PLC DAY TANK CONTROL PANEL September 2011 PLC Day Tank Control Panel • page 1 of 8 Contents PRIMARY INSPECTION ............................................................... 2 INSTALLATION............................................................................. 2 OPERATION.................................................................................. 2 Automatic Operation ............................................................. 3 Manual Operation ................................................................... 4 DRAWINGS AND PARTS LIST .................................................... 5 APPENDIX A - ABBREVIATIONS USED IN THIS MANUAL....... 6 APPENDIX B - TECHNICAL DATA .............................................. 7 The information herein is the property of Simplex, Inc. and/or its subsidiaries. Without written permission, any copying, transmitting to others, and other use except that for which it is loaned, is prohibited. Simplex, Inc., 5300 Rising Moon Road, Springfield, IL 62711-6228 • 217-483-1600 • Fax 217-483-1616 © 2011 Simplex, Inc. All Rights Reserved. • Printed in the USA. • www.simplexdirect.com PLC Day Tank Control Panel • page 2 of 8 PRIMARY INSPECTION OPERATION Preventative visual inspection of the shipping crate, Remote Pump Unit, and accessories must be performed before installation. Physical or electrical problems due to handling and vibration may occur during shipment. 1. If the packing crate shows signs of damage inspect the controller for damage. Check the entire outside of the controller for damage which could cause internal mechanical or electrical problems. 2. Check main disconnect switch, door and hinge operation. 3. Check all electrical terminals and connections for tightness. The PLC Level Controller nameplate contains the Day Tank operation status indicators and controls. The control panel is the central point for Day Tank operation and is where the Day Tank operating mode is selected. INSTALLATION 1. Properly mount and attach all components as shown in the dimensional drawings using the mounting feet/ holes provided. 2. Connect all components to earth ground at ground studs provided as shown on the electrical drawings. Unit must be grounded for operator safety. 3. If equipped, install level and alarm indication accessories as shown on dimensional drawing and connect them to the Control Panel as shown on the electrical drawings. 4. If equipped, connect dry alarm contacts for customer use per specifications on the electrical drawings. 5. Connect control power to the Control Panel per specifications on the electrical drawings. This manual represents a generic configuration. Please refer to the operator's manual supplied with your equipment. The PLC Day Tank control panel contains the following components: 1. Indicator Lights: a. Power Available b. Summary Alarm 2. Press to Reset Alarm push-button 3. Press to Silence Alarm push-button 4. Fill Pump 1 / Day Tank Auto-OffHand switch 5. HMI Touch-screen Controls and Indicators: a. Fill Pump 1 / Day Tank Filling b. Fill Pump 1 / Day Tank Call For Fuel Runtime c. Day Tank Fuel Level – Percent d. Day Tank Fuel Level – Gallons e. Test Fill push-button f. View Alarms push-button g. Leak Detected Indicator h. Day Tank Fuel Level Indication – Graphically i. Day Tank Fuel Level Indication a. High-High – 98% b. High – 95% c. Full Tank/Fill Stop – 90% d. Fill Start – 50% e. Low – 25% f. Low-Low – 10% Each of these controls and indicators has a specific function and is described in the Automatic and Manual operation sections. Simplex, Inc., 5300 Rising Moon Road, Springfield, IL 62711-6228 • 217-483-1600 • Fax 217-483-1616 © 2011 Simplex, Inc. All Rights Reserved. • Printed in the USA. • www.simplexdirect.com PLC Day Tank Control Panel • page 3 of 8 WARNING!! Always connect the Day Tank and Controller to an earth ground before Day Tank operation! Electrical shock can cause personal injury or death! The programmable