Underground Cable RWU-90 XLPE Insulation 1,000 Volts Sequential Metre Markings Rated for CT Use (1/0 and Larger) Sunlight Resistant in Black APPLICATIONS For direct earth burial (with protection as required by inspecting authority). Suitable for service entrance above or below ground. Suitable for exposure to weather when rated "sunlight resistant" and marked "SR." Maximum conductor temperature is 90°C. Minimum recommended installation temperature is -40°C (with suitable handling procedures). CONDUCTORS Stranded conductors: Uncoated, soft copper per ASTM-B3 and ASTM-B8. INSULATION XLPE (cross-linked polyethylene). Printed with True Sequential Markings™. INDUSTRY STANDARDS CSA File No. 251402, Class 5832-03 CSA C22.2, No. 38-05 Canadian Electrical Code® RoHS Compliant SURFACE PRINT Sample (14-10 AWG): CERROWIRE-U 14 AWG (2.08mm2) CSA RWU90 (-40C) 1000V XL SR Sample (8-2 AWG): CERROWIRE-U 8 AWG (8.37mm2) CSA RWU90 (-40C) 1000V XL SR Sample (1AWG-750 MCM): CERROWIRE-U 1 AWG (42.4mm2) CSA RWU90 (-40C) 1000V XL SR *For Colours "SR" is omited. 2012, Cerro Wire LLC All Rights Reserved © REV-02/2013 *It is the sole responsibility of the end user to determine suitability of this product for its intended end use and application. Electrical Distribution Division: 800.523.3869 | FAX 877.877.9563 Consumer Markets Division: 866.572.3776 | FAX 812.793.2626 www.cerrowire.com A Marmon Group/ Berkshire Hathaway Company Underground Cable RWU-90 Cross-Linked Polyethylene (XLPE) Insulated Copper Conductors PRODUCT CODE NUMBER CONDUCTORS AWG SIZE NO. OF STRANDS INSULATION THICKNESS MM. APPROX. O.D. MM ALLOWABLE AMPACITIES* 60°C 75°C APPROX. NET WT. KG/KM 90°C 1202-24xx14 7 1.14 2.79 152015 31 1202-26xx12 7 1.14 4.57 202520 43 1202-28xx10 7 1.14 5.08 304030 63 1202-40xx8 7 1.52 7.11 405055 97 1202-42xx6 7 1.52 8.13 556575 152 1202-44xx4 7 1.52 9.40 708595 229 1202-45xx 3 7 1.52 10.16 85 100 115 286 1202-46xx 2 95 115 130 351 7 1.52 10.92 1202-47xx 1 19 2.03 12.70 110130145 457 1202-50xx 1/0 19 2.03 13.72 125150170 564 1202-52xx 2/0 19 2.03 15.00 145175195 694 1202-54xx 3/0 19 2.03 16.26 165200225 863 1202-56xx 4/0 19 2.03 17.78 195230260 1,070 1202-60xx250 37 2.41 19.81 215255290 1,281 1202-64xx300 37 2.41 21.37 240285320 1,511 1202-68xx350 37 2.41 22.35 260310350 1,761 1202-72xx400 37 2.41 23.37 280335380 1,987 1202-80xx 500 37 2.41 25.65 2,468 1202-84xx600 61 2.79 27.94 355420475 2,977 1202-86xx750 61 2.79 30.48 400475535 3,689 380 430 1658 • xx colour add code is as follows: Black - 01, White - 02, Red - 03, Blue - 04, Green - 05, Orange - 06, Yellow 07, Brown - 08, Gray - 10. * General use according to the CEC.® 2008, Table 2. • Packaging Code (9th Digit) - W=300M Reel, Y=1,500M Reel. All products are available in 300M Reels and 1,500M reels except for 500, 600, and 750 MCM which are available only in 300M reels. REV-02/2013 REV-03/2012 Electrical Electrical Distribution Distribution Division: Division 800.523.3869 | FAX 877.877.9563 Consumer Markets 866.572.3776 | FAX 812.793.2626 800.523.3869 | FAXDivision: 877.877.9563 www.cerrowire.com www.cerrowire.com Marmon Group/ AA Marmon Wire & Cable/ Berkshire Hathaway Company Berkshire Hathaway Company Underground Cable RWU-90 Cross-Linked Polyethylene (XLPE) Insulated Copper Conductors PACKAGE CODE J K L R M P AWG SIZE 500' SPOOL 1,000' REEL 1,500' REEL 2,000' REEL 2,500' REEL 5,000' REEL 14 XX 12 XX 10 XX 8 X X 6 X X 4 X X 3 X X 2 X X 1 X X 1/0 X X 2/0 X X 3/0 X X 4/0 X X 250 MCM X X 350 MCM X X 400 MCM X X 500 MCM X X 600 MCM XX 750 MCM X X REV-02/2013 Electrical Distribution Division: 800.523.3869 | FAX 877.877.9563 Consumer Markets Division: 866.572.3776 | FAX 812.793.2626 www.cerrowire.com A Marmon Group/ Berkshire Hathaway Company