH THE CEILING TYPE.
29. AIR INTAKES SHALL BE MINIMUM 10 FEET FROM ALL EXHAUST FAN OUTLETS AND PLUMBING VENTS THROUGH ROOF.
W
30. ALL TRANSFER DUCTS SHALL BE SIZED AT A MAXIMUM OF 500 FPM. PROVIDE 1" ACOUSTICAL LINING.
31. INSTALL SUPPLY DUCT MOUNTED SMOKE DETECTORS AT AIR HANDLING UNITS WITH A CAPACITY GREATER THAN 2000 CFM. DEVICES SHALL BE WIRED BY FIRE ALARM
CONTRACTOR.
PIPING:
32. PIPING CONNECTIONS TO AIR HANDLING UNIT COILS AND MAJOR EQUIPMENT SHALL BE FABRICATED WITH ISOLATION VALVES, FLANGES, AND/OR UNIONS POSITIONED
TO ALLOW REMOVAL AND SERVICE OF THE COMPONENT PARTS.
33. CONDENSATE DRAIN DISCHARGE LINE FROM AIR CONDITIONING UNITS SHALL CONNECT TO NEAREST FLOOR DRAIN.
34. WHENEVER REMOVING PIPING, DUCTWORK, ETC... REMOVE IT AND CAP IT OFF AT THE MAIN.
BRANCH PIPE CONNECTION
TEE-OUTLET DOWN
1.
17. FLEXIBLE DUCTWORK RUNS SHALL BE LIMITED TO 5'-0" AT THE END OF BRANCH DUCTWORK.
ELBOW DOWN
DUCT TEE WITH SPLITTER DAMPER
GENERAL:
35. ALL PIPING SYSTEMS SHALL BE ADEQUATELY SUPPORTED FROM "BUILDING" STRUCTURE AND BE PROVIDED WITH IDENTIFICATION LABELS EVERY 20 FEET.
ABBREVIATION LIST IS GENERAL IN NATURE, NOT ALL ABBREVIATIONS ARE NECESSARILY USED IN THIS PROJECT.
NOTES ARE GENERAL IN NATURE, NOT ALL NOTES ARE NECESSARILY USED IN THIS PROJECT.
TEE-OUTLET UP
OR
OR
BRANCH DUCT CONNECTION,
RECTANGULAR OR ROUND BRANCH
WITH MANUAL VOLUME DAMPER
AND RECTANGULAR TRUNK.
SPLITTER WITH SPLIT SIZES SHOWN
POINT OF CONNECTION, NEW
TO EXISTING
PIPE REDUCER
GATE VALVE
DUCT WITH INTERNAL LINER, DUCT
SIZE SHOWN ON PLANS ARE
INSIDE CLEAR DIMENSIONS
2011 by Linfield, Hunter & Junius, Inc.
FRESH AIR
FURNISHED BY CONTRACTOR
FURNISHED BY OWNER
FLEXIBLE CONNECTION
FAN COIL UNIT
FIRE DAMPER
FLOOR DRAIN
FINISHED FLOOR
FINISHED
FULL LOAD AMPS
FLEXIBLE
FLOOR
FACTORY MUTUAL
FINS PER INCH
FEET PER MINUTE
FIRE SMOKE DAMPER
FEET
FUTURE
FACE VELOCITY
3608 18th Street, Suite 200
Metairie, Louisiana 70002
TIME:
SPLITTER WITH SPLIT SIZES SHOWN
F/A
FBC
FBO
FC
FCU
FCW
FD
FF
FIN
FLA
FLEX
FLR
FM
FPI
FPM
FSD
FT
FUT
FV
APPROVED BY
1S100
RISE OR DROP IN ELEVATION
F
CHECKED BY
R/D
R/D
ABS
ABSOLUTE
A/C
AIR CONDITIONING UNIT
ACCU AIR COOLED CONDENSING
UNIT
ACH
AIR CHANGES PER HOUR
ACY
ACETYLENE
ADA
AMERICAN DISABILITIES ACT
AF
AIR FILTER
AFF
ABOVE FINISHED FLOOR
AFM
AIR FLOW METER
AHJ
AUTHORITIES HAVING
JURISDICTION
AHP
AIR HORSEPOWER
AHU
AIR HANDLING UNIT
AMB AMBIENT
AMP
AMPERE
ANSI AMERICAN NATIONAL
STANDARDS INSTITUTE
APD
AIR PRESSURE DROP
AO
AIR OUTLET
AS
AIR SEPARATOR
ASHRAE AMERICAN SOCIETY OF
HEATING, REFRIGERATING, AND
AIR CONDITIONING ENGINEERS
ASME AMERICAN SOCIETY OF
MECHANICAL ENGINEERS
AV
AIR VENT
AUTO AUTOMATIC
AVD
AUTOMATIC VOLUME DAMPER
PROJ. NO.
12-23
DATE
10/02/2014
SHEET NO.
POINT OF DEMOLITION
SYMBOL LIST IS GENERAL IN NATURE, NOT ALL SYMBOLS ARE NECESSARILY USED IN THIS PROJECT.
OF
SHEETS
DRAWN BY
DUCT ACCESS DOOR
A
THIS SHEET
AD
DESCRIPTION
PROFESSIONAL ENGINEERS, ARCHITECTS
AND SURVEYORS
SUPPLY DIFFUSER AND AIR
QUANTITY. (SHADED AREA
INDICATES NO THROW IN THIS
DIRECTION) (24x24 FACE)
SYMBOL
MECHANICAL GENERAL NOTES
LINFIELD, HUNTER & JUNIUS, INC.
DESCRIPTION
4:55 PM
SYMBOL
MECHANICAL ABBREVIATIONS
CITY OF KENNER - CONVERSION OF
ANNE WASHINGTON COMMUNITY CENTER
MECHANICAL LEGEND
ESP
MOTOR
VOLT/PH
AHU-1
1,060
0.5"
0.33 HP
208/1
30
9.6
2
AHU-2
600
0.5"
0.33 HP
208/1
24
7.7
AHU-3
550
0.5"
0.33 HP
208/1
30
AHU-4
600
0.5"
0.33 HP
208/1
24
MCA
MOCP
MANUFACTURER
MODEL
WEIGHT
REMARKS
240/1
53/25
60/25
TRANE
TEM3A0B30
140 LBS
1, 2
1
240/1
42
45
TRANE
TEM3A0B24
140 LBS
1
7.7
1
240/1
42
45
TRANE
TEM3A0B24
140 LBS
1
7.7
1
240/1
42
45
TRANE
TEM3A0B24
140 LBS
1
kW
STAGES
VOLTS/PH
REMARKS:
1. FURNISH WITH TOP DISCHARGE, BOTTOM RETURN, PLENUM STAND, AND 7-DAY PROGRAMMABLE THERMOSTAT.
2. TWO (2) ELECTRICAL CIRCUITS SHALL BE REQUIRED.
MARK
TONS OF
COOLING
REFRIGERANT
SEER
CU-1
2.5
R-410A
CU-2
1.5
CU-3
CU-4
COOLING
ELECTRICAL
MANUFACTURER
MODEL
WEIGHT
REMARKS
240/1
TRANE
4TTB3030
175 LBS
1
20
240/1
TRANE
4TTB3018
130 LBS
1
10.4
20
240/1
TRANE
4TTB3018
130 LBS
1
10.4
20
240/1
TRANE
4TTB3018
130 LBS
1
MCA
MOCP
VOLTS/PH
-
13.0
25
18.0 MBH
-
10.4
13.0
18.0 MBH
-
13.0
18.0 MBH
-
MIN CAPACITY
EVAP TEMP
13.0
30.0 MBH
R-410A
13.0
1.5
R-410A
1.5
R-410A
AMBIENT
REMARKS:
1. FURNISH WITH FIELD INSTALLED DRIER, FIELD INSTALLED SIGHT GLASS, SERVICE VALVES, SUCTION LINE ACCUMULATOR, HIGH PRESSURE SWITCH, START KIT, CYCLE PROTECTOR, AND THERMOSTATIC EXPANSION VALVE.
AIR FLOW
MIN
MAX
MAX APD IN
WG
SQUARE
-
125
0.100
CEILING SURFACE
12x12
S-2
LOUVERED FACE
-
130
0.100
WALL
10x8
T-1
LOUVERED FACE
-
130
0.100
WALL
R-1
LOUVERED FACE
-
1400
0.05
R-2
LOUVERED FACE
-
1400
0.05
MARK
TYPE
S-1
MOUNTING
FACE SIZE NECK SIZE
MAX NC
DAMPER
FINISH
MANUFACTURER
MODEL
REMARKS
20
OPD
-
TITUS
TMS-AA
1
8x6
20
OPD
-
TITUS
300FL
1
10x8
8x6
20
NONE
-
TITUS
301FL
1
CEILING
36 x 18
34 x 16
20
NONE
-
TITUS
350FL
1
CEILING
36 x 18
34 x 16
20
NONE
-
TITUS
350FL
1
REMARKS:
1. PROVIDE FULL RANGE OF MANUFACTURER'S COLORS FOR COLOR SELECTION BY ARCHITECT.
KENT A. POYSER
REG. No. 37788
LOUVER SCHEDULE
REGISTERED
MARK
SIZE
CFM
S.P. IN.
W.C.
MAX
VELOCITY
(FPM)
MINIMUM
FREE AREA
MANUFACTURER
MODEL
SERVES
REMARKS
L-1
24"W x 18"H
300
>0.10
500
1.07
GREENHECK
EHH-601
AHU-1
1, 2
L-2
24"W x 12"H
75
>0.10
500
0.53
GREENHECK
EHH-601
AHU-1
1, 2
L-3
24"W x 12"H
300
>0.10
500
0.53
GREENHECK
EHH-601
AHU-1
1, 2
L-4
24"W x 12"H
300
>0.10
500
0.53
GREENHECK
EHH-601
AHU-1
1, 2
IN
EXHAUST FAN SCHEDULE
MARK
CFM
S.P. IN.
W.C.
INLET
DB
VOLTS/
PH
HP/
WATTS
MANUFACTURER
MODEL
WEIGHT
REMARKS
EF-1
75
0.3
41
115/1
54W
GREENHECK
SP-B80
15 LBS
1
EF-2
75
0.3
41
115/1
54W
GREENHECK
SP-B80
15 LBS
1
EF-3
75
0.3
41
115/1
54W
GREENHECK
SP-B80
15 LBS
1
EF-4
75
0.3
41
115/1
54W
GREENHECK
SP-B80
15 LBS
1
EF-5
75
0.3
41
115/1
54W
GREENHECK
SP-B80
15 LBS
1
REMARKS:
1. FURNISH WITH DESIGNER GRILLE AND HOODED WALL CAP.
CHECKED BY
1. FURNISH WITH BIRD SCREEN AND OPPOSED BLADE DAMPER.
2. COORDINATE LOUVER COLOR WITH ARCHITECT.
APPROVED BY
REMARKS:
PROJ. NO.
12-23
DATE
10/02/2014
SHEET NO.
OF
SHEETS
DRAWN BY
FILE: P:\LinfieldHunter&Junius\14-098_CommunityResourceCenter\Design Documents\Drawings\Mechanical\M-001 MECHANICAL SCHEDULES.dwg
AIR DEVICE SCHEDULE
THIS SHEET
DATE: 10/1/2014
CONDENSING UNIT SCHEDULE (OUTDOOR UNIT)
2011 by Linfield, Hunter & Junius, Inc.
CFM
3608 18th Street, Suite 200
Metairie, Louisiana 70002
ELECTRIC HEAT
PROFESSIONAL ENGINEERS, ARCHITECTS
AND SURVEYORS
LINFIELD, HUNTER & JUNIUS, INC.
FAN
COOLING
TMBH
MARK
CITY OF KENNER - CONVERSION OF
ANNE WASHINGTON COMMUNITY CENTER
TIME:
4:54 PM
AIR HANDLING UNIT SCHEDULE (INDOOR UNIT)
S-1
75
S-2
75
EF-5
AHU-2
BATHROOM S-1
50
218
S-2
75
LIVING
ROOM/
BEDROOM
217
CONNECT OUTSIDE AIR LOUVER L-2 TO RETURN AIR PLENUM AT BASE OF
UNIT. BALANCE TO 100 CFM.
CONNECT OUTSIDE AIR LOUVER L-3 TO RETURN AIR PLENUM AT BASE OF
UNIT. BALANCE TO 100 CFM.
CONNECT OUTSIDE AIR LOUVER L-4 TO RETURN AIR PLENUM AT BASE OF
UNIT. BALANCE TO 100 CFM.
KENT A. POYSER
REG. No. 37788
REGISTERED
S-1
100
T-1
-
S-1
115
AHU-4
S-1
125
T
CONNECT RETURN AIR GRILLE TO RETURN AIR PLENUM AT BASE OF UNIT.
LINE RETURN AIR PLENUM WITH 1/2" ACOUSTICAL DUCT LINER.
PROVIDE 4" DRYER EXHAUST VENT THROUGH THE EXTERIOR WALL AND
AND FINISH WITH HOODED WALL CAP.
2011 by Linfield, Hunter & Junius, Inc.
BATHROOM
209
PLAN NOTES:
CONNECT OUTSIDE AIR LOUVER L-1 TO RETURN AIR PLENUM AT BASE OF
UNIT. BALANCE TO 250 CFM.
EF-4
BEDROOM #4
(ADA)
118
S-1
125
S-2
75
KITCHEN/
DINING
216
LIVING
ROOM/
BEDROOM
211
T
S-1
125
AHU-3
CORRIDOR
112
KITCHEN/
DINING
212
EF-2
BATHROOM
(ADA)
111
BEDROOM #3
115
S-1
75
S-1
50
S-1
125
R-2
-
S-1
115
T-1
-
BEDROOM #2
110
S-1
125
R-2
-
IN
LAUNDRY
ROOM
113
16x10 SA
AHU-3
AHU-1
AHU-4
L-4
R-1
-
L-1
L-3
CU-4
CU-3
CU-2
CU-1
APPROVED BY
THERMOSTATS SHALL BE MOUNTED AT 48" A.F.F. UNLESS OTHERWISE
NOTED.
S-1
115
CHECKED BY
8.
T-1
-
S-1
115
PROJ. NO.
12-23
DATE
10/02/2014
SHEET NO.
OF
SHEETS
DRAWN BY
SIZE AND ROUTE REFRIGERANT PIPING PER REQUIREMENTS AND
RECOMMENDATIONS BY EQUIPMENT MANUFACTURER.
T-1
-
S-1
75
S-1
50
S-1
75
KITCHEN
119
BEDROOM #1
107
S-1
75
CORRIDOR
200
S-1
50
THIS SHEET
7.
T
BEDROOM
205
8x6 SA
S-1
100
BATHROOM
106
CITY OF KENNER - CONVERSION OF
ANNE WASHINGTON COMMUNITY CENTER
ALL DIFFUSERS AND GRILLES SHALL BE FURNISHED WITH OPPOSED
BLADE DAMPERS.
S-1
75
EF-1
REFER TO THE ARCHITECTURAL REFLECTED CEILING PLANS FOR CEILING
GRID ROOM LAYOUTS AND COORDINATE ALL GRILLES, REGISTERS,
AND DIFFUSERS WITH CORRESPONDING REFLECTED CEILING PLANS.
6.
LIVING ROOM /
DINING
102
16x10 SA
5.
S-1
75
STAIRWELL
219
BECAUSE OF THE LIMITED SPACE AVAILABLE TO INSTALL ALL OF THE
MECHANICAL WORK, COORDINATION BETWEEN THE VARIOUS TRADES
IS OF THE UTMOST IMPORTANCE.
4. IF THE HEATING CONTRACTOR DOES NOT CLEARLY UNDERSTAND
THESE PLANS, OR IS NOT SURE OF THEIR MEANING, HE SHOULD
OBTAIN THE ENGINEER'S WRITTEN EXPLANATION AND INTERPRETATION,
PRIOR TO SUBMITTING HIS BID, SINCE THE HEATING CONTRACTOR
WILL BE HELD RIGIDLY TO THE INTERPRETATION OF THE ENGINEER.
