Supervision Module for Battery Backup

advertisement
Supervision Module for Battery Backup
Emerson EnergyMasterTM
Features and benefits
:9Fem[h\eh
8ki_d[iiø9h_j_YWb9edj_dk_jo
The Supervision Module for Batteries (SM BAT) provides detailed
Lower maintenance cost related
to battery backup
information and alarms regarding the condition and status
Higher availability thanks to
automated battery backup test and
detailed information and alarms from
the battery backup
site visits related to the battery backup are based upon this
of the Telecom sites’s battery backup. When maintenance and
information they can be optimized to save both time and money,
especially for sites located remotely.
The SM BAT is an easily installed monitoring device connected to
the integrated control unit (ACU1) of the DC power system, and the
battery backup it supervises. It is designed for measuring cell/block
voltages, battery current, and battery temperature.
The information and alarms, regarding the battery backup on a
specific site, can be monitored or checked by means of a simple
web browser or specific management SW2. No additional software
is needed, and login to monitor the site is password protected.
(Examples of alarms provided by means of the control unit of the
power system are specified in the datasheet and/or manual for the
specific unit.)
1
ACU = Advanced Control Unit
2
ENEC and EXMG are management softwares from Emerson Network Power
Supervision Module for Battery Backup
Emerson EnergyMasterTM
Technical Specifications
General
Power Supply
Power Consumption
Temperature Range
EMC
Safety
Approvals
18 – 60 V DC
5W
0°C to +60°C/32°F to +140°F
EN 300 386:2001 class B, FCC part 15 class B
IEC 60950, EN 60950, UL 60950
CE, UL and NEBS level 3
Mechanical Data
Dimensions (HxWxD)
Standard Installation Methods
Weight
150x300x43 mm/5.9x11.8x1.7 inch
Rack and wall mounted
<2 kg/4.4 lbs
Inputs/Outputs
External Communication
Digital Inputs:
8 Digital Inputs
Analog Inputs:
25 Analog Inputs
1 Analog Input
4 Analog Inputs
RS232
Emerson Network Power
Energy Systems AB
SE-141 82 Stockholm, Sweden
Phone: +46 8 721 60 00
Fax: +46 8 721 71 77
Emerson Network Power
Energy Systems, North America
1122 ”F” Street, Lorain, OH 44052
Phone: 440-246-6999
Fax: 440-246-4876
www.emersonnetworkpower.com/
energysystems/
Alarms/events
0 – 14.5 V <0.5% for cell/block voltages
0 – 75 V <0.5% for total battery voltage
0 – 10 V <0.5%, 0 – 20 mA <0.5%,
0 – 100 mV <1%, 1 uA/K <2% configurable
Digital Outputs:
2 Relay Outputs
:9Fem[h\eh
8ki_d[iiø9h_j_YWb9edj_dk_jo
60 V DC 2 A, 24 V DC 5 A
Emerson Network Power
Co Ltd., China
No. 1 Kefa Rd., Science &
Industry Park
Nanshan District 518057,
Shenzhen, China
Phone: 86-755-860 108 08
www.emersonnetworkpower.com.cn
System Layout
For global contact, visit:
www.emersonenergy.com
Network Management
ENEC
EN/LZT 145 237 RE
Web
Browser
© Emerson Network Power Energy Systems 2006
PSTN, TCP/IP, GSM
;c[hiedD[jmehaFem[h$
J^[]beXWbb[WZ[h_d[dWXb_d]
8ki_d[iiø9h_j_YWb9edj_dk_joJC$
Switching Centre
ACU
SM BAT
SM IO
SM AC
ABBREVIATIONS
PSTN
Public Switched Telephony Network,
a ordinary telephone line
IE
Internet Explorer
ENEC
Emerson Network Energy Center. Oracle based
software for web based monitoring of Emerson
Network Power equipment.
SCU
Standard Control Unit
ACU
Advanced Control Unit
PSU
Power Supply Unit (AC/DC converter/rectifier)
SM AC
Supervision Module for Alternating Current
SM BAT Supervision Module for Battery Backup
SM IO
Supervision Module for generic monitoring
79Fem[h
9edd[Yj_l_jo
:9Fem[h
;cX[ZZ[Z9ecfkj_d]
;cX[ZZ[ZFem[h
Ced_jeh_d]
Ekji_Z[FbWdj
Fem[hFhej[Yj_ed
Fh[Y_i_ed9eeb_d]9edjhebi
HWYai?dj[]hWj[ZIebkj_edi
I[hl_Y[i
Ikh][Fhej[Yj_ed
;c[hiedD[jmehaFem[h$Yec
;c[hiedD[jmehaFem[hWdZj^[;c[hied
D[jmehaFem[hbe]eWh[jhWZ[cWhaiWdZ
i[hl_Y[cWhaie\;c[hied;b[Yjh_Y9e$
ž(&&,;c[hied;b[Yjh_Y9e$
Download