Control Systems for Cooling Tower Fan Motors TR-CS91 Control Systems for Cooling Tower Fan Motors Contents Page Motor control required by electrical codes ............................................................................ 3 Wiring diagrams – symbols and general forms ..................................................................... 4 Control enclosures – NEMA types ........................................................................................ 5 Sizing short-circuit protection ................................................................................................ 6 Disconnect (safety) switch .................................................................................................... 7 Circuit breaker ....................................................................................................................... 8 Combination starter ............................................................................................................... 9 Lightning arrester .................................................................................................................. 9 Manual controller ................................................................................................................... 9 Magnetic controller ................................................................................................................ 9 Across-the-line starters ....................................................................................................... 10 Reduced voltage starters .................................................................................................... 11 Reconnectable starters ....................................................................................................... 14 Special features .................................................................................................................. 15 Control of magnetic starters ................................................................................................ 16 Control for motor heating .................................................................................................... 17 Motor overload protection ................................................................................................... 18 Sizing of motor-overload protection .................................................................................... 18 Soft start motor controller .................................................................................................... 21 Variable frequency drive ..................................................................................................... 21 Programmable controllers ................................................................................................... 22 Purchasing information ....................................................................................................... 23 Wiring diagram of single speed motor with time delay ........................................................ 24 Wiring diagrams of two speed motors with various special features .............................. 25-32 Note: This file was revised in 91. This is not it, it is the original from PageMaker 2. Check over the illustrations carefully to find which Fig was revised. DL 6-26-95. 1 List of Tables Table 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Page Diagram symbols and letters .................................................................................... 4 Motor connections ..................................................................................................... 4 Motor design voltages ............................................................................................... 5 Locked rotor code letters .......................................................................................... 6 Max. rating or setting of motor branch-circuit protective devices .............................. 6 Recommended dual-element fuse sizes ................................................................... 7 Typical circuit breaker sizes ...................................................................................... 7 Typical disconnect switch ratings .............................................................................. 8 Standard fuse sizes .................................................................................................. 8 HP ratings for manual starters .................................................................................. 9 Characteristics and costs of magnetic starters ....................................................... 10 HP ratings for magnetic starters ............................................................................. 11 HP ratings for high voltage controllers .................................................................... 11 Average motor amps & conductors for 200 V & 230 V ........................................... 20 Average motor amps & conductors for 460 V & 575 V ........................................... 20 2 Motor Control Required by Electrical Codes This section describes the various protective devices, controls, and enclosures required for this equipment by most electrical Codes. Refer to the Codes for alternates which are allowable under certain conditions. 1. 2. 3. 4. Use three Running Overcurrent units. Note: Items 1 through 4 are available in a “pump panel” or combination starter. 5. Conductors supplying a single motor must have a carrying capacity not less than 125% of motor full load current. Conductors supplying more than one motor must have a carrying capacity not less than 125% of full load current rating of the highest rated motor plus the sum of the full load current ratings of the rest of the motors. Voltage drop for conductors must not exceed 3% on the branch circuit. Any conductor intended only for grounding purposes must be colored green unless it is bare. Grounded current carrying conductors must be white or natural gray color. All ungrounded conductors of the same color must connect to the same ungrounded feeder conductor. The conductors for systems of different voltages must be different colors. 6. Non-Fused Disconnect Switch — Not required if Item 1 can lock in open position or is within sight from* motor. Motors and control boxes must be grounded. * Item Contained In Required Devices Disconnecting Means — to disconnect motor and controller from the circuit. It must either open all ungrounded conductors and be in sight from* controller or it must lock in the open position. This design must indicate whether switch is open or closed. The disconnect must be a switch rated in horsepower or a circuit breaker of the inverse time or instantaneous trip type. The disconnect, either switch or breaker, for 600 volts or less motor circuits must be ampere rated for at least 115% of full load current. It must also be capable of interrupting stalledrotor current. Motor Feeder — Short-Circuit Protection — to protect the motor-branch-circuit conductors, the motor control apparatus, and the motors against overcurrent due to short circuits or grounds. There must be one in each ungrounded conductor. It must carry motor starting current, but not over 400% of full load current. See Tables 4 and 5 for sizing. Motor Controller — to start and stop the motor. Select the controller for motor basic HP and voltage. See Tables 10, 11, 14 and 15. Overload Protection — to protect the motor, control apparatus and the branch-circuit conductors against excessive heating due to motor overloads, stalled rotor and excessive cycling. Select overloads sized at 125% or less of motor full load current for motors with service factor of at least 1.15. Overload size must not exceed 115% of full load current for all other motors. “in sight from” — must be visible and not more than 50 feet distant. 