LIVING
ROOM
201
S-1
75
16x10 SA
EF-3
OFFICE/
CHECK-IN
101
3608 18th Street, Suite 200
Metairie, Louisiana 70002
8x6 SA
8x6 SA
S-1
50
12x10 SA
3.
S-1
100
T
CONTRACTOR TO COORDINATE ALL DEMOLITION & NEW CONSTRUCTION
WITH THE PROJECT CONSTRUCTION MANAGER AND ALL OTHER TRADES
PER PROJECT AREA PHASING.
ALL ELBOWS, FITTINGS, ETC. IN PIPING AND DUCTWORK ARE NOT
NECESSARILY INDICATED TO CLEAR ALL EXISTING AND NEW JOB
OBSTRUCTIONS.
S-2
100
AHU-1
12x10 SA
2.
S-1
75
KITCHEN/
DINING
203
PROFESSIONAL ENGINEERS, ARCHITECTS
AND SURVEYORS
LINFIELD, HUNTER & JUNIUS, INC.
THE OWNER SHALL MAINTAIN ALL SALVAGE RIGHTS OF EQUIPMENT AND
MATERIALS REMOVED. ALL EQUIPMENT AND MATERIALS NOT CLAIMED
BY THE OWNER SHALL BE REMOVED FROM THE PREMISES BY THE
CONTRACTOR.
THESE PLANS ARE DIAGRAMMATIC IN NATURE SINCE THEY REFLECT
ONLY THE AVAILABLE INFORMATION OBTAINED FROM EXISTING PLANS,
SPECIFICATIONS, AND FIELD SURVEYS. THE EXACT LOCATION OF
EXISTING DUCTWORK, PIPING, AND EQUIPMENT MAY DEVIATE FROM
THE LOCATION INDICATED ON THESE DRAWINGS. THE CONTRACTOR
SHALL BE PREPARED TO MAKE SOME ALTERATIONS TO NEW AND/OR
EXISTING SERVICES TO FIT ACTUAL JOB CONDITIONS.
S-1
75
S-2
100
BATHROOM
202
1.
ENTRANCE
CORRIDOR
100
R-2
-
ALL EXISTING MECHANICAL ITEMS SHALL BE REMOVED, INCLUDING AIR
HANDLING UNITS, CONDENSING UNITS, CONTROLS, REFRIGERANT
PIPING, DUCTWORK, DIFFUSERS, AND ACCESSORIES.
GENERAL MECHANICAL NOTES:
FILE: P:\LinfieldHunter&Junius\14-098_CommunityResourceCenter\Design Documents\Drawings\Mechanical\M-201 MECHANICAL PLANS.dwg
12x10 SA
16x10 SA
5.
ENTRANCE
CORRIDOR
(BELOW)
IF THE HEATING CONTRACTOR DOES NOT CLEARLY UNDERSTAND THESE
PLANS, OR IS NOT SURE OF THEIR MEANING, HE SHOULD OBTAIN THE
ENGINEER'S WRITTEN EXPLANATION AND INTERPRETATION, PRIOR TO
SUBMITTING HIS BID, SINCE THE HEATING CONTRACTOR WILL BE HELD
RIGIDLY TO THE INTERPRETATION OF THE ENGINEER.
12x10 SA
DATE: 10/1/2014
4.
AHU-2
12x10 SA
3.
L-2
12x10 SA
2.
THESE PLANS ARE DIAGRAMMATIC IN NATURE SINCE THEY REFLECT
ONLY THE AVAILABLE INFORMATION OBTAINED FROM EXISTING PLANS,
SPECIFICATIONS, AND FIELD SURVEYS. THE EXACT LOCATION OF
EXISTING DUCTWORK, PIPING, AND EQUIPMENT MAY DEVIATE FROM
THE LOCATION INDICATED ON THESE DRAWINGS. THE CONTRACTOR
SHALL BE PREPARED TO MAKE SOME ALTERATIONS TO NEW AND/OR
EXISTING SERVICES TO FIT ACTUAL JOB CONDITIONS.
12x10 SA
1.
12x10 SA
TIME:
4:53 PM
GENERAL DEMOLITION NOTES:
*
L
W
**
SUPPORT FANS W/
METAL STRAPS FROM
STRUCTURE ABOVE
WALL CAP
USE THIS WITH
RECTANGULAR DUCT
USE THIS WITH ROUND
DUCT TAKEOFF'S
ENTRY FITTING: L= 1/4
W, (4" MIN.) (MAY ALSO
BE PARALLEL FLOW
FITTING)
EXH DUCT-SEE
PLANS FOR SIZE
**
EXTERIOR WALL
* = BRANCH TO INDIVIDUAL DIFFUSER OR GRILLE
4
SCALE: NTS
CEILING MOUNTED EXHAUST FAN DETAIL
SCALE: NTS
KENT A. POYSER
REG. No. 37788
REGISTERED
IN
SEE SPECIFIATIONS FOR
PIPING MATERIAL.
OPEN VENT
FIELD POWER SUPPLY CONN
FIELD CONTROL SUPPLY
CONN.
FULL CONN.
SIZE PIPE MIN.
1 1/4 "
X
ELEVATE A/C UNIT SUFFICIENT DISTANCE ABOVE
FLOOR OR ROOF TO ALLOW FOR INSTALLATION OF
TRAP WITH ADEQUATE DIMENSIONS TO WITHSTAND
SYSTEM OPERATING PRESSURE. COORDINATE WITH
DETAIL FOR A UNIT MOUNTING.
ELBOW
NOTES:
-FOLLOW MFR'S INSTRUCTIONS FOR
INSTALLATION OF SUPPLY DIFFUSER IN
CEILING
-SEE SPECIFICATIONS FOR DUCT
SUPPORTS, FABRICATION AND
INSTALLATION
BOTTOM
4" THICK MINIMUM
CONCRETE MOUNTING PAD
ELASTOMERIC ISOLATION
PADS, FOUR (4) PER
CONDENSING UNIT
3
CONDENSING UNIT MOUNTING DETAIL
6" MIN.
SCALE: NTS
COOLING COIL CONDENSATE DRAIN
SCALE: NTS
SHEET METAL SCREW
(TYPICAL)
PIPE SUPPORT, MAX. SPACING OF
PIPE SUPPORTS 4'-0"
TOTAL HEIGHT OF TRAP= X+H+ ( 1 1/2 x PIPE DIAMETER )
FOR DRAW THRU UNITS
FOR BLOW THRU UNITS
X= MIN. 1/2 H (PREFERRED X=H)
X= FAN STATIC PRESSURE +1"
H= NEGATIVE STATIC PRESSURE +1"
H= MIN. 1"
2
SPIN-IN FITTING WITH MANUAL
VOLUME DAMPER (NO
EXTRACTOR USED)
SECURING STRAP
PANDUIT (OR EQUAL)
SLOPE CONDENSATE PIPING
@1/8" PER FOOT TO ROOF DRAIN
TURN PIPE DOWN AT
NEAREST FLOOR DRAIN,
UNLESS SHOWN
OTHERWISE ON PLANS.
SUPPLY
DUCT
CEILING
1
SUPPLY DIFFUSER WITH
INSULATED BACK PANEL
DUCTWORK CONNECTION TO SUPPLY DIFFUSER (FLEX DUCT)
SCALE: NTS
CHECKED BY
TEE
H
PROJ. NO.
12-23
DATE
10/02/2014
SHEET NO.
OF
SHEETS
DRAWN BY
NOTE:
THIS SHEET
FLEXIBLE DUCT
MAXIMUM FLEXIBLE
DUCT LENGTH 6'-0"
APPROVED BY
UNION
TEE
CITY OF KENNER - CONVERSION OF
ANNE WASHINGTON COMMUNITY CENTER
3"
"TAP-OUT" EITHER SIDE OR BOTTOM OF
DUCT. TOP "TAP-OUT" IS NOT ACCEPTABLE
DRAIN PAN
CONNECTION
CLEAN-OUT
PLUG
TOTAL HEIGHT
FILE: P:\LinfieldHunter&Junius\14-098_CommunityResourceCenter\Design Documents\Drawings\Mechanical\M-301 MECHANICAL DETAILS.dwg
** = SUBMAIN, BRANCHMAIN , OR BRANCH.
LOW PRESSURE DUCT VOLUME DAMPER REQUIREMENTS
2011 by Linfield, Hunter & Junius, Inc.
CEILING ASSEMBLY
REFER TO ARCH DWGS
FOR TYPE
EXHAUST GRILLE, INTEGRAL WITH FAN
5
3608 18th Street, Suite 200
Metairie, Louisiana 70002
SPIN-IN FITTING WITH
MANUAL VOLUME
DAMPER
PROFESSIONAL ENGINEERS, ARCHITECTS
AND SURVEYORS
DATE: 10/1/2014
TYPICAL MANUAL
VOLUME DAMPER
LINFIELD, HUNTER & JUNIUS, INC.
4:51 PM
TIME:
MAIN SUPPLY RETURN
OR EXHAUST DUCT
F. MATERIAL EXPOSED WITHIN DUCTS OR PLENUMS SHALL HAVE A FLAME-SPREAD INDEX OF NOT MORE THAN 25 AND A
SMOKE-DEVELOPED RATING OF NOT MORE THAN 50 IN ACCORDANCE WITH SECTION 102 (A), IMC (675 IAC 18-1).
G. DRAWINGS (PLANS, SCHEMATICS, AND DIAGRAMS) INDICATE GENERAL LOCATION AND ARRANGEMENT OF PIPING,
DUCTWORK, AND EQUIPMENT. THE LOCATIONS AND ARRANGEMENT TAKE INTO CONSIDERATION PIPE SIZING AND
FRICTION LOSS, EXPANSION, PUMP SIZING, AND OTHER DESIGN PARAMETERS. CLEARANCES ABOVE CEILINGS IN
CERTAIN AREAS ARE LIMITED AND NECESSITATE DUCTWORK AND/OR PIPING ROUTINGS. WHERE POSSIBLE, PIPING,
DUCTWORK, AND EQUIPMENT SHALL BE INSTALLED AS INDICATED. CHANGES REQUIRED TO MEET ARCHITECTURAL AND
STRUCTURAL CONDITIONS ARE TO BE APPROVED BY THE ENGINEER. NEW PIPING, DUCTWORK, ETC. SHALL BE
SUPPORTED FROM THE BUILDING STRUCTURE ONLY, AND NOT FROM ANY NEW OR EXISTING EQUIPMENT, DUCTWORK,
ETC.
A. THE MECHANICAL CONTRACTOR SHALL FURNISH AND INSTALL NEW AIR HANDLING UNITS AS SHOWN AND DETAILED ON
THE DRAWINGS. THE NEW AIR HANDLING UNITS SHALL BE AS MANUFACTURED BY THE TRANE COMPANY, YORK
INTERNATIONAL, OR CARRIER CORPORATION.
B. ALL SHEET METAL DUCTWORK SHALL BE G-90 COATED GALVANIZED STEEL CONFORMING TO ASTM A653 AND A924
STANDARDS OF GAUGE AND REINFORCEMENT. DUCTWORK SHALL BE AIRTIGHT (5% LEAKAGE). FABRICATE ELBOWS
WITH CENTERLINE RADIUS EQUAL TO 1.5 TIMES THE DUCT WIDTH IN THE PLANE OF THE TURN UNLESS SPECIFICALLY
NOTED OTHERWISE; ALL ELBOWS SHALL BE FABRICATED WITH FACTORY MANUFACTURED TURNING VANES. LIMIT
C. DUCT DIMENSIONS ARE "FREE AREA" AND SHALL NOT BE REDUCED. ALL SUPPLY AIR RECTANGULAR, ROUND, AND OVAL
DUCT SHALL BE WRAPPED EXTERNALLY WITH 1-1/2" THICK FLEXIBLE FIBERGLASS INSULATION IN CONCEALED
LOCATIONS (IN CHASES AND ABOVE CEILINGS). ALL MIXED AIR DUCTWORK SHALL BE WRAPPED EXTERNALLY WITH
1-1/2" THICK FLEXIBLE FIBERGLASS INSULATION. RETURN DUCT AND EXHAUST DUCT NEED NOT BE INSULATED OR
LINED. USE 2" RIGID FIBER BOARD EXTERNAL INSULATION FOR ALL SUPPLY DUCTWORK LOCATED IN THE MECHANICAL
ROOMS AND FOR ALL OUTSIDE AIR INTAKE DUCTWORK.
D. MINERAL-FIBER BLANKET INSULATION SHALL BE SECURED WITH ADHESIVE AND ANCHOR PINS AND SPEED WASHERS ON
EACH SIDE AND BOTTOM OF HORIZONTAL DUCTS AND ALL SIDES OF VERTICAL DUCTS. INSTALL ANCHOR PINS AND
SPEED WASHERS SPACED 16" O.C. EACH WAY, AND 3" MAX. FROM INSULATION JOINTS. APPLY ADDITIONAL PINS AND
CLIPS TO HOLD INSULATION TIGHTLY AGAINST SURFACE AT CROSS BRACING. ANCHOR PINS MAY BE OMITTED FROM
TOP SURFACE OF HORIZONTAL, RECTANGULAR DUCTS AND PLENUMS.
E. MAXIMUM STRAIGHT LENGTH OF FLEX DUCT SHALL BE 6'-0".
F. FLEXIBLE DUCT SHALL NOT BE USED IN PLACE OF ELBOWS.
G. SUPPLY AIR DUCT TAKEOFFS SHALL NOT BE PLACED CLOSER THAN 12" FROM THE END OF A TRUNK OR LESS THAN 24"
DOWNSTREAM FROM AN ELBOW.
H. INSTALL INSULATION PRODUCTS ON SPECIFIED DUCTWORK, PIPING, AND EQUIPMENT IN ACCORDANCE WITH
MANUFACTURER'S WRITTEN INSTRUCTIONS AND IN ACCORDANCE WITH RECOGNIZED INDUSTRY PRACTICES TO ENSURE
THAT THE INSULATION SERVES ITS INTENDED PURPOSE.
1.2 WORK INCLUDED
A. THE MECHANICAL CONTRACTOR SHALL FURNISH ALL LABOR, MATERIAL, ACCESSORIES, TOOLS, ETC. TO COMPLETE
THE HEATING, VENTILATING AND AIR CONDITIONING WORK AS INDICATED AND SPECIFIED.
H. AIR DEVICES SHALL BE TYPE AND SIZE LISTED ON THE DRAWINGS, OR SIMILAR BY KRUEGER, PRICE, TUTTLE & BAILEY,
OR NAILOR, SUBJECT TO COMPLIANCE WITH REQUIREMENTS.
I. FLEXIBLE DUCT (AS NOTED ON DRAWINGS) SHALL BE RATED FOR LOW VELOCITY (1+ IN. W.G.). CONTRACTOR SHALL
INSTALL FLEXDUCT PER MANUFACTURER'S RECOMMENDATIONS. MAXIMUM LENGTH SHALL NOT EXCEED 6'-0" WHERE
SUPPLYING AN AIR DEVICE.
2.2 IDENTIFICATION
FILE: P:\LinfieldHunter&Junius\14-098_CommunityResourceCenter\Design Documents\Drawings\Mechanical\M-401 MECHANICAL SPECIFICATIONS.dwg
B. MECHANICAL WORK SHALL INCLUDE IN GENERAL TERMS, BUT NOT LIMITED TO THE FOLLOWING:
1. DEMOLITION OF ALL EXISTING MECHANICAL SYSTEMS, INCLUDING (BUT NOT LIMITED TO) ALL AIR HANDLING UNITS,
CONDENSING UNITS, DUCTWORK, PIPING, CONTROLS, AND ACCESSORIES.
2. INSTALLATION OF NEW MECHANICAL SYSTEMS AS SHOWN ON THE DOCUMENTS.
1.3 SHOP DRAWINGS
A. SUBMIT ONE ELECTRONIC COPY ON ALL EQUIPMENT FURNISHED UNDER THIS CONTRACT, INCLUDING AIR DISTRIBUTION
DEVICES, AUTOMATIC FLOW CONTROL VALVES, MANUAL VOLUME DAMPERS AND MANUAL CIRCUIT SETTERS.