logic controller gets the tank level from the Day Tank’s level transducer to energize and de-energize fill pumps as necessary to maintain proper fuel levels within the Day Tank. Day Tank level float-switches work in parallel with the level transducer should a transducer failure occur. As the fuel level rises and falls, the level transducer is continually calibrated based on the float-switch activation points. AUTOMATIC OPERATION The Fill Pump 1/Day Tank Auto-OffHand mode switch is provided to allow the operator complete control over the Day Tank. The 3-position mode switch should be placed in the AUTO mode for automatic, hands-free operation. As the prime mover consumes fuel, the Day Tank will cycle through the normal fuel range as determined by the fuel level transducer. This normal operating range is Fill Start – 50% through Full Tank/Fill Stop – 90%. The control panel HMI will continuously, visually annunciate the fuel level in the Day Tank from both the level transducer and the individual floatswitch indicators. Automatic operation is explained below. The operator selects the AUTO mode via the Fill Pump 1/Day Tank 3-position switch. As fuel is consumed the level drops below the Fill Start-50% level and a fill pump is energized via relay contact closure. As fuel enters the Day Tank, the fuel level rises to the Full Tank/Fill Stop-90% level, at which time the relay contacts open and the fill pump will be de-energized. During a pump running condition, a customer supplied, normally closed, flow switch is WARNING Ground must be connected as shown in the wiring drawing. Failure to properly ground the unit will result in a fire and personnel safety hazard. monitoring fuel progression and should the flow switch not detect sufficient fuel motion for a period of 30 seconds, the relay contacts open and the fill pump is de-energized and considered failed. Once a loss of flow condition is detected, an indicator is illuminated on the HMI touch-screen, an alarm horn will sound, and the fill pump is locked from use until the condition is reset by pressing the Reset Alarm push-button. During normal automatic, operation, fuel is consumed and replenished as necessary and the Day Tank cycles between the 50% and 90% levels. DAY TANK HIGH-HIGH FUEL High-High – 98% fuel level detection is provided as a redundant backup to the High – 95% fuel level. Should the Day Tank fuel level reach a High-High-98%, the pump start contacts will open, the fill pump will stop and no further fill start requests will be generated until the fuel level within the Day Tank is lowered below the High-95% level. Visual indicators will be illuminated on the HMI touch-screen and an alarm horn will sound. Once the fuel level has been lowered, the Reset Alarm push-button must be pressed to resume normal Day Tank operations. DAY TANK HIGH FUEL High – 95% fuel level detection is provided as a redundant backup to the Full Tank/Fill Stop – 90% fuel level, such that, should the Fill Stop fail to engage, the High 95% performs backup functionality to open the pump start relay Simplex, Inc., 5300 Rising Moon Road, Springfield, IL 62711-6228 • 217-483-1600 • Fax 217-483-1616 © 2011 Simplex, Inc. All Rights Reserved. • Printed in the USA. • www.simplexdirect.com PLC Day Tank Control Panel • page 4 of 8 contacts, de-energize the fill pump and halt any further fuel entry into the Day Tank. The Day Tank High fuel alarm indicates the fuel level has reached or exceeded 95%. Should the Day Tank fuel level reach a High-95%, the pump start contacts will open, the fill pump will stop and no further fill start requests will be generated until the fuel level within the Day Tank is lowered below the High-95% level. Visual indicators will be illuminated on the HMI touch-screen and an alarm horn will sound. Once the fuel level has been lowered, the Reset Alarm push-button must be pressed to resume normal Day Tank operations. LOW FUEL LEVEL Should the Day Tank fuel