3 Electrical Supply Fusible Safety Switch or Circuit Breaker Manual or Magnetic Starter Conductors Non-Fused Disconnect Switch In Sight from Motor Motor Wiring Diagrams There are two common types of wiring diagrams. The control equipment supplier provides the standard “Wiring Diagram”, showing the physical layout of components and wiring. These diagrams depict the exact connections required. Each manufacturer uses unique connection points and physical layout, so each drawing applies only to one manufacturer. in the simplest manner with no attempt to show physical layout. This requires separation of the coils from their contacts. A letter designation ties coil “S” and contact “S”. Only “Elementary Diagrams” appear in this manual. All cooling tower motors and control enclosures must be grounded, even though grounding connections do not appear in this manual. The diagram symbols are shown below: “Elementary Diagrams” show the operation of a circuit Table 1 - Diagram Symbols and Letters Temperature Actuated Switch NO* NC* Selector Switch 2 Position 3 Position A1 A2 X X Low High Push Buttons Single Circuit Double Circuit NO NC NO NC A1 X A2 X Hand Off Auto A1 A1 A2 A2 R Contacts Timed Contacts - Contact Action Retarded When Coil is Energized De-Energized NO NC NO NC Instant Operating NO NC Pilot Light Transformer Letter Iron Core Indicates Color Coil Overload Relay Thermal A.C. Motor Single Three Phase Phase *NO - normally open, NC - normally closed - contact position when not energized, pushed, etc. F - Forward LF - Low Forward CR - Control Relay OL - Overload R - Reverse LR - Low Reverse M - Program Timer LOL - Low Overload H - High HF - High Forward TR - Time Relay HOL - High Overload L - Low T1,T2 - Motor Terminal L1,L2 - Line Terminals By far, the largest percentage of cooling tower motors are three phase squirrel cage induction type. Only these motors appear in the diagrams. For reference, the three phase motor winding connections most often used on cooling tower motors appear below. To reverse a three phase motor, change any two of the three leads (L1, L2, and L3). Table 2 - Motor Connections 3 Phase 2 Speed Consequent Pole (1 Winding) Variable Torque 3 Phase Single Speed Dual Voltage “Y” (most common) Connection T3 T6 T9 T1 T4 T7 T4 T8 T5 T2 High Voltage Connection T1 Low Voltage Connection T3 L1 L2 L3 L1 L2 L3 Low Speed Connection T1 T2 T3 T1 T2 T3 L1 L2 L3 T1 T2 T3 T7 T8 T9 T7 T8 T9 T1 T2 T3 T6 T4 T5 T4 T5 T6 T4 T5 T6 T6 T4 T5 L1 L2 L3 4 T2 T5 T6 High Speed Connection Control Enclosures of a rod larger than .250" diameter. Live parts must be at least 4" from the nearest drain hole. The National Electrical Manufacturer’s Association (NEMA) has established standard types of enclosures for control equipment. Types most commonly used with cooling towers are described below. Type 1 Type 3 General Purpose — This enclosure is intended primarily to prevent accidental contact with the control apparatus. It is suitable for general purpose application indoors under normal atmospheric conditions. It serves as protection against dust and indirect, light splashing. It is not dustproof. Type 4 Water-tight — A water-tight enclosure must exclude water. It must pass a hose test. This enclosure is adequate for outdoor use on a cooling tower. It is usually a gasketed 304 stainless steel enclosure. Type 4X is a water-tight corrosion resistant enclosure that will pass a 200-hour salt fog test. Type 7 Hazardous Locations — Class I Air Break — This enclosure meets the application requirements of the National Electrical Code for Class I, Group A, B, C, or D hazardous locations. These locations may contain specific types of flammable gases or vapors. Refer to the Code for more complete definitions of hazardous locations*. Type 7 enclosures are intended for indoor use but are sometimes used outdoors on cooling towers. Type 9 Hazardous Locations — Class II — This enclosure is designed for use in Class II (combustible dust), Group E, F, or G areas. Dust-tight, Rain-tight and Sleet (Ice) Resistant — This enclosure is intended for use outdoors to protect the enclosed equipment against windblown dust and water. It is not sleet (ice) proof. This enclosure must have watertight conduit connections, mounting means external to the equipment cavity, and locking provision. Type 3R Rain-tight — This enclosure is intended for use outdoors to protect the enclosed equipment against rain. It is not dust, snow or sleet (ice) proof. When completely and properly installed, this enclosure prevents entrance of rain above the level of the lowest live part. The 3R enclosure prevents the entrance of a rod .125" in diameter except at drain holes. Drain holes will not permit entry Type 12 Industrial Use — This enclosure is used for industrial applications to prevent entrance of foreign materials such as dust, lint, fibers, oil seepage, or coolant seepage. *The Code defines hazardous locations in Division 1 and Division 2. In general, starters for either location division must be in explosion-proof enclosures. Motors for Division 1 locations must also be explosion-proof. Motors for Division 2 locations can be any enclosure, so long as motor does not employ sliding contacts, centrifugal switches or other types of switching mechanisms, or integral resistance devices. Table 3 - Motor Design Voltages Power System Voltages 120 208 240 480 600 2400 4160 4800 6900 Point of Utilization (Motor Design) Voltage 115 200 230 460 575 2300 4000 4600 6600 5 Disconnect Means and Short Circuit Protection Sizing Short-Circuit Protection A properly sized device serving as both disconnect means and short circuit protection must: (1) Carry normal circuit current continuously (2) Safely switch the circuit under normal or abnormal conditions (3) Prevent overcurrents of a predetermined magnitude for a particular time interval, and (4) Automatically and safely interrupt current of any magnitude that the system can produce. letter and full load current of the motor to properly size the short circuit protection for a given motor. These values appear on the motor name plate. Table 4 lists the locked rotor kilovolt amperes for code letters appearing on motor name plates. Table 5 lists the maximum rating or setting of motor branch circuit protective devices. Actual locked rotor current of a motor might approach 600% of full load current. However, the proper size fuse or circuit breaker will not go out on a normal motor start. Either a circuit breaker or fusible disconnect switch can serve as a disconnect means and short-circuit protection. The designer must know the locked rotor code Table 4 - Locked Rotor Code Letters Code Letter A B C D E F G H J K KVA per HP 0-3.14 3.15-3.54 3.55-3.99 4.0-4.49 4.5-4.99 5.0-5.59 5.6-6.29 6.3-7.09 7.1-7.99 8.0-8.99 Code Letter L M N P R S T U V KVA per HP 9.0-9.99 10.0-11.19 11.2-12.49 12.5-13.99 14.0-15.99 16.0-17.99 18.0-19.99 20.0-22.39 22.4-and up Table 5 - Rating or Setting of Motor Branch-Circuit Protective Devices Type of Motor Nontime Delay Fuse Max. Percent of Full Load Current Dual Element Instantaneous (Time Delay) Trip Fuse Breaker Max. RecomMax. mended All AC single-phase and polyphase squirrel cage and synchronous motors with fullvoltage, resistor or reactor starting: No Code Letter Code Letter F to V Code Letter B to E Code Letter A Where max. rating in table above is not sufficient for starting current of motor the max. rating can be increased to these percent values 300 300 250 150 400% not exceeding 600 amps 175 175 175 175 225% 6 125 125 125 125 Inverse Time Breaker Max. Recommended 700 700 700 700 1300% 250 150-225% 250 150-225% 200 150-200% 150 150% 400% (with full load current less than 100 amps) 300% (with full load current greater than 100 amps) Disconnect (Safety) Switch Disconnect switches are rated by amperage and horsepower. A disconnect switch for a motor load is horsepower rated. It must carry 115% of motor full load current continuously and must be capable of interrupting motor stalled-rotor current. Many fusible switches have three horsepower ratings: standard fuse, dual element fuse, and non-fuse. See Table 8 on Page 8. Manufacturers differ slightly in horsepower rating of their switches. Typical values follow: Table 6 - Recommended Dual Element Fuse Size for Overload and/or Short Circuit Protection of Three Phase Motors with a 1.15 or Larger Service Factor Voltage 200 Volts HP 1/2 3/4 1 1 1/2 2 3 5 7 1/2 10 15 20 25 30 40 50 60 75 100 125 150 200 250 Full Load Amps 2.3 3.2 4.1 6.0 7.8 11.0 17.5 25.3 32.2 48.3 62.1 78.2 92.0 119.6 149.5 177.1 220.8 285.2 358.8 414.0 552.0 Fuse Size Overload Short* & Short Circuit Circuit Protection Protection Only 2.8 4 4 5.6 5 8 7 12 9 15 12 20 20 30 30 45 40 60 60 80 70 100 90 110 110 150 125 175 175 200 200 250 250 300 350 400 400 500 500 600 230 Volts Full Load Amps 2.0 2.8 3.6 5.2 6.8 9.6 15.2 22 22 42 54 68 80 104 130 154 192 248 312 360 480 460 Volts Fuse Size Overload Short* & Short Circuit Circuit Protection Protection Only 2.5 3.5 3.5 5 4.5 6.25 6.25 9 8 12 12 15 17.5 30 25 40 35 50 50 70 60 90 80 110 100 125 125 150 150 200 175 200 200 300 300 350 350 450 405 500 600 Full Load Amps 1.0 1.4 1.8 2.6 3.4 4.8 7.6 11 14 21 27 34 40 52 65 77 96 124 156 180 240 Fuse Size Overload Short* & Short Circuit Circuit Protection Protection Only 1.25 1.8 1.6 2.5 2.25 3.2 3.2 4.5 4 6 5.6 9 9 15 12 20 17.5 25 25 40 30 50 40 50 50 70 60 80 80 110 90 125 110 150 150 175 175 200 200 250 300 350 300 350 * Based on wire size in Tables 14 and 15 for RH, RHW, RVH, THW, THWN, & XHHW wire. Table 7 - Typical Circuit Breaker Available Sizes 15 20 25 30 35 40 45 50 60 70 80 Thermal Magnetic 90 450 100 500 125 600 150 700 175 800 200 900 225 1000 250 1200 300 1400 350 400 Amp Rating 3 7 15 30 50 100 150 7 Instantaneous Trip Trip Amp Range Rating 8-28 225 18-70 400 50-180 600 100-350 800 150-580 300-1100 750-1500 Trip Range 300-2250 500-4000 625-9000 625-9000 500 Table 8 - Typical Disconnect Switch Horsepower Rating 240V - 3 Phase Switch Ampere Rating 30 60 100 200 400 600 Standard Fuse 3 7.5 15 25 50 75 Dual Fuse 7.5 15 30 50 125 200 480V - 3 Phase Non Fuse 7.5 15 30 50 125 Standard Fuse 5 15 25 50 100 150 Dual Fuse 15 30 60 125 250 400 Standard ampere ratings are 30, 60, 100, 200, 400, 600, 800, and 1200 amperes. Disconnect switches are available in NEMA Type 1, 3, 3R, 4, 7, 9 and 12 enclosures. 600V - 3 Phase Non Fuse 20 50 75 125 250 400 Standard Fuse 7.5 15 30 60 125 200 Dual Fuse 20 50 75 150 350 500 Non Fuse 20 60 100 150 350 500 elements. Good practice dictates using dual-element fuses rather than one-time fuses. Dual-element fuses interrupt higher fault currents, generate less heat in the control box, and permit use of smaller fuses for better protection. In addition, if a fuse clip is loose on a one-time fuse, the case can carbonize and fail when the fuse blows. A loose clip on a dual-element fuse will cause the fuse to blow before the case can carbonize. Do not use plug type fuses at voltages greater than 125 volts between conductors except in a grounded neutral system with less than 150 volts from conductors to ground. Therefore, they are inappropriate for most three phase systems. Cartridge type fuses are available with either renewable or non-renewable fuse Table 9 - Standard Fuse Sizes (Amperes) 250 or 600 Volts 1 3 6 10 15 20 25 30 Single Element 35 100 40 110 45 125 50 150 60 175 70 200 80 225 90 250 300 350 400 450 500 600 0.1 0.15 0.2 0.3 0.4 0.5 0.6 0.8 1.0 1.125 1.25 1.4 1.6 1.8 2.0 2.25 Dual Element 2.5 6.25 2.8 7 3.2 8 3.5 9 4.0 10 4.5 12 5.0 15 5.6 17.5 20 25 30 35 40 45 50 60 70 80 90 100 110 125 150 175 200 250 300 350 400 450 500 600 Circuit Breaker Circuit breakers used for motor protection usually have both thermal and magnetic trip elements. The thermal elements protect on overloads where inverse time tripping is desired. The magnetic trip elements instantly operate the breaker in case of dangerous overload or short-circuit faults. Usually circuit breakers do not operate as fast as fuses at high overcurrents, but operate faster on normal overloads. They do not have to be replaced when operated. They also prevent operating the motor single phase. Circuit breakers can also be equipped for remote operation. Low voltage (600 volts and less) circuit breakers are of the air break type. Both oil and air type breakers are available for high voltage systems. Air circuit breakers are rated 15, 20, 30, 40, 50, 60, 70, 90, 100, 125, 150, 175, 200, 225, 250, 300, 350, and 400 amps. They are available in NEMA 1, 3R, 4, 7, 9 and 12 enclosures. Circuit breakers offer certain advantages over fuses. 8 Combination Starter A combination starter includes circuit breakers and disconnect switches as part of the motor controller. equipment. Install arresters on the incoming side as near as practical to the piece of equipment to be protected. Connect one arrester element to each ungrounded lead. Lightning Arrester Usually, to protect a motor, it is necessary to use a secondary class arrester along with a surge-absorbing capacitor. A secondary class arrester is designed for secondary distribution systems such as those supplying motors. Arresters consist of a spark gap and a device to limit or quench the spark. Each manufacturer uses his own method or material to limit the spark. Lightning arresters are usually rated for the maximum phase-to-phase and phase-to-ground voltage. Lightning damage to motors and control equipment is usually caused by high voltage induced in the power line rather than lightning hitting the motor or control directly. Lightning can cause immediate failures or it can weaken insulation, causing failures at a later date. In areas where thunderstorms are frequent, it is advisable to install lightning arresters to protect motors and other Motor Controller Manual Controller Manual Controllers consist of snap-action switch(es) and overload(s). They are available in NEMA 1, 4, 7, 9, and 12 enclosures. Standard sizes appear in Table 10. Manual controllers are available for reversing or twospeed two-winding motor control. Single phase controllers are available with selector switch and pilot light. Table 10 - Horsepower Ratings for Across-the-Line Manual Starters NEMA Size M-0 M-1 M-1P 60 Hz 200 or 230 V 3 7.5 Horsepower at: Three Phase 50 Hz 60 Hz 380 V 480 or 575 V 5 5 15 10 Single Phase 50 or 60 Hz 50 or 60 Hz 115 V 230 V 1 2 2 3 3 5 Magnetic Controller Types of Magnetic Starters The motor controller normally used on cooling towers is a magnetic starter. The standard magnetic starter uses a magnetic coil to close contacts and springs and/or gravity to open them. Some type of pilot device, such as a push button or float switch, actuates the magnetic coil. The main types of magnetic starters are acrossthe-line, reduced voltage, and reconnectable. use of reduced voltage or reconnectable type starters for larger horsepower motors. Reduced starting current and torque, and increased starting time typify reduced voltage and reconnectable type starters. Therefore, the designer must allow sufficient torque to accelerate the load and to keep starting time short enough to avoid overheating the motor. Power company limitations on inrush current dictate the 9 Table 11 - Characteristics and Costs of Common Magnetic Starters Used for Squirrel-Cage Induction Motors Acrossthe-Line Y V IS IS TS C Connection Phase Voltage Starting Current (phase) Starting Current (line) Starting Torque Approx. Cost Comparison Primary AutoPart Resistance Transformers Winding Y Y Y KV* KV V KIS KIS .6 TO .8 iS KIS K2IS .6 TO .8 iS K2TS K2TS .4 TO .48 TX 4.2 4.3 3.0 (2 steps) (closed transition) Star Delta Y .58V .333 IS .333 IS .333 TS 5.2 (closed transition) *“K” is a constant equal to the reduced voltage over the full line voltage. Across-the-Line Starters: Across-the-line starters are the most widely used. The transformer must have enough capacity to allow the motors to be started this way. The motor leads receive full voltage as soon as the pilot device energizes the magnetic coil in an across-the-line starter. Table 