B. ANY PRODUCT MANUFACTURER LISTED ON THE DRAWINGS OR IN THE PROJECT MANUAL AS A PRE-APPROVED EQUAL
MUST BE SUBMITTED TO ENGINEER FOR APPROVAL NOT LESS THAN SEVEN DAYS PRIOR TO BID DATE.
C. THE CONTRACTOR SHALL SUPPLY THREE COPIES OF OPERATIONS AND MAINTENANCE MANUALS (O&M), AND ONE COPY
OF AS-BUILT DRAWINGS WHEN THE JOB IS COMPLETED. O&M MANUALS SHALL INCLUDE EQUIPMENT CUTS AND
WIRING DIAGRAMS.
1.4 CUTTING AND PATCHING
A. THIS CONTRACTOR SHALL CUT AND PATCH ALL HOLES IN THE INTERIOR PARTITIONS AND CEILINGS AS REQUIRED FOR
THE INSTALLATION OF HIS WORK. G.C. SHALL BE RESPONSIBLE FOR CUTTING NEW OPENINGS IN OUTSIDE WALLS,
FLOORS, AND FOR PATCHING ALL OPENINGS RESULTED BY MECHANICAL SCOPE OF WORK, EXCEPT PATCHING FIRE
RATED PENETRATIONS. PATCHING SHALL MATCH EXISTING AREAS AND SHALL BE DONE BY WORKMEN SKILLED IN THE
APPROPRIATE TRADE.
A. ALL EQUIPMENT SHALL HAVE ENGRAVED, PLASTIC NAMEPLATES. PLASTIC NAMEPLATES SHALL BE BLUE IN COLOR, WITH
WHITE LETTERING A MINIMUM OF 3/4" IN HEIGHT. NAMEPLATE SHALL IDENTIFY EQUIPMENT NAME AND NUMBER. (FOR
EXAMPLE; "AIR HANDLING UNIT "5-AHU-2C")
2.3 REFRIGERANT PIPING
A. INSTALL HANGERS, SUPPORTS, CLAMPS AND ATTACHMENTS TO SUPPORT PIPING PROPERLY FROM BUILDING
STRUCTURE; COMPLY WITH MSS SP-69. ARRANGE FOR GROUPING OF PARALLEL RUNS OF HORIZONTAL PIPING TO BE
SUPPORTED TOGETHER ON TRAPEZE HANGERS WHERE POSSIBLE. ALL PIPING HANGER AND SUPPORTS SHALL BE UL
OR FM APPROVED.
B. ALL PIPING SUPPORTS OR STRAPS SHALL HAVE A THERMAL SHIELD TO PREVENT CONDENSATION.
I. WHEN BRAZING OR SOLDERING, REMOVE SOLENOID-VALVE COILS AND SIGHT GLASSES, VALVE STEMS, SEATS, AND
PACKING, AND ACCESSIBLE INTERNAL PARTS OF REFRIGERANT SPECIALTIES. DO NOT APPLY HEAT NEAR
EXPANSION-VALVE BULB. CLEAN ALL JOINTS BEFORE BRAZING. ALL BRAZING OPERATIONS SHALL BE PERFORMED
USING DRY NITROGEN DRIFT PROCEDURE TO PREVENT EXCESS OXIDATION.
B. INSTALL STEEL PIPE FOR SLEEVES SMALLER THAN 6 INCHES IN DIAMETER. INSTALL CAST-IRON WALL PIPES FOR
SLEEVES 6 INCHES AND LARGER IN DIAMETER. ALL UNDERGROUND, EXTERIOR-WALL PIPE PENETRATIONS SHALL HAVE
CAST-IRON WALL PIPES FOR SLEEVES.
J. REFRIGERANT: R-410
C. LIMIT THE SIZE OF THE SPACE BETWEEN THE OPENING AND THE OUTSIDE OF THE DUCT OR PIPE TO 1" MAXIMUM.
1.7 COORDINATION OF WORK
A. COORDINATE THE WORK WITH OTHER DISCIPLINES ON THE JOB. CLEARANCES ARE CRITICAL AND THERE SHALL BE
COMPLETE COOPERATION BETWEEN ALL TRADES. THERE WILL BE NO EXTRA COSTS ALLOWED FOR THE INABILITY OF
THIS CONTRACTOR TO COORDINATE HIS WORK WITH CABLE TRAYS AND OTHER EQUIPMENT/SYSTEMS PROVIDED BY
OWNER/OTHER CONTRACTORS.
B. ALL WORK SHALL BE DONE DURING NORMAL WORKING HOURS EXCEPT WHEN SPECIFICALLY AUTHORIZED BY THE
OWNER OR WHEN IT MAY BENEFIT THE CONTRACTOR DIRECTLY.
G. THE UNIT SHALL HAVE STANDARD 1 INCH THROWAWAY FILTERS AND SHALL BE SIZED AT 500 FPM MAX.
H. THE MOTORS SHALL HAVE PLUS OR MINUS 10 PERCENT VOLTAGE UTILIZATION RANGE. THE MOTOR SHALL MEET
NEMA PREMIUM EFFICIENCY SPECIFICATIONS, AND SHALL BE OPEN DRIP PROOF, WITH PERMANENTLY SEALED BALL
BEARINGS, INTERNAL CURRENT AND THERMAL OVERLOAD PROTECTION, A 1.15 SERVICE FACTOR AND SHALL BE
FACTORY INSTALLED AND WIRED TO THE UNIT.
K. ALL PIPING SHALL BE TESTED AND FLUSHED PRIOR TO INSULATION AND ACCEPTANCE. SUCTION LINES SHALL BE
TESTED AT 185 PSIG. HOT-GAS & LIQUID LINES SHALL BE TESTED AT 325 PSIG.
L. PIPING INSTALLATION: INSTALL REFRIGERANT PIPING ACCORDING TO ASHRAE 15. REFRIGERANT PIPING SHALL BE
SUPPORTED BY THE FLOOR, WALLS OR CEILING ONLY.
1.
2.
3.
4.
5.
INSTALL SO THAT INSULATION MAY BE APPLIED WHERE REQUIRED.
INSTALL HORIZONTAL SUCTION LINES WITH UNIFORM SLOPE OF .4% DOWNWARD TO COMPRESSORS.
INSTALL TRAPS AND DOUBLE RISERS WHERE REQUIRED TO ENTRAIN OIL IN VERTICAL RUNS.
LIQUID LINES MAY BE INSTALLED LEVEL.
PROVIDE BYPASS AROUND ALL MOISTURE-LIQUID INDICATORS. PROVIDE ALL PIPING, VALVES AND FITTINGS
NECESSARY TO INSTALL BYPASS.
6. REPLACEABLE CORE-FILTER DRYERS SHALL HAVE ISOLATION VALVES AND VALVED BYPASS.
7. REFRIGERANT VALVES SHALL BE INSTALLED ACCORDING TO MANUFACTURE RECOMMENDATIONS.
8. MOUNT THERMOSTATIC EXPANSION VALVES IN ANY POSITION, CLOSE TO EVAPORATOR.
9. CHARGE AND PURGE SYSTEMS, AFTER TESTING, AND DISPOSE OF REFRIGERANT FOLLOWING ASHRAE 15
PROCEDURES.
10. INSTALL HORIZONTAL HOT-GAS DISCHARGE PIPING WITH UNIFORM DOWNWARD SLOPE AWAY FROM COMPRESSOR.
M. ALL REFRIGERANT PIPING SHALL BE INSTALLED IN ACCORDANCE WITH THE UNIT MANUFACTURERS SPECIFIC
REQUIREMENTS, BASED ON THE EQUIPMENT SELECTED. MECHANICAL CONTRACTOR SHALL PROVIDE MANUFACTURER
APPROVED REFRIGERANT PIPING SUBMITTALS, INCLUDING ACCURATE PIPING DIAGRAM (PIPING LENGTH & ELEVATION
CHANGES CLEARLY SHOWN), PIPE SIZES AND CONTROL DEVICES, TO THE ENGINEER FOR APPROVAL.
2.7 CEILING / IN-LINE FAN
A. FURNISH AND INSTALL DUCT MOUNTED, DIRECT DRIVEN, CENTRIFUGAL INLINE FAN.
B. FAN SHALL BE UL LISTED (UL 705). FAN SHALL BEAR THE AMCA CERTIFIED RATINGS SEAL FOR SOUND AND AIR
PERFORMANCE.
PART 3 PERFORMANCE BALANCING
A. A COMPLETE AIR TEST AND BALANCE SHALL BE PERFORMED IN ACCORDANCE WITH NEBB OR AABC NATIONAL
STANDARDS FOR FIELD MEASUREMENTS AND INSTRUMENTATION. MECHANICAL CONTRACTOR SHALL CHANGE BELTS
AND SHEAVES ON AIR HANDLING EQUIPMENT AS DIRECTED BY BALANCING CONTRACTOR IF REQUIRED TO ACHIEVE
DESIGN PARAMETERS AT NO ADDITIONAL COST TO THE OWNER.
B. TEST AND BALANCE THE AIR DISTRIBUTION WITHIN 5% OF THE DESIGN. TEST AND BALANCE THE WATER SYSTEM TO
WITHIN 5% OF THE DESIGN.
C.
IT IS THE BALANCING CONTRACTOR'S RESPONSIBILITY UPON FINDING ANY DEFICIENCIES IN THE SYSTEM DUCTWORK
OR PIPING TO IMMEDIATELY BRING IT TO THE ATTENTION OF THE ENGINEER.
D. CHECK ALL DEVICES IN THE CONTROL SYSTEM FOR FUNCTION AND CALIBRATION.
E. PREPARE FOUR COPIES OF THE FINAL WRITTEN REPORT.
F. THE BALANCING CONTRACTOR SHALL BE PREPARED TO DEMONSTRATE TO THE OWNER AND THE ENGINEERS THAT THE
ACTUAL CONDITIONS MATCH THE BALANCE REPORT.
ALL T & B WORK SHALL BE CONDUCTED WITH EQUIPMENT OPERATING UNDER OPTIMAL DESIGN CONDITIONS. ALL
SYSTEMS SHALL BE FULLY INSTALLED, OPERATIONAL AND PROGRAMMED PRIOR TO THE T & B CONTRACTOR BEGINNING
THE TESTING PROCEDURES. THE T & B CONTRACTOR SHALL RECEIVE A COPY OF THE "SYSTEM PRE-COMMISSION
CERTIFICATION", SIGNED AND DATED BY BOTH THE GENERAL CONTRACTOR AND THE TEMPERATURE CONTROL
CONTRACTOR, PRIOR TO SCHEDULING ANY TEST/BALANCING WORK. THIS CERTIFICATION IS TO VERIFY THAT ALL NEW
AND EXISTING (MODIFIED) SYSTEMS ARE READY FOR FINAL TESTING AND COMMISSIONING BY THE T & B FIRM AS PER THE
SCOPE OF THE PROJECT.
THE FOLLOWING GUIDELINES FOR EACH SYSTEM SHALL BE FOLLOWED (NOT ALL EQUIPMENT IS LISTED):
1. AIR HANDLING UNITS AND AIR OUTLETS:
C. THE FAN HOUSING SHALL BE MINIMUM 20 GAUGE GALVANIZED STEEL AND ACOUSTICALLY INSULATED. BLOWER AND
MOTOR ASSEMBLY SHALL BE MOUNTED TO A MINIMUM 14 GAUGE REINFORCING CHANNEL AND SHALL BE REMOVABLE
FROM HOUSING.
D.
MOTOR SHALL BE MOUNTED ON RUBBER-IN-SHEAR VIBRATION ISOLATORS. UNIT SHALL BE SUPPLIED WITH
INTEGRAL WIRING BOX AND RECEPTACLE. THE OUTLET DUCT COLLAR SHALL INCLUDE A REINFORCED ALUMINUM
DAMPER WITH CONTINUOUS ALUMINUM HINGE ROD AND BRASS BUSHINGS. AN INLET DUCT COLLAR SHALL BE
PROVIDED TO ACCOMMODATE A SLIP-FIT DUCT CONNECTION.
A. FURNISH AND INSTALL NEW CONDENSING UNITS AS SHOWN AND SCHEDULED ON THE DRAWINGS.
B. THE CONDENSING UNITS SHALL BE UL LISTED AND SHALL BE CERTIFIED AND RATED IN ACCORDANCE WITH ARI
STANDARD 210/240.
C. THE CASING SHALL BE CONSTRUCTED OF 18 GAUGE ZINC COATED HEAVY GAUGE, GALVANIZED STEEL. EXTERIOR
SURFACES SHALL BE CLEANED, PHOSPHATIZED AND FINISHED WITH A WEATHER-RESISTANT BAKED ENAMEL FINISH.
UNITS SHALL HAVE REMOVABLE END PANELS WHICH ALLOW ACCESS TO ALL MAJOR COMPONENTS AND CONTROLS.
D. REFRIGERATION SYSTEM SHALL HAVE AN INTEGRAL SUBCOOLING CIRCUIT, LIQUID AND SUCTION GAS LINE SERVICE
VALVES WITH GAUGE PORTS.
E. EACH COMPRESSOR SHALL BE A DIRECT-DRIVE HERMETIC TYPE WITH CENTRIFUGAL OIL PUMP AND PROVIDE POSITIVE
LUBRICATION TO ALL MOVING PARTS. MOTORS SHALL BE SUCTION COOLED AND SHALL OPERATE WITHIN PLUS OR
MINUS OF 10 PERCENT OF NAMEPLATE VOLTAGE. THE UNITS SHALL BE PROVIDED WITH CRANKCASE HEATERS,
INTERNAL TEMPERATURE AND CURRENT-SENSITIVE MOTOR OVERLOADS. COMPRESSORS SHALL BE MOUNTED ON
SPRING ISOLATION. EXTERNAL HIGH AND LOW CUTOUT DEVICES SHALL BE PROVIDED.
F. CONDENSER COIL SHALL BE 3/8" COPPER TUBES MECHANICALLY BONDED TO ALUMINUM PLATE FINS. FACTORY
PRESSURE TESTED TO 425 PSIG AIR PRESSURE. PROVIDE HAIL PROTECTION CONDENSER COIL GUARD.
G. CONDENSER FAN SHALL BE DIRECT-DRIVE, STATICALLY AND DYNAMICALLY BALANCED PROPELLER FAN WITH ALUMINUM
BLADES AND STEEL HUB. MOTORS SHALL HAVE BUILT IN CURRENT AND THERMAL OVERLOAD PROTECTION.
H. CONDENSING UNITS SHALL BE COMPLETELY FACTORY WIRED. CONTROL WIRING SHALL BE 24-VOLT INCLUDING FUSING
AND TRANSFORMER. THE FOLLOWING OPTIONS SHALL BE INCLUDED: VIBRATION ISOLATION, TIME DELAY RELAY,
ANTI-SHORT-CYCLE TIMER.
THE T & B CONTRACTOR SHALL PROVIDE A DIAGRAM OF EACH AHU, PROVIDE A STATIC PROFILE ACROSS EACH
COMPONENT (FILTERS, COIL, ETC.), AND PROVIDE TOTAL STATIC PRESSURE ACROSS EACH UNIT. THE T & B
CONTRACTOR SHALL BALANCE THE AIRFLOW RATE FOR EACH AIR SYSTEM TO WITHIN 10% OF DESIGN. FOR ALL NEW AND
MODIFIED-EXISTING AIR HANDLING UNITS, THE T & B CONTRACTOR SHALL ADJUST THE OUTSIDE AIR DAMPER AND RETURN
AIR DAMPER POSITIONS TO ACHIEVE TOTAL DESIGN AIRFLOW RATE UNDER BOTH SUMMER COOLING MODE (MINIMUM
OUTSIDE AIR WITH MECHANICAL COOLING ON) AND WINTER ECONOMIZER MODE (100% OUTSIDE AIR WITH MECHANICAL
COOLING LOCKED OUT).