level reach a Low-25%, visual indicators will be illuminated on the HMI touch-screen and an alarm horn will sound. Once the fuel level has been increased above the 25% level, the Reset Alarm push-button must be pressed to resume normal Day Tank operations. LOW-LOW FUEL LEVEL Should the Day Tank fuel drop below the Low-Low – 10% level, the operator should consider generator shutdown to prevent fuel starvation to the generator injectors. Dry contacts are provided as means of automatically stopping generator operations on a Low-Low fuel level detection. Should the Day Tank fuel level reach a Low-Low-10%, visual indicators will be illuminated on the HMI touch-screen and an alarm horn will sound. Once the fuel level has been increased above the 10% level, the Reset Alarm push-button must be pressed to resume normal Day Tank operations. DAY TANK LEAK Should a Day Tank Leak condition occur, this indicates the inner tank has ruptured and allowed fuel detection within the secondary containment. Upon a Day Tank Leak detection, the pump start contacts will open, the fill pump will be de-energized and no further fill start requests will be generated to prevent any further fuel entry into the Day Tank. Should a Day Tank Leak be detected, a visual indicator will be illuminated on the HMI touch-screen and an alarm horn will sound. Once the fuel leak has been resolved and the secondary containment drained, the Reset Alarm push-button must be pressed to resume normal Day Tank operations. MANUAL OPERATION For Manual (continuous run) Day Tank operations, the operator must choose the HAND mode on the Pump 1/Day Tank 3-position mode switch. This will generate a Fill Start request, close the relay contacts, and energize the fill pump to increase the fuel level within the Day Tank. Caution must be used when in the Manual mode and the Day Tank should never be left unattended. Manual mode allows the Day Tank to acquire the High-95% fuel level, at which time the High fuel alarm will be annunciated, the Fill Start contacts will open, and the fill pump will be de-energized. Once the fuel level is brought down to below the High-95% level, the reset alarm push-button must be pressed to resume normal Day Tank operations. By placing the Pump 1/Day Tank 3-position switch back in the AUTO mode, the Day Tank will resume hands-free, automatic operation and maintain fuel levels between the 50% and 90% range. Should general maintenance or repairs be required, the OFF mode is provided. TEST FILL PUSH-BUTTON A Test Fill push-button is provided on the HMI/Touch-screen to confirm Day Tank fill functionality. With the Pump 1 / Day Tank in the Auto mode and the Simplex, Inc., 5300 Rising Moon Road, Springfield, IL 62711-6228 • 217-483-1600 • Fax 217-483-1616 © 2011 Simplex, Inc. All Rights Reserved. • Printed in the USA. • www.simplexdirect.com PLC Day Tank Control Panel • page 5 of 8 fuel level below the Full Tank/Fill Stop – 90% level, the operator may press and release the Test Fill push-button to generate a Fill Start contact closure and energize a fill pump. This will increase the Day Tank fuel level to the Full Tank/ Fill Stop-90% level, at which time the relay contacts open and the fill pump will de-energize. DAY TANK CALIBRATION RESET ALARMS PUSH-BUTTON By pressing the Calibrate Level pushbutton on the HMI/Touch-screen, the operator can accurately set the Day Tank level for the level transducer. The Day Tank Calibration routine requires the operator to enter an upper fuel level setting and a lower fuel level setting. Best results are obtained if the operator can increase the fuel to the Full Tank/Fill Stop – 90% level for the upper setting and then reduce the fuel to the Low-Low – 10% level for the lower setting. Graphical and text-based displays inform the operator at all times of the upper and lower fuel levels. After the calibration process is complete, the operator may return to the main Day Tank status screen. The Reset