12 lists sizes of across-the-line magnetic starters (including reversing) for use with single or multi-speed variable-torque squirrel cage induction motors (nonplugging or non-jogging duty). Standard Single Speed Across the Line Starter with Hand-Off Auto Selector Switch, Push Button (Three-Wire) and Thermostat (Two-Wire) Control B1 STOP START OL F L1 F B2 L2 L3 F F F FUNCTION at 60°F B2 B1 X X Hand M Typical Current and Torque Curves for Design “B” Induction Motor 10 Off Auto Table 12 - Horsepower Ratings for Across-the-Line Magnetic Starters Single Speed and Multi-Speed Variable & Constant Torque Horsepower at: Size of Starter 00 0 1 1P 2 3 4 5 6 7 8 9 Continuous Current Rating Amperes 9 18 27 36 45 90 135 570 540 810 1215 2250 200 V 60 Hz 1.5 3 7.5 — 10 25 40 75 150 — — — Three Phase 230 V 380 V 60 Hz 50 Hz 1.5 1.5 3 5 7.5 10 — — 15 25 30 50 50 75 100 150 200 300 300 — 450 — 800 — Single Phase 460 or 575 V 50 or 60 Hz 50 or 60 Hz 60 Hz 115 V 230 V 2 1/3 1 5 1 2 10 2 3 — 3 5 25 3 7.5 50 100 200 400 600 900 1600 Table 13 - Horsepower Ratings for High Voltage Controllers and Line Contactors Size of Controller & Contactor H2 H3 Continuous Current Ratings Amperes 180 360 Horsepower Rating Induction Motors Three Phase 2200-2400 Volts 4000-4800 Volts 700 1250 1500 2500 Reduced Voltage Starters Primary Resistance Starters: Reduced voltage starters are either primary resistance type or autotransformer type. The pilot device energizes the magnetic coil of a primary resistance starter, connecting the motor to the line through resistors. The resistors normally limit the motor voltage to 65% or 80% of normal voltage. A timer, energized at the same time as the motor, times out and picks up the run contactor which in turn connects the motor directly across the line at a predetermined time interval. This type of starter limits the inrush current, gives smooth motor and load acceleration, and provides a higher starting cycle. Disadvantages of this starter are the physical size of the starter and resistors and the power loss in the resistors. Primary resistance type starters are called “close transition starting units.” 11 2 Wire Control STOP 1 L1 START 2 F L2 OL 3 L3 F TR TR F F F S S S RES RES RES OL S S Motor Typical Wiring Diagram of Primary Resistance Starter Typical Current and Torque Curves with 65% Voltage on First Step for Design “B” Induction Motor Auto-transformer Starters: Auto-transformers reduce the starting voltage in this type of starter. The advantages of this type of starter are: The starter contains several voltage taps. The designer may select the correct reduced voltage for each application. For motors up through 50 HP, 65% and 80% voltage taps are included. For larger horsepower motors, 50%, 65% and 80% voltage taps are included. The transformer ratio reduces the line current for a given torque. Both open-circuit transition and closed-circuit transition auto-transformer starters are available. At a predetermined time, the timer opens the lines to the primary of the auto-transformer, then connects the motor directly across the line. Disadvantages of this type starter are: high cost, low power factor, complete loss of power when the motor is disconnected from the auto-transformer, and high inrush current when the motor is connected across the line. Closed-circuit transition: Three transformers are first connected in wye and the motor is energized through the transformer taps. After a timed interval, the wye connections open, leaving the transformer secondary winding in series with the motor. The motor is then connected directly across the line and the transformers are disconnected. Full voltage induces a lower current peak and complete loss of power does not occur. Open-circuit transition: A timer and the motor are energized simultaneously through the transformer tap. Reconnectable Starters 12 Stop Start 2 Wire Control - Use Dotted Lines and Remove Jumper 3 to 4 3 L1 TR F TR TR 4 TR L2 L3 F S S F S S S F F OL S S OL OL T2 T1 OL T3 Motor Typical Wiring Diagram of Auto-Transformer Starter with Open-Circuit Transition Typical Current and Voltage Curves with 65% Voltage on First Step for Design “B” Induction Motor 2 Wire Control Stop Start L1 L2 TR1 F TR1 S TR1 L3 TR1 S S F F S T T F F OL T T OL OL T2 T1 Motor OL T3 Typical Wiring Diagram of Auto-Transformer Starter with Closed-Circuit Transition Typical Current and Voltage Curves with 65% Voltage on First Step for Design “B” Induction Motor 13 Part-winding Starters: Reconnectable starters can be either part-winding, or star delta type. Part-winding starters require that the motor stator winding must be made up of two or more circuits connected in parallel for normal operation. Standard 230/460 volt motors, 15 horsepower and larger, are generally suitable for part-winding starting at the lower voltage. Check first with the motor manufacturer. half. The locked rotor current on the first step is approximately 60% to 65% of full locked rotor amps. The locked rotor torque is approximately 46% to 49% of full locked rotor torque. Part-winding starting is primarily used to allow the voltage regulator to adjust, preventing excessive line voltage reduction. With this method, a dip appears in the torque curve at half speed. Overloads and fuses for use with part-winding starters should be sized for half the motor full load current and placed in each of the six lines to the motor. In the first step of part-winding starting, half the motor winding and a timer are energized. At a predetermined time interval (usually one second), the second half of the motor winding is connected in parallel with the first Star-delta Starters: The motor must be wired for 2 Wire Control Stop TR Start OL S L1 S L2 TR F L3 Fuse S S S F F F OL OL OL OL OL OL T1 T2 T3 T7 T8 T9 Motor Typical Wiring Diagram of Part-Winding Starting Typical Current and Torque Curves with Part-Winding Starting for Design “B” Induction Motor running delta, with enough leads brought out to connect the motor for a star (or wye) start. In the first step of starting with open transition, the motor is connected wye and the timer energized. At a predetermined time interval, the motor is disconnected and reconnected to the line wired delta. Locked rotor amperage on the star connection is only 33% of the locked rotor amperage on delta connections. However, the voltage fluctuation caused by disconnecting and reconnecting the motor may be objectionable. Star-delta starters are available with closed transition. 14 2 Wire Control 1 L1 Stop Start 3 2 TR S S F L2 TR L3 F F F F T S T S OL T T S OL OL OL T1 T2 T3 T6 T4 T5 Motor Typical Wiring Diagram of Star-Delta Starter with Open-Circuit Transition Typical Current and Torque Curves for Design “B” Induction Motor at the factory. Pilot lights are normally wired in parallel with the coils whose operation they indicate (see wiring diagram on page 24). In the closed transition type, the motor remains connected to the line through resistors during the connection change from star to delta. Control Transformer: Personnel safety sometimes dictates low voltage control circuits. To accomplish this, the control circuit can be wired for connection to a separate power source, or a control circuit transformer can be a part of the starter to provide a 115-volt control circuit voltage. Some control circuit transformers have enough capacity for a 100-watt work lamp. A fuse in the secondary circuit provides short circuit protection for the transformer and control circuit. The wiring diagram on page 30 shows how to wire a control transformer into the controls system. Special Features Single-Speed Motor Starters Auxiliary Contacts: Auxiliary contacts, sometimes called interlocks, are mechanically connected to the starter so that energizing the starter coil opens the contacts (N.C.) or closes the contacts (N.O.). Most starters come with one auxiliary contact. This contact appears in the holding circuit with three-wire control or it can control operation of