C60H Miniature circuit breakers Ratings 1 to 63A C60HB type B (3 - 5In) Applications Protection and control of circuits against overloads and short circuits. ■ In applications with general load characteristics. ■ Tripping characteristics: BS EN 60898 type B: magnetic setting between 3 and 5 In. ■ Cable capacity: 2 1 - 25A = 25mm . 2 32 - 63A = 35mm . ■ Tightening torque: ≤ 25A = 2.5Nm. 32 - 63A = 3.5Nm. C60HC type C (5 - 10In) Applications Protection and control of circuits against overloads and short circuits. ■ In applications with moderate inrush currents, such as certain lighting systems. ■ Tripping characteristics: BS EN 60898 type C: magnetic setting between 5 and 10 In. ■ Cable capacity: 2 1 - 25A = 25mm . 2 32 - 63A = 35mm . ■ Tightening torque: ≤ 25A = 2.5Nm. 32 - 63A = 3.5Nm. C60HD type D (10 - 14In) Applications Protection and control of circuits against overloads and short circuits. ■ In applications with high inrush currents, such as transformers, motors, certain lighting systems etc. ■ Tripping characteristics: BS EN 60898 type D: magnetic setting between 10 and 14 In. ■ Cable capacity: 2 1 - 25A = 25mm . 2 32 - 63A = 35mm . ■ Tightening torque: ≤ 25A = 2.5Nm. 32 - 63A = 3.5Nm. C60HB miniature circuit breaker Part No’s Ratings (A) 1 2 4 6 10 16 20 25 32 40 50 63 1P C60HB C60HB C60HB C60HB C60HB C60HB C60HB C60HB C60HB C60HB C60HB C60HB 2P 101 102 104 106 110 116 120 125 132 140 150 163 C60HB C60HB C60HB C60HB C60HB C60HB C60HB C60HB C60HB C60HB C60HB C60HB 3P 201 202 204 206 210 216 220 225 232 240 250 263 C60HB C60HB C60HB C60HB C60HB C60HB C60HB C60HB C60HB C60HB C60HB C60HB 4P 301 302 304 306 310 316 320 325 332 340 350 363 C60HB C60HB C60HB C60HB C60HB C60HB C60HB C60HB C60HB C60HB C60HB C60HB 401 402 404 406 410 416 420 425 432 440 450 463 C60HC miniature circuit breaker Part No’s Ratings (A) 1 2 4 6 10 16 20 25 32 40 50 63 1P C60HC C60HC C60HC C60HC C60HC C60HC C60HC C60HC C60HC C60HC C60HC C60HC 2P 101 102 104 106 110 116 120 125 132 140 150 163 C60HC C60HC C60HC C60HC C60HC C60HC C60HC C60HC C60HC C60HC C60HC C60HC 3P 201 202 204 206 210 216 220 225 232 240 250 263 C60HC C60HC C60HC C60HC C60HC C60HC C60HC C60HC C60HC C60HC C60HC C60HC 4P 301 302 304 306 310 316 320 325 332 340 350 363 24872 24873 24875 24876 24877 24878 24879 24880 24881 24882 24883 24884 C60HD miniature circuit breakers Part No’s Ratings (A) 1 2 4 6 10 16 20 25 32 40 50 63 1P C60HD C60HD C60HD C60HD C60HD C60HD C60HD C60HD C60HD C60HD C60HD C60HD 2P 101 102 104 106 110 116 120 125 132 140 150 163 C60HD C60HD C60HD C60HD C60HD C60HD C60HD C60HD C60HD C60HD C60HD C60HD 3P 201 202 204 206 210 216 220 225 232 240 250 263 C60HD C60HD C60HD C60HD C60HD C60HD C60HD C60HD C60HD C60HD C60HD C60HD 4P 301 302 304 306 310 316 320 325 332 340 350 363 25211 25212 25214 25215 25216 25217 25218 25219 25220 25221 25222 25223 43 Vigi C60 Add on residual current device for use with C60 MCB’s only Applications Clipped onto the side of any C60 MCB, add on Vigi’s provide a high level of protection against earth fault in addition to overload and short circuit protection provided by the MCB alone. = + MCB 2P Vigi Effectively creating an RCBO to BS EN 61009, C60 MCB’s with add on Vigi's can be used with any Isobar 4 distribution board pan assemblies as well as a wide range of DIN enclosures. RCBO 1 Vigi modules - 2 pole for assembly with 1 or 2 pole MCB’s Part No. MGV MGV MGV MGV 25 63 63 63 010 030 100 300 2 2 2 2 Ratings (A) 25 63 63 63 Sensitivity (mA) 10 30 100 300 Ratings Sensitivity (A) (mA) MGV 63 030 4 63 30 MGV 63 300 4 63 300 Terminal screw shields available for Vigi RCD’s. See C60 accessories on page 49. Standards Approval: BS EN 61008 (BS EN 61009 when fitted to MCB). Operating voltage: 2 pole = 110/240V, 50/60Hz, 4 pole = 240/415V, 50/60Hz. ■ Cable capacity: 2 pole = 25mm2, 4 pole = 35mm2. Note: Must not be used as the sole means of protection against direct contact with live parts (BS 7671). ■ 44 Dimensions: see page 137. 2 4 1 3 5 7 T Width in 18mm SP ways 4 4 Specification: ■ ■ T Width in 18mm SP ways 2 2 2 2 Vigi modules - 4 pole for assembly with 3 or 4 pole MCB’s Part No. 3 2 4 68