Alarm push-button is used to reset any alarm condition, should they occur. DRAWINGS AND PARTS LIST ALARM HORN SILENCE PUSHBUTTON Should an alarm condition occur, such as High-High Fuel, High Fuel, Low Fuel, Low-Low Fuel, or Day Tank Leak, the alarm horn will energize. By pressing the alarm horn silence push-button, the alarm horn can be silenced. POWER AVAILABLE LIGHT To confirm control power is present within the Day Tank control panel, the power available light will remain illuminated. SUMMARY ALARM LIGHT A Summary Alarm light is contained on the Day Tank control panel to indicate the presence of an alarm condition, should one occur. This allows the operator to monitor the panel from a distance for any possible alarms. Should an alarm condition exist, the operator can investigate more detailed information on the HMI/Touch-screen contained within the Day Tank control panel. The drawings included in this manual are the most accurate source of part numbers for your Pump Set. When ordering replacement parts for Simplex Pump Sets, always consult the Parts Legend Drawing. When contacting the Simplex Service Department always have your work order and drawing number ready for reference. The Work Order Number and the Drawing Numbers are also located on each drawing legend. Simplex, Inc., 5300 Rising Moon Road, Springfield, IL 62711-6228 • 217-483-1600 • Fax 217-483-1616 © 2011 Simplex, Inc. All Rights Reserved. • Printed in the USA. • www.simplexdirect.com PLC Day Tank Control Panel • page 6 of 8 APPENDIX A - ABBREVIATIONS USED IN THIS MANUAL Listed below are abbreviations of terms found on Fuel Supply Systems. When following a drawing utilize this guide to define abbreviated system and component names. As this is a master list, drawings and text pertaining to your equipment may not contain all these terms. AC-Alternating Current AHR-Alarm Horn Relay AR-Alarm Horn BPRV-Back Pressure Regulating Valve BRK-Motor/Pump Bracket BV-Ball Valve C-Contactor CB-Ciruit Breaker CSR-Check Strainer Relay CV-Check Valve DC-Direct Current DPDT-Double Pole Double Throw F-Fuse FLS-Flowswitch FS-Floatswitch FSR-Simplex Fuel Strainer GA-Gauge GAL-Gallons GPM-Gallons Per Minute HFL-High Fuel Level Relay HG-Mercury HP-Horsepower HZ-Hertz I.D.-Inside Diameter JB-Junction Box Hz-Hertz INHG-Inches of Mercury L-Lamp L.E.D.-Light Emitting Diode LAFD-Los Angeles Fire Department LFF-Loss of FLow Relay LFL-Low Fuel Level Relay LPR-Low Pressure Relay MDB-Main Distribution Block MDS-Main Disconnect Switch MOT-Motor N.C.-Normally Closed NEC-National Electric Code NEMA-National Electric Manufacturers Association NFPA-National Fire Protection Association N.O.-Normally Open NP-Nameplate NPT-National Pipe Thread O.D.-Outside Diameter OLR-Over Load Relay OPT-Option PCB-Printed Circuit Board PCRX-Pump Control Relays PG-Pressure Gauge PLR-Pipe Leak Relay PRV-Pressure Relief Valve PS-Pressure Switch PSI-Pounds Per Square Inch PSR-Pressure Switch Relay PRR-Pump Running Relay SC-Swing Check Valve SOL-Solenoid SST-Simplex Super Tank TB-Terminal Block T-Control Transformer TDR-Time Delay Relay TEFC-Totally Enclosed, Fan Cooled THR-Tank Heater Control Relay TS-Transducer Pressure Switch V-Voltage VAC-Voltage, Alternating Current VDC-Voltage, Direct Current VG-Vacuum Gauge Simplex, Inc., 5300 Rising Moon Road, Springfield, IL 62711-6228 • 217-483-1600 • Fax 217-483-1616 © 2011 Simplex, Inc. All Rights Reserved. • Printed in the USA. • www.simplexdirect.com PLC Day Tank Control Panel • page 7 of 8 APPENDIX B - TECHNICAL DATA Thermal expansion of oil is approximately 1 cubic inch per 1 gallon per 10°F rise in temperature. Hydraulic Formulas Horsepower = Torque (lb. in.) = GPM x PSI 1714 CU IN./REV. x PSI 2 Torque (lb. in.) = HP X 63025 RPM Flow (gpm) = CU IN./REV x RPM 231 Head and Pressure Equivalents Conversion Factors 1HP = 33,000 ft. lbs. per minute 1HP = 42.4 btu per minute 1HP = 0.746 kwhr (kilowatt hours) 1 U.S. gallon= 231 cubic inches Pipe Volume varies as the square of the diameter; volume in gallons = 0.0034 D 2 L where: D=inside diameter of pipe in inches; L=length in inches Velocity in feet per sec.