other equipment with twowire control. Additional contacts (1 to 4, depending on starter) are available factory installed or for field installation. Time Delay Contacts or Relays: Reversing a fan without a time delay imposes a heavy shock load on the drive. Marley recommends a two-minute time delay when reversing so that the fan can slow down to windmilling speed before it actually reverses (see wiring diagram on page 24). Push Buttons or Selector Switch on Cover: Push buttons, pilot lights, or selector switches are available pre-installed on the cover of NEMA Type 1, 4, 7, 9, and 12 starter enclosures. They are wired into the circuits The timing head used by some manufacturers employs 15 the starter coil and does not require a coil of its own (see page 24). Other manufacturers use a timer with its own coil. On page 24, these timer coils must be in parallel with the proper starter coil (forward timer coil in parallel with forward starter coil, etc.). Timers are available with two different types of contact operation: when the motor changes to a lower speed without allowing the motor to adjust to the lower speed. Marley recommends a 20-second time delay before energizing a lower speed winding. Control of Magnetic Starters Instantaneous operation on energization with time delay operation on de-energization. Time delay operation on energization with instantaneous operation on de-energization. Three-Wire (Push Button) Control The controls for magnetic starters are either three-wire or two-wire controls. Three-wire control is manual control. An operator must push a button to start the motor. Additional contacts without time delay are available. On multi-fan towers, it is sometimes desirable to prevent more than one fan starting at the same time. Interlocks in the motor starters and time delay relays can accomplish this goal. However, some means is necessary to permit removing a fan from service for maintenance while the rest of the fans are operating. A sequence alternator can accomplish the same thing if only one fan is required at a time and alternating fans is desirable. Multi-Speed Starters Multi-speed motor magnetic starters are available with the same features listed for single-speed motor starters. The following additional features are also available: Compelling Relay: A compelling relay connected in a multi-speed starter allows the motor to start only at low speed. Any higher speed is available only after a lowspeed start. Pressing any push button except low speed will not start the motor. This arrangement insures that the motor will always first move the load at low speed. The motor can only change from a higher to a lower speed after the stop button is pressed. Accelerating Relays: A multi-speed starter equipped with accelerating relays starts the motor at low speed and automatically accelerates it through successive steps until the motor reaches the selected speed. The operator selects the motor speed by pressing the proper start button. Definite time intervals must elapse between each speed change. Individual timing relays control each interval, and all are adjustable. The motor can only change from a higher to a lower speed after the stop button is pressed. Decelerating Relays: These are similar to accelerating relays except that they prevent immediate reduction from a higher to a lower speed. Both the driven machinery and the motors suffer tremendous strains Starters with three-wire control provide “under voltage protection” for a motor. When the motor stops because of a voltage failure, it will not restart until the start button is pushed. Separate push buttons select each speed and stop. Push buttons serve as momentary contact devices. Once the push button energizes the starter coil, the circuit bypasses the start button. The circuit may include any number of push buttons. Start buttons are in parallel and stop buttons are in series. Standardduty push buttons are available with either normally open or normally closed contacts. Heavy-duty push buttons have both normally open and normally closed contacts. Push buttons are also available with lock-out devices, built-in lights, and different actuators and actuator guards. Indicator lights are available with or without attached transformer. Push buttons are available in NEMA Type 1, 4, 7, 9, and 12 enclosures. Selector switches can serve the same function as push buttons. Since a selector switch is a maintained contact device, only one can be used to energize a starter wired for three-wire control. Any number can be used to de-energize a starter. Hand key or coil operated selector switches are available with two or three contact positions. Two-Wire Control The starter must use three-wire control to provide both manual and automatic starter control. Where only automatic control is required, the magnetic starter is wired for two-wire control. Starters with two-wire control provide “under voltage release”, which disconnects the motor from the line if the voltage gets too low. However, the motor automatically goes back on the line when the voltage comes back up. Limit switches, pressure switches, temperature switches, and relays used with two-wire magnetic starter control offer automatic motor control. 16 Control for Motor Heating Fan motors that will be idle for long periods should have some method of heating. Elevating the motor temperature five or more degrees above ambient prevents condensation in or on the motor. Two commonly used heating methods are electric space heaters and low (5% of normal) voltage single-phase heating using the motor winding. The motor manufacturer normally installs the space heaters and determines the transformer size necessary for single-phase heating. Neither space heaters nor single-phase heating should be energized while the motor is running. Typical wiring diagrams appear below. STOP L1 START OL F F L2 R F L3 F F G F F OL OL OL Motor Space Heater M Typical Wiring Diagram Showing Connections to Space Heater STOP START CR1 L1 F L2 R F L3 F F G CR1 F TR CR1 OL OL OL CR2 F TR CR2 CR2 Heating Transformer CR2 CR2 OL Motor Typical Wiring Diagram Showing Connections for Single Phase Heating The use of single-phase heating is normally limited to low voltage (600 volts or less) squirrel cage induction motors. The wiring diagram shows a time delay relay to prevent connecting the transformer to the motor winding until the motor voltages have collapsed. An available solid state motor winding heater can be connected to a single-speed full voltage motor starter without additional control. 17 Motor Overload Protection The following types of motor overload protection are used: motors can always accelerate the load across-the-line in 13 seconds or less. Refer any questions about fan starting time to The Marley Cooling Tower Company. Sensors Built into the Motor Thermocouples (usually copper-constantan), imbedded in the coils during assembly, provide a signal to read or record temperature or sound an alarm. Resistance temperature detectors imbedded in the coils provide a signal in a circuit to sound an alarm or turn off a motor on high temperature. They are normally used only in form wound motors (large HP). Thermistors, usually with a positive temperature coefficient, can provide a signal to an auxiliary circuit to switch a motor starter off. The thermistors, imbedded in the winding, have a constant resistance until the critical temperature occurs. The resistance value then changes by a factor up to one hundred. Special rate-of-rise temperature switches protect a motor against overloads and stalled rotor conditions. Two or more sensors installed in the end turns sense at least two phases of a three-phase motor and turn off the motor starter. They automatically reset when the temperature drops about 15°C. This type of protector can sense the rapid temperature changes caused by a stalled rotor. Thermostats used in motors are usually bimetallic-disc type attached to the winding end turns. They are