FOR EACH FAN, INCLUDE THE FOLLOWING DESIGN AND ACTUAL DATA IN THE FINAL REPORT:
A. SYSTEM IDENTIFICATION
B. MAKE AND MODEL NUMBER
C. MANUFACTURER'S SERIAL NUMBER
D. SHEAVE DIAMETER/BORE (INCHES)
KENT A. POYSER
REG. No. 37788
REGISTERED
INCLUDE THE FOLLOWING MOTOR DATA:
A. MAKE
B. HORSEPOWER
C. VOLTS, PHASE
D. FULL LOAD AMPERAGE AND SERVICE FACTOR
IN
INCLUDE DESIGN AND ACTUAL TEST VALUES FOR THE FOLLOWING:
A. TOTAL SUPPLY, RETURN AND OUTSIDE AIRFLOW RATES (CFM)
B. TOTAL SYSTEM STATIC PRESSURE (INCHES W.G.)
C. FAN RPM
D. DISCHARGE STATIC PRESSURE (INCHES W.G.)
E. SUCTION STATIC PRESSURE (INCHES W.G.)
F. COOLING COIL STATIC PRESSURE DIFFERENTIAL (INCHES W.G.)
G. OUTSIDE/RETURN AIR DAMPER LOCATION
H. AVERAGE FACE VELOCITY ACROSS COIL (FPM)
I. DESIGN AND ACTUAL AIRFLOW AT EACH SUPPLY AND RETURN AIR OUTLET (CFM)
J. OUTSIDE AIR, RETURN AIR, AND SUPPLY AIR TEMPERATURES (DEG F.)
3.3 REPORTING
THE T & B CONTRACTOR SHALL PREPARE FOUR COPIES OF THE FINAL WRITTEN T & B REPORT. THE REPORT SHALL
INCLUDE SCHEMATIC LAYOUTS OF ALL AIR DISTRIBUTION SYSTEMS. THE DIAGRAMS SHALL INCLUDE AIRFLOW RATES
(CFM) AND LOCATIONS. THE T & B CONTRACTOR SHALL BE PREPARED TO DEMONSTRATE TO THE OWNER AND THE
ENGINEERS THAT THE ACTUAL CONDITIONS MATCH THE BALANCE REPORT. UPON COMPLETION OF THE WORK, THE T & B
CONTRACTOR SHALL SIGN, DATE, AND FILL OUT THEIR PORTION OF THE "SYSTEM ACCEPTANCE SIGN OFF SHEET",
INDICATING ALL APPLICABLE SYSTEMS ARE APPROVED FOR OWNER ACCEPTANCE.
I. UNIT MANUFACTURER SHALL FURNISH REPLACEABLE CORE FILTER DRYER FOR EACH CONDENSING UNIT, FOR FIELD
INSTALLATION AS SHOWN ON THE DETAILS.
2.9 LOUVERS
A. THE MECHANICAL CONTRACTOR SHALL FURNISH AND INSTALL LOUVERS AS SHOWN ON THE DRAWINGS. THE GENERAL
CONTRACTOR SHALL BE RESPONSIBLE FOR MEASURING AND CUTTING THE OPENINGS AND COORDINATING ACTUAL
SIZE OF LOUVERS WITH MECHANICAL CONTRACTOR PRIOR TO ORDER. THE LOUVERS SHALL BE 6" DEEP, .081
EXTRUDED ALUMINUM FRAME & BLADES, 55% OR HIGHER FREE AREA, DRAINABLE, FIXED LOUVERS. PROVIDE TEST
DATA ON A 4'X4' UNIT SHOWING THE LOUVER CONFORMS TO THE DATA SIMILAR TO THE LOUVER SPECIFIED.
B. ALL LOUVERS SHALL BE POTTORFF, RUSKIN, AMERICAN WARMING, OR GREENHECK, SUBJECT TO COMPLIANCE WITH
REQUIREMENTS SPECIFIED.
2.4 DRAIN PIPING
C. LOUVERS' COLOR SELECTION FOR KYNAR FINISH SHALL BE SUBMITTED TO THE ARCHITECT FOR APPROVAL.
C. THIS CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING AND RELOCATING ANY MINOR INTERFERENCE TO
INCLUDE CONDUITS, HANGERS, ETC. AS THE BASE BID OF THIS PROJECT.
A. DRAIN PIPING SHALL BE TYPE L COPPER PIPE WITH WROUGHT COPPER FITTINGS.
1.8 PLANS AND SPECIFICATIONS
2.5 PIPE INSULATION
2.10 ELECTRICAL MOTORS FOR HVAC EQUIPMENT
A. THESE SPECIFICATIONS AND PLANS ARE MUTUALLY EXPLANATORY AND ANYTHING DESCRIBED OR SHOWN ON ONE, BUT
NOT ON THE OTHER, SHALL BE CONSIDERED ON BOTH.
A. INSTALL INSULATION PRODUCTS ON SPECIFIED PIPING IN ACCORDANCE WITH MANUFACTURER'S WRITTEN
INSTRUCTIONS, AND IN ACCORDANCE WITH RECOGNIZED INDUSTRY PRACTICES, TO INSURE THAT THE INSULATION
SERVES ITS INTENDED PURPOSE. FOR ALL PIPING INSULATION, A CONTINUOUS VAPOR RETARDER MUST BE
MAINTAINED. THE INSULATION SHALL BE APPLIED WITH A CONTINUOUS, UNBROKEN MOISTURE AND VAPOR SEAL. ALL
INSULATION JOINTS, SEAMS, FITTINGS AND PENETRATION LOCATIONS (I.E. P/T PORTS, VALVE STEMS, HEAT TRACE
WIRING, ETC.) SHALL BE PROPERLY SEALED. IF RIGID INSERTS ARE REQUIRED, BETWEEN PIPE AND INSULATION
SHIELDS, THEY SHALL BE OF EQUAL THICKNESS TO THE ADJACENT INSULATION AND SHALL BE VAPOR SEALED.
A. MOTORS SHALL COMPLY WITH THIS SECTION EXCEPT WHEN STRICTER REQUIREMENTS ARE SPECIFIED IN HVAC
EQUIPMENT SCHEDULES AND SECTIONS.
B. SHOULD ERROR OR DISCREPANCY APPEAR ON THE PLANS OR SPECIFICATION, IT SHALL BE REFERRED TO THE
ENGINEER BEFORE BIDDING.
F. THERMAL PROTECTION: COMPLY WITH NEMA MG 1 REQUIREMENT FOR THERMALLY PROTECTED MOTORS.
3.2 TESTING AND BALANCING
I. THE UNIT SHALL BE FURNISHED WITH A 7-DAY PROGRAMMABLE THERMOSTAT CAPABLE OF CONTROLLING BOTH THE
AIR HANDLING UNIT AND ASSOCIATED CONDENSING UNIT.
2.8 CONDENSING UNITS
A. INSTALL SLEEVES FOR PIPES PASSING THROUGH CONCRETE AND MASONRY WALLS AND CONCRETE FLOOR AND ROOF
SLABS. SEAL ALL PIPE PENETRATIONS USING SLEEVES AND MECHANICAL SLEEVE SEALS. SELECT SLEEVE SIZE TO
ALLOW FOR ADEQUATE CLEAR SPACE, BETWEEN SLEEVE AND PIPE (OR PIPE INSULATION), FOR INSTALLATION OF
MECHANICAL SLEEVE SEALS AND FIRE-STOPPING MATERIALS.
B. CAULKING: A SYNTHETIC ELASTOMER THAT IS UL CLASSIFIED FIRE STOP.
F. THE UNIT SHALL BE FURNISHED WITH ELECTRICAL HEATING ELEMENTS AS SPECIFIED AND DETAILED ON THE DRAWINGS.
COORDINATE POWER REQUIREMENTS WITH THE ELECTRICAL CONTRACTOR.
E. PIPE FITTINGS SHALL BE WROUGHT COPPER STREAMLINED PATTERN COPPER FITTINGS (ASTM B 16.22).
H. THERMOSTATIC EXPANSION VALVES MAY BE SOLDERED USING HARRIS STAY BRITE #8.
A. FURNISH AND INSTALL CAULKING AND SEALANT FOR ALL PIPING PASSING THROUGH ALL PARTITION WALLS WHETHER
CONCEALED IN CHASES, ABOVE CEILINGS OR EXPOSED.
E. REFRIGERANT COOLING COILS
SUCTION AND LIQUID LINE CONNECTIONS SHALL BE CLEARLY LABELED ON THE OUTSIDE OF THE UNIT. COILS SHALL BE
BURST TESTED TO 450 PSIG AND PROOF TESTED TO 300 PSIG AIR PRESSURE UNDER WATER. AFTER TESTING,
INSIDES OF COILS ARE TO BE DRIED, ALL CONNECTIONS ARE TO BE SEALED AND COIL SHALL BE SHIPPED WITH A
CHARGE OF DRY NITROGEN. SUCTION HEADERS SHALL BE CONSTRUCTED OF COPPER TUBING. SUCTION
CONNECTIONS SHALL PENETRATE UNIT CASINGS TO ALLOW FOR SWEAT CONNECTIONS TO REFRIGERANT LINES. COILS
SHALL HAVE EQUALIZING VERTICAL DISTRIBUTORS SIZED ACCORDING TO THE CAPACITIES OF THE COILS.
F. MOTOR SHALL MEET NEMA PREMIUM EFFICIENCY SPECIFICATIONS, AND SHALL BE OPEN DRIP PROOF TYPE WITH
PERMANENTLY LUBRICATED SEALED BEARINGS AND BUILT-IN THERMAL OVERLOAD PROTECTION.
1.5 SLEEVES
E. MOTORS SHALL HAVE A MINIMUM SERVICE FACTOR OF 1.15.
3.1 GENERAL INFORMATION
D. THE FAN SHALL BE FORWARD CURVED, CENTRIFUGAL BLOWER TYPE EQUIPPED WITH AN ADJUSTABLE SPEED V-BELT
DRIVE. THE FAN SHALL BE DYNAMICALLY BALANCED AND SHALL HAVE PERMANENTLY SEALED BALL BEARINGS.
D. PIPING SHALL BE TYPE ACR, ASTM B 280, DRAWN TEMPER HARD COPPER TUBE.
B. PROVIDE ASBESTOS FREE SMOKE AND FIRE TIGHT SEALS FOR ANY OPENING THROUGH FIRE RATED WALLS, FLOORS,
CHASES OR CEILINGS USED AS PASSAGE FOR MECHANICAL COMPONENTS SUCH AS PIPING, CONDUIT OR DUCTWORK.
1.6 CAULKING AND SEALANT
C. THE DRAIN PAN SHALL BE SLOPED IN BOTH DIRECTIONS AND SHALL BE FULLY DRAINABLE. THE COILS SHALL MOUNT
ABOVE THE DRAIN PAN AND NOT IN THE PAN. THE PAN SHALL HAVE A 3/4 INCH CONNECTION AND AN AUXILIARY
CONNECTION, BOTH OF WHICH SHALL BE TIED TOGETHER FOR DRAINAGE. THE UNIT SHALL BE FURNISHED WITH A
CONDENSATE OVERFLOW SWITCH, INSTALLED IN THE DRAIN PAN, TO SHUT DOWN THE UNIT TO PREVENT THE
CONDENSATE DRAIN PAN FROM OVERFLOWING.
E. WHEEL SHALL BE CENTRIFUGAL FORWARD CURVED TYPE, CONSTRUCTED OF GALVANIZED STEEL. WHEEL SHALL BE
BALANCED IN ACCORDANCE WITH AMCA STANDARD 204-96.
G. ALL COPPER-BRONZE AND COPPER-STEEL JOINTS MUST BE BRAZED ACCORDING TO AWS'S BRAZING HANDBOOK,
CHAPTER "PIPE AND TUBE". USE AWS A5.8 CLASS BAG-5, CADMIUM-FREE SILVER ALLOY BRAZING FILLER METAL
(SAFETY-SILV 45 WITH STAY-SILV WHITE BRAZING FLUX).
C. CUT SLEEVES TO LENGTH FOR MOUNTING FLUSH WITH BOTH SURFACES, EXCEPT WHEN INSTALLED IN FLOORS OF
MECHANICAL EQUIPMENT AREAS, OR OTHER WET AREAS, WHERE THE SLEEVES SHALL BE EXTENDED 2 INCHES ABOVE
THE FINISHED FLOOR LEVEL. EXTEND CAST-IRON SLEEVE FITTINGS BELOW FLOOR SLAB AS REQUIRED TO SECURE
CLAMPING RINGS.
D. MOTORS SHALL COMPLY WITH IEEE 841 FOR SEVERE-DUTY MOTORS.
B. THE UNIT CASING SHALL BE 18 GAUGE GALVANIZED STEEL WITH 1 INCH 1.5 LB DENSITY INSULATION. THE FAN
ACCESS SHALL BE ON BOTH SIDES OF THE UNIT BY ACCESS PANELS. THE COIL ACCESS SHALL BE ON BOTH SIDES.
C. ANYTIME THE PIPING MATERIAL CHANGES FROM A FERROUS TO A NONFERROUS MATERIAL, A DIELECTRIC CONNECTION
MUST BE MADE, REGARDLESS OF SIZE.
F. ALL COPPER JOINTS MUST BE BRAZED ACCORDING TO AWS'S BRAZING HANDBOOK, CHAPTER "PIPE AND TUBE". USE
HARRIS STAY-SILV 15 (14.5 - 15.5% SILVER) BRAZING FILLER METAL AND COMPLY WITH ANSI/AWS A5.8 CLASS
BCUP5.
C. MOTORS SHALL COMPLY WITH ENERGY EFFICIENCY AS DEFINED IN NEMA MG 1 (PREMIUM EFFICIENCY) UNLESS
OTHERWISE INDICATED.
2011 by Linfield, Hunter & Junius, Inc.
A. METAL DUCTS SHALL BE CONSTRUCTED AND INSTALLED IN ACCORDANCE WITH THE LATEST EDITION OF THE SMACNA
"HVAC DUCT CONSTRUCTION STANDARDS", UNLESS SPECIFICALLY INSTRUCTED OTHERWISE ON THE DRAWINGS.
CONSTRUCT FROM STANDARD COMMERCIAL GRADE GALVANIZED STEEL. ALL NEW SUPPLY, RETURN, EXHAUST, AND
OUTSIDE AIR DUCTWORK SHALL COMPLY WITH PRESSURE CLASS FOR 1" W.G. SEAL ALL TRANSVERSE AND
LONGITUDINAL SEAMS.
3608 18th Street, Suite 200
Metairie, Louisiana 70002
DATE: 10/1/2014
E. CONTRACTOR SHALL INSTALL CONSTRUCTION FILTERS ON ALL AIR DISTRIBUTION EQUIPMENT SERVING NEW OR
REMODELED AREAS TO ENSURE THAT COILS AND INTERNAL COMPONENTS ARE PROTECTED. BY COMPLETION OF THE
PROJECT THE M.C. SHALL REPLACE CONSTRUCTION FILTERS WITH NEW FILTERS. M.C. SHALL PROVIDE TEMPORARY
FABRIC FILTERS WRAPPED OVER ALL NEW AND EXISTING SUPPLY AIR GRILLES, CONNECTED TO THE DISTRIBUTION
DUCTWORK IN ALL AREAS AFFECTED BY CONSTRUCTION.
2.6 AIR HANDLING UNITS
APPROVED BY
D. DURING REMOVAL OF ITEMS SO INDICATED, CAUTION SHALL BE USED TO PREVENT DAMAGE TO ANY EQUIPMENT
HAVING SALVAGE VALUE. ALL REUSABLE SALVAGED MATERIAL SHALL REMAIN PROPERTY OF THE OWNER AND BE
RETAINED FOR HIS INSPECTION. ONLY ITEMS INSPECTED AND REJECTED BY THE OWNER SHALL BE DISPOSED OF BY
THE CONTRACTOR. ALL OTHER ITEMS SHALL BE TURNED OVER AND DEPOSITED AS DIRECTED BY THE OWNER.
2.1 DUCTWORK AND DUCT ACCESSORIES
2. CAPACITY AND TORQUE CHARACTERISTICS: SUFFICIENT TO START, ACCELERATE AND OPERATE CONNECTED LOADS
AT DESIGNATED SPEEDS, AT INSTALLED ALTITUDE AND ENVIRONMENT, AND WITHOUT EXCEEDING NAMEPLATE
RATINGS OR CONSIDERING SERVICE FACTOR.