= 0.408 x flow (gpm) D2 where: D=inside diameter of pipe in inches Atmospheric pressure at sea level = 14.7PSI Atmospheric pressure decreases approximately 0.41PSI for each one thousand feet of elevation up to 23,000 feet. When converting pressure from feet of water to P.S.I., the specific gravity of the liquid must be considered. Pressure (PSI) = feet head x 0.433 x specific gravity Here are some typical conversion figures: Specific gravity of oil is approximately 0.85. 1 P.S.I.=2.30 feet of water (specific gravity 1.0) 1 P.S.I.=2.88 feet of oil (specific gravity 0.8) PRESSURE AND CONVERSION TABLE Feet Water PSI Oil PSI Water 1 2 3 4 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 .35 .70 1.05 1.4 1.75 3.5 5.2 7.0 8.7 10.5 12.2 14.0 15.7 17.5 19.2 21.0 22.7 24.5 26.2 28.0 29.7 31.5 .43 .87 1.3 1.73 2.17 4.33 6.5 8.66 10.8 13.0 15.2 17.3 19.5 21.7 23.9 26.0 28.1 30.5 32.5 34.6 36.8 39.0 Simplex, Inc., 5300 Rising Moon Road, Springfield, IL 62711-6228 • 217-483-1600 • Fax 217-483-1616 © 2011 Simplex, Inc. All Rights Reserved. • Printed in the USA. • www.simplexdirect.com PLC Day Tank Control Panel • page 8 of 8 Pipe Friction- Fuel Oil 2 FLAMMABLE LIQUIDS FLASH POINTS Pressure Drop in PSI per 100 feet of Pipe and Tube NOMINAL SIZES - INSIDE DIAMETERS Pipe Size, In. 2.0 GPM 7.0 GPM 10.0 GPM 17.0 GPM 23.0 GPM 30. GPM .50 2.337 24.65 56.10 148.75 233.75 408.00 3.61 7.31 21.25 39.53 64.6 93.5 182.75 .75 40.0 GPM 50.0 GPM Flash Points °F(°C) 1.00 .306 2.00 4.16 11.70 19.55 31.87 54.40 80.75 1.25 .10 .51 1.00 2.55 5.10 8.50 14.88 22.10 .23 .425 1.10 2.04 3.27 5.70 8.33 2.00 .13 .34 .60 .96 3.10 2.38 2.50 .10 1.62 .30 .51 .94 1.275 .10 1.74 3.06 4.93 1.5 3.00 Excerpts from NFPA 325, “Fire Hazards properties of Flammable Liquids...” NOTE: Pipe sizes shown apply to standard weight schedule 40 pipe. Tube is standard copper tubing Specific Gravity and Viscosity of Oils *Specify Gravity At 60°F Oils Auto Lubricating S.A.E.10 Max. 20 Max. 30 Max. 40 50 60 70 10W 20W Fuel OilDiesel No. 2D Diesel No. 3D Diesel No. 4D Diesel No. 5D No. 1 No. 2 No. 3 No. 5A No. 5B No. 6 Navy Spec. Navy II TurbineHeavy Light Viscosities In SSU at Various Temperatures 30°F .880 to .935 .880 to .935 .880 to .935 .880 to .935 .880 to .935 .880 to .935 .880 to .935 .880 to .935 .880 to .935 4,400 6,900 13,000 25,000 58,000 100,000 .82 to .95 .82 to .95 .82 to .95 .82 to .95 .82 to .95 .82 to .95 .82. to .95 .82 to .95 .82 to .95 .82 to .95 .989 Max. 1.0 Max. .91 Avg. .91 Avg. 4,800 770 60°F 80°F 100°F 130°F 170°F 210°F 250°F 1,090 1,650 2,700 4,850 10,000 15,000 22,000 430 750 1,200 2,000 3,700 5,300 7,500 240 400 580 950 1,600 2,300 3,100 120 185 255 380 600 800 1,050 66 90 120 150 220 285 342 57 66 80 105 128 150 49 55 67 76 86 138 390 4,400 16,500 70 145 700 3,500 53.6 92 280 1,500 39 48 70 320 39 44.2 136 76.5 54 104 126 1,480 850 56 68 420 600 72,000 1,100 24,000 45.5 53 215 490 21,500 600 8,600 45.5 65 140 750 35 40 45 125 400 7,800 360 3,500 39 72 315 2,150 190 1,150 48 235 590 100 370 178 225 66 160 141 110 50.2 89 1,280 330 625 208 350 138 170 87 86 58.8 3,300 Diesel Fuel Oil No. 1-D 100 Min. (38) or Legal Diesel Fuel Oil No. 2-D 125 Min. (52) or Legal Diesel Fuel Oil No. 4-D 130 Min. (54) or Legal Fuel Oil No. 1 (Kerosene) (Range Oil) (Coal Oil) 100-162 (43-72) Fuel Oil No.2 126-204 (52-96) Fuel Oil No. 4 142-240 (61-116) Fuel Oil No. 5 Light Fuel Oil No. 5 Heavy 156-336 (69-169) 160-250 (71-121) Fuel Oil No. 6 150-270 (66-132) Jet Fuels Jet A and A-1 110-150 (43-66) Jet Fuels Jet B -10 to +30 (-23 to -1) Jet Fuels JP-4 -10 to +30 (-23 to -1) Jet Fuels JP-5 95-145 (35-63) 57 Simplex, Inc., 5300 Rising Moon Road, Springfield, IL 62711-6228 • 217-483-1600 • Fax 217-483-1616 © 2011 Simplex, Inc. All Rights Reserved. • Printed in the USA. • www.simplexdirect.com