available with either normally open or normally closed contacts and reset automatically with about a 10°C temperature drop. They do not normally protect a motor against the rapid temperature increases caused by a stalled rotor. Sensors Built into the Motor Starter Temperature and current sensitive relays in the motor starter open the line to the holding coil of the magnetic starter. A three-phase motor requires three relays, one in each line. A single-phase motor normally requires one relay. Properly sized relays trip at not more than 125% of the full load current for motors with a 1.15 or larger service factor (115% for all other motors). NEMA classifies these overload relays by time current characteristics. The class number indicates the time at which the relay will trip at 600% of the current rating. Class 10 relays trip in 10 seconds and are normally used with hermetically sealed motors and other motors which can endure locked rotor current for only a very short time. Class 20 relays trip in 20 seconds and are normally used on cooling tower motors and other normal motor acceleration applications. Marley fan In a cooling tower, the fan horsepower increases with high air density in the winter and decreases with low air density in the summer. Cooling tower fans are pitched to draw contract horsepower for summer duty. Fan horsepower quite often exceeds the motor name plate horsepower in winter when the air density is high; but this does not hurt the motor. Allowable motor horsepower is limited by motor temperature, which consists of ambient plus the temperature rise due to the power losses in the motor. The temperature rise in winter (due to increased power losses) is more than offset by the drop in ambient temperature. Starter overload capacities vary with ambient (see Page 19). Overloads can best protect a motor in summer and winter, without false tripping of the overloads, if they are always at about the same ambient as the motor. This can be done by installing the starters outside near the motor. Overloads which are compensated to carry the same horsepowers at high or low ambient conditions should not be used with cooling tower fans. Overloads as Part of the Safety Switch Dual element fuses in a fusible safety switch give both short-circuit protection and motor-running overcurrent protection. Where motors are protected by switches described above, dual element fuses should be used to protect the starter and conductors. Sizing of Motor-Overload Protection Motor manufacturers select and install Type A overcurrent devices. The proper size for a Type B device depends on the motor operating horsepower full load current, the starter enclosure, and the temperature of the starter relative to the temperature of the motor. Most overload selection tables apply to motors with a service factor greater than 1.0. The overload heaters for 1.0 service factor motors are normally smaller and their selection appears in a footnote with the table. Overload selection tables are usually attached to the inside of the motor starter enclosure. The proper size for a Type C device depends on the motor operating horsepower full load current. The motor full load current appears on the motor name plate. Currents vary with manufacturer and with motor design (one-speed, two-speed, one-winding, etc.). Nominal current values for 60 Hz, 1800 RPM motors appear in Tables 14 and 15. 18 Variation in Starter Overload Tripping Current with Ambient Temperatures 19 Table 14 - Average Motor Full Load Amps and Minimum Conductor and Conduit Size (1984 N.E.C.) for 60 Cycle Induction Type A.C. Motor Circuits 200 V & 230 V Full Load Amps HP 200 V 230 V 1/2 3/4 1 1 1/2 2 3 5 7 1/2 10 15 20 25 30 40 50 60 75 100 125 150 200 2.3 3.2 4.1 6.0 7.8 11.0 17.5 25.3 32.2 48.3 62.1 78.2 92.0 119.6 149.5 177.1 220.8 285.2 358.8 414 552 2.0 2.8 3.6 5.2 6.8 9.6 15.2 22 28 42 54 68 80 104 130 154 192 248 312 360 480 Wire & Conduit Sizes for Wire & Conduit Sizes for Types RUW, T, TW Wire Types RH, RHW, RUH, THW, THWN, XHHW Wire 200 V 230 V 200 V 230 V Wire Conduit Wire Conduit Wire Conduit Conduit Wire Conduit Conduit AWG or AWG or AWG or RH, RHW, THWN AWG or RH, RHW, THWN MGM MGM MGM RUH, THW XHHW MGM RUH, THW XHHW 14 1/2 14 1/2 14 1/2 1/2 14 1/2 1/2 14 1/2 14 1/2 14 1/2 1/2 14 1/2 1/2 14 1/2 14 1/2 14 1/2 1/2 14 1/2 1/2 14 1/2 14 1/2 14 1/2 1/2 14 1/2 1/2 14 1/2 14 1/2 14 1/2 1/2 14 1/2 1/2 12 1/2 14 1/2 12 1/2 1/2 14 1/2 1/2 10 1/2 10 1/2 10 3/4 * 1/2 10 3/4 * 1/2 8 1/2 8 1/2 8 1 * 1/2 8 1 * 1/2 6 1 6 1 6 1 1/4 * 3/4 8 1 * 1/2 3 1 1/4 4 1 4 1 1/4 * 1 6 1 1/4 * 3/4 2 1 1/4 2 1 1/4 3 1 1/4 1 4 1 1/4 * 1 0 1 1/2 1 1 1/4 2 1 1/4 1 1/4 3 1 1/4 1 00 1 1/2 0 1 1/2 0 2 1 1/4 2 1 1/4 1 1/4 0000 2 000 2 00 2 1 1/2 0 2 * 1 1/4 300 2 1/2 250 2 1/2 0000 2 1/2 * 2 000 2 1 1/2 400 3 300 2 1/2 250 2 1/2 2 0000 2 1/2 * 2 600 3 500 3 400 3 2 1/2 300 2 1/2 2 1/2 900 4 700 3 1/2 600 3 1/2 * 3 500 3 3 2000 1250 4 1/2 900 4 3 1/2 700 3 1/2 * 3 1/2 2000 1250 5 * 4 900 4 3 1/2 Table 15 - Average Motor Full Load Amps and Minimum Conductor and Conduit Size (1984 N.E.C.) for 60 Cycle Induction Type A.C. Motor Circuits 460 V & 575 V Full Load Amps HP 460 V 575 V 1/2 3/4 1 1 1/2 2 3 5 7 1/2 10 15 20 25 30 40 50 60 75 100 125 150 200 1.0 1.4 1.8 2.6 3.4 4.8 7.6 11 14 21 27 34 40 52 65 77 96 124 156 180 240 0.8 1.1 1.4 2.1 2.7 3.9 6.1 9 11 17 22 27 32 41 52 62 77 99 125 144 192 Wire & Conduit Sizes for Wire & Conduit Sizes for Types RUW, T, TW Wire Types RH, RHW, RUH, THW, THWN, XHHW Wire 460 V 575 V 460 V 575 V Wire Conduit Wire Conduit Wire Conduit Conduit Wire Conduit Conduit AWG or AWG or AWG or RH, RHW, THWN AWG or RH, RHW, THWN MGM MGM MGM RUH, THW XHHW MGM RUH, THW XHHW 14 1/2 14 1/2 14 1/2 1/2 14 1/2 1/2 14 1/2 14 1/2 14 1/2 1/2 14 1/2 1/2 14 1/2 14 1/2 14 1/2 1/2 14 1/2 1/2 14 1/2 14 1/2 14 1/2 1/2 14 1/2 1/2 14 1/2 14 1/2 14 1/2 1/2 14 1/2 1/2 14 1/2 14 1/2 14 1/2 1/2 14 1/2 1/2 14 1/2 14 1/2 14 1/2 1/2 14 1/2 1/2 12 1/2 14 1/2 12 1/2 1/2 14 1/2 1/2 10 1/2 12 1/2 10 3/4 * 1/2 12 1/2 1/2 8 1/2 10 1/2 10 3/4 * 1/2 10 3/4 1/2 6 1 8 1/2 8 1 * 1/2 8 1 1/2 6 1 6 1 6 1 1/4 * 3/4 8 1 1/2 4 1 6 1 6 1 1/4 * 3/4 6 1 1/4 3/4 3 1 1/4 4 1 4 1 1/4 * 1 6 1 1/4 3/4 1 1 1/4 3 1 1/4 3 1 1/4 1 4 1 1/4 1 0 1 1/2 2 1 1/4 2 1 1/4 1 1/4 3 1 1/4 1 000 2 0 1 1/2 0 2 * 1 1/4 2 1 1/4 1 1/4 0000 2 000 2 000 2 1 1/2 0 2 1 1/4 300 2 1/2 0000 2 0000 2 1/2 * 2 000 2 1 1/2 400 3 300 2 1/2 300 2 1/2 2 1/2 0000 2 1/2 2 700 3 1/2 500 3 500 3 3 300 2 1/2 2 1/2 20 Soft Start Motor Controller Several manufacturers offer “Soft Start Motor Controllers”. These controllers use silicon controlled rectifiers (SCR’s) to ramp the motor starting voltage (starting at zero and increasing to full voltage over a period of time). The starting time is adjustable from one second up to 24 seconds or more, depending on the manufacturer. The advantage of soft start is the reduced starting torque and shock on the fan drive. An energy saving feature in these controllers reduces the voltage to the motor at partial loads. This reduces the losses in the motor by reducing the magnetic flux density. It also improves the power factor. The cost of these controllers is approximately $30 per horsepower in a NEMA 12 enclosure. A soft start controller is usually installed between the “across-the-line” starter and the motor. Variable Frequency Drive The past few years have seen considerable development of variable frequency controls that permit operating standard, three-phase, squirrel cage induction motors as variable speed motors. These controllers convert one or three-phase a.c. power to d.c., then reconvert it to three-phase variable voltage and frequency power. They try to maintain constant volts per cycle so that the motor torque remains constant at all speeds. Motor cooling becomes less effective at low speeds, so some applications may require reduced load torque at lower speeds. However, this limitation does not apply to fan and pump applications. inverter are less than with a VSI inverter since the power