CHECKED BY
C. MECHANICAL CONTRACTOR SHALL PAY FOR ALL PERMITS AS WELL AS LICENSE AND INSPECTION FEES REQUIRED FOR
HIS WORK.
C. THE CONDENSATE DRAIN SHALL HAVE 3/4" FLEXIBLE ELASTOMERIC INSULATION (INTERIOR AND EXTERIOR).
SELF-SEALING FLEXIBLE ELASTOMERIC INSULATION WILL NOT BE ACCEPTED.
PROJ. NO.
12-23
DATE
10/02/2014
SHEET NO.
C. KEEP ONE SET OF PLANS AND SPECIFICATIONS IN GOOD CONDITION ON THE JOB AT ALL TIMES.
OF
SHEETS
DRAWN BY
B. IF THE MECHANICAL CONTRACTOR ELECTS TO USE EQUIPMENT OTHER THAN THE NAMED BASIS OF DESIGN, ANY
ADDITIONAL COSTS ASSOCIATED WITH ELECTRICAL, GENERAL, AND MECHANICAL MODIFICATIONS REQUIRED SHALL
BECOME HIS ULTIMATE RESPONSIBILITY. THIS MUST BE IDENTIFIED PRIOR TO THE BID SO THAT THERE WILL BE NO
ADDITIONAL COSTS TO THE OWNER AFTER THE BID.
PART 2 PRODUCTS
1. DUTY: CONTINUOUS DUTY AT AMBIENT TEMPERATURE OF 104 DEGREES F AND AT ALTITUDE OF 3300 FEET ABOVE
SEA LEVEL.
THIS SHEET
A. PERTINENT FEDERAL, STATE AND LOCAL REGULATIONS AND REQUIREMENTS OF NATIONAL BOARD OF THE FIRE
UNDERWRITERS AND NATIONAL ELECTRICAL CODE ARE HEREBY MADE PART OF THIS CONTRACT. REQUIREMENTS OF
AUTHORITY HAVING LOCAL JURISDICTION SHALL SUPERSEDE ALL OTHER REQUIREMENTS.
A. THE MECHANICAL CONTRACTOR SHALL GUARANTEE ALL EQUIPMENT, ACCESSORIES, WORKMANSHIP, AND MATERIAL
FURNISHED BY HIM FOR A PERIOD OF ONE YEAR FROM FINAL ACCEPTANCE AGAINST ALL DEFECTS.
PROFESSIONAL ENGINEERS, ARCHITECTS
AND SURVEYORS
TIME:
4:48 PM
1.1 GENERAL
B. CHARACTERISTICS:
B. REFRIGERANT SUCTION (AND HOT GAS) PIPING: 1" FLEXIBLE ELASTOMERIC INSULATION (INTERIOR AND EXTERIOR).
SELF-SEALING FLEXIBLE ELASTOMERIC INSULATION WILL NOT BE ACCEPTED.
LINFIELD, HUNTER & JUNIUS, INC.
PART 1 GENERAL
1.9 GUARANTEE
CITY OF KENNER - CONVERSION OF
ANNE WASHINGTON COMMUNITY CENTER
MECHANICAL SPECIFICATIONS
6.
FIXTURES, EQUIPMENT, CONNECTIONS, AND PIPING SHALL BE FURNISHED AND INSTALLED TO MEET OR EXCEED
STATE AND LOCAL CODES AND REQUIREMENTS.
7.
8.
9.
10.
11.
12.
13.
14.
15.
FURNISH AND INSTALL WATER HAMMER ARRESTORS IN COLD WATER LINES AT CONNECTIONS TO FLUSH
VALVES, QUICK CLOSING VALVES, AND AT ALL HOT AND COLD WATER CONNECTIONS TO FIXTURES.
PLUMBING VENTS AND STACKS THROUGH ROOF SHALL BE INSTALLED A MINIMUM OF 10'-0" CLEAR OF A/C
OUTSIDE AIR INTAKES, CLINICAL AIR COMPRESSOR INTAKES, OR WINDOWS IN STRUCTURE.
PENETRATIONS THROUGH PARTITIONS AND FLOORS SHALL BE SLEEVED AND SEALED TO MAINTAIN INTEGRITY
OF PARTITION AND FLOOR RATING.
DRAWINGS ARE SCHEMATIC IN NATURE. CONTRACTOR IS RESPONSIBLE FOR COORDINATING EXACT ROUTING
OF ALL SERVICES WITH EXISTING CONDITIONS AND WITH ALL OTHER TRADES.
ORIENT FLUSH VALVE HANDLES ASSOCIATED WITH BARRIER-FREE WATER CLOSETS ON WIDE SIDE OF STALL TO
COMPLY WITH ADA REQUIREMENTS.
PROVIDE INSULATION KIT FOR SUPPLIES, DRAIN PIPING AND TRAP FOR ALL HANDICAP ACCESSIBLE LAVATORIES
AND SINKS. INSULATION KIT SHALL BE EQUAL TO TRUEBRO MODEL 103 (WHITE). WHERE PROTECTIVE SKIRT
UNDER FIXTURES IS PROVIDED, INSULATION OF PIPING IS NOT REQUIRED.
CONTRACTOR SHALL COORDINATE WITH PHASING REQUIREMENTS PROVIDED BY ARCHITECT/OWNER.
TEMPORARY SERVICES SHALL BE PROVIDED FOR ANY AREA SERVED BY ANOTHER AREA IF DEMOLITION OF
EXISTING SERVICE IS NECESSARY. COORDINATE ALL PLUMBING WORK WITH PHASING PLAN AS REQUIRED TO
COMPLETE COMPLETE WORK.
EXISTING SERVICES INDICATED ON THESE DRAWINGS WERE DERIVED FROM EXISTING DRAWINGS AND LIMITED
FIELD OBSERVATIONS. THESE DRAWINGS MAY NOT BE ALL INCLUSIVE OF SERVICES THAT EXIST IN THE
PROJECT AREA. CONTRACTOR SHALL VERIFY SERVICES, LOCATIONS, TYPE, AND SIZE PRIOR TO ANY BIDDING,
PRICING, OR CONSTRUCTION. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL WORK INVOLVING DEMOLITION
TIE-INS AND ROUTING CONFLICTS WITH EXISTING CONDITIONS. ANY DEVIATIONS IMPACTING WORK
SHOWN ON THESE DOCUMENTS SHALL BE REPORTED TO THE ARCHITECT FOR COORDINATION PRIOR TO
CONSTRUCTION.
PROVIDE ISOLATION BALL VALVES AT BRANCH LINES SERVING EACH ROOM WITH PLUMBING FIXTURES SUCH
THAT EACH ROOM MAY BE INDIVIDUALLY ISOLATED. ACCESS SHALL BE PROVIDED.
16.
17.
EXISTING TIE-IN POINTS ARE APPROXIMATE, FIELD VERIFY ACTUAL TIE-IN POINTS AND PROVIDE PIPING RUNS AS
REQUIRED FOR TIE-INS, PRIOR TO BIDDING.
18.
ALL SANITARY SEWER, STORM DRAIN, AND GREASE WASTE PIPING SHOWN SHALL BE RUN BELOW FLOOR,
UNLESS NOTED OTHERWISE.
19.
ALL CW, HW, HWR, NATURAL GAS, FIRE PROTECTION, AND VENT PIPING SHOWN SHALL BE RUN ABOVE CEILING,
UNLESS NOTED OTHERWISE.
20.
PROVIDE ALL PLUMBING FIXTURES AND EQUIPMENT WITH ACCESSIBLE STOPS.
21.
UNLESS OTHERWISE NOTED, ALL DRAINS SHALL BE INSTALLED AT THE LOW POINT OF ROOFS, AREAWAYS,
FLOOR, ETC.
22.
ALL CLEANOUTS SHALL BE THE FULL SIZE OF THE PIPE FOR PIPE SIZES 6 IN AND SMALLER, AND SHALL BE 6 IN
FOR PIPE SIZES LARGER THAN 6 IN.
23.
PROVIDE SHUTOFF VALVES IN ALL DOMESTIC WATER PIPING SYSTEM BRANCHES IN WHICH BRANCH PIPING
SERVES TWO OR MORE FIXTURES.
NOTES ARE GENERAL IN NATURE, NOT ALL NOTES ARE NECESSARILY USED IN THIS PROJECT.
PIPE AND FITTING SCHEDULE
TYPE
WASTE AND VENT
ICE MAKER
AP
ACCESS PANEL
INV
INVERT
AV
ACID VENT
IW
INDIRECT WASTE
AW
ACID WASTE
JS
JANITORS SINK
BEH
BEHIND
KS
KITCHEN SINK
BFP
BACKFLOW PREVENTER
KW
KILOWATT
BMS
BUILDING MANAGEMENT SYSTEM
LxWxH
LENGTH x WIDTH x HEIGHT
BOP
BOTTOM OF PIPE
LAV
LAVATORY
BT
BATHTUB
LBS
POUNDS
BTUH
BRITISH THERMAL UNITS PER HOUR
LDR
LEADER
CL
CENTERLINE
LWT
LEAVING WATER TEMPERATURE
CLG
CEILING
MB
MOP BASIN
SANITARY SEWER ABOVE
CM
COFFEE MAKER
MBH
1000 BRITISH THERMAL UNITS PER HOUR
SANITARY SEWER BELOW
CO
CLEANOUT
MECH.
MECHANICAL
CODP
CLEAN OUT DECK PLATE
MGCV
MASTER GAS CONTROL VALVE
CONT.
CONTINUATION
MH
MANHOLE
COTG
CLEAN OUT TO GRADE
MICV
METER INLET CONTROL VALVE
COWP
CLEAN OUT WALL PLATE
MOCV
COYB
CLEANOUT IN YARD BOX
CP
EXISTING PIPING TO BE REMOVED
NEW PIPING
DOMESTIC COLD WATER PIPING
EXISTING EQUIPMENT
TO BE DEMOLISHED
DOMESTIC HOT WATER PIPING
DOMESTIC HOT WATER PIPING AT
INDICATED SERVICE TEMPERATURE
XX
1
DOMESTIC HOT WATER RECIRCULATION
CD
NEW EQUIPMENT
WITH IDENTIFICATION
CONDENSATE DRAIN PIPING
PUMP
BACKFLOW PREVENTER
GW
GREASE WASTE
ELBOW UP
AW
ACID WASTE ABOVE
ELBOW DOWN
METER OUTLET CONTROL VALVE
AW
ACID WASTE BELOW
BRANCH PIPE CONNECTION
MS
MOP SINK
AV
ACID VENT
TEE-OUTLET DOWN
CONTROL PANEL
NIC
NOT IN CONTRACT
G
NATURAL GAS PIPING
TEE-OUTLET UP
CWTP
TRAP PRIMER COLD WATER LINE
NFGH
NON FREEZE GROUND HYDRANT
DOUBLE CHECK DETECTOR ASSEMBLY
NFWH
NON FREEZE WALL HYDRANT
TEMPERED WATER
PIPE REDUCER
DCDA
DCV
DOUBLE CHECK VALVE
NO
NUMBER
FLOOR CLEANOUT
GATE VALVE
DCW
DOMESTIC COLD WATER
NTS
NOT TO SCALE
GLOBE VALVE
DF
DRINKING FOUNTAIN
OD
OVERFLOW DRAIN
EXTERIOR CLEANOUT (SEE
SCHEDULE SPECIFICATIONS)
DFU
DRAINAGE FIXTURE UNIT(S)
OFCI
OWNER FURNISHED CONTRACTOR INSTALLED
DHW
DOMESTIC HOT WATER
OS&Y
OUTSIDE SCREW & YOKE
DHWR
DOMESTIC HOT WATER RETURN
OSD
OPEN SITE DRAIN
DN
DOWN
PD
PRESSURE DROP
DR
DRAIN
PG
PRESSURE GAUGE
DW
DISHWASHER
PLMB
PLUMBING
DWG
DRAWING
PO
PLUGGED OUTLET
ECO
EXTERIOR CLEANOUT
POE
POINT OF ENTRY
EL
ELEVATION
PRV
PRESSURE REDUCING VALVE
ES/EW
EMERGENCY SHOWER/EYEWASH
PS
PANTRY SINK
EWC
ELECTRIC WATER COOLER
PSIG
POUNDS PER SQUARE INCH GAGE
EWH
ELECTRIC WATER HEATER
RD
ROOF DRAIN
EWT
ENTERING WATER TEMPERATURE
REF
REFRIGERATOR
EX
EXISTING
RPM
REVOLUTIONS PER MINUTE
F
FAHRENHEIT
RPZ
REDUCED PRESSURE ZONE BFP ASSEMBLY
FAI
FRESH AIR INLET
SA
SHOCK ABSORBER
FCO
FLOOR CLEANOUT
SE
SEWAGE EJECTOR
FD
FLOOR DRAIN
SH
SHOWER
FFD
FUNNEL FLOOR DRAIN
SK
SINK
FFE
FINISHED FLOOR ELEVATION
SS
SANITARY SEWER
FMS
FACILITY MANAGEMENT SYSTEM
SD
STORM DRAIN
FPWH
FREEZE PROOF WALL HYDRANT
SP
SUMP PUMP
FS
FLOOR SINK
TD
TERRACE/TRENCH DRAIN
FSP
FIRE STAND PIPE
TP
TRAP PRIMER
FT
FOOT, FEET
TW
TEMPERED WATER
FU
FIXTURE UNIT(S)
TYP
TYPICAL
G
GAS
UON
UNLESS OTHERWISE NOTED
GT
GREASE TRAP
UR
URINAL
GPH
GALLONS PER HOUR
V
VENT
GPM
GALLONS PER MINUTE
VB
VACUUM BREAKER
GPR
GAS PRESSURE REGULATOR
V/Ph/Hz
VOLTS/PHASE/HERTZ
GT
GREASE TRAP
VFD
VARIABLE FREQUENCY DRIVE
GW
GREASY WASTE
VO
VALVED OUTLET
GWH
GAS WATER HEATER
VTR
VENT TO ROOF
HB
HOSE BIB
WB
WET BULB
HC
HANDICAPPED
WC
WATER CLOSET
HLAV
HANDICAPPED LAVATORY
WCO
WALL CLEANOUT
HP
HORSEPOWER
W/D
CLOTHES WASHER/DRYER
HPG
HIGH PRESSURE GAS
WG
WATER GAGE
FITTINGS
LOCATION
15" AND
SMALLER
STD. WT. C.I.
HUBLESS
STD. NO-HUB COUPLINGS
ABOVE GRADE AND
BELOW GRADE
HR
HOUR
WH
WALL HYDRANT
15" AND
SMALLER
STD. WT. C.I. HUB
AND SPIGOT
HT
HOUSE TRAP
WHA
WATER HAMMER ARRESTOR
STD. WT. C.I. HUB AND SPIGOT
BELOW GRADE
(16 MIL WRAPPED)
HTR
HEATER
WM
WATER METER
ALL SIZES
SCHEDULE 40 PVC
SCHEDULE 80 PVC
ABOVE GRADE AND
BELOW GRADE
HUR
HANDICAPPED URINAL
WPD
WATER PRESSURE DROP
TYPE "L" HARD
COPPER
HVAC
HEATING, VENTILATION & AIR CONDITIONING
WSFU
WATER SUPPLY FIXTURE UNIT
ALL SIZES
WROUGHT COPPER
ABOVE GRADE
HWC
HANDICAPPED WATER CLOSET
ALL SIZES
TYPE "K" HARD
COPPER
WROUGHT COPPER, SILVER BRAZED
BELOW GRADE
(16 MIL WRAPPED)
HWH
HOT WATER HEATER
HWT
HOT WATER STORAGE TANK
ALL SIZES
TYPE "M" HARD
COPPER
ABOVE GRADE
EXISTING EQUIPMENT
TO REMAIN
VENT PIPING
MATERIAL
WROUGHT COPPER
EXISTING PIPING TO REMAIN
ABBREVIATION LIST IS GENERAL IN NATURE, NOT ALL ABBREVIATIONS ARE NECESSARILY USED IN THIS PROJECT.
TW
BUTTERFLY VALVE
WALL CLEANOUT
2011 by Linfield, Hunter & Junius, Inc.