supplied is closer to a sine wave. In addition, the motor losses on a VSI control increase 10% to 20% because the input is a square wave rather than a sine wave source. The temperature rise in a motor varies almost directly with the losses. As an example of these two effects, an 80°C rise 90% efficient motor would have a 96°C rise and be 88% efficient when operating on a square wave. Because of this effect, some motor manufacturers recommend using a high efficiency 1.15 service factor motor with an inverter power source. Diode or SCR bridges convert the a.c. power to d.c. The drive also controls the voltage by adjusting the firing point of the SCR’s. Some users have reported that SCR’s introduce noise back in the line, causing problems with computers. An isolation transformer and/or suppression equipment either at the computer or at the variable frequency drive may be necessary if this occurs. Motor starting time and torque and decelerating time and torque are adjustable with a variable frequency controller. The cost per horsepower of variable frequency controls decreases as the horsepower capacity of the control increases. Cost and performance of variable frequency drives will continue to improve as development continues and the devices gain popularity. Base unit prices do not include a temperature controller, start-up engineer, critical speed lockout, safety disconnect or motor starters to permit alternate operation direct across-the-line. Diode bridges, on the other hand, cannot regenerate power back to the a.c. line (regenerative braking). Manufacturers who use diode bridges instead of SCR’s to convert to d.c. usually guarantee that they will not put noise back to the line. Since the d.c. from a diode bridge is at constant voltage, it is necessary to add an SCR or transistor to the output to control the voltage to some inverters. The designer must consider several other restrictions when specifying a variable frequency controller for a water cooling tower. Splash lubricated gear reduction units require a minimum operating speed for adequate lubrication. This minimum input speed varies with the gear unit design, and is between 440 and 750 RPM on a Marley Geareducer®. The inverter controls must prevent motor operation below the minimum speed. The device that changes d.c. back to variable frequency a.c. is called an inverter. Three basic inverter designs are common: (1) Six steps voltage inverter (VSI). (2) Six steps current inverter (CSI). (3) Pulse width modulating inverter (PWM). This inverter uses constant voltage d.c. Also, some tower components may have a natural frequency within the range of operating speeds of a variable frequency motor drive. If the equipment operates for any significant time at the critical speed, a catastrophic failure could occur. Therefore, the inverter controls must prevent operation at or near a critical frequency. Most variable frequency control manufacturers offer field-installed kits to “lock out” a 4 Hz band around a critical frequency. Most variable frequency drives in the 1 to 200 HP range use voltage source inverters (VSI). Many 1 to 20 HP units are the (PWM) type. The losses at full load in the power source are about 3% for the VSI type and 5% for the PWM type. Motor losses with a PWM 21 Programmable Controllers It has always been possible to reduce the cooling effect on a multi-fan tower by turning off fans or reducing fan speed with a multi-speed motor. Either an operator changed speeds manually or automatic controls with thermostats changed the speed using relays and timers. A thermostat normally controlled each speed change on each motor. The thermostats were all set at different temperatures to prevent changing speed on more than one fan at a time. By adding timers or a multicircuit timer, it was possible to use one thermostat (temperature) to increase speed and another thermostat (temperature) to decrease speed of all fans as required. Programmable controllers are now available to increase or decrease fan speed; wait for the water temperature to stabilize; then change another fan speed. These controls can also prevent motor overheating from excessive cycling. They still require two thermostats, one to increase fan speed and one to decrease fan speed. A dead band between the two temperatures allows operation with no speed change required. Programmable controllers replace only the control of the magnetic motor starters, not the magnetic starters themselves. The cost of a programmable controller depends on the number of inputs and outputs required. An input could be a thermostat or selector switch, for example. Switching a motor speed would be considered an output. For example, 4 two-speed motors would require eight outputs to get eight changes in tower air rate. 22 Purchasing Information (for Control Equipment) The customer should specify the following information when purchasing individual items of control equipment. 6. Timing range desired. 7. Relay type: “Fluid dashpot”, “Pneumatic”, “Motor drive”, or “Electronic”. Magnetic Across-the-Line Starter Push-Button Stations 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. Single or multi-speed. Motor horsepower (each speed). Line voltage. Frequency (cycles). Number of phases. (Number of wires if twophase.) Full load motor current (at each speed if more than one speed). Enclosure type by NEMA type number and size number. Desired control type on cover: start-stop buttons, plain cover, or selector switch marked “Hand”, “Off”, and “Automatic”. On multi-speed motor starters, state if “consequent pole” or “separate winding”. State if motor is “constant torque”, “variable torque”, or “constant horsepower”. On Multi-speed and single-phase motor starters, send terminal diagram of motor. State whether pilot control device is two or three-wire. Three-wire is for push button control. If two-wire, describe pilot device. State voltage if different from line voltage. State if compelling relay, accelerating relay, decelerating relay, or extra interlocks are desired on starter. State if motor will be reversed. If two-speed motor, will motor be reversed one-speed or twospeed. If reverse one-speed, which speed. 1. 2. 3. 4. Number of stations needed. Marking of each button. Enclosure type by NEMA number. State whether contacts are normally-open, normally-closed, or both. Standard-duty buttons have normally-closed or normally-open switches. Heavy-duty buttons are all normallyopen, normally-closed. Safety Switch 1. 2. 3. 4. 5. 6. 7. 8. Motor horsepower and full load current. Line voltage. Number of phases. Enclosure type by NEMA number. State if fuse holders are desired. State if fuses are to be included (extra). State if cover is interlocked. State the position and size of hub or conduit openings, if not standard. Float Switch 1. 2. 3. 4. 5. 6. 7. Timing Relay 1. 2. 3. 4. Whether a.c. or d.c. Line voltage. If a.c., state frequency (cycles). Contact arrangement desired, (i.e., normallyopen or normally-closed). 5. Enclosure type by NEMA number. Voltage. Horsepower rating. Whether a.c. or d.c. If a.c., state phases. Chain or rod operated. Length of chain or rod. Enclosure type by NEMA number. Temperature Switch (Thermostat) 1. 2. 3. 4. 5. 