IM
SIZE
DOMESTIC WATER
CONDENSATE DRAIN
ABOVE FINISHED FLOOR
3608 18th Street, Suite 200
Metairie, Louisiana 70002
COORDINATE WATER, WASTE, VENT, AND STORM WATER PIPING WITH OTHER TRADES TO AVOID SPACING OR
ROUTING PROBLEMS.
AFF
BALL VALVE
CONTROL VALVE, 2 WAY
CONTROL VALVE, 3 WAY
DETAIL NO.
CHECK VALVE
STRAINER
SHEET ON WHICH
DETAIL IS LOCATED
STRAINER AND BLOWDOWN VALVE
PLUG COCK/ BALANCING VALVE/
GAS COCK
SPECIFIC NOTE DESIGNATION
CIRCUIT SETTER
PRESSURE REDUCING VALVE
POINT OF DISCONNECT
GAS PRESSURE REGULATOR
UNION
KENT A. POYSER
REG. No. 37788
FLEXIBLE CONNECTOR
POINT OF CONNECTION, NEW
TO EXISTING
REGISTERED
PIPE CAP
IN
GAUGE AND GAUGE COCK
THERMOMETER
VALVE WITH BLIND FLANGE
VACUUM INLET
T
NATURAL GAS OUTLET
STEAM TRAP
THERMOSTATIC EXPANSION VALVE
FLOOR OR AREA DRAIN
CLEAN OUT IN YARD BOX
FLOOR SINK
TRAP PRIMER
ROOF DRAIN
WATER HAMMER ARRESTOR
OVERFLOW ROOF DRAIN
ES/EW
EMERGENCY SHOWER / EYEWASH
INDIRECT WASTE RECEPTOR
EEW
EMERGENCY EYEWASH
FLOOR CLEAN OUT
SYMBOL LIST IS GENERAL IN NATURE, NOT ALL SYMBOLS ARE NECESSARILY USED IN THIS PROJECT.
APPROVED BY
5.
INVERT ELEVATION
CHECKED BY
CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING MOUNTING OF ALL PLUMBING FIXTURES. THIS
WORK SHALL INCLUDE BUT NOT BE LIMITED TO PROVIDING WALL CARRIERS AND COORDINATING FIXTURES
WITH CASEWORK.
IE
PROJ. NO.
12-23
DATE
10/02/2014
SHEET NO.
OF
SHEETS
DRAWN BY
CONTRACTOR SHALL COORDINATE EQUIPMENT CONNECTIONS WITH EQUIPMENT DRAWINGS AND SUPPLIER.
INSTALL EQUIPMENT AND MAKE FINAL CONNECTIONS, FURNISHING CUTOFF VALVES, P-TRAPS, P.R.V'S,
BACKFLOW PREVENTERS, AND PIPING AS REQUIRED. CONTRACTOR SHALL BE RESPONSIBLE FOR IDENTIFYING
ANY CONFLICTS BETWEEN THESE DOCUMENTS AND EQUIPMENT CUT SHEETS PRIOR TO CLOSING IN WALLS
AND CEILINGS.
AREA DRAIN
THIS SHEET
PROVIDE ALL MATERIAL AND EQUIPMENT AND PERFORM ALL LABOR REQUIRED TO INSTALL COMPLETE AND
OPERABLE MECHANICAL SYSTEMS AS INDICTED ON THE DRAWINGS, AS SPECIFIED AND AS REQUIRED BY
CODE.
AD
PROFESSIONAL ENGINEERS, ARCHITECTS
AND SURVEYORS
4.
LOUISIANA PLUMBING CODE - 2013
INTERNATIONAL BUILDING CODE - 2012
NATIONAL ELECTRICAL CODE - 2008
NFPA 70 - 2014
NFPA 72 - 2013
THE CONTRACT DOCUMENTS
ALL REQUIREMENTS OF THE STATE FIRE MARSHAL
INSURING AGENCY
ALL REQUIREMENTS OF THE AUTHORITIES HAVING JURISDICTION.
PLUMBING LEGEND
LINFIELD, HUNTER & JUNIUS, INC.
DATE: 10/1/2014
3.
FILE: P:\LinfieldHunter&Junius\14-098_CommunityResourceCenter\Design Documents\Drawings\Plumbing\P-000 PLUMBING LEGEND.dwg
ALL WORK SHALL COMPLY WITH THE LATEST STATE AND CITY CODES INCLUDING BUT NOT LIMITED TO THE
FOLLOWING:
A.
B.
C.
D.
E.
F.
G.
H.
I.
2.
PLUMBING ABBREVIATIONS
CITY OF KENNER - CONVERSION OF
ANNE WASHINGTON COMMUNITY CENTER
1.
TIME:
9:48 PM
PLUMBING GENERAL NOTES
FIBERGLASS BATHTUB 4-PIECE TUB/SHOWER ENCLOSURE WITH GRAB BARS, FOLDING SEAT,
PRESSURE BALANCED MIXING VALVE PRE-PIPED TO SUPPLY ELBOW, CHROME PLATED
SHOWER HEAD, CHROME PLATED DRAIN.
BT-2
BATH TUB
ACRYLIC HANDICAP BATHTUB WITH HANDICAP SEAT WITH STAINLESS STEEL GRAB BARS,
SINGLE HAND PRESSURE BALANCING MIXING SHOWER UNIT, HAND SHOWER HEAD, 60"
FLEXIBLE METAL HOSE, MOUNTING WALL BRACKET, TUB SPOUT AND CHROME FINISHED DRAIN.
SH-1
SHOWER
S-1
SINK
DOUBLE BOWL
25" X 22" X 10" DEEP
L-1
LAVATORY
SELF-RIMMING
VITREOUS CHINA, ROUND BOWL, SELF-RIMMING WITH OVERFLOW, DOME LEVER FAUCET
WITH 4" CENTERS, POP-UP DRAIN, WHITE FINISH.
WC-1
WATER CLOSET
FLOOR MOUNT
TANK TYPE
VITREOUS CHINA, TANK TYPE, TWO-PIECE, FLOOR MOUNT, ELONGATED BOWL, FULLY GLAZED
2" TRAP-WAY, 1.6 GAL PER FLUSH, WHITE FINISH.
TOTO CST716 CARUSOE
CLOSE COUPLED TOILET
McGUIRE
LFBV2166CC
WC-2
WATER CLOSET
FLOOR MOUNT
TANK TYPE - ADA
VITREOUS CHINA, TANK TYPE, TWO-PIECE, ADA HEIGHT, FLOOR MOUNT, ELONGATED BOWL,
FULLY GLAZED 2" TRAP-WAY, 1.6 GAL PER FLUSH, WHITE FINISH.
TOTO CST716 CARUSOE
CLOSE COUPLED TOILET
McGUIRE
LFBV2166CC
FLOOR DRAIN
FCO
FLOOR CLEANOUT
IMB-1
ICE MAKER BOX
MB-1
MOP BASIN
24x24
ACCEPTABLE
EQUALS
ACCESSORIES
ZURN
Z7000-S8
BARRIER FREE
4ETSF6030A165
DCW
DHW
VENT
SAN.
1/2"
1/2"
2"
3"
1/2"
1/2"
2"
3"
1/2"
1/2"
2"
2"
STERLING
ACCORD
71140115
ZURN
Z7120-SS-LH-HW
Z700-T4
32"x32" 2-PIECE FIBERGLASS SHOWER WITH CHROME FINISHED CENTER DRAIN DRAIN, AND
PRESSURE BALANCE SHOWER VALVE WITH STANDARD SHOWER HEAD.
MAAX
GALLERY SERIES
6714556
ZURN
Z7121-SS-LH
18 GAUGE STAINLESS STEEL DOUBLE COMPARTMENT SELF-RIMMING SINK, BRUSHED FINISH,
3-1/2" DRAIN OPENING, THREE HOLE PUNCH, HEAVY DUTY SOUND COATED UNDERSIDE.
ELKAY
SLPF2522104
ELKAY
LK2477CR
McGUIRE
LFBV2165CC
AMERICAN STANDARD
& JUST
1/2"
1/2"
2"
2"
ZURN
Z5120
ZURN
Z81103-XL-P
McGUIRE
LFBV2165CC
AMERICAN STANDARD
& ELJER
1/2"
1/2"
2"
2"
TOTA SS114
SOFTCLOSE SEAT
AMERICAN STANDARD,
ELJER, & KOHLER
1"
---
3"
4"
TOTA SS114
SOFTCLOSE SEAT
AMERICAN STANDARD,
ELJER, & KOHLER
1"
---
3"
4"
ZURN Z415B
JR SMITH, WADE, &
WATTS
1/2"
---
3"
3"
ZURN Z1400-VP
JR SMITH & WATTS
1/2"
---
3"
3"
OATEY 38608
SIOUX CHIEF & IPS
1/2"
---
JR SMITH, WADE, &
WATTS
1/2"
1/2"
ROUND FLOOR DRAIN WITH DURA-COATED CAST IRON BODY AND 3" BOTTOM
OUTLET,COMBINATION INVERTIBLE MEMBRANE CLAMP AND ADJUSTABLE COLLAR
WITH SEEPAGE SLOTS AND "TYPE B" POLISHED NICKEL BRONZE, LIGHT-DUTY STRAINER
FD-1
TRIM
ADJUSTABLE POLISHED BRONZE FLOOR CLEANOUT, DURA-COATED CAST IRON BODY WITH
GAS AND WATER TIGHT ADS TAPERED THREAD PLUG, ROUND SECURED TOP, VANDAL PROOF
SCREWS, NO HUB CONNECTION
1
4
TURN BRASS HAMMER BALL VALVE, COPPER SWEAT, STANDARD PACK
24x24 HIGH-DENSITY COMPOSITE, MOLDED MOP BASIN, 10" DEEP, INTEGRAL STAINLESS
STEEL DRAIN ASSEMBLY AND STRAINER, WALL MOUNTED FAUCET WITH PAIL HOOK.
ZURN Z1996-24
AMERICAN STANDARD
& ELJER
ZURN Z843M2
ZURN Z8800LR-PC
---
2011 by Linfield, Hunter & Junius, Inc.
BATH TUB
REFERENCE PRODUCT
3608 18th Street, Suite 200
Metairie, Louisiana 70002
BT-1
DESCRIPTION
PROFESSIONAL ENGINEERS, ARCHITECTS
AND SURVEYORS
FIXTURE
LINFIELD, HUNTER & JUNIUS, INC.
FAUCETS / FITTINGS
MARK
---
2"
2"
ELECTRIC WATER HEATER SCHEDULE
MARK
CHECK VALVE (TYP.)
EWH-1
STORAGE
CAPACITY
SYSTEM
AND/OR
SERVICE
TYPE
DOMESTIC
HOT WATER
TANK
RELIEF VALVE
SETTING
GAL
GAL/HR
PSIG
120
91
150
ELECTIRCAL INPUT
NO OF
ELEMENTS
1
REFERENCE
MODEL
TOTAL
kW
kW PER
ELEMENT
VOLT
PHASE
FLA
24
24
240
1
-
KENT A. POYSER
REG. No. 37788
STATE
CSB-120-24-SFE
REGISTERED
112
IN
THERMOSTATIC MIXING VALVE
3" COLD WATER SUPPLY
MODEL
LOCATION
TMV-1
POWERS
LF4M432
-
INLET
3
4"
OUTLET
1"
CAPACITY
MIN
MAX
4 GPM
21 GPM
PRESSURE
DROP
NOTES
5 PSI
ROUGH BRONZE FINISH, EXPOSED
MOUNTING
FPWH @ 24" ABOVE
FINISHED GRADE
BUILDING EXTERIOR WALL
CITY OF KENNER - CONVERSION OF
ANNE WASHINGTON COMMUNITY CENTER
UNION (TYP.)
A.S.M.E. APPROVED TEMPERATURE
AND PRESSURE RELIEF VALVE
SLEEVE AND SEAL
WATER-TIGHT
GRADE
DOMESTIC COLD WATER LINE
TO BUILDING
D
DOMESTIC WATER LINE
TO SITE POTABLE
WATER MAIN
FINISHED FLOOR
RELIEF PIPE - ROUTE FULL SIZE TO
NEAREST FLOOR SINK OR DRAIN
DRAIN VALVE
DCW
OVERFLOW PAN
UNDERGROUND VALVE WITH
CAST IRON VALVE BOX
2
DOMESTIC WATER SERVICE ENTRY DETAIL
SCALE: NTS
1
TANK TYPE WATER HEATER DETAIL
SCALE: NTS
CHECKED BY
MANUFACTURER
PROJ. NO.
12-23
DATE
10/02/2014
SHEET NO.
OF
SHEETS
DRAWN BY
MARK
THIS SHEET
SHUTOFF VALVE (TYP.)
APPROVED BY
THERMOSTATIC MIXING VALVE SCHEDULE
DCW
FILE: P:\LinfieldHunter&Junius\14-098_CommunityResourceCenter\Design Documents\Drawings\Plumbing\P-001 PLUMBING SCHEDULES.dwg
DATE: 10/1/2014
TIME:
9:47 PM
PLUMBING FIXTURE SCHEDULE
IF THE PLUMBING CONTRACTOR DOES NOT CLEARLY UNDERSTAND
THESE PLANS, OR IS NOT SURE OF THEIR MEANING, HE SHOULD
OBTAIN THE ENGINEER'S WRITTEN EXPLANATION AND INTERPRETATION,
PRIOR TO SUBMITTING HIS BID, SINCE THE PLUMBING CONTRACTOR
WILL BE HELD RIGIDLY TO THE INTERPRETATION OF THE ENGINEER.
3.
ALL EXISTING PLUMBING ITEMS SHALL BE REMOVED, INCLUDING
EXISTING PLUMBING FIXTURES, WATER HEATER, WASTE PIPING, VENT
PIPING, AND DOMESTIC WATER PIPING.
4.
THE OWNER SHALL MAINTAIN ALL SALVAGE RIGHTS OF EQUIPMENT AND
MATERIALS REMOVED. ALL EQUIPMENT AND MATERIALS NOT CLAIMED
BY THE OWNER SHALL BE REMOVED FROM THE PREMISES BY THE
CONTRACTOR.
5.
THE PLUMBING CONTRACTOR SHALL BE RESPONSIBLE FOR ALL
CUTTING AND PATCHING OF CONCRETE SLAB FOR PIPING REMOVAL
AND CAPPING AT ACTIVE MAINS.
6.
THE PLUMBING CONTRACTOR SHALL BE RESPONSIBLE FOR ALL ROOF
PATCHING WHEN REMOVING EXISTING PLUMBING VENTS. CONTRACTOR
SHALL PATCH ROOF TO MATCH EXISTING.
7.
CONTRACTOR TO COORDINATE ALL DEMOLITION & NEW CONSTRUCTION
WITH THE PROJECT CONSTRUCTION MANAGER AND ALL OTHER TRADES
PER PROJECT AREA PHASING.
PLAN NOTES:
2011 by Linfield, Hunter & Junius, Inc.
2.
3608 18th Street, Suite 200
Metairie, Louisiana 70002
THESE PLANS ARE DIAGRAMMATIC IN NATURE SINCE THEY REFLECT
ONLY THE AVAILABLE INFORMATION OBTAINED FROM EXISTING PLANS,
SPECIFICATIONS, AND FIELD SURVEYS. THE EXACT LOCATION OF
EXISTING DUCTWORK, PIPING, AND EQUIPMENT MAY DEVIATE FROM
THE LOCATION INDICATED ON THESE DRAWINGS. THE CONTRACTOR
SHALL BE PREPARED TO MAKE SOME ALTERATIONS TO NEW AND/OR
EXISTING SERVICES TO FIT ACTUAL JOB CONDITIONS.
PROFESSIONAL ENGINEERS, ARCHITECTS
AND SURVEYORS
1.
LINFIELD, HUNTER & JUNIUS, INC.
DATE: 10/1/2014
TIME:
9:47 PM
GENERAL DEMOLITION NOTES:
REMOVE EXISTING DRINKING FOUNTAIN AND CAP DOMESTIC WATER,
WASTE, AND VENT PIPING AT ACTIVE MAINS.
REMOVE EXISTING LAVATORY AND CAP DOMESTIC WATER, WASTE, AND
VENT PIPING AT ACTIVE MAINS.