23 Whether a.c. or d.c. Horsepower rating. Desired cut-in & cut-out temperatures. Voltage. If a.c. state phases. Wiring Diagram of Three Phase Magnetic Starter Single Speed Motor with Reversing with Time Delay and Push Button Control Minimum Time Delay Reversing - 2 Minutes STOP R FWD R R OL L1 F CR1 CR1 L2 L3 R R R REV F F F F CR2 G F R CR2 OL T1 T2 T3 Fan Motor Item Starter Push Button Allen Bradley Bulletin 505 Bulletin 800T Cutler Hammer File A50 File E20 General Electric CR 309 Form CR 104P Form 24 Square D Class 8736 Class 9001 Westinghouse Class A-211 Type PB2 Wiring Diagram of Three Phase Non-Reversing Starter Two Speed Consequent Pole Variable Torque Motor with Time Delay on Deceleration and Push Button Control Low A1 Minimum Time Delay High to Low Speed - 20 Seconds H Stop OL H L L1 CR1 L2 A2 CR1 L3 High L L H L L L H LOL H H H H HOL H A1 A2 T1 T2 T3 T6 T4 T5 X X Safe Run Fan Motor Item Starter Push Button Allen Bradley Bulletin 520 Bulletin 800T Cutler Hammer File A700 File E20 General Electric CR 309 Form CR 104P Form Square D Class 8810 Class 9001 Westinghouse Class A-900 Type PB2 L1 L2 L3 L Note: If motor is separate winding type, use same control circuit but change power circuit to that shown at right. L L LOL T1 T2 T3 Fan Motor 25 H H H HOL T11 T12 T13 Wiring Diagram of Three Phase Magnetic Starter Two Speed Consequent Pole Variable Torque Motor with Time Delay on Deceleration, Reversing Low Speed with Time Delay and Push Button Control Minimum Time Delay 1. High to Low Speed - 20 Seconds 2. Reversing - 2 Minutes VIB SW A1 Stop L1 L3 20 Sec HF LF CR3 CR2 CR1 A2 L2 LF CR1 LR 2 Min TR1 LR CR3 CR2 CR1 LF LF LF LR LR LR HF HF HF CR2 HF HF 2 Min LR CR3 CR2 CR1 CR3 LF TR1 HF HF HF T3 T1 T2 T6 T4 T5 OL Fan Motor A1 A2 X Run X Safe L1 L2 L3 LF LF LF LR LR LR HF HF HF Note: T3 T1 T2 T11 T12 If motor is separate winding type, use same control circuit but change power circuit to that shown at left. T13 Fan Motor Item Starter Push Button Selector Switch Allen Bradley Bulletin 520 Bulletin 800T Bulletin 800T Cutler Hammer File A700 File E20 File E20 General Electric CR 309 Form CR 104P Form CR 104P Form 26 Square D Class 8810 Class 9001 Class 9001 Westinghouse Class A-900 Type PB2 Type PB2 Wiring Diagram of Three Phase Magnetic Starter Two Speed Consequent Pole Variable Torque Motor with Time Delay on Deceleration, Reversing Both Speeds and Push Button Control A1 Stop Low H CR1 High L3 F F R R L CR1 A2 F OL H L1 L2 Minimum Time Delay 1. High to Low Speed - 20 Seconds 2. Reversing - 2 Minutes L H R H L L L L H LOL H H H C1 R C2 F F H HOL R H T1 T2 T3 T6 T4 T5 A1 A2 X Run C1 C2 X Safe X Fwd X Rev Fan Motor Item Starter Push Button Selector Switch Allen Bradley Bulletin 520 Bulletin 800T Bulletin 800T Cutler Hammer File A700 File E20 File E20 General Electric CR 309 Form CR 104P Form CR 104P Form Square D Class 8810 Class 9001 Class 9001 Westinghouse Class A-900 Type PB2 Type PB2 L1 L2 Note: If motor is separate winding type, use same control circuit but change power circuit to that shown at right. L3 F L F L F R R R L H H H LOL T1 T2 T3 Fan Motor 27 HOL T11 T12 T13 Wiring Diagram of Three Phase Starter Two Speed Consequent Pole Variable Torque Motor with Time Delay on Deceleration Automatic Temperature and Push Button Control Minimum Time Delay High to Low Speed - 20 Seconds A1 Functions @ 60°F Vib Switch Functions @ 40°F H B1 L1 L A2 L2 L L3 B2 Stop L L L LOL H H H H CR1 Low CR1 H CR1 HOL High L H H H T1 T2 T3 OL T6 T4 T5 Fan Motor A1 A2 X Run B1 B2 X Safe X X Hand Item Allen Bradley Cutler Hammer General Electric Square D Starter Bulletin 520 File A700 CR 309 Form Class 8810 Push Button Bulletin 800T File E20 CR 104P Form Class 9001 Temperature See Minneapolis Honeywell, Penn or Barber Coleman Switch Off Auto Westinghouse Class A-900 Type PB2 L1 L2 Note: If motor is separate winding type, use same control circuit but change power circuit to that shown at right. L3 L L L LOL T1 T2 T3 Fan Motor 28 H H H HOL T11 T12 T13 29 Run X X Safe L3 L2 L1 L3 L2 L1 B1 B2 X Hand Fan Motor T11 T12 LR LR LR LF LF LF HF HF HF T3 T1 T2 Off Auto X C1 C2 T13 T5 For X A2 A1 X Rev VIB SW B2 B1 Stop T1 L H Low LF HF CR2 High CR1 T2 C2 C1 LF Note: T1 Functions at 60°F T2 Functions at 40°F 2 Min TR1 20 Sec TR3 2 Min TR2 Type PB2 Class A-900 Westinghouse OL TR1 TR3 HF CR2 TR2 LR LF CR1 Minimum Time Delay 1. High to Low Speed - 20 Seconds 2. Reversing - 2 Minutes Item Allen Bradley Cutler Hammer General Electric Square D Starter Bulletin 520 File A700 CR 309 Form Class 8810 Push Button Bulletin 800T File E20 CR 104P Form Class 9001 Temperature See Minneapolis Honeywell, Penn or Barber Coleman Switch T6 T4 Fan Motor HF HF T3 T1 T2 LF LF LF LR LR LR HF HF HF Note: If motor is separate winding type, use same control circuit but change power circuit to that shown below. A1 A2 Wiring Diagram of Three Phase Magnetic Starter Two Speed Consequent Pole Variable Torque Motor with Time Delay on Deceleration Reversing Low Speed with Time Delay Automatic Temperature and Push Button Control Wiring Diagram of Three Phase Magnetic Starter Two Speed Consequent Pole Variable Torque Motor with Time Delay on Deceleration Reversing Both Speeds with Time Delay Automatic Temperature and Push Button Control and 120 VAC Control Transformer Minimum Time Delay 1. High to Low Speed - 20 Seconds 2. Reversing - 2 Minutes A1 Vib Switch L1 Functions @ 60°F Functions @ 40°F H B1 L A2 L2 L H L L3 F F F R R B2 Stop R H CR1 Low CR1 CR1 High L L L L LOL H H H H HOL L R C1 C2 H F H H T1 T2 T3 Fan Motor F R OL T6 T4 T5 A1 A2 X Run X Safe B1 B2 X X Hand Off C1 C2 X For Auto Item Allen Bradley Cutler Hammer General Electric Square D Starter Bulletin 520 File A700 CR 309 Form Class 8810 Push Button Bulletin 800T File E20 CR 104P Form Class 9001 Temperature See Minneapolis Honeywell, Penn or Barber Coleman Switch Westinghouse Class A-900 Type PB2 L1 L2 L3 R Note: If motor is separate winding type, use same control circuit but change power circuit to that shown at right. L R L R F F F L H H H LOL T1 T2 T3 Fan Motor 30 X Rev HOL T11 T12 T13 31 L3 L2 L1 Fan Motor T11 T12 T13 T3 T1 T2 HF HF LF LF LF LR LR LR HF HF HF T3 T1 T2 A1 A2 Run X Fan Motor T4 T6 A2 X Safe A1 VIB SW C2 C1 Stop C1 C2 CR2 H L X Hand Auto X TM2 TM1 CR2 LF HF CR1 CR2 CR2 Low HF High 2 Min LR Westinghouse Class A-900 Type PB2 Type PB2 Program Timer CR2 TM LR TR1 CR1 LF HF Square D Class 8810 Class 9001 Class 9001 OL 2 Min TR1 20 Sec HF LF Minimum Time Delay 1. High to Low Speed - 20 Seconds 2. Reversing - 2 Minutes Item Allen Bradley Cutler Hammer General Electric Starter Bulletin 520 File A700 CR 309 Form Push Button Bulletin 800T File E20 CR 104P Form Selector Bulletin 800T File E20 CR 104P Form Switch Program See Zenith or Automatic Timing & Controls Timer T5 LF LF LF LR LR LR HF HF HF Note: If motor is separate winding type, use same control circuit but change power circuit to that shown below. L3 L2 L1 Suggested Automatic Reversing Cycle 1. 40 Minutes Forward 2. 20 Minutes Reverse Wiring Diagram of Three Phase Magnetic Starter Two Speed Consequent Pole Variable Torque Motor with Time Delay on Deceleration Reversing Low Speed with Time Delay, Automatic Temperature and Push Button Control 32 Time X Fwd X Run X X Off X Rev X Safe L3 L2 L1 L3 L2 L1 B1 B2 X Hand Off Auto X T3 T1 T2 Fan Motor T6 T4 Fan Motor T2 T3 T11 T12 T13 LR LR LR LF LF LF HF HF HF T1 HF HF T5 LR LR LR LF LF LF HF HF HF Note: If motor is separate winding type, use same control circuit but change power circuit to that shown below. D1 D2 C1 C2 A1 A2 VIB SW B1 B2 Functions @ 32°F Stop CR2 CR1 D2 D1 L H HF LF CR2 CR1 Functions @ 40°F C2 C1 CR2 High CR1 CR1 CR2 Low LF 2 Min TM2 TR1 Functions 20 Sec @ 60°F HF TM1 OL CR2 CR1 TR1 HF LF TM Westinghouse Class A-900 Type PB2 2 Min LR LR Minimum Time Delay 1. High to Low Speed - 20 Seconds 2. Reversing - 2 Minutes Item Allen Bradley Cutler Hammer General Electric Square D Starter Bulletin 520 File A700 CR 309 Form Class 8810 Push Button Bulletin 800T File E20 CR 104P Form Class 9001 Selector See Minneapolis Honeywell, Penn, or Barber Coleman Switch Program See Zenith or Automatic Timing & Controls Timer A2 A1 Suggested Automatic Reversing Cycle 1. 40 Minutes Forward 2. 20 Minutes Reverse Wiring Diagram of Three Phase Magnetic Starter Two Speed Consequent Pole Variable Torque Motor with Time Delay on Deceleration Reversing Low Speed with Time Delay, Reversing Low Speed with Program Timer Automatic Temperature and Push Button Control Cooling Technologies 7401 W 129 Street • Overland Park, KS 66213 • 913 664 7400 www.marleyct.com • email: info@marleyct.com In the interest of technological progress, all products are subject to design and/or material change without notice. ©2001 Marley Cooling Technologies Printed in USA