REMOVE EXISTING SINK AND CAP DOMESTIC WATER, WASTE, AND VENT
PIPING AT ACTIVE MAINS.
REMOVE EXISTING WATER HEATER AND ASSOCIATED DOMESTIC WATER
PIPING.
REMOVE EXISTING WATER CLOSET AND ASSOCIATED WASTE PIPING AND
RISER, VENT PIPING AND RISER, AND DOMESTIC WATER.
REMOVE EXISTING LAVATORY AND ASSOCIATED WASTE PIPING AND RISER,
VENT PIPING AND RISER, AND DOMESTIC WATER.
KENT A. POYSER
REG. No. 37788
REMOVE EXISTING SINK AND ASSOCIATED WASTE PIPING AND RISER,
VENT PIPING AND RISER, AND DOMESTIC WATER.
REGISTERED
PROJ. NO.
12-23
DATE
10/02/2014
SHEET NO.
OF
SHEETS
DRAWN BY
THIS SHEET
CHECKED BY
APPROVED BY
IN
REMOVE EXISTING BATHTUB AND ASSOCIATED WASTE PIPING AND RISER,
VENT PIPING AND RISER, AND DOMESTIC WATER.
CITY OF KENNER - CONVERSION OF
ANNE WASHINGTON COMMUNITY CENTER
FILE: P:\LinfieldHunter&Junius\14-098_CommunityResourceCenter\Design Documents\Drawings\Plumbing\P-101 PLUMBING DEMOLITION.dwg
REMOVE EXISTING WATER CLOSET AND CAP DOMESTIC WATER, WASTE,
AND VENT PIPING AT ACTIVE MAINS.
LIVING ROOM /
DINING
102
2" SS
3" V
FD-1
STAIRWELL
219
LAV-1
ALL FINAL CONNECTION SIZES TO EQUIPMENT SHALL BE CONFIRMED
PRIOR TO FABRICATION.
WC-1
SH-1
3" VTR
4" SS DN
KITCHEN
119
BATHROOM
106
S-1
4" SS
2" V
4" SS UP
LAV-1
WC-1
2011 by Linfield, Hunter & Junius, Inc.
BEDROOM
205
SH-1
BATHROOM
218
2" SS
3608 18th Street, Suite 200
Metairie, Louisiana 70002
2" V
3" SS
3" SS
4" SS
LIVING
ROOM
201
BATHROOM
202
2" V
3" VTR
CORRIDOR
200
BEDROOM #4
(ADA)
118
BEDROOM #1
107
4" SS DN
3" V
4" SS
WC-1
2" SS
LAV-1
WMB-1
2" V
BEDROOM #2
110
KENT A. POYSER
REG. No. 37788
REGISTERED
IN
LIVING
ROOM/
BEDROOM
211
BEDROOM #3
115
3" SS
3" SS
2" V
2" V
4" SS DN
3" V DN
3" V UP
4" SS UP
3" V UP
APPROVED BY
FD-1
WMB-1
2" V
3" V DN
3" SS
CHECKED BY
FD-1
4" SS UP
LAV-1
LAUNDRY
ROOM
113
PROJ. NO.
12-23
DATE
10/02/2014
SHEET NO.
OF
SHEETS
DRAWN BY
FD-1
S-1
BT-2
THIS SHEET
3" VTR
4" SS DN
BATHROOM
(ADA)
111
MB-1
4" SS
2" V
2" V
WMB-1
4" SS
2" SS
3" SS
2" SS
2" V
2" V
CORRIDOR
112
WC-2
3" V
S-1
4" SS
KITCHEN/
DINING
212
CITY OF KENNER - CONVERSION OF
ANNE WASHINGTON COMMUNITY CENTER
KITCHEN/
DINING
216
4" SS
2" SS
4" SS
4" SS UP
3" V
BT-1
BATHROOM
209
3" V UP
2" SS
2" SS
LIVING
ROOM/
BEDROOM
217
2" V
FILE: P:\LinfieldHunter&Junius\14-098_CommunityResourceCenter\Design Documents\Drawings\Plumbing\P-201 PLUMBING WASTE & VENT.dwg
3" V UP
4" SS
6.
3" SS UP
4" SS
PROFESSIONAL ENGINEERS, ARCHITECTS
AND SURVEYORS
SH-1
ALL SANITARY SEWER LINES SHOWN SHALL BE RUN AT FLOOR BELOW.
3" SS DN
LAV-1
WC-1
4. IF THE PLUMBING CONTRACTOR DOES NOT CLEARLY UNDERSTAND
THESE PLANS, OR IS NOT SURE OF THEIR MEANING, HE SHOULD
OBTAIN THE ENGINEER'S WRITTEN EXPLANATION AND INTERPRETATION,
PRIOR TO SUBMITTING HIS BID, SINCE THE PLUMBING CONTRACTOR
WILL BE HELD RIGIDLY TO THE INTERPRETATION OF THE ENGINEER.
5.
S-1
EXISTING 4" SS
2" V
4" SS
3" SS
KITCHEN/
DINING
203
4" SS
BECAUSE OF THE LIMITED SPACE AVAILABLE TO INSTALL ALL OF THE
MECHANICAL WORK, COORDINATION BETWEEN THE VARIOUS TRADES
IS OF THE UTMOST IMPORTANCE.
4" SS DN
4"
SS
3.
4" SS UP
3" VTR
3" V
ALL ELBOWS, FITTINGS, ETC. IN PIPING ARE NOT NECESSARILY
INDICATED TO CLEAR ALL EXISTING AND NEW JOB OBSTRUCTIONS.
3" VTR
3" V
THESE PLANS ARE DIAGRAMMATIC IN NATURE SINCE THEY REFLECT
ONLY THE AVAILABLE INFORMATION OBTAINED FROM EXISTING PLANS,
SPECIFICATIONS, AND FIELD SURVEYS. THE EXACT LOCATION OF
EXISTING DUCTWORK, PIPING, AND EQUIPMENT MAY DEVIATE FROM
THE LOCATION INDICATED ON THESE DRAWINGS. THE CONTRACTOR
SHALL BE PREPARED TO MAKE SOME ALTERATIONS TO NEW AND/OR
EXISTING SERVICES TO FIT ACTUAL JOB CONDITIONS.
2.
3" SS
GENERAL PLUMBING NOTES:
1.
DATE: 10/1/2014
ENTRANCE
CORRIDOR
(BELOW)
ENTRANCE
CORRIDOR
100
LINFIELD, HUNTER & JUNIUS, INC.
9:46 PM
TIME:
FD-1
DCW DN
DHW DN
112" DHW
SH-1
1 "
2
4"
4"
1 "
2
DCW
DCW
4"
3
DHW
DCW UP
DHW UP
DHW
BEDROOM #1
107
CORRIDOR
200
LIVING
ROOM/
BEDROOM
217
3
4"
DCW DN
3 " DHW DN
4
1 "
2
DCW DN
1 "
2
1 "
2
BT-1
BATHROOM
209
1 "
2
1 "
2
3
4"
3
4"
3
LAV-1
4"
DCW
2011 by Linfield, Hunter & Junius, Inc.
DCW DN
BEDROOM #4
(ADA)
118
DCW UP
DHW UP
DCW DN
DHW DN
WC-1
1 "
2
DCW DN
DHW DN
1 "
2
DCW
3
DCW UP
1 "
2
1 "
2
DCW UP
DHW UP
4"
3
3
DCW UP
DHW UP
IMB-1
DHW
1 "
2
1 "
2
S-1
4"
BATHROOM
218
BEDROOM
205
DCW
112" DCW
3
WC-1
DHW
114" DHW
PROVIDE NEW
INCOMING DOMESTIC WATER SERVICE. COORDINATE
NEW WATER SERVICE AND METER WITH UTILITY COMPANY.
1 "
2
114" DCW
DCW DN
3 " DHW DN
4
LAV-1
112"
112" DCW
4"
DCW
DCW DN
3
PLAN NOTES:
KITCHEN
119
1 "
2
4"
1 "
2
1 "
2
SH-1
EWH-1
WC-1 LAV-1
3
ALL FINAL CONNECTION SIZES TO EQUIPMENT SHALL BE CONFIRMED
PRIOR TO FABRICATION.
DCW UP
3608 18th Street, Suite 200
Metairie, Louisiana 70002
TMV-1
DCW DN
4"
DCW DN
3 " DHW DN
4
DCW
1 "
2
4"
1 "
2
DCW
1 "
2
DCW DN
3 " DHW DN
4
3
4"
DHW
4"
3
DCW DN
LIVING ROOM /
DINING
102
DHW
1 "
2
3
4"
3
BATHROOM
202
3
DCW
LIVING
ROOM
201
WC-1
SH-1
1 "
2
DCW UP
"
4 DHW UP
4"
LAV-1
4"
DHW
BECAUSE OF THE LIMITED SPACE AVAILABLE TO INSTALL ALL OF THE
MECHANICAL WORK, COORDINATION BETWEEN THE VARIOUS TRADES
IS OF THE UTMOST IMPORTANCE.
3
3
3
IMB-1
STAIRWELL
219
DCW UP
DCW DN
1 "
2
WMB-1
3
4"
3
DHW
4"
DHW
KENT A. POYSER
REG. No. 37788
REGISTERED
DCW DN
DHW DN
1 "
2
1 "
2
DCW DN
1 "
2
S-1
1 "
2
1 "
2
3
DCW UP
DHW UP
4"
4"
DHW
DCW
DCW UP
LAV-1
IMB-1
3
IMB-1
1 "
2
DCW DN
3
1 "
2
1 "
2
DCW DN
DHW DN
4"
DCW DN
"
4 DHW DN
LAUNDRY
ROOM
113
DCW DN
DHW DN
WMB-1
1 "
2
1 "
2
DCW DN
DHW DN
1 "
2
DCW UP
1 "
2
1 "
2
DCW DN
DHW DN
1 "
2
1 "
2
DCW UP
DHW UP
APPROVED BY
1 "
2
BT-2
BATHROOM
(ADA)
111
DHW
4"
CHECKED BY
KITCHEN/
DINING
212
WMB-1
DCW UP
DHW UP
3
4"
4"
PROJ. NO.
12-23
DATE
10/02/2014
SHEET NO.
OF
SHEETS
DRAWN BY
3
1 "
2
1 "
2
3
THIS SHEET
DCW DN
DHW DN
3
DHW
1 "
2
1 "
2
MB-1
1 "
2
S-1
DCW
DCW
DCW DN
DHW DN
4"
1 "
2
1 "
2
1 "
2
DCW DN
1 "
2
3
1 "
2
CORRIDOR
112
DHW
WC-2
BEDROOM #3
115
1 "
2
KITCHEN/
DINING
216
IN
CITY OF KENNER - CONVERSION OF
ANNE WASHINGTON COMMUNITY CENTER
BEDROOM #2
110
DCW
LIVING
ROOM/
BEDROOM
211
DCW UP
DHW UP
1" DHW
1 "
2
1 "
2
1" DCW
FILE: P:\LinfieldHunter&Junius\14-098_CommunityResourceCenter\Design Documents\Drawings\Plumbing\P-301 PLUMBING DOMESTIC WATER.dwg
1 "
2
ALL ELBOWS, FITTINGS, ETC. IN PIPING ARE NOT NECESSARILY
INDICATED TO CLEAR ALL EXISTING AND NEW JOB OBSTRUCTIONS.
4. IF THE PLUMBING CONTRACTOR DOES NOT CLEARLY UNDERSTAND
THESE PLANS, OR IS NOT SURE OF THEIR MEANING, HE SHOULD
OBTAIN THE ENGINEER'S WRITTEN EXPLANATION AND INTERPRETATION,
PRIOR TO SUBMITTING HIS BID, SINCE THE PLUMBING CONTRACTOR
WILL BE HELD RIGIDLY TO THE INTERPRETATION OF THE ENGINEER.
5.
S-1
4"
1 "
2
DCW DN
DHW DN
DCW UP
DHW UP
PROFESSIONAL ENGINEERS, ARCHITECTS
AND SURVEYORS
LINFIELD, HUNTER & JUNIUS, INC.
1 "
2
1 "
2
1 "
2
1 "
2
KITCHEN/
DINING
203
3
THESE PLANS ARE DIAGRAMMATIC IN NATURE SINCE THEY REFLECT
ONLY THE AVAILABLE INFORMATION OBTAINED FROM EXISTING PLANS,
SPECIFICATIONS, AND FIELD SURVEYS. THE EXACT LOCATION OF
EXISTING DUCTWORK, PIPING, AND EQUIPMENT MAY DEVIATE FROM
THE LOCATION INDICATED ON THESE DRAWINGS. THE CONTRACTOR
SHALL BE PREPARED TO MAKE SOME ALTERATIONS TO NEW AND/OR
EXISTING SERVICES TO FIT ACTUAL JOB CONDITIONS.
DCW
3.
ENTRANCE
CORRIDOR
100
1 "
2
2.
112" DCW
9:45 PM
TIME:
GENERAL PLUMBING NOTES:
1.
DATE: 10/1/2014
ENTRANCE
CORRIDOR
(BELOW)
B. IF THE CONTRACTOR ELECTS TO USE EQUIPMENT OTHER THAN THE NAMED BASIS OF DESIGN, ANY ADDITIONAL COSTS ASSOCIATED WITH
ELECTRICAL, GENERAL, AND MECHANICAL MODIFICATIONS REQUIRED SHALL BECOME HIS ULTIMATE RESPONSIBILITY. THIS MUST BE IDENTIFIED
PRIOR TO THE BID SO THAT THERE WILL BE NO ADDITIONAL COSTS TO THE OWNER AFTER THE BID.
B. PROVIDE DIELECTRIC JOINTS OR UNIONS AT DISSIMILAR METALS.
C. INSTALL PIPE ESCUTCHEONS ON EACH PIPE PENETRATION THROUGH FLOORS, WALLS, PARTITIONS, AND CEILINGS WHERE PENETRATIONS ARE
EXPOSED TO VIEW AND ON EXTERIOR OF BUILDING.
C. CONTRACTOR SHALL PAY FOR ALL PERMITS AS WELL AS LICENSE AND INSPECTION FEES REQUIRED FOR HIS WORK.
D. MATERIAL EXPOSED WITHIN PLENUMS SHALL HAVE A FLAME-SPREAD INDEX OF NOT MORE THAN 25 AND A SMOKE-DEVELOPED RATING OF NOT
MORE THAN 50 IN ACCORDANCE WITH SECTION 102 (A), IMC (675 IAC 18-1).
N. INSTALL VALVES WHERE REQUIRED FOR PROPER OPERATION OF PIPING AND ISOLATION OF EACH PIECE OF EQUIPMENT. LOCATE VALVES TO MAKE
THEM ACCESSIBLE AND SO THAT SEPARATE SUPPORT(S) CAN BE PROVIDED WHEN NECESSARY. INSTALL VALVES WITH STEMS ORIENTED UPWARD
WHERE POSSIBLE, BUT NEVER DOWNWARD FROM HORIZONTAL PLANE. WHERE INSULATION IS INDICATED, INSTALL EXTENDED STEM VALVES
ARRANGED IN PROPER MANNER TO RECEIVE INSULATION.
2.2 WASTE AND VENT PIPING AND SPECIALTIES
O. INSTALL INSULATION PRODUCTS ON SPECIFIED PIPING AND EQUIPMENT IN ACCORDANCE WITH MANUFACTURER'S WRITTEN INSTRUCTIONS AND IN
ACCORDANCE WITH RECOGNIZED INDUSTRY PRACTICES TO ENSURE THAT THE INSULATION SERVES ITS INTENDED PURPOSE.
A. WASTE AND VENT PIPING: ALL WASTE AND VENT PIPING SHALL BE PVC. ALL ABOVE GROUND WASTE AND VENT PIPING SHALL BE NO HUB JOINTS
AND ALL BELOW GRADE WASTE AND VENT PIPING SHALL BE PVC.
P. DO NOT CONCEAL ANY WORK UNTIL SYSTEM HAS BEEN TESTED AND INSPECTED. NOTIFY OWNERS REPRESENTATIVE 48 HOURS BEFORE INSPECTION
AND TESTING.
B. INSTALL PIPE ESCUTCHEONS ON EACH PIPE PENETRATION THROUGH FLOORS, WALLS, PARTITIONS, AND CEILINGS WHERE PENETRATIONS ARE
EXPOSED TO VIEW AND ON EXTERIOR OF BUILDING.
1.2 WORK INCLUDED
A. THE CONTRACTOR SHALL FURNISH ALL LABOR, MATERIAL, ACCESSORIES, TOOLS, ETC. TO COMPLETE THE PLUMBING WORK AS INDICATED AND
SPECIFIED.
B. PLUMBING WORK SHALL INCLUDE IN GENERAL TERMS, BUT NOT LIMITED TO THE FOLLOWING:
PROVIDE NEW DOMESTIC WATER, WASTE, AND VENT SYSTEMS TO NEW PLUMBING FIXTURES. OBTAIN EXACT LOCATION OF ALL EQUIPMENT FROM
THE ARCHITECTURAL DRAWINGS.
1.3 SHOP DRAWINGS
A. SUBMIT FIVE (5) COPIES OR ELECTRONIC FORMAT ON ALL EQUIPMENT FURNISHED UNDER THIS CONTRACT.
B. ANY PRODUCT MANUFACTURER LISTED ON THE DRAWINGS OR IN THE PROJECT MANUAL AS A PRE-APPROVED EQUAL MUST BE SUBMITTED TO
ENGINEER FOR APPROVAL NOT LESS THAN SEVEN DAYS PRIOR TO BID DATE.
C. THE CONTRACTOR SHALL SUPPLY THREE COPIES OF OPERATIONS AND MAINTENANCE MANUALS (O&M), AND ONE COPY OF AS-BUILT DRAWINGS
WHEN THE JOB IS COMPLETED. O&M MANUALS SHALL INCLUDE EQUIPMENT CUTS AND WIRING DIAGRAMS.
1.4 CUTTING AND PATCHING
A. THIS CONTRACTOR SHALL CUT AND PATCH ALL HOLES IN THE INTERIOR PARTITIONS AND CEILINGS AS REQUIRED FOR THE INSTALLATION OF HIS
WORK. G.C. SHALL BE RESPONSIBLE FOR CUTTING NEW OPENINGS IN OUTSIDE WALLS, FLOORS, AND FOR PATCHING ALL OPENINGS RESULTED BY
MECHANICAL SCOPE OF WORK, EXCEPT PATCHING FIRE RATED PENETRATIONS. PATCHING SHALL MATCH EXISTING AREAS AND SHALL BE DONE BY
WORKMEN SKILLED IN THE APPROPRIATE TRADE.
B. PROVIDE ASBESTOS FREE SMOKE AND FIRE TIGHT SEALS FOR ANY OPENING THROUGH FIRE RATED WALLS, FLOORS, CHASES OR CEILINGS USED AS
PASSAGE FOR MECHANICAL COMPONENTS SUCH AS PIPING, CONDUIT OR DUCTWORK.
C. INSTALL HANGERS, SUPPORTS, CLAMPS AND ATTACHMENTS TO SUPPORT PIPING PROPERLY FROM BUILDING STRUCTURE; COMPLY WITH MSS SP-69.
ARRANGE FOR GROUPING OF PARALLEL RUNS OF HORIZONTAL PIPING TO BE SUPPORTED TOGETHER ON TRAPEZE HANGERS WHERE POSSIBLE. ALL
PIPING HANGERS AND SUPPORTS SHALL BE UL OR FM APPROVED. CONTRACTOR SHALL USE GALVANIZED OR PAINTED UNISTRUTS FOR PIPING
SUPPORTS. THE USE OF NON-PAINTED BLACK STEEL PIPING SUPPORTS SHALL NOT BE ALLOWED. ALL COPPER PIPING SHALL BE SUPPORTED WITH
COPPER COATED OR ISOLATED HANGERS.
D. ALL SEWER PIPING SHALL BE SUPPORTED NOT LESS THAN 5'-0" APART IN CONFORMANCE TO LOCAL CODE COMPLIANCE.
2.3 PIPE INSULATION
A. INSTALL INSULATION PRODUCTS ON SPECIFIED PIPING IN ACCORDANCE WITH MANUFACTURER'S WRITTEN INSTRUCTIONS, AND IN ACCORDANCE WITH
RECOGNIZED INDUSTRY PRACTICES, TO INSURE THAT THE INSULATION SERVES ITS INTENDED PURPOSE. FOR ALL PIPING INSULATION, A
CONTINUOUS VAPOR RETARDER MUST BE MAINTAINED. THE INSULATION SHALL BE APPLIED WITH A CONTINUOUS, UNBROKEN MOISTURE AND
VAPOR SEAL. ALL INSULATION JOINTS, SEAMS, FITTINGS AND PENETRATION LOCATIONS (I.E. P/T PORTS, VALVE STEMS, HEAT TRACE WIRING, ETC.)
SHALL BE PROPERLY SEALED. IF RIGID INSERTS ARE REQUIRED, BETWEEN PIPE AND INSULATION SHIELDS, THEY SHALL BE OF EQUAL THICKNESS TO
THE ADJACENT INSULATION AND SHALL BE VAPOR SEALED.
B. INSTALL PVC JACKETS OVER ALL EXTERIOR PIPING/INSULATION, INCLUDING OVER THE ELBOWS. PVC JACKETS SHALL BE SECURED AS PER THE
MANUFACTURER'S RECOMMENDATIONS. IF PVC TAPE IS USED, IT SHALL BE APPLIED ACCORDING TO THE MANUFACTURER'S INSTRUCTIONS. ALL
JOINTS SHALL BE SEALED COMPLETELY ALONG THE LONGITUDINAL SEAMS, AND BE INSTALLED SO AS TO SHED WATER. ALL CIRCUMFERENTIAL
JOINTS SHALL BE SEALED BY USE OF PREFORMED BUTT STRIPS, A MINIMUM OF 2" WIDE, OR A MINIMUM 2" OVERLAP, AND SHALL BE COMPLETELY
WEATHER SEALED. RIGID INSERTS/PIPE SUPPORTS SHALL NOT PENETRATE THE PVC JACKET. JACKETS SHALL BE INSTALLED SO THAT ALL RAW
EDGES, ENDS AND SURFACES OF THE INSULATION BELOW ARE PROTECTED.
KENT A. POYSER
REG. No. 37788
C. DOMESTIC COLD AND HOT WATER PIPING INSULATION SHALL BE 3/4" FLEXIBLE ELASTOMERIC INSULATION. ALL EXPOSED WATER PIPING SHALL BE
INSULATED WITH 3/4" FLEXIBLE ELASTOMERIC WITH UV RESISTANT COATING.
REGISTERED
1.5 SLEEVES
D. SANITARY SEWER PIPING SHALL BE INSULATED WITH 3/4" FLEXIBLE ELASTOMERIC OR EQUAL.
A. INSTALL SLEEVES FOR PIPES PASSING THROUGH CONCRETE AND MASONRY WALLS AND CONCRETE FLOOR AND ROOF SLABS. SEAL ALL PIPE
PENETRATIONS USING SLEEVES AND MECHANICAL SLEEVE SEALS. SELECT SLEEVE SIZE TO ALLOW FOR ADEQUATE CLEAR SPACE, BETWEEN SLEEVE
AND PIPE (OR PIPE INSULATION), FOR INSTALLATION OF MECHANICAL SLEEVE SEALS AND FIRE-STOPPING MATERIALS.
2.4 DOMESTIC WATER HEATERS
B. INSTALL STEEL PIPE FOR SLEEVES SMALLER THAN 6 INCHES IN DIAMETER. INSTALL CAST-IRON WALL PIPES FOR SLEEVES 6 INCHES AND LARGER IN
DIAMETER. ALL UNDERGROUND, EXTERIOR-WALL PIPE PENETRATIONS SHALL HAVE CAST-IRON WALL PIPES FOR SLEEVES.
A. FURNISH AND INSTALL WATER HEATERS WITH CAPACITIES AS SHOWN ON PLANS, AS MANUFACTURED BY A.O. SMITH, STATE, OR APPROVED EQUAL.
C. CUT SLEEVES TO LENGTH FOR MOUNTING FLUSH WITH BOTH SURFACES, EXCEPT WHEN INSTALLED IN FLOORS OF MECHANICAL EQUIPMENT AREAS,
OR OTHER WET AREAS, WHERE THE SLEEVES SHALL BE EXTENDED 2 INCHES ABOVE THE FINISHED FLOOR LEVEL. EXTEND CAST-IRON SLEEVE
FITTINGS BELOW FLOOR SLAB AS REQUIRED TO SECURE CLAMPING RINGS.
B. WATER HEATERS SHALL BE LISTED BY UNDERWRITERS LABORATORIES AND MEETS THE THERMAL EFFICIENCY AND STANDBY LOSS REQUIREMENTS OF
THE U.S. DEPARTMENT OF ENERGY AND CURRENT EDITION OF ASHRAE/IESNA 90.1.
IN
B. CAULKING: A SYNTHETIC ELASTOMER THAT IS UL CLASSIFIED FIRE STOP. "HILTI" FIRESTOPPING SHALL BE EXCLUSIVELY USED FOR ALL PENETRATIONS
SEALS.
C. LIMIT THE SIZE OF THE SPACE BETWEEN THE OPENING AND THE OUTSIDE OF THE DUCT OR PIPE TO 1" MAXIMUM.
1.7 COORDINATION OF WORK
A. COORDINATE THE WORK WITH OTHER DISCIPLINES ON THE JOB. CLEARANCES ARE CRITICAL AND THERE SHALL BE COMPLETE COOPERATION
BETWEEN ALL TRADES. THERE WILL BE NO EXTRA COSTS ALLOWED FOR THE INABILITY OF THIS CONTRACTOR TO COORDINATE HIS WORK WITH
CABLE TRAYS AND OTHER EQUIPMENT/SYSTEMS PROVIDED BY OWNER/OTHER CONTRACTORS.
B. ALL WORK SHALL BE DONE DURING NORMAL WORKING HOURS EXCEPT WHEN SPECIFICALLY AUTHORIZED BY THE OWNER OR WHEN IT MAY BENEFIT
THE CONTRACTOR DIRECTLY.
C. THIS CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING AND RELOCATING ANY MINOR INTERFERENCE TO INCLUDE CONDUITS, HANGERS,
ETC. AS THE BASE BID OF THIS PROJECT.
1.8 PLANS AND SPECIFICATIONS
A. THESE SPECIFICATIONS AND PLANS ARE MUTUALLY EXPLANATORY AND ANYTHING DESCRIBED OR SHOWN ON ONE, BUT NOT ON THE OTHER, SHALL
BE CONSIDERED ON BOTH.
B. SHOULD ERROR OR DISCREPANCY APPEAR ON THE PLANS OR SPECIFICATION, IT SHALL BE REFERRED TO THE ENGINEER BEFORE BIDDING.
C. KEEP ONE SET OF PLANS AND SPECIFICATIONS IN GOOD CONDITION ON THE JOB AT ALL TIMES.
1.9 GUARANTEE
A. THE CONTRACTOR SHALL GUARANTEE ALL EQUIPMENT, ACCESSORIES, WORKMANSHIP, AND MATERIAL FURNISHED BY HIM FOR A PERIOD OF ONE
YEAR FROM FINAL ACCEPTANCE AGAINST ALL DEFECTS.
CHECKED BY
A. FURNISH AND INSTALL CAULKING AND SEALANT FOR ALL PIPING PASSING THROUGH ALL PARTITION WALLS WHETHER CONCEALED IN CHASES, ABOVE
CEILINGS OR EXPOSED.
APPROVED BY
1.6 CAULKING AND SEALANT
PROJ. NO.
12-23
DATE
10/02/2014
SHEET NO.
OF
SHEETS
DRAWN BY
FILE: P:\LinfieldHunter&Junius\14-098_CommunityResourceCenter\Design Documents\Drawings\Plumbing\P-401 PLUMBING SPECIFICATIONS.dwg
E. INSTALL HANGERS, SUPPORTS, CLAMPS AND ATTACHMENTS TO SUPPORT PIPING PROPERLY FROM BUILDING STRUCTURE; COMPLY WITH MSS SP-69.
ARRANGE FOR GROUPING OF PARALLEL RUNS OF HORIZONTAL PIPING TO BE SUPPORTED TOGETHER ON TRAPEZE HANGERS WHERE POSSIBLE. ALL
PIPING HANGERS AND SUPPORTS SHALL BE UL OR FM APPROVED. CONTRACTOR SHALL USE GALVANIZED OR PAINTED UNISTRUTS FOR PIPING
SUPPORTS. THE USE OF NON-PAINTED BLACK STEEL PIPING SUPPORTS SHALL NOT BE ALLOWED. ALL COPPER PIPING SHALL BE SUPPORTED WITH
COPPER COATED OR ISOLATED HANGERS.
THIS SHEET
DATE: 10/1/2014
E. DRAWINGS (PLANS, SCHEMATICS, AND DIAGRAMS) INDICATE GENERAL LOCATION AND ARRANGEMENT OF PIPING, DUCTWORK, AND EQUIPMENT. THE
LOCATIONS AND ARRANGEMENT TAKE INTO CONSIDERATION PIPE SIZING AND FRICTION LOSS, EXPANSION, PUMP SIZING, AND OTHER DESIGN
PARAMETERS. CLEARANCES ABOVE CEILINGS IN CERTAIN AREAS ARE LIMITED AND NECESSITATE DUCTWORK AND/OR PIPING ROUTINGS. WHERE
POSSIBLE, PIPING, DUCTWORK, AND EQUIPMENT SHALL BE INSTALLED AS INDICATED. CHANGES REQUIRED TO MEET ARCHITECTURAL AND
STRUCTURAL CONDITIONS ARE TO BE APPROVED BY THE ENGINEER. NEW PIPING, DUCTWORK, ETC. SHALL BE SUPPORTED FROM THE BUILDING
STRUCTURE ONLY, AND NOT FROM ANY NEW OR EXISTING EQUIPMENT, DUCTWORK, ETC.
D. INSTALL BALL VALVES AS SHOWN ON THE DRAWINGS AND AT ALL WATER PIPING TERMINATIONS FOR FIXTURE CONNECTION. VALVES SHALL BE
RATED FOR 150 PSI STEAM WORKING PRESSURE, 600 PSI COLD WORKING PRESSURE, TWO-PIECE FULL PORT CONSTRUCTION, BRONZE BODY,
CHROME PLATED BRASS BALL, REPLACEABLE TEFLON SEALS AND SEATS, BLOW PROOF STEAM, AND VINYL COVERED STEEL HANDLE. VALVES SHALL
BE MANUFACTURED BY CONBRACO, NIBCO OR WATTS.
2011 by Linfield, Hunter & Junius, Inc.
A. DOMESTIC HOT AND COLD WATER: INSTALL TYPE L DRAWN-TEMPER TUBING WITH WROUGHT COPPER FITTINGS AND 95/5 TIN/ANTIMONY SOLDER
JOINTS. ALL DOMESTIC WATER PIPING SHALL BE TESTED TO 125 PSIG FOR TWO (2) HOURS WITHOUT LEAKAGE.
3608 18th Street, Suite 200
Metairie, Louisiana 70002
A. PERTINENT FEDERAL, STATE AND LOCAL REGULATIONS AND REQUIREMENTS OF NATIONAL BOARD OF THE FIRE UNDERWRITERS AND NATIONAL
ELECTRICAL CODE ARE HEREBY MADE PART OF THIS CONTRACT. REQUIREMENTS OF AUTHORITY HAVING LOCAL JURISDICTION SHALL SUPERSEDE
ALL OTHER REQUIREMENTS.
2.1 DOMESTIC WATER PIPING AND SPECIALTIES
CITY OF KENNER - CONVERSION OF
ANNE WASHINGTON COMMUNITY CENTER
9:44 PM
TIME:
1.1 GENERAL
PROFESSIONAL ENGINEERS, ARCHITECTS
AND SURVEYORS
PART 2 PRODUCTS
PART 1 GENERAL
LINFIELD, HUNTER & JUNIUS, INC.
PLUMBING SPECIFICATIONS